3949-0004
Drawing Title
RKMGMGH
Johnson Controls
633-104 HUTTON ST
RALEIGH
NC 27606
Phone: 919-743-3500 Fax: 919-743-3591
10/28/2010
REFERENCE DRAWING
TYPE 9
Systems & Services Division L09.1
Project Title
NO. REVISION-LOCATION DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE
DRAWN
Branch Information CONTRACT NUMBER
DRAWING NUMBER
(1) DDC MIXING BOX
CD & TOT W/O EQ. ALM
(1) TEK-AIR EXHAUST
NIEHS SITE METASYS
UPGRADE 03 & 04
National Institute of Environmental Health Sciences - RTP, NC
SLW System ID:
AS-BUILT 11/02/06 JMS
File Name:z:\jci stuff\39490004\drawings\labs\ltype9-1.vsd File Edited:10/28/10 at 3:01:27 PM
LAB AREA FLOW DIAGRAM
ROOM
Cold Deck Air
Hot Deck Air
Mixing Box
24 Vac24V
VMA-MB-C
DPR/DPT-1
Rm Temp1
Equip. Alarm3
N2 InN2
N2 OutN2
1 24VAC
2 24VAC
Not Used
3 Earth Gnd.
4 BO-1
5 BCOM
6 BO-2
7 BCOM
8 BO-3
9 BCOM
SH
LD
R
EF N
2-
N 2+
VMA-MB-C
TX-1
92 VA
120VAC/24VAC
H
N
16 AWG (2) CONDUCTOR 24VSW-1
TE-1
RM-TEMP
ROOM
TEMPERATURE
DPR-1
DPR-OUT
HOT DECK
CONTROL
CONTROLLER/FIELD DEVICE TERMINATIONS
24V
Temp Adj.2
H L
To CD Flow
Station
¼” Polytubing
Red red blk red blk
N2N2 N2 OutN2 In
¼" Polytubing
¼" Polytubing
Total Flow
Cold Deck Flow
Hot Deck Flow
DPT-1
FLOW
in out gnd
TOTAL
FLOW
cw ccw
Exhaust Air
SEQUENCE OF OPERATION
Exhaust Air Flow Control:
An air flow measuring station (Tek-Air) in the lab exhaust duct is used to control exhaust flow to exhaust CFM setpoint. A Pneumavalve through operator (VMA-EB-C and EP-1), will modulate to maintain the exhaust CFM setpoint. Upon the loss of the associated exhaust fan, the Pneumavalve will be overridden closed for a general exhaust and overridden open if serving a hood.
Supply Air Flow and Temperature Control:
A temperature sensor (TE-1) is located in the room. A dual duct mixing box supplies conditioned air to the room.
Air flow measuring stations are located on the mixing box to measure Cold deck and Total flow. The hot deck and cold deck dampers will modulate through operator (VMA-MB-C) and DPR-1, to maintain the total supply CFM setpoint. The sequence will on a fall in room temperature below setpoint, modulate open the hot deck damper from minimum CFM to maximum CFM to maintain room temperature setpoint. On a rise in space temperature above setpoint, the hot deck damper will close to minimum CFM and on a continued rise, open the cold deck damper from minimum CFM setpoint to maximum CFM setpoint to maintain room temperature setpoint. Upon the loss of the associated Supply fan, the mixing box will be overriden to a shutdown condition, which will close the Hot and Cold deck dampers.
The temperature sensor has an adjustable slide bar to offset the base setpoint +/- 2 degrees.
Designation # Part Number Description Field Devices
DPR/DPT-1 1 M 9106-AGS-2N02 ROTARY ACTUATOR
EP-1 1 EP2100S1 EP TRANS, LCD, OVRIDE,AUTO-M AN SW
EP-1 (See Note Below) 1 EPC2GB FP TO PNEUM ENC BLEED
SW-1 1 SIB05S 20A,2-POS ENCLOSED, M AINTAINED SWITCH (FUNCTIONAL DEVICES)
TE-1 1 TE-67PT-1B00 SENSOR,RM ,1K PLT,TERM BLK,W/C,THERM OM
TX-1 1 Y64T22-0 XFM R,120-208-240/24,92VA,PLATE,8IN LEADS
VM A-EB-C 1 A-12N10PP 12" X10" PREF PANEL (HOFFM AN)
1 AP-VM A1430-0 VAV CTRL W/DPT LESS ACTUATOR
VM A-M B-C 1 AP-VM A1420-0 VAV M ODULAR ASSY - CLG W/ REHEAT
1 CBL-2000-3 WIRING HARNESS, 72IN
NOTE: TX-1, SW-1
Power Disconnect Switch and Plate Mounted Transformer Located on 4x4 J-Box in Interstitial above space served.
LEGENDField Wiring
Cable Designation Example:
2C 18G Cable #1 Terminated at VMA-MB-C Analog Input #1
N2 N2 Bus (3C TSP 18G Cable)
VMA-MB-C
AI-1
brn wht grn red blu blk 1 UPDATED HARNESS COLORS 1/19/06 CLW
¼" Polytubing
¼" Polytubing
TEK-AIR
CVR-2
H L
¼" Polytubing
¼" Polytubing
TE-1
RM-TEMP
1 VMA-MB-C
AI-1
2 VMA-MB-C
AI-2
NOTE: TE-1
A thermostat will be provided to monitor and control the room temperature. A warmer/cooler adjustment is provided to adjust the setpoint +/- 2 degrees.
Tek-Air
CVR-2
VMA-EB-C
BI-1
COM
COM
BI-2
BI-3
COM
+15
VDC
+15
VDC
AI-1
COM
AI-2
COM
AI-3
COM
+15
VDC
BO-4
BCOM
BO-5
BCOM
AO-1
COM
AO-2
COM
1 24VAC
2 24VAC
Not Used
3 Earth Gnd.
4 BO-1
5 BCOM
6 BO-2
7 BCOM
8 BO-3
9 BCOM
BO-4
BCOM
BO-5
BCOM
AO-1
COM
AO-2
COM
BI-1
COM
COM
BI-2
BI-3
COM
+15
VDC
+15
VDC
AI-1
COM
AI-2
COM
AI-3
COM
AI-4
COM
ZB+
ZB-
SH
LD
R
EF N
2-
N 2+
VMA-EB-C
24V
16 AWG (2) CONDUCTOR 24V
H L
To Tek- Air Flow Station
¼” PolytubingRed
N2N2 N2 OutN2 In
EP-1
EB-OUT
P
I
EXHAUST BOX
CONTROL
C
S
Instrument Air Supply
Pneumavalve
SO
24 Vac24V
N2 InN2
N2 OutN2
¼ Polytubing
S
EP-1
Note: EP (Part # EPC2GB) installed for following rooms:
C263A, E414A, C458A
| Cover |
| A101 |
| A201 |
| M100 |
| M101 |
| P100 |
| L09_1 |
| E100 |