The provided document is a Technical Exhibit titled "Boiler Monthly" that details the monthly inspection and maintenance tasks for a hot water boiler system. The key tasks include testing safety interlocks, inspecting fuel lines and connections, performing visual opacity checks, checking operation of control switches and valves, and inspecting the flue pipe and safety relief valve.
The related federal contract opportunity is a solicitation for Inspection, Testing and Maintenance (ITM) of Mechanical Equipment at USAG Humphreys. The contractor shall provide ITM services for mechanical equipment at the installation. The solicitation number is W91QVN24R0007, and the response date for proposal submission is 24 May 24, 13:00 hrs, Korean Time. The contracting agency is the Department of the Army Materiel Command Army Contracting Command.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technician :
MFR :
Step# CHK
Remark
Hot Water Boiler (H.W.H.B & D.H.W.H)
Test high & low oil pressure & temperature interlocks.
Test high & low gas pressure & temperature interlocks.
Test operation of low water fuel cut-off devices.
Check hot water pressure gauges.
Bldg No. : Date :
Task
Make visual inspection of the igniter.
Check both pilot & main flame signal strength.
Check flame failure detection system. Close manual fuel supply pilot & main; check safety shutdown timing and log.
Job Plan Title Monthly
Check fuel lines & connections for damage.
CAPACITY : MODEL :
Perform visual opacity checks IAW unmanned boiler SOP.
Inspect and clean or replace water column sightglass.
Check operation of mercury control switches (i.e., hot water temp limit atomizing or combustion air proving, etc.)
Check firing rate control and verify factory settings
Open limit switch and make aural and visual check of the pilot and/or main fuel valves; check valve position indicators
Check condition of flue pipe, damper & exhaust stack.
Check operation & condition of safety pressure relief valve.
Test low draft, fan, air pressure & damper position interlocks.
Check low fire start interlock.
HWB(M)