This document includes a pre-solicitation notice and technical drawings for a federal contract opportunity. The Department of Veterans Affairs intends to issue an Invitation for Bid to replace elevators in two parking structures at the John D. Dingell Veterans Medical Center in Detroit, Michigan. The pre-solicitation provides technical drawings depicting fire alarm system notes, device mounting heights, riser diagrams, and related details. The eventual IFB is expected to be released on September 9th, 2022 and will require contractors to furnish all labor, materials, equipment, and supervision to complete the elevator replacement project in accordance with the drawings and specifications. The work must be performed during normal daytime business hours excluding federal holidays. The NAICS code for this procurement is 238990 with a small business size standard of $16.5 million. The contract value is estimated between $5-10 million to be awarded as a firm fixed price contract within 120 days of bid opening. This opportunity is reserved as a 100% set-aside for Service-Disabled Veteran Owned Small Businesses registered in the Vendor Information Pages database. Prospective contractors must also register in the System for Award Management and have an active VETS-4212 report on file if applicable. All questions must be submitted in writing to the named contracting specialist.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM PULL STATION
SYMBOL HEIGHT DESCRIPTION
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD FIRE ALARM DUCT SMOKE DETECTOR
FIRE ALARM HEAT DETECTOR
42"-48"
90"
90"
90"
FIRE ALARM CONTROL PANEL
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
FLOW SWITCH
FACP
NAC
FAAP
TAMPER SWITCH
POST INDICATOR VALVEPIV
REMOTE LIGHT/TEST SWITCH FOR DUCT DETECTORS
F FIRE ALARM BELL90"
75 - CANDELA
75 - CANDELA
1 - WATTAGEF
S
F
S
HD
SD
WALL
CEILING
CEILING
CEILING
6'
6'
6'
6'
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP 6'
1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:
A. NFPA 13- STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
B. NFPA 14- STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM.
C. NFPA 20- STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION.
D. NFPA 70 NATIONAL ELECTRICAL CODE.
E. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.
F. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS.
G. NFPA 101 LIFE SAFETY CODE.
H. VA FIRE PROTECTION DESIGN MANUAL.
I. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.
2. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).
3. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.
4. BEFORE STARTING WORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
5. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.
6. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
7. CONTRACTOR TO PROVIDE AN ALLOWANCE IN THEIR BID TO REPAIR INCORRECT SYSTEM OPERATIONS.
8. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE ALARM DEVICES.
9. CONNECT SPRINKLER SYSTEM SUPERVISORY DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE LOCATION WITH THE
SPRINKLER CONTRACTOR.
10. CONNECT ALL ELECTROMAGNETIC DOOR HOLD OPEN DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE WITH THE
DOOR HARDWARE CONTRACTOR.
11. PROVIDE RELAY CONTROL MODULES FOR PACS, COORDINATE WITH PHYSICAL ACCESS CONTROL SYSTEM (PACS), CONTRACTOR.
12. PROVIDE RELAY CONTROL MODULES FOR COOKING POWER SUPPLY SHUT OFF.
13. PROVIDE RELAY CONTROL MODULES FOR KITCHEN HOOD FIRE SUPPRESSION SYSTEM.
14. THE OPERABLE PART OF A MANUAL ACTUATED ALARM INITIATING DEVICE SHALL BE NOT LESS THAN 42" (1.07M) AND NOT
MORE THEN 48" (1.22M) FROM FINISH FLOOR.
15. FOR LOCATION (CORRIDOR, ROOM OR ADJACENT SPACE) WITH TWO OR MORE VISIBLE FIRE ALARM NOTIFICATION APPLIANCES WITHIN THE FIELD OF VIEW, PROGRAM VISIBLE TO FLASH IN SYNCHRONIZATION.
16. REQUIRED 3 WEEK SHUT DOWN NOTICE TO BE GIVEN TO COR.
AFF ABOVE FINISH FLOOR
BOD BASIS OF DESIGN
COR CONTRACTING OFFICER REPRESENTATIVE
DN DOWN
DVC DIGITAL VOICE COMMAND
E EXISTING DEVICES
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
FO FIBER OPTIC
N NEW DEVICES
NAC NETWORK APPLIANCE CIRCUIT PANEL
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
UL UNDERWRITERS LABORATORY
CONDUIT
INSTALL PER
NATIONAL ELECTRIC CODE
AIR SUPPLY
DIFFUSER OR
RETURN AIR
OPENINGSMOKE/HEAT
DETECTORCEILING
FINISHED
FLOOR
NOTIFICATION DEVICE
(STROBE OR HORN/STROBE)
HORN SMOKE/HEAT
DETECTOR
CONTROL PANEL
GRAPHIC
ANNUNCIATOR
MANUAL PULL
STATION
15'-0" MAX 3'-0" MIN
6" MIN 4" MIN
1'-0" MAX
96" MAX
TOP OF
DEVICE
80" MIN
BOTTOM OF
DEVICE
5'-6"
3'-8"
(3'-6" MIN)
(4'-0" MAX)
5'-0" MAX
EXIT
JUNCTION BOX
(SEAL TIGHT
FLEX MAX 6')
CONDUIT
JUNCTION BOX
(SEAL TIGHT
FLEX MAX 6')
5"
DOOR
WIDTH
DOOR
HOLDER
15'-0" MAX
DETAIL NOTES:
A. MOUNT ALL AUDIBLE & VISUAL DEVICES IN APPROVED BOXES.
B. ALL ABOVE CEILING DEVICES TO BE MOUNTED IN ACCESSIBLE LOCATION.
NOTES:
1. FIRE ALARM SYSTEM SHALL BE INTERCONNECTED WITH ACCESS
CONTROL SYSTEM TO ALLOW EGRESS DURING ALARM CONDITIONS.
COORDINATE BETWEEN ACCESS CONTROL SYSTEM AND FIRE ALARM
SYSTEM MANUFACTURERS.
2. ALL FIRE ALARM WIRING SHALL BE IN FACTORY PAINTED "RED" EMT
CONDUIT.
3. ALL WIRING SHALL BE AS RECOMMENDED BY MANUFACTURER.
4. PROVIDE ELEVATOR RELAYS FOR EACH ELEVATOR.
a. PRIMARY RECALL.
b. ALTERATIVE RECALL.
c. EMERGENCY SHUNT.
d. EMERGENCY SHUNT POWER SUPERVISION.
e. IN CAB NOTIFICATIONS/FIRE FIGHTER.
5. PROVIDE POWER AMPLIFIERS FOR ALL SPEAKERS.
6. THE NEW FIRE ALARM SYSTEM SHALL MATCH THE EXISTING
SIMPLEX/TYCO FIRE ALARM SYSTEM
TO ADDITIONAL
INDICATING
APPLIANCES
NEW SIMPLEX
NOTIFICATION
APPLIANCE
CIRCUIT (NAC )
S S S
F F HDSDF
S
F
S
RRR
RR
EXISTING
SIMPLEX FIRE
ALARM
CONTROL
PANEL (FACP)
UP TO NEW ELEVATOR
PENTHOUSE
DOWN TO LOWER
LEVEL SIGNAL ROOM
SP104
HD
INTERFACE RELAYS INSTALL WITHIN 3' OF
ELEVATOR CONTROLLER
R1
EQL
R2
EQL
R3
EQL
SHUNT TRIP
BREAKER
R4
EQL
HOT NEUTRAL
120 VAC CIRCUIT
(POWER TO OPERATE
SHUNT TRIP BREAKER)
FROM EMERGENCY
POWER SOURCE
R5
EQL
FIRE ALARM CONTROL UNIT
SCC1 SCC2 SCC3 SCC4
ACTUARION
CAUSES
RECALL TO
ALTERNATE
LEVEL
ACTUARION
CAUSES
RECALL TO
DESIGNATED
LEVEL
ACTUARION
CAUSES
FLASHING
OF
WARNING
SIGNAL
ACTUARION
CAUSES
DISCONNECT
OF MAIN LINE
ELEVATOR
POWER
1DC1
(SUPERVISORY)
ACTUARION
CAUSES
SUPERVISORY
SIGNAL
CONVENTIONAL OR
ADDRESSABLE
ZONE / CIRCUIT
MODULE
HD
ELEVATOR
HOISTWAY HEAT
DETECTOR(S)
ELEVATOR
MACHINE ROOM
HEAT DETECTOR(S)
SD
ELEVATOR
HOISTWAY SMOKE
DETECTOR(S)
ELEVATOR MACHINE
ROOM SMOKE
DETECTOR(S)
SD SD
ELEVATOR LOBBY
SMOKE DETECTOR
5TH FLOOR
SD
ELEVATOR LOBBY
SMOKE DETECTOR
4TH FLOOR
SD
ELEVATOR LOBBY
SMOKE DETECTOR
3RD FLOOR
SD
ELEVATOR LOBBY
SMOKE DETECTOR
2ND FLOOR
(ALTERNATE LEVEL)
SD
ELEVATOR LOBBY
SMOKE DETECTOR
GROUND FLOOR
(DESIGNATED LEVEL)
SD
ELEVATOR LOBBY
SMOKE DETECTOR
LOWER LEVEL
NOTE:
1. FIRE ALARM CIRCUITS ARE TO BE SIGNED AND INSTALLED
IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM
CODE AND NEC 70, NATIONAL ELECTRICAL CODE
R1 SIGNAL TO ELEVATOR CONTROLLER FOR RECALL TO DESIGNATED LEVEL.
R2 SIGNAL TO ELEVATOR CONTROLLER TO RECALL TO ALTERNATE LEVEL.
R3 SIGNAL TO ELEVATOR CONTROLLER FOR RECALL TO ALTERNATE LEVEL.
R4 SIGNAL TO ACTIVATE SHUNT TRIP RELAY.
R5 SUPERVISORY RELAY TO MONITOR PRESENCE OF VOLTAGE (POWER) TO OPERATE SHUNT
TRIP BREAKER
SCC1 SUPERVISED CONTROL CIRCUIT FOR OPERATING R1.
SCC2 SUPERVISED CONTROL CIRCUIT FOR OPERATING R2.
SCC3 SUPERVISED CONTROL CIRCUIT FOR OPERATING R3.
SCC4 SUPERVISED CONTROL CIRCUIT FOR OPERATING R4.
IDC1 INITIATING DEVICE CIRCUIT TO SUPERVISE R5 CONTACTS (MONITORING POWER TO OPERATE
SHUNT TRIP BREAKER).
COMPONENT FUNCTION
NOTES:
1. FIRE ALARM SYSTEM SHALL BE INTERCONNECTED WITH ACCESS
CONTROL SYSTEM TO ALLOW EGRESS DURING ALARM CONDITIONS.
COORDINATE BETWEEN ACCESS CONTROL SYSTEM AND FIRE ALARM
SYSTEM MANUFACTURERS.
2. ALL FIRE ALARM WIRING SHALL BE IN FACTORY PAINTED "RED" EMT
CONDUIT.
3. ALL WIRING SHALL BE AS RECOMMENDED BY MANUFACTURER.
4. PROVIDE ELEVATOR RELAYS FOR EACH ELEVATOR.
a. PRIMARY RECALL.
b. ALTERATIVE RECALL.
c. EMERGENCY SHUNT.
d. EMERGENCY SHUNT POWER SUPERVISION.
e. IN CAB NOTIFICATIONS/FIRE FIGHTER.
5. PROVIDE POWER AMPLIFIERS FOR ALL SPEAKERS.
6. THE NEW FIRE ALARM SYSTEM SHALL MATCH THE EXISTING
SIMPLEX/TYCO FIRE ALARM SYSTEM
TO ADDITIONAL
INDICATING
APPLIANCES
NEW SIMPLEX
NOTIFICATION
APPLIANCE
CIRCUIT (NAC )
S S S
F F HDSDF
S
F
S
RRR
RR
EXISTING
SIMPLEX FIRE
ALARM
CONTROL
PANEL (FACP)
UP TO NEW ELEVATOR
PENTHOUSE
DOWN TO LOWER
LEVEL SIGNAL ROOM
NP104
FIRE EXTINGUISHER MONITORING SYSTEM
SOLE SOURCE: ENGAUGE
SOLE SOURCE SUPPLIER CONTACT INFORMATION
SIMPLEX JOHNSON CONTROLS AND VANGUARD APPROVED
PROVIDERS.
NOTE
CONTRACTOR SHALL HAVE ENGAUGE REPRESENTATIVE
MODIFY PROGRAMMING FOR ALL NEW COMPONENTS.
NEW 3/4" CONDUIT
NEW 3 - G BOX
NEW FIRE EXTINGUISHER
CABINET
1. VA TO PROVIDE THE FIRE
EXTINGUISHER.
2. VA TO PROVIDE THE
ENGAUGE MODULE.
3. VA TO PROVIDE THE CABLE
BETWEEN THE ENGAUGE
MODULE TO THE FIRE
EXTINGUISHER.
4. CONTRACTOR TO PROVIDE
NEW FIRE ALARM
EXTINGUISHIER CABINET AND
ALL OTHER ITEMS.
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
BRAND ITEM SPECIFICATION SECTION NOTES
HILTI FS1-FIRESTOP 07 84 00 BOTH SIDES OF FIRE-RATED WALLS, SMOKE BARRIERS, AND
FLOORS REGARDLESS OF FIRE RATING
DIVISION 08 - OPENINGS
BRAND ITEM SPECIFICATION SECTION NOTES
YALE LOCKS & DOOR HARDWARE 08 71 00 LARGE FORMAT 7-PIN REMOVABLE CORE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
BRAND ITEM SPECIFICATION SECTION NOTES
SIEMENS HVAC CONTROLS 23 09 23
SIEMENS BUILDING MANAGEMENT SYSTEM (BMS)
DIVISION 26 - ELECTRICAL
BRAND ITEM SPECIFICATION SECTION NOTES
SIEMENS ELECTRICAL 26 22 00
26 24 16 26 29 11 26 29 21 26 43 13
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
BRAND ITEM SPECIFICATION SECTION NOTES
SECURITY 2000 PHYSICAL SECURITY 28 13 00
28 23 00
SIMPLEX FIRE ALARM SYSTEM / VENDOR 28 31 00
EN-GAUGE EN-VISION OBSTRUCTION SENSOR 28 31 00 VA SUPPLIED / CONTRACTOR INSTALLED
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
JOHN D. DINGELL
VA MEDICAL
CENTER
/3 /2
:5
:2
P
M
FA001
FIRE ALARM GENERAL NOTES,
SYMBOL LEGEND, AND RISER
1 3EFJ
REPLACE/ADD PARKING
STRUCTURE ELEVATORS
VAMC DETROIT 4646 JOHN R. ST.
DETROIT, MI 48201
FEBRUARY 16, 2022
BID DOCUMENTS
553-19-10118-319
101 & 102
RSB
FIRE ALARM SYMBOL LEGEND
FIRE ALARM GENERAL NOTES
FIRE ALARM ABBREVIATIONS LIST
Scale: No Scale
FIRE ALARM DEVICE MOUNTING HEIGHTS
Scale: No Scale
FIRE ALARM RISER BUILDING 101
Scale: No Scale
FIRE ALARM INTERFACE WITH ELEVATORS
Scale: No Scale
FIRE ALARM RISER BUILDING 102
Scale: No Scale
FIRE EXTINGUSHER BACK BOX DIAGRAM (TYP.)
SOLE SOURCE LIST
1 ADDENDUM 01 11/30/2022