This document contains detailed programming instructions for the W3 LF 450PLUS system, providing a comprehensive step-by-step guide for system setup and configuration. The instructions cover multiple configuration stages, including system setup, device configuration, tank settings, and security parameters. Key configuration steps include setting system language to English, configuring time and date settings, setting up tank parameters for a diesel tank (TK-101) with a 3,782-gallon capacity, configuring probes and sensors, setting relay configurations, and establishing user administration with specific security settings. The document provides granular instructions for each step, including enabling/disabling various system features, setting up tank profiles, configuring alarm and test settings, and establishing user access with specific security restrictions like disabling web access, SSH, and serial command ports.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W3 LF 450PLUS Programming Instructions
************************************************System Setup************************************************
1. Once the console has been installed and connected to the power panel boot the console and wait for the home screen to display.
2. Access Workflow Wizard Setup by touching MENU>SETUP> WORKFLOW WIZARD>SETUP
WORKFLOW
3. On the SETUP>DISPLAY>LANGUAGE/UNITS page, set System Language to English
4. Set System Units to US
5. Press checkmark to save any changes and press Next
6. Set Current Date
7. Set Current Time
8. Set Time Zone to (UTC -07:00) US/Mountain
9. Set NPT to DISABLED
10. Press checkmark to save any changes and press Next
11. Set Date Format to mm_dd_yyyy
12. Set Date Separator to /
13. Set Time Format to hh:mm AP
14. Press checkmark to save any changes and press Next
15. Set Decimal Separator to .
16. Set Thousands Separator to None.
17. Press checkmark to save any changes and press Next
18. Header 1: Enter site name (e.g. Alpha – 01)
19. Set Header 2: to street address
20. Set Header 3: to City, State, and ZIP code
21. Set Header 4: to Facility ID from state (e.g. XX-XXXX)
22. Press checkmark to save any changes and press Next
23. Set Alarm Filtering to Disabled
24. Press checkmark to save any changes and press Next
25. Enter System Hostname to TLS450
26. Press checkmark to save any changes and press Next
27. Set IP Default Gateway to Disabled
28. Press checkmark to save any changes and press Next
29. On Internal Modem menu, Press Next
30. On CDIM port menu, Press Next
31. Set TDIM Port configuration to Disabled.
32. Press checkmark to save any changes and press Next
33. Set TLG IFSF to disabled
34. Press checkmark to save any changes and press Next
35. Set Serial Port Configured to DISABLED
36. Press checkmark to save any changes and press Next
37. Ensure Email Relay Enabled is not checked
38. Press checkmark to save any changes and press Next
39. Set Gateway configuration to DISABLED
40. Press checkmark to save any changes and press Next
****************************************************Probe****************************************************
41. Set Up Devices Starting with Probe 1
42. Set Configuration to Enabled
43. Assign Address as B1.S1.x (x corresponds to the slot the Magnetostrictive probe was installed in)
44. Set Label to TK-101
45. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
46. Set Water Minimum to [IN] to 0
47. Press Checkmark to save any changes
*************************************************Sump Sensor*************************************************
48. Select bottom left Probe icon to open the devices submenu
49. Select Liquid Sensor and begin configuring Liquid Sensor 1
50. Set configuration to enabled
51. Set address to B1.S1.x (x corresponds to the slot the Magnetostrictive probe was installed in)
52. Set label to Sump
53. Set Model to Tri-State (Single Float)
54. Set Category to Piping Sump
55. Press checkmark to save any changes
**********************************************Interstitial Sensor**********************************************
56. Select bottom left MAG Sensor icon to open devices submenu
57. Select Liquid Sensor and begin configuring Liquid Sensor 2
58. Set Configuration to enabled
59. Set address to B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
60. Set label to Interstitial
61. Set Model to Tri-State (Single Float)
62. Set Category to Annular Space
63. Press checkmark to save any changes and press Next
****************************************************Relays****************************************************
64. Press the bottom left Liquid Sensor icon to open the devices submenu
65. Select Relay
66. Set configuration of Relay 1 to ENABLED
67. Set Address to B1.S7.1 (The relay address B1:S7:1 refers to the single input Power Bay relay)
68. Set Label to Overfill Alarm
69. Set type to Standard
70. Set Orientation to Normally Open
71. Press checkmark to save any changes
72. Select Relay 2 from bottom menu
73. Set configuration of Relay 2 to ENABLED
74. Set Address to B1.S2.5
75. Set Label to Alarm Output
76. Set type to Standard
77. Set Orientation to Normally Closed
78. Press checkmark to save any changes
79. Select Relay 3 from bottom menu
80. Set configuration of Relay 3 to ENABLED
81. Set Address to B1.S2.6
82. Set Label to Closed Loop
83. Set type to Standard
84. Set Orientation to Normally Open
85. Press checkmark to save any changes and press Next
****************************************************Tank 1****************************************************
86. Set up Tank 1
87. Set Tank 1 Configuration to enabled
88. Set tank label to TK – 101
89. Set product code to 1
90. Set Probe to Probe 1
91. Set Probe offset to 0.00 Inches
92. Set Full volume to 3782 GALLONS
93. Set Diameter to 72.0 Inches
94. Set tank tilt to 0.00 inches
95. Set Thermal Coefficient to 0.000450
96. Set Meter Data Present to DISABLED
97. Set Delivery Delay [min] to 1
98. Set Gross Test Fail to ENABLED
99. Set Periodic Test Fail to ENABLED
100. Set Annual test Fail to DISABLED
101. Set GOST Volume Correction to DISABLED
102. Press checkmark to save any changes and press Next
103. Setup Tank Limits for Tank 1
104. Set Max Volume (Label Vol.) [gal] to 3782
105. Set High Product (% of max. vol.) to 95%
106. Set Delivery Overfill to (% of max. vol.) 90%
107. Set Delivery Limit (% of Full vol.) to 10%
108. Set Low Product [gal] to 2600
109. Set High Water Warning [in.] to 1.0
110. Set High Water Alarm [in.] to 2.0
111. Set Water Alarm Filter Level to OFF
112. Set Water Alarm Filter Delay to 30 S
113. Set Leak Alarm Limit [gal] to 99
114. Set Sudden Loss Limit [gal] to 100
115. Set Fuel Temperature Low Limit [DEG F] to -58.0
116. Set Fuel Temperature High Limit to [DEG F] 140.0
117. Press checkmark to save any changes and press Next
118. Set Test Tank Method to CSLD
119. Set Probability of Detection to 95%.
120. Set Climate Factor to MODERATE
121. Set CSLD evaporation compensation to DIABLED
122. Set Stage II Vapor Recover to DISABLED
123. Press checkmark to save any changes and press Next
124. Set up Tank Profile for Tank 1
125. Set Tank Profile to FOUR POINTS
126. Set 54.0 INCHES [gal] to 3184
127. Set 36.0 INCHES [gal] to 2001
128. Set 18.0 INCHES [gal] to 781
129. Press checkmark to save any changes and press Next
130. Set up Tank charts
131. Press the check box next to entry 1
132. Press the actions menu
133. Select Apply chart check mark and press Next
**************************************************All Tanks***************************************************
134. On Siphon Sets page, press Next
135. Set up All Tanks
136. Set Ullage Display mode to USER ULLAGE
137. Set User Ullage % to 90
138. Set Print TC Volumes to DISABLED
139. Set Periodic Test Needed Warnings to DISABLED
140. Set Annual Test Needed Warnings to DISABLED
141. Set TC Density to DISABLED
142. Set Stick Height to DISABLED
143. Set Leak Test Report Format to STANDARD
144. Set Leak Test Region to EPA
145. Press checkmark to save any changes and press Next
**********************************************Product Mapping**********************************************
146. Check Product # 1 box
147. Press actions
148. Press edit label
149. Set product 1 label to DIESEL
150. Press checkmark to save any changes and press Next
151. Check tank # 1 box
152. Press actions
153. Press edit Tank(s) product mapping
154. Select Product 1 DIESEL
**************************************All else, Tasks, Custom Alarms**************************************
155. Press checkmark to save any changes and press Next
156. Set Pumps and Lines > Pumps, Configured to disabled
157. Press checkmark to save any changes and press Next
158. Set Pumps and Lines > Line, Configured to disabled
159. Press checkmark to save any changes and press Next
160. On PLLD, Press Next
161. Set Pumps and Lines > All Lines, Restart on Alarm Clear to DISABLED
162. Set Line Lockout Schedule to disabled
163. Press checkmark to save any changes and press Next
164. Set Pumps and Lines > All PLLD, set Line Re-Enable method to Pass Line Test
165. Set Periodic Test Warnings to DISABLED
166. Set Annual Test Warnings to DISABLED
167. Press checkmark to save any changes and press Next
168. On Inventory > Report Times, Set Reporting Interval to DISABLED
169. Press checkmark to save any changes and press Next
170. Set shift close method to TIMED
171. Press checkmark to save any changes and press Next
172. Set delivery method to Standard Automatic
173. Set Tank Idle Delivery to DISABLED
174. Press checkmark to save any changes and press Next
175. On Address Book menu select next
176. On Automatic Events > AutoXmit, set delay time (Secs) to 5
177. Set repeat time (mins) to 60
178. Set Leak Alarm to DISABLED
179. Set High Water Alarm to DISABLED
180. Set Overfill Alarm to DISABLED
181. Set Low Limit Alarm to DISABLED
182. Set Theft Alarm to DISABLED
183. Set Delivery Start to DISABLED
184. Set Delivery Stop to DISABLED
185. Set External Input On to DISABLED
186. Set External Input Off to DISABLED
187. Set Sensor Fuel Alarm to DISABLED
188. Set Sensor Water Alarm to DISABLED
189. Set Sensor Out Alarm to DISABLED
190. Press checkmark to save any changes and press Next
191. On Autoconnect Tasks menu select next
192. On Device tasks menu select Actions
193. Press Add Task
194. Set Device as RELAY 1: Overfill Alarm
195. In Event submenu, select TANK drop down
196. Check the following boxes
• OVERFILL ALARM
197. Press checkmark to save any changes.
198. On Device tasks menu select Actions
199. Press Add Task
200. Set Device as RELAY 2: Alarm Output
201. In Event submenu, select LIQUID SENSOR drop down
202. Check the following boxes
• FUEL ALARM
• SENSOR OUT ALARM
• SHORT ALARM
• WATER ALARM
• LIQUID WARNING
203. In Event submenu, select MAG SENSOR drop down
204. Check the following boxes
• COMMUNICATION ALARM
• SENSOR FAULT ALARM
• FUEL WARNING
• FUEL ALARM
• WATER WARNING
• WATER ALARM
• HIGH LIQUID WARNING
• HIGH LIQUID ALARM
• INSTALL FAULT
205. In Event submenu, select TANK drop down
206. Check the following boxes
• SETUP DATA WARNING
• LEAK ALARM
• HIGH WATER ALARM
• LOW PRODUCT ALARM
• SUDDEN LOSS ALARM
• PROBE OUT
• HIGH WATER WARNING
• DELIVER NEEDED
• GROSS TEST FAIL
• PERIODIC TEST FAIL
• CSLD IDLE TIME
• CSLD RATE INCR WARNING
207. Press checkmark to save any changes and press Next
208. On Print Tasks menu, Press next
209. On All Tasks menu, Press Next
210. On Roles Admin menu, Press Next
211. On Users Admin, select Actions
212. Press Add User
213. Set Username to WFSM
214. Set Fullname to Fuels
215. Set Role to Administrator
216. Set Email to Wing ORG email
217. Set Password to 450plus
218. Press checkmark to save any changes and press Next
219. On Security menu Set front panel security to DISABLED
220. Set Serial Command Port to DISABLED
221. Set SSH Port to DISABLED
222. Set serial command over SSH to DISABLED
223. Set HTTPS Port (WEB ACESS) to DISABLED
224. Set User admin via web to DISABLED
225. Press checkmark to save any changes and press Next
226. Exit Set up Wizard
227. Ensure printer has paper