VAV DNT 02301-2MH626.pdf

PDF 391 KB Posted

Attached to
Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
Solicitation number
Not on record
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document contains an HVAC air terminal unit and fan coil unit schedule for the first floor of Building 2MH626 at the New Orleans VA Medical Center replacement project.

The schedule lists supply, return, and fan coil units by location with specifications including size, maximum and minimum airflow, control type, and notes. Over 150 supply terminal units, return terminal units, and fan coil units are scheduled across floors D1, D2, D3, E1, E2, F1, F2, and G2. Unit sizes range from 50-2400 CFM and control types include constant volume, variable air volume, and variable coil volume. Notes reference additional drawings for schedule capacities and control sequences. The related federal contract opportunity is an amendment to provide attachments to a solicitation for rebalancing the HVAC system under Solicitation Number Z2DA--CFM issued by the Department of Veterans Affairs Veterans Health Administration VISN 16.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--CFM - Rebalance HVAC System, newest first.
File Type Posted
VAV DNT 02303-2MH628.pdf PDF
P12-AMS CEP 115-7MH608.pdf PDF
S02-XHIBIT B PAST AND PRESENT PERFORMANCE QUESTIONNAIRE v2.pdf PDF
VAV DNT 02305-2MH630.pdf PDF
DNT L05 G.pdf PDF
RESEARCH 4th mech plan.pdf PDF
CEP L03.pdf PDF
P12-000110 Table of Contents 4-7-20.pdf PDF
AMS TLR 03470-6MH604.pdf PDF
ICRA ILSM for CFM - Rebalance HVAC System.xlsx XLSX spreadsheet
013526 Safety Requirements.pdf PDF
VAV DNT 02302-2MH627.pdf PDF
OUT L08.pdf PDF
S02-EXHIBIT A PERFORMANCE RELEVANCY SURVEY v2.pdf PDF
PANAM 104.pdf PDF
03503-6EP103-M3.pdf PDF
OUT L06.pdf PDF
OUT L04.pdf PDF
OUT L03.pdf PDF
S02-EXHIBIT E SURETY FORM.pdf PDF
P15-M-2 DNT Building Existing AHU sequence.pdf PDF
AMS Research 348-8MH609.pdf PDF
P14-M-4 OP Building Existing AHU sequence.pdf PDF
P15-M-5 OP Building Existing DOAS sequence.pdf PDF
OUT L02.pdf PDF
VAV Research 352-8MH613.pdf PDF
RESEARCH 5 dixie penthouse.pdf PDF
INP L03.pdf PDF
DNT L02i F-G.pdf PDF
PANAM 101.pdf PDF
DNT L06 D.pdf PDF
P12-230593 Testing Adjusting and Balancing for HVAC 4-7-20.pdf PDF
DNT L01i F-G.pdf PDF
VAV Research 353-8MH614.pdf PDF
AMS DNT 02288-2MH613.pdf PDF
014219 Reference Standards.pdf PDF
RESEARCH 3rd mech plan.pdf PDF
AMS DNT 02289-2MH614.pdf PDF
PANAM 102.pdf PDF
INP L04.pdf PDF
S05- AMENDMENT- 0001.pdf PDF
S02-EXHIBIT C SUBCONTRACTOR INFORMATION AND CONSENT v2.pdf PDF
CEP L02.pdf PDF
DNT L02i D-E.pdf PDF
AMS IP 01414-1MH604.pdf PDF
P12-VAV PANAM 0252-9MH610.pdf PDF
INP L05.pdf PDF
VAV CON -00MH602.pdf PDF
CEP L01.pdf PDF
382-8EL105-P.pdf PDF
Show all 50

Z2DA--CFM - Rebalance HVAC System has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

2MH626

BLDG 02 HVAC AIR TERMINAL UNIT AND FAN

COIL UNIT SCHEDULE

KJS DCDFebruary 29, 2012

02629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

ARCHITECTURAL ENGINEERING/ PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT

I.S.C. GROUP, INC./ IRRIGATION

DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE

Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

WP_08

CONSTRUCTION DOCUMENTS 1

FULLY SPRINKLERED

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR D1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 02�1D1 D1 925 CFM 925 CFM NO COIL CV DETAIL 2/MH821 NOTE (1)

S�2 02�1D1 G2 1750 CFM 1750 CFM 2.75 CV DETAIL 5/MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE � FIRST FLOOR D1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R�1 02�1D1 D1 925 CFM 925 CFM � S�1 NOTE (1)

R�2 02�1D1 E1 1000 CFM 650 CFM � � NOTE (1)

R�3 02�1D1 G2 1875 CFM 1050 CFM � S�7,S�8,S�10 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE � FIRST FLOOR D2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

INTERLOCK WITH

BOX Remarks

R�1 02�1D2 A1 250 CFM 125 CFM � S�2 NOTE (1)

R�2 02�1D2 D2 900 CFM 900 CFM � S�6,S�14 NOTE (1)

R�3 02�1D2 B2 350 CFM 175 CFM � S�3 NOTE (1)

R�4 02�1D2 E2 1250 CFM 725 CFM � S�7,S�8,S�10 NOTE (1)

R�5 02�1D2 C3 450 CFM 225 CFM � S�19 NOTE (1)

R�6 02�1D2 D3 825 CFM 425 CFM � S�4,S�9,S�11 NOTE (1)

R�7 02�1D2 E3 1150 CFM 575 CFM � S�26,S�27 NOTE (1)

R�8 02�1D2 D3 675 CFM 350 CFM � S�15,S�16 NOTE (1)

R�9 02�1D2 E3 1015 CFM 525 CFM � S�22,S�23 NOTE (1)

R�10 02�1D2 C3 500 CFM 250 CFM � S�21,S�24 NOTE (1)

R�11 02�1D2 E2 1125 CFM 600 CFM � S�17,S�28 NOTE (1)

R�12 02�1D2 A3 225 CFM 125 CFM � S�31 NOTE (1)

R�13 02�1D2 E3 1050 CFM 350 CFM � S�32,S�33 NOTE (1)

R�14 02�1D2 E2 1350 CFM 675 CFM � S�18,S�20 NOTE (1)

R�15 02�1D2 A3 200 CFM 200 CFM � S�30 NOTE (1)

R�17 02�1D2 A2 125 CFM 125 CFM � S�35 NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR D2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 02�1D2 D1 800 CFM 800 CFM 1.5 CV DETAIL 2/MH821 NOTE (1)

S�2 02�1D2 A1 250 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�3 02�1D2 B2 350 CFM 175 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�4 02�1D2 A3 125 CFM 75 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�5 02�1D2 A3 100 CFM 50 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�6 02�1D2 E2 1125 CFM 1125 CFM 2.0 CV DETAIL 2/MH821 NOTE (1)

S�7 02�1D2 E2 1000 CFM 500 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S�8 02�1D2 E2 1050 CFM 575 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S�9 02�1D2 B3 375 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�10 02�1D2 D2 750 CFM 375 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S�11 02�1D2 B3 325 CFM 175 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�12 02�1D2 D1 700 CFM 700 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)

S�13 02�1D2 C1 650 CFM 650 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)

S�14 02�1D2 D2 875 CFM 875 CFM 1.5 CV DETAIL 2/MH821 NOTE (1)

S�15 02�1D2 A3 125 CFM 75 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�16 02�1D2 C3 550 CFM 275 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S�17 02�1D2 E2 1050 CFM 525 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S�18 02�1D2 D2 900 CFM 450 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S�19 02�1D2 C3 475 CFM 225 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�20 02�1D2 C2 450 CFM 225 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�21 02�1D2 A3 200 CFM 100 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�22 02�1D2 B3 325 CFM 175 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�23 02�1D2 D2 690 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S�24 02�1D2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�25 02�1D2 D2 700 CFM 700 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)

S�26 02�1D2 C3 600 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�27 02�1D2 C3 550 CFM 275 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�28 02�1D2 A2 200 CFM 200 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)

S�29 02�1D2 C3 600 CFM 600 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)

S�30 02�1D2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�31 02�1D2 B3 325 CFM 325 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)

S�32 02�1D2 B2 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�33 02�1D2 D3 750 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�34 02�1D2 B1 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�35 02�1D2 E1 1025 CFM 1025 CFM 1.75 CV DETAIL 2/MH821 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FIRST FLOOR D1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC�1 1D�C01 02�1D1 F � � NOTE (2)(3)

FCU�1 02�1D1 2F4 � DETAIL 1/MH820 NOTE (2)

FCU�2 STD�01 02�1D1 4B3 � DETAIL 2/MH820 NOTE (2)

RETURN TERMINAL UNIT SCHEDULE � FIRST FLOOR E2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

INTERLOCK WITH

BOX Remarks

R�1 02�1E2 D2 850 CFM 425 CFM � S�1,S�6 NOTE (1)

R�2 02�1E2 A3 250 CFM 125 CFM � S�10 NOTE (1)

R�3 02�1E2 B3 400 CFM 200 CFM � S�5 NOTE (1)

R�5 02�1E2 B3 325 CFM 175 CFM � S�6 NOTE (1)

R�6 02�1E2 F2 1575 CFM 700 CFM � S�2,S�3,S�7 NOTE (1)

R�7 02�1E2 C1 575 CFM 275 CFM � S�4 NOTE (1)

R�8 02�1E2 C3 550 CFM 275 CFM � S�8,S�9 NOTE (1)

R�9 02�1E2 G2 1875 CFM 950 CFM � S�13 NOTE (1)

R�10 02�1E2 B3 300 CFM 150 CFM � S�18 NOTE (1)

R�11 02�1E2 G2 1700 CFM 850 CFM � S�16 NOTE (1)

R�12 02�1E2 E2 1150 CFM 575 CFM � S�14 NOTE (1)

R�13 02�1E2 E2 1300 CFM 650 CFM � S�17 NOTE (1)

R�14 02�1E2 B2 275 CFM 275 CFM � S�19,S�20 NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR E1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 02�1E1 B2 400 CFM 400 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)

S�2 02�1E1 D2 750 CFM 750 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)

S�3 02�1E1 D1 925 CFM 925 CFM NO COIL CV DETAIL 2/MH821 NOTE (1)

S�4 02�1E1 C2 450 CFM 450 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)

S�5 02�1E1 C2 600 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�6 02�1E1 A2 250 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR E2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 02�1E2 A3 100 CFM 50 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�2 02�1E2 D2 675 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S�3 02�1E2 D2 900 CFM 450 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S�4 02�1E2 C1 675 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S�5 02�1E2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�6 02�1E2 B3 325 CFM 175 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�7 02�1E2 A2 100 CFM 100 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)

S�8 02�1E2 A3 100 CFM 50 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�9 02�1E2 C2 450 CFM 225 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�10 02�1E2 A3 250 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�11 02�1E2 D2 900 CFM 900 CFM 1.5 VCV DETAIL 4/MH821 NOTE (1)

S�12 02�1E2 D2 675 CFM 675 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)

S�13 02�1E2 G2 1875 CFM 950 CFM 1.75 CV DETAIL 2/MH821 NOTE (1)

S�14 02�1E2 E2 1150 CFM 575 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S�15 02�1E2 A2 100 CFM 50 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�16 02�1E2 G2 1800 CFM 900 CFM 1.5 VCV DETAIL 4/MH821 NOTE (1)

S�17 02�1E2 E2 1300 CFM 650 CFM 1.25 VCV DETAIL 4/MH821 NOTE (1)

S�18 02�1E2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�19 02�1E2 B2 375 CFM 375 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)

S�20 02�1E2 C2 600 CFM 600 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FIRST FLOOR E1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC�1 02�1E1 F � � NOTE (2)(3)

FCU�1 02�1E1 2F4 � DETAIL 1/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR F1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 02�1F1 D1 925 CFM 925 CFM NO COIL CV DETAIL 2/MH821 NOTE (1)

S�2 1F100 02�1F1 G2 1775 CFM 1775 CFM 3 CV DETAIL 2/MH821 NOTE (1)

S�3 02�1F1 E2 1010 CFM 1010 CFM 1.75 CV DETAIL 2/MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE � FIRST FLOOR F2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R�1 02�1F2 C3 1125 CFM 625 CFM � S�23,S�24 NOTE (1)

R�2 02�1F2 C3 550 CFM 450 CFM � S�26,S�28 NOTE (1)

R�3 02�1F2 B1 400 CFM 200 CFM � S� NOTE (1)

R�4 02�1F2 E3 975 CFM 500 CFM � S�32,S�33,S�34,S�35 NOTE (1)

R�5 02�1F2 D2 750 CFM 750 CFM � S�25 NOTE (1)

R�6 02�1F2 B2 300 CFM 150 CFM � S�31 NOTE (1)

R�7 02�1F2 F2 1650 CFM 1650 CFM � S�16,S�21 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE � FIRST FLOOR F1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R�1 02�1F1 D1 925 CFM 925 CFM � S�1 NOTE (1)

R�2 02�1F1 E2 975 CFM 450 CFM � S�1,S�2 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FIRST FLOOR F1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC�1 02�1F1 E � � NOTE (2)(3)

FCU�1 02�1F1 2F4 � DETAIL 1/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR F2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 02�1F2 E2 1075 CFM 550 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S�2 02�1F2 A1 250 CFM 250 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)

S�3 02�1F2 F2 1440 CFM 720 CFM 1.25 VCV DETAIL 4/MH821 NOTE (1)(4)

S�4 02�1F2 E2 990 CFM 500 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S�5 02�1F2 G2 1920 CFM 960 CFM 1.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S�6 02�1F2 G2 1920 CFM 960 CFM 1.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S�7 02�1F2 F2 1440 CFM 720 CFM 1.25 VCV DETAIL 4/MH821 NOTE (1)(4)

S�8 02�1F2 F2 1440 CFM 720 CFM 1.25 VCV DETAIL 4/MH821 NOTE (1)(4)

S�9 1F101C 02�1F2 E2 1160 CFM 575 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S�10 1F101C 02�1F2 E2 1160 CFM 575 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S�11 02�1F2 G2 1920 CFM 960 CFM 1.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S�12 02�1F2 G2 1920 CFM 960 CFM 1.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S�13 02�1F2 G2 1920 CFM 960 CFM 1.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S�14 02�1F2 G2 1920 CFM 960 CFM 1.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S�15 02�1F2 F2 1440 CFM 720 CFM 1.25 VCV DETAIL 4/MH821 NOTE (1)(4)

S�16 02�1F2 D2 750 CFM 750 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)

S�17 02�1F2 H1 2400 CFM 1200 CFM 2.0 VCV DETAIL 4/MH821 NOTE (1)(4)

S�18 02�1F2 E1 1000 CFM 450 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S�19 02�1F2 C1 650 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�20 02�1F2 H1 2400 CFM 1200 CFM 2.0 VCV DETAIL 4/MH821 NOTE (1)(4)

S�21 02�1F2 E2 1000 CFM 1000 CFM 1.75 CV DETAIL 2/MH821 NOTE (1)

S�22 02�1F2 G1 1800 CFM 900 CFM 1.5 VCV DETAIL 4/MH821 NOTE (1)

S�23 02�1F2 C2 625 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S�24 02�1F2 C3 600 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�25 02�1F2 E2 1375 CFM 1375 CFM 2.25 CV DETAIL 2/MH821 NOTE (1)

S�26 02�1F2 A1 200 CFM 100 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�27 02�1F2 C1 450 CFM 225 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�28 02�1F2 B3 350 CFM 350 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)

S�29 02�1F2 C3 450 CFM 450 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)

S�30 02�1F2 B1 400 CFM 400 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)

S�31 02�1F2 B2 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�32 02�1F2 B1 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�33 02�1F2 B2 800 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�34 02�1F2 B3 375 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S�35 02�1F2 B2 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FIRST FLOOR F2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU�1 02�1F2 4C1 � DETAIL 2/MH820 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FIRST FLOOR D2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU�1 STD�05 02�1D2 4B1 � DETAIL 2/MH820 NOTE (2)

FCU�2 02�1D2 4D7 � DETAIL 2/MH820 NOTE (2)(3)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FIRST FLOOR D3

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU�1 02�1D3 4J2 � DETAIL 2/MH820 NOTE (2)

FCU�2 02�1D3 4J2 � DETAIL 2/MH820 NOTE (2)

FCU�3 1D201 02�1D3 4J2 � DETAIL 1/MH820 NOTE (2)

GENERAL NOTES:

1. REFER TO DRAWINGS MH603 AND

MH604 FOR SCHEDULE CAPACITES

2. REFER TO DRAWINGS MH607 AND

MH608 FOR SCHEDULE CAPACITIES

3. REQUIRES EMERGENCY POWER

4. INTERLOCK WITH KITCHEN HOOD VAV

EXHAUST PER DRAWING 2MH802.

FAN EF� 31: S�1,S�6,S�7,S�8,S�13

FAN EF� 30: S�5,S�11,S�12,S�14,S�15

FAN EF� 19: S�17,S�20,S�22

RETURN TERMINAL UNIT SCHEDULE � FIRST FLOOR E1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R�1 02�1E1 D1 925 CFM 925 CFM � S�3 NOTE (1)

REFER TO SKETCH:

SK-8-1-NJ-2-MH-626-1

REFER TO SKETCH:

SK-8-1-NJ-2-MH-626-2