Asbestos Survey Report April 8, 2015
Facility Surveyed:
NASJRAB Ft Worth Building 1630 Ft Worth TX 76127
Survey Area A – Floor Renovation Area 150sf – Single Level
Project: 150403A3
Prepared For:
Nalin Vyas Dept of the Air Force 1215 Military Pkwy Ft Worth TX 76127
This report presents the results of our asbestos survey of the above referenced property performed on April 7, 2015. This report was performed in general accordance with the executed authorization to perform asbestos survey services dated April 3, 2015.
Summary of Findings The results of the laboratory analysis determined that the following suspect asbestos containing building material(s) contained greater than 1% asbestos – the threshold state and federal regulatory compliance:
• Green vinyl floor tile / black mastic / brown floor tile / black mastic (150SF)
Asbestos containing material containing greater than 1% asbestos may only be disturbed or removed by properly licensed and trained asbestos abatement contractors or other regulated processes.
Project Scope The survey includes a small interior floors of Survey Area A – Floor Renovation Area within the building as denoted by the Site Layout and Sample Locations Diagram within this report.
The survey does not include the remainder of the facility.
The purpose of this report is to provide bulk sample collection analysis of the suspect asbestos-containing building materials (ACBM) that would be impacted during maintenance, renovation or demolition activities as regulated by the Texas Department of State Health Services (DSHS), the Texas Asbestos Health Protection Rules (TAHPR), the Asbestos Hazard Emergency Response Act (AHERA), and the National Emission Standards for Hazardous Air Pollutants (NESHAP) for determination of asbestos content in building materials.
Facility Description The single-level building includes exterior reinforced concrete panel walls, metal frame windows and doors, interior framed walls, and a flat roof on a concrete slab foundation.
http://www.abestosinspectors.com/
Survey Area A – Floor Renovation Area The floor system includes resilient flooring.
Field Inspection Asbestos Inspectors, Inc. conducted an Asbestos Survey of the above referenced property. The survey was conducted by Jack Tucker DSHS licensed Asbestos Inspector (license number 602922).
The survey included observation of the space and collection of bulk samples of suspected asbestos containing building materials (ACBM), which could be impacted by renovation and/or demolition activities.
Load bearing wall demolition or asbestos abatement activities cannot commence until ten (10) working days after notification is provided to the Texas Department of State Health Services Asbestos Division.
The following suspect asbestos-containing building materials were observed and sampled within the scope of this survey.
Code/ Sample
Homogeneous Material Suspect Asbestos Containing Material
Quantity Location - see Site Layout Diagram
Asbestos/ Type
Cond.
A 01-03
Green vinyl floor tile / black mastic / brown floor tile / black mastic
150sf Survey Area A area marked A
Yes Category I
Good
Utilizing DSHS protocol and generally accepted procedures, a minimum of one (1) sample from the identified exterior areas and three (3) samples from the identified interior areas were taken.
The bulk samples were collected in a manner which reduced the potential for fiber release and exposure.
The bulk samples were placed in secure containers and appropriate chain-of-custody protocols were initiated at this time.
The bulk samples were transported to Crisp Analytical Laboratory for laboratory analysis. Crisp Analytical Laboratory is licensed and authorized by the DSHS as an asbestos laboratory and is accredited by the National Voluntary Laboratory Accreditation Program (NVLAP) and the American Industrial Hygiene Association (AIHA) for selected test methods for bulk asbestos fiber analysis (PLM) and airborne fiber analysis (TEM).
Those materials marked in the ACBM column with Yes indicate materials that contain greater than 1% asbestos and are considered asbestos containing building materials.
Asbestos containing materials may only be disturbed or removed by properly licensed and trained asbestos abatement contractors or other regulated processes.
Definitions Demolition – The wrecking or removal of any load-supporting structural member of a public building or facility or the intentional burning of any public building or facility.
Renovation – Additions to or alterations of a building by removal, repairing, or rebuilding.
Friable Material - materials that when dry can be crumbled, pulverized, or reduced to powder by hand pressure, and includes previously nonfriable material after such previously nonfriable material becomes damaged to the extent that, when dry, may be crumbled, pulverized, or reduced to powder by hand.
Asbestos-containing Material (ACM) – materials made of asbestos, or having asbestos within them.
Asbestos Containing Building Materials (ACBM) – building materials made of asbestos, or having asbestos within them, including surfacing materials (SM), thermal system insulation (TSI), and miscellaneous materials (MM) that are found in or on interior structural members or other parts of a building.
Category I nonfriable asbestos-containing material (ACM) - asbestos-containing packing, gaskets, resilient floor covering, and asphalt roofing products containing more than one percent asbestos.
Category II nonfriable ACM - any material, excluding Category I nonfriable ACM, containing more than one percent asbestos that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
Regulated asbestos-containing material (RACM) - (a) Friable asbestos material, (b) Category I nonfriable ACM that has become friable, (c) Category I nonfriable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or (d) Category II nonfriable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations regulated by this subpart.
Alternatives for Treatment of Asbestos Containing Materials
A public building owner has the following regulated options for the removal or the management of ACBM found in their building:
• Removal (abatement) – This option is the most permanent solution for the treatment of ACBM. It involves the use of regulated methods in the removal and disposal of the ACBM. Removal requires the use of a state licensed Asbestos Contractor under the control of a licensed Asbestos Consultant with appropriate air monitoring and project management or other federally regulated process.
With the exception of certain Category I and II asbestos containing roofing materials and floor tile, all asbestos containing materials must be removed prior to renovation or demolition that would result in a disturbance.
• Removal of Roofing Materials – When a rotating blade roof cutter or equipment that similarly damages the roofing material is used to remove Category I or II non-friable asbestos-containing roofing material, the removal of 5,580sf or more of asbestos-containing roofing material will create at least 160sf of RACM and is subject to the National Emission Standards for Hazardous Air Pollutants (NESHAP) 40 Code of Federal Regulations (CFR) Part 61, Subpart M, 61.145(a). If the material removed in this manner is less than 5,580sf then the removal is not subject to the NESHAP, except that notification is always required for demolitions.
When the removal of Category I or II non-friable asbestos-containing roofing material or other exterior materials is at least 160sf and the removal methods will crumble, pulverize, reduce to powder, or contaminate with other RACM, the removal is subject to the NESHAP and TAPHR.
When the removal of Category I or II non-friable asbestos-containing roofing material or other exterior materials is less than 160sf or 260lf then the removal is not subject to NESHAP or TAPHR.
However, notification is always required for demolition project.
• Removal of Vinyl Floor Tile - The floor tile and mastics may be removed by a state licensed Asbestos Abatement Contractor or by a qualified contractor using the Resilient Floor Covering Institute’s (RFCI) Recommended Work Practices for Removal of Resilient Floor Covering (issued by the Resilient Floor Covering Institute, 401 East Jefferson Street, Suite 102, Rockville MD 20850) http://www.rfci.com/int_ARF-TechInfo.htm.
This method involves careful removal of the floor tiles and use of specialized solvents to remove the mastics from the concrete sub floor. All removed materials and solvents would be transported and disposed of in an appropriate asbestos landfill. If the floor tile does not contain greater than 1% asbestos, then it can be removed and treated as non-asbestos containing building material. However, the mastics will continue to be treated as asbestos containing building material for removal purposes.
The RFCI method is slower and more labor intensive method than the contained abatement method. However, no barrier containment, negative air pressure filtration, or air monitoring is required, thus saving setup costs and other professional services. If done incorrectly, the RFCI method would have to be halted and a decontamination and non-RFCI state-licensed asbestos abatement begun.
• Management - According to state regulation, the ACBM does not have to be removed as long as the ACBM is undisturbed and undamaged.
For instance, the ACBM may not be subject to drilling or suffer erosion. It may be also be possible to cover the ACBM with another material without disturbing the ACBM, and to allow planned renovations to go forward without an asbestos abatement.
• Management - Operations and Maintenance Program - An Operations and Maintenance (O&M)
Plan may be written describing appropriate actions for surveillance and management of asbestos-containing material, including a manual that records the O&M activities in the public building as long as the asbestos remains in place. The O&M Plan identifies the location of ACBM, recommends maintenance methodologies to avoid disturbing the ACBM, and chronologically logs all ACBM-related maintenance activities.
Estimated costs for developing an Operations and Maintenance Plan have not been determined and are not considered within the scope of this assignment, however please contact us for additional information regarding this issue.
• Management - Encapsulation – This option is a temporary solution which utilizes specialized bonding products that seal the ACBM to prevent asbestos fiber release. The encapsulated ACBM is best suited to stable, undamaged, and unexposed conditions. An Operations and Maintenance (O&M) Plan documenting periodic inspections will ensure the ACBM has suffered no further damage or deterioration.
• Management - Enclosure – This option is a temporary solution in which involves surrounding the
ACBM with an airtight sealed containment barrier to prevent asbestos fiber release. An Operations and Maintenance (O&M) Plan documenting periodic inspections will ensure the ACBM has suffered no further damage or deterioration.
General Recommendations
Please consider that any current or future renovation activity may require an Operations and Maintenance Plan to assist in ensuring that no new asbestos containing building materials are introduced into the building, thus facilitating future commercial permitting requirements.
It is recommended that property owners, occupants, employees or maintenance workers are notified of the presence, location and condition of the ACM, if present, and the need to avoid the disturbance of these materials, and the potential health hazards relating to asbestos. Further information can be found at the TDSHS website: www.dshs.state.tx.us/asbestos/default.shtm.
Limitations
Asbestos Survey reports are based on field investigations and analysis of selected samples that were assumed representative of the material within the structure. This report does not in any manner represent a warranty or guarantee; either expressed or implied, that other asbestos containing materials do not exist within the building or within building components that were not accessible or sampled. This Asbestos Survey should not be used to define the work scope for asbestos remediation or abatement.
This report describes only the conditions present at the time of our survey, in the areas surveyed.
Destructive sampling was not performed for access into all wall cavities, attic spaces or other inaccessible areas. The site investigation did not include inspection, sampling, or evaluation of materials outside of the main structure. If remodeled, repair or renovation to the roof system or to other non-assessed area is anticipated, they should be inspected prior to any disturbance of that material.
This report has been prepared on behalf of, and for the exclusive use of the client, solely for use in an asbestos evaluation of the site. This report and the findings contained herein shall not, in part or whole, be disseminated or conveyed to any other party without prior written consent of Asbestos Inspectors, Inc.
The following sections are attached and complete this report.
• SITE LAYOUT AND SAMPLE LOCATION DIAGRAM
• CHAIN OF CUSTODY
• LABORATORY REPORTS
• SUSPECT ASBESTOS CONTAINING BUILDING PRODUCTS LIST
• PROFESSIONAL SERVICES, TERMS & CONDITIONS AND LICENSES
We appreciate the opportunity to provide these services to you. If you have any questions, or require additional information, please contact us.
Sincerely, Jack Tucker III Asbestos Inspector License Number 602922 - Expires 08/19/2014
Honor Stroud Asbestos Management Planner License Number 205493 – Expires 04/17/2015
Site Layout – Material and Sample Locations
NASJRAB Ft Worth Building 1630 Ft Worth TX 76127
Asbestos Inspectors Inc April 7, 2015
Chain of Custody Asbestos Samples
Page i of i 0 PLM D Other _
Turnaround: \2 24hr D Other Positive Stop: D Yes Q No
Project Location
Client Total Sample:
asbestos inspectors me environmental consultants
PO Box 195014 " Dallas TX 75219 214-520-2897 " Fax 214-520-Q2S7 services@asbestosinspectors.com
Project ID: /5U
/6?o /2/r
Inspector
L Send To services@asbestosinspectors.com
Date/Time Sampled Date/Time Released Date/Time Received Date/Tinie Released Date/Time Received
V-7-.
1 1
Sample ID Sample Description/Location (for further clarification see Site Layout and Sample Locations Diagram)
Common Material
Condition Quantity
L
Attn:
Customer Project:
Reference #: Date: 4/8/2015
Analysis and Method
Discussion
Qualifications
CA Labs
Dedicated to
Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Materials Characterization - Bulk Asbestos Analysis Laboratory Analysis Report - Polarized Light
Asbestos Inspectors, Inc. Greg Gant
P.O. Box 195014
Dallas, TX 75219 150403A3, Bldg 16300 1215 Military Pkwy
CAL15042408CB
Summary of polarizing light microscopy (PLM / Stereomicroscopy bulk asbestos analysis) using the methods described in 40CFR Part 763
Appendix E to Subpart E (Interim and EPA 600 / R-93 / 116 (Improved). The sample is first viewed with the aid of stereomicroscopy. Numerous liquid slide preparations are created for analysis under the polarized microscope where identifications and quantifications are preformed. Calibrated liquid refractive oils are used as liquid mouting medium. These oils are used for identification (dispersion staining). A calibrated visual estimation is reported, should any asbestiform mineral be present. Other techniques such as acid washing are used in conjugation with refractive oils for detection of smaller quantities of asbestos. All asbestos percentages are based on calibrated visual estimation traceable to NIST standards for regulated of asbestos. Traceability to measurement and calibration is achieved by using known amounts and types of asbestos from standards where analyst and laboratory accuracy are measured. As little as 0.001% asbestos can be detected in favorable samples, while detection in unfavorable samples may approach the detection limit of 0.50% (well above the laboratory definition of trace).
Vermiculite containing samples may have trace amounts of actinolite-tremolite, where not found be PLM should be analyzed using TEM methods and / or water separation techniques. Suspected actinolite/vermiculite presence will be indicated through the sample comment section of this report.
Fibrous talc containing samples may even contain a related asbestos fiber known as anthophyllite. Under certain conditions the same fiber may actually contain both talc and anthophyllite (a phenomenon called intergrowth). Again, TEM detection methods are recommended. CA Labs PLM report comments will denote suspected amounts of asbestiform anthophyllite with talc, where further analysis is recommended.
Some samples (floor tiles, surfacings, etc.) may contain fibers too small to be delectable by PLM analysis and should be analyzed by TEM bulk protocols.
A "trace asbestos" will be reported if the analyst observes far less than 1% asbestos. CA Labs defines "trace asbestos" as a few fibers detected by the analyst in several preparations and will indicate as such under these circumstances.
Quantification of <1% will actually be reported as <=1% (allowable variance close to 1% is high). Such results are ideal for point counting, and the technique is mandatory for friable samples (NESHAP, Nov. 1990 and clarification letter 8 May 1991) under 1% percent asbestos and the "trace asbestos". In order to make all initial PLM reports issued from CA Labs NESHAP compliant, all <1% asbestos results (except floor tiles) will be point counted at no additional charge.
CA Labs is accredited by the National Voluntary Accreditation Program (NVLAP) for selected test methods for airborne fiber analysis (TEM), and for bulk asbestos fiber analysis (PLM). CA Labs is also accredited by AIHA LAP, LLC. in the PLM asbestos field of testing for Industrial Hygiene. All analysts have a college degree in a natural science (geology, biology, or environmental science) or are recognized by a state professional board in one these disciplines .Extensive in-house training programs are used to augment education background of the analyst. The group leader of polarized light has received supplemental McCrone Research training for asbestos identification. Analysis performed at Crisp Analytical Labs, LLC 1929 Old
Denton Road Carrollton, TX 75006
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929
Labs
A
C
Overview of Project Sample Material Containing Asbestos
Customer Project: 150403A3, Bldg 16300 1215 Military Pkwy CA Labs Project #: CAL15042408CB green floor tile black mastic brown floor tile
Glossary of abbreviations (non-asbestos fibers and non-fibrous minerals):
CA Labs
Dedicated to
Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Sample # Layer
Analysts Physical Description of
Subsample
Asbestos type / calibrated visual estimate percent
List of Affected Building
Material Types
4% Chrysotile
1A-2 black mastic <1% Chrysotile
1A 1A-1 9x9 VCT/ green floor tile
10% Chrysotile
1B 1B-1 9x9 VCT/ black mastic <1% Chrysotile
1A-3 brown floor tile
5% Chrysotile
2A-2 black mastic <1% Chrysotile
2A 2A-1 9x9 VCT/ green floor tile
10% Chrysotile
2B 2B-1 9x9 VCT/ black mastic <1% Chrysotile
2A-3 brown floor tile
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
This report relates to the items tested. This report is not to be used by the customer to claim product certification, approval or endorsement by NVLAP, NIST, AIHA LAP, LLC, or any other agency of the federal government. This report may not be reproduced except in full without written permission from CA Labs. These results are submitted pursuant to CA Labs' current terms and sale, condition of sale, including the company's standard warranty and limitations of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, CA Labs will store the samples for a period of ninety (90) days before discarding. A shipping or handling fee may be assessed for the return of any samples.
Labs
A
Overview of Project Sample Material Containing Asbestos
Customer Project: 150403A3, Bldg 16300 1215 Military Pkwy CA Labs Project #: CAL15042408CB
Glossary of abbreviations (non-asbestos fibers and non-fibrous minerals):
CA Labs
Dedicated to
Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Sample # Layer
Analysts Physical Description of
Subsample
Asbestos type / calibrated visual estimate percent
List of Affected Building
Material Types
4% Chrysotile
3A-2 black mastic <1% Chrysotile
3A 3A-1 9x9 VCT/ green floor tile
8% Chrysotile
3B 3B-1 9x9 VCT/ black mastic <1% Chrysotile
3A-3 brown floor tile
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
This report relates to the items tested. This report is not to be used by the customer to claim product certification, approval or endorsement by NVLAP, NIST, AIHA LAP, LLC, or any other agency of the federal government. This report may not be reproduced except in full without written permission from CA Labs. These results are submitted pursuant to CA Labs' current terms and sale, condition of sale, including the company's standard warranty and limitations of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, CA Labs will store the samples for a period of ninety (90) days before discarding. A shipping or handling fee may be assessed for the return of any samples.
Labs
A
Polarized Light Asbestiform Materials Characterization
Customer Info: Attn: Customer Project:
4/8/2015
4/7/15 11am
Phone # 4/7/15
Fax #
Technical Manager
Chad Lytle
CA Labs
Dedicated to
Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Greg Gant CA Labs Project #:
Asbestos Inspectors, Inc.
150403A3, Bldg 16300 1215
Military Pkwy
CAL15042408CB
P.O. Box 195014
Dallas, TX 75219 Date:
Turnaround Time: Samples Received:
214-520-2897 24 Hours Date Of Sampling:
214-520-0287 Purchase Order #:
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type
/ percent
1A 1A-1 9x9 VCT/ green floor tile y 4% Chrysotile 96% qu,ca
7 1A-2 black mastic y <1% Chrysotile 100% gy,bi
1A-3 brown floor tile y 10% Chrysotile 90% qu,ca
1B 7 1B-1 9x9 VCT/ black mastic y <1% Chrysotile 100% gy,bi
2A 2A-1 9x9 VCT/ green floor tile y 5% Chrysotile 95% qu,ca
7 2A-2 black mastic y <1% Chrysotile 100% gy,bi
2A-3 brown floor tile y 10% Chrysotile 90% qu,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:
Chad Lytle QAC
Analyst Leslie Crisp, P.G.
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
10. TEM analysis suggested
Labs
A
Polarized Light Asbestiform Materials Characterization
Customer Info: Attn: Customer Project:
4/8/2015
4/7/15 11am
Phone # 4/7/15
Fax #
Technical Manager
Chad Lytle
CA Labs
Dedicated to
Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Greg Gant CA Labs Project #:
Asbestos Inspectors, Inc.
150403A3, Bldg 16300 1215
Military Pkwy
CAL15042408CB
P.O. Box 195014
Dallas, TX 75219 Date:
Turnaround Time: Samples Received:
214-520-2897 24 Hours Date Of Sampling:
214-520-0287 Purchase Order #:
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type
/ percent
2B 7 2B-1 9x9 VCT/ black mastic y <1% Chrysotile 100% gy,bi
3A 3A-1 9x9 VCT/ green floor tile y 4% Chrysotile 96% qu,ca
7 3A-2 black mastic y <1% Chrysotile 100% gy,bi
3A-3 brown floor tile y 8% Chrysotile 92% qu,ca
3B 7 3B-1 9x9 VCT/ black mastic y <1% Chrysotile 100% gy,bi
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:
Chad Lytle QAC
Analyst Leslie Crisp, P.G.
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
10. TEM analysis suggested
Labs
A
214-520-2897 fax 214-520-0287 www.abestosinspectors.com PO Box 195014 Dallas TX 75219
ENVIRONMENTAL CONSULTING SERVICES
General Terms and Conditions agreed to by the parties are as follows:
1. Parties: Asbestos Inspectors, Inc. (AI) refers to the firm performing the Scope of Services described herein and detailed in the attached AI Proposal. “Client” refers to the person or business entity ordering the Scope of Services to be performed by AI. If the Client is ordering work on the behalf of another entity, Client represents and warrants that it is the duly authorized agent of the party that will benefit from the work. Unless otherwise stated in writing, Client assumes sole responsibility for the sufficiency of the work ordered. Client shall communicate these General Terms and Conditions to any third party to whom Client transmits any part of AI’s work. After execution of the Proposal Acceptance Notification (PAN) to which these General Terms and Conditions are attached and made a part thereto, AI shall have no duty or obligation to any third party greater than that set forth in these General Terms and Conditions.
2. Scope of Assignment: “Assignment” means the specific environmental testing, analysis, or other service to be performed by AI as set forth in AI’s Scope of Services, previously referenced herein and made a part hereof.
3. Tests and Inspections: Client shall ensure that all tests and inspections of the site, all materials provided, and work performed by others are delivered in a timely manner in accordance with the plans, specifications, contract documents , and AI’s recommendations. No claims for loss, damage or injury shall be brought against AI by Client or any third party unless all reviews, tests and inspections have been so performed and unless AI’s recommendations have been followed. Client agrees to indemnify, defend and hold AI, its officers, employees and agents harmless from any and all claims, suits, losses, costs and expenses, including but not limited to, court costs and reasonable attorney’s fees in the event that all such reviews, tests, and inspections are not so performed or AI’s recommendations are not so followed except to the extent that such failure is the result of the negligence, willful or wanton act, or omission of AI, its officers, agents or employees.
4. Scheduling of Service: The services set forth in the Proposal will be accomplished in a timely, workmanlike and professional manner by AI personnel or authorized subcontractors. If AI is required to delay commencement of work or if, upon undertaking work, AI is required to halt work due to changes in the scope of services, interruptions in other aspects of the Project, or other causes beyond the reasonable control of AI additional charges may be applicable and payable by the Client.
5. Access to the Property: Client will provide AI with access to the work site to perform the services. AI shall take reasonable measures to minimize damage to the site and any improvements as the result of its work; however, AI has not included in its fee the cost of restoration of damage which may occur during the course of its work.
6. Damage to Existing Man‐Made Objects: Unless AI assumes in writing the responsibility of locating subsurface or latent conditions, Client agrees to indemnify and save AI harmless from all claims, suits, losses, cost and expenses, including reasonable attorney’s fees as a result of personal injury, death or property damage occurring with respect to AI’s performance of its work and arising from subsurface or latent conditions, or damage to subsurface or latent objects, structures, lines or conduits where the actual presence and location thereof was not revealed to AI by the Client.
7. Confidentiality: If during the Project, AI and its employees obtain, directly or indirectly, secret and confidential information considered proprietary by Client, AI agrees, on behalf of itself and its employees, to maintain the confidentiality of information formally designated as proprietary by the Client unless directed by Client in writing to disclose the information to others.
8. Responsibility: AI’s work shall not include determining or implementing the means, methods, techniques, sequences or procedures of construction. AI will not be responsible for evaluating, reporting or affecting job conditions relative to the health, safety or welfare of any persons other than its own employees. AI’s work or failure to perform same shall not in any way excuse any contractor, subcontractor or supplier from performance of its work in accordance with the Contract documents.
9. Sample Disposal: Unless otherwise agreed, test specimens or samples may be disposed of immediately upon completion of the test. All drilling samples or specimens will be disposed of sixty (60) days after submission of AI’s report. All archeological samples will be returned to the Client for permanent curation following submittal of AI’s final report.
10. Payment: Client shall pay upon receipt of the report unless other arrangements have been agreed upon in writing.
Client agrees to pay AI’s cost of collection of all amounts due and unpaid after sixty (60) days, including court costs and reasonable attorney’s fees. Remedies available to AI for collection of amounts due, including mechanic’s liens, shall not be limited to any contractual provision or other agreement that is not specifically made a part of this Agreement.
11. Termination: This Agreement may be terminated by either party upon five (5) business days’ prior written notice. In the event of termination, AI shall be compensated by Client for all services performed up to and including the termination date, including reimbursable expenses, and for the completion of such services and records as are necessary to place AI’s files in order and/or protect its professional reputation.
12. Warranty: AI’s services will be performed, its findings obtained, and its reports prepared in accordance with the Proposal which has been mutually agreed upon as well as these General Terms and Conditions. In performing its professional services, AI will strive to perform services under these General Terms and Conditions in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing in the same locality under similar conditions. This warranty is in lieu of all other warranties, either express or implied. Should AI, or any of its professional employees, be found to have been negligent in the performance of professional services or to have breached the express warranty made herein, Client and all third parties claiming through Client agree that the maximum aggregate liability of AI and its employees shall be limited to $50,000.00 or the amount of the fee paid to AI for professional services with respect to the Project, whichever amount is less. In the event Client does not agree to restrict professional liability to $50,000.00 or to the total amount of the fee paid to AI with respect to the Project, whichever is less, Client agrees to pay for the actual cost of the additional desired insurance coverage, if such insurance is available.
13. Insurance and Indemnity: AI agrees to carry the following liability insurance: Statutory Workers’ Compensation and Employers’ Liability, Comprehensive General Liability, and Professional Environmental Consultant’s Liability. AI will furnish certificates of insurance upon request. To the extent of the coverage limits maintained by AI and subject to the exclusions therein and the amount of the claims paid by such insurance, AI agrees to indemnify and hold Client harmless from all losses, claims, demands, causes of action, and suits arising out of the willful or negligent acts of AI, its officers, agents, employees, or subcontractors, in performing professional services at the worksite. If Client specifically requires additional insurance coverage, AI will obtain the specific insurance coverage (if procurable) at Client’s expense. AI does not indemnify the Client for damage arising out of Client’s independent use of AI data, advice, recommendations and reports.
14. Agreement to Arbitrate: All disputes related directly or indirectly to any aspect of this contract, work related to this contract, or to any matter in this contractual relationship, shall be arbitrated pursuant to and by the American Arbitration Association in Dallas, Texas.
15. Priority of Documents: These General Terms and Conditions, together with the Proposal Acceptance Notification and associated documents, shall control over any conflicting provisions with purchase orders, work orders, letters of intent, or other similar documents.
16. Applicable Law: These General Terms and Conditions shall be governed by and construed according to the laws of the State of Texas. The venue for all claims made under these General Terms and Conditions shall be Dallas, County, Texas.
| 00 Report 20150107 |
| Facility Description |
| The single-level building includes exterior reinforced concrete panel walls, metal frame windows and doors, interior framed walls, and a flat roof on a concrete slab foundation. |
| The floor system includes resilient flooring. |
| COC15042408 |
| CAL15042408 |
| 08 License Page - Tucker, Jack |