N40085-22R-2577 Amend 0001
CONTINUATION SHEET
THE PURPOSE OF THIS AMENDMENT IS TO PROVIDE THE FOLLOWING:
PROJECT TABLE OF CONTENTS
SECTION 01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
3.2.1 Temporary Utilities
Add to the end of the current paragraph:
“For construction temporary electrical service requirements, the existing medium voltage switch and service transformer feeding existing building CEP-126 may be used. See sheet ED101 in bid package drawings. Relocate the switch and transformer to a location on the project site, but outside of any new construction conflicts. Primary feeder to the medium voltage switch is fed underground from pole CEP-65 riser and may be reused to feed switch and transformer in new location. Exact switch and transformer relocation area shall be coordinated with the Construction Manager to accommodate the contractor’s needs and construction site layout. Contractor shall extend primary feeders to switch and transformer, and secondary feeders from transformer to contractor provided secondary equipment, as needed and in compliance with UFC 3 550 01, Change 3 and 2023 NEC (NFPA 70). All construction temporary electrical service equipment must be demolished after no longer needed as shown on the bid package drawings.”
-- End of Amendment --