Amend 0010 Enclosure 3 DWGS.pdf

PDF 15 MB Posted

Attached to
Mechanical Repairs Bldg TT113 CDC
Solicitation number
N4008526R9010
Issued by

About this file

These are mechanical construction drawings and schedules for Building TT113 at Marine Corps Base Camp Lejeune, North Carolina, prepared under federal contract N40085-24-F-5940. The drawings document mechanical repairs and HVAC systems installation for what appears to be a child development facility containing classrooms, offices, and support spaces.

The project includes three dedicated outside air systems (DOAS-1, DOAS-2, DOAS-3), 30 four-pipe fan coil units (FCU-1-01 through FCU-3-10), hot water and chilled water distribution systems, and associated ductwork, piping, and controls. Key equipment specifications include three air-cooled package chillers (CH-1 and CH-2 at 90 tons, with standby capacity), three condensing boilers (B-1, B-2, B-3 at 399 MBH each) with variable frequency drive pumps, and multiple exhaust fans. The HVAC systems serve occupied spaces maintained at 70°F heating and 75°F cooling with 50% relative humidity, while mechanical and electrical rooms are designed to 41°F minimum/95°F maximum. Mechanical schedules detail fan coil capacities ranging from 300-1,375 CFM supply with 1.8-8.3 MBH heating and 1.8-41.6 MBH cooling capacity, control valves, expansion tanks, air separators, and secondary condensate drain systems. All equipment is specified with marine-grade 10,000-hour salt spray protective coatings and includes BACnet MS/TP communication integration for building automation system controls. The design revision dated March 9, 2026 represents sheet 59-99 of a 119-sheet document set.

View the file

Other files

File Type Posted
Amend 0015.pdf PDF
Amend 0014.pdf PDF
Amend 0013.pdf PDF
Amend 0012.pdf PDF
M-202-T.pdf PDF
60042069_Rev03.pdf PDF
60042049 _Rev03.pdf PDF
60042066_Rev03.pdf PDF
Amend 0011.pdf PDF
60042073_Rev03.pdf PDF
60042047 _Rev03.pdf PDF
60042070_Rev03.pdf PDF
N4008523B0044 PPI Revision 03.pdf PDF
Amend 0010 Enclosure 1 DWG List.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
Amend 0008.pdf PDF
Amend 0004.pdf PDF
Amend 0007.pdf PDF
Amend 0006.pdf PDF
Amend 0005.pdf PDF
Amend 0003.pdf PDF
Amend 0002 SECTION 01 31 50 TRANSFER AND ACCEPTANCE OF MILITARY REAL PROPERTY.pdf PDF
Amend 0002.pdf PDF
Amend 0001.pdf PDF
N4008523B0044 Dwgs.pdf PDF
230044 Termite Inspection Report.pdf PDF
Mech MACC RFP.pdf PDF
N4008523B0044 Specs.pdf PDF
230044 SID Binder.pdf PDF
230044 Basis of Design.pdf PDF
230044 Lead and Asbesto Report.pdf PDF
230044 APPD.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M

M

E

HVAC SHUTOFF SWITCH

E

HVAC SHUTOFF SWITCH

PRETODDLER

TRAINING SPECIALIST

VESTIBULE

ADMIN

ADMIN

COMM/CCTV

STORAGE

STAFF RR

PUBLIC RR

CORRIDOR

LAUNDRY

BREAK ROOM

JANITOR

INFANT

INFANT

INFANT

PRESCHOOL

TODDLER

TODDLER

TODDLER

TODDLER

STAFF RR

CLOSET

101A

CLOSET

102A

CLOSET

103A

CLOSET

104A

CLOSET

105A

CLOSET

108A

CLOSET

107A

CLOSET

106A

CLOSET

119A

CLOSET

126A

CLOSET

134A

CLOSET

132A

CLOSET

133A

CLOSET

142A

CLOSET

135A

CLOSET

145A

CLOSET

144A

CLOSET

143A

CLOSET

146A

CLOSET

149A

CLOSET

148A

CLOSET

151A

CLOSET

147A

CLOSET

150A

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

CORRIDOR

STAFF TRAINING

OFFICE

DEPUTY DIRECTOR

DIRECTOR

LOBBY

INFANT

INFANT

CORRIDOR

INFANT

SCULLERY

KITCHEN

ELECTRICAL

MECHANICAL

DRY STORAGE

SPRINKLER

INFANT

PRESCHOOL

PRESCHOOL

PRESCHOOL

TODDLER

CORRIDOR

CLOSET

142A

CLOSET

135A

F C

U -2

-0

F C

U -2

-0

FCU-2-04

FCU-2-03

F C

U -2

-0

FCU-2-05

F C

U -2

-0

F C

U -2

-0

FCU-1-01

F C

U -2

-0

FCU-2-11

FCU-2-12

FCU-1-03

F C

U -1

-0

FCU-1-09

FCU-1-07

F C

U -1

-0

FCU-1-04

FCU-1-12F

C

U -1

-1

FCU-1-08

FCU-3-02

FCU-3-01

F C

U -3

-0

FCU-3-03

FCU-3-05

FCU-3-06

FCU-3-07

FCU-3-09

FCU-3-08

F C

U -1

-1

UH-2

DAC-1

UH-3

AD-1

EF-1

EF-2

EF-3

FCU-1-14

FCU-1-02

F C

U -1

-1

FCU-3-10

FCU-2-10

DCU-1

DDC

CONTROL

PANEL

OFFICE

117A

OFFICE

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MH101

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

FIRST FLOOR PLAN - OVERALL - MECHANICAL HVAC

60042066 N40085-24-F-5940

# PLAN NOTES

1 PROVIDE WALL MOUNTED EMERGENCY HVAC

SHUTDOWN SWITCH. SEE SHEET M-701 FOR

MORE INFORMATION. SEE ENLARGED SHEETS

FOR MORE INFORMATION.

GRAPHIC SCALE: 1/8"=1'-0"

8' 0 4' 8' 16'

1/8" = 1'-0" A1

FIRST FLOOR PLAN - OVERALL - MECHANICAL HVAC

N

GENERAL NOTES:

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

3. FAN COIL UNITS AND ASSOCIATED DUCTWORK

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE ATTIC AND SECTION VIEWS FOR

ELEVATIONS AND LOCATIONS OF EQUIPMENT.

2 PPI REVISION 2 03.09.26

M

FCU-3-02

FCU-1-05

F C

U -1

-0

FCU-1-08

FCU-1-11

FCU-1-09

UH-3

UH-2

FCU-2-12

F C

U -1

-0

FCU-1-03

LAUNDRY

STAFF TRAINING

VESTIBULE

INFANT

ADMIN

ADMIN

COMM/CCTV

PRESCHOOL

CLOSET

119A

CLOSET

126A

CORRIDOR

CORRIDOR

STORAGE

INFANT

INFANT

INFANT

INFANT

INFANT

ELECTRICAL

MECHANICAL

INFANT

CLOSET

134A

CLOSET

132A

CLOSET

133A

CLOSET

142A

CLOSET

135A

STAFF RR

PUBLIC RR

CORRIDOR

BREAK ROOM

JANITOR

SCULLERY

KITCHEN

DRY STORAGE

SPRINKLER

CLOSET

135A

DEPUTY DIRECTOR

LOBBY

8"x14" F

C U

-1 -0

FCU-1-10

FCU-1-12

8" ø

"ø

CLOSET

143A

CLOSET

146A

CLOSET

144A 12"ø

S2

S4

S2

S2

S2

S2

S1

S1

S1

S1

S1

S1

S3

S3

S1

S2

S2

S3

S3

S3

S3

S3

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

"ø

12"ø

8"ø

8" x1

2"

"ø

8" x1

0"

"ø

8"x12" 8" ø

6"ø

10"ø

8"x10"

"x

8"ø

8"ø

"x

6"

6" ø

14"ø

6" ø

6" ø

6" ø

6" ø

6" ø

6"x8"

6" ø

6" ø

"ø

8"ø

8"ø 8" x1 2"

10"ø

"ø

"x

6"

"x

8"ø

8"ø

"x

8"ø

8"ø

8" x1

2"

8"ø

8"ø

"x

6"

"x

6"

"ø

"ø

"x

8"ø

8"ø

"ø

"ø

"x

6"

"x

6"

8"ø

8"ø 8"ø

"x

"x

"x

10"ø

10"ø

10"ø

10"ø

10"ø

14"ø

6" ø

"ø

10"ø

10"ø

16"x6"

16"x6"

"ø

10"ø

16"x6"

16"x6"

T

T

T

T

T

T

T

TT T

T

T

TT

T

T

T

E5

E5

E1

E5 350 E5

E5

E5

E5

E5

E5

AD-1

E

HVAC SHUTOFF

SWITCH

DAC-1

T

DCU-1

R5

S2

S2

S2

8"ø

8"ø8"ø

"ø

R5

8"ø

R5

8"ø

S2

8"ø

S2

S2

S2

S2

8"ø8"ø

"ø

8"ø

S2

S2

S2

S2

8"ø

R5

8"ø 8"ø

"ø

S2

"ø

8"ø

8"ø

8" ø

S2 175 S2

S2

8"ø

8"ø

"ø

R5 600R5

8"ø

S2

S2

S2

S2

S2

S2

8"ø

8"ø

8"ø

R5

12"ø

12"ø

S2

S2

8" ø

8" ø

8"ø

8"ø

EF-1

EF-2

EF-3

L-1

L-2

L-3

FCU-3-01

8"x12"

8" ø

S2

S2

S2

S2

S2

8" ø

12"ø

10"ø

S1

S3

S3

S2

"x

8" ø

8" ø

S2

4"ø

8"ø

S2

"ø

FCU-1-02

FCU-1-01

FCU-3-10

S2

R5

R6

R5

R4

4" ø

4" ø 4" ø 4" ø

S2

"x

O A

14"x12"

8" ø

8" ø

12"x12"

10"x6"

10"x6"

10"x6"

"x

8"ø

S2

S2

H-1

E3

10"x10"

M

MD-1

(L-1)

MD-2

(L-2)

MD-3

(L-3)

6"ø

6"ø R4

S1

E1

E1

R1

R2

R4

BAROMETRIC

DAMPER

"ø

8" ø

F C

U -1

-1

"ø

6" ø

8" ø

R5

R5

R7

R7

16"ø

16"ø

E1

E5

S2

S2

R3

S2

8" ø

8" ø

OFFICE

117A

OFFICE

T

DDC

CONTROL

PANEL

T

FCU-1-14

40"x16"

"x

"x

8" x1

2"

8"x14"

14"ø

8" ø

8" ø

8" ø

10"x12"

16"ø 14"ø

10"ø

8"ø

8"x12"

"x

8"ø

8"ø

8" ø

"ø

"ø

12"ø

"x

R4

12"ø 10"x12"

6" ø

"x

8"ø

"x

8"ø

8" x1

2"

"x

12"ø

S2

S2

8"ø8"ø

8" x1

0"

8"ø8"ø

"ø

"ø

"ø

"ø

"ø

14"ø

"x

14"ø

"ø

8"ø

8"ø

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MH102

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

FIRST FLOOR PLAN - EAST WING - MECHANICAL HVAC

60042067 N40085-24-F-5940

# PLAN NOTES

1 PROVIDE 4-PIPE FAN COIL UNIT ABOVE SECOND

GYPSUM BOARD CEILING. PROVIDE RETURN

DUCT PLENUM TO MATCH DUCT INLET

CONNECTION. PROVIDE TRANSITION OR TAP AS

SHOWN AND ROUTE SUPPLY AND RETURN

DUCTWORK DOWN THROUGH GYP CEILING TO

LAY-IN CEILING GRILLES. PROVIDE DUCT

MOUNTED BALANCING DAMPER BETWEEN GYP

CEILING AND GRILLE.

2 PROVIDE VENTILATION DUCTWORK DOWN FROM

DOAS MAIN DUCTWORK IN ATTIC, TO LAY-IN

CEILING MOUNTED GRILLES AS SHOWN. SEE

ATTIC PLANS FOR CONTINUATION. (TYPICAL)

3 PROVIDE EXHAUST DUCTWORK DOWN FROM

DOAS MAIN DUCTWORK IN ATTIC. ROUTE TO

VERTICAL EXHAUST DUCTWORK IN CHASE

DOWN TO SIDEWALL MOUNTED GRILLE AS

SHOWN. (TYPICAL)

4 PROVIDE EXHAUST VENT DUCTWORK FROM

DRYERS TO EXTERIOR WALL CAP(S) AS SHOWN.

REUSE EXISTING PENETRATIONS.

5 PROVIDE WALL MOUNTED EMERGENCY HVAC

SHUTDOWN SWITCH. PROVIDE SWITCH WITH A

DIFFERENT COLOR THAN FIRE ALARM PULL

STATIONS. SEE SHEET M-701 FOR MORE

INFORMATION.

6 PROVIDE WALL MOUNTED DUCTLESS SPLIT AIR

HANDLER ABOVE DOOR. PROVIDE

MANUFACTURER'S RECOMMENDED

CLEARANCES AND COORDINATE INSTALLATION

WITH OTHER EQUIPMENT IN SPACE.

7 PROVIDE AIR DOOR ABOVE EXTERIOR DOOR.

OPERATION MUST BE TIED TO DOOR SWITCH.

8 PROVIDE EXHAUST HOOD DUCTED UP TO

EXHAUST FAN IN ATTIC. EXHAUST HOOD AND

FAN OPERATION MUST BE TIED TO WALL

MOUNTED SWITCH, AND ONLY BE ENERGIZED

UPON PROOF OF CLOSURE OF MOTORIZED

DAMPER IN DOAS EXHAUST DUCT SERVING

SPACE.

9 PROVIDE CONDENSING UNIT MOUNTED ON

EQUIPMENT SUPPORT PAD ON EXTERIOR OF

BUILDING AS SHOWN. COORDINATE EXACT

LOCATION WITH CIVIL AND ENSURE

MANUFACTURER RECOMMENDED CLEARANCES

ARE MAINTAINED.

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

3/16" = 1'-0" A1

FIRST FLOOR PLAN - EAST WING - MECHANICAL HVAC

N

NTS

A5

KEY PLAN - EAST WING

GENERAL NOTES:

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

3. FAN COIL UNITS AND ASSOCIATED DUCTWORK

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE ATTIC AND SECTION VIEWS FOR

ELEVATIONS AND LOCATIONS OF EQUIPMENT.

2 PPI REVISION 2 03.09.26

FCU-3-02

FCU-3-03

F C

U -3

-0

FCU-3-06

FCU-3-07

FCU-3-05

FCU-3-08

FCU-3-09

TRAINING SPECIALIST

TODDLER

CORRIDOR

PRESCHOOL

TODDLER

CLOSET

151A

CLOSET

147A

CLOSET

150A

STAFF RR

TODDLER

CLOSET

148A

CLOSET

149A

PRESCHOOL

TODDLER

PRESCHOOL

TODDLER

CLOSET

146A

CLOSET

144A

CLOSET

145A

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

8"x12" 8 "ø

"ø 8 "ø

"ø

8"x12" 14"x12"

"ø

"ø

8"x12" 14"x12"

10"ø

16"x6"

16"x6"

"ø

"ø

8"x12"

8"x12"

10"ø

10"ø

10"ø

"ø

"ø8 "ø

10"x12"

14"x12"

8"x12" 16"x12" 12"x12"

"ø

"ø

"ø

6"ø

16"x6" 10"ø

10"ø

16"x6"

16"x6"

16"x6"

T

T

T

T

T T

T

T

E5

E5

E5

E5

E5

E5

E5

E1

E1

HVAC SHUTOFF

SWITCH

E

S2

"ø

S2

"ø

"ø

S2

S2

"ø

S2

"ø

"ø

8"ø

S2

S2

S2

S2

S2

S2

"ø

"ø

12"ø

"ø8 "ø

S2

S2

12"ø

S2

S2 2008"ø

8"ø

S2

S2

"ø

"ø

"ø

S2

S2

"ø

12"ø

R5

S2

S2

"ø

"ø

12"ø

S2

S2

12"ø

12"ø

S2

S2

"ø 8 "ø

FCU-3-01

8"x12"

"ø

S2

S2

S2

S2

S2

"ø

12"ø

10"ø

S1

FCU-3-10

S2

R5

R5

R6

R5

R5

S2

R5

R6

R5

R5

"ø

"ø 4

"ø 4 "ø

S2

14"x12"

"ø

"ø

"ø

"ø

8"ø

S2

10"ø

6"ø

E5

"ø

OFFICE

117A

T

"ø

"ø

"ø

"ø 8 "ø

"ø

"ø

"ø

"ø

"ø

10"x12"

14"ø

"ø

"ø

"ø 10"x12"

14"ø

"ø

"ø

"ø

16"ø

10"x12"

16"ø 14"ø

8"ø

8"ø

8"ø

8"ø

"ø

"ø

"ø

"x

"ø

12"ø

14"ø

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MH103

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

FIRST FLOOR PLAN - SOUTH WING - MECHANICAL HVAC

60042068 N40085-24-F-5940

# PLAN NOTES

1 PROVIDE EXHAUST VENT DUCTWORK FROM

DRYERS TO EXTERIOR WALL CAP(S) AS SHOWN.

REUSE EXISTING PENETRATIONS.

2 PROVIDE 4-PIPE FAN COIL UNIT ABOVE SECOND

GYPSUM BOARD CEILING. PROVIDE RETURN

DUCT PLENUM TO MATCH DUCT INLET

CONNECTION. PROVIDE TRANSITION OR TAP AS

SHOWN AND ROUTE SUPPLY AND RETURN

DUCTWORK DOWN THROUGH GYP CEILING TO

LAY-IN CEILING GRILLES. PROVIDE DUCT

MOUNTED BALANCING DAMPER BETWEEN GYP

CEILING AND GRILLE.

3 PROVIDE VENTILATION DUCTWORK DOWN FROM

DOAS MAIN DUCTWORK IN ATTIC, TO LAY-IN

CEILING MOUNTED GRILLES AS SHOWN. SEE

ATTIC PLANS FOR CONTINUATION. (TYPICAL)

4 PROVIDE EXHAUST DUCTWORK DOWN FROM

DOAS MAIN DUCTWORK IN ATTIC. ROUTE TO

VERTICAL EXHAUST DUCTWORK IN CHASE

DOWN TO SIDEWALL MOUNTED GRILLE AS

SHOWN. (TYPICAL)

5 PROVIDE WALL MOUNTED EMERGENCY HVAC

SHUTDOWN SWITCH. PROVIDE SWITCH WITH A

DIFFERENT COLOR THAN FIRE ALARM PULL

STATIONS. SEE SHEET M-701 FOR MORE

INFORMATION.

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

3/16" = 1'-0" A2

FIRST FLOOR PLAN - SOUTH WING - MECHANICAL HVAC

N

NTS

A5

KEY PLAN - SOUTH WING

GENERAL NOTES:

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

3. FAN COIL UNITS AND ASSOCIATED DUCTWORK

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE ATTIC AND SECTION VIEWS FOR

ELEVATIONS AND LOCATIONS OF EQUIPMENT.

2 PPI REVISION 2 03.09.26

FCU-2-05

F C

U -2

-0

FCU-2-08

F C

U -2

-0

FCU-2-02

FCU-2-03

F

C U

-2 -0

FCU-2-09

FCU-2-11

FCU-2-07

FCU-2-12

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

TRAINING SPECIALIST

STAFF TRAINING

OFFICE

DIRECTOR

CLOSET

101A

CLOSET

102A

CLOSET

103A

CLOSET

104A

CLOSET

105A

CLOSET

108A

CLOSET

107A

CLOSET

106A

PRETODDLER

CORRIDOR

CLOSET

102A

CLOSET

103A

CLOSET

107A

CLOSET

106A

TODDLER

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S4

S4

S2

S2

S2

"ø

"ø

"ø1

"ø

"x

"x

"x

"x

"x

"x

"x

"x

"x

"x

"x

8"ø

8"ø8"ø

8"ø

8"ø

"x

8"ø

12"ø

8"ø

"x

"ø

"x

"x

"x

"x

"8"ø

8"ø

"x

8"ø

8"ø

"x

"ø

T T T T

T T T

T

T

T

T

E5

E5

E5

E5

E5

E5

E5

E5

8"ø

S2

S2

S2

S2

R5

R5

8"ø 8"ø

S2

R5

S2

8"ø

8"ø

S2

S2

S2

R5

S2

S2

S2

"ø

8"ø

S2

S2

S2

8"ø

8"ø

"ø

R5

R5

S2

S2

S2

"ø

R5

S2

8"ø

S2

S2

8"ø

S2

S2

S2

8"ø 8"ø

8"ø8"ø 8"ø

"ø

8"ø

"ø

8"ø 8"ø

8"ø

8"ø 8"ø

S3

S3

S2

"x

"ø

"ø

S2

4"ø

8"ø

S2

"ø

FCU-1-02

FCU-1-01

R4

"x

FCU-2-10

12"ø

S2

10"ø R5

R2

R2

R5

R2

8"ø

S2

S2

R5

R3

S2

"ø

"ø

OFFICE

117A

OFFICE

T

T T

"ø

"x

4"ø

14"ø

10"ø

8"ø

8"x12"

"x

"x

8"ø

"x

12"ø

"x

"ø

14"ø

20"x12"

R4

12"ø 10"x12"

"x

"x

14"ø

8"ø

14"ø

"ø

8"ø 8"ø

8"ø

"x

8"ø

8"ø

8"ø

8"ø

8"ø

8"ø

14"ø

"x

8"ø

8"ø

14"ø

"x

8"ø

8"ø

"ø

"ø

"ø

"ø

"ø

3 3

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MH104

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

FIRST FLOOR PLAN - WEST WING - MECHANICAL HVAC

60042069 N40085-24-F-5940

GENERAL NOTES:

# PLAN NOTES

1 PROVIDE 4-PIPE FAN COIL UNIT ABOVE SECOND

GYPSUM BOARD CEILING. PROVIDE RETURN

DUCT PLENUM TO MATCH DUCT INLET

CONNECTION. PROVIDE TRANSITION OR TAP AS

SHOWN AND ROUTE SUPPLY AND RETURN

DUCTWORK DOWN THROUGH GYP CEILING TO

LAY-IN CEILING GRILLES. PROVIDE DUCT

MOUNTED BALANCING DAMPER BETWEEN GYP

CEILING AND GRILLE.

2 PROVIDE VENTILATION DUCTWORK DOWN FROM

DOAS MAIN DUCTWORK IN ATTIC, TO LAY-IN

CEILING MOUNTED GRILLES AS SHOWN. SEE

ATTIC PLANS FOR CONTINUATION. (TYPICAL)

3 PROVIDE EXHAUST DUCTWORK DOWN FROM

DOAS MAIN DUCTWORK IN ATTIC. ROUTE TO

VERTICAL EXHAUST DUCTWORK IN CHASE

DOWN TO SIDEWALL MOUNTED GRILLE AS

SHOWN. (TYPICAL)

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

3/16" = 1'-0" B1

FIRST FLOOR PLAN - WEST WING - MECHANICAL HVAC

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

3. FAN COIL UNITS AND ASSOCIATED DUCTWORK

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE ATTIC AND SECTION VIEWS FOR

ELEVATIONS AND LOCATIONS OF EQUIPMENT.

N

NTS

A5

KEY PLAN - WEST WING

2 PPI REVISION 2 03.09.26

M

M

M

M

C1

M-301

DOAS-3

A1

M-301

A1

M-302

C1

M-302

A1

M-303

C1

M-303

DOAS-2

DOAS-1

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MH105

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

ATTIC PLAN - OVERALL - MECHANICAL HVAC

60042070 N40085-24-F-5940

1/8" = 1'-0" A1

ATTIC PLAN - OVERALL - MECHANICAL HVAC

GENERAL NOTES:

GRAPHIC SCALE: 1/8"=1'-0"

8' 0 4' 8' 16'

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

N

M

DOAS-1

C1

M-301

10"ø 10"ø 10"ø 10"ø

12"x12" EA

20"x12" EA

30"x18" OA

20"x20" EA

"x

E

A

"x

E

A

30"x18" EA

"x

E

A

10"ø

10"ø

10"ø

3 10"ø

A1

M-301

6"x6" EA

6"x6" EA

EF-5

6x6 EA DOWN TO

EXHAUST HOOD

MD-6

MD-7

MD-10

"x

E

A

"ø

"ø

"ø

"ø

"ø

"ø

8"x14" OA

8"ø

"ø

12"x12" EA 16"x12" EA 20"x12" EA18"x12" OA

18"x18" OA 22"x22" OA 6 "ø

20"x20" EA

12"x12" EA

"ø

"ø

8"x12" OA

"ø

"ø1 "ø

12"x16" OA18"x16" OA

"ø

8"ø

"ø

"ø

6"ø 6"ø

"ø

"ø

"ø

"ø

"x

E

A

"x

O A

12"ø

12"ø

8"ø

FCU-3-02

FCU-3-01

FCU-3-10

FCU-1-14

FCU-2-12

FCU-1-02

FCU-1-01

FCU-1-04

FCU-1-13

FCU-1-06

FCU-1-07

FCU-1-05 FCU-1-08

FCU-1-09

FCU-1-10

FCU-1-11

FCU-1-12

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MH106

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

ATTIC PLAN - EAST WING - MECHANICAL HVAC

60042071 N40085-24-F-5940

GENERAL NOTES:

# PLAN NOTES

1 PROVIDE DOAS MOUNTED ON EQUIPMENT

PLATFORM IN ATTIC. COORDINATE EXACT

LOCATION ON PLATFORM WITH STRUCTURE

AND PROVIDE MANUFACTURER RECOMMENDED

CLEARANCES.

2 PROVIDE OUTSIDE AIR VENTILATION DUCTWORK

FROM EXTERIOR WALL LOUVER WITH CLASS 1A

MOTORIZED DAMPER TO DOAS OA INTAKE AS

SHOWN. PROVIDE DUCT PLENUM BEHIND

ARCHITECTURAL LOUVER, SIZE TO MATCH

MOTORIZED DAMPER SIZE. SEE

ARCHITECTURAL SHEETS FOR MORE

INFORMATION ON LOUVER TYPE AND SIZE.

3 PROVIDE EXHAUST AIR DUCTWORK FROM

EXTERIOR WALL LOUVER WITH CLASS 1A

MOTORIZED DAMPER TO DOAS EXHAUST

OUTLET AS SHOWN. PROVIDE DUCT PLENUM

BEHIND ARCHITECTURAL LOUVER, SIZE TO

MATCH MOTORIZED DAMPER SIZE. SEE

ARCHITECTURAL SHEETS FOR MORE

INFORMATION ON LOUVER TYPE AND SIZE.

4 PROVIDE OUTSIDE AIR VENTILATION DUCTWORK

FROM DOAS OA OUTLET AND ROUTE AS SHOWN

TO SPACES BELOW. SEE FLOOR PLANS FOR

CONTINUATION

5 PROVIDE INLINE EXHAUST FAN AS SHOWN.

INSTALL PER MANUFACTURER'S INSTALLATION

AND CLEARANCE RECOMMENDATIONS. ROUTE

DUCTWORK TO HOOD AND EXTERIOR LOUVER

WITH CLASS 1A MOTORIZED DAMPER. SEE

CONTROL DETAIL FOR SEQUENCE OF

OPERATION.

3/16" = 1'-0" B1

ATTIC PLAN - EAST WING - MECHANICAL HVAC

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

N

NTS

A5

KEY PLAN - EAST WING

DOAS-3

10"ø

10"ø

10"ø

"x

E

A

18"x16" EA

"x

E

A

"x

O A

"x

E

A

30"x18" EA

"x

E

A

10"ø

10"ø

22"x20" EA

18"x16" EA

10"ø

10"ø

10"ø

MD-10

MD-11

12"ø

"x

O A

12"ø

12"ø

"ø

"ø

"ø

12"ø

"ø

A1

M-303

C1

M-303

"x

E

A

"x

O A

12"ø

12"ø

8"ø

"ø

20"x20" OA

20"x20" OA

30"x18" EA

"x

O A

"x

O A

12"ø12"ø

FCU-3-02

FCU-3-01

FCU-3-10

FCU-3-04

FCU-3-06

FCU-3-03

FCU-3-05

FCU-3-07

FCU-3-08

FCU-3-09

FCU-1-14

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MH107

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

ATTIC PLAN - SOUTH WING - MECHANICAL HVAC

60042072 N40085-24-F-5940

GENERAL NOTES:

# PLAN NOTES

1 PROVIDE DOAS MOUNTED ON EQUIPMENT

PLATFORM IN ATTIC. COORDINATE EXACT

LOCATION ON PLATFORM WITH STRUCTURE

AND PROVIDE MANUFACTURER RECOMMENDED

CLEARANCES.

2 PROVIDE OUTSIDE AIR VENTILATION DUCTWORK

FROM EXTERIOR WALL LOUVER WITH CLASS 1A

MOTORIZED DAMPER TO DOAS OA INTAKE AS

SHOWN. PROVIDE DUCT PLENUM BEHIND

ARCHITECTURAL LOUVER, SIZE TO MATCH

MOTORIZED DAMPER SIZE. SEE

ARCHITECTURAL SHEETS FOR MORE

INFORMATION ON LOUVER TYPE AND SIZE.

3 PROVIDE EXHAUST AIR DUCTWORK FROM

EXTERIOR WALL LOUVER WITH CLASS 1A

MOTORIZED DAMPER TO DOAS EXHAUST

OUTLET AS SHOWN. PROVIDE DUCT PLENUM

BEHIND ARCHITECTURAL LOUVER, SIZE TO

MATCH MOTORIZED DAMPER SIZE. SEE

ARCHITECTURAL SHEETS FOR MORE

INFORMATION ON LOUVER TYPE AND SIZE.

4 PROVIDE EXHAUST AIR DUCTWORK FROM DOAS

EA INLET AND ROUTE AS SHOWN TO SPACES

BELOW. SEE FLOOR PLANS FOR CONTINUATION.

3/16" = 1'-0" A2

ATTIC PLAN - SOUTH WING - MECHANICAL HVAC

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

N

NTS

A5

KEY PLAN - SOUTH WING

DOAS-2

"ø

"ø

"ø

"ø

16"x14" EA

16"x14" EA

30"x18" OA

30"x18" EA30"x18" EA

"x

E

A

24"x22" OA

20"x20" EA

MD-9

MD-8

A1

M-302

C1

M-302

8"x14" OA

8"ø

"ø

8"ø

FCU-2-12

FCU-1-02

FCU-1-01

FCU-2-04 FCU-2-05

FCU-2-01

FCU-2-02

FCU-2-03

FCU-2-06 FCU-2-08

FCU-2-11

FCU-2-09FCU-2-07FCU-2-10

"ø

"ø1 "ø

"ø

14"x12" OA

"ø

"ø

18"x16" OA

18"x20" OA

"ø

16"x14" OA

"ø

8"x14" OA

"ø

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MH108

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

ATTIC PLAN - WEST WING - MECHANICAL HVAC

60042073 N40085-24-F-5940

GENERAL NOTES:

# PLAN NOTES

1 PROVIDE DOAS MOUNTED ON EQUIPMENT

PLATFORM IN ATTIC. COORDINATE EXACT

LOCATION ON PLATFORM WITH STRUCTURE

AND PROVIDE MANUFACTURER RECOMMENDED

CLEARANCES.

2 PROVIDE OUTSIDE AIR VENTILATION DUCTWORK

FROM EXTERIOR WALL LOUVER WITH CLASS 1A

MOTORIZED DAMPER TO DOAS OA INTAKE AS

SHOWN. PROVIDE DUCT PLENUM BEHIND

ARCHITECTURAL LOUVER, SIZE TO MATCH

MOTORIZED DAMPER SIZE. SEE

ARCHITECTURAL SHEETS FOR MORE

INFORMATION ON LOUVER TYPE AND SIZE.

3 PROVIDE EXHAUST AIR DUCTWORK FROM

EXTERIOR WALL LOUVER WITH CLASS 1A

MOTORIZED DAMPER TO DOAS EXHAUST

OUTLET AS SHOWN. PROVIDE DUCT PLENUM

BEHIND ARCHITECTURAL LOUVER, SIZE TO

MATCH MOTORIZED DAMPER SIZE. SEE

ARCHITECTURAL SHEETS FOR MORE

INFORMATION ON LOUVER TYPE AND SIZE.

4 PROVIDE OUTSIDE AIR VENTILATION DUCTWORK

FROM DOAS OA OUTLET AND ROUTE AS SHOWN

TO SPACES BELOW. SEE FLOOR PLANS FOR

CONTINUATION

5 PROVIDE EXHAUST AIR DUCTWORK FROM DOAS

EA INLET AND ROUTE AS SHOWN TO SPACES

BELOW. SEE FLOOR PLANS FOR CONTINUATION.

3/16" = 1'-0" B1

ATTIC PLAN - WEST WING - MECHANICAL HVAC

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

N

NTS

A5

KEY PLAN - WEST WING

MECHANICAL

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

TRAINING SPECIALIST

VESTIBULE

INFANT

ADMIN

ADMIN

COMM/CCTV

STORAGE

STAFF RR

PUBLIC RR

INFANT

CORRIDOR

LAUNDRY

BREAK ROOM

JANITOR

INFANT

INFANT

INFANT

INFANT

PRESCHOOL

TODDLER

TODDLER

TODDLER

TODDLER

STAFF RR

CLOSET

101A

CLOSET

102A

CLOSET

103A

CLOSET

104A

CLOSET

105A

CLOSET

108A

CLOSET

107A

CLOSET

106A

CLOSET

119A

CLOSET

126A

CLOSET

134A

CLOSET

132A

CLOSET

133A

CLOSET

142A

CLOSET

135A

CLOSET

145A

CLOSET

144A

CLOSET

143A

CLOSET

146A

CLOSET

149A

CLOSET

148A

CLOSET

151A

CLOSET

147A

CLOSET

150A

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

CORRIDOR

STAFF TRAINING

OFFICE

DEPUTY DIRECTOR

DIRECTOR

LOBBY

CORRIDOR

CORRIDOR

SCULLERY

KITCHEN

ELECTRICAL

DRY STORAGE

SPRINKLER

INFANT

PRESCHOOL

PRESCHOOL

PRESCHOOL

TODDLER

CORRIDOR

FCU-2-01

FCU-2-02

FCU-2-04

FCU-2-03

FCU-2-06

FCU-2-05

FCU-2-07

FCU-2-08

FCU-1-01

FCU-2-09

FCU-2-11

FCU-2-12

FCU-1-03

FCU-1-05

FCU-1-09FCU-1-07FCU-1-06FCU-1-04

FCU-1-12FCU-1-10FCU-1-08

FCU-3-02

FCU-3-01

FCU-3-04

FCU-3-03

FCU-3-05

FCU-3-06

FCU-3-07

FCU-3-09

FCU-1-11

UH-2

DAC-1

UH-3

AD-1

EF-1

EF-2

EF-3

FCU-1-13

FCU-3-10

FCU-2-10

FCU-3-08

FCU-1-02

DCU-1

OFFICE

117A

OFFICE

FCU-1-14

DOAS-3

DOAS-1

DOAS-2

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MP101

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

FIRST FLOOR PLAN - OVERALL - MECHANICAL PIPING

60042074 N40085-24-F-5940

GENERAL NOTES:

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. SEE CHILLED AND HOT WATER SYSTEM

DIAGRAMS FOR PIPE SIZING AND MORE

INFORMATION.

3. FAN COIL UNITS AND ASSOCIATED PIPING

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE SECTION VIEWS FOR ELEVATIONS

AND LOCATIONS OF EQUIPMENT.

1/8" = 1'-0" A1

FIRST FLOOR PLAN - OVERALL - MECHANICAL PIPING

GRAPHIC SCALE: 1/8"=1'-0"

8' 0 4' 8' 16'

N

DOAS-1

FCU-3-01

FCU-1-01

FCU-1-04

FCU-2-12

FCU-1-03 FCU-1-05

FCU-1-07FCU-1-06

FCU-1-08 FCU-1-10

FCU-1-11

FCU-1-12

FCU-1-09

FCU-1-14

UH-3

UH-2

STAFF TRAINING

VESTIBULE

ADMIN

ADMIN

COMM/CCTV

DEPUTY DIRECTOR

T

T

T

T

T

T

INFANT

CLOSET

119A

CLOSET

126A

CORRIDOR

STORAGE

INFANT

INFANT

INFANT

INFANT

INFANT

ELECTRICAL

MECHANICAL

SPRINKLER

INFANT

CLOSET

134A

CLOSET

132A

CLOSET

142A

CLOSET

135A

STORAGE

STAFF RR

PUBLIC RR

CORRIDOR

BREAK ROOM

JANITOR

SCULLERY

KITCHEN

ELECTRICAL

DRY STORAGE

LOBBY

TT T

T

TTT

T

T

T

PRESCHOOL

CORRIDOR

CLOSET

133A

TODDLER

TODDLER

CLOSET

143A

CLOSET

146A

CLOSET

144A

T

DAC-1

AD-1

1 1 1

2 2

DCU-1

FCU-1-13

FCU-3-10

EF-1

EF-2

EF-3

OFFICE

117A

OFFICE

T

T

T 2

DDC

CONTROL

PANEL

T

T

T

PRESCHOOL

CORRIDOR

LAUNDRY

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MP102

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

FIRST FLOOR PLAN - EAST WING - MECHANICAL PIPING

60042075 N40085-24-F-5940

# PLAN NOTES

1 PROVIDE 4-PIPE FAN COIL UNIT (FCU) ABOVE

SECOND GYPSUM BOARD CEILING. ROUTE

CHILLED AND HOT WATER PIPING TO UNIT AND

PROVIDE MANUFACTURER RECOMMENDED

CLEARANCES FOR SERVICE OF COILS AND

VALVING. PROVIDE FCU WITH SECONDARY

CONDENSATE DRAIN PAN. SEE FAN COIL DETAIL

FOR MORE INFORMATION.

2 PROVIDE WALL MOUNTED THERMOSTAT

MOUNTED AT 54" AFF.

3 PROVIDE CHILLED AND HOT WATER PIPING UP

FROM UNDERGROUND AND ROUTE TO

EQUIPMENT IN ATTIC. SEE ATTIC PLANS FOR

CONTINUATION.

4 PROVIDE HOT WATER UNIT HEATERS

SUSPENDED FROM STRUCTURE. COORDINATE

EXACT LOCATION WITH EQUIPMENT IN SPACE.

5 PROVIDE WALL MOUNTED DUCTLESS SPLIT AIR

HANDLER ABOVE DOOR. PROVIDE AIR HANDLER

WITH CONDENSATE PUMP AND ROUTE

CONDENSATE TO NEAREST DRAIN. ROUTE

REFRIGERANT PIPING IN MOST DIRECT ROUTE

POSSIBLE TO EXTERIOR CONDENSING UNIT

MOUNTED ON EQUIPMENT PAD ON GRADE..

3/16" = 1'-0" B1

FIRST FLOOR PLAN - EAST WING - MECHANICAL PIPING

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

GENERAL NOTES:

N

NTS

A5

KEY PLAN - EAST WING

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. SEE CHILLED AND HOT WATER SYSTEM

DIAGRAMS FOR PIPE SIZING AND MORE

INFORMATION.

3. FAN COIL UNITS AND ASSOCIATED PIPING

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE SECTION VIEWS FOR ELEVATIONS

AND LOCATIONS OF EQUIPMENT.

DOAS-3

FCU-3-07

T

T

TRAINING SPECIALIST

TODDLER

CORRIDOR

PRESCHOOL

TODDLER

CLOSET

151A

CLOSET

147A

CLOSET

150A

STAFF RR

TODDLER

CLOSET

148A

CLOSET

149A

PRESCHOOL

TODDLER

PRESCHOOL

TODDLER

CLOSET

146A

CLOSET

144A

CLOSET

145A

T

T

T

T T

T

T

FCU-3-10

FCU-3-09

FCU-3-08

FCU-3-05

FCU-3-06

FCU-3-04

FCU-3-03

FCU-3-01

OFFICE

117A

T 2

PRESCHOOL

CORRIDOR

LAUNDRY

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MP103

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

FIRST FLOOR PLAN - SOUTH WING - MECHANICAL PIPING

60042076 N40085-24-F-5940

# PLAN NOTES

1 PROVIDE 4-PIPE FAN COIL UNIT (FCU) ABOVE

SECOND GYPSUM BOARD CEILING. ROUTE

CHILLED AND HOT WATER PIPING TO UNIT AND

PROVIDE MANUFACTURER RECOMMENDED

CLEARANCES FOR SERVICE OF COILS AND

VALVING. PROVIDE FCU WITH SECONDARY

CONDENSATE DRAIN PAN. SEE FAN COIL DETAIL

FOR MORE INFORMATION.

2 PROVIDE WALL MOUNTED THERMOSTAT

MOUNTED AT 54" AFF.

3/16" = 1'-0" A2

FIRST FLOOR PLAN - SOUTH WING - MECHANICAL PIPING

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

GENERAL NOTES:

N

NTS

A5

KEY PLAN - SOUTH WING

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. SEE CHILLED AND HOT WATER SYSTEM

DIAGRAMS FOR PIPE SIZING AND MORE

INFORMATION.

3. FAN COIL UNITS AND ASSOCIATED PIPING

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE SECTION VIEWS FOR ELEVATIONS

AND LOCATIONS OF EQUIPMENT.

DOAS-2

FCU-2-01

FCU-2-03

FCU-2-06

FCU-2-08

FCU-2-11

FCU-2-09

FCU-2-12

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

PRETODDLER

STAFF TRAINING

OFFICE

DIRECTOR

CLOSET

101A

CLOSET

102A

CLOSET

103A

CLOSET

104A

CLOSET

105A

CLOSET

108A

CLOSET

107A

CLOSET

106A

PRETODDLER

CORRIDOR

CLOSET

102A

CLOSET

103A

CLOSET

107A

CLOSET

106A

T

T T T

T T T

T

TRAINING SPECIALIST

TODDLER

TT

1 1

2 2 2 2 2

FCU-2-02

FCU-2-04

FCU-2-05

FCU-2-07

FCU-1-01

FCU-2-10

OFFICE

117A

OFFICE

T

T

T

T

T

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MP104

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

FIRST FLOOR PLAN - WEST WING - MECHANICAL PIPING

60042077 N40085-24-F-5940

# PLAN NOTES

1 PROVIDE 4-PIPE FAN COIL UNIT (FCU) ABOVE

SECOND GYPSUM BOARD CEILING. ROUTE

CHILLED AND HOT WATER PIPING TO UNIT AND

PROVIDE MANUFACTURER RECOMMENDED

CLEARANCES FOR SERVICE OF COILS AND

VALVING. PROVIDE FCU WITH SECONDARY

CONDENSATE DRAIN PAN. SEE FAN COIL DETAIL

FOR MORE INFORMATION.

2 PROVIDE WALL MOUNTED THERMOSTAT

MOUNTED AT 54" AFF.

3/16" = 1'-0" B1

FIRST FLOOR PLAN - WEST WING - MECHANICAL PIPING

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

GENERAL NOTES:

N

NTS

A5

KEY PLAN - WEST WING

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. SEE CHILLED AND HOT WATER SYSTEM

DIAGRAMS FOR PIPE SIZING AND MORE

INFORMATION.

3. FAN COIL UNITS AND ASSOCIATED PIPING

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE SECTION VIEWS FOR ELEVATIONS

AND LOCATIONS OF EQUIPMENT.

DOAS-3

FCU-2-02

FCU-2-01

FCU-2-03

FCU-2-04 FCU-2-05

FCU-2-06

FCU-2-10 FCU-2-07

FCU-2-09

FCU-2-08

FCU-2-11

FCU-1-02

FCU-2-12

F C

U -1

-0

FCU-1-04

FCU-1-03

FCU-1-06

FCU-1-13 FCU-1-05

FCU-1-07

FCU-1-08

FCU-1-09

FCU-1-10 FCU-1-12

FCU-1-11

FCU-1-14

FCU-3-01

FCU-3-10

FCU-3-02

FCU-3-04

FCU-3-06

FCU-3-03

FCU-3-05

FCU-3-07

FCU-3-08

FCU-3-09

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MP105

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

ATTIC PLAN - OVERALL - MECHANICAL PIPING

60042078 N40085-24-F-5940

1/8" = 1'-0" A1

ATTIC PLAN - OVERALL - MECHANICAL PIPING

GRAPHIC SCALE: 1/8"=1'-0"

8' 0 4' 8' 16'

GENERAL NOTES:

N

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. SEE CHILLED AND HOT WATER SYSTEM

DIAGRAMS FOR PIPE SIZING AND MORE

INFORMATION.

3. FAN COIL UNITS AND ASSOCIATED PIPING

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE SECTION VIEWS FOR ELEVATIONS

AND LOCATIONS OF EQUIPMENT.

FCU-1-02

F C

U -1

-0

FCU-1-04

FCU-1-06 FCU-1-07 FCU-1-09 FCU-1-11

FCU-1-12FCU-1-10FCU-1-08FCU-1-13

FCU-1-03

FCU-2-12

FCU-1-14

FCU-3-01

FCU-3-02

FCU-3-10

FCU-1-05

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MP106

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

ATTIC PLAN - EAST WING - MECHANICAL PIPING

60042079 N40085-24-F-5940

# PLAN NOTES

1 PROVIDE DOAS MOUNTED ON EQUIPMENT

PLATFORM IN ATTIC. ROUTE CHILLED AND HOT

WATER PIPING TO UNIT AND PROVIDE

MANUFACTURER RECOMMENDED CLEARANCES

FOR SERVICE OF COILS AND VALVING.

2 PROVIDE 4-PIPE FAN COIL UNIT (FCU) ABOVE

SECOND GYPSUM BOARD CEILING. UNIT TO BE

INSTALLED AT ELEVATION AND ORIENTATION TO

ALLOW FOR MAINTENANCE ACCESS FROM

CATWALK. PROVIDE CHILLED AND HOT WATER

PIPING TO 4-PIPE FAN COIL UNIT (FCU). INSTALL

PER MANUFACTURER INSTALLATION

INSTRUCTIONS AND PROVIDE RECOMMENDED

CLEARANCES FOR SERVICE OF COILS AND

VALVING. FCU TO BE PROVIDED WITH

SECONDARY CONDENSATE DRAIN PAN. SEE

FLOOR PLANS FOR CONTINUATION.

3 PROVIDE CHILLED AND HOT WATER PIPING UP

FROM LEVEL BELOW AND ROUTE TO

EQUIPMENT IN ATTIC AS SHOWN. COORDINATE

EXACT ROUTING WITH OTHER EQUIPMENT,

DUCTWORK AND STRUCTURE IN ATTIC.

3/16" = 1'-0" B1

ATTIC PLAN - EAST WING - MECHANICAL PIPING

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

GENERAL NOTES:

N

NTS

A5

KEY PLAN - EAST WING

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. SEE CHILLED AND HOT WATER SYSTEM

DIAGRAMS FOR PIPE SIZING AND MORE

INFORMATION.

3. FAN COIL UNITS AND ASSOCIATED PIPING

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE SECTION VIEWS FOR ELEVATIONS

AND LOCATIONS OF EQUIPMENT.

2 PPI REVISION 2 03.09.26

DOAS-3

FCU-3-01

FCU-3-02

FCU-3-10

FCU-3-04

FCU-3-06

FCU-3-03

FCU-3-05

FCU-3-07

FCU-3-08

FCU-3-09

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MP107

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

ATTIC PLAN - SOUTH WING - MECHANICAL PIPING

60042080 N40085-24-F-5940

# PLAN NOTES

1 PROVIDE DOAS MOUNTED ON EQUIPMENT

PLATFORM IN ATTIC. ROUTE CHILLED AND HOT

WATER PIPING TO UNIT AND PROVIDE

MANUFACTURER RECOMMENDED CLEARANCES

FOR SERVICE OF COILS AND VALVING.

2 PROVIDE 4-PIPE FAN COIL UNIT (FCU) ABOVE

SECOND GYPSUM BOARD CEILING. UNIT TO BE

INSTALLED AT ELEVATION AND ORIENTATION TO

ALLOW FOR MAINTENANCE ACCESS FROM

CATWALK. PROVIDE CHILLED AND HOT WATER

PIPING TO 4-PIPE FAN COIL UNIT (FCU). INSTALL

PER MANUFACTURER INSTALLATION

INSTRUCTIONS AND PROVIDE RECOMMENDED

CLEARANCES FOR SERVICE OF COILS AND

VALVING. FCU TO BE PROVIDED WITH

SECONDARY CONDENSATE DRAIN PAN. SEE

FLOOR PLANS FOR CONTINUATION.

3/16" = 1'-0" A2

ATTIC PLAN - SOUTH WING - MECHANICAL PIPING

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

GENERAL NOTES:

N

NTS

A5

KEY PLAN - SOUTH WING

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. SEE CHILLED AND HOT WATER SYSTEM

DIAGRAMS FOR PIPE SIZING AND MORE

INFORMATION.

3. FAN COIL UNITS AND ASSOCIATED PIPING

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE SECTION VIEWS FOR ELEVATIONS

AND LOCATIONS OF EQUIPMENT.

2 PPI REVISION 2 03.09.26

FCU-2-02

FCU-2-01

FCU-2-04

FCU-2-03

FCU-2-06

FCU-2-05

FCU-2-10 FCU-2-07 FCU-2-09

FCU-2-11

FCU-1-02

F C

U -1

-0

FCU-2-12

FCU-2-08

2 2

2 2

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

MP108

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

ATTIC PLAN - WEST WING - MECHANICAL PIPING

60042081 N40085-24-F-5940

# PLAN NOTES

1 PROVIDE DOAS MOUNTED ON EQUIPMENT

PLATFORM IN ATTIC. ROUTE CHILLED AND HOT

WATER PIPING TO UNIT AND PROVIDE

MANUFACTURER RECOMMENDED CLEARANCES

FOR SERVICE OF COILS AND VALVING.

2 PROVIDE 4-PIPE FAN COIL UNIT (FCU) ABOVE

SECOND GYPSUM BOARD CEILING. UNIT TO BE

INSTALLED AT ELEVATION AND ORIENTATION TO

ALLOW FOR MAINTENANCE ACCESS FROM

CATWALK. PROVIDE CHILLED AND HOT WATER

PIPING TO 4-PIPE FAN COIL UNIT (FCU). INSTALL

PER MANUFACTURER INSTALLATION

INSTRUCTIONS AND PROVIDE RECOMMENDED

CLEARANCES FOR SERVICE OF COILS AND

VALVING. FCU TO BE PROVIDED WITH

SECONDARY CONDENSATE DRAIN PAN. SEE

FLOOR PLANS FOR CONTINUATION.

3/16" = 1'-0" B1

ATTIC PLAN - WEST WING - MECHANICAL PIPING

GRAPHIC SCALE: 3/16"=1'-0"

6' 0 4' 10'

GENERAL NOTES:

N

NTS

A5

KEY PLAN - WEST WING

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. SEE CHILLED AND HOT WATER SYSTEM

DIAGRAMS FOR PIPE SIZING AND MORE

INFORMATION.

3. FAN COIL UNITS AND ASSOCIATED PIPING

SHOWN IS LOCATED IN ATTIC AND SHOWN ON

FLOOR PLANS FOR COORDINATION PURPOSES

ONLY. SEE SECTION VIEWS FOR ELEVATIONS

AND LOCATIONS OF EQUIPMENT.

2 PPI REVISION 2 03.09.26

TOP OF WALL

10' - 8"

FIRST FLOOR

0' - 0"

C1

M-301

DOAS-1

SD

20"x20" EA

18"x30" OA

16"x12" OA

12"x8" OA8"ø OA

8"ø OA

16"x40" RA

12"x20" EA 20"x20" EA 12"x20" EA 12"x16" EA 12"x12" EA

20"x20" EA 10"ø EA

16"x18" OA

18"x18" OA

6"ø OA

"ø

E A

"ø

O A

12"x18" OA

"ø

O A

"ø

O A

6"ø EA6"ø EA

"x

E A

"x

E A

"ø

O A

FCU-1-12

FCU-1-10

"x

12"x18"

FCU-1-09

FCU-1-08

FCU-1-06 FCU-1-04FCU-1-03

"ø

10"ø

"ø

TOP OF WALL

10' - 8"

FIRST FLOOR

0' - 0"

A1

M-301

DOAS-1

12"ø OA

8"ø OA12"x8" SA

"ø

S A

10"ø EA

"x

E

A

FCU-1-10

"ø

O A

"x

E

A

"ø

O A

14"ø OA

14"x14" SA

14"ø OA

10"x10" EA

20"x20" EA

30"x18" OA

60"x20" OA

12"x12" OA

6"x6" EA

H-1

E5

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

M-301

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

MECHANICAL SECTION VIEW

60042083 N40085-24-F-5940

GENERAL NOTES:

GRAPHIC SCALE: 1/4"=1'-0"

4' 0 2' 4' 8'

3/8" = 1'-0" C1

WEST SECTION VIEW AT DOAS-1

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

1/4" = 1'-0" A1

SOUTH SECTION VIEW AT DOAS-1

GRAPHIC SCALE: 3/8"=1'-0"

3' 0 2' 6'

FIRST FLOOR

0' - 0"

C1

M-302

DOAS-2

SD

18"x30" EA

18"x30" OA

20"x60" OA

14"x16" EA

14"x16" OA

"ø

O A

14"x8" OA14"x8" OA

"ø

O A

"ø

O A

14"ø RA

8"ø OA

10"ø SA

"ø

E A

"x

E A

"x

E A

"ø

O A

22"x24" OA "ø

O A

16"x14" OA

18"x30" EA 14"x16" EA

12"x14" OA

12"ø OA

8"ø OA

20"x20" EA

14"x16" EA 14"x16" EA

18"x30" OA

FCU-2-02

12"ø OAFCU-2-06FCU-2-10

FCU-2-07FCU-2-09FCU-2-11

FCU-1-02

"x

"x

E5

E5

E5

E5

TOP OF WALL

10' - 8"

FIRST FLOOR

0' - 0"

A1

M-302

18"x30" EA

"x

E

A

12"ø OA

"ø

E A

"ø

O A

12"ø OA

10"ø EA

12"ø OA

12"x8" SA8"ø SA

"ø

S A

8"ø OA

"x

E

A

FCU-2-04

"ø

R A

"x

E

A

DOAS-2

10"ø EA

"ø

R A

"x

O A

60"x20" OA

"ø

O A

"ø

O A

"ø

O A

"x

E

A

12"ø OA

"ø

S A

E5

E5

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

M-302

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

MECHANICAL SECTION VIEW

60042084 N40085-24-F-5940

GENERAL NOTES:

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

1/4" = 1'-0" A1

SOUTH SECTION VIEW AT DOAS-2

GRAPHIC SCALE: 1/4"=1'-0"

4' 0 2' 4' 8'

GRAPHIC SCALE: 3/8"=1'-0"

3' 0 2' 6'

3/8" = 1'-0" C1

EAST SECTION VIEW AT DOAS-2

FIRST FLOOR

0' - 0"

C1

M-303

SD

24"x22" OA

18"x30" EA

18"x30" OA20"x60" OA

16"x18" EA

14"x12" OA

14"x16" OA

14"x20" OA 18"x30" EA

"ø

E A

10"ø EA10"ø EA12"ø OA

8"ø OA

"x

E A

"x

E A

DOAS-3

14"x16" EA

12"ø OA

16"x16" OA

8"ø OA

14"x14" EA 12"ø OA

"x

E A

"x

E A

10"ø SA

8"ø OA

10"ø SA

8"ø OA

"ø

E A

"ø

E A

20"x20" OA

20"x22" EA

18"x16" EA

"x

E A

10"ø EA8"ø OA

FCU-3-10 FCU-3-01FCU-3-04FCU-3-03FCU-3-05FCU-3-07

FCU-3-09

"ø

O A

TOP OF WALL

10' - 8"

FIRST FLOOR

0' - 0"

A1

M-303

DOAS-3

12"ø OA

12"x8" SA

8"ø OA

12"ø OA

18"x30" EA

20"x60" EA

30"x18" OA

30"x18" OA

60"x20" OA

16"x18" EA

12"ø OA

"ø

E A

"ø

E A

"ø

E A

"ø

E A

12"ø OA

"ø

O A

"ø

O A

10"ø EA

12"x8" SA

12"ø OA

6"ø SA 8"ø SA

FCU-3-07

"ø

"ø

FCU-3-03

E5

"x

E5

"x

10"ø

12"ø OA

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

M-303

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

MECHANICAL SECTION VIEW

60042085 N40085-24-F-5940

GENERAL NOTES:

1. SEE SHEET M-001 FOR GENERAL NOTES,

LEGEND & ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NO ILLUSTRATE SPECIFIC

DUCT TAKE-OFF CONFIGURATIONS OR TAPS.

GRAPHIC SCALE: 1/4"=1'-0"

4' 0 2' 4' 8'

GRAPHIC SCALE: 3/8"=1'-0"

3' 0 2' 6'

1/4" = 1'-0" A1

WEST SECTION VIEW AT DOAS-3

3/8" = 1'-0" C1

NORTH SECTION VIEW AT DOAS-3

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

M-601

PJR

JDL

JENNI REED

LWM

MECHANICAL REPAIRS

BUILDING TT113

MECHANICAL SCHEDULES

60042093 N40085-24-F-5940

HEATING 70°F 60°F 55°F 50%

ALL OTHER ROOMS

COOLING 75°F 80°F 85°F 50%

HEATING - - 41°F (MIN) 8% (MIN)

TELECOM ROOM

COOLING 68°F - 95°F (MAX) 80% (MAX)

EXTERIOR OR PRIMARY ELECTRICAL EQUIPMENT ROOMS ONLY. OTHERWISE FOLLOW UFC 3-410-01.

HEATING 41°F (MIN) - 41°F (MIN) 8% (MIN)

ELECTRICAL ROOM

COOLING 95°F (MAX) - 95°F (MAX) 80% (MAX)

NFPA 72 10.3.5. FOLLOW THIS OR MANUFACTURER'S REQUIREMENTS, WHICHEVER IS MORE STRINGENT.

HEATING 32°F (MIN) - 32°F (MIN) 0-85%

FIRE ALARM/SPRINKLER

COOLING 120°F (MAX) - 120°F (MAX) 0-85%

SPACE CLASSIFICATION SEASON OCCUPIED UNOCCUPIED ALARM RELATIVE HUMIDITY

INDOOR DESIGN CONDITIONS

83.3 (1.0% ASHRAE) 140.62 (1.0% ASHRAE)

MCDB (°F) W (grains H2O/lbm dry air)

DEHUMIDIFICATION CONDITIONS

WINTER 22 (99.6% ASHRAE)

SUMMER 91/77 (1% ASHRAE)

SEASON DB/WB (°F)

OUTDOOR DESIGN CONDITIONS

DESIGN CONDITIONS

14. PROVIDE VENTILATION SUPPLY DUCTWORK WITH SMOKE DETECTOR.

13. PROVIDE UNIT WITH A MINIMUM 8" INTEGRAL BASE FRAME. EQUIPMENT SUPPORTS TO HAVE VIBRATION ISOLATION. SEE DETAILS AND STRUCTURAL DRAWINGS FOR MORE INFORMATION.

12. AIR HANDLER DESIGNED WITH A FOULING FACTOR OF 0.00025 FT^2-HR-°F/BTU FOR ALL COILS.

11. MAXIUMUM ALLOWABLE DISCHARGE OR RADIATED NOISE CRITERIA (NC) = 30.

10. PROVIDE UNIT WITH RECIRCULATION PUMP AT PREHEAT COIL FOR FREEZE PROTECTION. ALSO PROVIDE 120/1 CIRCUIT FOR PUMP. PUMP IS SIZED FOR 110% OF PREHEAT COIL PRESSURE DROP AND DESIGN FLOW GPM. SEE HOT WATER PREHEAT COIL DETAIL AND CONTROLS FOR FURTHER INFORMATION.

9. REFER TO CV SCHEDULE FOR CONTROL VALVE REQUIREMENTS.

8. PROVIDE UNIT WITH SINGLE POINT CONNECTION.

7. UNIT MUST HAVE CROSSFLOW FIXED PLATE TOTAL ENTHALPY HEAT EXCHANGER, PLENUM SUPPLY/EXHAUST FANS, COOLING COIL, REHEAT COIL AND MARINE LIGHTS IN EACH FAN & ACCESS SECTIONS.

6. PROVIDE A 10,000 HR SALT SPRAY PROTECTIVE COATING ON THE COOLING AND REHEAT COILS.

5. VERIFY THAT UNIT CAN BE INSTALLED IN LOCATION SHOWN ON DRAWINGS PRIOR TO SUBMITTING FOR APPROVAL.

4. PROVIDE UNIT WITH HORIZONTAL SUPPLY DISCHARGE, EXHAUST INLET AND OUTSIDE AIR INLET DUCT CONNECTION. UNIT MUST HAVE 2" DOUBLE WALL CONSTRUCTION.

3. PROVIDE WITH CLASS 1A LOW LEAKAGE DAMPERS ON THE EXHAUST DISCHARGE AND OUTSIDE AIR INTAKE UNIT CONNECTIONS.

2. PROVIDE PREMIUM EFFICIENCY MOTORS FOR SUPPLY AND EXHAUST FANS, COMPATIBLE WITH VARIABLE FREQUENCY DRIVES.

1. PROVIDE WITH 2" MERV 8 FILTERS ON THE EXHAUST AND 2" MERV 8 PREFILTERS & 2" MERV 13 FINAL FILTERS ON THE RETURN AND OUTSIDE AIR INTAKE, STATIC PRESSURE INCREASE FROM CLEAN FILTERS IS INCLUDED IN THE SCHEDULED TOTAL STATIC PRESSURE VALUE.

REMARKS

TOTALS: 533.8 35.6 997.8 199.6 246.8 16.5

DOAS-3 3505 1.50 2.98 3225 1.50 2.09 174.6 22.0 68.0 550 5.00 140.0 110.0 5.00 11.6 326.4 123.0 0.38 84.0 78.6 52.0 52.0 550 5.00 44.0 54.0 5.00 6 65.3 80.7 55.0 76.0 550 5.00 140.0 110.0 5.00 5.4 1.0 2.9 5.0 1.0 4.0 5.0 17.1 19.1 25.0 480/3 3200 180" 55" - 1-14

DOAS-2 3195 1.50 3.67 2900 1.50 2.79 159.2 22.0 68.0 550 5.00 140.0 110.0 5.00 10.6 297.5 112.1 0.38 84.0 78.6 52.0 52.0 550 5.00 44.0 54.0 5.00 6 59.5 73.6 55.0 76.0 550 5.00 140.0 110.0 5.00 4.9 1.0 4.0 5.0 1.0 2.9 5.0 17.1 19.1 25.0 480/3 3200 180" 55" - 1-14

DOAS-1 3915 1.50 5.20 3525 1.50 3.34 200.0 22.0 68.0 550 5.00 140.0 110.0 5.00 13.3 373.9 140.9 0.38 84.0 78.6 52.0 52.0 550 5.00 44.0 54.0 5.00 6 74.8 92.5 55.0 76.0 550 5.00 140.0 110.0 5.00 6.2 1.0 5.8 7.5 1.0 3.6 5.0 19.9 22.6 30.0 480/3 3200 180" 55" - 1-14

(IN.WG) (IN. WG) (IN. WG) (IN. WG) (MBH) ( ºF) ( ºF) (FPM) (FT. WG) ( ºF) ( ºF) (FT. WG) (MBH) (MBH) ( ºF) ( ºF) ( ºF) ( ºF) (FPM) (FT. WG) ( ºF) ( ºF) (FT. WG) (MBH) ( ºF) ( ºF) (FPM) (FT. WG) ( ºF) ( ºF) (FT. WG) QTY BHP HP QTY BHP HP FLA MCA MOP (LBS) LENGTH WIDTH HEIGHT

CFM CFM VEL. MAX MAX DB WB DB WB VEL. MAX MAX VEL. MAX MAX

SA

ESP TSP

EA

ESP TSP

TOTAL

CAP.

EAT LAT

FACE AIR PD

EWT LWT

WATER PD

GPM

TOTAL

CAP.

SENS.

CAP. SHR

EAT EAT LAT LAT FACE AIR PD

EWT LWT

WATER PD

MIN. NUM. OF

ROWS

GPM

TOTAL

CAP.

EAT LAT

FACE AIR PD

EWT LWT

WATER PD

GPM

SUPPLY FAN EXHAUST FAN

SINGLE POINT

CONNECTION V/PH

MARK

SUPPLY FAN EXHAUST FAN PREHEAT HEATING CAPACITY (HOT WATER) COOLING CAPACITY (CHILLED WATER) REHEAT HEATING CAPACITY (HOT WATER) ELECTRICAL

UNIT

WEIGHT

MAX DIMENSIONS

REMARKS

DEDICATED OUTSIDE AIR SYSTEM (DOAS) SCHEDULE

83.3 78.5 76.0 50.0 80.1 76.9 26.8 22.4 70.0 35.0 51.7 37.5 58.8 / 76.7

83.3 78.5 76.0 50.0 81.7 76.9 26.8 22.4 70.0 35.0 48.1 35.5 39 / 65.3

83.3 78.5 76.0 50.0 81.2 77.0 26.8 22.4 70.0 35.0 48.8 35.9 35.4 / 63.7

DB WB DB %RH DB WB DB WB DB %RH DB WB

OA RA SA OA RA SA

SUMMER WINTER HX EFF.

SUMMER/

WINTER %

TOTAL ENERGY HEAT EXCHANGER

6. PROVIDE UNIT WITH SECONDARY DRAIN PAN AND DRAIN PAN FLOAT SWITCH TO CLOSE CHILLED WATER VALVE UPON ALARM.

5. PROVIDE UNIT WITH SINGLE POINT POWER CONNECTION.

4. VERIFY THAT UNIT CAN BE INSTALLED IN LOCATION SHOWN ON DRAWINGS PRIOR TO SUBMITTING FOR APPROVAL.

3. PROVIDE UNIT WITH HORIZONTAL SUPPLY DISCHARGE AND HORIZONTAL RETURN INLET DUCT CONNECTIONS. UNIT MUST HAVE 2" DOUBLE WALL CONSTRUCTION.

2. PROVIDE ECM MOTOR FOR SUPPLY FAN. UNIT LEFT HAND AND RIGHT HAND CONFIGURATION FOR CONTROL PANEL AND COIL CONNECTIONS MUST BE PROVIDED TO ALLOW FOR ACCESS FROM CATWALK.

1. PROVIDE WITH TOP ACCESS FILTER SECTION WITH 2" MERV-8 EFFICIENCY THROWAWAY FLAT FILTER. PROVIDE WITH FIVE (5) SETS TOTAL: ONE (1) FOR STARTUP, ONE (1) FOR BOD, TWO (2) IN BOX, AND ONE (1) FOR 2ND SEASON. CHANGE FILTERS AT BOD AND 2ND SEASON TAB.

REMARKS:

TOTALS: 613.6 122.7 447.9 38.1 23.4

FCU-3-10 650 375 0.50 1.07 19.7 15.1 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.9 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.36 0.725 4.7 / 15 130 1,2,3,4,5,6

FCU-3-09 700 500 0.50 1.15 21.1 16.3 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 4.2 16.2 65 / 95 140 / 110 1.40 9.2 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.145 0.693 4.7 / 15 130 1,2,3,4,5,6

FCU-3-08 800 500 0.50 1.31 24.2 18.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 4.8 16.2 65 / 95 140 / 110 1.40 9.2 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.609 0.733 4.7 / 15 130 1,2,3,4,5,6

FCU-3-07 600 375 0.50 1.42 18.1 14.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.6 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.355 0.732 4.7 / 15 130 1,2,3,4,5,6

FCU-3-06 600 375 0.50 1.42 18.1 14.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.6 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.355 0.732 4.7 / 15 130 1,2,3,4,5,6

FCU-3-05 700 500 0.50 1.15 21.1 16.3 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 4.2 16.2 65 / 95 140 / 110 1.40 9.2 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.145 0.693 4.7 / 15 130 1,2,3,4,5,6

FCU-3-04 600 375 0.50 1.42 18.1 14.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.6 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.355 0.732 4.7 / 15 130 1,2,3,4,5,6

FCU-3-03 700 500 0.50 1.15 21.1 16.3 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 4.2 16.2 65 / 95 140 / 110 1.40 9.2 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.145 0.693 4.7 / 15 130 1,2,3,4,5,6

FCU-3-02 600 375 0.50 1.42 18.1 14.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.6 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.355 0.732 4.7 / 15 130 1,2,3,4,5,6

FCU-3-01 700 375 0.50 1.15 21.1 16.3 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 4.2 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.145 0.693 4.7 / 15 130 1,2,3,4,5,6

FCU-2-12 500 250 0.50 1.15 12.1 9.3 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 2.4 8.1 65 / 95 140 / 110 0.70 4.6 55 / 72 140 / 110 0.35 5.0 4 2 277/1 0.145 0.693 4.7 / 15 120 1,2,3,4,5,6

FCU-2-11 750 500 0.50 1.23 23.9 17.5 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 4.8 16.2 65 / 95 140 / 110 1.40 9.2 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.517 0.733 4.7 / 15 130 1,2,3,4,5,6

FCU-2-10 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-2-09 300 250 0.50 0.86 9.1 7.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 1.8 8.1 65 / 95 140 / 110 0.70 4.6 55 / 72 140 / 110 0.35 5.0 4 2 277/1 0.085 0.645 4.7 / 15 120 1,2,3,4,5,6

FCU-2-08 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-2-07 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-2-06 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-2-05 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-2-04 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-2-03 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-2-02 600 375 0.50 1.42 18.1 14.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.6 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.355 0.732 4.7 / 15 120 1,2,3,4,5,6

FCU-2-01 600 375 0.50 1.42 18.1 14.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.6 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.355 0.732 4.7 / 15 120 1,2,3,4,5,6

FCU-1-14 525 250 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 8.1 65 / 95 140 / 110 0.70 4.6 55 / 72 140 / 110 0.35 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-1-13 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-1-12 600 375 0.50 1.42 18.1 14.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.6 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.355 0.732 4.7 / 15 120 1,2,3,4,5,6

FCU-1-11 1375 800 0.50 1.05 41.6 32.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 8.3 25.9 65 / 95 140 / 110 1.75 14.7 55 / 72 140 / 110 1.05 5.0 4 2 277/1 0.521 1.198 7.23 / 15 120 1,2,3,4,5,6

FCU-1-10 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-1-09 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-1-08 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-1-07 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-1-06 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-1-05 400 250 0.50 1.15 12.1 9.3 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 2.4 8.1 65 / 95 140 / 110 0.70 4.6 55 / 72 140 / 110 0.35 5.0 4 2 277/1 0.145 0.693 4.7 / 15 120 1,2,3,4,5,6

FCU-1-04 500 375 0.50 1.44 15.1 11.6 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 3.0 12.2 65 / 95 140 / 110 1.05 6.9 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.242 0.723 4.7 / 15 120 1,2,3,4,5,6

FCU-1-03 400 400 0.50 1.15 12.1 9.3 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 2.4 13.0 65 / 95 140 / 110 1.05 7.3 55 / 72 140 / 110 0.70 5.0 4 2 277/1 0.145 0.693 4.7 / 15 120 1,2,3,4,5,6

FCU-1-02 500 250 0.50 1.15 12.1 9.3 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 2.4 8.1 65 / 95 140 / 110 0.70 4.6 55 / 72 140 / 110 0.35 5.0 4 2 277/1 0.145 0.693 4.7 / 15 120 1,2,3,4,5,6

FCU-1-01 300 250 0.50 0.86 9.1 7.0 76.2 67.0 57.0 57.0 44 / 54 5.0 3 4 1.8 8.1 65 / 95 140 / 110 0.70 4.6 55 / 72 140 / 110 0.35 5.0 4 2 277/1 0.085 0.645 4.7 / 15 120 1,2,3,4,5,6

ºF ºF ºF ºF EWT/LWT

(DB) (WB) (DB) (WB)

MAX

CFM

MIN CFM

E.S.P.

"WC

T.S.P.

"WC

TOTAL

MBH

SENSIBLE

MBH

EAT EAT LAT LAT WATER TEMP.

(ºF) WATER PD

FT. MAX.

VELOCITY

FPS, MAX

MIN. NUM. OF

ROWS

GPM

TOTAL

MBH

EAT/LAT ºF EWT/LWT ºF GPM

TOTAL

MBH

EAT/LAT ºF EWT/LWT ºF GPM

HEATING REHEAT (DEHUMIDIFICATION)

WATER PD

FT. MAX

VELOCITY

FPS, MAX

ROWS V/PH BHP ECM HP MCA/MOP

MARK

COOLING CAPACITY (CHW)

HEATING CAPACITY (HW) ELECTRICAL

UNIT

WEIGHT

(LBS)

REMARKS

FAN COIL UNIT (FCU) SCHEDULE

4. PROVIDE BLANKET INSULATION ON THE BACK OF ALL DIFFUSERS.

3. ALL AIR DISTRIBUTION MUST BE 100% ALUMINUM CONSTRUCTION.

2. PROVIDE WITH SQUARE TO ROUND TRANSITION.

1. VERIFY CONSTRUCTION TYPES WITH ARCHITECTURAL PLANS TO DETERMINE MOUNTING DETAILS AND ACCESSORIES REQUIRED. COORDINATE COLOR W/ ARCHITECT.

REMARKS

R7 PERFORATED RETURN DIFFUSER NA 24X24 16"ø SURFACE 940 940 30

R6 PERFORATED RETURN DIFFUSER NA 24X24 16"ø LAY-IN 725 CFM 950 CFM 30 1-4

R5 PERFORATED RETURN DIFFUSER NA 24X24 14"ø LAY-IN 425 CFM 700 CFM 30 1-4

R4 PERFORATED RETURN DIFFUSER NA 24X24 12"ø LAY-IN 300 CFM 400 CFM 30 1-4

R3 PERFORATED RETURN DIFFUSER NA 24X24 10"ø LAY-IN 200 CFM 275 CFM 30 1-4

R2 PERFORATED RETURN DIFFUSER NA 24X24 8"ø LAY-IN 100 CFM 175 CFM 30 1-4