This pre-solicitation notice announces the Department of Veterans Affairs' intent to issue an invitation for bids to replace parking structure elevators at the John D. Dingell Veterans Medical Center in Detroit, Michigan. The project entails furnishing all labor, materials, equipment, and supervision to complete the work according to drawings and specifications. The work is to be performed during normal business hours excluding federal holidays. The acquisition is reserved for verified service-disabled veteran-owned small businesses. The invitation for bids is scheduled for release on September 9, 2022 via SAM.gov, with a bid due date and other relevant dates to follow in the solicitation. The contract type will be firm-fixed-price with an anticipated award within 120 days of bid opening. The project magnitude is estimated between $5 million and $10 million. Questions should be directed to the named contracting specialist by email only.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
SD-B
SD-A.9
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
1 SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8
EXISTING 3" UP TO RD
4" SD 4"
4" SD
4"
EXISTING 3" UP TO RD
4" SD
ELEVATOR LOBBY
SP601
STAIR #1
ELEV
101-1
ELEV
101-2
FUTURE ELEV
101-3
UNASSIGNED
CO
CO
CO
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:2
A
M
PD103
5TH LEVEL PLUMBING DEMOLITION
PLAN - BUILDING 101
2 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
5TH LEVEL PLUMBING DEMOLITION PLAN - BLDG 101
1 REMOVE EXISTING PIPING AS INDICATED FOR
REROUTING ALONG WALLS.
DocuSign Envelope ID: A2E84575-819A-4324-B109-CAAD6666B90C
3/23/2022
ND-4 ND-3 ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9
ND-DD
ND-CC
ND-BB
ND-AA
ND-A.9
ND-A
ND-B
3" PD
ELEVATOR PIT
SP-2
SP-1
STAIR #1
STAIR #1
PUMP ROOM
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:3
A
M
PD111
BASEMENT PLUMBING DEMOLITION
PLAN - BUILDING 102
3 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN - BLDG 102
1 REMOVE EXISTING VERTICAL SUMP PUMPS,
MOTORS, AND RELATED PIPING AS INDICATED FOR
REPLACEMNT.
ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9 31
ND-CC
ND-BB
ND-AA
ND-A.9
ND-A
L
ND-B
EXISTING 3" UP TO RD
EXISTING 3" UP TO RD
STAIR #1
ELEVATOR LOBBY
NP601
ELEV
102-3
ELEV
102-2
FUTURE ELEV
102-1
UNASSIGNED
1 4"
4" SD
CO
CO
4" SD4" V
4" V
4" SD
CO
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:3
A
M
PD113
5TH LEVEL PLUMBING DEMOLITION
PLAN - BUILDING 102
4 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
5TH LEVEL PLUMBING DEMOLITION PLAN - BLDG 102
1 REMOVE EXISTING PIPING AS INDICATED FOR
REROUTING ALONG WALLS.
UP
SD-A.9
SD-A
SD-AA
SD-2.3
101-SP-11
43" PD
SD-B
SD-A.9
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8
3" PD42
3 5
CO
3" PD 53" PD 5
3" PD 5 6
3" PD
5 3" PD
SEE P-501/DETAIL 3 FOR ELEVATION VIEW
101-TP-1
EXISTING 6" WASTE STACK UP;
8" WASTE STACK DOWN
8" SAN
3" PD
EXISTING 6" VENT UP
8" VENT STACK DOWN
8" SAN
ELEVATOR LOBBY
SP101
EMERGENCY ELEC
SP103
ELECTRICAL
SP102
SIGNAL
SP104
STAIR #1
SPS101
ELEV
101-1
ELEV
101-2
FUTURE ELEV
101-3
CORRIDOR
WOMEN
MEN
STAIR
Room
PROVIDE NEW 1/2" DCW BRANCH &
BALL VALVE FROM EXISTING DCW
TO SERVE NEW TRAP PRIMER
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:5
A
M
P-101
ELEVATOR PIT AND LOWER LEVEL
PLUMBING PLANS - BUILDING 101
5 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
1 NEW SUMP PUMP IN EXISTING SUMP. PIPE TO
INDIRECT WASTE INTO EXISTING SANITARY PIPE.
SEE 2/P-501.
2 ROUTE NEW PIPING IN PIT TO AVOID CONFLICT
WITH STRUCTURE, ELEVATOR EQUIPMENT, ETC.
3 PIPING UP ON WALL TO BOTTOM OF EXISTING
STRUCTURE.
4 PIPING UP ON WALL AND THROUGH, JUST ABOVE
EXISTING MECHANICAL ROOM FLOOR LEVEL.
5 PIPING TIGHT TO STRUCTURE. ROUTE NEW PIPING
TO AVOID CONFLICT WITH STRUCTURE, CONDUITS,
EQUIPMENT, ETC.
6 PIPING IN GARAGE EXPOSED TO OUTSIDE AIR TO
BE HEAT TRACED.
7 3" PUMPED DISCHARGE INTO NEW 6" TRAP ARM.
SEE 3/P-501.
8 SUMP PUMP CONTROL PANEL ON WALL WITH
BOTTOM AT 4 FEET AFF.
9 CAREFULLY PENETRATE EXISTING GLAZED BRICK
EXTERIOR WALL TO ROUTE NEW DISCHARGE
PIPING INTO THE EXISTING MECHANICAL ROOM.
N O
R T H
0 2 4 8
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
ELEVATOR PIT PLUMBING PLAN - BLDG 101
Scale: 1/4" = 1'-0"
LOWER LEVEL PLUMBING PLAN - BLDG 101
SD-A.9
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
1 SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8
EXISTING 3" UP TO RD
NEW 2" UP TO RD
CO
2" SD
4" SD
4" SD
4" SD
CO
EXISTING 3" UP TO RD
4" SD
ELEVATOR LOBBY
SP601
4" SD 1
2 2" SD
2" SD
CO
FIRE STANDPIPE AND HOSE CONNECTION
ELEV
101-1
STAIR #1
ELEV
101-2
FUTURE ELEV
101-3
UNASSIGNED
CO
CO
SD-B
SD-A.9
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
1 SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8
EXISTING 3" RD
EXISTING 3" RD
RD-2
2" SD43
STAIR #1
SPS601
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:5
A
M
P-103
5TH LEVEL AND LOBBY ROOF
PLUMBING PLANS - BUILDING 101
6 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RBK
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
5TH LEVEL PLUMBING PLAN - BLDG 101
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
LOBBY ROOF PLUMBING PLAN - BLDG 101
1 PIPING TIGHT TO STRUCTURE. ROUTE NEW PIPING
TO AVOID CONFLICT WITH STRUCTURE, CONDUITS,
EQUIPMENT, ETC.
2 PIPE UP. SEE 2/P-103 FOR CONTINUATION.
3 PIPE DOWN. SEE 1/P-103 FOR CONTINUATION.
4 PIPE UP. SEE 1/P-104 FOR CONTINUATION.
SD-A.9
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
1 SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8
2" SD
2" SD
2" SD3
STAIR #1
ELEV MACHINE ROOM
SP701
SD-B
SD-A.9
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
1 SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8
RD-1
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:0
A
M
P-104
NEW PENTHOUSE AND PENTHOUSE
ROOF PLUMBING PLANS - BUILDING
7 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RBK
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
N O
R T H
0 2 4 8
N O
R T H
0 2 4 8
1 PIPE DOWN FROM ROOF DRAIN ABOVE. SEE 2/P-104
FOR CONTINUATION.
2 PIPING TIGHT TO STRUCTURE.
3 PIPING DOWN. SEE 2/P-103 FOR CONTINUATION.
Scale: 1/4" = 1'-0"
NEW PENTHOUSE PLUMBING PLAN - BLDG 101
Scale: 1/4" = 1'-0"
NEW PENTHOUSE ROOF PLUMBING PLAN - BLDG 101
ND-4
ND-3 ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9
ND-DD
ND-CC
ND-BB
ND-AA
ND-A.9
ND-A
ND-B
1102-SP-2
102-SP-1
3" PD
STAIR #1
ELEVATOR PIT
PUMP ROOM
2" PD
2" PD
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:0
A
M
P-111
BASEMENT PLUMBING PLAN - BLDG 102
8 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
1 NEW SUMP PUMP TO REPLACE EXISTING PUMP IN
EXISTING SUMP.
2 CONNECT NEW PUMPS TO EXISTING PIPE. PROVIDE
NEW CHECK VALVES, UNIONS, AND ISOLATION
VALVES.
3 SEE 2/P-501, SIMILAR.
4 SUMP PUMP CONTROL PANEL WITH BOTTOM AT 4
FEET AFF.
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
BASEMENT PLUMBING PLAN - BLDG 102
ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9 31
ND-CC
ND-BB
ND-AA
ND-A.9
ND-A
L
ND-B
EXISTING 3" UP TO RD
EXISTING 3" UP TO RD
4" V
4" V
NEW 2" UP TO RD
STAIR #1
ELEVATOR LOBBY
NP601
ELEV
102-3
ELEV
102-2
FUTURE ELEV
102-1
UNASSIGNED
2 5
2" SD
4" SD
4" SD
CO
CO
4" SD
4" SD
2" SD
2" SD
FIRE STANDPIPE AND HOSE CONNECTION
4" SD
CO
CO
ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9 31
ND-DD
ND-CC
ND-BB
ND-AA
ND-A.9
ND-AL
ND-B
EXISTING 3" RD
EXISTING 3" RD
RD-2
2" SD 3 4
4" V
4" V 3 4 5
2" SD ?
STAIR #1
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:1
A
M
P-113
5TH LEVEL AND LOBBY ROOF
PLUMBING PLANS - BUILDING 102
9 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
N O
R T H
0 2 4 8
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
5TH LEVEL PLUMBING PLAN - BLDG 102
1 PIPING TIGHT TO STRUCTURE. ROUTE NEW PIPING
TO AVOID CONFLICT WITH STRUCTURE, CONDUITS,
EQUIPMENT, ETC.
2 PIPE UP. SEE 2/P-113 FOR CONTINUATION.
3 PIPE DOWN. SEE 1/P-113 FOR CONTINUATION.
4 PIPE UP. SEE 1/P-114 FOR CONTINUATION.
5 EXTEND EXISTING 4" VENT FROM 1 FOOT ABOVE
EXISTING ROOF UP IN CHASE AND TERMINATE 1
FOOT ABOVE NEW ROOF.
Scale: 1/4" = 1'-0"
LOBBY ROOF PLUMBING PLAN - BLDG 101
ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9
ND-CC
ND-BB
ND-AA
ND-A.9
ND-A
ND-B
STAIR #1
ELEV MACHINE ROOM
NP701
4" V
4" V
2" SD 3
PIPING DOWN. SEE 2/P-113
FOR CONTINUATION.
2" SD
2" SD
STAIR #1
ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.8 ND-1 ND-.9 31
ND-DD
ND-CC
ND-BB
ND-AA
ND-A.9
ND-AL
ND-B
RD-1
4" VTR
4" VTR
4 6
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:1
A
M
P-114
NEW PENTHOUSE AND PENTHOUSE
ROOF PLUMBING PLANS - BUILDING
10 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
NEW PENTHOUSE PLUMBING PLAN - BLDG 102
1 PIPING DOWN FROM ROOF DRAIN ABOVE. SEE
2/P-113 FOR CONTINUATION.
2 PIPING TIGHT TO STRUCTURE.
3 PIPING DOWN. SEE 2/P-113 FOR CONTINUATION.
4 EXTEND EXISTING 4" VENT FROM 1 FOOT ABOVE
EXISTING ROOF UP IN CHASE AND TERMINATE 1
FOOT ABOVE NEW ROOF.
5 PIPE UP. SEE 2/P-114 FOR CONTINUATION.
6 PIPE DOWN. SEE 1/P-114 FOR CONTINUATION.
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
NEW PENTHOUSE ROOF PLUMBING PLAN - BLDG 101
NOM. SIZE (IN.)
PIPE (FT.)
TUBING (FT.)
5 FT
THRU 3/4
1 1 1/4
1 1/2
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR
LOW TEMPERATURE
PIPE)
PROVIDE HIGH
COMPRESSIVE
STRENGTH
INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD AT
HANGER
WELD
SADDLE
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE
SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE
SPECIFICATIONS
1/2" DIA. HANGER RODS WITH 36"
MAX. SPACING ON EACH CHANNEL
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2" x 2" x 1/4" ANGLE
NOTES:
SEE SPECIFICATIONS FOR
DETAILED HANGER
REQUIREMENTS. SIDE VIEW TRAPEZE HANGER
FOR UP TO 1000 LB. UNIFORM
LOAD
1" MAX.
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8" MIN.)
2 2 1/2 3 4 5 6 8 10 12
11 12 14 16 17 19 22 23
9 10 12 13 14 16 - -
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE
MAXIMUM PIPE/TUBING SUPPORT SPACING
ELECTRIC OUTLET NIPC
POWER SUPPLY
MULTI-PIN CONNECTOR
AND CORD IN CONDUIT
AS REQUIRED.
OLD ELEVATOR
MACHINE ROOM
FLOOR
JUNCTION BOX
GATE VALVE
3.
4.
5.
6.
2.
1.
1. SUBMERSIBLE EFFLUENT PUMP .
2. CHECK VALVE.
3. CONTROL SYSTEM AUDIBLE AND VISUAL
ALARM WHEN PUMP DOES NOT RUN DUE TO
HIGH AMPERAGE OR HIGH LIQUID CONDITION.
PROVIDE SILENCING BUTTON FOR AUDIBLE
ALARM BUILT INTO PANEL. PANEL SHALL
HAVE ADDITIONAL CONTACT FOR A REMOTE
ALARM LOCATION.
4. PROVIDE JUNCTION BOX WITH MULTI-PIN
CONNECTOR AND CORD IN LENGTHS AS
REQUIRED.
5. COMBINED POWER CABLE, PROBE CABLE
AND FLOAT CABLE (ALL 16' LONG).
6. HIGH LIQUID ALARM FLOAT WITH CLAMP
DEVICE TO MOUNT TO PUMP DISCHARGE
PIPING.
UNION, TYP.
REDUCER FITTING AS FUNNEL
1" AIR GAP MINIMUM
PUMP DISCHARGE CENTERED
OVER SANITARY WASTE PIPE
TRAP PRIMER DISCHARGE
OVER SANITARY WASTE PIPE
NEXT TO PUMPED DISCHARGE
CONNECT TO EXISTING PIPING
EXISTING 8" SAN
6" TRAP ARM BACKWATER VALVE
EXISTING 6" SAN UP
EXISTING 6" VENT UP
TRAP PRIMER
1/2" DCW FROM PIPING IN THIS AREA
3" VENT
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:1
A
M
P-501
PLUMBING DETAILS
11 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
Scale: No Scale
PIPE HANGER DETAIL
Scale: No Scale
ELEVATOR PIT SUMP PUMP DETAIL
Scale: No Scale
SUMP PUMP DISCHARGE TRAP DETAIL
5TH LEVEL
54' - 6"
NEW
P
.H . R
OOF
83' - 8"
NEW
P
.H . L
EVEL
72' - 4"
5TH LEVEL
54' - 6"
NEW
P
.H . R
OOF
83' - 8"
NEW
P
.H . L
EVEL
72' - 4"
RD-1
4" SD
4" SD
EXISTING 4"
FROM LOBBY
ROOF DRAINS
EXISTING FIRE
STANDPIPE
2" SD
NEW FIRE
STANDPIPE
RD-1
NEW FIRE
STANDPIPE
EXISTING 4"
FROM LOBBY
ROOF DRAINS
EXISTING FIRE
STANDPIPE
2" SD
4" SD
4" SD
4" V
4" V
4" V
4" V
4" VTR
4" VTR
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:2
A
M
P-901
STAIRWELL STORM DRAIN PIPING
ISOMETRICS
12 12WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
Scale: No Scale
STAIRWELL STORM DRAIN PIPING ISOMETRIC - BUILDING 101
Scale: No Scale
STAIRWELL STORM DRAIN PIPING ISOMETRIC - BUILDING 102
NORTH
N O R
TH
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR-COOLED CONDENSER
ACCH AIR-COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
ACD AUTOMATIC CONTROL DAMPER,
MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER,TWO
POSITION
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERAGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND
REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT
EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BSC BIOLOGICAL SAFETY CABINETS
BT BUFFER TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CENTIGRADE (CELSIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CH CHILLER
CHWP CHILLED WATER PUMP
CHW CHILLER WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CHWCC CHILLED WATER COOLING COIL
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
D-4 ECONOMIZER OUTDOOR AIR
DAMPER
dB DECIBELS Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE
ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECC ENGINEERING CONTROL CENTER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FM FLOW METER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GS GALVANIZED STEEL
H HUMIDIFIER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HHW HEATING HOT WATER
HHWC HEATING HOT WATER COIL
HHWP HEATING HOT WATER PUMP
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM
CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
Hz HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
IS INSECT SCREEN
IV INLET VANES
kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
L LITER
L/s LITERS PER SECOND
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LH LATENT HEAT
LPR LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPS LOW PRESSURE SUPPLY (STEAM)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL
PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/s METERS PER SECOND (OR
METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM
CONDENSATE)
MPS MEDIUM PRESSURE SUPPLY (STEAM)
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OR OPERATING ROOM
OSA OUTSIDE SUPPLY AIR
(CONDITIONED)
P PUMP
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PHC PREHEAT COIL
PHCP PREHEAT COIL PUMP
PPM PARTS PER MILLION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH –
ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
R/E RETURN OR EXHAUST
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND
DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSR SOLID SEPARATOR
ST STEAM TRAP
SV STEAM SAFETY VALVE
SVS STEAM VENT SILENCER
T & PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TP TRAP
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
UC UNDER CUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL
OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE)
RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WATTS
Wb WET-BULB (TEMPERATURE)
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
XT EXPANSION TANK
YR YEAR
CO2 CARBON DIOXIDE SENSOR
HUMIDISTAT OR HUMIDITY SENSOR
SUPPLY DIFFUSER
RETURN GRILLE
EXHAUST GRILLE
ROUND FLEX DUCT
EQUIPMENT TAG
LINEAR SLOT DIFFUSER
BALANCING DAMPER
FIRE DAMPER
SMOKE DAMPER
D
R INCLINED RISE, IN
DIRECTION OF AIRFLOW
INCLINED DROP, IN DIRECTION
OF AIRFLOW
CONNECT NEW DUCT
TO EXISTING
LIMIT OF DEMOLITION
VANED ELBOW (PROVIDE ALL
SQUARE OR RECTANGULAR
ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
STANDARD RADIUS ELBOW
(LONG RADIUS)
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
DUCT TRANSITION
END MOUNTED OR SIDEWALL GRILLE
SUPPLY
RETURN45°
45°
DN
DN
UP
UP
DNUP
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45° TAP)
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
S-60
S-15
CR-15
CHWS
CHWR
HIGH PRESSURE STEAM
PIPING (60 PSI AND ABOVE)
LOW PRESSURE STEAM PIPING
(15 PSI AND BELOW)
LOW PRESSURE STEAM
CONDENSATE RETURN
CHILLED WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
PIPE UP
PIPE DOWN
BOTTOM CONNECTION
TOP CONNECTION
CAPPED OR PLUGGED PIPE
GLOBE VALVE
GATE VALVE
BALL VALVE
STEAM SAFETY VALVE
PRESSURE REGULATING VALVE
WYE STRAINER VALVE
BALANCING VALVE
MODULATING TWO-WAY CONTROL
VALVE
STEAM TRAP
COND CONDENSATE DRAIN LINE
CR-60 HIGH PRESSURE STEAM
CONDENSATE RETURN
HWS
HWR
HEATING HOT WATER SUPPLY
PIPING
HEATING HOT WATER RETURN PIPING
RLS REFRIGERANT LINE SET (LIQUID
AND SUCTION)
CONNECT TO EXISTING PIPE
LIMIT OF DEMOLITION
INLINE CENTRIFUGAL PUMP
STEAM PRESSURE REDUCING
VALVE
DRAIN VALVE
TEST PLUG
SUPPLY
TERMINAL UNIT SUPPLY
DUCT BRANCH (CONICAL
TAP)
CHECK VALVE
FIRE / SMOKE DAMPER
VANED ELBOW (SHORT RADIUS) S-30
CR-30
MEDIUM PRESSURE STEAM
PIPING (16 PSI TO 59 PSI)
MEDIUM PRESSURE STEAM
CONDENSATE RETURN
THERMOSTAT OR TEMPERATURE SENSOR
TWO POSITION CONTROL VALVE
DIFFUSER TAG | DIFFUSER CFM
32-CU-4
EG-8 2000
MODULATING THREE-WAY
CONTROL VALVE
T
H
F
SD
FS
1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
3. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.
4. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE PURPOSES INTENDED.
5. WHERE POSSIBLE, PROVIDE STANDARD PRODUCTS OF THE VARIOUS MANUFACTURERS EXCEPT WHERE SPECIAL CONSTRUCTION OR PERFORMANCE FEATURES ARE REQUIRED.
6. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS SHALL BE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.
7. PROVIDE MECHANICAL EQUIPMENT THAT IS LISTED AND LABELED BY UNDERWRITERS LABORATORIES (U.L.).
8. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT MAINTENANCE, REPAIRS, AND REPLACEMENT.
9. INSTALL EQUIPMENT WITH PROPER CLEARANCES FOR REQUIRED PIPING AND ELECTRICAL SERVICES AND CONNECTIONS. INSTALL EQUIPMENT WITH REQUIRED ACCESS AND CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS AND APPLICABLE CODES AND STANDARDS.
10. COORDINATE LOCATION, INSTALLATION, AND ROUTING OF DUCTWORK, PIPING, AND EQUIPMENT WITH WORK OF ALL OTHER TRADES.
11. PROVIDE SUPPORT FOR MECHANICAL EQUIPMENT. COORDINATE SUPPORT LOCATIONS WITH ALL CONTRACTORS PRIOR TO INSTALLATION.
12. PROVIDE POWER CONNECTIONS TO EQUIPMENT PROVIDED UNDER THIS CONTRACT AS WORK OF DIVISION 26.
13. PROVIDE CONTROL WIRING FOR MECHANICAL EQUIPMENT AS WORK OF DIVISION 23.
14. DUCTWORK AND PIPING LAYOUTS AND LOCATIONS ARE SCHEMATIC. DO NOT SCALE THESE DRAWINGS. COORDINATE AND DETERMINE EXACT ROUTING OF DUCTWORK AND
PIPING IN THE FIELD.
15. FIELD VERIFY DIMENSIONS BY ACTUAL MEASUREMENT AND OBSERVATION BEFORE ORDERING OR FABRICATING DUCTWORK, PIPING OR EQUIPMENT.
16. NOTIFY COR REGARDING DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND EXISTING CONDITIONS OR DIMENSIONS BEFORE PERFORMING WORK. FAILURE TO VERIFY AND REPORT SHALL CONSTITUTE CONTRACTOR'S ACCEPTANCE OF EXISTING CONDITIONS AS FIT FOR THE PROPER EXECUTION OF THE WORK.
17. SEE ARCHITECTURAL DRAWINGS FOR FINAL LOCATION OF CEILING INSTALLED EQUIPMENT.
18. INSTALL DUCTWORK AND PIPING AS HIGH AS POSSIBLE AND AS CLOSE AS POSSIBLE TO BUILDING WALLS, CEILING AND FLOOR AND ROOF STRUCTURE. PROVIDE OFFSETS, FITTINGS, AND DIMENSIONAL TRANSITIONS NOT SHOWN BUT REQUIRED TO MAINTAIN MINIMUM CLEAR SPACE TO BUILDING SURFACES AT NO ADDITIONAL COST.
19. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH MECHANICAL WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.
20. SUBMIT BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AT COMPLETION OF PROJECT.
21. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION.
22. MAKE A COMPLETE REVIEW OF DRAWINGS, INCLUDING SCHEDULES AND DETAILS, PRIOR TO BEGINNING MECHANICAL SYSTEM INSTALLATION. RESOLVE CONFLICTS WITH COR.
23. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING SYSTEMS.
24. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE
NOT ACCEPTABLE UNLESS SPECIFICALLY INDICATED OTHERWISE.
25. INSTALL PIPING FREE OF SAGS AND BENDS.
26. INSTALL PIPING TO ALLOW APPLICATION OF INSULATION.
27. PIPING SHALL NOT BE ROUTED OVER TELECOM OR ELECTRICAL CLOSETS/ROOMS.
28. PREPARE DRAWINGS SHOWING MECHANICAL SYSTEMS AND EQUIPMENT FOR COORDINATION WITH WORK OF OTHER DIVISIONS AND WORK BY THE GOVERNMENT.
A. INCLUDE PLAN VIEWS, SECTIONS, AND ELEVATIONS, AS REQUIRED, TO FULLY COORDINATE ALL NEW WORK WITH ITSELF AND EXISTING CONDITIONS.
B. DRAWINGS SHALL SHOW ALL DUCTWORK, AIR DISTRIBUTION, MECHANICAL EQUIPMENT, MECHANICAL PIPING, FIRE PROTECTION PIPING, PLUMBING PIPING, CABLE TRAYS, LIGHTING FIXTURES, CEILING GRID AND HEIGHT, BEAMS AND JOISTS (WITH ELEVATIONS MARKED), ELECTRICAL CONDUIT LARGER THAN 2 INCHES IN DIAMETER AND OTHER
CEILING MOUNT DEVICES OR EQUIPMENT THAT PROTRUDE INTO THE CEILING CAVITY.
C. IF THERE ARE OUTSTANDING ISSUES THAT CANNOT BE RESOLVED, CONSULT WITH COR FOR GUIDANCE AND MAKE CORRECTIONS IN ACCORDANCE WITH DIRECTIONS GIVEN.
D. DO NOT BEGIN FABRICATION OR PLACE EQUIPMENT ORDERS UNTIL COORDINATION DRAWINGS HAVE BEEN APPROVED.
29. INSTALLATION COMMENCED PRIOR TO COORDINATION DRAWING APPROVAL IS TAKEN AT THE CONTRACTORS OWN RISK. MODIFY, MOVE OR RECONFIGURE WORK LACKING
COORDINATION AT NO ADDITIONAL COST
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
BRAND ITEM SPECIFICATION SECTION NOTES
HILTI FS1-FIRESTOP 07 84 00 BOTH SIDES OF FIRE-RATED WALLS, SMOKE BARRIERS, AND
FLOORS REGARDLESS OF FIRE RATING
DIVISION 08 - OPENINGS
BRAND ITEM SPECIFICATION SECTION NOTES
YALE LOCKS & DOOR HARDWARE 08 71 00 LARGE FORMAT 7-PIN REMOVABLE CORE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
BRAND ITEM SPECIFICATION SECTION NOTES
SIEMENS HVAC CONTROLS 23 09 23
SIEMENS BUILDING MANAGEMENT SYSTEM (BMS)
DIVISION 26 - ELECTRICAL
BRAND ITEM SPECIFICATION SECTION NOTES
SIEMENS ELECTRICAL 26 22 00
26 24 16 26 29 11 26 29 21 26 43 13
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
BRAND ITEM SPECIFICATION SECTION NOTES
SECURITY 2000 PHYSICAL SECURITY 28 13 00
28 23 00
SIMPLEX FIRE ALARM SYSTEM / VENDOR 28 31 00
EN-GAUGE EN-VISION OBSTRUCTION SENSOR 28 31 00 VA SUPPLIED / CONTRACTOR INSTALLED
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:0
A
M
M-001
MECHANICAL GENERAL INFORMATION
1 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
MECHANICAL ABBREVIATIONS
MECHANICAL LEGEND
MECHANICAL GENERAL NOTES
SOLE SOURCE LIST
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
1 SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8 SD-3
1 2
ELEVATOR LOBBY
SP101
ELEVATOR LOBBY
SP101
STAIR #1
SPS101
STAIR #1
SPS101
ELECTRICAL
SP102
EMERGENCY ELEC
SP103
SIGNAL
SP104
FUTURE ELEV
101-3
ELEV
101-2
ELEV
101-1
101-EF-EX
101-EUH-EX 101-FC-LL-EX
101-CU-LL-EX
T
101-LVR-EX
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:4
A
M
MD101
LOWER LEVEL MECHANICAL
DEMOLITION PLAN - BUILDING 101
2 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
1 EXISTING UNIT HEATER TO REMAIN.
2 DEMOLISH EXISTING DX HVAC SYSTEM.
REFRIGERANT SHALL BE RECOVERED BY A
QUALIFIED CONTRACTOR.
3 DEMOLISH EXISTING HYDRAULIC PIPING THAT
SERVES THE HYDRAULIC ELEVATOR MACHINERY.
SEE AD101 FOR COORDINATION OF DEMOLITION.
4 EXISTING EXHAUST FAN AND INTAKE LOUVER
SYSTEM TO REMAIN.
Scale: 1/4" = 1'-0"
LOWER LEVEL MECHANICAL DEMOLITION PLAN - BLDG 101
N O
R T H
0 2 4 8
SD-B
SD-A.9
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8
SD-3
ELEVATOR LOBBY
SP601
STAIR #1
ELEV
101-1
ELEV
101-2
FUTURE ELEV
101-3
UNASSIGNED
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:4
A
M
MD103
5TH LEVEL MECHANICAL DEMOLITION
PLAN - BUILDING 101
3 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
1 DEMOLISH EXISTING OUTSIDE AIR INTAKE & HOOD.
SEE STRUCTURAL DRAWINGS FOR ADDITIONAL
COORDINATION.
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
5TH LEVEL MECHANICAL DEMOLITION PLAN - BLDG 101
ND-3 ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9 31
ND-CC
ND-BB
ND-AA
ND-A.9
ND-AL
ND-B
ELEVATOR LOBBY
NP101
ELEVATOR LOBBY
NP101
ELECTRICAL
NP102
EMERGENCY ELEC
NP103
SIGNAL
NP104
ELEV
102-3
ELEV
102-2
FUTURE ELEV
102-1
STAIR #1
NPS101
UNASSIGNED
NP105
STAIR #1
NPS101
102-CU-LL-EX
102-FC-LL-EX
102-EUH-EX
102-EF-EX
T
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:4
A
M
MD111
LOWER LEVEL MECHANICAL
DEMOLITION PLAN - BUILDING 102
4 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
Scale: 1/4" = 1'-0"
LOWER LEVEL MECHANICAL DEMOLITION PLAN - BLDG 102
N O
R T H
0 2 4 8
1 EXISTING UNIT HEATER TO REMAIN.
2 DEMOLISH EXISTING DX HVAC UNIT. REMAINING
REFRIGERANT SHALL BE REMOVED AND DISPOSED
OF BY A QUALIFIED CONTRACTOR.
3 DEMOLISH EXISTING HYDRAULIC PIPING THAT
SERVES THE HYDRAULIC ELEVATOR MACHINERY.
SEE AD112 FOR COORDINATION OF DEMOLITION.
4 EXISTING EXHAUST FAN AND INTAKE LOUVER
SYSTEM TO REMAIN.
ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9 31
ND-DD
ND-CC
ND-BB
ND-AA
ND-A.9
ND-A
ND-B
UNASSIGNED
NP602
FUTURE ELEV
102-1
ELEV
102-2
ELEV
102-3
ELEVATOR LOBBY
NP601
STAIR #1
NPS601
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:5
A
M
MD113
5TH LEVEL MECHANICAL DEMOLITION
PLAN - BUILDING 102
5 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
1 EXISTING INTAKE HOODS TO BE REMOVED.
CONTRACTOR TO INSTALL WIRE-MESH SCREENING
TO PROTECT OPENINGS DURING CONSTRUCTION.
Scale: 1/4" = 1'-0"
5TH LEVEL MECHANICAL DEMOLITION PLAN - BLDG 102
N O
R T H
0 2 4 8
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
1 SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8 SD-3
101-CU-4
STAIR #1
ELEV
101-1
ELEV
101-2
FUTURE ELEV
101-3
ELEVATOR LOBBY
SP101
SIGNAL
SP104
EMERGENCY ELEC
SP103
ELECTRICAL
SP102
T
101-EF-EX
101-EUH-EX
T 101-MCHP-1
6x6
6x6
6x6
6x6 50RR-01
50SD-01
6x6
101-ERV-1
101-LVR-EX
S
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:1
A
M
M-101
LOWER LEVEL MECHANICAL PLAN -
BUILDING 101
6 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
Scale: 1/4" = 1'-0"
LOWER LEVEL MECHAINCAL PLAN - BUILDING 101
N O
R T H
0 2 4 8
1 INSTALL NEW MINI-SPLIT SYSTEM UNIT TO PROVIDE
COOLING FOR THE NEW OFFICE SPACE.
2 INSTALL NEW OUTDOOR CONDENSING UNIT
MOUNTED APPROXIMATELY 4' ABOVE GARAGE
DECK.
3 EXISTING ELECTRIC UNIT HEATER TO REMAIN.
4 EXISTING EXHAUST FAN AND INTAKE LOUVER
SYSTEM TO REMAIN.
5 CONTROL EXHAUST FAN FROM NEW OCCUPANCY
SENSOR. SEE ELECTRICAL PLANS FOR
CONNECTION DETAILS.
6 INSTALL NEW ENERGY RECOVERY VENTILATOR TO
PRE-CONDITION OUTSIDE AIR ENTERING THE
SPACE.
7 INSTALL NEW RETURN AIR REGISTER.
8 INSTALL NEW SUPPLY AIR REGISTER.
9 INSTALL NEW DDC T-STAT TO CONTROL NEW
MINI-SPLIT HEAT PUMP.
SD-B
SD-A.9
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8
ELEVATOR LOBBY
SP601
STAIR #1
ELEV
101-2
ELEV
101-1
FUTURE ELEV
101-3
STAIR #1
UNASSIGNED
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:1
A
M
M-103
5TH LEVEL MECHANICAL PLAN -
BUILDING 101
7 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
KEY PLAN
SCALE: NO SCALE
BLUE
RED
1 INSTALL NEW OUTSIDE AIR INTAKE HOOD, AS
SHOWN, SEE ARCHITECTURAL DETAILS FOR
WATER-PROOFING & FLASHING REQUIREMENTS.
2 INSTALL NEW SHEET METAL ATOP EXISTING HOOD
SUPPORT STANCHIONS. NEW SHEET METAL TO
OVERHANG EXISTING SUPPORTS BY 12", ALL SIDES.
PAINT BOTTOM OF NEW SHEET METAL FLAT BLACK.
N O
R T H
0 2 4 8
Scale: 1/4" = 1'-0"
5TH LEVEL MECHANICAL PLAN - BLDG 101
SD-A
SD-AA
SD-CC
SD-DD
SD-EE
SD-.9 SD-1 SD-1.6 SD-2SD-1.9 SD-2.3 SD-2.7 SD-2.8
SD-3
101-HP-12
101-HP-2
101-HP-3
101-UH-1 4
ELEV MACHINE ROOM
SP701
STAIR #1
101-CU-1 5
101-CU-3
101-CU-2
T
T T T
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:2
A
M
M-104
NEW PENTHOUSE MECHANICAL PLAN -
BUILDING 101
8 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
Scale: 1/4" = 1'-0"
NEW PENTHOUSE MECHANICAL PLAN - BLDG 101
N O
R T H
0 2 4 8
1 NEW WALL LOUVERS SHALL BE INSTALLED TO
ACCOMMODATE NEW AIR INTAKE. SEE
ARCHITECTURAL DRAWINGS.
2 MOUNT NEW INDOOR MINI-SPLIT HEAT PUMP UNIT
HIGH ON WALL. LOCATE UNIT CLEAR OF
ELECTRICAL EQUIPMENT AND ELEVATOR
MACHINERY/ CONTROLS. ROUTE REFRIGERANT
PIPING DOWN THROUGH PENTHOUSE FLOOR AND
INTO THE PLENUM BELOW. CONNECT
REFRIGERANT PIPING TO OUTDOOR CONDENSING
UNIT. ROUTE AND HEAT TRACE CONDENSATE
FROM UNITS TO NEW PLENUM ROOF DRAIN.
3 NEW OUTDOOR CONDENSING UNIT MOUNTED ON
WALL RACK WITH BOTTOM AT 3 FEET ABOVE
EXISTING ROOF LEVEL.
4 NEW ELECTRIC UNIT HEATER SHALL BE INSTALLED
HIGH IN SPACE, HUNG FROM ROOF STRUCTURE.
5 INSTALL NEW DDC TEMPERATURE SENSOR AND
CONNECT TO BAS FOR SPACE TEMPERATURE
MONITORING/ALARM.
6 INSTALL NEW DDC TEMPERATURE CONTROL PANEL
ON WALL. COORDINATE EXACT LOCATION WITH
OTHER EQUIPMENT, PANELS, CONDUITS, PIPING,
AND STRUCTURE.
7 INSTALL NEW T-STAT TO CONTROL NEW MINI-SPLIT
HEAT PUMP UNIT.
ND-3 ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9 31
ND-CC
ND-BB
ND-AA
ND-A.9
ND-AL
ND-B
102-MCHP-1
102-CU-4
T
T
4 5
0SD-11
50RR-11
6x6 102-ERV-1
FUTURE ELEV
102-1
ELEV
102-2
ELEV
102-3
ELEVATOR LOBBY
NP101 ELECTRICAL
NP102
EMERGENCY ELEC
NP103
SIGNAL
NP104
STAIR #1
NPS101
102-LVR-EX
6x6
6x6
6x6
S
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:2
A
M
M-111
LOWER LEVEL MECHANICAL PLAN -
BUILDING 102
9 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
Scale: 1/4" = 1'-0"
LOWER LEVEL MECHANICAL PLAN - BLDG 102
N O
R T H
0 2 4 8
1 INSTALL NEW MINI-SPLIT SYSTEM UNIT TO PROVIDE
COOLING FOR THE NEW OFFICE SPACE.
2 INSTALL NEW OUTDOOR CONDENSING UNIT
MOUNTED APPROXIMATELY 4' ABOVE GARAGE
DECK.
3 EXISTING ELECTRIC UNIT HEATER TO REMAIN.
4 EXISTING EXHAUST FAN AND INTAKE LOUVER
SYSTEM TO REMAIN.
5 CONTROL EXHAUST FAN FROM NEW OCCUPANCY
SENSOR. SEE ELECTRICAL PLANS FOR CONNECTION
DETAILS.
6 INSTALL NEW ENERGY RECOVERY VENTILATOR TO
PRE-CONDITION OUTSIDE AIR ENTERING THE
SPACE.
7 INSTALL NEW RETURN AIR REGISTER.
8 INSTALL NEW SUPPLY AIR REGISTER.
9 INSTALL NEW DDC T-STAT TO CONTROL NEW
MINI-SPLIT HEAT PUMP.
ND-3
ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9 31
ND-DD
ND-CC
ND-BB
ND-AA
ND-A.9
ND-A
ND-B
ELEVATOR LOBBY
NP601
STAIR #1
ELEV
102-3
ELEV
102-2
FUTURE ELEV
102-1
STAIR #1
UNASSIGNED
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION4 08/23/2021
BID DOCUMENTS5 02/16/2022
/1
/2
:1
:2
A
M
M-113
5TH LEVEL MECHANICAL PLAN -
BUILDING 102
10 13WLF
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RHA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BLUE
RED
Scale: 1/4" = 1'-0"
5TH LEVEL MECHANICAL PLAN - BLDG 102
N O
R T H
0 2 4 8
1 EXISTING OUTSIDE AIR INTAKES TO REMAIN.
INSTALL NEW SHEET METAL ATOP EXISTING HOOD
SUPPORT STANCHIONS. NEW SHEET METAL TO
OVERHANG EXISTING SUPPORTS BY 12", ALL SIDES.
PAINT BOTTOM OF NEW SHEET METAL FLAT BLACK.
ND-3 ND-2.8 ND-2.7 ND-2.3 ND-2 ND-1.9 ND-1.8 ND-1.6 ND-1 ND-.9
ND-CC
ND-BB
ND-AA
ND-A.9
ND-A
ND-B
102-HP-1
102-CU-1
102-HP-3
102-HP-2
102-CU-2
102-CU-3
102-UH-14
STAIR #1
NPS701
ELEV MACHINE ROOM
NP701
T
T T T
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
35 % SCHEMATIC DESIGN SUBMISSION 1 12/23/2020
65% DESIGN DESIGN SUBMISSION 2 04/02/2021
65% DESIGN DEVELOPMENT RE-SUBMISSION3 05/28/2021
95%…