Amendment 0006 - PPI 129 - Estimated Electrical Loads - Combined Facility.pdf

PDF 73 KB Posted

Attached to
DESIGN-BUILD, P-1458 2ND RADIO BATTALION COMPLEX, PHASE 2 MARINE CORPS BASE, CAMP LEJEUNE, NORTH CAROLINA
Solicitation number
N4008523R2557
Issued by

View the file

Other files

File Type Posted
AMENDMENT 0010.pdf PDF
Amendment 0010 - Attachment B - Price Proposal Form - REV 3.docx DOCX document
Amendment 0009 - 23 09 23.13 - BACNET DIRECT DIGITAL CONTROL SYSTEMS FOR HVAC.pdf PDF
Amendment 0009 - PPI 393 2015-2020_MCBCL_INRMP_MASTER.pdf PDF
Amendment 0009 - 25 05 11.00 - CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - ISOLATED SYSTEMS.pdf PDF
Amendment 0009 - 01 78 23 - OPERATION AND MAINTENANCE DATA.pdf PDF
Amendment 0009 - 01 78 30.00 22 - GIS DATA DELIVERABLES.pdf PDF
AMENDMENT 0009.pdf PDF
Amendment 0009 - Attachment B - Price Proposal Form - REV 2.docx DOCX document
Amendment 0009 - 01 31 23.13 20 - ELECTRONIC CONSTRUCTION AND FACILITY SUPPORT CONTRACT MANAGEMENT SYSTEM.pdf PDF
Amendment 0009 - 6_ESR_E20 - Furnishings.pdf PDF
Amendment 0009 - 01 78 00 - CLOSEOUT SUBMITTALS.pdf PDF
Amendment 0008.pdf PDF
Amendment 0007.pdf PDF
Amendment 0006 - PPI 129 - Supply Warehouse Space Tabulation.pdf PDF
Amendment 0006 - Attachment F - DFARS 252.225-7059 AND 7060.pdf PDF
Amendment 0006 - PPI 129 - Supply Warehouse Affinity Diagram.pdf PDF
Amendment 0006.pdf PDF
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0003.pdf PDF
Amendment 0003 - Attachment 1 - Combined Vehicle Maintenace Facility and Boat Operations Facility.pdf PDF
Amendment 0003 - P1458 MACC General Requirements - Rev 1.pdf PDF
Amendment 0002.pdf PDF
Amendment 0002 - Site Visit Roster P-1458.pdf PDF
Amendment 0001 - Attachment 1 - 01 78 00 PPI 3.pdf PDF
Amendment 0001 - Attachment 2 - REGISTER.pdf PDF
Amendment 0001.pdf PDF
Amendment 0001 - Attachment 3 - Table of Contents.pdf PDF
P1458 MACC General Requirements.pdf PDF
Attachment E - PIEE Vendor Access Instructions.pdf PDF
Attachment C - Pre-Proposal Inquiry (PPI) Form.xlsx XLSX spreadsheet
Attachment A - 1397586rfp02of03.pdf PDF
Attachment A - 1397586rfp01of03.pdf PDF
Attachment A - 1397586rfp03of03.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ESTIMATED ELECTRICAL LOAD

Client: Name

Project: 2nd Radio Battalion RFP

Location Jackonsville, NC

Project Number:

Date: 14-Jun-19

Load Description Area [Sqft]

LPD

[Watts/Sqft]

Allowable

Wattage

Lighting KVA Volts Phase

Coincident

Demand

Connected kVA Load

Paraloft 480 3

Admin Spaces 326.8 0.98 320.3 3.2 120 1 1.0 3.2

Secure Parachute Storage Room 253.33 0.63 159.6 1.1 120 1 1.0 1.1

Female Head 82.22 0.98 80.6 1.4 120 1 1.0 1.4

Male Head 276.16 0.98 270.6 1.6 120 1 1.0 1.6

Electrical Room 74.67 0.95 70.9 0.6 120 1 1.0 0.6

Telecom Room 80 0.95 76.0 1.8 120 1 1.0 1.8

HRST 255.03 0.95 242.3 1.3 120 1 1.0 1.3

Fire Pump Room 64 0.95 60.8 2.9 120 1 1.0 2.9

Mechanical 488.72 0.95 464.3 164.3 480 3 1.0 164.3

Janitor 37.86 0.63 23.9 0.2 120 1 1.0 0.2

Training Area 584.86 1.24 725.2 2.8 120 1 1.0 2.8

Parachute Inspection and Packing Area 1374.98 1.29 1773.7 7.3 120 1 1.0 7.3

Parachute Repair Room 229.64 1.29 296.2 1.4 120 1 1.0 1.4

Parachute Drying Tower 1433.48 1.23 1763.2 4.6 120 1 1.0 4.6

Subtotal KVA 194.7

Subtotal AMPS 234.2

Total KVA 282.3

Total AMPS 339.6

Supply Warehouse 480 3

Shipping Receiving Co Issue 2572.02 1.19 3060.7 5.9 120 1 1.0 5.9

HQTRS Co 2D Rad BN 4754.18 1.19 5657.5 13.4 120 1 1.0 13.4

PN Effects HQTRS 281.61 1.19 335.1 0.7 120 1 1.0 0.7

PN Effects MAGTF 220.09 1.19 261.9 0.6 120 1 1.0 0.6

PN Effects MEU 220.09 1.19 261.9 0.6 120 1 1.0 0.6

PN Effects Info WAR 220.09 1.19 261.9 0.6 120 1 1.0 0.6

Break Room 395.93 0.73 289.0 2.1 120 1 1.0 2.1

Female Head 193.71 0.98 189.8 1.5 120 1 1.0 1.5

Male Head 276.16 0.98 270.6 1.6 120 1 1.0 1.6

Janitor 20.68 0.63 13.0 0.2 120 1 1.0 0.2

Mechanical Room 592.53 0.95 562.9 261.3 480 3 1.0 261.3

Electrical Room 125.33 0.95 119.1 0.8 120 1 1.0 0.8

Telecom Room 80 0.95 76.0 1.6 120 1 1.0 1.6

Fire Pump Room 64 0.95 60.8 1.6 120 1 1.0 1.6

Administrative 974.39 0.98 954.9 10.5 120 1 1.0 10.5

Office 1 90 1.11 99.9 1.2 120 1 1.0 1.2

Office 2 90 1.11 99.9 1.2 120 1 1.0 1.2

Subtotal KVA 305.5

Subtotal AMPS 367.5

Total KVA 443.0

Total AMPS 532.9

1/13/2023

Load Description Area [Sqft]

LPD

[Watts/Sqft]

Allowable

Wattage

Lighting KVA Volts Phase

Coincident

Demand

Connected kVA Load

Combined Electrical / Communication Vehicle Maintenance Facility and Boat Operations Facility480 3

HQ CO Shops 3359.85 1.59 5342.2 22.1 120 1 1.0 22.1

EM Cage 735.82 1.59 1170.0 1.2 120 1 1.0 1.2

Service Bay Circ 333.33 1.19 396.7 1.5 120 1 1.0 1.5

Maintenance Bay 1 640 1.19 761.6 4.9 120 1 1.0 4.9

Maintenance Bay 2 640 1.19 761.6 4.9 120 1 1.0 4.9

Maintenance Bay 3 640 1.19 761.6 5.6 120 1 1.0 5.6

Male Head 1 336.72 0.98 330.0 1.7 120 1 1.0 1.7

Female Head 1 204.94 0.98 200.8 1.6 120 1 1.0 1.6

Janitor 1 49.58 0.63 31.2 0.2 120 1 1.0 0.2

Office 1 90.75 1.11 100.7 1.2 120 1 1.0 1.2

Office 2 89.83 1.11 99.7 1.2 120 1 1.0 1.2

Office 3 90.69 1.11 100.7 1.2 120 1 1.0 1.2

Admin Space 318.68 1.11 353.7 2.2 120 1 1.0 2.2

Storage Room 520.1 1.11 577.3 2.4 120 1 1.0 2.4

Training Room 1100.9 1.11 1222.0 3.0 120 1 1.0 3.0

MEU Support 302.45 1.11 335.7 2.1 120 1 1.0 2.1

MAGTF Ove 153.12 0.95 145.5 0.9 120 1 1.0 0.9

MAGTF/MEU Boat Stor Room 628.12 0.98 615.6 5.7 120 1 1.0 5.7

Mechanical Room 653.05 0.95 620.4 213.3 480 3 1.0 213.3

Mechanical Fan Room 801.67 0.95 761.6 213.5 480 3 1.0 213.5

Telecom Room 1 88 0.95 83.6 6.3 120 1 1.0 6.3

Electrical Room 508.32 0.95 482.9 1.0 120 1 1.0 1.0

Telecom Room 2 88 0.95 83.6 6.3 120 1 1.0 6.3

Mothers Room 58.23 0.95 55.3 0.4 120 1 1.0 0.4

Break Room 137.69 0.73 100.5 1.9 120 1 1.0 1.9

Male Head 2 296.01 0.98 290.1 1.7 120 1 1.0 1.7

Female Head 2 93.71 0.98 91.8 1.5 120 1 1.0 1.5

Janitor 2 64.94 0.63 40.9 0.2 120 1 1.0 0.2

Entry Corridor 895.6 0.66 591.1 1.5 120 1 1.0 1.5

Office 95.4 1.11 105.9 1.0 120 1 1.0 1.0

Office 125.53 1.11 139.3 1.0 120 1 1.0 1.0

Office 125.53 1.11 139.3 1.0 120 1 1.0 1.0

Open Office 240.63 0.98 235.8 1.7 120 1 1.0 1.7

Office 130.4 1.11 144.7 1.4 120 1 1.0 1.4

Office 95.44 1.11 105.9 1.0 120 1 1.0 1.0

Corridor 440.24 0.66 290.6 1.0 120 1 1.0 1.0

OVE 371.43 0.95 352.9 1.1 120 1 1.0 1.1

Tool and Layettes 638.26 0.63 402.1 0.6 120 1 1.0 0.6

Compressor 125.67 0.95 119.4 10.1 480 3 1.0 10.1

Common Work Area 1788 0.98 1752.2 4.5 120 1 1.0 4.5

POL 151.8 0.95 144.2 0.9 120 1 1.0 0.9

Battery Charging 95.68 0.95 90.9 5.8 480 3 1.0 5.8

Work Area 1 470.42 0.98 461.0 3.2 120 1 1.0 3.2

Maintenance Bay 1 640 1.59 1017.6 5.1 120 1 1.0 5.1

Maintenance Bay 2 640 1.59 1017.6 5.1 120 1 1.0 5.1

Maintenance Bay 3 640 1.59 1017.6 5.1 120 1 1.0 5.1

Maintenance Bay 4 640 1.59 1017.6 5.1 120 1 1.0 5.1

Maintenance Bay 5 640 1.59 1017.6 5.1 120 1 1.0 5.1

Maintenance Bay 4 640 1.59 1017.6 5.1 120 1 1.0 5.1

Maintenance Bay 5 640 1.59 1017.6 5.1 120 1 1.0 5.1

Subtotal KVA 581.1

Subtotal AMPS 698.9

Total KVA 774.3

Total AMPS 931.3

Hazardous Material Storage Facility 480 3

New POL 167.62 0.63 105.6 0.3 480 3 1.0 0.3New NON-POL 138.72 0.63 87.4 0.3 3 0.3Used POL/NON-POL 138.72 0.63 87.4 0.3 3 0.3

MISC 144.5 0.63 91.0 0.3 480 3 1.0 0.3

Expended Batteries 138.72 0.63 87.4 0.3 480 3 1.0 0.3

Subtotal KVA 1.4

Subtotal AMPS 1.6

Total KVA 2.0

Total AMPS 2.4

Load Description Area [Sqft]

LPD

[Watts/Sqft]

Allowable

Wattage

Lighting KVA Volts Phase

Coincident

Demand

Connected kVA Load

Wash Rack and Pad 480 3

Load N/A 250 480 3 1.0 250.0

Subtotal KVA 250.0

Subtotal AMPS 300.7

Total KVA 362.5

Total AMPS 436.0

SUMMARY TABLE

System 3 Phase Voltage 480V

Connected KVA

Connected Amps

Total (With Spare Capacity) KVA

Total (With Spare Capacity) Amps 2,242.2

1,332.7

1,603.0

1,864.1