Vendor Questions Round 4
1. Question: Sir, the walk thru only went through 2 buildings and the cooling towers.
But I seen more buildings than that on the solicitation. Can you tell me, do any of these other buildings have fire sprinklers or alarms in them? Or can I come back and see?
ANSWER: All the buildings have sprinkler and alarm systems. There will not be another site-visit.
2. Question: Are the requirements on this RFP the same as the requirements on the incumbent’s contract?
ANSWER: The most prevalent changes are 1.3.1.14- BJ Back-up chiller, 1.3.1.15- J Wing chiller Tie-in, 1.3.2.1 and 1.3.2.1.1 both for the PGS. The mention of CLINs X004, X005, X006 in the PWS, along with the requirements considering these CLINs could also be considered a change.
However, generally speaking, most changes in the PWS between the past contract and the current requirement are a polishing process rather than a completely different requirement.
File details come from the government source that posted it. Updated .