Att_22_Work_Order_historical_data.xlsx

XLSX spreadsheet 163 KB Posted

Attached to
Mx & Repair Bldg 500 Federal contract opportunity
Solicitation number
FA4600-16-R-0012
Issued by
Department of the Air Force Air Combat Command

About this file

Attachment 22 - Work Order Historical Data

View the file

Other files for this federal contract opportunity

Other files attached to Mx & Repair Bldg 500, newest first.
File Type Posted
Answers-Vendor_Questions_4_Final.pdf PDF
Answers-Vendor_Questions_3_Final.pdf PDF
FA4600-16-R-0012-0002_Amendment_2.pdf PDF
Att_20-Performance_Work_Statement_6-13-17.pdf PDF
Answers-Vendor_Questions_2_Final.pdf PDF
Answers-Vendor_Questions_Final.pdf PDF
FA4600-16-R-0012-0001_Amendment_1.pdf PDF
Appendices_A_B_C.pdf PDF
Appendix_B_Plumbing_Equipment.xlsx XLSX spreadsheet
Appendix_M.pdf PDF
Appendix_B_HVAC_Equipment.xlsx XLSX spreadsheet
Appendix_B_Pegasus_Supplemental.XLSX XLSX spreadsheet
Appendix_B_MISC.xlsx XLSX spreadsheet
Appendices_E_F_G_H_I_J_K_L.pdf PDF
Appendix_D.pdf PDF
Appendix_B_Electrical_Equipment.xlsx XLSX spreadsheet
Appendix_B_Fire_Protection_Equipment.xlsx XLSX spreadsheet
Att_6_NDA_Agreement_(new).pdf PDF
Att_12_Pst_Perf_Info_(PPI)_Doc.doc DOC document
Att_14_Pst_Prsnt_Perf_Qstnr.docx DOCX document
Att_6_NDA_Agreement.pdf PDF
Att_1_Maps_drwngs_eqpt_list.pdf PDF
Att_15_Pst_Perf_Trkng_Rec.docx DOCX document
Att_2_Pricing_Model.xlsx XLSX spreadsheet
Att_16_Sub-KT_Tm_Consent_Ltr.docx DOCX document
Att_17_Client_Auth_Letter.docx DOCX document
Att_3_QASP.pdf PDF
Att_13__PPQ_Cover_Letter.docx DOCX document
Att_5_SF328.pdf PDF
Att_20-Performance_Work_Statement.pdf PDF
Att_8_DODM_5200.01,_Vol._4.pdf PDF
Att_7_DODI_8582.01.pdf PDF
Att_19_EAL.xlsx XLSX spreadsheet
Att_11_OFCCP_EEOC_Clrnc_Req.doc DOC document
Att_21_List_of_Required_Reports.pdf PDF
FA4600-16-R-0012.pdf PDF
Att_18_Local_Instructions.pdf PDF
Att_10_Wg_Dtrmntn.pdf PDF
Att_9_Contractor_Validation.xls XLS spreadsheet
Att_4_CoI.pdf PDF
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

June '15-June '16

WO #ShopFacilityOriginatedCompletedWork Requested
P7515GENERAL5006/3/16BJ15: TRIM COMING LOOSE FROM THE DOOR
P7514ELECTRICAL5006/3/163H1-3H9: THREE LIGHT BALLASTS ARE BAD
P7513ELECTRICAL5006/3/166/3/16BH24: EMERGENCY LIGHT INOP
P7512HVAC5006/2/16BJ4P: SERVICE AIR HANDLER
P7511PLUMBING5006/2/162H SOUTH WOMESN RESTROOM: NO WATER PRESSURE IN SINK #1
P7510GENERAL5006/2/161A WOMENS RESTROOM: CRACK IN THE CORNER OF THE WALL NEEDS TO BE CAULKED AND REPAIRED
P7509GENERAL5006/2/16BA MENS RESTROOM: DOOR THRESHOLD IS COMING LOOSE
P7508PLUMBING5006/2/162D MENS RESTROOM: URINAL #3 NOT FLUSHING
P7507GENERAL5006/2/162F5: DOOR SLAMS SHUT
P7506HVAC5016/2/16M108: TOO COLD
P7505LOCKS5016/2/166/2/16L99: CYPHER LOCK INOP
P7504ELECTRICAL5006/2/166/2/16BH12: EMERGENCY LIGHT INOP
P7503ELECTRICAL5006/2/166/2/16BH17: EMERGENCY LIGHT INOP
P7502GENERAL5006/1/16BB WOMENS RESTROOM: TOILET SEAT IN STALL #4 IS BROKEN
P7501HVAC5016/1/166/2/16U135: LITTLE GIANT PUMP IN THE CEILING IS LEAKING
P7500HVAC5006/1/166/2/16BJ15: HOT WATER PUMP #2 HAS A LEAKING FLANGE
P7499GENERAL5006/1/166/1/161E11: DOOR KNOB LOOSE
P7498HVAC5006/1/166/1/16BB16: WATER LEAKING FROM THE CEILING OVER THE DESK
P7497PLUMBING5006/1/162D WOMENS RESTROOM: SINK INOP
P7496GENERAL5006/1/166/1/16LOWER-LEVER HALLWAY BY L102: FIRE DOORS WILL NOT CLOSE ALL THE WAY
P7495HVAC5006/1/162A MECH ROOM: WORK ON STEAM TRAP
P7495GENERAL5006/1/166/2/16BB30L: ESCUTCHEON RING MISSING
P7494GENERAL5006/1/16BB14: ESCUTCHEON RING MISSING
P7493GENERAL5006/1/166/2/16BB18: ESCUTCHEON RING MISSING
P7492HVAC5006/1/166/1/163B MECH ROOM: CHECK CONDENSATE PAN
P7491LOCKS5006/1/166/1/163D16: LOCK STICKING
P7490PLUMBING5016/1/16LOWER-LEVEL MENS RESTROOM (AIR-ROOM): URINAL OVERFLOWING
P7489PLUMBING4075/31/16BLDG 407: WATER WILL NOT SHUT OFF IN THE MENS RESTROOM
P7488PLUMBING5015/31/166/2/16L138 MENS RESTROOM: SINK WILL NOT SHUT OFF
P7487LOCKS5975/31/16BLDGT 597: DOOR LOCK INTERMITANTLY WORKING
P7486ELECTRICAL5015/31/165/31/16M129 (GO IN THROUGH M133): NO POWER TO THE ROOM
P7485ELECTRICAL5005/31/166/1/16BF STAIRWELL (NEAR BF11): EXIT LIGHT INOP
P7484LOCKS5005/31/165/31/16BH7: DOOR LOCK INOP
P7483ELECTRICAL5005/31/166/1/16BB16: CIRCUIT BREAKER BLOWN
P7482HVAC5005/31/166/1/16BB16: TOO WARM
P7481HVAC5005/31/165/31/161J: CRAC 2 LOST AIRFLOW
P7480PLUMBING5005/27/165/31/161E MENS RESTROOM: BAD ODOR FROM A DRY TRAP
P7479GENERAL5005/27/16BH24: ROOF LEAK AND CEILING TILE IS DAMAGED
P7478GENERAL5005/26/166/1/16DOOR BETWEEN 1B5 AND 1B15 IS STICKING
P7477PLUMBING5005/26/165/27/16BB16 MENS RESTROOM: URINAL CONTINUOUSLY RUNNING
P7476HVAC5005/26/166/1/163F16: TOO WARM
P7475GENERAL5005/26/165/26/162A STAIRS: ADJUST DOOR CLOSER
P7474HVAC5005/26/165/26/163A MECH ROOM: REPLACE STEAM TRAP
P7473HVAC5005/26/165/26/162E27: HEAT COMING OUT OF THE VENTS
P7472LOCKS5005/26/165/26/16BJ2: OMNI LOCK HAS DEAD BATTERIES
P7471ELECTRICAL5005/26/165/26/162H19: CIRCUIT BREAKER TRIPPED
P7470PLUMBING5005/26/165/26/161C MENS RESTROOM: #3 URINAL CONTINOUSLY RUNNING
P7469LOCKS5015/26/165/26/16M116E CYPHER LOCK INOP
P7468ELECTRICAL5005/26/165/26/16THEATER: WORK ON WALL PACK LIGHTINING
P7467HVAC5005/26/165/26/16WORK ON BOILERS
P7466HVAC5005/26/165/26/16FUEL TANKS: DIP THE TANKS
P7465PLUMBING5005/26/165/31/161B HALLWAY: WATER FOUNTAIN HAS LOW FLOW
P7464HVAC5005/26/166/1/16BH5: TOO HOT
P7463HVAC5005/26/163D19: TOO HOT
P7462HVAC5005/26/166/1/163H15: ROOM IS WARM
P7461ELECTRICAL5005/26/165/26/163C1: MAGNETIC DOOR OPEN DEVICE
P7460ELECTRICAL5005/26/165/26/163F24: EMERGENCY LIGHT IS OUT
P7459ELECTRICAL5005/26/165/26/163F22: EMERGENCY LIGHT IS OUT
P7458ELECTRICAL5005/26/165/26/163F19: EMERGENCY LIGHT INOP
P7457ELECTRICAL5005/26/165/26/163C19: EMERGENCY LIGHT IS OUT
P7456ELECTRICAL5005/26/165/26/163C12: EMERGENCY LIGHT IS OUT
P7455ELECTRICAL5005/26/165/26/163C5: EMERGENCY LIGHT INOP
P7454GENERAL5015/26/16U135: REPAIR WALL WHERE PHONE BOX WAS REMOVED
P7453GENERAL5005/26/165/26/161B12: REMOUNT FIRE EXTINGUISHER BRACKET
P7452HVAC5005/26/165/26/16THEATER: REMOVE OLD FIRE ALARM PULL STATION
P7451ELECTRICAL5005/26/165/27/161F9: EXIT LIGHT INOP
P7450GENERAL5005/26/165/26/161H14: ESCUTCHEON RING LOOSE
P7449GENERAL5005/26/161F6: ESCUTCHEON RING IS LOOSE
P7448ELECTRICAL5005/26/166/1/161A8: EXIT LIGHT INOP
P7447ELECTRICAL5005/26/166/2/161C8: EXIT LIGHT INOP
P7446GENERAL5005/26/165/26/162J SERVER ROOM: ESCHUTCHEON RING IS HANGING FROM THE CEILING
P7445GENERAL5005/26/165/26/162C13: ESCUTCHEON RING IS HANGING FROM THE CEILING
P7444GENERAL5005/26/165/26/16335: METAL HINGES GRINDING
P7443GENERAL5005/26/165/26/163C3: DOOR NOT LATCHING
P7442HVAC5005/26/165/26/162A MECH ROOM: BELTS BROKE ON AHU
P7441ELECTRICAL5005/26/165/26/161F22: BROKEN LIGHT LENS
P7440LOCKS5005/26/165/26/162A: NEED 3 KEYS MADE
P7439HVAC5005/26/165/26/163F22: NO AIRFLOW
P7438HVAC5005/26/165/26/162E24: TOO HOT
P7437HVAC5005/26/165/26/161J: CRAC IN ALARM
P7436ELECTRICAL5005/26/161F22: INSTALL LIGHT DIFUSER
P7435ELECTRICAL5005/26/166/2/162D20: EXIT LIGHT INOP
P7434HVAC5005/26/165/26/163J2: TOO HOT
P7433PLUMBING5975/26/165/26/16BLDG 507: SUMP PUMP IN ALARM
P7432ELECTRICAL5005/26/165/26/162B28: MULTIPLE LIGHT PANELS WNET OUT
P7431LOCKS5015/26/155/26/16M116E: SETUP AND INSTALL CYPHER LOCK
P7430LOCKS5005/26/165/26/162J: XO9 LOCK INOP
P7429HVAC5015/26/165/26/16M103: LIEBERT UNIT ACTUATOR INOP
P7428PLUMBING5005/26/161J WOMENS RESTROOM: SINK LEAKING
P7427PLUMBING5005/26/16WATER FOUNTAIN BY 2C9 MAKING A LOUD NOISE
P7426HVAC5005/26/165/26/161E9: HIGH TEMPS IN THE ROOM
P7428HVAC5015/26/165/26/16M103: NO COMMUNICATIONS ON WEB CONTROL
P7427PLUMBING5005/26/162C RESTROOM: REPLACE BROKEN SEWER LINE
P7426ELECTRICAL5015/26/16U102: BAD BALLAST
P7425GENERAL5005/26/165/26/161A6: DOOR NOT CLOSING ALL THE WAY
P7424PLUMBING5005/26/165/26/162C MENS RESTROOM: 2ND URINAL OVERFLOWING
P7423PLUMBING5015/26/165/26/16UPPER-LEVEL MENS RESTROOM: #1 SINK INOP
P7422PLUMBING5015/26/165/26/16MENS RESTROOM TOILET #1 INOP
P7421PLUMBING5005/26/165/26/162H NORTH MENS RESTROOM: #2 STALL LEAKING
P7420PLUMBING5005/26/165/26/162C MENS RESTROOM: STALL CLOGGED
P7419HVAC5005/26/165/26/16BB30 HALLWAY: WATER LEAK IN THE CEILING
P7418GENERAL5155/26/16BLDG 515: MENS RESTROOM TOILET SEAT BROKEN
P7417HVAC5015/26/165/26/16BLDG 501: WATER LEAKING IN THE CEILING
P7416PLUMBING5155/26/165/26/16BLDG MENS RESTROOM: WATER FOUNTAIN PLUGGED
P7415ELECTRICAL5005/26/165/26/162E23: BAD BALLAST
P7414LOCKS5005/26/165/26/161A2B: CYPHER LOCK INOP
P7413PLUMBING5005/26/165/26/162G MENS RESTROOM: SINK PLUGGED
P7412GENERAL5015/26/165/26/16M116E: DOOR CLOSER INOP
P7411GENERAL5005/17/165/18/161B JANITORS CLOSET: HANDLE BROKE OFF THE DOOR. SESITIVE INFO IN THE ROOM.
P7410HVAC5005/17/166/1/161J SERVER ROOM: HIGH HUMIDITY ALARM
P7408ELECTRICAL5005/17/165/18/16MULTIPLE BALLAST IN THE DISPLAY CASE IN THE MUSEUM
P7407GENERAL5225/17/16BLDG 522 ENTRY WAY: REPLACE DAMAGED DRYWAY WHERE THERE WAS A LEAK
P7406HVAC5975/17/165/18/16Bldg 597: WHINING SOUNDS IN THE OOM
P7405PLUMBING5005/17/165/18/162D MENS RESTROOM: RIGHT URINAL INOP
P7404GENERAL5005/17/166/1/162D MENS RESTROOM: PAPER TOWEL DISPENSER INOP
P7403GENERAL5005/16/165/18/16BB HALLWAY BY MENS RESTROOM: MOUNT HAND SANITIZER
P7402GENERAL5005/16/165/18/163A STAIRWELL DOOR: REPAIR THRESHOLD AND REATTACH THE TRIM
P7401ELECTRICAL5015/16/165/18/16HALLWAY NEAR U139: BAD BALLAST
P7400ELECTRICAL5015/16/165/18/16HALLWAY NEAR L125: BAD BALLAST
P7399ELECTRICAL5015/16/165/18/16HALLWAY NEAR M140: BAD BALLAST
P7398PLUMBING5005/16/165/18/163D WOMENS RESTROOM: SINK DRAINING SLOWLY
P7397HVAC5015/16/166/1/16M121: HVAC UNIT LEAKING IN THE CEILING
P7396HVAC5015/16/165/18/16M103: NO WATER IN THE PAN ALARM
P7395HVAC5005/16/165/16/163B30: NO WATER IN THE PAN ALARM
P7394GENERAL5005/13/165/16/16BB16 WOMENS RESTROOM: PAPER TOWL DISPENSER INOP
P7393PLUMBING5005/13/165/16/16BB16 WOMENS RESTROOM: SINKS HAVE TOO MUCH WATER PRESSURE AND SPRAY WATER ALL OVER
P7392PLUMBING5005/13/165/18/16BJ MENS RESTROOM: FIRST SINK DRAINING SLOWLY
P7391LOCKS5005/13/163H35: LOCK NOT SECURING ON THE DOOR
P7390LOCKS5005/13/163E1: LOCK NOT SECURING ON THE DOOR
P7389HVAC5015/13/165/18/16L120: OVERPRESSURE ON THE DOOR
P7388LOCKS5005/13/165/13/161G4: XO9 LOCK WILL NOT RELEASE
P7387PLUMBING5005/12/165/16/162H NORTH MENS RESTROOM: 2ND URINAL INOP
P7386PLUMBING5005/12/165/16/161C MENS RESTROOM: LAST STALL IS LEAKING
P7385PLUMBING5005/12/165/13/162A MENS RESTROOM: SINKS DRAINING SLOWLY
P7384HVAC5015/12/165/12/16M108: TOO HOT
P7383LOCKS5005/12/165/12/161J VAULT: DOOR WILL NOT LATCH
P7382PLUMBING5005/11/165/13/162J MENS RESTROOM: URINAL IS OVERFLOWING
P7381GENERAL5005/11/165/12/162C13: DOOR HANDLE LOOSE
P7380ELECTRICAL5005/11/165/16/16BG16: BALLAST INOP
P7379LOCKS5005/11/165/11/16BB03: LOCK INOP
P7378HVAC5005/11/165/11/162E20D: PHUMATIC LINE CAME LOOSE
P7377GENERAL5005/11/166/2/16BG VAULT: DOUBLE DOORS NEED NEW WEATHER STRIPPING AT THE BOTTOM
P7376ELECTRICAL5005/10/16BLDG 407: MULTIPLE BALLAST OUT
P7375HVAC5005/10/165/11/162H26: AIRDUCTS BLOWING DUST AND DEBRIS
P7374PLUMBING5005/10/165/12/162D MENS RESTROOM: 1S URINAL WILL NOT FLUSH
P7373PLUMBING5005/10/165/13/16BE WOMENS RESTROOM: 4TH SINK INOP
P7372PLUMBING5005/10/165/11/16BB01-BB03: KITCHENET HAS A BAD SEWER SMELL
P7371GENERAL4075/10/165/18/16BLDG 407 ROOM 4: ROOF LEAK
P7370HVAC5005/10/165/10/162H23: AIR HISSING NOISE COMING FROM THE CEILING
P7369ELECTRICAL5005/9/165/10/16BA5: EMERGENCY LIGHT IS INOP
P7368LOCKS5015/9/165/10/16M133: DOOR LOCK MECHANISM NEEDS TO BE DISABLED
P7367HVAC5005/9/165/10/163J MECH ROOM: FIRE ALARM PANEL SHOWING TROUBLE FROM 3J14 AHU 3
P7366PLUMBING5155/9/165/11/16BLDG 515 FRONT MENS RESTROOM: URINAL LEAKING
P7365PLUMBING5005/9/165/18/162H NORTH MENS RESTROOM: 2ND STALL WON'T FLUSH
P7364GENERAL5915/9/165/9/16BLDG 591 VISITOR CENTER (NORTH SIDE): ROOF LEAK BY THE SOLAR LIGHT
P7363HVAC5005/9/165/18/161J SERVER ROOM IS SHOWING HIGH HUMIDITY
P7362LOCKS5005/9/165/9/163H35 XO9 LOCK INOP
P7361HVAC5005/6/165/12/161G COMM CLOSET: NO WATER IN THE PAN
P7360HVAC5005/6/165/12/162G COMM CLOSET: NO WATER IN THE PAN
P7359HVAC5005/6/165/12/162J SEVER FLOOR: CRAC #1 HIGH TEMPS
P7358HVAC5155/6/165/10/16SO54: FIRE ALARM PANEL BEEPING
P7357HVAC5005/6/165/6/163B10: HUMIDIFIER ALARM. NO WATER IN PAN
P7356ELECTRICAL5005/6/165/92016BF9: NO POWER
P7355GENERAL5005/6/165/9/162B MENS RESTROOM: PAPER TOWEL DISPENSER INOP
P7354LOCKS5005/6/165/16/163F12: XO7 LOCK NOT WORKING PROPERLY. NEED SCHEDULED FOR 10TH OR 11TH MAY
P7353HVAC5005/5/165/10/16BB16 CONFERENCE ROOM: NO AIRFLOW
P7352HVAC5005/5/165/5/162H SOUTH WOMENS RESTROOM: WATER IS TOO HOT
P7351GENERAL5005/5/165/6/16CHECK THE ROOF DRAINS ON BLDG 515 AND 500
P7350LOCKS5015/5/165/10/16L120A: DOOR IS NOT SECURING
P7349HVAC5015/5/165/6/16M121: FILTERS IN A/C UNIT NEED TO BE CHANGED
P7348ELECTRICAL5135/5/165/6/16BLDG 513 (BITC): EMERGENCY LIGHT OUT ON MAIN FLOOR
P7347HVAC5005/5/165/11/16BOILER ROOM: WORK ON CHILLED WATER PUMP #7
P7346HVAC5005/5/165/5/16BOILER ROOM: WORK ON CHILLED WATER PUMP #1
P7345LOCKS5005/5/165/5/16BJ2; DOOR WILL NOT CLOSE COMPLETELY
P7344LOCKS5005/5/02165/5/163J SCIF DOOR WILL NOT CLOSE. AIRFLOW PROBLEM
P7343LOCKS5005/5/165/5/161F18: BACK OF THE CYPHER LOCK IS LOOSE
P7342GENERAL5155/4/165/5/16BLDG 515: CEILING GRID IS SAGGING
P7341HVAC5005/4/165/4/16BH5: RATTELING NOISE IN THE CEILING
P7340PLUMBING5005/4/16BG MENS RESTROOM: SINK CONTINUOUSLY RUNNING
P7339HVAC5005/4/166/1/162J UPS ROOM: CRAC UNIT INOP. HGH TEMPS
P7338HVAC5005/4/165/5/162H20: SOUNDS LIKE AN AIR LEAK IN THE DUCT
P7337ELECTRICAL5005/3/165/4/16BH17: 5 BALLAST BAD
P7336GENERAL5005/3/165/3/16CAFETERIA DOOR WILL NOT LATCH
P7335PLUMBING5005/3/165/4/16BG VAULT WOMENS RESTROOM: SINK SPRAYING WATER WHEN TURNED ON
P7334HVAC5005/3/16BH12: NO WATER IN THE PAN ALARM
P7333ELECTRICAL5015/3/165/4/16U102: EMERGENCY LIGHT INOP
P7332ELECTRICAL5005/3/165/3/162B23: NO POWER
P7331LOCKS5015/3/165/3/15M121: CYPHER LOCK INOP
P7330PLUMBING5015/2/165/3/16LOWER-LEVEL MENS RESTROOMS ARE ALL BACKING UP
P7329LOCKS5005/2/165/2/162G VAULT DOOR CAME OFF THE HINGES
P7328PLUMBING5005/2/165/18/162C WOMENS RESTROOM: SINK CONTINUOUSLY RUNNING
P7327ELECTRICAL5005/2/165/2/16CAFETERIA: OUTLET INOP
P7326HVAC5005/2/165/3/162E26: HISSING SOUND FROM THE VENT
P7325LOCKS5005/2/165/2/16BA8: DOOR WILL NOT SECURE
P7324HVAC5974/29/165/5/16BLDG 597: GROUND FAULT ALARM SHOWING
P7323GENERAL4074/29/164/29/16BLDG 407: DOOR WILL NOT SECURE
P7322GENERAL5004/29/164/29/16COURTYARD DOOR WON'T LOCK IN THE OPEN POSITION
P7321HVAC5004/29/164/29/162B10: TOO HOT
P7320ELECTRICAL5004/28/165/2/16THEATER: 6 LIGHTS OUT
P7319ELECTRICAL5004/28/16BAD BALLAST IN THE HALLWAY OUTSIDE OF U130
P7318ELECTRICAL5004/28/16BAD BALLAST IN THE HALLWAY OUTSIDE OF U139
P7317HVAC5004/28/164/28/161J: CRAC #2 HAS NO AIRFLOW AND IS LEAKING
P7316PLUMBING5004/27/164/28/16BB16: LEFT URINAL DRAIN REAL SLOWLY
P7315ELECTRICAL5004/27/164/28/161E6: LIGHT FIXTURE HAS A BROKEN SWITCH
P7314HVAC5004/27/164/27/161C16: AHU BELT IS SQUELLING
P7313GENERAL5014/27/164/27/16U104: HINGES LOOSE ON THE DOOR
P7312ELECTRICAL5014/26/164/27/16U102: BAD BALLAST
P7311HVAC5004/26/164/29/161B MECH ROOM: AHU 1074 IS SQUEELING
P7310HVAC5004/26/164/27/161J: CRAC #3 HAS A HIGH HUMIDITY ALARM
P7309GENERAL5004/26/163J13: PATCH HOLES AND PAINT WALL WHERE DIGITAL CLOCKS WHERE REMOVED
P7308ELECTRICAL5014/26/164/27/16L120: BALLAST BAD IN FIXTURES
P7307LOCKS5004/26/164/26/16BJ4N: DOOR HANDLE ON THE OMNI LOCK DOES NOT RETRACK
P7306GENERAL5004/26/164/26/16BB03: DOOR SLAMMING SHUT
P7305ELECTRICAL5004/25/164/26/16BB18: EMERGENCY LIGHT OUT
P7304HVAC5004/25/164/25/16BOILER ROOM: SERVICE AIR COMPRESSOR AS NEEDED
P7303PLUMBING5004/25/164/27/162H NORTH MENS RESTROOM: URINAL NOT FLUSHING
P7302LOCKS5004/25/164/25/162B9: CYPHER LOCK INOP
P7301HVAC5004/22/164/28/16BB16 (VTC ROOM): TOO HOT
P7300LOCKS5004/22/164/22/161G6: CYPHER LOCK COMING OFF THE DOOR
P7299HVAC5004/21/164/21/16BJ5: WATER LEAK
P7298GENERAL5004/21/164/22/161B29: DOOR STICKING
P7297ELECTRICAL5004/21/16BG: REPLACE BROKEN LENS COVER
P7296ELECTRICAL5004/21/164/22/161H15: LOST POWER TO THE OUTLET FOR THE PRINTER
P7295PLUMBING5004/21/164/25/161G MENS RESTROOM: WATER LEAKING FROM THE CEILING
P7294LOCKS5004/21/164/21/162F8: SCIF DOOR WILL NOT SECURE PROPERLY
P7293PLUMBING5004/21/164/21/16BH WOMENS RESTROOM: TOILET WILL NOT STOP RUNNING
P7292PLUMBING5004/21/164/21/163H SOUTH MENS RESTROOM: TOILET CONTINUOUSLY RUNNING
P7291LOCKS5004/20/164/20/16DELTA 11 OVERRIDE KEY: NEED A NEW KEY MADE WITH CODE WS-35
P7290HVAC5014/20/164/20/16U146: SUMP PUMP INOP AND ROOM IS FLOODING
P7289ELECTRICAL5154/20/164/20/16SO24: NO POWER TO THE PROJECTORS
P7288ELECTRICAL5004/20/164/20/161H17: BREAKER TRIPPED
P7287PLUMBING5004/20/164/25/161G MENS RESTROOM: TOILET LEAKING
P7286HVAC5974/19/164/22/16BLDG 597 FRONT OFFICES ARE TOO HOT
P7285HVAC5004/19/165/6/161H NORTH MECH ROOM: CHILLED WATER PUMP #5 IS LOUD
P7284ELECTRICAL4074/19/164/25/16BLDG 407: There is an open wire box in the outside mech room as well as a broken or at least open heat/smoke detector
P7283PLUMBING5154/18/164/18/16BLDG 515 BACK RESTROOM: TOILET OVERFLOWING
P7282GENERAL4074/18/164/21/16BLDG 407 MECH ROOM: FIRE EXTINGUISHER NEEDS TO BE RE-MOUNTED
P7281GENERAL4074/18/164/21/16BLDG 407: ROOMS 28,29,30 33 ALL NEED OUTLET COVERS INSTALLED
P7280HVAC5224/18/164/18/16GOC: FIX AIR HANDLER #1
P7279ELECTRICAL4074/18/164/25/16BLDG 407: EMERGENCY LIGHTS IN ROOMS 11, 41 AND INSIDE THE AIR HANDLER ARE INOP
P7278LOCKS5004/18/164/19/162E24: OMNI LOCK INOP. NEEDS BATTERIES
P7277PLUMBING5004/18/164/26/161C WOMENS RESTROOM: 5TH STALL WILL NOT FLUSH
P7276GENERAL5004/18/163G MENS RESTROOM: PAPER TOWEL DISPENSER HAS A BROKEN HANDLE
P7275PLUMBING5004/18/164/26/16BA8: SINK DRAINS SLOW AND HAS NO HOT WATER
P7274HVAC5014/18/164/18/16U146: TEMPS OVER 90 DEGREES
P7273PLUMBING5004/18/164/18/163E MENS RESTROOM: 3RD STALL CONTINUOUSLY RUNNING AND OVERFLOWING
P7272LOCKS5004/18/164/20/16BB01: XO9 LOCK INOP
P7271ELECTRICAL5004/18/164/18/161F22: NEED 2 LIGHT DIFUSERS REPLACED IN NORTHWEST OFFICE
P7270PLUMBING5004/14/164/18/161F COFFEE PREP ROOM: SINK SPRAYING WATER ALL OVER
P7269GENERAL5004/14/164/28/163C14: REPLACE BROKEN CEILING TILE
P7268LOCKS5004/14/164/18/161C17: REPAIR XO LOCK. BOB SIMMS HAS THE PARTS
P7267ELECTRICAL5004/14/164/14/163H21: BURNING ELECTRICAL COMING FROM OUTLET
P7266PLUMBING5014/14/164/14/16LOWER-LEVEL RESTROOMS ARE ALL BACKING UP
P7265LOCKS5004/14/164/14/161E19: OMNI LOCK HAS DEAD BATTERIES
P7264GENERAL5154/14/164/14/16BLDG 515 DOOR WILL NOT LATCH
P7263GENERAL5004/14/164/14/162A8: DOOR STOP IS LOOSE
P7262PLUMBING5004/13/164/14/162H NORTH MENS RESTROOM: URINAL NOT FLUSHING
P7261PLUMBING5014/13/164/13/16BLDG 501 AIR-ROOM RESTROOM: URINAL #3 LEAKING
P7260GENERAL5004/13/164/14/163C WOMENS RESTROOM: TOILET SEAT NEEDS TO BE REPLACED
P7259HVAC5004/12/164/14/16SO42: AHU IS NOT PUTTING OUT ANY AIR PRESSURE
P7258HVAC5004/12/164/13/16BB30F: RATTELING NOISE IN THE CEILING ABOVE MR GOULD'S DESK
P7257HVAC5004/11/164/13/16BJ7: TOO HOT
P7256ELECTRICAL5004/11/152A MENS RESTROOM: LIGHT INOP OVER 2ND STALL
P7255ELECTRICAL5004/11/164/13/162D WOMENS RESTROOM: BAD BALLAST IN MIDDLE LIGHT
P7254LOCKS5974/11/164/12/16BLDG 597: DOOR LOCK CAME OFF THE RESTROOM DOOR
P7253HVAC5004/11/164/11/163B30: NO WATER IN THE PAN ALARM
P7252PLUMBING5004/8/164/11/162G WOMENS RESTROOM: BOTH SINKS BACKED UP
P7251ELECTRICAL5014/8/164/12/16LIGHT INOP IN THE HALLWAY BY ROOM U131
P7250LOCKS5004/8/164/8/163D29: MAKE 2 KEYS (CODE CD25)
P7249LOCKS5004/8/164/12/161C17: REPAIR XO LOCK AND CHANGE COMBO
P7248HVAC5004/8/164/13/16BB30F: TOO WARM
P7247PLUMBING5004/8/164/12/163H NORTH WOMENS RESTROOM: TOILET LEAKING
P7246GENERAL5004/7/164/14/16FLASHING COMING OFF THE SIDE OF THE B-WING ROOF
P7245GENERAL5004/7/164/8/16REINSTALL HANDRAIL IN C-WIN ELEVATOR
P7244GENERAL5004/7/164/7/16FIX THE CAFETERIA DOOR
P7243ELECTRICAL5004/7/164/7/162B28: NO POWER
P7242PLUMBING5004/7/164/12/16M121: FAUCET LEAKING
P7241PLUMBING5004/7/164/11/163E MENS RESTROOM: SINK DRAINING SLOWLY
P7240ELECTRICAL5004/7/16REPLACE THE MOTOR ON THE SWITCH GEAR FOR THE EXHAUST FAN
P7239GENERAL5014/6/164/7/16M121B: CEILING GRID IS FALLING DOWN
P7238GENERAL5014/6/164/7/16L127: DOOR LATCH WILL NOT ENGAGE
P7237HVAC5224/6/164/6/16GOC: BELT BROKE ON AIR HANDLER #3
P7236HVAC5004/6/164/14/16BH7-9: TOO COLD
P7235HVAC5004/6/164/6/16BG REPORTING LOW HUMIDITY
P7234HVAC5004/5/16BOILER ROOM: WORK ON THE BOILERS
P7233PLUMBING5154/5/164/7/16BLDG 515 UNISEX RESTROOM: SINK CLOGGED
P7232PLUMBING5004/5/164/8/162C WOMENS RESTROOM: SINKS 1 AND 4 ARE INOP
P7231PLUMBING5014/5/164/7/16WATER FOUNTAIN BY L137 INOP
P7230GENERAL5224/4/164/5/16GOC ROOM 103: DOOR HINGES LOOSE
P7229PLUMBING5004/4/164/5/161B COFFEE PREP ROOM: SINK SPRAYS WATER ALL OVER
P7228HVAC5004/4/16BB30 SERVER ROOM: TOO COLD
P7227GENERAL5004/4/164/4/16BB01: DOOR IS HARD TO OPEN AND CLOSE
P7226ELECTRICAL5014/4/164/5/16L120: LIGHT INOP
P7225PLUMBING5004/4/164/4/163G MENS RESTROOM: 3RD URINAL CONTINUOUSLY RUNNING
P7224ELECTRICAL5004/4/164/5/16LIGHT OUT BY THE BH ELEVATOR
P7223ELECTRICAL5004/4/164/4/161H15: NO POWER
P7222PLUMBING5004/1/164/12/162C MENS RESTROOM: 1ST URINAL OVERFLOWING
P7221PLUMBING5224/1/164/1/16GOC: WATER HEATER LEAKING
P7220HVAC5004/1/164/14/162E19: MUSTY SMELL COMING FROM THE VENTS
P7219GENERAL5003/31/164/1/163H25: DOOR HINGE GRINDING ON THE DOOR
P7218PLUMBING5153/31/164/4/16BLDG 515 FRONT MENS RESTROOM: SINK CLOGGED
P7217PLUMBING5003/31/164/5/162HS WOMENS RESTROOM: TOILET CONTINUOUSLY RUNNING
P7216PLUMBING5003/31/164/8/163E WOMENS RESTROOM: 6TH SINK INOP
P7215GENERAL5003/31/163/31/163H SOUTH MENS RESTROOM: 4TH SOAP DISPENSER INOP
P7214ELECTRICAL5003/31/163/14/163C1B: LIGHT INOP
P7213ELECTRICAL5003/31/163/31/163C WOMENS RESTROOM: 3RD LIGHT IS BROKEN
P7212GENERAL5003/31/163/31/16BJ2: DOOR SLAMMING SHUT
P7211ELECTRICAL5003/30/164/1/162A STAIRS: LIGHT BURNED OUT
P7210HVAC5003/30/164/13/162C5: TOO COLD
P7209PLUMBING5153/30/164/4/16BLDG 515 REAR WOMEN'S RESTROOM: SINK INOP
P7208GENERAL4073/30/163/30/16BLDG 407: SCIF DOOR SLAMS SHUT AND HARD TO OPEN
P7207ELECTRICAL5003/29/163/30/163D19: LIGHTS INOP. BAD BALLAST
P7206PLUMBING5013/29/164/1/16MID-LEVEL MENS RESTROOM: URINAL OVERFLOWING
P7205HVAC5003/29/164/14/16BF16: HIGH TEMP ALARM
P7204PLUMBING5013/29/163/29/16LOWER-LEVEL MENS RESTROOM: TOILETS BACKING UP
P7203PLUMBING5003/29/163/31/16BB MENS RESTROOM IS FLOODING
P7202LOCKS5013/29/163/29/16M133: XO9 LOCK INOP
P7201PLUMBING5003/29/163/29/16MID-LEVEL MENS RESTROOM: LAST STALL CONTINUIOUSLY RUNNING
P7200GENERAL5223/28/164/4/16GOC ROOM 202 RESTROOM: REPAIR SOAP DISPENSER
P7199ELECTRICAL5003/28/163/29/16J-DOCK ELEVATOR: BALLAST OUT
P7198PLUMBING5003/28/163/31/162H SOUTH MENS RESTROOM: PIPE SPRAYING WATER
P7197ELECTRICAL5003/25/163/28/16BB16: DEAD OUTLET NEAR J51 SECRETARY WALL
P7196GENERAL5003/25/163/28/16BB16, ROOM 1A6: REMOUNT FIRE EXTINGUISHER
P7195GENERAL5003/25/163/28/16BB12: REMOUNT FIRE EXTINGUISHER
P7194PLUMBING5003/25/163/26/16BH WOMENS RESTROOM: TOILET WILL NOT STOP RUNNING
P7193LOCKS5003/24/163/28/16L112: DOOR CLOSER BROKEN
P7192PLUMBING5003/24/163/26/16MID-LEVEL MENS RESTROOM: URINAL #1 OVERFLOWING
P7191HVAC5003/24/163/26/16BB18: TOO HOT IN THE SERVER ROOM
P7190PLUMBING5003/24/163/24/16GOC: URINAL IS CLOGGED
P7189LOCKS5003/24/163/24/161G6: LOCK INOP
P7188PLUMBING5003/24/163/24/161E MENS RESTROOM: PIPES LEAKING UNDER THE SINKS
P7187GENERAL5003/23/163/24/161E: PATCH HOLE IN THE CEILING
P7186LOCKS5003/23/163/24/163C22: REPAIR LOCK ON THE DOOR
P7185PLUMBING5003/23/163/24/161C MENS RESTROOM: LAST TOILET CLOGGED
P7184ELECTRICAL5153/23/163/23/16SO85: LIGHT BALLAST IS OUT
P7183GENERAL5003/22/163/22/16BOILER ROOM: TOILET BROKEN IN RESTROOM AT THE TOP OF THE STEPS
P7182ELECTRICAL5003/22/163/23/162E MENS RESTROOM: BALLAST OUT
P7181ELECTRICAL5013/22/163/23/16HALLWAY BY ROOM 108: BALLAST OUT
P7180ELECTRICAL5013/22/163/23/16HALLWAY BY ROOM M105: BALLAST OUT
P7179HVAC5003/22/163/22/162F26: SMOKE SMELL COMING FROM THE A/C UNIT
P7178HVAC5003/22/163/22/162C5: TOO COLD
P7177GENERAL5003/21/164/4/16BA8: FOAM SEAL FOR SCIF DOOR NEEDS TO BE REPLACED
P7176HVAC5013/21/163/26/16M112: NO WATER IN THE PAN ALARM
P7175ELECTRICAL5003/21/163/22/162D HALLWAY BY THE ELEVATOR: BALLAST OUT
P7174ELECTRICAL5003/21/163/22/161D BEHIND THE CAFETERIA: BALLAST OUT BY THE FIRE EXIT
P7173GENERAL5003/21/163/22/161A MENS RESTROOM: TOILET COMING LOOSE FROM THE FLOOR
P7172HVAC5003/21/163/21/16BB16: TOO HOT IN THE CONFERENCE ROOM
P7171ELECTRICAL5003/21/163/22/163C6: BAD BALLAST
P7170ELECTRICAL5013/18/163/21/16L120: BAD BALLAST
P7169LOCKS5003/18/163/17/16BH24: SCIF DOOR LOCK INOP
P7168HVAC5003/17/163/17/16BB30F: RATTELING SOUND IN THE DUCT
P7167PLUMBING5003/17/164/7/16BG WOMENS RESTROOM: PIPE LEAKING
P7166PLUMBING5223/17/163/17/16GOC: SINK CLOGGED
P7165LOCKS5003/17/163/17/162E26: OMNI LOCK INOP (BATTERIES)
P7164ELECTRICAL5003/17/163/17/163G STAIRWELL: CENTER BALLAST IS OUT
P7163PLUMBING4073/16/163/16/16BLDG 407 NON-SCIF MEN'S RESTROOM: SINK WILL RUN FOR 3 MINUTES
P7162PLUMBING5003/16/163/16/162H NORTH MENS RESTROOM: 3RD URINAL INOP
P7161HVAC5003/16/163/16/16BB16: ALARM BEEPING
P7160HVAC5003/16/163/16/162G: ALARM PANEL BEEPEING
P7159PLUMBING5003/15/163/16/163G MEN'S RESTROOM: 3RD TOILET INOP
P7158ELECTRICAL5003/15/163/16/162E10: LIGHT BULB BROKEN IN THE FIXTURE
P7157HVAC5003/15/163/16/16BB30F: NO AIRFLOW TO THE ROOM
P7156HVAC5003/15/163/16/16BH24: A/C LEAKING
P7155PLUMBING5003/15/163/16/163G MEN'S RESTROOM: TOILET INOP
P7154HVAC5003/15/164/14/162E7: TOO COLD
P7153LOCKS5003/15/163/15/163D9: XO0 LOCK INOP
P7152LOCKS5153/15/163/15/16BLDG 515 SCIF DOOR INOP.
P7151HVAC5013/14/163/14/16M121: TOO MUCH AIR PRESSURE ON THE SCIF DOOR
P5150ELECTRICAL5013/14/163/14/15U135: POWER OUT TO THE ROOM
P7149ELECTRICAL5003/14/163/16/16BB01: FIXTURE KEEPS BURNING OUT THE BULBS QUICKLY
P7148PLUMBING5013/14/163/16/16LOWER-LEVEL MENS RESTROOM: FIRST TOILET INOP
P7147PLUMBING5003/14/163/16/16BF/BE WOMEN'S RESTROOM: FIRST TOILET INOP
P7146PLUMBING5003/14/163/16/16BJ MENS RESTROOM: TOILET LEAKING
P7145HVAC5003/11/163/10/162C14: OVERHEAD UNIT NOT WORKING PROPERLY
P7144LOCKS5003/10/163/10/16BB01 CONFERENCE ROOM HAS A BROKEN DOOR KNOB
P7143ELECTRICAL5003/10/163/10/162E10: LIGHT INOP
P7142GENERAL5013/10/163/15/16M121: DOOR NOT OPENING AND CLOSING PROPERLY
P7141PLUMBING5003/10/163H SOUTH MENS RESTROOM: FIRST URINAL IS LEAKING
P7140HVAC5003/9/163/10/161B19: CHECK THERMOSTAT
P7139LOCKS5003/9/163/9/161B29: LOCK DOES NOT LATCH (TOP SCREWS CAME LOOSE)
P7138HVAC5003/9/163/9/162F22-2F26: TOO HOT
P7137GENERAL5003/9/163/9/16BJ MEN'S RESTROOM: SLIDING HANDLE ON STALL DOOR BROKE
P7136ELECTRICAL5003/9/163/10/162H SOUTH MEN'S RESTROOM: BALLAST OUT IN LIGHT OVER THE SINK
P7135ELECTRICAL5003/8/163/8/16BH5: NO POWER
P7134GENERAL5003/8/163/9/162C15: BLINDS FELL FROM THE CEILING. NEED TO BE REMOUNTED
P7133GENERAL5003/8/163/9/162C13: ESCUTCHEON RING IS HANGING FROM THE CEILING
P7132GENERAL5003/8/163/9/162J SERVER ROOM: ESCHUTCHEON RING IS HANGING FROM THE CEILING
P7131HVAC5223/8/163/9/16GOC: DVC SERVER IS DOWN
P7130ELECTRICAL5003/8/163/15/162D20: EXIT LIGHT INOP
P7129GENERAL5013/7/163/8/16L135: 2 METAL STRIPS AT THE END OF THE STAIRWELL ARE STICKING UP
P7128LOCKS5003/7/163/7/16BB30F: OMNI LOCK HAS DEAD BATTERIES
P7127PLUMBING5003/7/163/8/161F COFFEE PREP ROOM: SINK LEAKING
P7126LOCKS5003/7/163/7/161E5: OMNI LOCK NEEDS THE BATTERIES CHANGED
P7125GENERAL5003/7/163/7/162E18: DOOR CLOSER NEEDS TO BE ADJUSTED
P7124GENERAL5003/7/163/7/162F9: DOOR CLOSING TO HARD
P7123HVAC5003/7/163/7/16BG1: LEIBERT UNIT HAS NO AIR FLOW
P7122ELECTRICAL5003/7/163/7/162B9: NO POWER
P7121HVAC5003/7/163/7/16BJ11: TOO HOT (DUCT CAME LOOSE)
P7120ELECTRICAL5913/7/163/7/16BLDG 591 VISITOR CONTROL CENTER: LIGHT INOP
P7119LOCKS5003/4/163/4/16EMC H8 KEY NEEDS TO BE MADE. PLEASE GIVE NEW KEY TO MERLE
P7118ELECTRICAL5003/4/163/8/161C16: 3 BALLAST BURNED OUT
P7117PLUMBING5153/3/163/4/16BLDG 515 FRONT MENS RESTROOM: TOILET LEAKING
P7116GENERAL5003/2/163/3/163H35 CONFERENCE ROOM: DOOR STOP IS LOOSE
P7115HVAC5223/1/163/1/16FIRE ALARMS GOING OFF IN THE GOC
P7114PLUMBING5003/1/163/1/161E MENS RESTROOM: TOILET SEAT BROKEN
P7113LOCKS5002/29/163/1/16BJ4U: BATTERIES NEED CHANGED ON THE LOCK
P7112GENERAL5002/29/16BLDG 515: REPLACE DAMAGED CEILING TILES FROM ROOF LEAK
P7111ELECTRICAL5002/29/162/29/16BH1: NO POWER TO PORTION OF THE ROOM
P7110HVAC5002/29/162/29/16BJ4P: CRAC UNIT MAKING A LOUD NOISE
P7109HVAC5002/29/162/29/16BJ2K: CRAC UNIT KEEPS GOING FROM HIGH TO NORMAL
P7108PLUMBING5002/29/162/29/161B COFFEE PREP ROOM: WATER NOT SHUTTING OFF COMPLETELY
P7107ELECTRICAL5012/29/163/1/16UPPER-LEVEL HALLWAY BY ROOM U108: LIGHT INOP (BALLAST)
P7106ELECTRICAL5012/29/163/3/16LOWER-LEVEL BY THE ELEVATOR: LIGHT INOP (BALLAST)
P7105ELECTRICAL5012/29/163/1/16LOWER-LEVEL HALLWAY BY ROOM L125: LIGHT INOP (BALLAST)
P7104PLUMBING5012/26/163/1/16MID-LEVEL MENS RESTROOM: 3RD UTINAL IS LEAKING
P7103ELECTRICAL5012/26/162/26/16U102: LIGHT INOP AND HAS BURT ENDS
P7102PLUMBING5222/26/162/29/16GOC: SUMP PUMP IN THE LIFTSTATION IS INOP
P7101HVAC5152/25/162/25/16BLDG 515 ROOM SO83: LOUD NOISE COMING FROM THE VENTS
P7100PLUMBING5152/25/162/26/16BLDG 515 WOMENS RESTROOM: TOILET CLOGGED
P7099LOCKS5002/25/162/25/161G4: SCIF DOOR KNOB IS LOOSE
P7098PLUMBING5002/25/163/1/162C MENS RESTROOM: 3RD SINK FROM THE DOOR IS LEAKING
P7097ELECTRICAL5002/25/162/29/161F4: LIGHT DIFFUSER FELL DOWN AND NEEDS REPLACED
P7096HVAC5002/25/162/25/202163F17: NO WATER IN THE PAN ALARM
P7095ELECTRICAL5002/25/162/29/16BH9: BALLAST OUT
P7094ELECTRICAL5002/25/162/26/16BB01: 2 RED LIGHTS FOR THE SCIF INOP
P7093ELECTRICAL5002/24/162/29/16BJ5: BAD BALLAST
P7092ELECTRICAL5002/24/162/24/163B6: NO POWER TO WORKSTATIONS
P7091GENERAL5002/24/162/24/161E9: DOOR KNOB WILL NOT OPEN THE DOOR
P7090LOCKS5002/24/162/24/16BB30H: XO9 LOCK INOP
P7089ELECTRICAL5002/23/162/23/162H19 - 2H20: NO POWER TO THE ROOMS
P7088ELECTRICAL5002/23/162/24/162D STAIRWELL: LIGHT MAKING A LOUD NOISE
P7087HVAC5972/23/162/29/16BLDG 597 ELEVATOR SHAFT: DISALARM THE FIRE ALARM SYSTEM
P7086LOCKS5002/23/162/23/163F26: CYPHER LOK WILL NOT RETRACK
P7085HVAC5002/22/162/29/162H19: ROOM TOO WARM
P7084HVAC5002/22/162/25/163J11: CRACK UNIT WILL NOT SHUT OFF
P7083ELECTRICAL5222/22/162/22/16GOC RM CC 102: NO POWER TO OURLETS
P7082PLUMBING5012/22/162/23/16LOWER-LEVEL MENS RESTROOM: URINAL WILL NOT SHUT OFF
P6081GENERAL5002/19/162/25/16BB16: CHANGE 6 CEILING TILES
P7080HVAC5002/19/162/22/16BJ2K: WEB CONTROL ALARM GOING OFF
P7079PLUMBING5002/19/162/22/16CAFETERIA FLOOR DRAIN IS BACKED UP
P7078HVAC5002/19/162/22/16BG VAULT: LIEBERT UNIT MAKING A LOUD NOISE
P7077PLUMBING5002/19/162/22/16BB16: SINK IS CLOGGED
P7076PLUMBING5002/18/162/22/163H NORTH MENS RESTROOM: THE URINAL FURTHEST FROM THE DOOR IS LEAKING
P7075GENERAL5002/18/162/18/161E MENS RESTROOM: W2ND STALL HAS A LOOSE TOILET SEAT
P7074PLUMBING5002/18/162/18/161E MENS RESTROOM: 3RD SINK CLOGGED
P7073HVAC5002/18/162/22/162E7: FANS ON THE FCU ARE MAKING A LOUD NOISE
P7072HVAC5002/18/162/22/161E4: CLASSROOM TOO HOT
P7071HVAC5002/17/162B15: TOO HOT
P7070ELECTRICAL5002/17/163C19: EMERGENCY LIGHT IS OUT
P7069ELECTRICAL5002/17/163F24: EMERGENCY LIGHT IS OUT
P7068ELECTRICAL5002/17/162/17/163F22: EMERGENCY LIGHT IS OUT
P7067ELECTRICAL5002/17/162/17/163C12: EMERGENCY LIGHT IS OUT
P7066GENERAL5002/16/162/17/16BH24: REPLACE BROKEN CEILING TILE AND WIPE DOWN AIR HANDLER
P7065LOCKS5002/16/162/16/16BH1: LOCK INOP
P7064PLUMBING5002/16/162/16/163D MENS RESTROOM: CENTER SINK IS CLOGGED
P7063HVAC5002/16/163F17: HIGH WATER IN THE PAN ALARM
P7062LOCKS5002/16/162/16/16BJ2G: OMNI LOCK INOP
P7061GENERAL5002/12/162/12/162F23: DOOR STOP NOT WORKING
P7060PLUMBING5012/12/162/12/16LOWER-LEVEL AIR ROOM: TOILET CLOGGED AD WILL NOT FLUSH
P7059GENERAL5002/12/162/12/16BB16: DOOR LATCH IS LOOSE
P7058LOCKS5002/12/162/12/162E23: LOCK INOP
P7057ELECTRICAL5002/12/162/12/162H27: NO POWER TO THE ROOM
P7056ELECTRICAL5002/12/162/16/161A CONFERENCE ROOM: LIGHT SWITCH SPARKS WHEN TURNED ON
P7055LOCKS5002/11/162/11/162B34: LOCK INOP
P7054HVAC5002/10/162/10/163H35: TOO COLD
P7053HVAC5002/10/162/10/16EQF3: NO WATER IN THE PAN ALARM
P7052PLUMBING5002/10/162/10/162H NORTH MENS RESTROOM: URINAL OVERFLOWING
P7051ELECTRICAL5002/10/162/10/161H1: POWER TRIPPED
P7050PLUMBING5002/10/162/10/16BB01: FLAPPER ON THE TOILET IS BROKEN
P7049ELECTRICAL5002/9/162/11/161E5: NO POWER
P7048ELECTRICAL5002/9/162/16/163H HALLWAY (NEAR 3H 1) RECEPTACLE IS DAMAGED
P7047HVAC5002/9/162/11/16BJ4U: AUDIBLE CRAC ALARM
P7046HVAC5002/9/162/11/163D4: AUDIO ALARM ON HUMIDIFIER
P7045GENERAL5002/8/162/9/16A-WING MAIN ENTRANCE DOORS ARE RUBBING TOGETHER AND OPENING SLOWLY
P7044LOCKS5012/8/162/8/16M121: SCIF DOOR NOT SECURING PROPERLY
P7043GENERAL5002/8/162/8/163H1: SPRINKLER HEADS NEED TO BE CLEANED. (BILL HAS MORE INFO)
P7042HVAC5152/8/16BLDG 515 DOOR: TOO MUCH AIR PRESSURE ON THE DOOR
P7041LOCKS5002/8/162/8/162H27: OMNI LOCK INOP
P7040GENERAL5012/8/162/17/16M116B: WATER LEAK RUINED 3 CEILING TILES AND THEY NEED TO BE REPLACED
P7039LOCKS5002/8/162/10/163F12: XO7 LOCK NOT WORKING PROPERLY
P7038LOCKS5002/8/162/10/163B6: XO7 LOCK NOT WORKING PROPERLY
P7037LOCKS5002/8/162/10/162F16: XO7 LOCK NOT WORKING PROPERLY
P7036PLUMBING5002/8/162/8/162G MENS RESTROOM: LEFTSIDE URINAL IS LEAKING
P7035ELECTRICAL5002/8/162/16/162E10: OUTLET INOP
P7034ELECTRICAL5002/5/163C5: EMERGENCY LIGHT INOP
P7033HVAC5002/5/162/11/16BB02: CEILING LEAK
P7032ELECTRICAL5002/5/163C HALLWAY: DOOR WILL NOT STAY OPEN
P7031LOCKS5002/5/162/5/162E23: CYPHER LOCK INOP
P7030HVAC5002/5/162/9/162C14: CEILING UNIT KEEPS TURNING ON AND OFF
P7029ELECTRICAL5002/4/162/10/161F9: EXIT SIGN IS FLICKERING
P7028ELECTRICAL5002/4/162/4/161H14: NO POWER TO THE ROOM
P7027GENERAL5002/4/162/4/162B23; DOOR DOES NOT SHUT PROPERLY
P7026LOCKS5012/4/162/4/16S3 DOOR: MAKE 2 COPIES OF DB60 KAY KEY (SEE MERLE FOR INFO)
P7025ELECTRICAL5002/4/152/4/163D9: RESET CIRCUIT BREAKER
P7024HVAC5222/4/162/4/16GOC CC204: AC-8 REPORT SUMMARY ALARM
P7023HVAC5002/3/162/4/162B31B: WALL UNIT BLOWING COLD AIR
P7022HVAC5002/3/162/3/162J3: WATER UNDER THE FLOOR ALARM GOING OFF
P7021HVAC5152/3/162/3/16BLDG 515: CRAC UNIT SHOWING SYSTEMS ERROR
P7020GENERAL5152/1/162/1/16BLDG 515: ROOF LEAK. PATCH HOLES
P7019GENERAL5002/1/162/3/16A-WING GUARD STATION: REATTACH CABINET DOOR
P7018HVAC5002/1/162/1/163F17: FIX HUMIDIER
P7017ELECTRICAL5001/29/163G7A: FIRE ALARM STROBE IS HANGING AND NEEDS TO BE REMOUNTED
P7016HVAC5001/29/162/1/163C14: HUMIDITY ALARM IN COMM ROOM
P7015HVAC5001/29/161/29/162H19: TOO WARM
P7014ELECTRICAL5001/29/162A AND 3A STAIRS: JELLYFISH LIGHTS ARE OUT
P7013ELECTRICAL5001/29/163F20: BAD LIGHT BALLAST
P7012ELECTRICAL5001/29/162/10/163D22: EMERGENCY LIGHT INOP
P7011ELECTRICAL5001/29/162/1/163F19: EMERGENCY LIGHT INOP
P7010ELECTRICAL5001/29/161E6: BAD BALLAST
P7009PLUMBING5151/29/162/8/16BLDG 515 FRONT MENS RESTROOM: URINAL OVERFLOWS WHEN FLUSHED
P7008PLUMBING5001/29/161/29/162H SOUTH MENS RESTROOM: LAST URINAL OVERFLOWING
P7007PLUMBING5001/29/161/29/161F HALLWAY: DRINK FOUNTAIN HAS TOO MUCH WATER PRESSURE
P7006PLUMBING5001/29/162/16/161A WOMENS RESTROOM: TOILET DRAINING SLOWLY
P7005HVAC5001/29/162/1/162H14: NO WATER IN THE PAN ALARM
P7004HVAC5001/29/162/1/162F1: HIGH WATER IN THE PAN ALARM
P7003ELECTRICAL5001/29/162/16/16BB HALLWAY: OUTSIDE THE ELEVATOR THERE IS A BAD BALLAST
P7002PLUMBING5011/29/162/1/16LOWER-LEVEL MENS RESTROOM: 1ST SINK INOP AND 2ND SINK CLOGGED
P7001PLUMBING5151/29/16BLDG 515 HANDICAPPED RESTROOM: TOILET LEAKING
P7000ELECTRICAL5001/29/161C STAIRWELL: BAD BALLAST
P6999GENERAL5001/25/161/25/161C MENS RESTROOM: PAPER TOWEL DISPENSER INOP
P6998LOCKS5001/25/161/25/162F16: XO9 LOCK INOP
P6997HVAC5001/25/161/25/16BB12: TOO HOT
P6996HVAC5001/25/161/25/162C12: NO WATER IN THE HUMIDIFIER PAN ALARM
P6995GENERAL5001/25/161/25/16C-WING ELEVATOR HAS A BROKEN HAND RAIL
P6994GENERAL5001/25/161/25/16BBO1: CONFERENCE ROOM DOOR WILL NOT LATCH
P6993GENERAL5001/25/161/25/163C MENS RESTROOM: DOOR CLOSURE IS MAKING A LOUD NOISE.
P6992HVAC5001/25/161/25/162F1: HIGH WATER IN THE PAN ALARM
P6991HVAC5001/22/161/22/163A8: CEILING LEAK
P6990HVAC5011/22/161/22/16M112: NO WATER IN THE PAN ALARM
P6989GENERAL5151/22/161/22/16BLDG 515 ENTRANCE: DRYWALL AND CARPET IS PEELING AWAY FROM THE WALL IMMEDIATELY INSIDE THE DOORWAY
P6988GENERAL5001/22/161/22/163H1: 4 FOOT GRID RUNNER IS TWISTED
P6987HVAC5011/22/161/23/16M112: HUMIDIFIER WON'T CLOSE
P6986PLUMBING4071/22/161/22/16BLDG 407: WOMAN'S RESTROOM HAS A SINK LEAKING
P6985HVAC5001/22/161/22/162H14: NO WATER IN THE PAN ALARM
P6984PLUMBING5011/22/161/22/16BLDG 501 AIR-ROOM: TOIELT OVERFLOWS WHEN FLUSHED
P6983ELECTRICAL5001/21/161/22/161H19: LOST POWER TO SEVERAL WORK STATIONS
P6982GENERAL5001/21/161/22/161G STAIRS GOING TO THE TURNSTILES: RUBBER TREAD TORN AND IS A TRIPPING HAZARD
P6981LOCKS5001/21/161/22/163C1A: MAKE COPY OF KEY. SEE MERLE
P6980ELECTRICAL5001/21/161/22/162H10: BALLAST OUT
P6979ELECTRICAL5001/21/161/22/162A COMMAND SEARGANT OFFICE: BALLAST OUT
P6978PLUMBING5221/20/161/21/16GOC MEN'S RESTROOM: TOILET CLOGGED
P6977GENERAL5151/20/161/20/16BLDG 515: SCIF DOORS WILL NOT UNLOCK
P6976PLUMBING5151/20/161/20/16BLDG 515 MENS FRONT RESTROOM: 1ST SINK IS LEAKING
P6975ELECTRICAL4071/20/161/20/16BLDG 407 ROOMS 10 AND 11: BALLAST OUT
P6974HVAC5001/19/161/20/16CHECK ALL PUMPS AND LOVEJOYS IN MECHANICAL ROOMS ON THE 3RD-FLOOR MECHANICAL ROOMS
P6973HVAC5001/19/161/20/16CHECK ALL PUMPS AND LOVEJOYS IN MECHANICAL ROOMS ON THE 2ND-FLOOT MECHANICAL ROOMS
P6972PLUMBING5001/19/161/20/16LOWER-LEVEL MENS RESTROOM: 1ST SINK INOP
P6971LOCKS5001/19/161/19/162A GLASS DOORS: LOCK FELL OUT OF THE BOTTOM OF THE DOOR AND THE DOORS ARE UNABLE TO BE SECURED
P6970LOCKS5011/19/161/19/16M116E: HYDRUALIC CLOSER WILL NOT SHUT THE DOOR COMPLETELY
P6969ELECTRICAL5001/19/161/19/163B24: NO POWER TO PART OF THE ROOM
P6968HVAC5001/19/161/19/16BB16: TOO HOT
P6967HVAC5001/19/161/20/16BB16: WATER LEAK
P6966ELECTRICAL5001/15/161/19/16BB16: LIGHT INOP
P6965ELECTRICAL5001/15/161/22/16BB16: CIRCUIT BREAKER POPPING AT THE CALIBRATION STATION
P6964LOCKS5001/15/161/15/163A7: CUT 2 KEYS FOR THE DOOR
P6963PLUMBING5011/15/161/15/16LOWER-LEVEL MENS AND WOMENS RESTROOMS ARE BACKING UP
P6962PLUMBING5001/15/161/20/16BA MEN'S RESTROOM: THIRD TOILET LEAKING AT THE BASE
P6961GENERAL5001/15/161/19/163H11: DOOR HANDLE REALLY LOOSE
P6960HVAC5001/15/161/22/162E13: TOO HOT
P6959PLUMBING5001/14/161/15/16MID-LEVEL MENS RESTROOM: SINK BACKED UP
P6958PLUMBING5001/14/161/22/163G HALLWAY: WATER FOUNTAIN IS LEAKING
P6957PLUMBING5001/14/161/15/162G MENS RESTROOM: 1ST FAUCET IS LEAKING
P6956ELECTRICAL5001/14/161/15/16BB16: NO POWER TO THE WORKSTATION
P6955PLUMBING5001/14/161/15/16BB16 MENS RESTROOM: MANUEL FLUSHER IS INOP
P6954GENERAL5001/14/161/19/16BB16 MENS RESTROOM: PAPER TOWEL DISPENSER INOP
P6953PLUMBING5001/14/161/14/163H SOUTH MENS RESTROOM: #5 SINK LEAKS ONTO THE FLOOR
P6952PLUMBING5001/14/161/14/163D HALLWAY: DRINKING FOUNTAIN IS PLUGGED
P6951ELECTRICAL5001/13/161/14/16CAFETERIA: OUTLET IN THE BACK ROOM INOP
P6950HVAC5001/13/161/13/162A MECH ROOM: BELTS BROKE ON AHU
P6949PLUMBING5001/13/161/14/162E MENS RESTROOM: 3 SINKS HAVE TOO MUCH PRESSURE
P6948HVAC5011/13/161/14/16L116: FOUL ODOR COMING FROM THE VENT
P6947PLUMBING5971/13/161/13/16BLDG 597: UNISEX BATHROOM HAS A CLOGGED SINK
P6946HVAC5001/13/16GOC: CLEAR FRESH AIR INTAKE
P6945HVAC5001/12/161/15/163E1: TOO HOT
P6944HVAC5221/12/161/12/16GOC: AHU1C IS VIBRATING AND MAKING A LOUD NOISE
P6943LOCKS5001/12/161/13/162E7: REPLACE XO7 LOCK WITH AN X09 LOCK
P6942ELECTRICAL5011/11/161/17/16MID-LEVEL HALLWAY BY M105: BAD BALLAST
P6941ELECTRICAL5011/11/161/14/16UPPER-LEVEL HALLWAY BY ROOM U120: BAD BALLAST
P6940HVAC5151/11/161/11/16BLDG 515: AHU ALARM GOING OFF
P6939HVAC5001/11/161/11/162F5: TOO HOT
P6938HVAC5011/11/161/11/16U146: PIPE LEAKING IN THE CEILING
P6937HVAC5001/11/161/11/162A COMMAND SECTION: TOO HOT (76 DEGREES)
P6936ELECTRICAL5001/11/161/11/162B23: BLOW CIRCUIT
P6935PLUMBING5151/11/161/12/16BLDG 515: FRONT MENS RESTROOM: LEFT URINAL NOT DRAINING
P6934LOCKS4071/11/161/14/16BLDG 407: NEED A NEW KEY MADE FOR THE DOOR ON THE NORTH SIDE OF THE BLDG. SEE THE REQUESTER IN ROOM 19.
P6933PLUMBING5001/11/161/11/16UPPER-LEVEL MENS RESTROOM: URINAL CONTINUOUSLY RUNNING
P6932PLUMBING5001/11/161/12/16GOC: LIFT STATION MOTOR IS PROPER
P6931GENERAL5001/8/161/12/162B9: REMOVE DOOR CLOSURE. (KNOW ON THE DOOR AND ASK FOR THE POC)
P6930ELECTRICAL5001/8/161/12/163H10: BALLAST OUT IN LIGHT FIXTURE
P6929GENERAL5001/8/162B17: DOOR CLOSURE LOOSE
P6928ELECTRICAL5001/8/161/8/163F12: NO POWER
P6927HVAC5001/8/161/13/15BB14: LEAK IN THE CEILING
P6926HVAC5001/8/161/15/163J13: TOO HOT
P6925LOCKS5021/7/151/11/16MOLE HOLE PUSH BAR WILL NOT UNLOCK
P6924HVAC5151/7/161/8/16SO47: TOO HOT
P6923LOCKS5001/7/161/7/16SECURITY CONTROL OFFICE DOOR IN BF WILL NOT SECURE
P6922HVAC5001/7/161/8/163C14: NO WATER IN HUMIDIFIER PAN ALARM
P6921HVAC5001/7/161/8/162C12: NO WATER IN THE HUMIDIFIER PAN ALARM
P6920HVAC5001/6/161/7/161F4: TOO HOT
P6919PLUMBING5011/6/161/11/16UPPER-LEVEL MENS RESTROOM: URINAL OVERFLOWING
P6918PLUMBING5001/6/161/11/162G MENS RESTROOM: BATTERIES LOW ON URINAL
P6917PLUMBING5221/6/161/6/16GOC FIRST FLOOR MENS RESTROOM: SINK IS LEAKING
P6916ELECTRICAL5001/6/161/6/163F3: BLOWN CIRCUIT BREAKER (#19)
P6915GENERAL5011/6/161/11/15U120: PLASTIC LENS MISSING FROM LIGHT FIXTURE
P6914HVAC5001/6/161/7/163A2: LOUD SOUND COMING FROM THE MECH ROOM
P6913GENERAL5001/6/161/6/16THEATER DOORS WILL NOT CLOSE
P6912ELECTRICAL5001/6/161/7/162D15: BAD BALLAST
P6911ELECTRICAL5001/6/161/12/162A STAIRWELL: LIGHT BURNED OUT
P6910ELECTRICAL5001/6/161/14/16CANNED LIGHTS IN THE THEATER ARE OUT
P6909HVAC5221/5/161/6/16GOC: AHU #3 HAS AN ALARM GOING OFF. TOO MUCH STATIC PRESSURE. IT IS AT 5.0
P6908GENERAL5001/5/161/6/16DOOR LEADING FOR THE CAFETERIA TO THE COURTYARD WILL NOT SECURE
P6907PLUMBING5001/5/161/5/163D MENS RESTROOM: TOILET WILL NOT QUIT FLUSHING
P6906ELECTRICAL5011/4/161/11/16U102: BAD BALLAST
P6905ELECTRICAL50112/30/1512/30/15LOWER-LEVEL HALLWAY: EXIT SIGN INOP
P6904PLUMBING50112/30/1512/30/15UPPER-LEVEL MENS RESTROOM: ONE SINK INOP AND THE OTHER IS LEAKING
P6903PLUMBING50012/30/1512/30/15BB16: SINK NOT DRAINING
P6902HVAC51512/30/1512/30/15BLDG 515: DOORS HAVE OVERPRESSURE
P6901GENERAL50012/30/1512/30/15B-WING STAIRWELLS: HANDRAIL LOOSE
P6900LOCKS50012/30/1512/30/152C11: XO9 LOCK INOP
P6899HVAC50112/30/1512/30/15U102: PIPE LEAKING ABOVE THE CRACK UNIT
P6898HVAC50012/29/1512/30/151J12: HIGH TEMP ALARM GOING OFF
P6897HVAC50112/29/151/5/16L124E: WATER LEAKING IN THE CEILING
P6896HVAC50012/23/1512/24/152J3: WATER UNDER THE FLOOR ALARM GOING OFF
P6895PLUMBING50112/23/1512/23/15BB MENS RESTROOM: URINAL OVERFLOWING
P6894PLUMBING59712/23/15BLDG 597 ELEVATOR PIT: CHECK THE PUMP IN THE ELEVATOR WELL TO SEE IF IT IS WORKING
P6893PLUMBING50112/23/15LOWER-LEVEL MENS RESTROOM: FAR RIGHT SINK WILL NOT SHUT OFF
P6892GENERAL59112/23/1512/23/15BLDG 591 VISITOR CONTROL CENTER: DOOR HANDLE CAME OFF THE DOOR
P6891HVAC50012/23/1512/23/151H19: TOO COLD
P6890LOCKS50112/23/1512/23/15L125: XO9 LOCK WILL NOT SECURE
P6889HVAC50012/23/1512/23/153D22: TOO COLD
P6888PLUMBING50012/22/151C WOMENS RESTROOM: 4TH TOILET WILL NOT FLUCH
P6887HVAC50012/21/1512/22/15BB16: WATER LEAK IN THE CEILING
P6886LOCKS50012/21/1512/21/153C3: ELECTRIC STRIKE NOT ENGAGING ON XO9 LOCK
P6885HVAC50012/21/1512/24/151H11: TOO COLD
P6884PLUMBING51512/18/1512/21/15BLDG 515 REAR WOMEN'S RESTROOM: SINK IS CLOGGED
P6883ELECTRICAL50012/18/1512/18/153H HALLWAY (NEAR 3H 1) RECEPTACLE IS DAMAGED
P6882LOCKS50012/18/1512/21/151G ELECTRICAL ROOM: SECURE THE DOOR TO THE LOOK. SAFETY WRITEUP.
P6881ELECTRICAL50012/17/1512/18/153B15: TRIPPED BREAKER
P6880PLUMBING50012/17/1512/18/15BJ MENS RESTROOM: URINAL OVERFLOWED
P6879ELECTRICAL50012/17/1512/17/153D9: TRIPPED BREAKER
P6878HVAC50012/17/1512/22/152D7: FCU INOP
P6877HVAC50012/17/1512/17/153F22: TOO COLD
P6876ELECTRICAL50012/17/1612/17/152C11: DOOR STICKING
P6875HVAC50012/15/1512/17/152C11: TOO WARM
P6874GENERAL50012/15/1512/15/15BB30F: REMOUNT FIRE EXTINGUISHER
P6873HVAC50012/15/1512/17/153F326: TOO COLD
P6872PLUMBING50012/15/1512/16/151G MENS RESTROOM: NO WATER PRESSURE
P6871HVAC51512/15/1512/15/15SO42: AHU MAKING A LOUD NOISE
P6870LOCKS50012/15/1512/15/153C3: XO9 LOCK NOT RELEASING
P6869ELECTRICAL50012/15/152F16: RECEPTACLE NOT COMPLIANT BY THE FIRE INSPECTOR
P6868ELECTRICAL50012/15/152F9: RECEPTACLE NOT COMPLIANT BY FIRE INSPECTOR
P6867ELECTRICAL50012/15/162C10: RECEPTACLE NOT COMPLIANT BY FIRE INSPECTOR
P6866ELECTRICAL50012/15/1512/15/15BB16: NO POWER TO A PORTION OF THE ROOM
P6865PLUMBING51512/15/1512/15/15BLDG 515 FRONT MENS RESTROOM HAS A CLOGGED TIOILET
P6864GENERAL51512/15/1512/15/15BLDG 515: DOORS NOT CLOSING PROPERLY
P6863HVAC50012/15/1512/18/152D7: COLD AIR BLOWING OUT OF THE UNIT
P6862HVAC51512/15/1512/16/15BLDG 515 AHU IS OFF
P6861ELECTRICAL51512/15/1512/15/15IN THE HALLWAYS BY THE TURNSTILES FOR BLDG 515 THERE ARE 3 BALLAST OUT
P6860HVAC50012/15/1512/16/152B29: WATER LEAKING IN THE CEILING
P6859HVAC52212/15/1512/15/15GOC: WATER LEAK INSIDE THE MAIN SET OF DOORS
P6858HVAC50112/14/1512/15/15SUMP PUMP INOP AT THE BOTTOM OF THE MOLE HOLE
P6857GENERAL50012/14/1512/15/15BE MENS RESTROOM: TOILET BROKEN ON THE BACK STALL
P6856HVAC59712/14/1512/17/15BLDG 597: WATER IN THE ELEVATOR SHAFT
P6855ELECTRICAL50012/14/1512/16/152G: RECEPTACLE NEEDS TO BE REPLACED. IT WAS WRITTEN UP BY FIRE INSPECTOR
P6854ELECTRICAL50012/14/153J SCIF: RECEPTACLE NEEDS TO BE REPLACED. IT WAS WRITTEN UP BY FIRE INSPECTOR
P6853ELECTRICAL50012/14/152E10: RECEPTACLE NEEDS TO BE REPLACED. IT WAS WRITTEN UP BY FIRE INSPECTOR
P6852PLUMBING50012/14/1512/15/152E MENS RESTROOM: PARTITION WALL BETWEEN FIRST AND SECOND STALL IS LEANING
P6851PLUMBING50012/14/1512/16/153G MENS RESTROOM: WATER LEAKING UNDER THE SINK
P6850PLUMBING51512/14/1512/15/15BLDG 515 FRONT MENS RESTROOM: TOILET CONTINUOUSLY FLUSHING
P6849HVAC50012/11/1512/11/15SO60: TOO HOT
P6848HVAC50012/11/1512/11/152C11: TOO WARM
P6847PLUMBING50012/11/1512/18/151J MENS RESTROOM: WATER WILL NOT SHUT OFF
P6846PLUMBING50012/11/1512/11/152D WATER FOUNTAIN IS CLOGGED
P6845PLUMBING50012/10/1512/10/153E MENS RESTROOM: LAST STALL CLOGGED
P6844HVAC40712/10/1512/10/15BLDG 407: BAD SEWAGE SMELL IN THE SCIF
P6843HVAC50012/10/1512/10/151F COFFEE PREP ROOM: SYSTEM ALARM GOING OFF
P6842LOCKS50012/10/1512/10/151J VAULT DOOR WILL NOT SECURE
P6841LOCKS50012/10/1512/10/15BJ2: WHEN CYPHER CODE IS ENTERED, DOOR DOES NOT OPEN
P6840LOCKS50012/9/1512/9/153B9: CYPHER LOCK IS STICKING
P6839HVAC50012/9/1512/11/15CAFETERIA: FAN COIL UNIT COVER IS DISCONNECTED
P6838GENERAL50012/9/1512/21/15STAIRS FROM THE COURTYARD TO H-WING ARE LOOSE FROM THE CONCRETE
P6837GENERAL50012/9/1512/11/15BB MENS RESTROOM: #2 PAPER TOWEL DISPENSER HAS A BROKEN COVER. THE COVER IS IN PEARL'S OFFICE.
P6836PLUMBING50012/9/1512/10/151E WOMENS RESTROOM: SINK LEAKING
P6835ELECTRICAL50012/9/1512/10/152F22: CIRCUIT BLOWN NEEDS RESET
P6834HVAC50112/9/1512/10/15U127: SEWAGE SMELL IN THE HALLWAY
P6833PLUMBING50012/9/15BH MENS RESTROOM: SINK CONTINUOUSLY RUNNING
P6832ELECTRICAL50112/9/1512/9/15L120: OUTLET INOP
P6831GENERAL50012/8/1512/22/152B10: DOOR LATCH DOOR NOT WORK PROPERLY
P6830HVAC50012/8/15BJ2K: AIR SUPPLY DUCT NEEDS TO BE REMOVED
P6829ELECTRICAL50012/8/1512/10/152D7: NO POWER TO THE OUTLET
P6828PLUMBING50112/7/1512/7/15L138 MENS RESTROOM: TOILET OVERFLOWING
P6827ELECTRICAL50012/7/1512/8/152A16: CAVE OUTLET NOT WORKING
P6826PLUMBING50012/7/1512/7/151A MENS RESTROOM: TOILET OVERFLOWING
P6825PLUMBING51512/7/1512/9/15BLDG 515 WOMENS RESTROOM: TOILET CLOGGED
P6824HVAC50012/7/151J UPS ROOM: TOO HOT
P6823GENERAL50112/7/1512/8/15L125: REMOUNT FIRE EXTINGUISHER NEXT TO THE DOOR
P6822PLUMBING50012/7/1512/7/153C WOMENS RESTROOM: TOILETS OVERFLOWING
P6821HVAC40712/7/1512/8/15BLDG 407: TOO HOT IN THE SCIF AREA
P6820PLUMBING50012/7/1512/10/153G MENS RESTROOM: SINK LEAKING
P6819PLUMBING50112/7/1512/10/15LOWER-LEVEL MENS RESTROON: SINK WILL NOT SHOT OFF
P6818HVAC50012/7/1512/7/15BH31: FILTERS IN CRAC UNIT ARE PLUGGED AND UNIT IS BLOWING DUST
P6817ELECTRICAL50112/7/1512/8/15U102: EMERGENCY LIGHT #4 INOP
P6816HVAC50012/4/1512/8/152B27: WATER LEAK IN THE CEILING
P6815ELECTRICAL50012/4/1512/4/151E5: NO POWER TO THE CUBICAL
P6814HVAC50012/4/1512/4/153D16: WATER LEAKING FROM THE CEILING
P6813GENERAL50012/4/1512/4/15BJ MENS RESTROOM: 1ST TOILET SEAT IS LOOSE
P6812GENERAL50012/4/1512/4/151B STAIRS: HANDRAIL IS LOOSE
P6811HVAC50012/4/1512/4/152E26: TOO HOT
P6810LOCKS50012/4/1512/4/151C8: SPIN DIAL INOP.
P6809GENERAL52212/4/1512/30/15GOC: STAIR TREAD COMING UP
P6808GENERAL50012/4/1512/8/151H11: FIRE EXTINGUISHER NEEDS TO BE REMOUNTED TO THE WALL
P6806HVAC50012/3/1512/8/151E5: CEILING LEAK (HAVE GEN. MAINTENANCE CHANGE CEILING TILE WHEN COMPLETE)
P6805ELECTRICAL50112/3/1512/8/15U102: EMERGENCY LIGHT INOP
P6804PLUMBING50012/3/1512/9/152G VAULT MENS RESTROOM: ONLY 1 SINK WORKS
P6803HVAC50012/3/15BB16: UNITS BLOWING HEAT OUT OF SOME AND COLD AIR OUT OF OTHERS.
P6802HVAC50012/3/1512/3/152G VAULT: WATER SCOLDING HOT IN BOTH BATHROOMS
P6801ELECTRICAL50012/3/1512/3/151E WOMENS RESTROOM: BALLAST ABOVE THE SINK INOP
P6800HVAC50112/3/1512/9/15MID-LEVEL MENS RESTROOM: 2ND SINK INOP
P6799HVAC52212/3/1512/3/15GOC ROOM CC207: FCU MAKING A LOUD NOISE

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .