Technical Exhibit 2-14_Warm Air Furnace_Semi Annually.pdf
PDF 179 KB Posted
- Solicitation number
- W91QVN24R0007
About this file
This document is a technical exhibit for the semi-annual maintenance and inspection of warm air furnaces (oil) at the US Army Garrison Humphreys. The exhibit provides a detailed checklist of 17 steps that a technician must perform, including inspecting and cleaning the firebox and flue piping, checking fan and limit controls, inspecting the fuel system, cleaning the area, changing filters, checking for vibration and noise, lubricating moving parts, and checking electrical wiring.
The related federal contract opportunity is for Inspection, Testing and Maintenance (ITM) of Mechanical Equipment at USAG Humphreys. The solicitation number is W91QVN24R0007, and the response date for proposal submission is May 24, 2024 at 13:00 hrs Korean Time. The contract will be awarded by the Department of the Army Materiel Command Army Contracting Command.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technician :
MFR :
Step# CHK
Remark 기타
Warm Air Furnaces(Oil)
Inspect & clean firebox & flue piping; repair or replace as necessary, reseal smoke pipe as required.
화실 및 연통 점검 및 청소, 필요한 경우 교체 및 봉합
Check condition of flue pipe, damper & stack; repair or replace as necessary.
연통, 댐퍼, 스택 상태 점검 ; 필요의 경우 정비 및 교체
Check fan & fan limit controls for operation; repair or replace as necessary.
팬과 팬 리밋 컨트롤 작동 점검 ; 필요의 경우 정비 및 교체
Check furnace operation through complete cycle.
셋팅 온도까지 장비 운행의 이상 유무
Check with operating personnel or area personnel for deficiencies.
인원 및 운행 결함 확인
Inspect, clean & adjust electrodes & nozzles; replace nozzles as necessary.
전극봉 및 노즐 점검 및 조정 ; 필요한 경우 노즐 교체
Inspect fuel system for leaks; report all leaks promptly to COR.
연료 시스템 누유 점검; COR에게 즉각 보고
Check room thermostat is properly conmunicated with furnance and is programmed w/proper settings for energy saving; replace battery as necessary.
기계실 온도조절기 운행 및 절전 유무 점검; 필요의 경우 배터리 교체
Check furnace combustion w/calibrated analyzer.
연비 측정기로 연소테스트
Clean area around furnace.
장비주변 청소
Change fuel filter & fuel strainer elements.
연료필터 및 연료 스트레이너 부품 교체
Check for operation of burner primary controls, check & adjust thermostat.
버너 컨트롤 작동 및 온도 조절기 점검
Replace air filters at least once a month for heating season.
난방시즌 최소 월 1회 공기필터 교체
Check blower & fan motor for vibration & noise; repair or replace as necessary.
블로워 및 팬모터의 진동 및 소음 점검; 필요시 수리 및 교체
Clean fan motor & blower, lubricate bearings and all moving parts.
팬모터 및 블로워 청소, 베어링등 모든 운동부품 윤활작업
Check electrical wiring to burner controls & blower.
버너 컨트롤 및 블로워의 전선 점검
Bldg No. : Date :
Job Plan Title Annual (or more)
Task
Check belts for wear & tension, tighten or replace.
벨트상태 및 장력 점검; 조임 혹은 교체
CAPACITY : MODEL :
WAF(O)
File details come from the government source that posted it. Updated .