This document is a solicitation for a Design-Build Design-Bid-Build Indefinite Delivery Indefinite Quantity Multiple Award Construction Contract for Projects, Primarily Located at Rota, Spain and Worldwide. The solicitation is seeking contractors to provide construction services for projects located primarily at Rota, Spain and other worldwide locations. The contract will have multiple awardees and will utilize both Design-Build and Design-Bid-Build approaches for individual task orders. Task orders will be issued on an IDIQ basis for construction projects over the lifetime of the multiple award contract. The Naval Facilities Engineering Command is the contracting agency.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-811 Port Operations Facilities 1561956
SECTION 28 10 05
ELECTRONIC SECURITY SYSTEMS (ESS)
05/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM B32 (2008; R 2014) Standard Specification for Solder Metal
ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.23 (2010) Electromagnetic Locks
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C2 (2017; Errata 1-2 2017; INT 1 2017) National Electrical Safety Code
INTELLIGENCE COMMUNITY STANDARD (ICS)
ICS 705-1 (2010) Physical and Technical Security Standard for Sensitive Compartmented Information Facilities
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)
ANSI ISO/IEC 7816 (R 2009) Identification Cards - Integrated Circuit Cards
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2014) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2005; Errata 2008) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and
SECTION 28 10 05 Page 1
Systems: Enclosures
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14) National Electrical Code
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)
NIST FIPS 201-2 (2013) Personal Identity Verification (PIV) of Federal Employees and Contractors
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568-C.2 (2009; Errata 2010; Add 2 2014; Add 1 2016) Balanced Twisted-Pair Telecommunications Cabling and Components Standards
U.S. DEPARTMENT OF DEFENSE (DOD)
DODI 8500.01 (2014) Cybersecurity
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
47 CFR 15 Radio Frequency Devices
UNDERWRITERS LABORATORIES (UL)
UL 1037 (2016; Reprint Sep 2017) UL Standard for Safety Antitheft Alarms and Devices
UL 1076 (2018) UL Standard for Safety Proprietary Burglar Alarm Units and Systems
UL 1610 (2016) UL Standard for Safety Central-Station Burglar-Alarm Units
UL 294 (2018; Reprint Oct 2018) UL Standard for Safety Access Control System Units
UL 437 (2013; Reprint Oct 2017) UL Standard for Safety Key Locks
UL 634 (2007; Reprint Mar 2015) Connectors and Switches for Use with Burglar-Alarm Systems
UL 639 (2007; Reprint May 2012) Standard for Intrusion Detection Units
UL 681 (2014) Installation and Classification of Burglar and Holdup Alarm Systems
UL 796 (2016) UL Standard for Safety Printed-Wiring Boards
SECTION 28 10 05 Page 2
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
Naval Facilities Engineering Command will approve submittals requiring special review in this section.
SD-02 Shop Drawings
ESS Components; G
Overall System Schematic; G
SD-03 Product Data
Premise Control Unit; G
Detection Sensors; G
Access Control Unit; G
Access Control Devices; G
Communications Interface Devices; G
Network Switch; G
ESS Transmission; G
Batteries; G
Component Enclosure; G
SD-05 Design Data
Backup Battery Capacity Calculations; G
Access Control Throughput Rates; G
SD-07 Certificates
Contractor Qualifications; G
Instructor Qualifications; G
SD-10 Operation and Maintenance Data
Training Plan; G
Training Content; G
ESS Components and ESS Software: Data Package 4; G
ESS Software and ESS Components: Data Package 4; G
SECTION 28 10 05 Page 3
Submit data package in accordance with Section 01 78 23
OPERATION AND MAINTENANCE DATA
SD-11 Closeout Submittals
As-Built Drawings; G
1.3 QUALITY ASSURANCE
1.3.1 Regulatory Requirements
The advisory provisions in each of the publications referred to in this specification are mandatory. Interpret these publications as though the word "must" has been substituted for "should" wherever it appears.
Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer.
Equipment, materials, installation, and workmanship must be in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.3.2 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening, and have been utilized in applications of equipment and materials under similar circumstances and of similar size.
b. Have been available on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer.
d. Provide commercial off-the-shelf (COTS) products in which the manufacturer allows a network of qualified distributors to sell, install, integrate, maintain, and repair the hardware and software products that make up the system.
1.3.2.1 Alternative Qualifications
Products having less than a 2 year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.3.2.2 Material and Equipment Manufacturing Date
Products manufactured more than one year prior to date of delivery to the site are not acceptable.
SECTION 28 10 05 Page 4
1.3.2.3 Product Safety
System components are to conform to applicable rules and requirements of NFPA 70 . Equip system components with instruction stickers including warnings and cautions describing physical safety, and special or important procedures to be followed in operating and servicing system equipment.
1.3.3 Shop Drawings
1.3.3.1 ESS Components
Submit the ESS Components, Data Package 4 with the ESS Software submittal package in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA.
Submit drawings that clearly and completely indicate each ESS component function that includes:
a. Termination device points
b. Interconnections required for system operation
c. Interconnections between modules and devices
d. Proposed wireway or conduit systems to be used including:
(1) Locations
(2) Sizes
(3) Types
e. Drawings showing:
(1) Device locations and spacing
(2) Mounting and positioning details
(3) Riser Diagrams with cable sizes and types
(4) Bill of Materials (Device make, model and quantities)
(5) Alarm and access control zones
(6) Spare capacity
1.3.3.2 Overall System Schematic
Indicate the relationship of integrated components on one-line diagram and show:
a. Power source
b. System controls
c. Impedance matches
d. Interconnecting wire data including:
(1) Number
SECTION 28 10 05 Page 5
(2) Size
(3) Identification
(4) Maximum lengths
1.3.4 Evidence of Experience and Qualifications
1.3.4.1 Contractor Qualifications
The installation of the Electronic Security System must be performed by an Approved U.S. Security Contractor, certified to work on Lenel systems.
Submit experience and certified qualifications data prior to installation. Show that specific installers who will perform the work have a minimum of 2 years of experience successfully installing ESS of the same type and similar design as specified. Include the names, locations, and points of contact of at least two installations of similar type and design as specified in this document where the installer has installed such systems. Indicate the type of each system installed. Certify that each system has performed satisfactorily in the manner intended for a period of at least 12 months.
1.3.4.2 Instructor Qualifications
The installation of the Electronic Security System must be performed by an Approved U.S. Security Contractor, certified to work on Lenel systems.
Submit the instructor's experience and certified qualifications data prior to installation. Show that the instructor has received a minimum of 24 hours of ESS training from a technical organization such as the National Burglar and Fire Alarm Association, and 2 years experience in installing the specified ESS type.
1.4 Environmental Conditions
1.4.1 Interior Conditions
Equipment installed in environmentally protected interior areas must meet performance requirements specified for the following ambient conditions:
1.4.1.1 Temperature
0 to 50 degrees C. Components installed in unheated security protected areas must meet performance requirements for temperatures as low as minus 17 degrees C
1.4.1.2 Pressure
Sea level to 4573 m above sea level
1.4.1.3 Relative Humidity
5 to 95 percent
1.4.1.4 Fungus
Components must be constructed of nonfungus nutrient materials or be treated to inhibit fungus growth
SECTION 28 10 05 Page 6
1.4.1.5 Acoustical Noise
Components must be suitable for use in high noise areas above 100 dB, without adversely affecting their performance
1.4.2 Exterior Conditions
Components in enclosures must meet performance requirements when exposed to the following ambient conditions:
1.4.2.1 Temperature
Minus 32 to 60 degrees C
1.4.2.2 Pressure
Sea level to 4573 m above sea level
1.4.2.3 Solar Radiation
Six hours of solar radiation per day at dry bulb temperature of 60 degrees C including 4 hours of solar radiation at 0.00112 watts per square mm
1.4.2.4 Rain
50 mm per hour and 125 mm per hour cyclic with wind plus one period of 300 mm per hour
1.4.2.5 Humidity
5 to 95 percent
1.4.2.6 Salt Fog
Salt atmosphere with 5 percent salinity
1.4.2.7 Wind
Continual velocity up to 80 kmph with gusts to 106 kmph, except that fence sensors must detect intrusions up to 56 kmph
1.4.2.8 Acoustical Noise
Components must be suitable for use in high noise areas above 110 dB without adversely affecting their performance. Examples areas include flight lines, runup pads, and generator sites.
1.5 SYSTEM CALCULATIONS AND ANALYSIS
1.5.1 Backup Battery Capacity Calculations
Submit calculations showing that backup battery capacity exceeds sensor operation, communications supervision, and alarm annunciation power requirements for proposed equipment plus 25 percent spare capcity.
1.6 ESS SOFTWARE, DATA PACKAGE 4
Submit the ESS software, Data Package 4 with the ESS Components submittal package in accordance with Section 01 78 23 OPERATION AND MAINTENANCE
SECTION 28 10 05 Page 7
DATA. Describe the functions of all software in the software manual and include:
a. All information necessary to enable proper loading, testing, and operation
b. Terms and functions definitions
c. Use of system and application software
d. Procedures for system initialization, start-up and shutdown
e. Alarm reports
f. Reports generation
g. Database format and data entry requirements
h. Directory of all files
i. All communication protocol descriptions, including data formats, command characters, and a sample of each type of data transfer
j. Interface definition
k. List of software keys
1.7 AS-BUILT DRAWINGS
Maintain a separate set of drawings, elementary diagrams, and wiring diagrams of the system to be used for as-built drawings. Keep this set accurately and neatly up-to-date with all changes and additions. This set is not to be used for installation purposes.
Finish the final drawings submitted with the endurance test report in accordance with Section 01 78 00 CLOSEOUT SUBMITTALS for as-built requirements.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide a complete and integrated electronic security system (ESS) that the meet requirements of SECNAV M-5510.36A Department of Navy Information Security Program. ESS must be compatible with the Installation's central monitoring system and monitored within the secure/protected area and at the Installation central monitoring station. Installation's central monitoring system is manufactured by Lenel. ESS consisting of the following subsystems and features:
a. Intrusion Detection System (IDS)
b. Access Control System (ACS)
c. Communications System
Include materials not normally furnished by the manufacturer with the ESS equipment as specified in:
SECTION 28 10 05 Page 8
a. Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
b. Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM
2.2 PERFORMANCE REQUIREMENTS
Integrate the installed and operating subsystems into the overall ESS system to detect intrusion, control access, and perform as an entity, as specified below. Provide electronic equipment that complies with 47 CFR 15 and are suitable for the environment where they will be installed.
2.2.1 Growth Capability
Provide capability for modular ESS expansion of inputs, outputs, card readers, and remote control stations with minimal equipment modification.
Software must be able to handle design requirements plus 25 percent spare capacity. Growth capability is not to be limited by the provided products.
2.2.2 Network Certification
Certify all Platform Information Technology (PIT) in accordance with DODI 8500.01 and the individual service implementation policy.
2.2.3 Maintainability
Provide components that can be maintained using commercially available tools and equipment. Arrange and assemble components to be readily accessible to maintenance personnel without compromising system defeat resistance and with no degradation in tamper protection, structural integrity, EMI or RFI attenuation, or line supervision after maintenance when it is performed in accordance with manufacturer's instructions.
2.2.4 Availablity
Provide components rated for continuous operation. Provide solid-state electronic components mounted on printed circuit boards, conforming to UL 796 . Provide boards that are plug-in, quick-disconnect type. Do not impede maintenance with densely packed circuitry. Provide power-dissipating components with safety margins of not less than 25 percent with respect to dissipation ratings, maximum voltages, and current-carrying capacity. Provide solid-state type or hemetically sealed electromechanical type light duty relays and similar switching devices.
2.2.5 Fail-Safe Capability
Provide fail-safe capability in critical elements of the ESS including, but not be limited to, the capability to monitor communication link integrity and to provide self-test. Provide fault annunciation when diminished functional capabilities are detected. Annunciate fail-safe alarms to clearly distinguish from other types of alarms.
2.2.6 Line Supervision
Provide the same geographic resolution for fault isolation at the systems level as provided for intrusion detection. Provide either a static or dynanmic system with active mode for line supervision of communication links of the ESS.
a. The static system must represent "no-alarm" always by the same signal, SECTION 28 10 05 Page 9 which is different than the originally transmitted signal.
b. The dynamic system must represent "no-alarm" with a signal which continually changes with time.
2.2.7 Power Loss Detection
Detect AC and DC power loss and generate an alarm when a critical component of the system experiences temporary or permanent loss of power.
Annunciate the alarm in the Secured Area to clearly identify the component experiencing power loss.
2.2.8 Controls and Designations
Provide controls and designations as specified in NEMA ICS 1 .
2.2.9 Special Test Equipment
Provide all special test equipment, special hardware, software, tools, and programming or initialization equipment needed to start or maintain any part of the system and its components. Special test equipment is defined as any test equipment not normally used in an electronics maintenance facility.
2.2.10 Electromagnetic Interference (EMI)
Configure and provide ESS components employing electromagnetic radiation constructed to provide minimal vulnerability to electronic countermeasures.
2.2.11 Electromagnetic Radiation (EMR)
Provide only ESS communication components which are Federal Communications Commission (FCC) licensed and approved. Provide system components which are electromagnetically compatible.
2.2.12 Interchangeability
Use off-the-shelf components which are physically, electrically, and functionally interchangeable with equivalent components as complete items. Equivalent, replacement components must not require new or other component modification. Do not use custom designed or one-of-a-kind items. Interchangeable components or modules must not require trial and error matching in order to meet integrated system requirements, system accuracy, or restore complete system functionality.
2.3 INTRUSION DETECTION SYSTEM (IDS)
The IDS primary function is to detect intrusion into secured areas.
Utilize a single database for all IDS programming data that seamlessly integrates with the ESS under a single operating environment. The IDS events must be viewable as separate or as a combined list of all ESS events. Control the IDS alarm monitoring through software control from the ESS.
a. Provide both supervised and non-supervised alarm point monitoring.
b. Secure or access alarm points both manually and automatically by time of day, day of week or by operator command.
SECTION 28 10 05 Page 10
2.3.1 IDS Components
Provide components:
a. Premise Control Units (PCU)
b. Detection Sensors
c. Tamper Switches
2.3.2 Detection Sensitivity
The sensitivity of the IDS must allow for the following:
a. Locating intrusions at individually protected assets or at an individual portal
c. Locating intrusions within the coverage on a single volumetric sensor
d. Locating failures or tampering at individual sensors
2.3.3 Detection Alarm and Reporting Capacity
Collect, communicate, and display up to 32 sensor zone alarms and to enable control of one card reader with integral keypad for secure and access inside of the protected area with a delayed alarm.
Identify individual sensors in alarm if the sensor zone is a multiple alarm source combination. Annunciate a single alarm within 2 seconds maximum, after sensor transducer or other detection device activation.
2.3.4 False Alarm Rate
The false alarm rate for each interior IDS zone must not exceed one false alarm per 30-day period. The false alarm rate for each exterior IDS zone must not exceed one false alarm per 24-hour period.
2.3.5 Nuisance Alarm Rate
The nuisance alarm rate for each interior IDS zone must not exceed three nuisance alarms per 30-day period. The nuisance alarm rate for each exterior IDS zone must not exceed three nuisance alarms per 24-hour period.
2.3.6 Premise Control Unit (PCU)
Install the PCU command processor in a tamper resistant enclosure that is specified in paragraph "Component Enclosure". Package the following with the PCU:
a. Power transformer
b. Battery(s)
c. Network connection cable
d. Keypad(s)
e. Keypad connection cable(s)
SECTION 28 10 05 Page 11
f. Additional components as required for full functionality
2.3.6.1 PCU Capabilities
Provide the PCU at a minimum but not limited to, the following capabilities;
a. Expansion to a total of at least 10,000 user codes with 99 user profile definitions.
b. Support 4 keypads with alphanumeric display. Each keypad must be capable of securing and accessing any system area based on a pass code or access control card and or key FOB authorization. Provide keypad alphanumeric display with complete prompt messages during all stages of operation and system programming and display all relevant operating and test data.
c. Four 4 shift schedules per area.
d. A total of at least 100 programmable output relay schedules.
e. 32 individual reporting areas.
f. Data line supervision.
g. Two-man access code or credentials.
h. Support programming to require the same or different access code entered within a programmed delay time of 1 to 15 minutes after disarming before activating a silent ambush alarm.
i. Support area programming that disables schedule and time-of-day changes while system is armed so that area can only be disarmed during scheduled times.
j. Provide a minimum of a 4,000 event log buffer per PCU. Record and hold alarm activity information in the log buffer until the ESS is connected and receives the information. Provide a software-configurable warning log buffer filling notification for PCU(s) configured with network switch capabilities.
k. Support a Network Interface Card (NIC) plug-in module with built in network router capable of 128 Bit AES Rijndael Encryption process certified by NIST (National Institute of Standards and Technology).
2.3.6.2 Overcurrent Protection and Indication
When overcurrent more than it is rated for is detected by the PCU, communication bus(es) and keypad(s) are to be shut down and an overcurrent notification LED lit to indicate the situation.
2.3.6.3 Manual and Self-Test
All testing from any alphanumeric keypad include testing for: standby battery, alarm bell or siren, and communication to the Security Command Center (SCC). Include provisions for an automatic, daily, weekly, 30 day, or up to 60 day communication link test from the PCU installation site to the SCC. Include a provision for displaying the internal system power and wiring conditions.
SECTION 28 10 05 Page 12
Include the following for internal monitoring points:
a. The bell circuit
b. AC power
c. Battery voltage level
d. Charging voltage
e. Panel box tamper
f. Phone trouble line 1
g. Phone trouble line 2
h. Transmit trouble
i. Network trouble
A battery test must be automatically performed to test the integrity of the standby battery by disconnecting the standby battery from the charging circuit and placing a load on the battery. Perform this test at an interval no greater than 180 days.
2.3.7 Detection Sensors
a. Sensors are to detect facility perimeter or protected zone penetrations by unauthorized personnel or intruders and transmit an alarm signal to the alarm annunciation system upon change detection.
Accomplish this with a probability of detection (PD) of 0.9 with a 95 percent confidence level and conforming to UL 639 where applicable.
b. Required sensor power is 12 VDC unless otherwise specified.
c. An interior IDS zone is a room or space within a building that can be secured and accessed independently from all other zones.
d. Provide line supervision for all sensors with an end-of-line resistor at the sensor or within a tampered junction box with conduit from the junction box to the sensor.
d. Provide sensors and components rated for operation in the installed environment. The sensors must transmit an alarm signal to the alarm annunication system upon change detection. Provide all sensors with a tamper switch and elements housed in a tamper-alarmed enclosure in accordance of paragraph "Component Enclosure".
2.3.7.1 Interior Sensors
2.3.7.1.1 High Security Balanced Magnetic Switch (BMS)
Mount the BMS inside the secure location and on the opening side of the door. BMS sensors do not have the capability to incorporate an end-of-line (EOL) resistor.
SECTION 28 10 05 Page 13
2.3.7.1.1.1 Level 1 Switch
UL 634 . Level 1 High Security
2.3.7.1.1.2 Level 2 Switch
UL 634 . Level 2 High Security
2.3.7.1.2 Passive Infrared Sensors
UL 639 .
2.3.7.1.3 Microwave Sensors
UL 639 .
2.3.7.1.4 Dual Technology Sensors
UL 639 . Provide sensor combining passive infrared (PIR) and microwave sensors configured and manufactured specifically to be mounted in a single tamper alarmed enclosure. The sensor must provide selectable "AND" logic or "OR" logic for alarm indication configured in the "OR" logic state.
Provide sensors that have a local means of indicating detection for use during installation and calibration with a means of disabling the indication.
The sensor is to have an LED walk test indicator which is not visible during normal operations. When visible, the walk test indicator will light when the sensor detects an intruder. Provide a sensor equipped with a manual control, located within the sensor's housing, to enable and disable the test indicator or with the test indicator located within the sensor housing so that it can only be seen when the housing is open or removed.
2.3.7.1.5 Photoelectric Sensors
UL 639 . The sensor is to detect opaque bodies and not allow an intruder to disable detection by shining another light source into the receiver.
Provide sensor with a local means of indicating detection for use during installation and calibration with a means of disabling the indication.
2.3.7.2 Tamper Switches
a. Corrosion-resistant tamper switches are required for the following IDS equipment with hinged doors or removable covers that contain open circuits:
(1) Enclosures
(2) Cabinets
(3) Housings
(4) Boxes
(5) Raceways
(6) Fittings
SECTION 28 10 05 Page 14
(7) Sensors
b. Tamper switches are to initiate an alarm signal when the door or cover is moved as little as 6 mm from the normally closed position.
Mechanically mount tamper switches to maximize defeat time when enclosure covers are opened or removed. One second is the minimum amount of time required to depress or defeat the tamper switch after opening or removing the cover. Enclosure and tamper switch must prevent direct line of sight to internal components and prevent switch or circuit tampering. Conceal mounting hardware so switch cannot be observed from enclosure exterior.
c. Tamper switches on doors which are opened to make normal maintenance adjustments to the system and to service power supplies must not have a maintenance position.
2.3.7.2.1 Tamper Switch Performance Requirements
Tamper switches are to be:
a. Inaccessible until switch is activated.
b. Under electrical supervision at all times, irrespective of the protection mode in which the circuit is operating.
c. Annunciated to be clearly distinguishable from intrusion detection alarms and exempt from being disarmed, shunted, or silenced.
d. Spring-loaded and held in the closed position by the door, or cover protected.
e. Wired to break the circuit when the door or cover is disturbed.
f. Wired so that each sensor and device is annunciated by zone at the central reporting processor.
2.4 ACCESS CONTROL SYSTEM (ACS)
Provide an access control system based upon a modular distributed microprocessor architecture complete with access control cards and ready for operation.
a. The ACS card credentials are required to be Common Access Cards (CAC), and CAC cards are being provided by the Government. Interface system with and provide alarm and other status to the overall ESS. Provide ACS that meets the communications requirements of UL 1076 and UL 294 and has the capability of controlling up to 4 card readers and keypads per card reader controller, 128 alarm inputs, or 128 relay outputs or any components combination.
b. System is to grant or deny access or exit based upon:
(1) Keypad identification data
(2) CAC card identification data
(3) Identification technologies combination
(4) Input through the access control devices compared to data stored
SECTION 28 10 05 Page 15 within the system
(5) Time of day, day of week, and special day and holiday scheduling with card validation override.
c. Decision to grant or deny access or exit is to be based upon authorization for such data to be input at a specific location for the current time period. Access decisions for high security areas are to be based upon two identification technology combinations: card and keypad.
d. Provide ACS that supports the configuration and simultaneous monitoring of multiple access control devices when TCP/IP communication interfaces are used between the ESS and the primary Access Control Unit (ACU). The events of the ACS are to be viewable as separate or as a combined list of all ESS events. Provide overall control of the ACS, alarm monitoring, and photo identification through software control of the ESS.
e. Access control, and programming data must reside on a single database and instantly accessible to every networked PC workstation connected to the ESS.
f. Provide both supervised and non-supervised alarm point monitoring.
g. Provide the capability to arm or disarm alarm points both manually and automatically by time of day, day of week or by operator command and the capability to disarm alarm points based on a valid access event.
h. When used for elevator control, the ACS is to grant access to elevator floors based on a valid credential, or by schedule.
i. Provide programmable 'delay' setting for all alarm points. The alarm points are not to report an ENTRY type alarm until the delay setting has expired and not report a dwell type alarm condition until the alarm has been active for the full delay period.
j. Provide the capability to place ACU(s) in an off-line mode. In the off-line mode, the ACU(s) must retain a historical summary of all ACU activity transactions, up to the maximum capacity of the ACU memory buffer. Provide the ability for manual operator control of system output relays with the manual functions to energize, de-energize, enable or disable.
2.4.1 ACS Programming
Provide software capable of, but not limited to, the following programming:
2.4.1.1 Time Schedules
Provide up to 256 user-definable time schedules. These time schedules are to determine the day(s) and times that access will be granted or a scheduled event is to occur. Any and all of the time schedules are to be available for defining access privileges and scheduled events. Provide ALWAYS and NEVER schedules that cannot be altered or removed from the system. Each user-defined time schedule must have the option of reacting or not reacting to user-defined special days, with the ability to react uniquely to each type of special day.
SECTION 28 10 05 Page 16
2.4.1.2 Special Days
Provide an unlimited number of user definable special days to be used for configuring exceptions to the normal operating rules, typically for specifying holiday operating rules. Allow for each special day to be assigned to a user-defined type.
2.4.1.3 ACU Daylight Savings Time Adjustment
Provide a software-configurable, user defined adjustment for Daylight Savings Time. The ACU must not need to be connected to a PC workstation in order for the adjustment to occur.
2.4.1.4 Scheduled Events
Any access controlled reader is to be capable of scheduled unlock periods to allow for card-free access. The access controlled reader is to also be capable of requiring one valid access event before beginning a scheduled unlock period.
Any access control point is to be capable of requiring a valid card as well as a PIN code via keypad on a scheduled basis for high security areas. The use of PIN via keypad functions must not reduce the number of card readers or alarm points available in the ACU(s). Any designated alarm input must be able to be scheduled Secured and Accessed. Any relay output must be capable of scheduled ON and OFF periods to allow for automatic input and output system control.
2.4.1.5 Maximum User Capability
Up to 64,000 individual users may be given access cards or codes and have their access controlled and recorded.
2.4.1.6 Access Groups
Each system user must be assignable to a maximum of 4 of 256 possible access groups. An access group is defined as one or more people who are allowed access to the same areas at the same days and time periods.
2.4.1.7 Active and Expire Dates
Any card or user may be configured with activation and expiration dates.
The card can be assigned to any valid access group and will be activated and expired according to the specified dates.
2.4.1.8 Maximum Use Settings
Any card or user may be configured with maximum number of uses for that card. The card can be assigned to any valid access group and will be expired according to the specified number of card uses.
2.4.1.9 Door Outputs
Provide each access control reader with two dedicated relay outputs. Both relays are to provide Normally Open and Normally Closed contacts. Use the first relay for electric lock control while the second is software configurable to activate for door forced open, door left open too long, duress, passback violations, invalid access attempts and valid unlock conditions. Allow for both relays to be separately programmable for
SECTION 28 10 05 Page 17 energize times from 1 second to 10 minutes. The second relay must allow a delay time to be specified, causing its activation to be delayed after an activating condition occurs.
2.4.1.10 User List or Who's In (Muster Reports)
Provide the capability to generate dynamic lists of users in certain access-controlled areas, based either upon selected users or selected areas. The lists must have the option of automatically refreshing after a user-selected interval of time.
2.4.1.11 Crisis Mode
Provide support for a "crisis mode", in which user-selected alarm point activations cause changes to user access privileges. The changes to user access privileges must be configurable to restrict normal access to no access or limited access.
2.4.1.12 Door Groups
Allow up to 256 door groups to be configured. Doors belonging to the same group are be able to be locked, unlocked, disabled, and enabled on command from the ACS.
2.4.1.13 Door Interlocking
Allow a group of doors to be software configured so that if any door in the group is unsecure, all other doors are automatically disabled. This feature is also known as a "mantrap" configuration. The interlocking features must not require the ACS to be on-line for proper operation.
2.4.1.14 PIN Required
Provide support for the required use of a keypad code, in addition to a valid credential during user-selected schedules.
2.4.1.15 Remote Door Control
Provide the ESS operator the capability of manually controlling any access point by issuing a simple command from the ACS. Provide the operator the ability to lock, unlock, enable, and disable any door or Door Group in this manner. This activity is to cause an entry to be logged displaying the door name, number and time that it was performed.
2.4.1.16 Key Control
When interfaced with an approved key-control system, the system is to allow users to deny access to certain doors for any users who have keys in their possession.
2.4.1.17 Reader Disable
Provide support for disabling readers in reaction to a user-selected number of invalid access attempts.
2.4.1.18 Disable Event Messages
Allow users to disable user-selected event messages (Door Forced Open, Door Open Too Long, Door Closed, Request to Exit) for user-selected
SECTION 28 10 05 Page 18 doors. Allow users to disable certain messages (Door Forced Open, Door Open Too Long) according to a user-selected schedule.
2.4.1.19 Input and Output Groups
Allow for up to 256 user-defined (input and output) groups to be defined.
Each Input device is to be able to be linked to these groups for arming, disarming, shunting and unshunting as well as output control.
2.4.1.20 Delays
Each alarm device must allow a delay to be specified which is either an entry type or a dwell type. An entry-type delay is to prevent the input from issuing an alarm event until the delay elapses. If unarmed during the delay period, the alarm is to be ignored. A dwell-type delay requires the input to remain in the alarm state for the full delay duration before issuing an alarm.
2.4.1.21 Output Configuration
Allow each output relay to be software configurable as:
(1) Follows
(2) Latch
(3) Timeout
(4) Scheduled
(5) Timeout Re-triggerable
(6) Limit
(7) Counter
Allow for a time schedule to automatically control the activiation and de-activation of the Scheduled type with all other types configured to activate based on input and output group conditions. Additionally, a time schedule must be specified to configure when the output is to actively monitor the input and output groups.
2.4.1.22 Remote Output Control
Provide the operator the capability of manually controlling any output point by issuing a simple command from the SCC. Based upon the output type, provide the ESS operator the ability to ENABLE, DISABLE, turn ON and turn OFF any output in this manner. A FOLLOWS type output must not be capable of being turned OFF or ON. Log an entry when this activity is performed displaying the output name and time performed. Manual control of outputs are not permissible in ICS 705-1 applications.
2.4.1.23 Remote Reset Command
Provide the capability for any ACU to reset manually or by command issued from the ACS with the option of simulating the ACU reset settings, or forcing a reset type as specified by the user. The remote reset command is not to cause the ACU to degrade its level of protection to any access points defined.
SECTION 28 10 05 Page 19
2.4.1.24 Time Zone
Allow the user to select the time zone in which the ACU is located, so that event times displayed for that ACU will match the local time where the ACU is located.
2.4.1.25 User-Selected LED Behavior
Allow the user to select different behaviors for the LEDs of each access controlled reader.
2.4.1.26 Traced Cards
Provide the capability of selecting any number of cardholders for the purpose of limiting reports to only traced users displaying all traced cardholder events in a user-selected alternate color.
2.4.2 Error and Throughput Rates
Rates must be portal to portal performance averages obtained when processing individuals one at a time. Features are not to reduce capability to meet throughput requirements when serial verification techniques or multiple attempts are required to satisfy error performance requirements.
A Type I error denies access to an authorized enrolled individual. A Type II error grants access to an unauthorized individual. Subsystem Type I and Type II error rates must both be less than 0.1 percent. At the error rates, subsystem access throughput rate must be minimum of 12 individuals per minute through one card reader and keypad access control device.
2.4.3 Access Control System Central Processing
a. Provide serial management and control of system processing. Provide a microprocessor control device able to monitor and control units and up to 32 card reader and keypad access control devices. Central processor must interrogate and receive responses from each ACU within 100 milliseconds. Failure to respond to an interrogation is to cause an alarm.
b. Provide the central processor with a Ethernet interface port to communicate with the printer. Provide an operator interface to control system operating functions. Provide the central processor with a facility-tailorable data base for a minimum of 1000 cardholders with by-name alphanumeric printout, and for automated monitoring, management, and control functions.
c. Provide system configuration controls and electronic diagnostic aids for subsystem setup and troubleshooting with the central processor.
Components are not to be accessible to operations personnel and must be tamper alarmed.
2.4.4 Access Control Unit(ACU)
UL 294 . Provide micro-processor based ACU with all access and input and output decisions to be made by the individual ACU(s). Provide modular solution which will allow for present security requirements and the capability to expand. Configure all field ACU panels to intercommunicate
SECTION 28 10 05 Page 20 via RS-232 hardwired, TCP/IP or fiber-optic communication. Equip all field ACU(s) with a tamper contact.
Designate one ACU as "Primary", responsible for all ACS-to-ACU communications. All other ACU(s) up to a maximum of 16 are to be designated as "Secondary" and communicate with the "Primary" via an TCP/IP network or fiber-optic configuration. Provide ACU capable of, but not limited to, the following:
a. Built-in surge suppression circuitry on plug-in modular circuit boards with surge suppression, configured as an integral component of the system and self-sacrificing in the event of extreme surges or spikes.
b. Capable of supporting at least 2 ports and be expandable in increments of two ports up to a maximum of 4 ports per ACU.
c. Each port configured by ACS to support any one of the following peripheral devices:
(1) Card reader
(2) Alarm Monitoring Module
(3) Output Relay Module
(4) Elevator Reader
(5) Elevator Output Module
Any device combination can be supported on each ACU, up to a total of 4 devices per ACU.
d. Capability of supporting multiple card reader technologies simultaneously, including:
(1) Keypad
(2) Card and Keypad
(3) CAC compatible
This capability must be an integral part of the ACU and will not require special external equipment.
e. Built-in battery back-up of programmed information sustainable for a period of at least 90 days.
f. Powered by a 12 or 24 VDC power source rated at a minimum of 2 amperes with a battery back-up for complete system operation in the event of power failure. Provide battery backup for all ACU(s) to sufficiently power the ACU for 8 hours continuous service.
g. Electric strikes, other locking devices and ancillary peripherals on a separate power supply with battery back-up for continued operation in the event of power failure as specified in paragraph "Backup Power".
h. A minimum of a 10,300 event log buffer per ACU to record and hold access and alarm activity information until the ACS is connected and receives the information. Provide a software-configurable warning log
SECTION 28 10 05 Page 21 buffer filling notification for ACU(s) configured with network switch capabilities.
2.4.5 Access Control Devices
UL 294 . Devices are to be tamper alarmed, tamper and vandal resistant, and solid state, containing no electronics which could compromise the access control subsystem should the subsystem be attacked.
2.4.5.1 Card Readers
Provide surface, semiflush, or weatherproof mountable card readers as indicated for each individual location. Provide contact and contactless type card readers capable of reading CAC and Keypad type of access control cards.
Keypads must contain an alphanumeric and special symbols keyboard with symbols arranged in ascending ASCII code ordinal sequence. Provide keypad as a stand-alone device or integrated into the card reader.
2.4.5.1.1 Contact Card Readers
Provide contact card readers that can read credential CAC cards whose characteristics of size and technology meet those defined by ANSI ISO/IEC 7816 and are in compliance with NIST FIPS 201-2 .
Provide readers with "flash" download capability to accommodate card format changes and the capability of reading the card data and transmitting the data, or a portion thereof, to the ESS control panel.
2.4.5.1.2 Contactless Card Readers
Provide contactless card readers that can read credential CAC cards whose characteristics of size and technology meet those defined by ANSI ISO/IEC 7816 in close proximity to the card reader and are in compliance with NIST FIPS 201-2 .
Provide readers with "flash" download capability to accommodate card format changes and the capability of reading the card data and transmitting the data, or a portion thereof, to the ESS control panel.
2.4.5.1.3 Card Reader Display
Provide card readers with an LED or other visual indicator display which indicate power ON and OFF and whether user passage requests have been accepted or rejected.
2.4.5.1.4 Card Reader Response Time
The card reader is to respond to passage requests by generating a signal to the local processor.
2.4.5.1.5 Card Reader Power
Power the card reader from the source as shown on the drawings. The card reader must not dissipate more than 5 Watts.
SECTION 28 10 05 Page 22
2.4.5.1.6 Card Reader Mounting Method
Provide card readers suitable for surface, semi-flush or weatherproof mounting as required.
2.4.5.2 Keypads
Entry control keypads are to use unique alphanumeric and other symbol combinations as an identifier. Keypads must contain an integral alphanumeric and special symbols keyboard with symbols arranged in ascending ASCII code ordinal sequence. Communications protocol is to be compatible with the local processor.
2.4.5.2.1 Keypad Display
Keypads are to include an LED or other type of visual indicator display and provide visual and audible status indications indicating power ON and OFF and whether user passage requests have been accepted or rejected.
The maxiumum horizontal and vertical viewing angles are to be limited by the keypad display or enclosure. The maximum horizontal viewing angle must be no more than plus and minus 5 degrees off a vertical plane perpendicular to the plane of the face of the keypad display. The maximum vertical viewing angle must be no more than plus and minus 15 degrees off a horizontal plane perpendicular to the plane of the face of the keypad display.
2.4.5.2.2 Keypad Response Time
The keypad is to respond to passage requests by generating a signal to the local processor.
2.4.5.2.3 Keypad Power
Power the keypad from the source as shown on the drawings. The keypad must not dissipate more than 5 Watts.
2.4.5.2.4 Keypad Mounting Method
Provide keypads suitable for surface, semi-flush or weatherproof mounting as required.
2.4.5.2.5 Keypad Duress Codes
Provide a means for users to indicate a duress situation by entering a special code into the keypad.
2.4.5.3 Card Readers with Integral Keypad
Equip contact and contactless card readers with integral keypads as specified in paragraph "Keypads".
2.4.5.4 Portal Control Devices
Portal control devices must meet the requirements in Section 08 71 00 DOOR
HARDWARE.
SECTION 28 10 05 Page 23
2.4.5.4.1 Panic Bar
Include panic bar emergency exit hardware on emergency exit doors as indicated. Provide an alarm shunt signal from the panic bar emergency exit hardware to the appropriate local processor.
2.4.5.4.1.1 Emergency Egress With Alarm
Include a conspicuous warning sign with 25 mm high, red lettering notifying personnel that an alarm will be annunciated if the panic bar is operated.
Panic bar hardware operation is to generate an intrusion alarm. The panic bar must depend upon a mechanical connection only and not depend upon electric power for operation, except for local alarm annunciation and alarm communications.
2.4.5.4.1.2 Normal Egress
Panic bar hardware operation is not to generate an intrusion alarm. The panic bar must depend upon a mechanical connection only when exiting.
Provide the exterior, non-secure side of the door with an electrified thumb latch or lever to provide access after the credential I.D.
authentication by the ESS.
Signal Switches: Strikes/bolts are to include signal switches indicating to the system when the bolt is not engaged or the strike mechanism is unlocked. The signal switches are to report a forced entry to the system.
2.4.5.4.1.3 Delay Egress With Alarm
Include a conspicuous warning sign with 25 mm high, red lettering notifying personnel that an alarm will be annunciated if the panic bar is operated.
Delay operation 15 seconds after initiation for portal control devices.
2.4.5.4.2 Electric Door Strikes and Bolts
Configure electric door strikes and bolts to remain secure in case of power failure using DC power to energize the solenoids. Incorporate end-of-line resistors to facilitate line supervision by the system.
Install metal-oxide varistors (MOVs) to protect the controller from reverse current surges if not incorporated into the electric strike or local controller. Electric strikes must have a minimum forcing strength of 101 kN.
2.4.5.4.2.1 Solenoid
The actuating solenoid for the strikes and bolts furnished must not dissipate more than 12 Watts and operate on 12 or 24 VDC. The inrush current must not exceed 1 ampere and the holding current must not be greater than 500 milli-amperes. The actuating solenoid must move from the fully secure to fully open positions in not more than 500 milliseconds.
2.4.5.4.2.2 Signal Switches
Strikes and bolts are to include signal switches indicating to the system when the strike mechanism is unlocked. The signal switches are to report
SECTION 28 10 05 Page 24 a forced entry to the system.
2.4.5.4.2.3 Tamper Resistance
The electric strike and bolt mechanism is to be encased in hardened guard barriers to deter forced entry.
2.4.5.4.2.4 Size and Weight
Electric strikes and bolts are to be compatible with standard door frame preparations.
2.4.5.4.2.5 Mounting Method
Provide electric strikes and bolts suitable for use with single and double door installations, with mortise-type or rim- type hardware as indicated, and compatible with right or left hand mounting.
2.4.5.4.2.6 Astragals
See Section 08 71 00 DOOR HARDWARE for Astragal lock guards.
2.4.5.4.3 Electrified Mortise Lock
Configure electrified mortise locks to remain secure in case of power failure using DC power to energize the solenoids. Provide solenoids rated for continuous duty. Incorporate end-of-line resistors to facilitate line supervision by the system. Install metal-oxide varistors (MOVs) to protect the controller from reverse current surges if not incorporated into the electric strike or local controller.
2.4.5.4.3.1 Solenoid
The actuating solenoid for the mortise locks furnished must not dissipate more than 12 Watts and operate on 12 or 24 VDC. The inrush current must not exceed 1 ampere and the holding current must not be greater than 500 milli-amperes. The actuating solenoid must move from the fully secure to fully open positions in not more than 500 milliseconds.
2.4.5.4.3.2 Signal Switches
The mortise locks are to include signal switches indicating to the system when the locks are not engaged. The signal switches are to report a forced entry to the system.
2.4.5.4.3.3 Hinge
Provide an electric transfer hinge with each mortise lock in order to get power and monitoring signals from the lockset to the door frame.
2.4.5.4.3.4 Size and Weight
Electrified mortise locks are to be compatible with standard door preparations.
2.4.5.4.3.5 Mounting Method
Provide electrified mortise locks suitable for use with single and double door installations. The lock would be in the active leaf and the fixed
SECTION 28 10 05 Page 25 leaf would be monitored in double door installations.
2.4.5.4.4 Electromagnetic Lock
Electromagnetic locks are to contain no moving parts and…