Attachment 7 - M601 - MECHANICAL SCHEDULES.pdf
PDF 186 KB Posted
- Solicitation number
- 36C77623B0049
About this file
This document contains mechanical schedules and specifications for an air handling unit project for the parking expansion at the Joliet Community Based Outpatient Clinic. Key details include specifications for two air handling units to serve the mechanical penthouse, with supply and return fans, cooling and heating coils, filters, and energy recovery sections. Also specified are hot water boilers, cabinet unit heaters, unit heaters, exhaust fans, finned tube radiation, a glycol makeup unit, pumps, expansion tanks, air separators, and humidifiers to provide HVAC services. The document provides equipment tags, locations, capacities, dimensions, connections sizes, electrical characteristics, manufacturers, and performance details. It is intended to procure HVAC equipment and components for the parking expansion project at the Joliet CBOC through the Department of Veterans Affairs Technology Acquisition Center Austin solicitation number 36C77623B0049.
View the file
Other files
Show 40 more
Latest 50 of 57 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AIR HANDLING UNIT HEATING PIPE SCHEDULE
# OF # OF HEATING SECTION
TAG TUBES FINS # OF CAPACITY (MBH) VELOCITY (FPM) FLOW RATE (ACFM) DBT (°F) WBT (°F) RH (%) SPEC. HUM. (GR/LB)
IN FACE PER INCH ROWS TOTAL SENSIBLE SUPPLY EXHAUST OA SA RA EA OA SA RA EA OA SA RA EA OA SA RA EA OA SA RA EA
AHU-1 50 11 5 342.5 342.5 459 459 10500 10500 10500 10500 -10.0 16.4 70.0 38.9 -11.0 10.6 53.0 38.1 58.2 13.8 30.7 93.1 2.40 1.94 34.06 33.18
AHU-2 50 11 5 342.5 342.5 459 459 10500 10500 10500 10500 -10.0 16.4 70.0 38.9 -11.0 10.6 53.0 38.1 58.2 13.8 30.7 93.1 2.40 1.94 34.06 33.18
AIR HANDLING UNIT COOLING PIPE SCHEDULE
# OF # OF COOLING SECTION
TAG TUBES FINS # OF CAPACITY (MBH) VELOCITY (FPM) FLOW RATE (ACFM) DBT (°F) WBT (°F) RH (%) SPEC. HUM. (GR/LB)
IN FACE PER INCH ROWS TOTAL SENSIBLE SUPPLY EXHAUST OA SA RA EA OA SA RA EA OA SA RA EA OA SA RA EA OA SA RA EA
AHU-1 50 11 5 105.2 105.2 459 459 10500 10500 10500 10500 95.0 85.0 70.0 79.5 75.0 72.3 53.0 56.8 40.1 54.9 30.7 22.3 101.53 101.64 34.06 34.04
AHU-2 50 11 5 105.2 105.2 459 459 10500 10500 10500 10500 95.0 85.0 70.0 79.5 75.0 72.3 53.0 56.8 40.1 54.9 30.7 22.3 101.53 101.64 34.06 34.04
444 W. Lake St. Suite 1700 Chicago, IL 60606
312.583.7023 www.virtualenergysolutions.com
Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432
Drawing No.
Scale:
Date:
Checked By:Drawn By:Designed By:
Drawing Title:
Contract No.
File No.Building No.
Client Project No.
Project Title:Approved: Chief, failites Management Services
Approved: Medical Center Director
Approved:
Approved: Location:
VES Project Number: 191006
AS NOTED
VA JOLIET CBOC
JOLIET, ILLINOIS
578-371 36C25219D0020
© 2020 Virtual Energy Solutions, INC.
B
IM
/2
-M
A T
O C
-P a rk in g E x p a n s io n a t J o lie t C
B O
C
-3
/2
-J o lie t C
B O
C P a rk in g
E x p a n s io n M
E C
H
.r v t
/2
/2
:5
:2
P M
M601
MECHANICAL SCHEDULES
PARKING EXPANSION AT
JOLIET CBOC
07/21/2023
EPTHEP
HOT WATER CONDENSING BOILER SCHEDULE
TAG LOCATION NATURAL GAS HEATING DATA ELECTRICAL DATA DIMENSIONS
UNIT WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
ROOM
NUMBER
ROOM NAME
GAS
INPUT
(BTU/HR)
HEATING
OUTPUT
(BTU/HR)
WATER FLOW
(GPM)
WATER TEMPS
FLA MOCP V PH HZ L W H MANUFACTURER MODEL
EWT (DEG. F) LWT (DEG. F)
B 1 -- Boiler Plant 3,000,000 2,760,000 138 120 160 6 20 208 3 60 120" 35" 87" 7100 FULTON VTG-3000
B 2 -- Boiler Plant 3,000,000 2,760,000 138 120 160 6 20 208 3 60 120" 35" 87" 7100 FULTON VTG-3000
B 3 -- Boiler Plant 3,000,000 2,760,000 138 120 160 6 20 208 3 60 120" 35" 87" 7100 FULTON VTG-3000
CABINET UNIT HEATER SCHEDULE (HYDRONIC)
TAG LOCATION
CAPACITY (BTU/HR)
FLUID
FLOWRATE
(GPM)
EWT
(DEG. F.)
LWT
(DEG. F.)
LEAVING
AIR TEMP
(DEG. F. )
FAN MOTOR DATA ELECTRICAL DATA DIMENSIONS
UNIT WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
ROOM
NUMBER
ROOM NAME
AIRFLOW
(CFM)
QTY FLA V PH HZ L W H MANUFACTURER MODEL
CUH 001 001
New North Vestibule
106,000 5.30
160 120 105 1410 3 3 120 1 60 85" 25" 10" 243 TRANE FF
CUH 104 104 Vestibule 48,100 3.00 160 120 105 790 2 3 120 1 60 61" 10" 25" 166 TRANE FF
CUH 1001 1001
Wheelchair
Storage 106,000
5.30
160 120 105 1410 3 3 120 1 60 85" 10" 25" 221 TRANE FF
CUH 1072 1072 Corridor 70,900 4.50 160 120 105 1105 3 3 120 1 60 73" 10" 25" 196 TRANE FF
CUH S-1 S-1 Stair #1 62,090 4.14 160 120 105 1015 3 3 120 1 60 66" 10" 25" 176 TRANE FF
UNIT HEATER SCHEDULE (HYDRONIC)
TAG LOCATION COIL DATA FAN MOTOR DATA ELECTRICAL DATA DIMENSIONS
UNIT WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
ROOM
NUMBER
ROOM NAME
CAPACITY
(BTU/HR)
EWT
(DEG. F.)
LWT
(DEG. F.)
LEAVING
AIR TEMP
(DEG. F. )
AIRFLOW
(CFM)
QTY FLA V PH HZ L W H MANUFACTURER MODEL
UH B018A B018 Mech. 36,000 160 120 95 850 1 1.2 120 1 60 21" 5" 19" 24 TRANE UHS
UH B018B B018 Mech. 36,000 160 120 95 850 1 1.2 120 1 60 21" 5" 19" 24 TRANE UHS
UH B019 B019 Elec. 24,000 160 120 95 580 1 0.8 120 1 60 18" 5" 16" 22 TRANE UHS
UH B020 B020 Gen Room 24,000 160 120 95 580 1 0.8 120 1 60 18" 5" 16" 22 TRANE UHS
HUMIDIFIER SCHEDULE- GAS FIRED
TYPE MARK SERVICE
NATURAL GAS BURNER DATA STEAM
DISCHARGE
(LB/HR)
WATER FLOW
(GPM)
ELECTRICAL DATA DIMENSIONS
UNIT WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
INPUT
(BTU/HR)
BURNER
QTY. TURNDOWN
N.G. PRESSURE
(INCH W.C.) FLA VOLTS PHASE HZ L W H MANUFACTURER MODEL
H 1 AHU-2 360,000 1 10:1 14 300 1 9 120 1 60 56" 22" 47" 916.00 DRI STEEM LX-300
H 2 AHU-1 360,000 1 10:1 14 300 1 9 120 1 60 56" 22" 47" 916.00 DRI STEEM LX-300
PUMP SCHEDULE - END SUCTION
TAG LOCATION
SYSTEM NAME
PUMP DATA ELECTRICAL DATA DIMENSIONS
WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
ROOM
NUMBER
ROOM NAME
DESIGN
FLOWRATE
(GPM)
DISCHARGE
PRESSURE (FT)
IMPELLER
SIZE
RPM NPSHr
(FT)
BHP HP VOLTS PHASE HZ L W H MANUFACTURER MODEL
P CHW-1 200
AHU
PENTHOUSE
PRIMARY CHILLED WATER 300 30 9 3/4" 1800
4.39
3.07 5.0 480 3 60 52" 19" 26" 637 BELL & GOSSETT e-1510 PROVIDE WITH VIBRATION ISOLATION INERTIA BASE
P CHW-2 200
AHU
PENTHOUSE
PRIMARY CHILLED WATER 300 30 9 3/4" 1800
4.39
3.07 5.0 480 3 60 52" 19" 26" 637 BELL & GOSSETT e-1510 PROVIDE WITH VIBRATION ISOLATION INERTIA BASE
P HW-1 -- Boiler Plant HEATING HOT WATER 200 75 9 1/2" 1800 5.96 5.06 7.5 208 3 60 35" 14" 18" 342 BELL & GOSSETT e-1510
P HW-2 -- Boiler Plant HEATING HOT WATER 200 75 9 1/2" 1800 5.96 5.06 7.5 208 3 60 35" 14" 18" 342 BELL & GOSSETT e-1510
P HW-3 -- Boiler Plant HEATING HOT WATER 200 75 9 1/2" 1800 5.96 5.06 7.5 208 3 60 35" 14" 18" 342 BELL & GOSSETT e-1510
EXPANSION TANK SCHEDULE
TAG LOCATION
SYSTEM NAME INLET SIZE
TANK
VOLUME
(GAL)
ACCEPTANCE
VOLUME
(GAL)
CHARGE
PRESSURE
(PSI)
MAX
WORKING
PRESSURE
(PSI)
DIMENSIONS
FLOODED
WEIGHT (LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
ROOM
NUMBER
ROOM NAME DIA. H MANUFACTURER MODEL
ET 1 -- Boiler Plant HEATING HOT WATER 1" 34.4 34.4 15 125 20" 37" 408 BELL & GOSSETT B130 BLADDER TYPE, FLOOR MOUNTED
ET 2 200
AHU
PENTHOUSE
1" 23.0 0.0 0 125 20" 29" 0 Taco CA90-125
AIR SEPARATOR SCHEDULE
TAG LOCATION
SYSTEM NAME
CONNECTION
SIZES
MAX
WORKING
PRESSURE
(PSI)
DIMENSIONS
FLOODED
WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
ROOM
NUMBER
ROOM NAME DIA. H MANUFACTURER MODEL
AS 1 -- Boiler Plant HEATING HOT WATER 6" 150 18" 40" 564 BELL & GOSSETT RL-6F
AS 2 6" 150 18" 40" 564 BELL & GOSSETT RL-6F
AIR HANDLING UNIT SCHEDULE
TAG
LOCATION TYPE
SUPPLY FAN DATA COOLING SECTION HEATING SECTION
FILTER
UNIT ELECTRICAL DATA
UNIT
WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
AIRFLOW (CFM)
EXTERNAL
STATIC
PRESSURE
(IN. W.C.) FAN RPM FAN QTY. HP (EA) TYPE
COIL CAPACITY
FLUID
FLOW
(GPM)
FACE
VELOCITY
WPD
(FT)
EAT
(DEG.F.)
LAT
(DEG.F.)
EWT
(DEG. F)
LWT
(DEG. F)
COIL
CAPACITY
(BTU/HR)
FLUID
FLOW
(GPM)
FLUID
PRESSU
RE
DROP
(FT.)
EAT
(DEG. F)
LAT (DEG.
F)
EWT
(DEG. F)
LWT
(DEG. F) FLA MCA MOCP V PH HZ
MANUFACTURER MODEL
SUPPLY MIN. OA
TOTAL
(BTU/HR)
SENSIBLE
(BTU/HR)
AHU 1 MECHANICAL PENTHOUSE VAV 35,000 10,500 3.50 3470 9 9.5 PLENUM 2,058,900 1,194,100 364 450 12.22 87 52 44 56 2,853,000 199 5.76 -2 65 160 120 MERV 8 PREFILTER/ MERV 13 INTERMEDIATE, MERV 17 FINAL FILTER 129 134 0 480 3 60 36,652 TEMTROL CUSTOM
AHU 2 MECHANICAL PENTHOUSE VAV 35,000 10,500 3.50 3470 9 9.5 PLENUM 2,058,900 1,194,100 364 450 12.22 87 52 44 56 2,853,000 199 5.76 -2 65 160 120 MERV 8 PREFILTER/ MERV 13 INTERMEDIATE, MERV 17 FINAL FILTER 129 134 0 480 3 60 36,652 TEMTROL CUSTOM
UNIT HEATER SCHEDULE (ELEC)
TAG LOCATION HTG. ELEMENT DATA FAN MOTOR DATA UNIT ELECTRICAL DATA DIMENSIONS (IN) UNIT
WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
ROOM
NUMBER
ROOM NAME
CAPACITY
(KW)
L.A.T.
(DEG. F)
FAN AIRFLOW
(CFM)
QTY FLA V PH HZ L W H MANUFACTURER MODEL
UH B003 B003 Elev. Equip. 3 105 350 1 15 480 3 60 21 5 19 24 MARLEY MUH0381 REMOTE THERMOSTAT
UH 003A 003A Mach. Room 3 105 350 1 15 480 3 60 21 5 19 24 MARLEY MUH0381 REMOTE THERMOSTAT
AHU RETURN/RELIEF FAN SECTION UNIT SCHEDULE
TAG
LOCATION
DISCHARGE
DIRECTION
RETURN FAN DATA UNIT ELECTRICAL DATA
UNIT
WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
RETURN
AIRFLOW
(CFM)
EXTERNAL
STATIC
PRESSURE
(IN. WC) FAN RPM FAN QTY. HP (EA) TYPE
FLA MCA MOCP V PH HZ MANUFACTURER MODEL
RF 1 ROOF HORIZONTAL 35,000 2.00 3490 6 11.5 PLENUM 87 90 100 480 3 60 7,078 TEMTROL CUSTOM
RF 2 ROOF HORIZONTAL 35,000 2.00 3490 6 11.5 PLENUM 87 90 100 480 3 60 7,078 TEMTROL CUSTOM
EXHAUST FAN SCHEDULE
TAG LOCATION FAN DATA MOTOR DATA DIMENSIONS
UNIT WEIGHT
(LBS)
BASIS OF DESIGN
REMARKSTYPE MARK
ROOM
NUMBER ROOM NAME CFM
E.S.P. (INCHES
W.C.) FAN TYPE RPM DRIVE BHP HP V PH HZ L W H MANUFACTURER MODEL
EF 1 C1-36 Ambulance Bay 2520 0.50 INLINE 1725 DIRECT 0.67 1.00 480 3 60 26" 24" 26" 100.00 GREENHECK SQ-140-VG
FINNED TUBE RADIATION SCHEDULE
TAG HYDRONIC DATA
FLUID FLOW
(GPM)
PRESSURE
DROP (FT. )
DIMENSIONS BASIS OF DESIGN
REMARKS
TYPE MARK
CAPACITY
(BTU/HR/LF)
EWT (DEG. F.) LWT (DEG. F.) L W H MANUFACTURER MODEL
FT S-2 990 160 120 0.50 2.00 72" 5.5" 20" STERLING LT SERIES
PROVIDE WITH SLOPED TOP ENCLOSURE TO
MATCH DEMOLISHED UNIT
REMARKS:
1. REFER TO SPECIFICATIONS FOR SPECIFIC REQUIREMENTS FOR AIR HANDLING UNITS AND COMPONENTS. REMARKS MADE HERE ARE NOT INCLUSIVE OF ALL REQUIREMENTS FOR PROCURING THESE UNITS, AND ARE SIMPLY TO HIGHLIGHT MAJOR ITEMS OF CONCERN TO CLARIFY DESIGN INTENT.
2. BOTH CHILLED WATER AND HEATING WATER SYSTEM UTILIZE 30% PROPYLENE GLYCOL AS THE FLUID. COILS SHALL BE SELECTED ACCORDINGLY.
3. UNIT SHALL BE PROVIDED WITH INDIVIDUAL VFD PER FAN - WITH ALL COMPONENTS HOUSED IN AN ELECTRICAL PANEL ATTACHED TO THE UNIT AND COORDINATED FOR ACCESS AND CLEARANCE WITH
ALL OTHER ELEMENTS.
4. UNIT SHALL BE PROVIDED WITH HEAT PIPE TYPE ENERGY RECOVERY SECTION.
5. UNIT SHALL BE PROVIDED WITH UV LIGHTS AT DOWNSTREAM SIDE OF COOLING COIL.
6. UNIT SHALL BE PROVIDED WITH 725 LB/HR HUMIDIFIER DISTRIBUTION MANIFOLD FACTORY INSTALLED AND PIPED TO EXTERIOR OF UNIT. STEAM GENERATING HUMIDIFIER SHALL BE SEPARATELY
PROVIDED AND INSTALLED BY MECHANICAL CONTRACTOR AS SHOWN IN DRAWINGS.
7. SINGLE POINT OF 120V/1PH POWER SHALL BE PROVIDED WITH UNIT AS A JUNCTION BOX WHICH IS FACTORY WIRED TO ALL LIGHTS, SWITCHES, RECEPTACLES, AND OTHER 120V LOADS.
8. SINGLE POINT OF 480V/3PH POWER FOR ALL FANS SHALL BE PROVIDED AS PART OF THE UNIT DESIGN.
9. IN GENERAL ALL DAMPERS WILL BE PROVIDED BY AHU MANUFACTURER, WITHOUT DAMPER ACTUATORS. THE TEMPERATURE CONTROLS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING DAMPER ACTUATORS IN THE FIELD TO MATCH THE REQUIREMENTS OF THE MANUFACTURER-PROVIDED DAMPERS. MECHANICAL CONTRACTOR AND TEMPERATURE CONTROLS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THIS ITEM IN SUBMITTALS AND FOR INSTALLATION.
GLYCOL MAKEUP UNIT SCHEDULE
TAG LOCATION
SYSTEM NAME
PUMP DATA ELECTRICAL DATA DIMENSIONS
WEIGHT
(LBS)
BASIS OF DESIGN
REMARKS
TYPE MARK
ROOM
NUMBER
ROOM NAME
TANK CAPACITY
(GAL.)
MAXIMUM
WORKING
PRESSURE
(PSI)
HP VOLTS PHASE HZ L W H MANUFACTURER MODEL
GMU 1 -- Boiler Plant HEATING HOT WATER 53 150 0.3 120 1 60 24" 24" 51" 145 ARMSTRONG GLA-U-HP-2
Revisions Date
ISSUED FOR 60% DD 12/30/2022
ISSUED FOR 90% CD 02/10/2023
ISSUED FOR 100% CD 03/07/2023
ISSUED FOR BID 03/24/2023
ISSUED FOR BID ADDENDUM 2 07/21/2023
| 200732-Joliet CBOC Parking Expansion MECH 2020 |
| M601 - MECHANICAL SCHEDULES |
File details come from the government source that posted it. Updated .