This file provides details on a cancelled federal contract opportunity for construction services. The Solicitation Number 36C77623B0049 was issued by the Department of Veterans Affairs Technology Acquisition Center Austin for a parking expansion project at the Joliet Community Based Outpatient Clinic. The opportunity was for construction work to expand parking capacity at the Joliet CBOC facility but has since been cancelled as indicated by the "Y" designation in the solicitation name. No information is provided on the specific requirements, response dates, or reasons for cancellation.
View the file
Other files
Show 40 more
Latest 50 of 57 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APD AIR PRESSURE DROP
BAS BUILDING AUTOMATION SYSTEM
BHP BRAKE HORSEPOWER
BLDG BUILDING
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
BYP BYPASS
CA COMBUSTION AIR
CAV CONSTANT AIR VOLUME
CFM CUBIC FEET PER MINUTE
CHW CHILLED WATER
CL CENTERLINE
CLG CEILING
CONC CONCRETE
COND CONDENSATE
COP COEFFICIENT OF PERFORMANCE
CNDW CONDENSER WATER
CPD CONDENSATE PUMP DISCHARGE
DB DRY BULB
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROL
DEG DEGREE
DP DIFFERENTIAL PRESSURE
DX DIRECT EXPANSION
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
ECON ECONOMIZER
EER ENERGY EFFICIENCY RATIO
EFF EFFICIENCY
EL ELEVATION
ELEC ELECTRIC/ELECTRONIC
ENGR ENGINEER
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EX EXISTING
EXH EXHAUST
EXP EXPANSION
FA FIELD ADJUSTABLE
FC FAIL CLOSED
FE FUME HOOD EXHAUST
FLA FULL LOAD AMPS
FLR FLOOR
FO FAIL OPEN
FOF FUEL OIL FILL
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FPI FINS PER INCH
FPM FEET PER MINUTE
FPS FEET PER SECOND
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GC GENERAL CONTRACTOR
GE GENERAL EXHAUST
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HHW HEATING HOT WATER
HOA HAND-OFF-AUTOMATIC
HP HORSE POWER
HPC HIGH PRESSURE CONDENSATE
HPS HIGH PRESSURE STEAM
HW HOT WATER
HZ HERTZ
IA INSTRUMENT AIR
KE KITCHEN EXHAUST
KEF KITCHEN EXHAUST FAN
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
LRA LOCKED ROTOR AMPS
LWT LEAVING WATER TEMPERATURE
MBH THOUSANDS OF BTU PER HOUR
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPS
MEP MECHANICAL, ELECTRICAL AND PIPING
MER MECHANICAL EQUIPMENT ROOM
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
NA NOT APPLICABLE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OV OUTLET VELOCITY
PC PLUMBING CONTRACTOR
PD PRESSURE DROP
PH PHASE
PP POLYPROPYLENE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
R RETURN
RA RETURN AIR
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
S SUPPLY
SA SUPPLY AIR
SCH SCHEDULE
SF SQUARE FOOT
SP STATIC PRESSURE
SS STAINLESS STEEL
TA TRANSFER AIR
TDH TOTAL DYNAMIC HEAD
TP TOTAL PRESSURE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UC UNDERCUT
UV ULTRAVIOLET
V VOLTS
VAV VARIABLE AIR VOLUME
VP VELOCITY PRESSURE
VTR VENT THRU ROOF
WB WET BULB
WC WATER COLUMN
WG WATER GAUGE
AO ANALOG OUTPUT (CONTROLS)
AI ANALOG INPUT (CONTROLS)
DI DIGITAL INPUT (CONTROLS)
DO DIGITAL OUTPUT (CONTROLS)
EQUIPMENT ABBREVIATIONS
AAV AUTOMATIC AIR VENT
AC AIR CONDITIONING
ACC AIR COOLED CONDENSER
ACCU AIR COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
AHU AIR HANDLING UNIT
CC COOLING COIL
CH CHILLER
CP CONDENSATE PUMP/CONTROL PANEL
CT COOLING TOWER
CUH CABINET UNIT HEATER
CV CONVERTOR
AS AIR SEPARATOR
AT AIR TERMINAL DEVICE
B BOILER
BBS BOILER BLOWDOWN SEPARATOR
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BFS BOILER FEEDWATER SYSTEM
BH BOOSTER HUMIDIFIER
D DAMPER
DOAS DEDICATED OUTDOOR AIR SYSTEM
EF EXHAUST FAN
EH EXHAUST HOOD
EBH ELECTRIC BASEBOARD HEATER
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EV EXHAUST VALVE
EVAP EVAPORATOR
F FILTER
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FD FLOOR DRAIN
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FPB FAN POWERED BOX
FT FLASH TANK
FTR FIN TUBE RADIATION
GEN GENERATOR
H HUMIDIFIER
HC HEATING COIL
HP HEAT PUMP
HRC HEAT RECOVERY COIL
HT HEAT TRACE
HX HEAT EXCHANGER
IH INTAKE HOOD
MAU MAKEUP AIR UNIT
MCC MOTOR CONTROL CENTER
P PUMP
PHC PREHEAT COIL
PRV PRESSURE REDUCING VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
RCP RADIANT CEILING PANEL
RF RETURN FAN
RH RELIEF HOOD
RHC REHEAT COIL
RTU ROOFTOP UNIT
SAD SOUND ATTENUATING DEVICE
SD SMOKE DETECTOR
SF SUPPLY FAN
SRV SAFETY RELIEF VALVE
ST STORAGE TANK
T TANK
UH UNIT HEATER
UV UNIT VENTILATOR
V VALVE
VAV VARIABLE AIR TERMINAL DEVICE
VFD VARIABLE FREQUENCY DRIVE
WCC WATER COOLED CONDENSER
WF WATER FILTER
DAMPERS AND ACTUATORS
MANUAL BALANCING DAMPER
CONTROL DAMPER (MOTORIZED)
M
BACKDRAFT DAMPER
BD
1 1/2 HOUR RATED FIRE DAMPER
F2
3 HOUR RATED FIRE DAMPER
F3
1 1/2 HOUR RATED FIRE/SMOKE DAMPER
FS
OPPOSED BLADE DAMPER
PARALLEL BLADE DAMPER
MANUAL ACTUATOR
MOTORIZED ACTUATOR
M
SOLENOID ACTUATOR
S
DUCT SYMBOLS
SUPPLY DIFFUSER ANNOTATION
DUCT SIZE (INCHES)
∅ INDICATES ROUND
SUPPLY AIR
DUCT (SA)
AIR QUANTITY
(CFM)
SUPPLY
DIFFUSERS (S)
EXISTING
S-1
4508"Ø SA
RETURN/EXHAUST GRILLE ANNOTATION
RETURN AIR DUCT
(RA)
DUCT SIZES
IN INCHES
AIR QUANTITY
(CFM)
RETURN
GRILLE (R)
EXISTING
R-1
25010x10 RA
EXHAUST AIR DUCT
(EA)
DUCT SIZES
IN INCHES
AIR QUANTITY
(CFM)
EXHAUST
GRILLE (E)
EXISTING
E-1
25010"Ø EA
(X)SNEW
(X)RNEW
(X)EEXISTING
DUCTWORK
SINGLE LINE
EXISTING DUCT TO BE REMOVED
DOUBLE LINE
EXISTING DUCT TO REMAIN
FLOW DIRECTION DESIGNATION
DUCT CONTINUATION BREAK
SUPPLY AIR (SA) OR
OUTDOOR AIR (OA) DUCT
EXHAUST AIR (EA) DUCT
RETURN AIR (RA), RELIEF AIR,
OR TRANSFER AIR (TA) DUCT
GENERAL SYMBOLS
EQUIPMENT TAG
KEYNOTE
POINT OF NEW CONNECTION TO EXISTING
WHEN ON DEMO SHEET: END POINT OF DEMO
DETAIL REFERENCE (TOP=DETAIL NUMBER,
BOTTOM=DRAWING NUMBER)
M-1
PLAN CONTINUATION REFERENCE
(BOTTOM=DRAWING NUMBER)
REFER
M-1
SECTION DESIGNATION (TOP=SECTION
NUMBER, BOTTOM=DRAWING NUMBER)
M-1
PIPING
SINGLE LINE
EXISTING PIPING TO BE REMOVED
DOUBLE LINE
EXISTING PIPING TO REMAIN
FLOW DIRECTION DESIGNATION
PIPE CONTINUATION BREAK
ELBOW DOWN
ELBOW UP
BOTTOM CONNECTION
TOP CONNECTION
PIPE TEE
PIPING ANNOTATION
CHILLED WATER SUPPLY/RETURNCHWS/R
CONDENSER WATER SUPPLY/RETURNCWS/R
HEATING HOT WATER SUPPLY/RETURNHWS/R
HEAT RECLAIM WATER SUPPLY/RETURNHRWS/R
LOW PRESSURE STEAM (<15 PSI)LPS
LOW PRESSURE CONDENSATELPC
HIGH PRESSURE STEAM (XX=PRESSURE)HPS (XX)
HIGH PRESSURE COND. (XX=PRESSURE)HPC (XX)
PROCESS CHILLED WATER SUPPLY/RETURNPCHWS/R
REFRIGERANT LIQUIDRL
REFRIGERANT SUCTIONRS
NATURAL GASNG
PIPING SPECIALTIES
GENERAL PIPELINE STRAINER WITHOUT DRAIN
GENERAL PIPELINE STRAINER WITH DRAIN
BASKET STRAINER
FLANGE
UNION
CAP
THERMOMETER
PRESSURE GAUGE
MANUAL AIR VENT
TEST PORT (PRESSURE/TEMP.)
PIPING VALVES
BUTTERFLY VALVE
GATE VALVE
GLOBE VALVE
BALL VALVE
BALANCING VALVE
AUTO FLOW BALANCING VALVE
CHECK VALVE
SOLENOID VALVE
S
STEAM PRESSURE REDUCING VALVE (PRV)
2-WAY CONTROL VALVE
3-WAY MIXING VALVE
3-WAY DIVERTING VALVE
DRAIN VALVE WITH CAP
GAS PRESSURE REGULATOR
GAS SHUTOFF VALVE
REDUCED PRESSURE
BACKFLOW PREVENTER (RPP)
PRESSURE RELIEF VALVE (RV)
OR SAFETY VALVE (SV)
VACUUM RELIEF/VACUUM BREAKER
GENERAL MECHANICAL NOTES
1. THE CONTRACTORS WORK SHALL CONFORM TO ALL VA
POLICIES ON CONSTRUCTION PROCEDURES AND SHALL
COMPLY WITH ALL LOCAL CODES AND VA STANDARDS.
2. COORDINATE WITH THE VA FOR ANY EQUIPMENT
REMOVED THAT NEEDS TO BE RETURNED TO THE
OWNER.
3. COORDINATE WITH VA FOR TEMPORARY SYSTEM
SHUTDOWN PER REQUIREMENTS IN THE
SPECIFICATIONS.
4. ALL DUCTWORK SHALL BE FABRICATED OF SHEET METAL
IN ACCORDANCE WITH SMACNA STANDARDS.
5. RE-INSULATE AND PATCH EXISTING DUCTWORK AS
REQUIRED AFTER INSTALLATION OF NEW DUCTWORK OR
OTHER DEMOLITION THAT DISTURBS EXISTING
DUCTWORK AND INSULATION.
6. PROVIDE LOCKING TYPE BALANCING DAMPER AT EACH
DIFFUSER, GRILLE, AND BRANCH TAKE-OFF IN ALL
SUPPLY, RETURN, AND EXHAUST DUCTWORK. LOCATE
BALANCING DAMPER AS CLOSE TO THE BRANCH
TAKEOFF AS POSSIBLE.
7. DUCT SIZE TO DIFFUSERS, REGISTERS, AND GRILLES
SHALL BE SAME AS NECK SIZE UNLESS OTHERWISE
NOTED.
8. DUCT SIZE TO AIR TERMINAL DEVICES SHALL BE SAME AS
INLET SIZE UNLESS OTHERWISE NOTED.
9. COORDINATE DIFFUSER, REGISTER, AND GRILLE
LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING
PLAN AND ALL OTHER CEILING DEVICES.
10. PROVIDE FLEXIBLE DUCTWORK FOR DIFFUSERS,
REGISTERS, AND GRILLES. FLEXIBLE DUCT SIZE SHALL BE
SAME AS NECK SIZE OF DIFFUSER OR GRILLE AND SHALL
HAVE MAXIMUM LENGTH OF 5'-0". REFER TO
SPECIFICATIONS FOR REQUIREMENTS.
11. LOCATE AIR TERMINAL DEVICES TO ALLOW ACCESS TO
AIR TERMINAL DEVICE CONTROLLERS. ACCESS
CLEARANCE IS SHOWN ON PLANS.
12. ALL EXISTING STEAM AND CONDENSATE PIPING IN THE
BUILDING WILL BE OBSOLETE AS A RESULT OF THIS
PROJECT AND IS REQUIRED TO BE REMOVED
COMPLETELY. NO ABANDONED STEAM OR CONDENSATE
PIPING WILL BE ALLOWED.
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:1
P M
M001
MECHANICAL SYMBOLS AND
ABBREVIATIONS
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPTHEP
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
ISSUED FOR 100% CD 03/07/2023
ISSUED FOR BID 03/24/2023
Dx
Ex
Gx
Hx
Jx
Kx
K'x
Lx
1x 4x 6x 9x 12x 13x 14x
Cx
Bx
Ax
3x 5x 5.8x 8x 10x6.1x
Fx
A.E
15x
15y
15z 15aa
15bb
15cc
15dd
15ee
15ff
15gg15hh
15ii
9.5x1.2x
A
1 2
B
AHU-1
EXIST.
AHU-2
EXIST.
AHU-3
EXIST.
AHU-4
EXIST.
T
T
EXISTING STEAM
RADIATION TO BE REMOVED
T
T
T
T
TT
T
T T
2 2 2
EXISTING EF-4
TO BE REMOVED
LOCATION OF
EXISTING BAS
CONTROL PANELS
AND JACE
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
N
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:3
P M
MD100-N
BASEMENT LEVEL -
MECHANICAL DEMOLITION PLAN
- NORTH
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPEPEP
1/8" = 1'-0"
1 BASEMENT LEVEL - MECHANICAL DEMOLITION PLAN - NORTH
0 4' 8' 16'
MECHANICAL DEMOLITION KEYNOTES
NUMBER KEYNOTE
1 EXISTING DDC THERMOSTAT/SENSOR TO BE REMOVED.
2 EXISTING AIR TERMINAL UNIT INCLUDING STEAM REHEAT COIL
AND ACCESSORIES TO BE REMOVED AS SHOWN. IF APPLICABLE,
LEAVE DUCTWORK CONNECTIONS FOR INSTALLATION OF NEW
VAV TERMINAL UNITS.
3 REMOVE EXISTING AIR HANDLING UNIT INCLUDING ALL
ASSOCIATED PIPING, ACCESSORIES, AND DUCTWORK
CONNECTIONS TO BOTH AHU AND ASSOCIATED RETURN/EXHAUST
FAN. REMOVE OUTDOOR AIR DUCTWORK BACK TO AREA WELL
AND CAP OPENING.
4 REMOVE EXISTING CHILLED WATER PUMP, ACCESSORIES, AND
ASSOCIATED PIPING TO ROOF MOUNTED CHILLERS.
5 REMOVE ALL EXISTING DUCTWORK AS SHOWN ON PLANS. THIS
SHALL INCLUDE HANGERS AND OTHER ACCESSORIES RELATED TO
THE DUCTWORK SYSTEM.
6 EXISTING STEAM UNIT HEATER TO BE REMOVED INCLUDING
ASSOCIATED THERMOSTAT, STEAM AND CONDENSATE PIPING
BACK TO MAINS, AND ANY ACCESSORIES AND HANGERS.
7 ALL BOOSTER COILS, DUCTWORK AND ASSOCIATED
GRILLES/DIFFUSERS ORIGIONATING FROM THIS DUCT RISER TO BE
REMOVED, INCLUDING TSTATS
8 REMOVE EXISTING STEAM CONDENSATE RECEIVER AND PUMP
SYSTEM.
9 REMOVE EXISTING STEAM BOILER INCLUDING STEAM AND
FEEDWATER PIPING, CONTROLS, FLUE THROUGH ROOF, AND ALL
OTHER ACCESSORIES AND STEAM/CONDENSATE PIPING IN BOILER
PLANT.
10 REMOVE EXISTING BOILER FEEDWATER UNIT INCLUDING PIPING
TO BOILERS, CONTROLS, AND OTHER ACCESSORIES. LEAVE
MAKEUP WATER CONNECTION AT DISCHARGE OF RPZ FOR
EXTENSION TO NEW GLYCOL FILL SYSTEM BY MECHANICAL
CONTRACTOR.
11 REMOVE EXISTING ROOF EXHAUST FAN AND PATCH ROOF
OPENING.
12 REMOVE EXISTING CHILLED WATER PIPING FROM CHILLERS DOWN
TO BASEMENT PUMPS. PATCH ROOF OPENINGS AFTER
DEMOLITION OF PIPES.
13 REMOVE EXISTING RELIEF AIR DUCT IN BASEMENT UP TO FLOOR
LEVEL OF FIRST FLOOR AND CAP BASE OF DUCT. SEE MH101-S
FOR NEW WORK SCOPE FOR THIS DUCT.
IMPORTANT PIPING DEMOLITION NOTES TO
CONTRACTOR:
THIS BUILDING HAS AN EXISTING SYSTEM OF
STEAM PIPING AND CONDENSATE RETURN
THAT SERVES AIR HANDLING UNITS, AIR
TERMINAL REHEAT COILS AND OTHER
HEATING DEVICES THROUGHOUT THE ENTIRE
BUILDING.
THIS STEAM AND CONDENSATE SYSTEM SHALL
REMAIN ACTIVE DURING PORTIONS OF THE
PROJECT AS DEFINED BY THE PHASING PLANS
TO SERVE BUILDING HEATING AND
VENTILATION NEEDS WHILE THE NEW HEATING
SYSTEM IS BEING INSTALLED AND
COMMISSIONED.
THE END RESULT OF THIS PROJECT IS THAT
ALL EXISTING STEAM AND CONDENSATE
PIPING, AS WELL AS ASSOCIATED
ACCESSORIES AND EQUIPMENT, WILL BE
REMOVED FROM THE BUILDING ENTIRELY
AFTER THE NEW HEATING HOT WATER BOILER
PLANT IS FULLY OPERATIONAL AND
COMMISSIONED.
ONCE THE STEAM AND CONDENSATE PIPING
ARE NO LONGER NECESSARY IN AN AREA,
THEY SHALL BE DEMOLISHED COMPLETELY IN
SEQUENCE WITH THE OVERALL
CONSTRUCTION SCHEDULE. ABANDONED
PIPING OR ASSOCIATED ITEMS IS NOT
ACCEPTABLE AND CONTRACTOR WILL BE
REQUIRED TO INCLUDE IN THEIR BID A
COMPLETE DEMOLITION SCOPE OF ALL SUCH
PIPING AND ASSOCIATED ITEMS FROM THE
BUILDING, WHETHER EXPLICITLY SHOWN ON
DRAWINGS OR NOT.
IMPORTANT VENTILATION DEMOLITION NOTES TO CONTRACTOR:
THE DEMOLITION INTENT OF THIS PROJECT IS FOR THE REMOVAL OF EXISTING
BASEMENT AIR HANDLING UNITS, ASSOCIATED RETURN/EXHAUST FANS,
DUCTWORK ASSOCIATED WITH DEMOLISHED EQUIPMENT AND PORTIONS OF THE
EXISTING DUCTWORK (AS SHOWN ON PLANS), DIFFUSERS, AIR TERMINAL UNITS,
BOOSTER COILS, CONTROLS, AND ASSOCIATED DUCTWORK HANGERS AND
ACCESSORIES, IN SEQUENCE WITH THE PHASING OF THE WORK AS DEFINED BY
PHASING PLANS AND THE PROPOSED SCHEDULE.
NOT ALL DUCTWORK OR DEVICES THAT ARE TO BE REMOVED ARE SHOWN ON
THIS SHEET IN THEIR ENTIRETY, HOWEVER THIS DOES NOT ABSOLVE
CONTRACTOR OF COMPLETING THE REQUIRED SCOPE OF WORK AS DESCRIBED
ABOVE. NO DUCTWORK OR ASSOCIATED ITEMS SHALL REMAIN ABANDONED IN
PLACE BY COMPLETION OF PROJECT.
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
F
F
F2
F2
F
F
F2
1x 4x 6x 9x 12x 13x 14x
Ax
A1x
B1x
C1x
D1x
E1x
3x 5x
A.E
15x1.2x
AHU-7
EXIST.
AHU-6
EXIST.
AHU-5
EXIST.
T
T
T
T
T
T T
T
T
T
2 2
18x14 EA
18x10 RA
48x22 RA
30x18 SA
32x24 SA x S
A x E
A
T
T
T
T T
T
1 1
T
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
S
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:4
P M
MD100-S
BASEMENT LEVEL -
MECHANICAL DEMOLITION PLAN
- SOUTH
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPEPEP
1/8" = 1'-0"
1 BASEMENT LEVEL - MECHANICAL DEMOLITION PLAN - SOUTH
0 4' 8' 16'
MECHANICAL DEMOLITION KEYNOTES
NUMBER KEYNOTE
1 EXISTING DDC THERMOSTAT/SENSOR TO BE REMOVED.
2 EXISTING AIR TERMINAL UNIT INCLUDING STEAM REHEAT COIL
AND ACCESSORIES TO BE REMOVED AS SHOWN. IF APPLICABLE,
LEAVE DUCTWORK CONNECTIONS FOR INSTALLATION OF NEW
VAV TERMINAL UNITS.
3 REMOVE EXISTING AIR HANDLING UNIT INCLUDING ALL
ASSOCIATED PIPING, ACCESSORIES, AND DUCTWORK
CONNECTIONS TO BOTH AHU AND ASSOCIATED RETURN/EXHAUST
FAN. REMOVE OUTDOOR AIR DUCTWORK BACK TO AREA WELL
AND CAP OPENING.
4 REMOVE EXISTING CHILLED WATER PUMP, ACCESSORIES, AND
ASSOCIATED PIPING TO ROOF MOUNTED CHILLERS.
5 REMOVE ALL EXISTING DUCTWORK AS SHOWN ON PLANS. THIS
SHALL INCLUDE HANGERS AND OTHER ACCESSORIES RELATED TO
THE DUCTWORK SYSTEM.
6 EXISTING STEAM UNIT HEATER TO BE REMOVED INCLUDING
ASSOCIATED THERMOSTAT, STEAM AND CONDENSATE PIPING
BACK TO MAINS, AND ANY ACCESSORIES AND HANGERS.
7 ALL BOOSTER COILS, DUCTWORK AND ASSOCIATED
GRILLES/DIFFUSERS ORIGIONATING FROM THIS DUCT RISER TO BE
REMOVED, INCLUDING TSTATS
8 REMOVE EXISTING STEAM CONDENSATE RECEIVER AND PUMP
SYSTEM.
9 REMOVE EXISTING STEAM BOILER INCLUDING STEAM AND
FEEDWATER PIPING, CONTROLS, FLUE THROUGH ROOF, AND ALL
OTHER ACCESSORIES AND STEAM/CONDENSATE PIPING IN BOILER
PLANT.
10 REMOVE EXISTING BOILER FEEDWATER UNIT INCLUDING PIPING
TO BOILERS, CONTROLS, AND OTHER ACCESSORIES. LEAVE
MAKEUP WATER CONNECTION AT DISCHARGE OF RPZ FOR
EXTENSION TO NEW GLYCOL FILL SYSTEM BY MECHANICAL
CONTRACTOR.
11 REMOVE EXISTING ROOF EXHAUST FAN AND PATCH ROOF
OPENING.
12 REMOVE EXISTING CHILLED WATER PIPING FROM CHILLERS DOWN
TO BASEMENT PUMPS. PATCH ROOF OPENINGS AFTER
DEMOLITION OF PIPES.
13 REMOVE EXISTING RELIEF AIR DUCT IN BASEMENT UP TO FLOOR
LEVEL OF FIRST FLOOR AND CAP BASE OF DUCT. SEE MH101-S
FOR NEW WORK SCOPE FOR THIS DUCT.
IMPORTANT DEMOLITION NOTES TO
CONTRACTOR:
THIS BUILDING HAS AN EXISTING SYSTEM OF
STEAM PIPING AND CONDENSATE RETURN
THAT SERVES AIR HANDLING UNITS, AIR
TERMINAL REHEAT COILS AND OTHER
HEATING DEVICES THROUGHOUT THE ENTIRE
BUILDING.
THIS STEAM AND CONDENSATE SYSTEM SHALL
REMAIN ACTIVE DURING PORTIONS OF THE
PROJECT AS DEFINED BY THE PHASING PLANS
TO SERVE BUILDING HEATING AND
VENTILATION NEEDS WHILE THE NEW HEATING
SYSTEM IS BEING INSTALLED AND
COMMISSIONED.
THE END RESULT OF THIS PROJECT IS THAT
ALL EXISTING STEAM AND CONDENSATE
PIPING, AS WELL AS ASSOCIATED
ACCESSORIES AND EQUIPMENT, WILL BE
REMOVED FROM THE BUILDING ENTIRELY
AFTER THE NEW HEATING HOT WATER BOILER
PLANT IS FULLY OPERATIONAL AND
COMMISSIONED.
ONCE THE STEAM AND CONDENSATE PIPING
ARE NO LONGER NECESSARY IN AN AREA,
THEY SHALL BE DEMOLISHED COMPLETELY IN
SEQUENCE WITH THE OVERALL
CONSTRUCTION SCHEDULE. ABANDONED
PIPING OR ASSOCIATED ITEMS IS NOT
ACCEPTABLE AND CONTRACTOR WILL BE
REQUIRED TO INCLUDE IN THEIR BID A
COMPLETE DEMOLITION SCOPE OF ALL SUCH
PIPING AND ASSOCIATED ITEMS FROM THE
BUILDING, WHETHER EXPLICITLY SHOWN ON
DRAWINGS OR NOT.
IMPORTANT VENTILATION DEMOLITION NOTES TO CONTRACTOR:
THE DEMOLITION INTENT OF THIS PROJECT IS FOR THE REMOVAL OF EXISTING
BASEMENT AIR HANDLING UNITS, ASSOCIATED RETURN/EXHAUST FANS,
DUCTWORK ASSOCIATED WITH DEMOLISHED EQUIPMENT AND PORTIONS OF THE
EXISTING DUCTWORK (AS SHOWN ON PLANS), DIFFUSERS, AIR TERMINAL UNITS,
BOOSTER COILS, CONTROLS, AND ASSOCIATED DUCTWORK HANGERS AND
ACCESSORIES, IN SEQUENCE WITH THE PHASING OF THE WORK AS DEFINED BY
PHASING PLANS AND THE PROPOSED SCHEDULE.
EXHAUST SYSTEMS FOR TOILET ROOMS, SOILED HOLDING, ETC. ARE
CONSIDERED EXISTING TO REMAIN AND SHALL NOT BE DEMOLISHED.
NOT ALL DUCTWORK OR DEVICES THAT ARE TO BE REMOVED ARE SHOWN ON
THIS SHEET IN THEIR ENTIRETY, HOWEVER THIS DOES NOT ABSOLVE
CONTRACTOR OF COMPLETING THE REQUIRED SCOPE OF WORK AS DESCRIBED
ABOVE. NO DUCTWORK OR ASSOCIATED ITEMS SHALL REMAIN ABANDONED IN
PLACE BY COMPLETION OF PROJECT.
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
F2
Ex
Gx
Hx
Jx
Kx
K'x
Lx
1x 4x 6x 9x 12x 13x 14x
Cx
Bx
Ax
3x 5x 5.8x 8x 10x6.1x
Fx
A.E
15x
15y
15z 15aa
15bb
15cc
15dd
15ee
15ff
15gg15hh
15ii
9.5x1.2x
A
1 2
B
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
TT
T T
T
T
T
T
T T
T
EXISTING GRILLES SERVING
AUDITORY AND CONTROL
ROOMS TO REMAIN (TYP)
9 9 910
1 1
EXISTING PACKAGED HVAC
UNIT TO REMAIN TO SERVE
BOILER PLANT
EXISTING PACKAGED HVAC
UNIT TO REMAIN TO SERVE
BOILER PLANT
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
N
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:5
P M
MD101-N
FIRST FLOOR - MECHANICAL
DEMOLITION PLAN - NORTH
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPBBEP
1/8" = 1'-0"
1 FIRST FLOOR - MECHANICAL DEMOLITION PLAN - NORTH
0 4' 8' 16'
MECHANICAL DEMOLITION KEYNOTES
NUMBER KEYNOTE
1 EXISTING DDC THERMOSTAT/SENSOR TO BE REMOVED.
2 EXISTING AIR TERMINAL UNIT INCLUDING STEAM REHEAT COIL
AND ACCESSORIES TO BE REMOVED AS SHOWN. IF APPLICABLE,
LEAVE DUCTWORK CONNECTIONS FOR INSTALLATION OF NEW
VAV TERMINAL UNITS.
3 REMOVE EXISTING AIR HANDLING UNIT INCLUDING ALL
ASSOCIATED PIPING, ACCESSORIES, AND DUCTWORK
CONNECTIONS TO BOTH AHU AND ASSOCIATED RETURN/EXHAUST
FAN. REMOVE OUTDOOR AIR DUCTWORK BACK TO AREA WELL
AND CAP OPENING.
4 REMOVE EXISTING CHILLED WATER PUMP, ACCESSORIES, AND
ASSOCIATED PIPING TO ROOF MOUNTED CHILLERS.
5 REMOVE ALL EXISTING DUCTWORK AS SHOWN ON PLANS. THIS
SHALL INCLUDE HANGERS AND OTHER ACCESSORIES RELATED TO
THE DUCTWORK SYSTEM.
6 EXISTING STEAM UNIT HEATER TO BE REMOVED INCLUDING
ASSOCIATED THERMOSTAT, STEAM AND CONDENSATE PIPING
BACK TO MAINS, AND ANY ACCESSORIES AND HANGERS.
7 ALL BOOSTER COILS, DUCTWORK AND ASSOCIATED
GRILLES/DIFFUSERS ORIGIONATING FROM THIS DUCT RISER TO BE
REMOVED, INCLUDING TSTATS
8 REMOVE EXISTING STEAM CONDENSATE RECEIVER AND PUMP
SYSTEM.
9 REMOVE EXISTING STEAM BOILER INCLUDING STEAM AND
FEEDWATER PIPING, CONTROLS, FLUE THROUGH ROOF, AND ALL
OTHER ACCESSORIES AND STEAM/CONDENSATE PIPING IN BOILER
PLANT.
10 REMOVE EXISTING BOILER FEEDWATER UNIT INCLUDING PIPING
TO BOILERS, CONTROLS, AND OTHER ACCESSORIES. LEAVE
MAKEUP WATER CONNECTION AT DISCHARGE OF RPZ FOR
EXTENSION TO NEW GLYCOL FILL SYSTEM BY MECHANICAL
CONTRACTOR.
11 REMOVE EXISTING ROOF EXHAUST FAN AND PATCH ROOF
OPENING.
12 REMOVE EXISTING CHILLED WATER PIPING FROM CHILLERS DOWN
TO BASEMENT PUMPS. PATCH ROOF OPENINGS AFTER
DEMOLITION OF PIPES.
13 REMOVE EXISTING RELIEF AIR DUCT IN BASEMENT UP TO FLOOR
LEVEL OF FIRST FLOOR AND CAP BASE OF DUCT. SEE MH101-S
FOR NEW WORK SCOPE FOR THIS DUCT.
IMPORTANT PIPING DEMOLITION NOTES TO
CONTRACTOR:
THIS BUILDING HAS AN EXISTING SYSTEM OF
STEAM PIPING AND CONDENSATE RETURN
THAT SERVES AIR HANDLING UNITS, AIR
TERMINAL REHEAT COILS AND OTHER
HEATING DEVICES THROUGHOUT THE ENTIRE
BUILDING.
THIS STEAM AND CONDENSATE SYSTEM SHALL
REMAIN ACTIVE DURING PORTIONS OF THE
PROJECT AS DEFINED BY THE PHASING PLANS
TO SERVE BUILDING HEATING AND
VENTILATION NEEDS WHILE THE NEW HEATING
SYSTEM IS BEING INSTALLED AND
COMMISSIONED.
THE END RESULT OF THIS PROJECT IS THAT
ALL EXISTING STEAM AND CONDENSATE
PIPING, AS WELL AS ASSOCIATED
ACCESSORIES AND EQUIPMENT, WILL BE
REMOVED FROM THE BUILDING ENTIRELY
AFTER THE NEW HEATING HOT WATER BOILER
PLANT IS FULLY OPERATIONAL AND
COMMISSIONED.
ONCE THE STEAM AND CONDENSATE PIPING
ARE NO LONGER NECESSARY IN AN AREA,
THEY SHALL BE DEMOLISHED COMPLETELY IN
SEQUENCE WITH THE OVERALL
CONSTRUCTION SCHEDULE. ABANDONED
PIPING OR ASSOCIATED ITEMS IS NOT
ACCEPTABLE AND CONTRACTOR WILL BE
REQUIRED TO INCLUDE IN THEIR BID A
COMPLETE DEMOLITION SCOPE OF ALL SUCH
PIPING AND ASSOCIATED ITEMS FROM THE
BUILDING, WHETHER EXPLICITLY SHOWN ON
DRAWINGS OR NOT.
IMPORTANT VENTILATION DEMOLITION NOTES TO CONTRACTOR:
THE INTENT OF THIS PROJECT FOR THE NORTH HALF OF THE FIRST FLOOR (AREA
SHOWN BY THIS SHEET) IS FOR ALL SUPPLY AND RETURN DUCTWORK, DIFFUSERS,
BOOSTER COILS, CONTROLS, AND ASSOCIATED DUCTWORK HANGERS AND
ACCESSORIES TO BE REMOVED ENTIRELY, IN SEQUENCE WITH THE PHASING OF THE
WORK AS DEFINED BY PHASING PLANS AND THE PROPOSED SCHEDULE.
THE ONLY SYSTEMS THAT ARE EXISTING TO REMAIN IN THE NORTH HALF OF THE
BUILDING ARE EXHAUST SYSTEMS FOR TOILET ROOMS AND SOILED HOLDING.
NOT ALL DUCTWORK OR DEVICES THAT ARE TO BE REMOVED ARE SHOWN ON THIS
SHEET IN THEIR ENTIRETY, HOWEVER THIS DOES NOT ABSOLVE CONTRACTOR OF
COMPLETING THE REQUIRED SCOPE OF WORK AS DESCRIBED ABOVE. NO SUPPLY OR
RETURN DUCTWORK OR ASSOCIATED ITEMS SHALL REMAIN ABANDONED IN PLACE BY
COMPLETION OF PROJECT.
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
ISSUED FOR 100% CD 03/07/2023
ISSSUED FOR BID ADDENDUM 1 04/21/2023
1x 4x 6x 9x 12x 13x 14x
Bx
Ax
A1x
B1x
C1x
D1x
E1x
3x 5x
A.E
15x1.2x
T
T
T
T
T
T
T
T
T
T
T T T T
T T
T
T
TTT T
T
T
T
T
T T
T
T
T
T
T
T T
T
T T
T
T
T
T
T
T
T
1 1 15
1 1
1 1
5 5 5
2 2
2 2
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
S
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:0
P M
MD101-S
FIRST FLOOR - MECHANICAL
DEMOLITION PLAN - SOUTH
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPTHEP
1/8" = 1'-0"
1 FIRST FLOOR - MECHANICAL DEMOLITION PLAN - SOUTH
0 4' 8' 16'
MECHANICAL DEMOLITION KEYNOTES
NUMBER KEYNOTE
1 EXISTING DDC THERMOSTAT/SENSOR TO BE REMOVED.
2 EXISTING AIR TERMINAL UNIT INCLUDING STEAM REHEAT COIL
AND ACCESSORIES TO BE REMOVED AS SHOWN. IF APPLICABLE,
LEAVE DUCTWORK CONNECTIONS FOR INSTALLATION OF NEW
VAV TERMINAL UNITS.
3 REMOVE EXISTING AIR HANDLING UNIT INCLUDING ALL
ASSOCIATED PIPING, ACCESSORIES, AND DUCTWORK
CONNECTIONS TO BOTH AHU AND ASSOCIATED RETURN/EXHAUST
FAN. REMOVE OUTDOOR AIR DUCTWORK BACK TO AREA WELL
AND CAP OPENING.
4 REMOVE EXISTING CHILLED WATER PUMP, ACCESSORIES, AND
ASSOCIATED PIPING TO ROOF MOUNTED CHILLERS.
5 REMOVE ALL EXISTING DUCTWORK AS SHOWN ON PLANS. THIS
SHALL INCLUDE HANGERS AND OTHER ACCESSORIES RELATED TO
THE DUCTWORK SYSTEM.
6 EXISTING STEAM UNIT HEATER TO BE REMOVED INCLUDING
ASSOCIATED THERMOSTAT, STEAM AND CONDENSATE PIPING
BACK TO MAINS, AND ANY ACCESSORIES AND HANGERS.
7 ALL BOOSTER COILS, DUCTWORK AND ASSOCIATED
GRILLES/DIFFUSERS ORIGIONATING FROM THIS DUCT RISER TO BE
REMOVED, INCLUDING TSTATS
8 REMOVE EXISTING STEAM CONDENSATE RECEIVER AND PUMP
SYSTEM.
9 REMOVE EXISTING STEAM BOILER INCLUDING STEAM AND
FEEDWATER PIPING, CONTROLS, FLUE THROUGH ROOF, AND ALL
OTHER ACCESSORIES AND STEAM/CONDENSATE PIPING IN BOILER
PLANT.
10 REMOVE EXISTING BOILER FEEDWATER UNIT INCLUDING PIPING
TO BOILERS, CONTROLS, AND OTHER ACCESSORIES. LEAVE
MAKEUP WATER CONNECTION AT DISCHARGE OF RPZ FOR
EXTENSION TO NEW GLYCOL FILL SYSTEM BY MECHANICAL
CONTRACTOR.
11 REMOVE EXISTING ROOF EXHAUST FAN AND PATCH ROOF
OPENING.
12 REMOVE EXISTING CHILLED WATER PIPING FROM CHILLERS DOWN
TO BASEMENT PUMPS. PATCH ROOF OPENINGS AFTER
DEMOLITION OF PIPES.
13 REMOVE EXISTING RELIEF AIR DUCT IN BASEMENT UP TO FLOOR
LEVEL OF FIRST FLOOR AND CAP BASE OF DUCT. SEE MH101-S
FOR NEW WORK SCOPE FOR THIS DUCT.
IMPORTANT DEMOLITION NOTES TO
CONTRACTOR:
THIS BUILDING HAS AN EXISTING SYSTEM OF
STEAM PIPING AND CONDENSATE RETURN
THAT SERVES AIR HANDLING UNITS, AIR
TERMINAL REHEAT COILS AND OTHER
HEATING DEVICES THROUGHOUT THE ENTIRE
BUILDING.
THIS STEAM AND CONDENSATE SYSTEM SHALL
REMAIN ACTIVE DURING PORTIONS OF THE
PROJECT AS DEFINED BY THE PHASING PLANS
TO SERVE BUILDING HEATING AND
VENTILATION NEEDS WHILE THE NEW HEATING
SYSTEM IS BEING INSTALLED AND
COMMISSIONED.
THE END RESULT OF THIS PROJECT IS THAT
ALL EXISTING STEAM AND CONDENSATE
PIPING, AS WELL AS ASSOCIATED
ACCESSORIES AND EQUIPMENT, WILL BE
REMOVED FROM THE BUILDING ENTIRELY
AFTER THE NEW HEATING HOT WATER BOILER
PLANT IS FULLY OPERATIONAL AND
COMMISSIONED.
ONCE THE STEAM AND CONDENSATE PIPING
ARE NO LONGER NECESSARY IN AN AREA,
THEY SHALL BE DEMOLISHED COMPLETELY IN
SEQUENCE WITH THE OVERALL
CONSTRUCTION SCHEDULE. ABANDONED
PIPING OR ASSOCIATED ITEMS IS NOT
ACCEPTABLE AND CONTRACTOR WILL BE
REQUIRED TO INCLUDE IN THEIR BID A
COMPLETE DEMOLITION SCOPE OF ALL SUCH
PIPING AND ASSOCIATED ITEMS FROM THE
BUILDING, WHETHER EXPLICITLY SHOWN ON
DRAWINGS OR NOT.
IMPORTANT VENTILATION DEMOLITION
NOTES TO CONTRACTOR:
THE INTENT OF THIS PROJECT FOR THE
SOUTH HALF OF THE FIRST FLOOR (AREA
SHOWN BY THIS SHEET) IS TO RETAIN A
MAJORITY OF THE EXISTING DUCTWORK
AND DIFFUSERS (OTHER THAN THOSE
SHOWN TO BE DEMOLISHED ON THIS
SHEET) WHILE REMOVING AND REPLACING
THE EXISTING AIR TERMINAL UNITS AND
ASSOCIATED CONTROLS, IN SEQUENCE
WITH THE PHASING OF THE WORK AS
DEFINED BY PHASING PLANS AND THE
PROPOSED SCHEDULE.
THE NEW AIR TERMINAL UNITS WITH HOT
WATER REHEAT ARE INTENDED TO
REPLACE EXISTING AIR TERMINAL UNITS
WITH STEAM REHEAT IN GENERALLY THE
SAME LOCATION UNLESS PLANS SHOW
OTHERWISE.
THE EXISTING DUCT RISERS FROM THE
BASEMENT ARE BEING REMOVED AS PART
OF THE PROJECT AND NEW DUCTWORK
MAINS FROM THE ROOF ARE BEING
PROVIDED TO CONNECT TO EXISTING
DUCT MAINS JUST OUTSIDE THE EXISTING
SHAFT AS SHOWN.
EXHAUST SYSTEMS FOR TOILET ROOMS,
SOILED HOLDING, ETC. ARE CONSIDERED
EXISTING TO REMAIN AND SHALL NOT BE
DEMOLISHED.
NOT ALL DUCTWORK OR DEVICES THAT
ARE TO BE REMOVED ARE SHOWN ON THIS
SHEET IN THEIR ENTIRETY, HOWEVER THIS
DOES NOT ABSOLVE CONTRACTOR OF
COMPLETING THE REQUIRED SCOPE OF
WORK AS DESCRIBED ABOVE. NO
DUCTWORK OR ASSOCIATED ITEMS SHALL
REMAIN ABANDONED IN PLACE BY
COMPLETION OF PROJECT.
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
Gx
Hx
Jx
Kx
K'x
Lx
1x 4x 6x 9x 12x 13x 14x
Cx
Bx
Ax
3x 5x 5.8x 8x 10x6.1x
Fx
A.E
15x
15y
15z 15aa
15bb
15cc
15dd
15ee
15ff
15gg15hh
15ii
9.5x1.2x
A
1 2
B
EXISTING
EXHAUST FAN
EXISTING
EXHAUST FAN
EXISTING
EXHAUST FAN
EXISTING
EXHAUST FAN
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
N
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:1
P M
MD102-N
ROOF NORTH - MECHANICAL
DEMOLITION PLAN
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPTHEP
1/8" = 1'-0"
1 ROOF - MECHANICAL DEMOLITON PLAN - NORTH
0 4' 8' 16'
MECHANICAL DEMOLITION KEYNOTES
NUMBER KEYNOTE
1 EXISTING DDC THERMOSTAT/SENSOR TO BE REMOVED.
2 EXISTING AIR TERMINAL UNIT INCLUDING STEAM REHEAT COIL
AND ACCESSORIES TO BE REMOVED AS SHOWN. IF APPLICABLE,
LEAVE DUCTWORK CONNECTIONS FOR INSTALLATION OF NEW
VAV TERMINAL UNITS.
3 REMOVE EXISTING AIR HANDLING UNIT INCLUDING ALL
ASSOCIATED PIPING, ACCESSORIES, AND DUCTWORK
CONNECTIONS TO BOTH AHU AND ASSOCIATED RETURN/EXHAUST
FAN. REMOVE OUTDOOR AIR DUCTWORK BACK TO AREA WELL
AND CAP OPENING.
4 REMOVE EXISTING CHILLED WATER PUMP, ACCESSORIES, AND
ASSOCIATED PIPING TO ROOF MOUNTED CHILLERS.
5 REMOVE ALL EXISTING DUCTWORK AS SHOWN ON PLANS. THIS
SHALL INCLUDE HANGERS AND OTHER ACCESSORIES RELATED TO
THE DUCTWORK SYSTEM.
6 EXISTING STEAM UNIT HEATER TO BE REMOVED INCLUDING
ASSOCIATED THERMOSTAT, STEAM AND CONDENSATE PIPING
BACK TO MAINS, AND ANY ACCESSORIES AND HANGERS.
7 ALL BOOSTER COILS, DUCTWORK AND ASSOCIATED
GRILLES/DIFFUSERS ORIGIONATING FROM THIS DUCT RISER TO BE
REMOVED, INCLUDING TSTATS
8 REMOVE EXISTING STEAM CONDENSATE RECEIVER AND PUMP
SYSTEM.
9 REMOVE EXISTING STEAM BOILER INCLUDING STEAM AND
FEEDWATER PIPING, CONTROLS, FLUE THROUGH ROOF, AND ALL
OTHER ACCESSORIES AND STEAM/CONDENSATE PIPING IN BOILER
PLANT.
10 REMOVE EXISTING BOILER FEEDWATER UNIT INCLUDING PIPING
TO BOILERS, CONTROLS, AND OTHER ACCESSORIES. LEAVE
MAKEUP WATER CONNECTION AT DISCHARGE OF RPZ FOR
EXTENSION TO NEW GLYCOL FILL SYSTEM BY MECHANICAL
CONTRACTOR.
11 REMOVE EXISTING ROOF EXHAUST FAN AND PATCH ROOF
OPENING.
12 REMOVE EXISTING CHILLED WATER PIPING FROM CHILLERS DOWN
TO BASEMENT PUMPS. PATCH ROOF OPENINGS AFTER
DEMOLITION OF PIPES.
13 REMOVE EXISTING RELIEF AIR DUCT IN BASEMENT UP TO FLOOR
LEVEL OF FIRST FLOOR AND CAP BASE OF DUCT. SEE MH101-S
FOR NEW WORK SCOPE FOR THIS DUCT.
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
1x 4x 6x 9x 12x 13x 14x
Bx
Ax
A1x
B1x
C1x
D1x
E1x
3x 5x
A.E
15x1.2x
EXISTING IT ROOM
AC CONDENSING
UNIT TO REMAIN
EXISTING AIR
COOLED CHILLER
TO REMAIN
EXISTING EXHAUST FAN
EXISTING EXHAUST FAN
EXISTING EXHAUST FAN
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
S
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:1
P M
MD102-S
ROOF SOUTH - MECHANICAL
DEMOLITION PLAN
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPTHEP
0 4' 8' 16'
1/8" = 1'-0"
1 ROOF - MECHANICAL DEMOLITON PLAN - SOUTH
MECHANICAL DEMOLITION KEYNOTES
NUMBER KEYNOTE
1 EXISTING DDC THERMOSTAT/SENSOR TO BE REMOVED.
2 EXISTING AIR TERMINAL UNIT INCLUDING STEAM REHEAT COIL
AND ACCESSORIES TO BE REMOVED AS SHOWN. IF APPLICABLE,
LEAVE DUCTWORK CONNECTIONS FOR INSTALLATION OF NEW
VAV TERMINAL UNITS.
3 REMOVE EXISTING AIR HANDLING UNIT INCLUDING ALL
ASSOCIATED PIPING, ACCESSORIES, AND DUCTWORK
CONNECTIONS TO BOTH AHU AND ASSOCIATED RETURN/EXHAUST
FAN. REMOVE OUTDOOR AIR DUCTWORK BACK TO AREA WELL
AND CAP OPENING.
4 REMOVE EXISTING CHILLED WATER PUMP, ACCESSORIES, AND
ASSOCIATED PIPING TO ROOF MOUNTED CHILLERS.
5 REMOVE ALL EXISTING DUCTWORK AS SHOWN ON PLANS. THIS
SHALL INCLUDE HANGERS AND OTHER ACCESSORIES RELATED TO
THE DUCTWORK SYSTEM.
6 EXISTING STEAM UNIT HEATER TO BE REMOVED INCLUDING
ASSOCIATED THERMOSTAT, STEAM AND CONDENSATE PIPING
BACK TO MAINS, AND ANY ACCESSORIES AND HANGERS.
7 ALL BOOSTER COILS, DUCTWORK AND ASSOCIATED
GRILLES/DIFFUSERS ORIGIONATING FROM THIS DUCT RISER TO BE
REMOVED, INCLUDING TSTATS
8 REMOVE EXISTING STEAM CONDENSATE RECEIVER AND PUMP
SYSTEM.
9 REMOVE EXISTING STEAM BOILER INCLUDING STEAM AND
FEEDWATER PIPING, CONTROLS, FLUE THROUGH ROOF, AND ALL
OTHER ACCESSORIES AND STEAM/CONDENSATE PIPING IN BOILER
PLANT.
10 REMOVE EXISTING BOILER FEEDWATER UNIT INCLUDING PIPING
TO BOILERS, CONTROLS, AND OTHER ACCESSORIES. LEAVE
MAKEUP WATER CONNECTION AT DISCHARGE OF RPZ FOR
EXTENSION TO NEW GLYCOL FILL SYSTEM BY MECHANICAL
CONTRACTOR.
11 REMOVE EXISTING ROOF EXHAUST FAN AND PATCH ROOF
OPENING.
12 REMOVE EXISTING CHILLED WATER PIPING FROM CHILLERS DOWN
TO BASEMENT PUMPS. PATCH ROOF OPENINGS AFTER
DEMOLITION OF PIPES.
13 REMOVE EXISTING RELIEF AIR DUCT IN BASEMENT UP TO FLOOR
LEVEL OF FIRST FLOOR AND CAP BASE OF DUCT. SEE MH101-S
FOR NEW WORK SCOPE FOR THIS DUCT.
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
F2
F
F
F2
F
F2F2
F2
Elev. Equip.
B003
Badge
B004
Phone
B002C
Home Based Primary
Care
B002
Stair #2
S-2
Comm.
B005
Reception
B001
Women's Restroom
B006
Men's Restroom
B011
HAC
B007
Copy Room
B009
Phone
B002A
Phone
B002B
Phone
B017
Phone
B016
A.O.
B015
Clinical Nurse Manager
B014
Chief Medical Director
B013
Patient Education/Group
Room
B011
Patient
Education/Exercise
B022
Store
B012
Corridor
C0-2
Corridor
C0-3
Corridor
C0-4
Corridor
C0-1
Mech.
B018
Elec.
B019
Gen Room
B020
PAS Call Center
B024
Education Storage
B022
Nutrition Services
B021
Main Conference Room
B023
Mech.
B025
Elevator
EL-1
New North Vestibule
Elec.
B026B
Lobby
Storage
002A
S-1
200 CFM
S-1
100 CFM
CUH
12x10 SA
VAV
Dx
Ex
Gx
Hx
Jx
Kx
K'x
Lx
1x 4x 6x 9x 12x 13x 14x
Cx
Bx
Ax
3x 5x 5.8x 8x 10x6.1x
Fx
A.E
15x
15y
15z 15aa
15bb
15cc
15dd
15ee
15ff
15gg15hh
15ii
9.5x1.2x
A
1 2
B
UH
003A
UH
B003
UH
B018A
UH
B018B
UH
B019
UH
B020
Mach. Room
003A
Elevator-2
E-2-2
T
VAV
B015
T
T
VAV
B013
VAV
B002
T
VAV
B001
T
T
T
T
T
T
T
E-1
350 CFM
E-1
300 CFM
S-1
250 CFM
S-1
200 CFM
S-1
315 CFM
S-1
315 CFM
(X)S
150 CFM
(X)S
150 CFM
(X)S
150 CFM
(X)S
50 CFM
(X)R
50 CFM
R-1
450 CFM
(X)S
50 CFM
S-1
50 CFM(X)S
50 CFM
(X)S
75 CFM
(X)S
90 CFM
(X)S
125 CFM
(X)S
50 CFM
(X)R
75 CFM
(X)R
90 CFM
(X)R
50 CFM
x R
A
28x14 SA x S
A
26x14 SA x R
A
22x14 SA
28x12 RA
S-3
260 CFM8x8 SA x S
A x S
A
T
T
T
T
T
TT
VAV
B022D
VAV
B022C
VAV
B011B
VAV
B011A
VAV
B022A
VAV
B022B
26x14 RA
(X)R
50 CFM
(X)R
50 CFM
(X)R
50 CFM
(X)S
125 CFM
(X)S
125 CFM
(X)S
125 CFM
(X)S
125 CFM
(X)R
250 CFM
(X)R
250 CFM
(X)S
200 CFM
(X)S
200 CFM
(X)R
400 CFM
(X)S
200 CFM
(X)S
200 CFM
(X)S
200 CFM
(X)R
400 CFM
(X)S
200 CFM
(X)S
200 CFM
(X)S
200 CFM
(X)R
400 CFM
(X)R
125 CFM
R-1
450 CFM
(X)R
400 CFM
12x10 SA
20x10 SA
S-3
800 CFM
S-3
800 CFM
VAV
C0-1
VAV
B023A
VAV
B023B
16x12 SA
16x12 SA
T
T
(X)S
175 CFM
(X)S
175 CFM
(X)S
150 CFM
(X)S
175 CFM
(X)R
200 CFM
(X)S
200 CFM
(X)S
100 CFM
(X)R
100 CFM
(X)S
150 CFM (X)S
175 CFM
(X)S
175 CFM
(X)S
125 CFM
(X)S
175 CFM
(X)S
175 CFM
(X)S
175 CFM
(X)S
175 CFM
(X)R
667 CFM (X)R
667 CFM
(X)R
667 CFM
(X)S
150 CFM
TYP. 8
FT
S-2 T
R-3
700 CFM
TYP. 4
x S
A x S
A
S-3
350 CFM
S-3
350 CFM
S-3
350 CFM
S-3
350 CFM
S-3
350 CFM
S-3
350 CFM
S-3
350 CFM
S-3
350 CFM
VAV
B018A
VAV
B018B
T
T
S-3
250 CFM
VAV
B003
S-3
250 CFM
12x8 SA
VAV
B003A x S
A
12x10 RA 12x10 RA
R-1
600 CFM
R-1
600 CFM
28x14 SA 28x12 RA
26x14 RA
36x16 RA
26x14 SA
SD
SD
SD
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
N
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:2
P M
MH100-N
BASEMENT LEVEL -
MECHANICAL VENTILATION
PLAN - NORTH
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPTHEP
1/8" = 1'-0"
1 BASEMENT LEVEL - MECHANICAL VENTILATION PLAN - NORTH
0 4' 8' 16'
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
ISSUED FOR 100% CD 03/07/2023
F
F2
F2
F2
F2
F
F
F2
F2
F2
F2
F2
F2 F2
F2
Mech.
B025
Patient Education/Group
Room
B033
Patient Education/Group
Room
B032
Patient Ed/Internet Cafe
B031
Corridor
C0-6
Corridor
C0-8
Corridor
C0-7
Room
B042
Men's Staff Locker
B036
Women's Staff Locker
B034
Mech.
Corridor
C0-9
Corridor
B047
Mech.
B026 Elec.
B029
Elec.
B028
Comm
B030
Facility Storage
B041
EMS
B038
Biomed
B039
FMS
B040
Stair #1
S-1
1x 4x 6x 9x 12x 13x 14x
Ax
A1x
B1x
C1x
D1x
E1x
3x 5x
A.E
15x1.2x
CUH
S-1
T
T
T
T
T T
T
T
VAV
B038
VAV
B040
VAV
B039
VAV
B041A
VAV
B041C
VAV
B041B
S-3
380 CFM
S-3
380 CFM
S-3
370 CFM
S-3
370 CFM
S-3
370 CFM
S-3
370 CFM
(X)S
225 CFM
(X)S
225 CFM
(X)S
255 CFM
(X)R
255 CFM
(X)R
450 CFM
(X)S
175 CFM
(X)S
200 CFM
(X)S
200 CFM
(X)R
575 CFM
T
T
T
VAV
B034
VAV
B042
VAV
B036
(X)S
210 CFM
(X)S
215 CFM
(X)S
210 CFM
R-1
635 CFM(X)S
225 CFM
(X)S
225 CFM
(X)E
450 CFM
(X)E
150 CFM
(X)E
100 CFM
(X)E
150 CFM
(X)E
780 CFM (X)S
390 CFM
(X)S
390 CFM
24x24 SA
VAV
B026A
T T
T
(X)S
115 CFM
(X)S
120 CFM
(X)S
120 CFM
(X)S
120 CFM
(X)R
475 CFM
VAV
B032
VAV
B033
(X)S
100 CFM
(X)S
100 CFM
(X)S
105 CFM
(X)S
105 CFM
(X)S
135 CFM
(X)S
135 CFM
(X)R
270 CFM
VAV
B031
VAV
B028A
VAV
B028B
VAV
C0-6
T
(X)S
110 CFM
(X)S
105 CFM S-1
105 CFM
x S
A x R
A x R
A
T
T
(X)R
405 CFM
24x12 SA x S
A x S
A
S-3
555 CFM
S-3
555 CFM
S-3
555 CFM
S-3
555 CFM
S-3
450 CFM
S-3
450 CFM
S-3
445 CFM
S-3
445 CFM
20x12 SA x S
A x S
A
VAV
B026B
TT
S-3
800 CFM
S-3
800 CFM
S-1
125 CFM
S-1
125 CFM
S-1
125 CFM
8x8 SA
6x6 SA
VAV
B047
T
(X)R
667 CFM (X)R
667 CFM
(X)R
667 CFM
(X)S
200 CFM
(X)S
200 CFM
(X)S
110 CFM
x S
A 12x10 SA
VAV
C0-8
PROPOSED LOCATION
OF NEW JACE FOR
CONTROL SYSTEM
R-3
560 CFM
R-3
560 CFM
R-3
560 CFM
R-3
560 CFM
18x10 RA
18x10 RA R-3
710 CFM
R-3
700 CFM
R-3
650 CFM
R-3
650 CFM
R-3
650 CFM
R-3
650 CFM
R-3
800 CFM
R-3
800 CFM
30x22 RA
30x22 RA
30x22 SA
26x18 RA x R
A
18x10 RA
48x22 RA x R
A
26x24 SA
30x20 RA
12x10 SA
SD
SD
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
S
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:3
P M
MH100-S
BASEMENT LEVEL -
MECHANICAL VENTILATION
PLAN - SOUTH
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPTHEP
1/8" = 1'-0"
1 BASEMENT LEVEL - MECHANICAL VENTILATION PLAN - SOUTH
0 4' 8' 16'
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
ISSUED FOR 100% CD 03/07/2023
F
F
F
F 2 F
F
F
F
F
F2
F2 F2
F2F2
F2F2
F2
Boiler Plant
Sound Booth
Control
Sound Booth
FMS
Elevator
EL-1 EXISTING STAIR
S-2
Corridor
C1-15
Rad Control
Dispensary
Storage
1116A
Diagnostic
Marco
Rad Room
Corridor
C1-13
Corridor
C1-15A
Corridor
C1-11
Toilet
Toilet
HAC
Toilet
1112E
Soiled Utility
1112A Storage
1112B
PM&R
Treatment
1112D
Eye Tech
Visual Fields
Treatment
1112C
Toilet
Toilet
1102A
Eye
Blood Draw
1114D
Eye
Blood Draw
1114C
Draw Analysis
1114E
Toilet
1114F
Blood Draw
1114B
Eye
Eye
Women Health Exam 21
Women Health Exam 20
Mobile Port Waiting
Toilet
1068A
Toilet
1031A
Pharm. D
Pharm. D
Nutritionist
Teleretinal
Cardio/Pod Shared
Office
Soiled Utility
Clean Utility
Social Worker
Shell Space
Corridor
C1-10
Podiatry Exam
Podiatry Exam
Tech Work Room
Audiology Exam
Cast Room
Podiatry Exam
Audiology Exam
Oxygen Evaluation
Pulminary Fuction
Arterial Blood Gas
Clean Utility
Soiled Utility
Control
Stor.
Corridor
C1-12
Corridor
C1-9 Corridor
Ambulance Bay
C1-36
Corridor
C1-8--
1065B
Elec. Clos.
1089A
Scale Alcove
PAS
Elec.
1114 --
1114A
Lobby
Elevator-1
E-2-1
Office
Vestibule
Dx
Ex
Gx
Hx
Jx
Kx
K'x
Lx
1x 4x 6x 9x 12x 13x 14x
Cx
Bx
Ax
3x 5x 5.8x 8x 10x6.1x
Fx
A.E
15x
15y
15z 15aa
15bb
15cc
15dd
15ee
15ff
15gg15hh
15ii
9.5x1.2x
A
1 2
B
B
B
B
T
30x16 SA x S
A x S
A x S
A
20x12 SA x S
A
28x16 SA 26x14 SA x S
A x S
A
S-1
135 CFM
S-1
135 CFM
S-1
140 CFM
S-1
135 CFM
VAV
1114E
S-1
135 CFMS-1
135 CFMS-1
135 CFM
S-1
135 CFM
VAV
1114D
S-1
130 CFM
VAV
S-1
160 CFM
VAV
C1-11B S-1
195 CFM
S-1
195 CFM
S-1
160 CFM
S-1
150 CFM
10x10 SA
VAV
S-1
80 CFM
S-1
85 CFM
S-1
140 CFM
S-1
110 CFM
VAV
S-1
165 CFM
S-1
275 CFM
VAV
S-1
105 CFM
S-1
120 CFM
S-1
165 CFM
S-1
110 CFM
VAV
S-1
230 CFM
S-1
225 CFM
VAV
C1-15B
S-1
180 CFM
VAV
S-1
180 CFM
S-1
180 CFM
S-1
180 CFM
S-1
180 CFM
S-1
180 CFM
x S
A x S
A x S
A
S-1
55 CFM
S-1
75 CFM
VAV
S-1
195 CFM
S-1
130 CFM
VAV
C1-15A
S-1
130 CFM
S-1
130 CFM
VAV
1112D
S-1
135 CFM
S-1
210 CFM
S-1
135 CFM
S-1
140 CFM
14x10 SA x S
A
VAV
C1-11A
S-1
145 CFM
S-1
100 CFM
S-1
145 CFM
10x10 SA x S
A x S
A
12x10 SA
VAV
VAV
S-1
145 CFM
S-1
145 CFM
S-1
130 CFM
S-1
130 CFM
VAV
VAV
C1-15
S-1
155 CFM
S-1
230 CFM S-1
45 CFM
S-1
200 CFM
S-1
200 CFM
VAV
S-1
135 CFM
S-1
135 CFM
S-1
100 CFM
VAV
S-1
140 CFM
S-1
250 CFM
10x10 SA x S
A
8x8 SA x S
A x S
A 8 x S
A x S
A x S
A
8x6 SA10x8 SA8x8 SA
12x10 SA x S
A
8x8 SA x S
A
12x10 SA x S
A x S
A
12x10 SA x S
A x S
A x S
A 10x10 SA10x8 SA8x8 SA
12x10 SA
10x10 SA8x8 SA x S
A x S
A
10x10 SA
VAV
1077S-1
110 CFM
S-1
105 CFM
S-1
200 CFM
10x10 SA8x8 SA
S-1
150 CFM
12x10 SA
S-1
140 CFM
x S
A
S-1
140 CFM
S-1
95 CFM
VAV
S-1
165 CFM
S-1
170 CFM
S-1
125 CFM
S-1
125 CFM
x S
A x S
A x S
A
VAV
C1-10
S-1
210 CFM
T
T
T
TT
T
T
T
T
T
T
T
T
VAV
T
T
T
T
T
T
T
T
T
R-1
410 CFM
R-1
405 CFM
R-1
135 CFM
R-1
135 CFM
R-1
160 CFM
R-1
130 CFM
R-1
150 CFM
R-1
390 CFM
R-1
250 CFM
R-1
165 CFM
R-1
220 CFM
R-1
140 CFM
R-1
85 CFM
R-1
95 CFM
R-1
125 CFM
10x8 RA
R-1
140 CFM
R-1
150 CFM
R-1
140 CFM
R-1
170 CFM
12x10 RA
R-1
165 CFM
R-1
435 CFM
R-1
125 CFM
R-1
455 CFM
CUH
R-1
310 CFM R-1
120 CFM
R-1
165 CFM
R-1
105 CFM
R-1
80 CFM
R-1
290 CFM
R-1
160 CFM
R-1
135 CFM
R-1
210 CFM
x R
A
R-1
105 CFM
28x12 RA 38x14 RA
18x12 RA x R
A
CUH
R-1
100 CFM R-1
250 CFM
R-1
140 CFM
R-1
200 CFM
14x10 RA 10x10 RA
R-1
270 CFM
R-1
200 CFM
R-1
230 CFM
12x10 RA 14x10 RA
R-1
155 CFM
R-1
45 CFM R-1
165 CFM
R-1
290 CFM
R-1
390 CFM
R-1
195 CFM
R-1
160 CFM
R-1
160 CFM
R-1
165 CFM
R-1
260 CFM
R-1
140 CFM
R-1
135 CFM
R-1
55 CFM
R-1
555 CFM
(TYP OF 2)
26x16 RA x R
A
10x8 RA x R
A
34x14 RA
T
S-1
255 CFM S-1
135 CFM
x S
A6x6 SA 6x6 SA
S-1
60 CFM
(X)S
160 CFM
S-4
50 CFM
S-4
50 CFM
S-4
50 CFM
S-4
75 CFM
S-4
50 CFM
S-4
50 CFM
10x8 SA x S
A
S-4
50 CFM
S-4
75 CFM
S-4
50 CFM
S-4
50 CFM
S-4
50 CFM
S-4
50 CFM
10x8 SA x S
A x S
A
(X)E
75 CFM
EXISTING PACKAGED HVAC
UNIT TO REMAIN TO SERVE
BOILER PLANT
EXISTING PACKAGED HVAC
UNIT TO REMAIN TO SERVE
BOILER PLANT
EF
14x14 SA
VAV
C1-36A
VAV
C1-36B
S-2
50 CFM
R-1
100 CFM
UP TO
EXISTING
EF
S-3
1160 CFM
S-3
1160 CFM
(X)E
70 CFM
(X)E
70 CFM
(X)E
70 CFM
(X)E
70 CFM
(X)E
70 CFM
T
T
GMU
18x14 SA
ET
AS
P
HW-1
P
HW-2
P
HW-3
8x8 SA
6x6 SA
UP TO
EXISTING
EF
(X)E
100 CFM
T
(X)S
50 CFM
(X)S
50 CFM
(X)S
50 CFM
(X)S
50 CFM
x R
A
18x10 RA
18x12 RA
24x12 RA
14x10 RA x R
A
26x14 RA DN 36x24 RA UP
26x14 SA DN 36x20 SA UP
28x12 RA DN 36x22 RA UP
12x12 RA10x10 RA
16x12 SA26x16 SA DN 36x20 SA UP
36x16 RA DN 40x20 RA UP
28x14 SA DN 36x24 SA UP
8ø SA
SD
SD
SD
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
N
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:3
:4
P M
MH101-N
FIRST FLOOR - MECHANICAL
VENTILATION PLAN - NORTH
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPBBEP
1/8" = 1'-0"
1 FIRST FLOOR - MECHANICAL VENTILATION PLAN - NORTH
0 4' 8' 16'
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
ISSUED FOR 100% CD 03/07/2023
F2
F2
F
F
F2
Blood Draw
1114B
Eye
Eye
1-On-1 Room
1017C
Work Room
1017B
Supervisor Office
1017A Nurse Triage
Exam 1
Exam 2
Nurse Triage
Women Health Exam 3
IT-1
1014-1
Telemed
Telemed
Closet
Telemed
1009Telemed
Toilet
1043A
Telemed
Telemed
Exam 17
Exam 16
PACT 2
PACT 1
Exam 15
Exam 14
Exam 12
Exam 13
Exam 5
Women Health Exam 4
Toilet
1045 Toilet
1047A
Men's Restroom
Women's Restroom
Treatment Room
Toilet
Treatment Room
CWT
CWT
Security
Wheelchair Storage
Group Treatment
Treatment Room
Group Treatment
Treatment Room
Treatment Room
Treatment Room
Treatment Room
Soiled Utility
Exam 6
Exam 7
Exam 8
Exam 9
Clean Storage
Room
B131
Exam10
Procedure 1 Shared
Gyno
Toilet
1059B Toilet
Closet
1059A
Procedure 2
Exam 11
Exam 19
1066 Exam 18
PACT
PACT 4
Women Health Exam 21
Women Health Exam 20
Corridor
C1-3
Telemed
HAC
Stair #1
S-1
Mobile Port Waiting
Toilet
1068A
Toilet
1031A
Pharm. D
Social Worker
Corridor
C1-5
Corridor
C1-7
Corridor
C1-6
Corridor
C1-4
Corridor
C1-8
Corridor
C1-1
General Waiting
Corridor
C1-2
Photo Alcove
Reception
Equipment Alcove
Nourishment Alcove
Scale Alcove
1040 Meds
1065C
1065B
1065A
1114 --
1114A
1x 4x
6x 9x 12x 13x 14x
Bx
Ax
A1x
B1x
C1x
D1x
E1x
3x 5x
A.E
15x
1.2x
IT
T
T
T
T
T
T
T
T
T T T
T T
T
T
TTTT
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
S-1
135 CFMS-1
135 CFMS-1
135 CFM
S-1
150 CFMS-1
85 CFM
S-1
140 CFMS-1
165 CFM
T
T
CUH
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
C1-6
VAV
VAV
C1-5
VAV
VAV
1017C
VAV
1017A
VAV
1003N
VAV
1003S
VAV
VAV
C1-2
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
1065B
VAV
VAV
VAV
VAV
VAV
VAV
S-1
280 CFM 12x8 SA
S-1
145 CFM
S-1
145 CFM
S-1
145 CFM
S-1
145 CFM
S-1
145 CFM
S-1
340 CFM
(X)S
120 CFM
(X)R
120 CFM
(X)S
120 CFM
(X)R
120 CFM
(X)R
120 CFM
(X)R
120 CFM
T
VAV
T
R-1
135 CFM
R-1
390 CFM
R-1
165 CFM
R-1
220 CFM
R-1
140 CFM
R-1
85 CFM
18x12 RA
(X)S
120 CFM
(X)R
120 CFM
(X)S
120 CFM(X)R
120 CFM
S-1
340 CFM
(X)R
340 CFM
S-1
270 CFM
(X)R
270 CFM
S-1
370 CFM
(X)R
520 CFM
S-1
150 CFM
S-1
255 CFM S-1
135 CFM
(X)R
390 CFM
(X)S
120 CFM
(X)R
120 CFM
(X)S
130 CFM
(X)S
130 CFM
(X)R
45 CFM
(X)R
45 CFM
S-1
120 CFM
S-1
120 CFM
(X)R
120 CFM
(X)S
90 CFM(X)S
90 CFM
(X)R
90 CFM (X)R
90 CFM
R-1
325 CFM
S-1
325 CFM
(X)S
90 CFM
(X)R
90 CFM (X)S
325 CFM
(X)S
325 CFM(X)R
350 CFM
(X)R
300 CFM
(X)S
90 CFM
(X)R
90 CFM
(X)S
150 CFM
(X)R
150 CFM
(X)R
105 CFM
(X)S
105 CFM
(X)R
105 CFM
(X)S
105 CFM
(X)R
155 CFM
(X)S
75 CFM
(X)R
75 CFM
(X)S
100 CFM
(X)R
100 CFM
(X)S
100 CFM
(X)R
100 CFM
(X)S
100 CFM
(X)R
100 CFM
(X)S
140 CFM
(X)R
140 CFM
(X)S
280 CFM
(X)S
260 CFM
(X)S
280 CFM
(X)R
280 CFM
(X)R
260 CFM
(X)R
280 CFM
(X)S
240 CFM
(X)R
240 CFM
(X)S
130 CFM
S-1
130 CFM
(X)S
125 CFM
S-1
255 CFM
(X)R
255 CFM
S-1
160 CFM
(X)R
160 CFM
S-1
240 CFM
(X)R
240 CFM
(X)R
385 CFM
(X)R
160 CFM
S-1
160 CFM
(X)S
215 CFM
(X)R
140 CFM
(X)S-4
225 CFM
(X)S-4
225 CFM
(X)S-4
225 CFM
(X)S-4
225 CFM
(X)S-4
225 CFM
(X)S-4
225 CFM
(X)S-4
225 CFM
(X)S-4
125 CFM
x S
A
(X)R
500 CFM
12x10 SA
S-4
225 CFM
S-4
225 CFM
S-1
225 CFM
12x10 SA
(X)S-4
225 CFM
(X)S-4
225 CFM
(X)S
160 CFM
(X)R
160 CFM
(X)R
145 CFM
(X)S
145 CFM
(X)S
140 CFM
(X)R
140 CFM
(X)R
90 CFM
(X)R
500 CFM
(TYP OF 3)
(X)S
75 CFM
(X)R
75 CFM
(X)S
75 CFM
(X)R
75 CFM
(X)R
75 CFM
(X)S
75 CFM
(X)S
75 CFM
(X)R
75 CFM
(X)R
75 CFM
(X)S
75 CFM
(X)S
230 CFM
(X)E
75 CFM
(X)E
60 CFM
(X)E
60 CFM
(X)E
330 CFM
E-1
360 CFM
(X)S
260 CFM
(X)R
340 CFM
(X)R
280 CFM
(X)S
120 CFM
(X)R
120 CFM
(X)S
120 CFM
(X)R
120 CFM
(X)R
120 CFM
16x10 SA x S
A
(X)R
120 CFM
(X)S
120 CFM
S-1
200 CFM
(X)R
200 CFM (X)R
250 CFM
S-1
250 CFM
(X)R
250 CFM
S-1
250 CFM
(X)R
250 CFM
S-1
250 CFM
(X)R
250 CFM
S-1
250 CFM
(X)R
285 CFM
(X)R
450 CFM
(X)S
140 CFM
(X)S
140 CFM
(X)S
140 CFM
S-1
140 CFM
(X)S
140 CFM
x S
A x S
A x S
A
12x10 SA
(X)R
500 CFM
(TYP OF 4)
190 CFM
X(S)
190 CFM
X(S) 190 CFM
X(S)
(X)E
65 CFM
(X)E
75 CFM
(X)E
65 CFM
(X)E
75 CFM
S-3
600 CFM
x S
A x S
A x S
A
12x10 SA
12x10 SA
12x10 SA x S
A x S
A x S
A
12x10 SA
12x8 SA
18x14 SA
10x10 SA x S
A x S
A x S
A x S
A
12x10 SA
12x10 SA
T
(X)S
120 CFM (X)S
120 CFM
T
(X)S
210 CFM
(X)S
210 CFM
S-1
210 CFM
(X)S
190 CFM
T
(X)S
50 CFM
40x22 SA
48x22 SA
12x10 SA
30x22 SA DN 52x24 SA UP
26x24 SA DN 52x24 SA UP ø
S A
8ø SA
(X)S
250 CFM
30x20 RA DN 44x24 RA UP
12x12 RA10x10 RA
30x22 RA DN 40x24 RA UP
(X)R
125 CFM
30x20 RA UP
SD
SD
SD
EXISTING
DEMOLITION
NEW
PHASE LEGEND
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
S
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:4
:0
P M
MH101-S
FIRST FLOOR - MECHANICAL
VENTILATION PLAN - SOUTH
PARKING EXPANSION AT
JOLIET CBOC
04/21/2023
EPTHEP
1/8" = 1'-0"
1 FIRST FLOOR - MECHANICAL VENTILATION PLAN - SOUTH
0 4' 8' 16'
MECHANICAL KEYNOTES
NUMBER KEYNOTE
1 CONDENSATE DRAIN FROM AHU DOWN TO ROOF DRAIN
BELOW AT AMBULANCE BAY ROOF. PROVIDE DRAIN TRAP
AT AHU PER DETAILS.
2 PROVIDE DRAIN COOLER FOR ALL STEAM CONDENSATE
DRAINAGE FROM HUMIDIFIER AND PIPE DISCHARGE OF
CONDENSATE COOLER TO ROOF DRAIN BELOW.
3 PROVIDE ACID NEUTRALIZATION BASIN AT REAR OF EACH
BOILER TO ACCEPT ALL FLUE CONDENSATE AND ROUTE
DISCHARGE OF ACID NEUTRALIZATION BASINS TO
EXISTING FLOOR DRAIN IN BOILER ROOM.
4 MECHANICAL CONTRACTOR TO PIPE FROM EXISTING
PLUMBING WATER RPZ TO MAKEUP WATER FILL
CONNECTOR ON GLYCOL MAKEUP UNIT. PIPE THE
PUMPED DISCHARGE FROM GMU TO THE FILL
CONNECTION ON THE SYSTEM PER DETAILS ON M703.
5 MANUAL DAMPER (NORMALLY OPEN)
6 NEW UNDERGROUND HEATING WATER SUPPLY AND
RETURN SHALL BE INSTALLED ALONGSIDE EXISTING
STEAM AND CONDENATE PIPES UNDERGROUND TO
ALLOW FOR STEAM SYSTEM TO BE IN OPERATION UNTIL
LATER PHASES OF PROJECT. COORDINATE ROUTING OF
NEW HEATING WATER…