About this file

This is a Questions and Answers (Q&A) document for a federal construction solicitation at Camp Lejeune, North Carolina, dated May 29 through June 15, 2026. The document contains inquiries from prospective bidders and government responses regarding specifications, drawings, and solicitation requirements for a major construction project estimated between $100 million and $250 million involving three Special Operations Forces (SOF) facilities.

Key technical clarifications address discrepancies in electrical drawings (conduit sizing, cable schedules, duct bank configurations), mechanical systems (louver schedules, water meter details, control wiring requirements), architectural elements (door hardware sets, window designations, wall finishes), and RF shielding specifications for secure facilities. Critical issues include the removal and subsequent reissuance of Controlled Unclassified Information (CUI) drawings requiring NDA execution and CMMC Level 2 compliance for subcontractors, which raised concerns about fair competition and timeline adequacy. The government declined to extend the original proposal due date but noted inquiries would be considered. Major unresolved questions concern IEEE 299 RF shielding testing parameters, structural beam detail conflicts, dampproofing specifications, roof warranty requirements, and the scope of essential personnel needed for project management. The government confirmed hiring an independent commissioning firm, clarified that repair and renovation projects do not qualify under corporate experience factors, and addressed utility cost responsibility, security requirements (US Citizens and Persons authorized to work), and tree removal responsibilities assigned to the King Timber Resources (KTR).

View the file

Other files

File Type Posted
P1550 PPI RESPONSES 5.pdf PDF
AMENDMENT 0010 - N4008526R0138.pdf PDF
AMENDMENT 0009 - N4008526R0138.pdf PDF
P1550 PPI RESPONSES 3.pdf PDF
AMENDMENT 0008 - N4008526R0138.pdf PDF
WD NC20260010.pdf PDF
1701820 Continuation Sheet_0004.pdf PDF
1701820dwg_Revision_0004_A2.pdf PDF
P1550 PPI RESPONSES 3.pdf PDF
AMENDMENT 0006- 26R0138.pdf PDF
AMENDMENT 0005 - 26R0138.pdf PDF
13 34 19.pdf PDF
1701820 Continuation Sheet.docx DOCX document
AMENDMENT 0004 - 26R0138.pdf PDF
1701820dwg_Revision_0003_A2.pdf PDF
AMENDMENT 0003 - 26R0138.pdf PDF
1701820 Continuation Sheet .docx DOCX document
1701820dwg01of01.pdf PDF
08 33 23.pdf PDF
AMENDMENT 0002 - 26R0138.pdf PDF
1701820dwg_Revision_0001_A2-A3-Site.pdf PDF
03 30 00.pdf PDF
P1550 Site Visit Sign-in Sheet.pdf PDF
26 32 15.00.pdf PDF
26 56 00.pdf PDF
1701820 Continuation Sheet 2026.06.04.docx DOCX document
Construction Site Visit MARSOC Access List.xlsx XLSX spreadsheet
AMENDMENT 0001 - 26R0138.pdf PDF
Attachment C - Price Proposal Form REVISED.docx DOCX document
P1550 PPI RESPONSES 1.pdf PDF
Attachment I - DOD-CUI_Non-Disclosure Agreement.pdf PDF
Attachment D - Construction and Design Experience Project Data Sheet.docx DOCX document
Attachment G - SPCD.docx DOCX document
1701820 SITE - FINAL_v2_4 Flattened 1 of 2.pdf PDF
Attachment E - Past Performance Questionnaire.pdf PDF
Attachment C - Price Proposal Form.docx DOCX document
Attachment A - Pre-Proposal Inquiry (PPI) Log.xlsx XLSX spreadsheet
Solicitation - N4008526R0138.pdf PDF
1701820 A1 - FINAL_1.pdf PDF
1701820 A2 - FINAL_2.pdf PDF
1701820 A3 - FINAL_3.pdf PDF
1701820 SPC -FINAL.pdf PDF
1701820 SITE - FINAL_v2_4 Flattened 2 of 2.pdf PDF
Attachment B - PIEE Vendor Access Instructions.pdf PDF
Attachment H -Small Business Subcontracting Plan.docx DOCX document
Attachment F - Historical Small Business Utilization.docx DOCX document
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date Submitted

Reference Question Response

Page Section Paragraph

5/29/2026 39 SecƟon 01 14 00 Work RestricƟons

1.2 SecƟon 01 14 00 Work RestricƟons, Part 1.2 states, "The Contractor shall comply with all special scheduling requirements as described in the aƩached project descripƟon and as noted on the drawings." The referenced special scheduling requirements are not found in the project descripƟon in SECTION 01 11 00 of the RFP. Please clarify the locaƟon and/or if these requirements are forthcoming?

Submit proposals in accordance with RFP, SpecificaƟons, Drawings and all amendments.

5/29/2026 Amendment 0001 4.1 Site Visit The informaƟon regarding the site visit provided in Amendment 0001 states: 1. "Everyone is required to submit their name on the aƩached spreadsheet for MARSOC." and 2. "Those wishing to aƩend the site visit must submit the base access and MARSOC spreadsheets no later than June 8, 2026, by 2:00 PM EDT to Ashley Ruiz at ashley.l.ruiz10.civ@us.navy.mil."

Please provide the necessary spreadsheet for submiƫng the names of site visit aƩendees.

Please check SAM.gov for aƩachment

5/29/2026 Amendment 0001 4.1 Site Visit A site visit is scheduled for Thursday, June 11th, and bidder inquiries are due on Monday, June 15th, which is two (2) business days aŌer the site visit, as outlined in the solicitaƟon requirements. Would the Government consider extending the inquiry due date? An extension would provide adequate Ɵme aŌer the site visit for bidders to submit quesƟons, thereby reducing project risks for both the Government and the Offerors, and improving the Offerors' ability to submit accurate and compeƟƟve pricing.

The Government is noƟng these inquiries and may decide accordingly.

Site Drawings ES504 & ES502 The cable schedule on ES504 references detail B4 on Drawings ES502. The sable schedule indicates new conduit size as 6", Detail B4 is indicaƟng a conduit size of 5 ". please confirm which conduit size is correct.

Provide 6" conduit per schedule.

Site Drawings ES101 & ES504 ES101 calls for the demoliƟon of JB2 and installaƟon of the new switch board 1. JB2 is currently connect down stream to JB3 that is not in contract. please confirm any restricƟons to replacing JB2 with SW 1 as it impacts JB3.

DownƟme must be specifically coordinated with contracƟng officer to minimize interrupƟon for acƟvity.

Site Drawings TS104, TS 105 on drawing TS104 plan note 2 adds six 5" conduits to the exisƟng duct bank. plan note 4 states to provide (4) 5" conduit duct bank. TS105 through TS107 increase the new duct bank back to (6) 5" Conduits. please confirm if plan note 4 should be for six conduits and not 4.

Yes, plan note 4 should be (6) conduits.

Site Drawings TS107 Detail A2 Detail A2 on TS107 includes a callout for plan note 4. plan note 4 is not provided on the drawing. please confirm what plan note 4 requires.

Please refer to Amendment TS drawings for updated plan clarificaƟons.

Building A3 E-105 and E-106 Drawings E-105 and E-106 show an H type light with a diagonal hash and not connected to any circuit. please confirm that this light fixture is not required.

Incorrect. Fixtures are required. They are night lights;

refer to light fixture legend on sheet E-001.

Building A2 FA105 Team Staging/Storage room 134 does not have a pull staƟon, all other team staging/storage rooms have pull staƟons. does this room require a pull staƟon?

Yes, this room requires a pull staƟon at the exterior door.

Civil Drawings

The civil plan documents provided are unable to be vectorized, meaning the contours shown on the plans cannot be imported into industry standard takeoff soŌware. Our understanding is that this is due to the engineer scanning the drawings to create the PDF rather than generaƟng a digitally vectorized PDF directly from CAD.

Would it be possible to provide either: A vectorizable PDF plan set, or The associated CAD files so that we can proceed with our takeoff?

The Civil PDF documents are created directly from cad and are not scanned drawings. However, they are flaƩened prior to submiƩal to the Government. The AE has provided simplified cad files of the exisƟng contours and proposed contours with this response to quickly resolve this issue.

SF-1442 Box 13 AddiƟonal SolicitaƟon Requirements

In light of the solicitaƟon’s issuance on May 15, 2026 and the subsequent removal of drawings containing Controlled Unclassified InformaƟon (CUI), we respecƞully request that the Government extend the proposal due date to July 10, 2026, providing a full proposal preparaƟon period following issuance of Amendment 0001 (May 28, 2026).

As confirmed in the PPI responses, certain CUI drawings were iniƟally released publicly and later removed, with access now requiring NDA execuƟon and distribuƟon via DoDSafe. This sequence may have allowed some offerors earlier access to criƟcal design informaƟon, creaƟng a potenƟal imbalance. Extending the due date would ensure all offerors have equitable access and sufficient Ɵme to fully review the complete drawing package and develop a well-informed, compeƟƟve proposal.

The Government is noƟng these inquiries and may decide accordingly.

RFP- Page 8 Non-Price Factors Factor 1 Corporate Experience

Would the Government consider allowing repair and renovaƟon projects to be submiƩed under Factor 1 – Corporate Experience, provided such projects meet or exceed the solicitaƟon’s stated requirements for size, scope, and complexity?

Given that the solicitaƟon defines relevant experience as projects comparable in size, scope, and complexity, including large-scale faciliƟes with significant coordinaƟon of structural, architectural, MEP, and site/civil elements, as many repair and renovaƟon projects of similar magnitude involve the same mulƟdisciplinary coordinaƟon, phasing, and technical challenges as new construcƟon. Inclusion of these projects would allow offerors to demonstrate comprehensive capabiliƟes aligned with the intent of the evaluaƟon criteria and support broader and more compeƟƟve parƟcipaƟon

Please propose per the RFP

RFP- Page 8 Non-Price Factors Factor 1 Corporate Experience

Would the Government consider expanding the allowable Ɵmeframe for relevant project experience under Factor 1 from 10 years to 15 years?

The solicitaƟon requires projects completed within the past 10 years, yet the magnitude of this procurement, esƟmated between $100M and $250M and involving highly specialized SOF faciliƟes, represents projects that are relaƟvely infrequent within the federal construcƟon market. Expanding the Ɵmeframe would allow the Government to evaluate a broader pool of highly relevant, comparable projects that best demonstrate contractor capability for projects of this size, complexity, and mission criƟcality.

Please propose per the RFP

6/5/2026 01 91 00.15 22 1.1 Could the government please confirm they will hire the building commissioning firm for this project?

“The Government has hired an independent Commissioning Firm as stated in Para 1.1.”

6/5/2026 CU108 & P-

Keynote 4 On sheet CU108 keynote 4 "Water Meter & Backflow Assembly (Inside Mech Rooms). See Plumbing Plans." on sheet P-501 for the Plumbing details it doesn't show any water meter connecƟons or sizes, and on Sheet P-601, that informaƟon is missing from the plumbing schedule. Could the government please provide the water meter details for each building?

All P-501 sheets show pipe sizes and water meter requirements on the Backflow Preventer Detail.

6/5/2026 M-001 Keynote 16 On sheet M-001, general note 16 states that "All mechanical control wiring must be installed in conduit." Does this apply to control wiring above ceiling systems/non exposed areas or is the government's intenƟon that all control wiring in all locaƟons to be installed in conduit?

Unless otherwise noted, control wiring to be installed in conduit. Provide per plans and specs.

6/5/2026 MH-401 &

M-602

Louver Schedule Sheet MH-401 has a callout for L-5, but it is not listed on the louver schedule on sheet M-

602. Is L-5 perhaps mislabeled, or could the government please provide an updated louver schedule to include L-5?

Discrepancy is corrected on MH401_R01 and M- 602_R01.

6/5/2026 MH-401 &

M-602

Louver Schedule Sheet MH-401 has a callout for L-6, but it is not listed on the louver schedule on sheet M-

602. Is L-6 perhaps mislabeled, or could the government please provide an updated louver schedule to include L-6?

Discrepancy is corrected on MH401_R01 and M- 602_R01.

6/5/2026 01 50 00 3.2.1 SpecificaƟon secƟon 01 50 00 paragraph 3.2.1 Temporary UƟliƟes states that "Reasonable amounts of water and electricity from the nearest outlet will be provided free of charge for pursuance of work within a facility under this contract." While SolicitaƟon paragraph UƟliƟes for ConstrucƟon and TesƟng states "The contractor shall provide these uƟliƟes at his expense, paid at the current uƟlity rate delivered to the job site." Please confirm what is accurate? If the contractor is to pay for temp uƟliƟes, please provide the current uƟlity rate for all exisƟng uƟliƟes.

See aƩached UƟlity Rates for Camp Lejeune. _MDM

6/5/2026 A1 - I-117 Room 132 Finish Plan Area G shows Room 132 as SV-1 and SV-3, however the Room Finish Schedule indicates this room to be SV-1 and SV-2. Please clarify

The floor finish in room 132 has been corrected. SV-1 and SV-2 are in the Open Medical Office, SV-3 is in the Exam Rooms.

6/5/2026 TS101 Keynote 2 Please clarify if manhole MHRR100 will need to be expanded to accommodate new conduits. Assume manhole MHRR100 will need to be expanded.

6/5/2026 TS101 Keynote 2, 3 The expansion of the telecommunicaƟon ductbank, as shown on Sheet TS101, will be cuƫng through two exisƟng buildings. Will both of these faciliƟes be occupied during construcƟon?

Drawings show one "exisƟng" building which is no longer there.

6/5/2026 TS101 Keynote 2, 3 The expansion of the telecommunicaƟon ductbank, as shown on Sheet TS101, will be cuƫng through two exisƟng buildings. To minimize damage and rework associated with the Building along Rifle Range Rd, can an alternate path be uƟlized so the building is not affected?

Drawings show one "exisƟng" building which is no longer there. Bid per shown rouƟng.

6/5/2026 TS107 Keynote 4 Please confirm that Keynote 4 on Sheet TS107 is supposed to be Keynote 3. If not, please provide Keynote 4 informaƟon for this drawing sheet.

Please refer to Amendment TS drawings for updated plan clarificaƟons.

6/5/2026 Civil The civil plan documents provided are unable to be vectorized, meaning the contours shown on the plans cannot be imported into our takeoff soŌware. Would it be possible to provide either a vectorizable PDF Plan set or the associated CAD files? This will allow all contractors to provide a more accurate proposal, thus reducing risk and conƟngency for all parƟes.

The Civil PDF documents are created directly from cad and are not scanned drawings. However, they are flaƩened prior to submiƩal to the Government. TheAE has provided simplified cadfiles of the exisƟng contours and proposed contours with this response to quickly resolve this issue. Stantec

6/5/2026 26 05 19.10.10 Please confirm that offerers are permiƩed to uƟlize the type(s) of material(s) described in UFC 3-520-01 and UFGS SecƟon 26 05 19.10 10 applicable to their scope of work, despite any potenƟally contradictory provisions in the design plans and specificaƟons.

UFC 3-520-01 is applicable, but spec secƟon 26 20 00 and design drawings have been specifically edited for this project and must be followed. If there is a specific quesƟon on allowed materials, please provide a more detailed PPI. UFGS secƟon 26 05 19.00 10 is an Army secƟon and not uƟlized for this project.

6/5/2026 CU101 Keynote 15 & General Note #3

General note #3 on sheet CU101 menƟons Piedmont Natural Gas is responsible for the design and intall of the Gas line on this project. Please confirm the winning contractor is not responsible for paying Piedmont Natural Gas for this work.

Confirmed

6/5/2026 Building A3 Sheet MH-

Keynote 1 For Building A3 in drawing MH401 note 1 references the mechanical room having exposed supply, exhaust, and return ductwork from the air handler unit. Spec secƟon 23 30 00,

2.10.11 Pre-Manufactured Double Wall Ductwork references using Double Wall for all interior exposed ductwork that is in finished/occupied spaces as indicated on plans. With mechanical rooms not being a high traffic or finished area, we would typically install single wall duct that is externally insulated. Are we to provide double wall ductwork for the rectangular exhaust duct and the rectangular outside air that's in the mechanical room, or do we provide single wall ductwork that's externally insulated, as we typically would?

Note was revised on MH401_R01. Provide per plans and specs.

6/5/2026 RFP Part 1 252.204-7021 In the RFP, Part 1 includes DFAR 252.204-7021 for contractor compliance with the cybersecurity maturity model cerƟficaƟon level requirements (Nov 2025), in clause (1)(i), the government has indicated that the contractor shall have CMMC Level 1 (Self) CMMC status for the duraƟon of the contract. Does this apply to the general contractor only or all contractors, including subcontractors for this pursuit?

See Amendment 1

6/5/2026 RFP Part 1 252.204-7021 In the RFP, Part 1 includes DFAR 252.204-7021 for contractor compliance with the cybersecurity maturity model cerƟficaƟon level requirements (Nov 2025), in clause (1)(i), the government has indicated that the contractor shall have CMMC Level 1 (Self) CMMC status for the duraƟon of the contract. Would the government waive the CMMC requirement for this project to allow for addiƟonal subcontractors and their suppliers to parƟcipate in this pursuit?

No

6/5/2026 RFP Part 1 252.204-7021 Could the government please confirm that the CMMC level and requirements do not just pertain to the CUI informaƟon but on all federal contract informaƟon (FCI) for this pursuit?

See Amendment 0001

6/10/2026 Please confirm there is no ConstrucƟon Security Plan (CSP) for this Project. If there is, please provide a copy of the CSP for this Project.

Confirmed

6/10/2026 Please confirm both US CiƟzens and US Persons (those authorized to work in this country) are allowed on this project.

Confirmed

6/10/2026 Amendment 1 removed the A1-BN HQ drawing set and reissued it labeled as CUI, requiring an NDA to be completed. However, 252.204-7021 nor 7025 were revised changing the CMMC Level 1 requirement. Please confirm CMMC Level 2 (self) is required to handle, store, or transmit the A1-BN HQ CUI drawings by both the Prime Contractor and any Subcontractor.

Confirmed

6/10/2026 Amendment 1 revised the A1 - BN HQ set of drawings labeled all drawings as CUI. The original set of drawings only had a CUI label for the AY or RF Shielding drawings in that file.

Making the enƟre file CUI has Ɵme and cost impacts as the documents have to be handled per CMMC Level 2 requirements and is restricƟve because many subcontractors do not have a CMMC Level 2. Please consider removing the CUI label to only the AY or RF shielding drawings as originally issued. If this can not be achieved, please extend the bid date by 4 weeks.

CUI labels will remain.

6/10/2026 31 00 00 Please provide a copy of the full geotechnical report for this project, if one is available. Full geotechnical report will not be provided.

6/11/2026 A-105, A-605 The storefront in Building A2-1 VesƟbule 100 (Column Line 8/9) on A-105 is not labeled.

Please confirm that the plan East and West storefronts should be type A-2 on A-605 and that the plan North and South should be A-1 on A-605.

Correct.

6/11/2026 A-601 On the Building A2-1 door schedule on A-601 no informaƟon is provided for door numbers 130E and 130F. AddiƟonally, the locaƟon of these openings cannot be found on the floor plans. Please provide the required informaƟon for these openings or confirm if they should be removed from the door schedule.

Those doors do not exist and may be deleted from the Door and Frame schedule.

6/11/2026 87100 3.6.2.2 The following door numbers in Building A2-1 are missing hardware sets in the specificaƟons (starƟng at paragraph 3.6.2.2). Please provide door hardware sets for: 100A, 100B, 102A, 104A, 104B, 105A, 106A, 110A, 114A, 118A, 122A, 126A, 130E, 130F, 149B, 153A, 153B, 156A, 160A, 164A, 168A, 172A, 176A, 180A, 181A.

Hardware Sets for the idenƟfied openings are in other SpecificaƟon SecƟons that are specific to door types (e.g. aluminum storefront, sound control doors, etc.)

6/15/2026 Please confirm the government will complete any of the necssary tree harvesƟng and/or assessment prior to award of the contract, if this is not done prior to award. Please confirm the Ɵmeframe it will be completed in to avoid future construcƟon delays.

The KTR is responsible for clearing the site. MCB CL waived their right to tree harvesƟng for this project.

6/15/2026 Please provide any addiƟonal government acƟviƟes that should be accounted for in the overall construcƟon duraƟon.

Submit proposals in accordance with RFP, SpecificaƟons, Drawings and all amendments. MBFA

6/15/2026 TS101 Plan Notes 2 Plan Notes #2 on Sheet TS101 states that the manhole may require expansion to accommodate new conduits. Please provide informaƟon of the quanƟty and required size of expansion.

No addiƟonal informaƟon is available at this Ɵme.

6/15/2026 1 26 13 00 Please clarify if SF6/High-Fire point Fluids Insulated Pad-Mounted Switchgear is to be manual or automated?

MV switch is only required to be manual.

6/15/2026 Structural Drawings In many locaƟons across all of the structural drawings, the B1 Beam per the schedule is idenƟfied to be 1'-6" wide x 1'-6" deep. In several locaƟons on the drawings, B1 is shown in a locaƟon where details C3/S-512 (A1) or C2/S-512 (A2), Typical is also shown. Please clarify which Beam detail is to be used where this occurs.

SECTION C3 AND C2 ARE SECTIONS CUT THROUGH THE

TIE BEAM. WIDTH, DEPTH, AND REINFORCING OF TIE

BEAM ARE PER THE SCHEDULE. NOTES CHANGED TO BE

PER SCHEDULE TO AVOID CONFUSION.

6/15/2026 Structural Drawings Please provide a detail to clarify what is intended at the crossing of B1 Beams and interior fooƟngs where both C3/S-511 and C2/S-512 are shown to be typical (e.g., A2 Dwgs, S-105)

SECTION C3 ILLUSTRATES HOW GRADE BEAM AND

INTERIOR FOOTINGS INTERSECT.

6/15/2026 Structural Drawings Please provide a detail to clarify what is intended at the terminaƟon of B1 Beams at perimeter fooƟngs where both B3/S-511 and C2/S-512 are shown to be typical (e.g., A2 Dwgs, S-103). Please clarify the beam design intent, as the details appear to be in conflict.

SECTION B3/S-511 ILLUSTRATES HOW TIE BEAM

TERMINATES AT PERIMETER COLUMN FOOTING.

6/15/2026 LS100 Site Drawings / Landscape Notes

Sheet LS100, general note #3 states "contractor shall install tree root barriers around all hardscape, uƟliƟes & site ameniƟes within 10' of the center of any planted tree". The drawings (Sheets LS101 thru LS111) show visual indicaƟon of where this barrier is to be placed. For purposes of bidding, please confirm we are to only locate root barriers where visually indicated on sheets LS101 through LS111, or if note #3 on LS100 takes precedence.

Both apply. General Note 3 on Sheet LS100 addresses any required area of root barrier that is not specifically illustrated.

6/15/2026 05 40 00 Is exterior Cold Form Framed walls required to be Blast Designed? No. Submit proposals in accordance with RFP, SpecificaƟons, Drawings and all amendments.

6/15/2026 1043 09 22 00 2.1.1.1 Cold roll suspended ceilings are not commonly installed in commercial spaces. Will a modern ASTM equivalent drywall grid system be acceptable for installaƟon? A512 A1 detail shows a drywall grid system.

Submit proposals in accordance with RFP, SpecificaƟons, Drawings and all amendments.

8 I-602 ACG-1/2 has 9/16" Interlude XL HRC noted as BOD. High recycled content is not shown as required in specs. Is High Recycled Content a requirement for a non-spec reason? It doesn't provide higher performance, and other systems meeƟng the minimum domesƟc steel needed for BABAA compliance. This product is much more expensive. Please confirm this is the requirement?

High recycled content is not a requirement. Please refer to the spec for requirements.

6/15/2026 S-513 and As Head of wall framing shows different systems. Architectural shows a strap blocking detail for walls, which would land perpendicular to the roof purlins. S drawings show solid framing blocking to catch walls. This would greatly affect head of wall design, sound tesƟng, and firestopping of rated wall systems. Please confirm what details should be used.

Architectural head of wall details are correct.

6/15/2026 8 236426 2.3 The project specificaƟons appear to contain requirements that differ from typical industry standards. Please confirm whether this project is required to comply with Camp Lejeune Mechanical Design Guidance. If so, please provide the latest applicable version of the guidance document for reference.

Submit proposals in accordance with RFP, SpecificaƟons, Drawings and all amendments.

6/15/2026 C-515 Detail A1 Please confirm if the vehicle sliding gates are to be motorized. Yes, the gates are motorized

6/15/2026 CS103 Keynote 37 Please provide addiƟonal informaƟon or BOD for the "MagneƟc Strip" to acƟvate the vehicle gates.

Contractor is required to provide a submiƩal for a dual channel loop detecƟon and accompanying slide gate operator system

6/15/2026 Site Drawings and SpecificaƟons

AŌer review of the site drawings and specificaƟons, no menƟon or requirements for temporaty construcƟon fencing can be located. Please confirm if there is a need/requirement for temporary construcƟon fencing on the project.

No temporary construcƟon fencing other than that outlined in the CSP is required. See General Note 3 / CS101 for addiƟonal informaƟon on fencing.

6/15/2026 09 51 00 2.1.1 Ceiling AƩenuaƟon Class and Test in the AcousƟcal Ceilings Spec calls for a CAC of 40 for ACT- 1 and 35 for ACT-2. Then in SecƟon 2.2.1, the criteria for ACT-1 calls for 0.75 NRC and 35 CAC.

The Fine Fissured Ceiling Ɵle called for on the Finish Legend that meets the 40 CAC does not meet the 0.75 NRC. If the 0.75 NRC is desired, SecƟon 2.1.1 would have to be excluded, and a 35 CAC ceiling Ɵle would have to be used. Please clarify which criterion should be followed.

(SEE ATTACHMENTS)

Please refer to what is called out in the finish legend. A

0.70 NRC is sƟll considered high absorpƟon.

6/15/2026 09 51 00 2.2.2.5 SecƟon calls for Minimum Light Reglectance of 0.85 for ACT-2. This will be impossible to accomplish since the Ɵle called for on the Finish Legend for ACT-2 in Building A1 is a black ceiling Ɵle. Please confirm that a black ceiling Ɵle is sƟll desired here. (SEE ATTACHMENTS)

Concur. This is a typo. Please provide black ceilings where requested.

6/15/2026 Sheet I-602 Per the Finish Legend, Sheet I-602 in Building A1, ACB-1 AcousƟcal Ceiling Baffles are to be Turf Design Beam / Beam LED. Per the Reflected Ceiling Plan on Sheets A-125 and A-126, it is unclear which baffles are to have the integrated LED light and which do not. Please clarify which baffles are to have the integrated LED light. (SEE ATTACHMENTS)

Please refer to the enlarged ceiling plans and configuraƟon key on I-403 and I-404.

6/15/2026 09 51 00 2.2.3 SecƟon describes the mounƟng method as "feltlock to Unistrut". Being that these baffles are directly below ceiling grid, directly mounƟng the baffles to the grid would make more sense than using Unistrut. Please advise if this is a valid aƩachment method for the baffles. (SEE

ATTACHMENTS)

If the baffles allow for grid mounƟng, that is acceptable, but the manufacturers recommendaƟon for mounƟng suggest mounƟng to the unistrut or aƩaching a cable to the deck.

6/12/2026 SpecificaƟons 01 57 19 Please confirm all exisƟng Hazardous waste generated within the confines of the faciliƟes is idenƟfied as generated by the Government and the government will sign all hazardous waste manifests.

The DOR edited this SecƟon, but this quesƟon doesn't make any sense.

6/15/2026 SpecificaƟons 13 47 00 SecƟon 2.1.3.1 of 13 47 00 references IEE 299, NSA 65-6, and MIL-STD-285 for RF door assemblies. Please confirm that conforiming to NSA 65-6 and MIL-STD-285 procedures are not required. Also, there are no commerically available doors that would achieve 100 dB and STC 50 (NSA 65-6 & MIL standards). Please provide manufacturer and product data or revise required aƩenuaƟon.

Basis of Design is Series RFI-60-STC-50 door and RF- Tight frame as manufactured by Krieger Specialty Products.

6/15/2026 SpecificaƟons 13 34 19 SpecificaƟon secƟon 133419 “Metal Building Systems”, references the metal roof panel system but no reference to a weather-Ɵghtness warranty can be found. Please confirm that no weather-Ɵghtness warranty for the roof is required for this project.

WarranƟes are required. See revised SecƟon 13 34 19.

6/15/2026 A2-1 A-103, A-107, A-605

Drawing set A2 drawing A-103 & A-107 show rooms (117,121,125,129, 159, 163, 167, 171) That have a glazing hatching in the wall between column line E/D.6 that do not have a window/storefront designaƟon. Please confirm that the glazing hatches in wall type A1 are the transom and windows as shown on detail B3/A-605.

Correct. Referenced revised Sheets previously issued by Amendment.

6/15/2026 SpecificaƟons 13 47 00 Power line filters do not appear to be included in spec 13 47 00 or drawings. Please provide details and specificaƟons for rf power line filters. If power line filters are not included, RF specialists will likely not guarentee the secured area's specified aƩenuaƟon becuase it will fail.

Electrical penetraƟons of the shielding have been limited to feeders for the secure area panel. All branch circuits within the secure are originate from the secure area panel. It was our understanding that power line filters for the panel feeders are not required. Suggest MARSOC or he AO confirm.

6/15/2026 A-501 Wall types A1 and A3 are rated STC 50 with type X sheetrock. Please confirm this assembly will meet the required STC raƟng.

Reference SecƟon 09 29 00.

6/15/2026 A-501 Wall type B3 has an STC requirement of 50 with only two layers of 5/8 type X and is not extended to the deck and sealed. Please confirm this assembly will meet the required STC RaƟng.

Submit proposals in accordance with RFP, SpecificaƟons, Drawings and all amendments. MBFA

6/15/2026 A2-1 A-503 Drawing set A2 detail A1/A-503 references transiƟoning to dampproofing below grade.

Please confirm that this is for the enƟrety of the perimeter foundaƟons. Please confirm that this is at buildings A1, A2-1, A2-2 and A3. No specificaƟon secƟon was provided for dampproofing, please provide.

The intent is to provide a damp proofing product that is compaƟble with the air and moisture barrier system.

Most of the air and moisture barrier system manufacturers also have a compaƟble damp proofing product that should be submiƩed with the air and moisture barrier system.

6/15/2026 SpecificaƟons 13 47 00 SecƟon 3.2.2 AƩenuaƟon requirements states "Achieve radio frequency aƩenuaƟon through a combinaƟon of materials and standoff that is equal to or greater than 100 meters of free space over the frequency range of 30 MHz to 6 GHz". Please confirm the level of aƩenuaƟon the secured space should achieve in dB when tested.

The shielding test parameters must be sƟpulated by the AO. We asked this quesƟon during design but never received an answer.

6/15/2026 SpecificaƟons 13 47 00 IEEE 299, 5.1 Overview specifically reads: This standard defines a test procedure but does not define the frequencies at which the measurements should be made, nor does it define the minimum shielding effecƟveness that consƟtutes pass/fail. The owner shall define these frequencies and all pass/fail requirements. IEEE 299, Annex D further explains that shielded enclosures can have a wide range of uses, and be constructed from welded steel enclosures, to demountable test cells. D.2 Performance Requirements goes on to read: The selecƟon and applicaƟon of methods described herein is the responsibility of the parƟes associated with the enclosure: principally the owner and the owner’s representaƟves. It would not be possible to fully test in accordance with this standard if the standard requires procedures or techniques that are inappropriate or incompaƟble with the parƟcular enclosure involved.

Upon review of the shielding enclosure for this project with several experienced shielding vendors meeƟng the requirements of 13 47 00 and respecƟve aƩenuaƟons specified, the consensus is that the IEEE 299 tesƟng requirements need to be tailored/suited for this applicaƟon, and more specific pass/fail requirements need to be defined. Please provide an updated IEEE 299 tesƟng plan that is tailored to this project.

The shielding test parameters must be sƟpulated by the AO. We asked this quesƟon during design but never received an answer.

6/15/2026 SpecificaƟons 13 47 00 SecƟon 13 47 00 is calling for the shielded spaces to meet the effecƟveness of what appears to be in the range of +60-80dB ranges and KHz frequencies listed in its respecƟve secƟons “when tested” per IEEE 299, NSA 65-6, MIL-STD-285. SecƟon 3.2.2 doesn’t specifically menƟon the IEEE 299 tesƟng, but it is assumed to be required. The General Contractor and the Shielding Specialist Subcontractor are comfortable to test the shielded space per IEEE 299 standards, however, there is no performance guarantee that can be provided for a field built facility. The shielding effecƟveness test results will be provided in a confidenƟal manner, but may show small local failure points in the shielding. Any potenƟal failure points, in the confidenƟal report, will be provided for informaƟon only. As discussed in IEEE 299, the tesƟng standard is built around six-sided, conƟnuously welded steel enclosures, bolted

The shielding test parameters must be sƟpulated by the AO. We asked this quesƟon during design but never received an answer.

together panel enclosures, etc. When trying to use rFOIL sheets, cut and applied on a construcƟon site, around obstacles, openings, etc, it doesn’t yield the same level of shielding results as a pre-fabricated, conƟnuously welded, six-sided box.

6/15/2026 SpecificaƟons 13 47 00 13 47 00, 1.5.3 Work Plan calls for an independent, third party tesƟng consultant for assembly tesƟng. 1.1 References refers to IEEE 299 & MIL-STD-202Methods for Measuring the EffecƟveness of EM Shielding Enclosures. From several past experiences and consulƟng with numerous RF Shielding contractors, tesƟng a 6-sided box, that uƟlizes the metal roof deck and floor slab as the fiŌh and sixth side of the box will yield many local failure points in the IEEE 299 tesƟng tables. What has been acceptable on other projects with an “Open Storage” level of classificaƟon is to perform the tesƟng, and provide the results confidenƟally to the Gov’t. This will show and idenƟfy the isolated points of weakness for informaƟon only.

However, to build a shielded space that would pass all of the tables in IEEE 299, on all six sides is an extremely expensive, and incredibly sensiƟve and Ɵme consuming endeavor (if not impossible). We just want to verify that the Gov’t is aware of and acceptable to the fact that the 4 sided box will yield local shielding failure points, and those will be tested and pointed out in the reports, but those won’t be able to be remedied in the field. Please confirm the Gov’t acknowledges and is acceptable to this.

The shielding does NOT uƟlize the roof deck or the floor slab. This project requires a 6-sided box. The shielding test parameters must be sƟpulated by the AO.

We asked this quesƟon during design but never received an answer.

6/15/2026 SpecificaƟons 13 47 00 SecƟon 1.5 Work Plan is asking for a “shielding expert.” Please confirm this “expert” can be employed by the shielding contractor hired to furnish and install the shielding products in 13 47 00. Also please verify who or what agency verifies this person as an “expert.” Is it a certain number of years of experience working with the product, a certain accreditaƟon, etc?

It is intended the shielding expert be provided by the KTR. The expert may be employed by the shielding subcontractor. The AO will need to define expert qualificaƟons.

6/15/2026 SpecificaƟons 13 47 00 SecƟon 1.5.3 says "The AccrediƟng Officer performs a final series of tests to determine work acceptance for accreditaƟon purposes". 1. Please confirm what the actual tesƟng procedures are for the secured space. 2. Please confirm if the government owns tesƟng of the secured space.

The shielding test parameters must be sƟpulated by the AO. We asked this quesƟon during design but never received an answer.

6/15/2026 SpecificaƟons 13 47 00 SecƟon 3.2.2 Floor and Wall Surfaces says "Sandwich radiant barrier foil between concrete slabs and finish flooring". Details provided for RF shielding at floors only show RF foil and conducƟve taping at seams above the concrete slab. Please confirm there is rFOIL required under the concrete slab.

Nowhere under the slab. Between the slab and the finished flooring just as the Drawing indicates.

6/15/2026 SpecificaƟons 13 47 00 There are mulƟple structural members below metal decking seams that are inaccessible to apply RF taping and ensure that there will not be failure points when tested to IEE-299. Please consider reducing the tesƟng procudures/aƩenuaƟon requirements if we are required to bid as per design even though you cannot guarentee the performance of this shielded space.

Reference Detail A2/AY504.

6/15/2026 SpecificaƟons 01 91 19 Please confirm if the Building Enclosure Commissioning Agent (BECx) referenced in specificaƟon secƟon 01 91 19 paragraph 1.3.7 &1.3.8 will be provided by the Government or is to be provided by the Contractor.

Reference 1.1, SecƟon 01 91 00.15 22.

6/15/2026 A2 A-515 Drawing set A2 detail C1/A-515references an air-barrier membrane on the underside of the roof insulaƟon. Please confirm if this is to be a post-applied air barrier membrane (applied directly to the roof insulaƟon/purlins) for the complete roof zone shown on A-141. Or confirm if the roof insulaƟon described in spec secƟon 13 34 19 paragraph 1.2.3.1 will suffice as the air-barrier membrane for the roof system.

Intended to be the PEMB insulaƟon liner system.

6/15/2026 A-603 Please confirm that the door frames installed in CMU as shown on A-603 are not required to be fully grouted.

Submit proposals in accordance with RFP, SpecificaƟons, Drawings and all amendments.

6/15/2026 SpecificaƟons 13 34 19 UFC 3-110-03 paragraph D-2.2 (General Contractor’s WarranƟes [one to five years]) states the following: “Recently some government roof specificaƟons call for a General Contractor’s WaterƟght Warranty to add another method of ensuring a quality roof installaƟon. Unless stated otherwise in the Scope of Work in the RFP, all permanent new construcƟon and replacement roofs require a Five-Year General Contractor Bonded WaterƟghtness Warranty.

The scope of work in the RFP may waive the Bonding requirement, but if not specified, the Bonded five-year waterƟghtness warranty is required. The required wording of the warranty will be provided in the applicable UFGS.” No roofing specificaƟon secƟons have been provided and specificaƟon secƟon 13 34 19 does not include any roof warranƟes. Please confirm that the need for a five-year general contractor bonded waterƟghtness warranty will not be required for this project.

WarranƟes are required. See revised SecƟon 13 34 19.

6/15/2026 D3/A-301 CMU wall type G1 in area A appers to show CMU to underside of metal deck on column line C.3 per detail D3/A-301. However, per Wall Type Details A-502, gyp walls are shown on top of CMU. Please confirm where the CMU wall height is supposed to stop.

Top of CMU aligns with Top of Brick. 12'-8" AFF.

6/15/2026 C1/A-504 Please provide size for shelf angle on C1/A-504 See Detail A4/S-514.

6/15/2026 01 35 26 01 35 26 Please confirm the P1550 Project jobsite is composed of all three (3) buildings and that only one set of essenƟal personnel is the minimum required for the performance of the Project (1 SSHO, 1 Superintendent, 1 QC Manager, etc). instead of each building being considered its own site and thus requiring three different sets of essenƟal personnel (3 SSHOs, 3 Superintendents, 3 QC Managers, etc).

P-1550 is four (4) Buildings total.

6/15/2026 SpecificaƟons MulƟple The role of the Contractor's Project Manager is referenced throughout the SpecificaƟons but no specific qualificaƟons are provided for this role. Please provide required qualificaƟons for the Contractor's Project Manager.

The GuideSpec only sƟpulates qualificaƟons for KTR Field Personnel, not for KTR Office Personnel. The government will need to confirm if there are specific KTR PM qualificaƟons.