Attachment_L6_-_TOR_214-20_-_Statement_of_Work_-_Revision_2.pdf

PDF 8 MB Posted

Attached to
Multiple Award Task Order Contract (MATOC) Federal contract opportunity
Solicitation number
NIHOF2013536
Issued by
Department of Health and Human Services National Institutes of Health

About this file

Attachment L6 - TOR 214-20 - Statement of Work - Revision 2

View the file

Other files for this federal contract opportunity

Other files attached to Multiple Award Task Order Contract (MATOC), newest first.
File Type Posted
Attachment_L9_-_TOR_214-26_-_Task_Order_Pricing_Template_-_Revision_3.xlsx XLSX spreadsheet
TOR_00-13_-_Revised_Drawings_-_dated_02-10-14.pdf PDF
Section_H_-_Special_Contract_Requirements_-_Revision_1.pdf PDF
Section_G_-_Contract_Administration_Data_-_Revision_1.pdf PDF
Attachment_L7_-_TOR_214-20_-_Task_Order_Pricing_Template_-_Revision_3.xlsx XLSX spreadsheet
SF_30_-_NIHOF2013536_-_Amendment_0005.pdf PDF
Specification_Section_01_33_00_-_Revision_1.pdf PDF
Amendment_0005.docx DOCX document
Attachment_L5_-_TOR_13-00_-_Task_Order_Pricing_Template_-_Revision_3.xlsx XLSX spreadsheet
SF_30_-_NIHOF2013536_-_Amendment_0004.pdf PDF
Amendment_0003.docx DOCX document
Attachment_L7_-_TOR_214-20_-_Task_Order_Pricing_Template_-_Revision_2.xlsx XLSX spreadsheet
MATOC_Pre-Proposal_Conference_Sign-in_Sheet.pdf PDF
SF_30_-_NIHOF2013536_-_Amendment_0003.pdf PDF
MATOC_Pre-Proposal_Conference_Briefing.pptx PPTX presentation
Attachment_L9_-_TOR_214-26_-_Task_Order_Pricing_Template_-_Revision_2.xlsx XLSX spreadsheet
Attachment_L8_-_TOR_214-26_-_Statement_of_Work_-_Revision_2.pdf PDF
Attachment_L7_-_TOR_214-20_-_Task_Order_Pricing_Template_-_Revision_1.xlsx XLSX spreadsheet
Attachment_L9_-_TOR_214-26_-_Task_Order_Pricing_Template_-_Revision_1.xlsx XLSX spreadsheet
SF_30_-_NIHOF2013536_-_Amendment_0002.pdf PDF
Attachment_L5_-_TOR_13-00_-_Task_Order_Pricing_Template_-_Revision_2.xlsx XLSX spreadsheet
Attachment_L8_-_TOR_214-26_-_Statement_of_Work_-_Revision_1.pdf PDF
Statement_of_Work_-_Revision_1_-_01-24-14.pdf PDF
Attachment_L7_-_TOR_214-20_-_Task_Order_Pricing_Template.xlsx XLSX spreadsheet
Attachment_L4_-_TOR_13-00_-_Statement_of_Work_-_Revision_1.pdf PDF
NIH_As-Built_Drawing_LOP_for_Contractors.doc DOC document
Specification_Section_01_35_26.docx DOCX document
Specification_Section_01_45_00.docx DOCX document
Section_J_-_List_of_Attachments_-_Revision_1.pdf PDF
Section_L_-_Instructions _Conditions _and_Notices_to_Offerors_-_Revision_1.pdf PDF
Attachment_L6_-_TOR_214-20_-_Statement_of_Work_-_Revision_1.pdf PDF
Section_E_-_Inspection_and_Acceptance_-_Revision_1.pdf PDF
SF_30_-_NIHOF2013536_-_Amendment_0001.pdf PDF
Attachment_L2_-_Past_Performance_Transmittal_Letter_-_Revision_1.docx DOCX document
Attachment_L5_-_TOR_13-00_-_Task_Order_Pricing_Template_-_Revision_1.xlsx XLSX spreadsheet
FMB-NC_Engineering_Guidelines_and_Material_Requirements--Revision_C.pdf PDF
Attachment_L3_Past_Performance_Questionnaire.pdf PDF
Wage_Determination--NC130093--Highway.pdf PDF
Wage_Determination--NC130080--Heavy.pdf PDF
Wage_Determination--NC130028--Building.pdf PDF
Wage_Determination--NC130019--Heavy_Dredging.pdf PDF
Attachment_L4_TOR_213-00--Statement_of_Work.pdf PDF
Attachment_L5_TOR_214-20--Statement_of_Work.pdf PDF
Safety_and_Health.pdf PDF
Attachment_L2_Past_Performance_Transmittal_Letter.pdf PDF
Attachment_L6_TOR_214-26--Statement_of_Work.pdf PDF
Attachment_L1_Experience_Summary_Sheet.pdf PDF
Certificate_of_Current_Cost_or_Pricing_Data.pdf PDF
Task_Order_Pricing_Template.xlsx XLSX spreadsheet
SF_1442.pdf PDF
Show all 50

Multiple Award Task Order Contract (MATOC) has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work

Building 106 Replace Incinerator Water Softener

National Institute of Environmental Health Sciences

Task Order Request #214-20

Revised February 3, 2014

COR: Mary Waligora

This Scope of Work details the requirements for a construction only project to replace the water softener system that supplies softened water (SW) for cooling loop purposes related to the incinerator in Building 106. The Contractor is to provide all services for review of existing conditions; preparation of construction documents/submittals; and construction in accordance with contract requirements.

I. GENERAL:

A. The Contractor shall provide all services necessary to complete the project as stated in this SOW. The Contractor is responsible for providing for demolition/construction, temporary contractor access, and must maintain the functionality of the existing facility.

B. The Contractor shall provide all personnel necessary per their approved quality control and safety plans to properly oversee the construction of this project. Quality control, project management, superintendent and site safety officer roles may be performed by the same individual as deemed appropriate by the Contractor for this contract provided that the designated personnel is qualified and meets the requirements set forth in the Contractor’s approved Site Specific Safety Plan and Site

Specific Quality Control Plan. The Contractor shall provide for review and acceptance, the resume and qualifications of any key personnel performing the tasks identified above that have not been previously approved by the Government.

II. CONSTRUCTION:

A. The Contractor shall comply with the quality control requirements for construction in accordance with the Contractor Quality Control Program and the contract.

B. The Contractor shall provide an overall project schedule showing the submittal and construction phases. The schedule shall be updated and submitted with each pay request. Final construction must be completed 75 calendar days from task order

Notice to Proceed. The incinerator operations will be maintained during the work period. Incinerator burn dates are typically Monday, Wednesday, and Thursday.

C. The Contractor must give 15 days’ written notice before any requested outages.

D. The Contractor must construct the project in accordance with the 2008 NIH Design

Requirements Manual for Biomedical Laboratories and Animal Research Facilities as modified by the FMB-NC Engineering Guidelines and Material Requirements

Manual (Revision C).

TO#214-20

Replace Incinerator Water Softener 2 February 3, 2014

III. SCOPE OF WORK

NOTE: The incinerator operations will be maintained during the work period.

Incinerator burn dates are typically Monday, Wednesday, and Thursday.

A. The Contractor shall:

1. Demolish the existing ANCO water softener system, flow meters, controls, piping, hangers, flexible connections, and instrumentation back to the main domestic water/softened water main (indicated in Attachment 1) and including the eye wash and drain line. Only demolish drain line between softeners and 90 degree elbow down into incinerator pit. See Attachment 4 for ANCOSOFT 2ATM 302-2 water softener installation and operating manual. Removal and disposal of the existing softener tanks, brine tank, and contents shall be at the contractor’s own expense. Use of government dumpsters is not allowed for the existing softener tanks, brine tank, and contents.

2. Provide and install a new water softener system. New softener tanks shall be located in the same location as present equipment. This includes associated electrical connections, flow meters, controls, piping, hangers, water sampling port, flexible connections, and instrumentation back to the main domestic water/softened water main (indicated in Attachment 1) and including the eye wash and drain line. Replace drain line between softeners and 90 degree elbow down into incinerator pit. SW piping shall be elevated approximately 8 feet between softener tanks and main in the same location as existing piping.

This work also includes:

a. Installation of new softener tanks

b. Installation of a new inline backflow preventer after the eye wash leg tee on the SW supply line. (Contractor must obtain a backflow preventer permit through the City of Durham’s Cross-Connection

Control office.)

c. Installation of new isolation valves.

New replacement isolation valves shall be provided and installed on:

i. the inlet and outlet of water line into each tank (1-1/2” valve)

ii. the SW supply line (1-1/2” valve)

iii. the bypass line (1-1/2” valve)

New isolation valves shall be provided and installed on:

iv. the SW return line (1-1/2” valve)

v. the eyewash leg near the submain (1” valve)

d. Insulation and labeling of new piping and new valves. PVC elbows on top of the new piping insulation shall be added in addition to 1” mineral fiber, ASTM C547, Type 1, Class 1, ASJ, with vapor barrier.

Do not insulate drain line within 3 feet of incinerator. Labeling shall be painted and stenciled per FMB-NC Engineering Guidelines and

Material Requirements Manual (Revision C).

e. Media loading of the new softener tanks

f. Start up and verification of operation

Replace Incinerator Water Softener 3 February 3, 2014

B. New water softener system shall be of a duplex alternating flow configuration with high capacity cation resin bed, corrosion resistant fiberglass vessels, flow meters, and advanced controller to maximize duration between regeneration and minimize water usage. New water softeners shall capable of meeting all existing system requirements.

The softeners shall be Vantage PTC Series, 21” diameter, Duplex Deluxe Softener

System, or approved equal (see Attachment 5-7).

C. The Contractor shall use seamless copper tube, ASTM B88, Type K Hard for the SW and DW piping. Joint type shall be ASTM B32 lead-free solder with ASTM B813 water soluble flux. Piping for the SW lines shall be 1-1/2” NPS and 1” NPS for the drain and eye wash lines.

D. The Contractor is responsible for proper disposal of the existing softeners and resin in accordance with all Federal, State, and local regulations.

E. The Government has the option to keep any equipment demolished as part of this project.

F. The Contractor shall provide a placard to be attached to the system that clearly describes the system via a one line diagram and includes a valve alignment table. The planned material/content of this placard shall be submitted for approval at time of proposal.

G. Prior to the start of construction, the Contractor shall submit the material indicated on the attached submittal register (Attachment 10) in accordance with Specification 01

33 00: SUBMITTAL PROCEDURES.

H. All equipment shall have a warranty period of at least 1 calendar year from the beneficial occupancy date.

Replace Incinerator Water Softener 4 February 3, 2014

IV. CLOSE-OUT REQUIREMENTS

A. In addition to standard requirements provided in the contract base specifications additional services are required for close-out and completion of this task order.

B. New Equipment Data Worksheets: The Contractor shall complete the attached

New Equipment Data Worksheet whenever new equipment is installed. This data will be used to replace or add new equipment to real property equipment lists and schedule preventative maintenance tasks. In addition, the contractor shall return to the COR any existing equipment identification tags found on existing equipment so the equipment can be revised on real property equipment lists. New equipment identification tags will be issued to the Contractor for placement on the new equipment. Equipment tag checks will be part of the Pre-Final Inspection.

C. Operation and Maintenance Manuals. The Contractor shall provide 5 copies in hard copy format of Operation and Maintenance manuals for all the new equipment.

The hard copies shall be bound in a three-ring binder. The Contractor shall also provide the Operation and Maintenance manuals in electronic format.

D. Tags for Warranted Equipment: The tag for equipment shall be similar to the following. Exact format and size will be as approved by the COR.

EQUIPMENT WARRANTY

CONTRACTOR FURNISHED EQUIPMENT

MFG ___________________ MODEL NO. ____________________________

SERIAL NO. _____________________________________________________

CONTRACT NO. _________________________________________________

CONTRACTOR NAME ____________________________________________

CONTRACTOR WARRANTY EXPIRES ______________________________

MFG WARRANTY(IES) EXPIRE ____________________________________

Replace Incinerator Water Softener 5 February 3, 2014

V. ATTACHMENTS

Attachment 1. Area indicated in red shows the DW/SW main; point of new construction.

Attachment 2. A picture of the existing ANCO water softening units and controller.

Replace Incinerator Water Softener 6 February 3, 2014

Attachment 3. New Equipment Data Worksheet

Attachment 4. ANCO Water Softener Installation and Operating Manual

USFilter Material Safety Data Sheet

SECTION 1 – CHEMICAL PRODUCT AND COMPANY INFORMATION

Product Name: USF C-211 UPS Ion Exchange Resin Part Number: multiple Chemical Family: ion exchange resin

Manufacturer’s Name: USFilter Corporation Address: 4669 Shepherd Trail, Rockford, IL 61103 Product/Technical Information Phone Number: (815) 877-3041 Medical/Handling Emergency Phone Number: Call CHEMTREC at (800) 424-9300

24 hours a day Transportation Emergency Phone Number: Call CHEMTREC at (800) 424-9300

24 hours a day Issue Date: October 27, 2004 Revision Date/Revision Number: October 27, 2004/Revision 0

SECTION 2 – COMPOSITION INFORMATION

UChemical NameU UPercent by WeightU UCAS# U

Sulfonated copolymer of styrene and 40 - 70 % 069011-22-9 divinylbenzene in sodium form

Water 30 - 60 % 007732-18-5

SECTION 3 – HAZARDS IDENTIFICATION

Appearance & Odor: Spherical beads/Odorless to slight amine odor Emergency Overview:

♦ May cause eye irritation ♦ May cause toxic fumes/vapors if burned ♦ May react violently when exposed to oxidizing agents such as Nitric Acid

(HNOB3 B)

Fire & Explosion Hazards: This material will not burn until moisture is removed, then resin starts to burn in flame at 230°C. Under fire conditions some components of this product may decompose. The smoke may contain unidentified toxic and/or irritating compounds. Nitric acid and other strong oxidizing agents can cause explosive-type reactions when mixed with ion exchange resins. Proper design of equipment to prevent build up of pressure is necessary if use of an oxidizing agent such as nitric acid is contemplated.

Primary Route(s) of Exposure: skin and eye contact

Attachment 5. USF C-211 UPS Ion Exchange Resin MSDS

USF C-211 UPS Ion Exchange Resin, Page 2 of 6

SECTION 3 – HAZARDS IDENTIFICATION (cont.)

Inhalation – Acute Effects: Vapors are unlikely due to physical properties.

Skin Contact – Acute Effects: Prolonged or repeated exposure is not likely to cause significant skin irritation. May cause more severe response if skin is scratched or cut.

Skin absorption is unlikely due to physical properties.

Eye Contact – Acute Effects: May cause severe eye irritation. May cause moderate corneal injury. Effects are likely to heal.

Ingestion – Acute Effects: Single dose oral toxicity is considered to be low. No hazards anticipated from swallowing small amounts incidental to normal handling operation.

SECTION 4 – FIRST AID MEASURES

Inhalation First Aid: Remove affected person from area to fresh air and provide oxygen if breathing is difficult. Give artificial respiration ONLY if breathing has stopped and give CPR ONLY if there is no breathing and no pulse. Obtain medical attention. No adverse effects anticipated by this route of exposure.

Skin Contact First Aid: Immediately remove clothing from affected area and wash skin vigorously with flowing water. Clothing should be washed before reuse. DO NOT instruct person to neutralize affected skin area.

Eye Contact First Aid: Immediately irrigate eyes with flowing water continuously for 15 minutes while holding eyes open. Contacts should be removed before or during flushing. Obtain medical attention. DO NOT instruct person to neutralize.

Ingestion First Aid: No adverse effects anticipated by this route of exposure incidental to proper industrial handling. If ingestion does occur, if victim is alert and not convulsing rinse mouth with water and give plenty of water to drink. If spontaneous vomiting occurs, have affected person lean forward with head down to avoid breathing in of vomitus.

Rinse mouth again and give more water to drink. Obtain medical attention.

Medical Conditions Aggravated: There are no known conditions aggravated by exposure.

Note to Physician: No specific antidote. Supportive care. Treatment based on judgement of the physician in response to reactions of the patient.

SECTION 5 – FIRE FIGHTING MEASURES

Flash Point/Method: Not applicable Auto Ignition Temperature: Above 500°C (900°F) Upper/Lower Explosion Limits: Not applicable

Extinguishing Media: Water, carbon dioxide, dry chemical Fire Fighting Procedures: Keep people away. Isolate fire area and deny unnecessary entry. Cool surrounding area with water to localize fire zone. Soak thoroughly with water to cool and prevent reignition.

USF C-211 UPS Ion Exchange Resin, Page 3 of 6

SECTION 5 – FIRE FIGHTING MEASURES (cont.)

Fire-Fighting Equipment: NIOSH approved positive-pressure self-contained breathing apparatus (SCBA) and protective fire fighting clothing (includes fire fighting helmet, coat, pants, boots and gloves). If protective equipment is not available or not used, fight fire from a protected location or a safe distance.

Fire & Explosion Hazards: This material will not burn until moisture is removed, then resin starts to burn in flame at 230°C. Under fire conditions some components of this product may decompose. The smoke may contain unidentified toxic and/or irritating compounds. Nitric acid and other strong oxidizing agents can cause explosive-type reactions when mixed with ion exchange resins. Proper design of equipment to prevent build up of pressure is necessary if use of an oxidizing agent such as nitric acid is contemplated.

Hazardous Products of Decomposition and/or Combustion: May include but not limited to hydrocarbons, sulfur oxides, organic sulfonates, carbon monoxide, carbon dioxide and benzene compounds.

NFPA Ratings:

HEALTH- 1 FLAMMABILITY- 1 REACTIVITY- 1 OTHER- none

SECTION 6 – ACCIDENTAL RELEASE MEASURES

Spill/Leak Procedures: Isolate spill area to prevent falls as material can be a slipping hazard. Avoid contact with eyes and skin. Material is heavier than water and has limited water solubility. It will collect on the lowest surface.

Cleanup: Clean up floor area. Sweep up.

Regulatory Requirements: Follow all applicable Federal, State, Local, or Provincial regulations. Disposal: DO NOT DUMP INTO ANY SEWERS, ON THE GROUND, OR INTO ANY BODY OF WATER. All disposal methods must be in compliance with all Federal, State, Local and Provincial laws and regulations. Regulations may vary in different locations. Waste characterizations and compliance with applicable laws are the responsibility solely of the waste generator.

SECTION 7 – HANDLING AND STORAGE

Handling: Practice reasonable care and caution. Metal equipment should be compatible with feed, regenerant, resin form and effluent of that process.

Storage: Keep containers tightly closed when not in use. Store between 2°- 38°C (35° - 100°F).

General Comments: Containers of this material may be hazardous when empty since they retain product residues (dust, solids); observe all warnings and precautions listed for the product.

USF C-211 UPS Ion Exchange Resin, Page 4 of 6

SECTION 8 –PERSONAL PROTECTION/ EXPOSURE CONTROL

Respiratory Protection: No respiratory protection should be needed.

Skin Protection: Wear gloves impervious to this material to prevent skin contact.

Eye Protection: Wear protective eyeglasses or chemical safety goggles. Contact lenses are not eye protective devices. Appropriate eye protection must be worn instead of, or in conjunction with contact lenses.

Ventilation Protection: Good general ventilation should be sufficient.

Other Protection: Never eat, drink, or smoke in work areas. Practice good personal hygiene after using this material, especially before eating, drinking, smoking, using the toilet, or applying cosmetics.

Safety showers, with quick opening valves which stay open, and eye wash fountains, or other means of washing the eyes with a gentle flow of cool to tepid tap water, should be readily available in all areas where this material is handled or stored. Water should be supplied through insulated and heat-traced lines to prevent freeze-ups in cold weather.

Exposure Limits:

Exposure limits have not been developed.

SECTION 9 – PHYSICAL AND CHEMICAL PROPERTIES

Appearance & Odor: Spherical beads/Odorless to slight amine odor Vapor Pressure: N/A* Vapor Density (Air=1): N/A Boiling Point: N/A Melting Point: N/A Specific Gravity: N/A Solubility in Water: Insoluble Volatile Percentage: N/A pH: N/A Flash Point/method: N/A Auto Ignition Temperature: Above 500°C (900°F) Upper/Lower Explosion Limits: N/A Other: none *N/A=Not applicable

SECTION 10 – STABILITY AND REACTIVITY

Stability: Stable under normal handling and storage conditions.

Incompatibilities: Oxidizing agents such as nitric acid attack organic ion exchange resins under certain conditions and could result is slightly degraded resin up to an explosive reaction. Before using strong oxidizing agents, consult sources knowledgeable in handling such materials.

Polymerization: Hazardous polymerization cannot occur.

Decomposition: Hazardous decomposition products depend upon temperature, air supply, and the presence of other materials. Hazardous decomposition products may include and are not limited to: aromatic compounds, hydrocarbons, organic sulfonates, sulfur oxides.

Conditions to Avoid: Resin can decompose at temperatures greater than 90°C (194°F).

Do not pack column with dry ion exchange resins. Dry beads expand when wet. This expansion can cause a glass column to shatter.

USF C-211 UPS Ion Exchange Resin, Page 5 of 6

SECTION 11 – TOXICOLOGICAL INFORMATION

Inhalation – Acute: Vapors are unlikely due to physical properties.

Inhalation – Chronic: There are no known chronic inhalation effects.

Skin Contact – Acute: Prolonged or repeated exposure is not likely to cause significant skin irritation. May cause more severe response if skin is scratched or cut. Skin absorption is unlikely due to physical properties.

Skin Contact – Chronic: There are no known chronic dermal effects.

Eye Contact – Acute: May cause severe eye irritation. May cause moderate corneal injury. Effects are likely to heal.

Ingestion – Acute: Single dose oral toxicity is considered to be low. No hazards anticipated from swallowing small amounts incidental to normal handling operation.

Ingestion – Chronic: There are no known chronic ingestion effects.

Carcinogenicity/Mutagenicity: There are no known carcinogenic/mutagenic effects.

Reproductive Effects: There are no known reproductive effects.

Neurotoxicity: There are no known neurotoxic effects.

Other Effects: There are no other known toxic effects.

Target Organs: This product will affect the eyes.

SECTION 12 – ECOLOGICAL INFORMATION

The environmental fate and ecological toxicity are not known.

SECTION 13 – DISPOSAL CONSIDERATIONS

Spill/Leak Procedures: Isolate spill area to prevent falls as material can be a slipping hazard. Avoid contact with eyes and skin. Material is heavier than water and has limited water solubility. It will collect on the lowest surface.

Cleanup: Clean up floor area. Sweep up.

Regulatory Requirements: Follow all applicable Federal, State, Local, or Provincial regulations.

Disposal: DO NOT DUMP INTO ANY SEWERS, ON THE GROUND, OR INTO ANY BODY OF WATER. All disposal methods must be in compliance with all Federal, State Local and Provincial laws and regulations. Regulations may vary in different locations. Waste characterizations and compliance with applicable laws are the responsibility solely of the waste generator.

SECTION 14 – TRANSPORTATION INFORMATION

DOT Shipping Description: This product is not regulated by DOT when shipped domestically by land.

Canadian TDG Information: For TDG regulatory information, if required, consult transportation regulations, or product shipping.

USF C-211 UPS Ion Exchange Resin, Page 6 of 6

SECTION 15 – REGULATORY INFORMATION

US Regulations:

SARA HAZARD CATEGORY: This product has been reviewed according to the EPA "Hazard Categories" promulgated under Sections 311 and 312 of the Superfund Amendment and Reauthorization Act of 1986 (SRA Title III) and is considered, under applicable definitions, to meet the following categories:

An immediate health hazard

TSCA Considerations: Every different salt or ionic form of an ion exchange resin is a separate chemical. If you use an ion exchange resin for ion exchange purposes and then remove the by-product resin from its vessel or container prior to recovery of the original or another form of the resin or of another chemical, the by-product resin must be listed on the TSCA Inventory (Unless an exemption is applicable). It is the responsibility of the customer to ensure that such isolated, recycled by-product resins are in compliance with TSCA. Failure to comply could result in substantial civil or criminal penalties being assessed by the EPA.

State Regulations: Consult individual state agency for further information.

Canadian Regulations:

WHMIS INFORMATION: The Canadian Workplace Hazardous Materials Information System (WHMIS) Classification for this product is:

D2B - eye or skin irritant

Refer elsewhere in the MSDS for specific warnings and safe handling information.

CPR Statement: This product has been classified in accordance with the hazard criteria of the Canadian Controlled Products Regulations (CPR) and the MSDS contains all the information required by the CPR.

SECTION 16 – OTHER INFORMATION

Disclaimer: The information contained herein is based on data considered accurate.

However, no warranty is expressed or implied regarding the accuracy of these data or the results to be obtained from the user thereof. It is the buyer’s responsibility to ensure that its activities comply with federal, state, provincial and local laws.

Created by: Douglas C. Kellogg

Attachment 6. Brine Safe-T-Salt MSDS

Vantage™ PTC Softeners

Vantage™ PTC softeners for commercial applications offer a flexible, reliable and feature-rich way to reduce the amount of hardness in feed water by filtering the water through a cation resin bed.

Softeners are necessary to remove hardness or calcium that can clog or minimize the effectiveness of other sensitive down stream devices, such as RO membranes.

Softener vessel diameters range from 9” (23cm) to 48” (122cm). Each softener contains high capacity cation resin for this ion exchange process.

Vantage™ PTC softeners are available in three models: Economy, Plus, and Deluxe.

� Economy – Controlled by a digital controller and composite valve � Plus – Controlled by mechanical time clock and a lead free brass valve � Deluxe – Controlled by a feature-rich digital controller and a lead free brass valve

The Deluxe models are available in four vessel configurations: Simplex, Duplex, Triplex and Quadplex.

Water Technologies

Deluxe Triplex Configuration

Vantage™ PTC System Features Vantage™ PTC System Benefits

Range of optional flow meters Maximize duration between regeneration and minimize water usage

24vac systems with UL and cUL listed transformers Complies with regulatory and safety requirements

Feature-rich digital controller for networked systems

Offers maximum operational flow and configuration flexibility to the customer

Tanks and valves are NSF/WQA* approved Requires stringent testing for leaching of contaminates, providing a safe system

Corrosion-resistant fiberglass vessels Prevents rust and increases longevity of the vessel

* NSF = National Science Foundation. WQA = Water Quality Association.

Attachment 7. Vantage PTC Softeners

Vantage is a trademark of Siemens, its subsidiaries or affiliates.

UL and cUL are trademarks of Underwriters Laboratories, Inc.

The information provided in this brochure contains merely general descriptions or characteristics of performance which in actual case of use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract.

www.siemens.com/vantage

Siemens Water Technologies 10 Technology Drive Lowell, MA 01851 Technical Support: 800.875.7873 ext 5000 Customer Support: 800.466.7873 Phone: 978.934.9349 ext 5000 Fax: 978.441.6025

© 2009 Siemens Water Technologies Corp.

PWS-PTCSOFT-DS-1009

Subject to change without prior notice.

Deluxe models are available in four operational flow configurations depending on the number of vessels.

� Simplex Operation – single vessel operation � Duplex Alternating – one vessel on, one vessel in standby (only option for the Twin Configuration) � Parallel – all vessels working together

X + 1 – two or three vessels working and one vessel in stand by for regeneration support

The Economy and Plus model will only operate in the following flows:

� Simplex Operation – single vessel operation. Multiple simplex units may be purchased to work together, however they will not function as one system as with the Deluxe model. A system lockout is available.

Simplex Softener

Tank Diameter

(in)

Media Height

(in)

Active Media (ft3)

Minimum Flow Rate

(GPM)1

Nominal Flow Rate

(GPM)2

Maximum Flow Rate

(GPM)3

Economy Valve Size

Plus & Deluxe

Valve Size

Capacity (K-grains)

PTCS_S09x40 09 22 0.8 0.9 2.4 4.8 1” 1” 24 PTCS_S12x52 12 31 2 1.6 6.0 12.0 1” 1” 60

PTCS_S14x65 14 34 3 2.1 9.0 18.0 1” 1” 90

PTCS_S16x65 16 34 4 2.8 12.0 24.0 1.5” 1” 120

PTCS_S18x65 18 34 5 3.5 15.0 30.0 1.5” 1.5” 150

PTCS_S21x62 21 32 6.5 4.8 19.5 39.0 NA 1.5” 195

PTCS_S24x72 24 34 9 6.3 27.0 54.0 NA 1.5” 270 PTCS_S30x72 30 37 15 9.8 45.0 90.0 NA 2” 450

PTCS_S36x72 36 34 20 14.1 60.0 120.0 NA 2” 600

PTCS_S42x72 42 32 26 19.2 78.0 156.0 NA 3” 780

PTCS_S48x72 48 34 36 25.1 108.0 216.0 NA 3” 1080 1Design Flow/ft2 (min) based on 2 gpm/ft2

2Design Flow/ft3 of media based on 3 gpm/ft3

3Design Flow/ft3 of media based on 6 gpm/ft3

These calculations are based on a Simplex system. Use the appropriate multiplier for Duplex, Triplex and Quadplex systems based on operational flow.

To calculate metrics: 1 inch equals 2.54 centimeter, 1 gallon per minute equals 3.79 liters per minute

Nominal Design Parameters

Configurations Simplex, Duplex, Triplex and Quadplex Inlet Pressure 30 psig minimum Inlet Temperature 65˚ F Sizing 3 gpm/ft3

Bed Depth* 30 to 38 inches of Siemens Water Technologies C-211 strong acid cation resin.

Freeboard* 33 to 37% of tank volume Capacities 30 Kgrains/ft3

Free Chlorine 0.5 ppm Regeneration 15 lb. NaCL/ft3

*9” diameter units have reduced bed height and freeboard

Flow Meter Options

Attachment 10

SECTION

PA

R

AG

R

AP

H

N U

M

BE

R

DESCRIPTION OF ITEM SUBMITTED

- P R

EC

O

N S

U

BM

IT

TA

LS

- S H

O P

D R

AW

IN

G S

- P R

O D

U C

T D

AT

A

- S

AM

PL

ES

- D

ES

IG

N

D

AT

A

- T

ES

T R

EP

O

R

TS

- C

ER

TI

FI

C

AT

ES

- M

FR

S

IN

ST

R

U C

TI

O

N S

- M

FR

S

FI

EL

D

R

EP

O R

T

- O &M

D

AT

A

- C

LO

SE

O

U T

SU

BM

IT

TA

LS

F

IO

FO

R

IN

FO

R

M

AT

IO

N

O N

LY

G A

- G O

VE

R

N M

EN

T

AP

PR

O

VE

D

D A

- D

ES

IG

N

ER

O

F R

EC

O

R D

A

PP

R O

VA

L

D A

/ G A

D

TR

D

IV

IS

IO

N

O F

TE

C

H N

IC

AL

R

ES

O U

R C

ES

D R

D

ES

IG

N

ER

O F

R

EC

O R

D

H

SB

H

EA

LT

H A

N D

S

AF

ET

Y

O

SB

SE

C U

R

IT

Y

P O

PR

O

JE

C T

O

FF

IC

ER

A E

- A R

C H

IT

EC

T / E

N G

IN

EE

R

Schedule X X X Task Order QC Plan X X X

Task Order APP Supplement X X X Activity Hazard Analysis X X X X Placard X X X

Water softener X X X Flow meter X X X Controller X X X Pipe X X X Fittings X X X Valves X X X

Hangers X X X Safety Data Sheets X X X Water Test X X X New Equipment Data Worksheet X X X

O & M Manuals X X X

Equipment Warranty Tag X X X

Replace Incinerator Water Softener, NIEHS, RTP, NC

CLASSIFICATION REVIEWING OFFICETYPE OF SUBMITTAL

TITLE AND LOCATION

SUBMITTAL REGISTER FORM TO 214-20

CONTRACT NUMBER DELIVERY ORDER

SOW Replace Incinerator Water Softener
Attachment 1. Project Area and Point of New Construction
Attachment 2. Existing ANCO Water Softening Units and Controller
Attachment 3. New Equipment Data Worksheet
Attachment 4. ANCO Water Softener Installation and Operating Manual
Attachment 5. USF C-211 UPS Ion Exchange Resin MSDS
Attachment 6. Brine Safe T Salt MSDS
Attachment 7. Vantage PTC Softeners
Attachment 8. Plan View of Project Area
Attachment 9. Softener Piping Schematic
Attachment 10. Submittal Register