SECT-50_WATER_DISTRIBUTION.DOC

DOC document 14 KB Posted

Attached to
17th Street T-Ball and Baseball Field Improvements REBID
Solicitation number
2024-040
Issued by
Polk County, Florida

About this file

The document is a technical specification section (SECT-50_WATER_DISTRIBUTION.DOC) from a municipal water distribution project, specifically detailing pipe and service connection materials and standards for the City of St. Cloud, Florida. The specification covers comprehensive requirements for water distribution system components, including polyvinyl chloride (PVC) and ductile iron pipes, service pipes, stops, fittings, and service saddles. The related state and local contract opportunity is for the 17th Street T-Ball and Baseball Field Improvements REBID, with sealed bids being accepted electronically via the OpenGov e-Procurement Platform until 2:00 pm on Tuesday, June 4, 2024.

The technical specification provides detailed technical requirements for pipe materials, including minimum pressure ratings, joint specifications, coating and lining standards, and inspection protocols. Specific requirements include PVC pipes with a minimum 150 psi working pressure, ductile iron pipes with a minimum Pressure Class 350, and service lines using polyethylene tubing. Contractors are responsible for material quality, testing, and replacement of defective items. The specification mandates strict adherence to various AWWA (American Water Works Association) and ANSI standards, with provisions for pipe marking, testing, and potential rejection of non-compliant materials. Bidders must submit responses exclusively through the OpenGov platform, with technical support available for assistance.

View the file

Other files

File Type Posted
17th_Street_T-Ball_and_Baseball_Field_Improvements_REBID_(Addendum_#5_Revision).pdf PDF
Building_Department_Fee_Schedule.pdf PDF
Pole_Barn.pdf PDF
Restroom_Building_Specifications.pdf PDF
Civil_Plans_-_BID_SET_-_17th_Street_Ball_Field_2024-02-23.pdf PDF
SECT-30_GENERAL.pdf PDF
Survey.pdf PDF
Restroom_Building_Plans_&_Site_Electrical.pdf PDF
Landscape_Plans_-_Bid_Set_-_17th_Street_Ball_Field_2023-05-18.pdf PDF
Geotechnical_Reports.pdf PDF
SFWMD_-_ERP_Permit_-_17th_Street_Ball_Fields.pdf PDF
Dugout_Plan.pdf PDF
FDOT_Drainage_Connection_Permit.pdf PDF
City_SDP22-00037_Permit_Approval.pdf PDF
Sect-20_Special_Conditions.pdf PDF
Insurance_Requirements_.pdf PDF
Acord_Certificate_of_Insurance_Sample_.pdf PDF
SECT-30_GENERAL.docx DOCX document
Contractual_Documents.pdf PDF
Payment_And_ContractCompletion_Forms.pdf PDF
SECT-56_CULVERTS_AND_STORM_SEWERS.docx DOCX document
SECT-54_PIPE_INSTALLATION_FOR_RECLAIMED_WATER_SYSTEMS.DOC DOC document
SECT-61_PAVEMENT_MARKING_REMOVAL_(THERMPLASTIC).docx DOCX document
SECT-58_HIGHWAY_SIGNING.docx DOCX document
Performance_Bond.pdf PDF
SECT-60_THERMOPLASTIC_TRAFFIC_STRIPES_AND_MARKINGS.docx DOCX document
SECT-55_VALVES_AND_ACCESS_FOR_RECLAIMED_WATER_MAINS.doc DOC document
SECT-57_INLETS_MANHOLES_AND_JUNCTION_BOXES.docx DOCX document
SECT-59_REFLECTIVE_PAVEMENT_MARKERS.docx DOCX document
SECT-52_VALVES_HYDRANTS_&_ACCESS_FOR_WATER_MAINS.DOC DOC document
SECT-49_Blank.DOC DOC document
SECT-40_PIPE_MATERIAL_FOR_GRAVITY_SANITARY_SEWERS.docx DOCX document
SECT-53_RECLAIMED_WATER_SYSTEMS.DOC DOC document
SECT-46_SEWAGE_PUMPING_STATIONS.rtf RTF text file
SECT-36_PAVEMENT_REMOVAL_AND_RESTORATION.doc DOC document
SECT-45_WASTEWATER_FORCE_MAINS.DOC DOC document
SECT-41_GRAVITY_SEWER_PIPE_LAYING_JOINTING_AND_MISC_CONSTRUCTION_DETAILS.doc DOC document
SECT-47_SUBMERSIBLE_WASTEWATER_PUMPS.DOC DOC document
SECT-39_GRASSING_AND_SEEDING.docx DOCX document
SECT-51_PIPE_INSTALLATION_FOR_WATER_MAINS.DOC DOC document
SECT-32_EXCAVATION_BACKFILL_COMPACTION_GRADING.docx DOCX document
SECT-38_CONCRETE.docx DOCX document
SECT-35_PRESSURE_CONNECTION.doc DOC document
SECT-31_SITE_PREP_SURF_REMOVE.docx DOCX document
SECT-48_PUMP_STATION_ELECTRICAL_POWER_&_CONTROL_SYSTEM.DOC DOC document
SECT-43_SERVICE_LATERALS.docx DOCX document
SECT-42_MANHOLES.docx DOCX document
Payment_Bond.pdf PDF
SECT-37_ROADWAY_CONSTRUCTION_STANDARDS.doc DOC document
SECT-33_BORING_&_JACKING.docx DOCX document
Show 40 more

Latest 50 of 53 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 50 - WATER DISTRIBUTION

SECTION 50 - WATER DISTRIBUTION

Item No. Title

50.1PIPE MATERIAL FOR WATER MAINS AND SERVICE CONNECTION
50.1.1General

50.2 PIPE INSPECTION AND TESTING

50.3PVC PIPE
50.3.1PVC Pipe
50.3.2Joints
50.3.3Fittings
50.4DUCTILE IRON PIPE AND FITTINGS
50.4.1Ductile Iron Pipe
50.4.2Fittings
50.4.3Joints
50.4.4Coatings and Linings
50.4.5Polyethylene Encasement
50.5SERVICE PIPE, STOPS, FITTINGS, AND SERVICE SADDLES
50.5.1Service Pipe
50.5.2Stops
50.5.3Fittings
50.5.4Service Saddles

50.1 PIPE MATERIAL FOR WATER MAINS AND SERVICE CONNECTIONS

50.1.1 GENERAL

These specifications cover the pipe, fittings, and accessory items used for water distribution systems.

Pipe used in water distribution systems shall be either polyvinyl chloride (PVC), or ductile iron pipe (DIP).

The CONTRACTOR shall be responsible for all materials furnished and storage of same, until the date of substantial completion. He shall replace at his expense all materials found to be defective or damaged in handling or storage. The CONTRACTOR shall, if requested by the CITY ENGINEER or designee, furnish certificates, affidavits of compliance, test reports, or samples for check analysis for any of the materials specified herein. All pipe delivered to project site for installation is subject to random testing for compliance with the designated specifications.

50.2 PIPE INSPECTION AND TESTING

Each length of pipe shall bear the name or trademark of the manufacturer, the location of the manufacturing plant, and the class or strength classification of the pipe. The markings shall be plainly visible on the pipe barrel. Pipe, which is not marked, clearly is subject to rejection. All rejected pipe shall be promptly removed from the project site by the CONTRACTOR.

All pipe and accessories to be installed under this Contract shall be inspected and tested at the place of manufacture by the manufacturer as required by the Standard Specifications to which the material is manufactured.

Each length of pipe shall be subject to inspection and approval at the factory, point of delivery, and site of work. If requested by the CITY ENGINEER or designee, a sample of pipe to be tested shall be selected at random by the CITY or the testing laboratory hired by the CITY.

When the specimens tested conform to applicable standards, all pipe represented by such specimens shall be considered acceptable based on the test parameters measured. Copies of test reports shall be available before the pipe is installed in the project.

In the event that any of the test specimens fail to meet the applicable standards, all pipe represented by such tests shall be subjected to rejection. The CONTRACTOR may furnish two additional test specimens from the same shipment or delivery, for each specimen that failed and the pipe will be considered acceptable if all of these additional specimens meet the requirements of the applicable standards. All such retesting shall be at the CONTRACTOR'S expense.

50.3 PVC PIPE

50.3.1 PVC PIPE

All PVC pipe shall be manufactured in accordance with AWWA standard C900, latest edition. PVC pipe shall have a minimum working pressure rating of 150 psi and shall have a dimension ratio (DR) of 18. Pipe shall be the same O.D. as ductile iron pipe.

50.3.2 JOINTS

PVC pipe shall have integral bell push on type joints conforming to ASTM D3139.

50.3.3 FITTINGS

Fittings used with PVC pipe shall conform to Section 50.4.

50.4 DUCTILE IRON PIPE AND FITTINGS

50.4.1 DUCTILE IRON PIPE

All ductile iron pipe of nominal diameter four (4) through fifty four (54) inches shall conform to ANSI/AWWA A21.51/C151. A minimum of Pressure Class 350 pipe shall be supplied for all sizes of pipe unless specifically called out in the DRAWINGS, or required by the CITY ENGINEER or designee.

50.4.2 FITTINGS

Any fittings required shall be mechanical joint ductile iron or gray iron conforming to ANSI/AWWA A21.10/C110, 250 psi minimum pressure rating, or ductile iron compact fittings four (4) through twelve (12) inches in accordance with ANSI/AWWA A21.53/C153.

50.4.3 JOINTS

Joints for ductile iron pipe and fitting joints shall be push-on or mechanical joints conforming to ANSI/AWWA A21.11/C111. Where called for in the plans, restrained or flanged joints shall be provided. Flanged joints shall conform to ANSI Standard B 16.1-125 LB. Restrained joints shall conform to Sections 34.3 and 34.4.

50.4.4 COATINGS AND LININGS

Where ductile iron pipe and fittings are to be below ground or installed in a casing pipe, the coating shall be a minimum 1.0 mil thick in accordance with ANSI/AWWA A21.51/C151. Where ductile iron pipe and fittings are to be installed above ground, pipe, fittings and valves shall be thoroughly cleaned and given one field coat (minimum 1.5 mils dry thickness) of rust inhibitor primer. Intermediate and finished field coats of Alkyd shall also be applied by the CONTRACTOR (minimum 1.5 mils dry thickness each coat). Primer and field coats shall be compatible and shall be applied in accordance with the manufacturers recommendations. Final field coat shall be green for raw water and blue for finished water.

All ductile iron pipe and fittings shall have an interior protective lining of cement-mortar with a seal coat of asphaltic material in accordance with ANSI/AWWA A21.4/C104.

50.4.5 POLYETHYLENE ENCASEMENT

The pipe shall be polyethylene encased (8 mil) where shown on the DRAWINGS or required by the CITY ENGINEER or designee in accordance with ANSI/AWWA A21.51/C105.

50.5 SERVICE PIPE, STOPS, FITTINGS, AND SERVICE SADDLES

50.5.1 SERVICE PIPE

All service lines shall be 1", 1-1/2" or 2" polyethylene tubing conforming to specifications in AWWA C800 and AWWA C901.

50.5.2 STOPS

Corporation stops shall be 1", 1-1/2" or 2" brass, equipped with connections compatible with the polyethylene tubing and threaded in accordance with specifications, in AWWA C800 and AWWA C901. Curb stops shall be sized to match the meter size and conform to the specifications in AWWA C800 and AWWA C901.

50.5.3 FITTINGS

Fittings shall be brass, cast and machined in accordance with specifications in AWWA C800 and AWWA C901, with compatible polyethylene tubing connections.

50.5.4 SERVICE SADDLES

A service saddle shall be used for all service line taps. Service saddles shall be double strap, anchored by a minimum four (4) bolt pattern on a ductile iron saddle body. Service saddles for PVC pipe shall have the double strap sized exactly to the pipe outside diameter. Sealing gaskets shall be BUNA-N rubber and straps shall be corrosion resistant alloy steel.

The CITY ENGINEER or designee may require a stainless steel strap and fusion epoxy or nylon coated ductile iron body with stainless steel hardware in areas designated as corrosive.

File details come from the government source that posted it. Updated .