This solicitation document requests proposals for the construction of an Aerospace Control Alert Facility and Alert Apron at Naval Air Station Joint Reserve Base New Orleans. The project includes construction of two aircraft shelters with drive-through capability, aircrew alert quarters with mission support and Alternate Command Post capabilities, and a secure entry control facility. An alert apron for two ready aircraft is required along with all associated utilities, site work, security upgrades, lighting and fencing. The contract will be a firm-fixed-price design-bid-build agreement with a total project magnitude between $25-100 million and a completion schedule of 1300 calendar days from award. The solicitation is unrestricted and open to all responsible sources. One or more items are subject to World Trade Organization Government Procurement Agreement and free trade agreements.
View the file
Other files for this federal contract opportunity
Show all 50
Alert Facility and Alert Apron has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NORTHCOM CONSTRUCT ALERT APRON/FACILITIES WON: 1323108/1621243
NAS JRB NEW ORLEANS, LOUISIANA B-3 DESIGN SUBMITTAL
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
02/14
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI C12.1 (2008) Electric Meters Code for Electricity Metering
ASTM INTERNATIONAL (ASTM)
ASTM B1 (2013) Standard Specification for Hard-Drawn Copper Wire
ASTM B8 (2011; R 2017) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2017; Errata 1-2 2017; INT 1 2017) National Electrical Safety Code
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2017; Errata 2017) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C80.1 (2005) American National Standard for Electrical Rigid Steel Conduit (ERSC)
ANSI C80.3 (2015) American National Standard for Electrical Metallic Tubing (EMT)
ANSI C80.5 (2015) American National Standard for Electrical Rigid Aluminum Conduit
SECTION 26 20 00 Page 1 michelle.contestabil Typewritten Text michelle.contestabil Typewritten Text
REVISION 1: AMENDMENT 0001
NEMA 250 (2014) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA BU 1.1 (2010) General Instructions for Proper Handling, Installation, Operation and Maintenance of Busway Rated 600 V or Less
NEMA FU 1 (2012) Low Voltage Cartridge Fuses
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2005; Errata 2008) Standard for Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 4 (2015) Application Guideline for Terminal Blocks
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)
NEMA MG 1 (2016; SUPP 2016) Motors and Generators
NEMA MG 10 (2017) Energy Management Guide for Selection and Use of Fixed Frequency Medium AC Squirrel-Cage Polyphase Induction Motors
NEMA MG 11 (1977; R 2012) Energy Management Guide for Selection and Use of Single Phase Motors
NEMA RN 1 (2005; R 2013) Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit
NEMA ST 20 (1992; R 1997) Standard for Dry-Type Transformers for General Applications
NEMA TC 2 (2013) Standard for Electrical Polyvinyl Chloride (PVC) Conduit
NEMA TC 3 (2016) Polyvinyl Chloride (PVC) Fittings for Use With Rigid PVC Conduit and Tubing
NEMA TP 1 (2002) Guide for Determining Energy Efficiency for Distribution Transformers
NEMA VE 1 (2017) Metal Cable Tray Systems
NEMA WD 1 (1999; R 2015) Standard for General Color Requirements for Wiring Devices
NEMA WD 6 (2016) Wiring Devices Dimensions
SECTION 26 20 00 Page 2
Specifications
NEMA Z535.4 (2011; R 2017) American National Standard for Product Safety Signs and Labels
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17)
National Electrical Code
NFPA 70E (2018; TIA 18-1; TIA 81-2) Standard for Electrical Safety in the Workplace
NFPA 780 (2017) Standard for the Installation of Lightning Protection Systems
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568-C.1 (2009; Add 2 2011; Add 1 2012) Commercial Building Telecommunications Cabling Standard
TIA-569 (2015d) Commercial Building Standard for Telecommunications Pathways and Spaces
TIA-607 (2011b) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.147 The Control of Hazardous Energy (Lock Out/Tag Out)
UNDERWRITERS LABORATORIES (UL)
UL 1 (2005; Reprint Aug 2017) UL Standard for Safety Flexible Metal Conduit
UL 1063 (2017) UL Standard for Safety Machine-Tool Wires and Cables
UL 1203 (2013; Reprint Apr 2018) UL Standard for Safety Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations
UL 1242 (2006; Reprint Mar 2014) Standard for Electrical Intermediate Metal Conduit -- Steel
UL 1449 (2014; Reprint Jul 2017) UL Standard for Safety Surge Protective Devices
UL 1561 (2011; Reprint Jun 2015) Dry-Type General
SECTION 26 20 00 Page 3
Purpose and Power Transformers
UL 1569 (2018) UL Standard for Safety Metal-Clad Cables
UL 1660 (2014) Liquid-Tight Flexible Nonmetallic Conduit
UL 1699 (2017) UL Standard for Safety Arc-Fault Circuit-Interrupters
UL 198M (2018) UL Standard for Mine-Duty Fuses
UL 20 (2010; Reprint Feb 2012) General-Use Snap Switches
UL 2043 (2013) Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces
UL 360 (2013; Reprint May 2018) UL Standard for Safety Liquid-Tight Flexible Metal Conduit
UL 4248-1 (2017) UL Standard for Safety Fuseholders
- Part 1: General Requirements
UL 4248-12 (2018) UL Standard for Safety Fuseholders
- Part 12: Class R
UL 44 (2018) UL Standard for Safety Thermoset-Insulated Wires and Cables
UL 467 (2013; Reprint Jun 2017) UL Standard for Safety Grounding and Bonding Equipment
UL 486A-486B (2018) UL Standard for Safety Wire Connectors
UL 486C (2018) UL Standard for Safety Splicing Wire Connectors
UL 489 (2016) UL Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures
UL 498 (2017; Reprint Nov 2017) UL Standard for Safety Attachment Plugs and Receptacles
UL 5 (2016) UL Standard for Safety Surface Metal Raceways and Fittings
UL 50 (2015) UL Standard for Safety Enclosures for Electrical Equipment, Non-Environmental Considerations
UL 506 (2017) UL Standard for Safety Specialty Transformers
SECTION 26 20 00 Page 4 michelle.contestabil Cross-Out michelle.contestabil Highlight
UL 508 (2018) UL Standard for Safety Industrial Control Equipment
UL 510 (2017) UL Standard for Safety Polyvinyl Chloride, Polyethylene and Rubber Insulating Tape
UL 514A (2013; Reprint Aug 2017) UL Standard for Safety Metallic Outlet Boxes
UL 514B (2012; Reprint Nov 2014) Conduit, Tubing and Cable Fittings
UL 514C (2014; Reprint Dec 2014) Nonmetallic Outlet Boxes, Flush-Device Boxes, and Covers
UL 5A (2015) Nonmetallic Surface Raceways and Fittings
UL 6 (2007; Reprint Nov 2014) Electrical Rigid Metal Conduit-Steel
UL 651 (2011; Reprint Jun 2016) UL Standard for Safety Schedule 40 and 80 Rigid PVC Conduit and Fittings
UL 67 (2018) UL Standard for Safety Panelboards
UL 674 (2011; Reprint May 2017) UL Standard for Safety Electric Motors and Generators for Use in Hazardous (Classified) Locations
UL 6A (2008; Reprint Nov 2014) Electrical Rigid Metal Conduit - Aluminum, Red Brass, and Stainless Steel
UL 719 (2015; Reprint Mar 2018) UL Standard for Safety Nonmetallic-Sheathed Cables
UL 797 (2007; Reprint Mar 2017) UL Standard for Safety Electrical Metallic Tubing -- Steel
UL 817 (2015; Reprint May 2017) UL Standard for Safety Cord Sets and Power-Supply Cords
UL 83 (2017) UL Standard for Safety Thermoplastic-Insulated Wires and Cables
UL 854 (2004; Reprint Nov 2014) Standard for Service-Entrance Cables
UL 857 (2009; Reprint Aug 2016) UL Standard for Safety Busways
UL 869A (2006) Reference Standard for Service Equipment
UL 870 (2016) UL Standard for Safety Wireways, SECTION 26 20 00 Page 5 michelle.contestabil Cross-Out
Auxiliary Gutters, and Associated Fittings
UL 943 (2016; Reprint Feb 2018) UL Standard for Safety Ground-Fault Circuit-Interrupters
UL 984 (1996; Reprint Sep 2005) Hermetic Refrigerant Motor-Compressors
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in
IEEE 100.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29.00 25 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00.
SD-02 Shop Drawings
Panelboards; G
Transformers; G
Busway; G
Cable trays; G
Motor control centers; G
Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation. Identify circuit terminals on wiring diagrams and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment. Indicate on the drawings adequate clearance for operation, maintenance, and replacement of operating equipment devices.
Wireways; G
Marking strips drawings; G
SD-03 Product Data
Receptacles; G
Circuit breakers; G
Switches; G
Transformers; G
Enclosed circuit breakers; G
SECTION 26 20 00 Page 6
Motor controllers; G
Manual motor starters; G
Metering; G
CATV outlets; G
Telecommunications Grounding Busbar; G
Surge protective devices; G
Include performance and characteristic curves.
SD-06 Test Reports
600-volt wiring test; G
Grounding system test; G
Transformer tests; G
Ground-fault receptacle test; G
SD-07 Certificates
Fuses; G
SD-09 Manufacturer's Field Reports
Transformer factory tests
SD-10 Operation and Maintenance Data
Electrical Systems, Data Package 5; G
Metering, Data Package 5; G
Submit operation and maintenance data in accordance with Section 01 78 23.00 25, OPERATION AND MAINTENANCE DATA and as specified herein.
1.4 QUALITY ASSURANCE
1.4.1 Fuses
Submit coordination data as specified in paragraph, FUSES of this section.
1.4.2 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" or "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
SECTION 26 20 00 Page 7
1.4.3 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.4.3.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.4.3.2 Material and Equipment Manufacturing Date
Products manufactured more than 3 years prior to date of delivery to site are not acceptable.
1.5 MAINTENANCE
1.6 WARRANTY
Provide equipment items supported by service organizations that are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
As a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70 for all materials, equipment, and devices.
2.2 CONDUIT AND FITTINGS
Conform to the following:
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
ANSI C80.1, UL 6.
SECTION 26 20 00 Page 8
2.2.1.2 Rigid Aluminum Conduit
ANSI C80.5, UL 6A.
2.2.2 Rigid Nonmetallic Conduit
PVC Type EPC-40, and EPC-80 in accordance with NEMA TC 2,UL 651.
2.2.3 Intermediate Metal Conduit (IMC)
UL 1242, zinc-coated steel only.
2.2.4 Electrical, Zinc-Coated Steel Metallic Tubing (EMT)
UL 797, ANSI C80.3.
2.2.5 Plastic-Coated Rigid Steel and IMC Conduit
NEMA RN 1, Type 40( 40 mils thick).
2.2.6 Flexible Metal Conduit
UL 1.
2.2.6.1 Liquid-Tight Flexible Metal Conduit, Steel
UL 360.
2.2.7 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit
UL 514B. Ferrous fittings: cadmium- or zinc-coated in accordance with
UL 514B.
2.2.7.1 Fittings for Rigid Metal Conduit and IMC
Threaded-type. Split couplings unacceptable.
2.2.7.2 Fittings for EMT
Steelcompression type.
2.2.8 Fittings for Rigid Nonmetallic Conduit
NEMA TC 3 for PVC, and UL 514B.
2.2.9 Liquid-Tight Flexible Nonmetallic Conduit
UL 1660.
2.3 SURFACE RACEWAY
2.3.1 Surface Metal Raceway
UL 5, two-piece painted steel, totally enclosed, snap-cover type.
2.3.2 Surface Nonmetallic Raceway
UL 5A, nonmetallic totally enclosed, snap-cover type.
SECTION 26 20 00 Page 9
2.4 BUSWAY
NEMA BU 1.1, UL 857. Provide the following:
a. Buses: copper.
b. Busways: rated 600 volts, 1200 continuous current amperes, three-phase, four-wire, and include integral or internal ground bus.
c. Short circuit rating: as indicated.
e. Enclosures: steel .
f. Hardware: plated or otherwise protected to resist corrosion.
g. Joints: one-bolt type with through-bolts, which can be checked for tightness without deenergizing system.
h. Maximum hot spot temperature rise at any point in busway at continuous rated load: do not exceed 55 degrees C above maximum ambient temperature of 40 degrees C in any position.
i. Internal barriers to prevent movement of superheated gases.
j. Coordinate proper voltage phasing of entire bus duct system, for example where busway interfaces with transformers, switchgear, switchboards, motor control centers, and other system components.
2.4.1 Feeder Busways
Provide ventilated, except that vertical busways within 6 feet of floors must be unventilated, low-impedance busway. Provide bus bars fully covered with insulating material, except at stabs. Provide an entirely polarized busway system.
2.4.2 Plug-In Busways
Unventilated type. Provide the following:
a. Plug-in units: circuit breaker-type.
b. Bus bars: covered with insulating material throughout, except at joints and other connection points.
c. A hook stick of suitable length for operating plug-in units from the floor.
2.5 CABLE TRAYS
NEMA VE 1. Provide the following:
a. Cable trays: form a wireway system, with a nominal depth as indicated.
b. Cable trays: constructed of steel that has been zinc-coated after fabrication.
c. Cable trays: include splice and end plates, dropouts, and miscellaneous hardware.
SECTION 26 20 00 Page 10
d. Edges, fittings, and hardware: finished free from burrs and sharp edges.
e. Fittings: ensure not less than load-carrying ability of straight tray sections and have manufacturer's minimum standard radius.
Radius of bends: as indicated.
2.5.1 Basket-Type Cable Trays
Provide size as indicated with maximum wire mesh spacing of 2 by 4 inch.
2.5.2 Trough-Type Cable Trays
Provide size as indicated.
2.5.3 Ladder-Type Cable Trays
Provide size as indicated with maximum rung spacing of 9 inches.
2.5.4 Channel-Type Cable Trays
Provide size as indicated. Provide trays with one-piece construction having slots spaced not more than 4 1/2 inches on centers.
2.5.5 Solid Bottom-Type Cable Trays
Provide size as indicated. Provide solid covers.
2.6 OPEN TELECOMMUNICATIONS CABLE SUPPORT
2.6.1 Open Top Cable Supports
Provide open top cable supports in accordance with UL 2043. Provide zinc-coated steelopen top cable supports.
2.6.2 Closed Ring Cable Supports
Provide closed ring cable supports in accordance with UL 2043. Provide zinc-coated steelclosed ring cable supports.
2.7 OUTLET BOXES AND COVERS
UL 514A, cadmium- or zinc-coated, if ferrous metal. UL 514C, if nonmetallic.
2.7.1 Floor Outlet Boxes
Provide the following:
a. Boxes: adjustable and concrete tight.
b. Each outlet: consisting of nonmetallic or cast-metal body with threaded openings, or sheet-steel body with knockouts for conduits, adjustable ring, and cover plate with 3/4 inch threaded plug.
c. Telecommunications outlets: consisting of flush, aluminum or stainless steel housing with a receptacle as specified and 1 inch bushed side opening.
SECTION 26 20 00 Page 11
d. Receptacle outlets: consisting of flush aluminum or stainless steel housing with duplex-type receptacle as specified herein.
e. Provide gaskets where necessary to ensure watertight installation.
f. Provide plugs with installation instructions to the Contracting Officer for 5 percent of outlet boxes for the capping of outlets upon removal of service fittings.
2.7.2 Outlet Boxes for Telecommunications System
Provide the following:
a. Standard type 4 inches square by 2 1/8 inches deep.
b. Outlet boxes for wall-mounted telecommunications outlets: 4 by 2 1/8 by 2 1/8 inches deep.
c. Depth of boxes: large enough to allow manufacturers' recommended conductor bend radii.
d. Outlet boxes for fiber optic telecommunication outlets: include a minimum 3/8 inch deep single or two gang plaster ring as shown and installed using a minimum 1 inch conduit system.
2.8 CABINETS, JUNCTION BOXES, AND PULL BOXES
Volume greater than 100 cubic inches, UL 50, hot-dip, zinc-coated, if sheet steel.
2.9 WIRES AND CABLES
Provide wires and cables in accordance applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Do not use wires and cables manufactured more than 12 months prior to date of delivery to site.
2.9.1 Conductors
Provide the following:
a. Conductor sizes and capacities shown are based on copper, unless indicated otherwise.
b. Conductors No. 8 AWG and larger diameter: stranded.
c. Conductors No. 10 AWG and smaller diameter: solid.
d. Conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3: stranded unless specifically indicated otherwise.
e. All conductors: copper.2.9.1.1 Aluminum Conductors
Provide aluminum conductors of AA-8000 series electrical grade aluminum alloy conductors. Type EC/1350 aluminum is not acceptable. If Contractor choosees to provide aluminum for conductors No. 4 AWG and larger diameter, Contractor is responsible for increasing conductor size to have same ampacity as copper size indicated; increasing conduit and pull box sizes to
SECTION 26 20 00 Page 12 accommodate larger size aluminum conductors in accordance with NFPA 70;
ensuring that pulling tension rating of aluminum conductor is sufficient;
providing panelboards that are UL listed for use with aluminum, and so labeled; relocating equipment, modifying equipment terminations, resizing equipment; and resolving problems that are direct results of providing aluminum conductors in lieu of copper.
2.9.1.2 Minimum Conductor Sizes
Provide minimum conductor size in accordance with the following:
a. Branch circuits: No. 12 AWG.
b. Class 1 remote-control and signal circuits: No. 14 AWG.
c. Class 2 low-energy, remote-control and signal circuits: No. 16 AWG.
d. Class 3 low-energy, remote-control, alarm and signal circuits: No. 22
AWG.
2.9.2 Color Coding
Provide color coding for service, feeder, branch, control, and signaling circuit conductors.
2.9.2.1 Ground and Neutral Conductors
Provide color coding of ground and neutral conductors as follows:
a. Grounding conductors: Green.
b. Neutral conductors: White.
c. Exception, where neutrals of more than one system are installed in same raceway or box, other neutrals color coding: white with a different colored (not green) stripe for each.
2.9.2.2 Ungrounded Conductors
Provide color coding of ungrounded conductors in different voltage systems as follows:
a. 208/120 volt, three-phase
(1) Phase A - black
(2) Phase B - red
(3) Phase C - blue
b. 480/277 volt, three-phase
(1) Phase A - brown
(2) Phase B - orange
(3) Phase C - yellow
c. 120/240 volt, single phase: Black and red
SECTION 26 20 00 Page 13
2.9.3 Insulation
Unless specified or indicated otherwise or required by NFPA 70, provide power and lighting wires rated for 600-volts, Type THWN/THHN conforming to UL 83, except that grounding wire may be type TW conforming to UL 83;
remote-control and signal circuits: Type TW or TF, conforming to UL 83.
Where lighting fixtures require 90-degree Centigrade (C) conductors, provide only conductors with 90-degree C insulation or better.
2.9.4 Bonding Conductors
ASTM B1, solid bare copper wire for sizes No. 8 AWG and smaller diameter;
ASTM B8, Class B, stranded bare copper wire for sizes No. 6 AWG and larger diameter.
2.9.4.1 Telecommunications Bonding Backbone (TBB)
Provide a copper conductor TBB in accordance with TIA-607 with No. 6 AWG minimum size, and sized at 2 kcmil per linear foot of conductor length up to a maximum size of 3/0 AWG. Provide insulated TBB with insulation as specified in the paragraph INSULATION and meeting the fire ratings of its pathway.
2.9.4.2 Bonding Conductor for Telecommunications
Provide a copper conductor Bonding Conductor for Telecommunications between the telecommunications main grounding busbar (TMGB) and the electrical service ground in accordance with TIA-607. Size the bonding conductor for telecommunications the same as the TBB.
2.9.5 Service Entrance Cables
Service Entrance (SE) and Underground Service Entrance (USE) Cables, UL 854.
2.9.6 Nonmetallic Sheathed Cable
UL 719, Type NM or NMC.
2.9.7 Wire and Cable for 400 Hertz (Hz) Circuits
Insulated copper conductors.
2.9.8 Metal-Clad Cable
UL 1569; NFPA 70, Type MC cable.
2.9.9 Mineral-Insulated, Metal-Sheathed Cable
UL listed; NFPA 70, Type MI cable. Do not use sheathing containing asbestos fibers.
2.9.10 Flat Conductor Cable
UL listed; NFPA 70, Type FCC.
2.9.11 Cable Tray Cable or Power Limited Tray Cable
UL listed; type TC or PLTC.
SECTION 26 20 00 Page 14 michelle.contestabil Cross-Out michelle.contestabil Cross-Out michelle.contestabil Highlight
2.9.12 Cord Sets and Power-Supply Cords
UL 817.
2.10 SPLICES AND TERMINATION COMPONENTS
UL 486A-486B for wire connectors and UL 510 for insulating tapes.
Connectors for No. 10 AWG and smaller diameter wires: insulated, pressure-type in accordance with UL 486A-486B or UL 486C (twist-on splicing connector). Provide solderless terminal lugs on stranded conductors.
2.11 DEVICE PLATES
Provide the following:
a. UL listed, one-piece device plates for outlets to suit the devices installed.
b. For metal outlet boxes, plates on unfinished walls: zinc-coated sheet steel or cast metal having round or beveled edges.
c. For nonmetallic boxes and fittings, other suitable plates may be provided.
e. Plates on finished walls: satin finish stainless steel or brushed-finish aluminum, minimum 0.03 inch thick.
f. Screws: machine-type with countersunk heads in color to match finish of plate.
g. Sectional type device plates are not be permitted.
h. Plates installed in wet locations: gasketed and UL listed for "wet locations."
2.12 SWITCHES
2.12.1 Toggle Switches
NEMA WD 1, UL 20, single pole, double pole, three-way, and four-way, totally enclosed with bodies of thermoplastic or thermoset plastic and mounting strap with grounding screw. Include the following:
a. Handles: white thermoplastic.
b. Wiring terminals: screw-type, side-wired.
c. Contacts: silver-cadmium and contact arm - one-piece copper alloy.
d. Switches: rated quiet-type ac only, 120/277 volts, with current rating and number of poles indicated.
2.12.2 Switch with Red Pilot Handle
NEMA WD 1. Provide the following:
a. Pilot lights that are integrally constructed as a part of the switch's handle.
SECTION 26 20 00 Page 15
b. Pilot light color: red and illuminate whenever the switch is closed or "on".
c. Pilot lighted switch: rated 20 amps and 120 volts or 277 volts as indicated.
d. The circuit's neutral conductor to each switch with a pilot light.
2.12.3 Breakers Used as Switches
For 120- and 277-Volt fluorescent fixtures, mark breakers "SWD" in accordance with UL 489.
2.12.4 Disconnect Switches
NEMA KS 1. Provide heavy duty-type switches where indicated, where switches are rated higher than 240 volts, and for double-throw switches.
Utilize Class R fuseholders and fuses for fused switches, unless indicated otherwise. Provide horsepower rated for switches serving as the motor-disconnect means. Provide switches in NEMA, enclosure as indicated per NEMA ICS 6.
2.13 FUSES
NEMA FU 1. Provide complete set of fuses for each fusible switch panel and control center. Coordinate time-current characteristics curves of fuses serving motors or connected in series with circuit breakers or other circuit protective devices for proper operation. Submit coordination data for approval. Provide fuses with a voltage rating not less than circuit voltage.
2.13.1 Fuseholders
Provide in accordance with UL 4248-1.
2.13.2 Cartridge Fuses, Current Limiting Type (Class R)
UL 198M, Class time-delay type. Provide only Class R associated fuseholders in accordance with UL 4248-12.
2.13.3 Cartridge Fuses, High-Interrupting Capacity, Current Limiting Type (Classes J, L, and CC)
UL 198M, Class J for zero to 600 amperes, Class L for 601 to 6,000 amperes, and Class CC for zero to 30 amperes.
2.13.4 Cartridge Fuses, Current Limiting Type (Class T)
UL 198M, Class T for zero to 1,200 amperes, 300 volts; and zero to 800 amperes, 600 volts.
2.14 RECEPTACLES
Provide the following:
a. UL 498, hard use (also designated heavy-duty), grounding-type.
b. Ratings and configurations: as indicated.
SECTION 26 20 00 Page 16
c. Bodies: white as per NEMA WD 1.
d. Face and body: thermoplastic supported on a metal mounting strap.
e. Dimensional requirements: per NEMA WD 6.
f. Screw-type, side-wired wiring terminals or of the solderless pressure type having suitable conductor-release arrangement.
g. Grounding pole connected to mounting strap.
h. The receptacle: containing triple-wipe power contacts and double or triple-wipe ground contacts.
2.14.1 Switched Duplex Receptacles
Provide separate terminals for each ungrounded pole. Top receptacle:
switched when installed.
2.14.2 Weatherproof Receptacles
Provide receptacles, UL listed for use in "wet locations". Include cast metal box with gasketed, hinged, lockable and weatherproof while-in-use, polycarbonate, UV resistant/stabilized cover plate.
2.14.3 Ground-Fault Circuit Interrupter Receptacles
UL 943, duplex type for mounting in standard outlet box. Provide device capable of detecting current leak of 6 milliamperes or greater and tripping per requirements of UL 943 for Class A ground-fault circuit interrupter devices. Provide screw-type, side-wired wiring terminals or pre-wired (pigtail) leads.
2.14.4 Special Purpose Receptacles
Receptacles serving in indicated places are special purpose. Provide in ratings indicated. Furnish one matching plug with each receptacle.
2.14.5 Plugs
Provide heavy-duty, rubber-covered three-, four-, or five-wire cord of required size, install plugs thereon, and attach to equipment. Provide UL listed plugs with receptacles, complete with grounding blades. Where equipment is not available, turn over plugs and cord assemblies to the Government.
2.14.6 Range Receptacles
NEMA 14-50 configuration, rated 50 amperes, 125/250 volts. Furnish one matching plug with each receptacle.
2.14.7 Dryer Receptacles
NEMA 14-30 configuration, rated 30 amperes, 125/250 volts. Furnish one matching plug with each receptacle.
SECTION 26 20 00 Page 17
2.14.8 Tamper-Resistant Receptacles
Provide duplex receptacle with mechanical sliding shutters that prevent the insertion of small objects into its contact slots.
2.15 PANELBOARDS
Provide panelboards in accordance with the following:
a. UL 67 and UL 50 having a short-circuit current rating as indicated.
b. Panelboards for use as service disconnecting means: additionally conform to UL 869A.
c. Panelboards: circuit breaker-equipped.
d. Designed such that individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining clearances as required by UL.
e. "Specific breaker placement" is required in panelboards to match the breaker placement indicated in the panelboard schedule on the drawings.
f. Use of "Subfeed Breakers" is not acceptable unless specifically indicated otherwise.
g. Main breaker: "separately" mounted "above" branch breakers.
h. Where "space only" is indicated, make provisions for future installation of breakers.
i. Directories: indicate load served by each circuit in panelboard.
j. Directories: indicate source of service to panelboard (e.g., Panel PA served from Panel MDP).
l. Type directories and mount in holder behind transparent protective covering.
n. Panelboard nameplates: provided in accordance with paragraph FIELD
FABRICATED NAMEPLATES.
2.15.1 Enclosure
Provide panelboard enclosure in accordance with the following:
a. UL 50.
b. Cabinets mounted outdoors or flush-mounted: hot-dipped galvanized after fabrication.
c. Cabinets: painted in accordance with paragraph PAINTING.
d. Outdoor cabinets: NEMA 3R raintight with conduit hubs welded to the cabinet.
e. Front edges of cabinets: form-flanged or fitted with structural shapes welded or riveted to the sheet steel, for supporting the panelboard front.
SECTION 26 20 00 Page 18
f. All cabinets: fabricated such that no part of any surface on the finished cabinet deviates from a true plane by more than 1/8 inch.
g. Holes: provided in the back of indoor surface-mounted cabinets, with outside spacers and inside stiffeners, for mounting the cabinets with a 1/2 inch clear space between the back of the cabinet and the wall surface.
h. Flush doors: mounted on hinges that expose only the hinge roll to view when the door is closed.
i. Each door: fitted with a combined catch and lock, except that doors over 24 inches long provided with a three-point latch having a knob with a T-handle, and a cylinder lock.
j. Keys: two provided with each lock, with all locks keyed alike.
k. Finished-head cap screws: provided for mounting the panelboard fronts on the cabinets.
2.15.2 Panelboard Buses
Support bus bars on bases independent of circuit breakers. Design main buses and back pans so that breakers may be changed without machining, drilling, or tapping. Provide isolated neutral bus in each panel for connection of circuit neutral conductors. Provide separate ground bus identified as equipment grounding bus per UL 67 for connecting grounding conductors; bond to steel cabinet. In addition to equipment grounding bus, provide second "isolated" ground bus, where indicated.
2.15.2.1 Panelboard Neutrals for Non-Linear Loads
Provide in accordance with the following:.
a. UL listed, with panelboard type specifically UL heat rise tested for use on non-linear loads.
b. Panelboard: heat rise tested in accordance with UL 67, except with the neutral assembly installed and carrying 200 percent of the phase bus current during testing.
c. Verification of the testing procedure: provided upon request.
d. Two neutral assemblies paralleled together with cable is not acceptable.
e. Nameplates for panelboard rated for use on non-linear loads: marked "SUITABLE FOR NON-LINEAR LOADS" and in accordance with paragraph FIELD
FABRICATED NAMEPLATES.
f. Provide a neutral label with instructions for wiring the neutral of panelboards rated for use on non-linear loads.
2.15.3 Circuit Breakers
UL 489,thermal magnetic or solid state type having a minimum short-circuit current rating equal to the short-circuit current rating of the panelboard in which the circuit breaker will be mounted. Breaker terminals: UL listed as suitable for type of conductor provided. Where indicated on the
SECTION 26 20 00 Page 19 drawings, provide circuit breakers with shunt trip devices. Series rated circuit breakers and plug-in circuit breakers are unacceptable.
2.15.3.1 Multipole Breakers
Provide common trip-type with single operating handle. Design breaker such that overload in one pole automatically causes all poles to open. Maintain phase sequence throughout each panel so that any three adjacent breaker poles are connected to Phases A, B, and C, respectively.
2.15.3.2 Circuit Breaker With Ground-Fault Circuit Interrupter
UL 943 and NFPA 70. Provide with "push-to-test" button, visible indication of tripped condition, and ability to detect and trip on current imbalance of 6 milliamperes or greater per requirements of UL 943 for Class A ground-fault circuit interrupter.
2.15.3.3 Circuit Breakers for HVAC Equipment
Provide circuit breakers for HVAC equipment having motors (group or individual) marked for use with HACR type and UL listed as HACR type.
2.15.3.4 Arc-Fault Circuit Interrupters
UL 489, UL 1699 and NFPA 70. Molded case circuit breakers: rated as indicated. Provide with "push-to-test" button.
2.15.4 400 Hz Panelboard and Breakers
Provide panelboards and breakers for use on 400 Hz systems rated and labeled "400 Hz."
2.16 ENCLOSED CIRCUIT BREAKERS
UL 489. Individual molded case circuit breakers with voltage and continuous current ratings, number of poles, overload trip setting, and short circuit current interrupting rating as indicated. Enclosure type as indicated. Provide solid neutral.
2.17 MOTOR SHORT-CIRCUIT PROTECTOR (MSCP)
Motor short-circuit protectors, also called motor circuit protectors (MCPs): UL 508 and UL 489, and provided as shown. Provide MSCPs that consist of an adjustable instantaneous trip circuit breaker used only in conjunction with a combination motor controller which provides coordinated motor branch-circuit overload and short-circuit protection. Rate MSCPs in accordance with the requirements of NFPA 70.
2.18 TRANSFORMERS
Provide transformers in accordance with the following:
a. NEMA ST 20, general purpose, dry-type, self-cooled, ventilated.
b. Provide transformers in NEMA 1 enclosure.
c. Transformer insulation system:
SECTION 26 20 00 Page 20
(1) 220 degrees C insulation system for transformers 15 kVA and greater, with temperature rise not exceeding 115 degrees C under full-rated load in maximum ambient of 40 degrees C.
(2) 180 degrees C insulation for transformers rated 10 kVA and less, with temperature rise not exceeding 115 degrees C under full-rated load in maximum ambient of 40 degrees C.
e. Transformer of 115 degrees C temperature rise: capable of carrying continuously 115 percent of nameplate kVA without exceeding insulation rating.
g. Transformers: quiet type with maximum sound level at least 3 decibels less than NEMA standard level for transformer ratings indicated.
2.18.1 Specified Transformer Efficiency
Transformers, indicated and specified with: 480V primary, 80 degrees C or 115 degrees C temperature rise, kVA ratings of 37.5 to 100 for single phase or 30 to 500 for three phase, energy efficient type. Minimum efficiency, based on factory test results: not be less than NEMA Class 1 efficiency as defined by NEMA TP 1.
2.18.2 Transformers With Non-Linear Loads
Provide transformers for non-linear loads in accordance with the following:
a. Transformer insulation: UL recognized 220 degrees C system. Neither the primary nor the secondary temperature is allowed to exceed 220 degrees C at any point in the coils while carrying their full rating of non-sinusoidal load.
b. Transformers are to be UL listed and labeled for K-Factor rating as indicated in accordance with UL 1561.
c. Transformers evaluated by the UL K-Factor evaluation: listed for 115 degrees C average temperature rise only.
d. Transformers with K-Factor ratings with temperature rise of 150 degrees C rise are not acceptable.
e. K-Factor rated transformers impedance: allowed range of 3 percent to 5 percent, with a minimum reactance of 2 percent to prevent excessive neutral current when supplying loads with large amounts of third harmonic.
2.19 MOTORS
Provide motors in accordance with the following:
a. NEMA MG 1
b. Hermetic-type sealed motor compressors: Also comply with UL 984.
c. Provide the size in terms of HP, or kVA, or full-load current, or a combination of these characteristics, and other characteristics, of each motor as indicated or specified.
d. Determine specific motor characteristics to ensure provision of
SECTION 26 20 00 Page 21 correctly sized starters and overload heaters.
e. Rate motors for operation on 208-volt, 3-phase circuits with a terminal voltage rating of 200 volts, and those for operation on 480-volt, 3-phase circuits with a terminal voltage rating of 460 volts.
f. Use motors designed to operate at full capacity with voltage variation of plus or minus 10 percent of motor voltage rating.
g. Unless otherwise indicated, use continuous duty type motors if rated 1 HP and above.
h. Where fuse protection is specifically recommended by the equipment manufacturer, provide fused switches in lieu of non-fused switches indicated.
2.19.1 High Efficiency Single-Phase Motors
Single-phase fractional-horsepower alternating-current motors: high efficiency types corresponding to the applications listed in NEMA MG 11.
In exception, for motor-driven equipment with a minimum seasonal or overall efficiency rating, such as a SEER rating, provide equipment with motor to meet the overall system rating indicated.
2.19.2 Premium Efficiency Polyphase Motors
Select polyphase motors based on high efficiency characteristics relative to typical characteristics and applications as listed in NEMA MG 10. In addition, continuous rated, polyphase squirrel-cage medium induction motors must meet the requirements for premium efficiency electric motors in accordance with NEMA MG 1, including the NEMA full load efficiency ratings. In exception, for motor-driven equipment with a minimum seasonal or overall efficiency rating, such as a SEER rating, provide equipment with motor to meet the overall system rating indicated.
2.19.3 Motor Sizes
Provide size for duty to be performed, not exceeding the full-load nameplate current rating when driven equipment is operated at specified capacity under most severe conditions likely to be encountered. When motor size provided differs from size indicated or specified, make adjustments to wiring, disconnect devices, and branch circuit protection to accommodate equipment actually provided. Provide controllers for motors rated 1-hp and above with electronic phase-voltage monitors designed to protect motors from phase-loss, undervoltage, and overvoltage. Provide protection for motors from immediate restart by a time adjustable restart relay.
2.19.4 Wiring and Conduit
Provide internal wiring for components of packaged equipment as an integral part of the equipment. Provide power wiring and conduit for field-installed equipment as specified herein. Power wiring and conduit:
conform to the requirements specified herein. Control wiring: provided under, and conform to, the requirements of the section specifying the associated equipment.
2.20 MOTOR CONTROLLERS
Provide motor controllers in accordance with the following:
SECTION 26 20 00 Page 22
a. UL 508, NEMA ICS 1, and NEMA ICS 2,.
b. Provide controllers with thermal overload protection in each phase, and one spare normally open auxiliary contact, and one spare normally closed auxiliary contact.
c. Provide controllers for motors rated 1-hp and above with electronic phase-voltage monitors designed to protect motors from phase-loss, undervoltage, and overvoltage.
d. Provide protection for motors from immediate restart by a time adjustable restart relay.
e. When used with pressure, float, or similar automatic-type or maintained-contact switch, provide a hand/off/automatic selector switch with the controller.
f. Connections to selector switch: wired such that only normal automatic regulatory control devices are bypassed when switch is in "hand" position.
g. Safety control devices, such as low and high pressure cutouts, high temperature cutouts, and motor overload protective devices: connected in motor control circuit in "hand" and "automatic" positions.
h. Control circuit connections to hand/off/automatic selector switch or to more than one automatic regulatory control device: made in accordance with indicated or manufacturer's approved wiring diagram.
i. Provide selector switch with the means for locking in any position.
j. Provide a disconnecting means, capable of being locked in the open position, for the motor that is located in sight from the motor location and the driven machinery location. As an alternative, provide a motor controller disconnect, capable of being locked in the open position, to serve as the disconnecting means for the motor if it is in sight from the motor location and the driven machinery location.
l. Overload protective devices: provide adequate protection to motor windings; be thermal inverse-time-limit type; and include manual reset-type pushbutton on outside of motor controller case.
m. Cover of combination motor controller and manual switch or circuit breaker: interlocked with operating handle of switch or circuit breaker so that cover cannot be opened unless handle of switch or circuit breaker is in "off" position.
o. Provide controllers in hazardous locations with classifications as indicated.
2.20.1 Control Wiring
Provide control wiring in accordance with the following:
a. All control wire: stranded tinned copper switchboard wire with 600-volt flame-retardant insulation Type SIS meeting UL 44, or Type MTW meeting UL 1063, and passing the VW-1 flame tests included in those standards.
SECTION 26 20 00 Page 23
b. Hinge wire: Class K stranding.
c. Current transformer secondary leads: not smaller than No. 10 AWG.
d. Control wire minimum size: No. 14 AWG.
e. Power wiring for 480-volt circuits and below: the same type as control wiring with No. 12 AWG minimum size.
f. Provide wiring and terminal arrangement on the terminal blocks to permit the individual conductors of each external cable to be terminated on adjacent terminal points.
2.20.2 Control Circuit Terminal Blocks
Provide control circuit terminal blocks in accordance with the following:
a. NEMA ICS 4.
b. Control circuit terminal blocks for control wiring: molded or fabricated type with barriers, rated not less than 600 volts.
c. Provide terminals with removable binding, fillister or washer head screw type, or of the stud type with contact and locking nuts.
d. Terminals: not less than No. 10 in size with sufficient length and space for connecting at least two indented terminals for 10 AWG conductors to each terminal.
e. Terminal arrangement: subject to the approval of the Contracting Officer with not less than four (4) spare terminals or 10 percent, whichever is greater, provided on each block or group of blocks.
f. Modular, pull apart, terminal blocks are acceptable provided they are of the channel or rail-mounted type.
g. Submit data showing that any proposed alternate will accommodate the specified number of wires, are of adequate current-carrying capacity, and are constructed to assure positive contact between current-carrying parts.
2.20.2.1 Types of Terminal Blocks
a. Short-Circuiting Type: Short-circuiting type terminal blocks:
furnished for all current transformer secondary leads with provision for shorting together all leads from each current transformer without first opening any circuit. Terminal blocks: comply with the requirements of paragraph CONTROL CIRCUIT TERMINAL BLOCKS above.
b. Load Type: Load terminal blocks rated not less than 600 volts and of adequate capacity: provided for the conductors for NEMA Size 3 and smaller motor controllers and for other power circuits, except those for feeder tap units. Provide terminals of either the stud type with contact nuts and locking nuts or of the removable screw type, having length and space for at least two indented terminals of the size required on the conductors to be terminated. For conductors rated more than 50 amperes, provide screws with hexagonal heads. Conducting parts between connected terminals must have adequate contact surface and
SECTION 26 20 00 Page 24 cross-section to operate without overheating. Provide eEach connected terminal with the circuit designation or wire number placed on or near the terminal in permanent contrasting color.
2.20.3 Control Circuits
Control circuits: maximum voltage of 120 volts derived from control transformer in same enclosure. Transformers: conform to UL 506, as applicable. Transformers, other than transformers in bridge circuits:
provide primaries wound for voltage available and secondaries wound for correct control circuit voltage. Size transformers so that 80 percent of rated capacity equals connected load. Provide disconnect switch on primary side. Provide fuses in each ungrounded primary feeder. Provide one fused secondary lead with the other lead grounded.
2.20.4 Enclosures for Motor Controllers
NEMA ICS 6.
2.20.5 Multiple-Speed Motor Controllers and Reversible Motor Controllers
Across-the-line-type, electrically and mechanically interlocked.
Multiple-speed controllers: include compelling relays and multiple-button, station-type with pilot lights for each speed.
2.20.6 Pushbutton Stations
Provide with "start/stop" momentary contacts having one normally open and one normally closed set of contacts, and red lights to indicate when motor is running. Stations: heavy duty, oil-tight design.
2.20.7 Pilot and Indicating Lights
Provide LED cluster lamps.
2.21 MANUAL MOTOR STARTERS (MOTOR RATED SWITCHES)
Single pole designed for surface mounting with overload protection and pilot lights.
2.21.1 Pilot Lights
Provide yoke-mounted, seven element LED cluster light module. Color: red.
2.22 LOCKOUT REQUIREMENTS
Provide disconnecting means capable of being locked out for machines and other equipment to prevent unexpected startup or release of stored energy in accordance with 29 CFR 1910.147. Comply with requirements of Division 23, "Mechanical" for mechanical isolation of machines and other equipment.
2.23 TELECOMMUNICATIONS SYSTEM
Provide system of telecommunications wire-supporting structures (pathway), including: outlet boxes, conduits with pull wires cable trays, and other accessories for telecommunications outlets and pathway in accordance with TIA-569 and as specified herein. Additional telecommunications requirements are specified in Section 27 10 00, BUILDING TELECOMMUNICATIONS
CABLING SYSTEM.
SECTION 26 20 00 Page 25
2.24 COMMUNITY ANTENNA TELEVISION (CATV) SYSTEM
Additional CATV requirements are specified in Section 27 54 00.00 20, COMMUNITY ANTENNA TELEVISION (CATV) SYSTEMS.
2.24.1 Backboards
Coordinate CATV backboard requirements with telecommunications backboard requirements as specified in Section 27 10 00, BUILDING TELECOMMUNICATIONS
CABLING.
2.25 GROUNDING AND BONDING EQUIPMENT
2.25.1 Ground Rods
UL 467. Ground rods: copper-clad steel, with minimum diameter of 3/4 inch and minimum length 10 feet. Sectional ground rods are permitted.
2.25.2 Ground Bus
Copper ground bus: provided in the electrical equipment rooms as indicated.
2.25.3 Telecommunications and CATVGrounding Busbar
Provide corrosion-resistant grounding busbar suitable for indoor installation in accordance with TIA-607. Busbars: plated for reduced contact resistance. If not plated, clean the busbar prior to fastening the conductors to the busbar and apply an anti-oxidant to the contact area to control corrosion and reduce contact resistance. Provide a telecommunications main grounding busbar (TMGB) in the telecommunications entrance facility and a (TGB) in all other telecommunications rooms and equipment rooms. The telecommunications main grounding busbar (TMGB) and the telecommunications grounding busbar (TGB): sized in accordance with the immediate application requirements and with consideration of future growth. Provide telecommunications grounding busbars with the following:
a. Predrilled copper busbar provided with holes for use with standard sized lugs,
b. Minimum dimensions of 0.25 in thick by 4 in wide for the TMGB and 2 in wide for TGBs with length as indicated;
c. Listed by a nationally recognized testing laboratory.
2.26 HAZARDOUS LOCATIONS
Electrical materials, equipment, and devices for installation in hazardous locations, as defined by NFPA 70: specifically approved by Underwriters' Laboratories, Inc., or Factory Mutual for particular "Class," "Division," and "Group" of hazardous locations involved. Boundaries and classifications of hazardous locations: as indicated. Equipment in hazardous locations: comply with UL 1203 for electrical equipment and industrial controls and UL 674 for motors.
2.27 MANUFACTURER'S NAMEPLATE
Provide on each item of equipment a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be
SECTION 26 20 00 Page 26 acceptable.
2.28 FIELD FABRICATED NAMEPLATES
Provide field fabricated nameplates in accordance with the following:
a. ASTM D709.
b. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified or as indicated on the drawings.
c. Each nameplate inscription: identify the function and, when applicable, the position.
d. Nameplates: melamine plastic, 0.125 inch thick, white with black center core.
e. Provide red laminated plastic label with white center core where indicated.
f. Surface: matte finish. Corners: square. Accurately align lettering and engrave into the core.
g. Minimum size of nameplates: one by 2.5 inches.
h. Lettering size and style: a minimum of 0.25 inch high normal block style.
2.29 WARNING SIGNS
Provide warning signs for flash protection in accordance with NFPA 70E and NEMA Z535.4 for switchboards, panelboards, industrial control panels, and motor control centers that are in other than dwelling occupancies and are likely to require examination, adjustment, servicing, or…