BILL OF MATERIAL
QTY DEVICE DESCRIPTION
REV
PROJECT
DWG NO:
Tri-M Building Automation Systems 206 Gale Lane Kennett Square, PA 19348 (610)-444-1002
DATE DESCRIPTION
TITLE
APPR BY DATE
3 i2866 ANDOVER CONTROLS I2866-V VAV CONTROLLER WITH ACTUATOR
Social Security Administration
Fan Powered VAV w/Reheat & Clg Coils
John Thomas 12/12/07
BSS001-324
NOTE: THE SCREW AND GROMMET PROVIDED WITH
THE CONTROLLER MUST BE USED TO ATTACH THE
CONTROLLER TO THE VAV BOX.
Install Controller over the VAV Box damper shaft
VAV Box Flow Cross (provided with VAV box)
Tube high and low side to the Andover Controller
2 Conductor to Controller
DRAWN BY
3 TD1 MAMAC TE-702-A-7-A DUCT MOUNTED TEMPERATURE SENSOR
MATERIAL PROVIDED BY VAV BOX MANUFACTURER
3 XFR1 VERIS X050CBA 277/24VAC 50VA ISOLATION TRANSFORMER
3 CO3 24VAC CONTACTOR
3 TS1 ANDOVER CONTROLS TTS-S SPACE TEMPERATURE SENSOR
6 MA2,3 SEE VALVE SCHEDULE
2MA
4 Conductor to Controller
TS 1
TYPICAL FOR FAN POWERED VAVS IN 1ST FLOOR IVT,
1ST FLOOR TRAINING AND CONFERENCE ROOMS
TOTAL (7) NEW TERMINAL UNITS
4 Conductor to Controller
MA
TD 1
2 Conductor to Controller
NOTE: INSTALL THE ACTUATOR SO THAT THE VAV BOX
DAMPER IS IN THE FULL OPEN POSITION WHEN THE
ACTUATOR IS ALIGNED WITH “1”. THE DAMPER SHOULD
BE LEFT IN THE FULL OPEN POSITION.
24VAC
X1
X2
277VAC
POWER 277VAC
XFR1
50VA
Discharge Temperature
TD 1
Space Temperature
TS 1
Infinet To Next ControllerSHIELD
BLK
WHT
SHIELD
BLK
WHT
Infinet From Previous Controller
MA3 Cooling Coil Valve
WHT
RED BLK2
MA2 Reheat Valve
WHT
RED BLK2
3CO Fan Start/Stop
39V Varistor
See Note 1
Notes:
1. Wire the Triac Reference output to the Neutral. The reference is NOT internally connected.
300V Varistor
1 3/18/08 VAV Quantity Revision
2 8/12/08 AS-BUILT DOCUMENTATION
BILL OF MATERIAL
QTY DEVICE DESCRIPTION
REV
PROJECT
DWG NO:
Tri-M Building Automation Systems 206 Gale Lane Kennett Square, PA 19348 (610)-444-1002
DATE DESCRIPTION
TITLE
DRW BY APPR BY DATE
6 i2865 ANDOVER CONTROLS I2865-V VAV CONTROLLER WITH ACTUATOR
Social Security Administration
Fan Powered VAV w/Reheat - TSC
John Thomas 12/12/07
BSS001-325
NOTE: THE SCREW AND GROMMET PROVIDED WITH
THE CONTROLLER MUST BE USED TO ATTACH THE
CONTROLLER TO THE VAV BOX.
Install Controller over the VAV Box damper shaft
VAV Box Flow Cross (provided with VAV box)
Tube high and low side to the Andover Controller
2 Conductor to Controller
6 XFR1 VERIS X050CBA 277/24VAC 50VA ISOLATION TRANSFORMER
6 TS1 ANDOVER CONTROLS TTS-S SPACE TEMPERATURE SENSOR
MATERIAL PROVIDED BY VAV BOX MANUFACTURER
6 CO3 24VAC CONTACTOR
6 MA2 SEE VALVE SCHEDULE
2MA
4 Conductor to Controller
TYPICAL FOR FAN POWERED VAVS IN 1ST FLOOR TSC,
SOUTHERN EXTERIOR ZONE
TOTAL (6) NEW TERMINAL UNITS
TS 1
NOTE: INSTALL THE ACTUATOR SO THAT THE VAV BOX
DAMPER IS IN THE FULL OPEN POSITION WHEN THE
ACTUATOR IS ALIGNED WITH “1”. THE DAMPER SHOULD
BE LEFT IN THE FULL OPEN POSITION.
Infinet To Next ControllerSHIELD
BLK
WHT
SHIELD
BLK
WHT
Infinet From Previous Controller
Space Temperature
TS 1
24VAC
X1
X2
50VA
XFR1
3MA2 Reheat Valve Drive Closed Reheat Valve Drive Open1
3CO Fan Start/Stop
39V Varistor
See Note 1
Notes:
1. Wire the Triac Reference output to the Neutral. The reference is NOT internally connected.
277VAC
POWER 277VAC
300V Varistor
1 8/12/08 AS-BUILT DOCUMENTATION