This document contains detailed programming instructions for configuring a W3 MAF 450PLUS system, specifically focusing on comprehensive setup procedures for tank monitoring and management. The instructions cover system initialization, probe configuration, MAG sensor setup, interstitial sensors, relays, and tank profiles for four separate tanks (TK-115, TK-107, MUR, and DL) with different volumes ranging from 612 to 14,272 gallons. The configuration process involves enabling specific tanks, setting product codes (Diesel and MUR), configuring probe offsets, defining tank dimensions, establishing thermal coefficients, and setting up various alarm and test parameters such as water level warnings, leak detection, and temperature limits. Additional system settings include disabling various automatic events, configuring user access with an administrator account (username: WFSM), and implementing security measures by disabling front panel, web, and SSH access.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W3 MAF 450PLUS Programming Instructions
************************************************System Setup************************************************
1. Once the console has been installed and connect to the power panel boot the console and wait for the home screen to display.
2. Access Workflow Wizard Setup by touching MENU>SETUP> WORKFLOW WIZARD>SETUP
WORKFLOW
3. On the SETUP>DISPLAY>LANGUAGE/UNITS page, set System Language to English
4. Set System Units to US
5. Press checkmark to save any changes and press Next
6. Set Current Date
7. Set Current Time
8. Set Time Zone to (UTC -07:00) US/Mountain
9. Set NPT to DISABLED
10. Press checkmark to save any changes and press Next
11. Set Date Format to mm_dd_yyyy
12. Set Date Separator to /
13. Set Time Format to hh:mm AP
14. Press checkmark to save any changes and press Next
15. Set Decimal Separator to .
16. Set Thousands Separator to None.
17. Press checkmark to save any changes and press Next
18. Header 1: Enter site name (e.g. Alpha – 01)
19. Set Header 2: to street address
20. Set Header 3: to City, State, and ZIP code
21. Set Header 4: to Facility ID from state (e.g. XX-XXXX)
22. Press checkmark to save any changes and press Next
23. Set Alarm Filtering to Disabled
24. Press checkmark to save any changes and press Next
25. Enter System Hostname to TLS450
26. Press checkmark to save any changes and press Next
27. Set IP Default Gateway to Disabled
28. Press checkmark to save any changes and press Next
29. On Internal Modem menu, Press Next
30. On CDIM port menu, Press Next
31. Set TDIM Port configuration to Disabled.
32. Press checkmark to save any changes and press Next
33. Set TLG IFSF to disabled
34. Press checkmark to save any changes and press Next
35. Set Serial Port Configured to DISABLED
36. Press checkmark to save any changes and press Next
37. Ensure Email Relay Enabled is not checked
38. Press checkmark to save any changes and press Next
39. Set Gateway configuration to Disabled
40. Press checkmark to save any changes and press Next
****************************************************Probes****************************************************
41. Set Up Devices Starting with Probe 1
42. Set Configuration to Enabled
43. Assign Address as B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
44. Set Label to TK-115
45. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
46. Set Water Minimum to [IN] to 0
47. Press Checkmark to save any changes
48. Select Probe 2
49. Set Configuration to Enabled
50. Assign Address as B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
51. Set Label to TK-107
52. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
53. Set Water Minimum to [IN] to 0
54. Press Checkmark to save any changes
55. Select Probe 3
56. Set Configuration to Enabled
57. Assign Address as B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
58. Set Label to MUR
59. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
60. Set Water Minimum to [IN] to 0
61. Press Checkmark to save any changes
62. Select Probe 4
63. Set Configuration to Enabled
64. Assign Address as B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
65. Set Label to DL
66. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
67. Set Water Minimum to [IN] to 0
68. Press Checkmark to save any changes
************************************************MAG Sensors************************************************
69. Select bottom left Probe icon to open the devices submenu
70. Select MAG Sensor and begin configuring MAG Sensor 1
71. Set configuration to enabled
72. Set address to B1.S1.x (x corresponds to the slot the Magnetostrictive probe was installed in)
73. Set label to Sump 115
74. Set Alarm Delay [hours] to 0
75. Set Water Alarm Delay [in] to 3.0
76. Set Water Warning [in] to 2.0
77. Press checkmark to save any changes
*********************************************Interstitial Sensors*********************************************
78. Select bottom left MAG Sensor icon to open devices submenu
79. Select Liquid Sensor and begin configuring Liquid Sensor 1
80. Set Configuration to enabled
81. Set address to B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
82. Set label to Interstitial 115
83. Set Model to Tri-State (Single Float)
84. Set Category to Annular Space
85. Press checkmark to save any changes and press Next
****************************************************Relays****************************************************
86. Press bottom left menu to open list of probes
87. Press the bottom left “Probe” icon to open the devices submenu
88. Select Relay
89. Set configuration of Relay 1 to ENABLED
90. Set Address to B1.S7.1
91. Set Label to Overfill Alarm
92. Set type to Standard
93. Set Orientation to Normally Open
94. Press checkmark to save any changes
95. Select Relay 2
96. Set configuration to ENABLED
97. Set Address to B1.S2.5
98. Set Label to Bell
99. Set Type to Standard
100. Set Orientation to Normally Open
101. Press checkmark to save any changes and press Next
****************************************************Tank 1****************************************************
102. Set up Tank 1
103. Set Tank 1 Configuration to enabled
104. Set tank label to TK – 115
105. Set product code to 1
106. Set Probe to Probe 1
107. Set Probe offset to 0.00 Inches
108. Set Full volume to 2319 GALLONS
109. Set Diameter to 72.0 Inches
110. Set tank tilt to 0.00 inches
111. Set Thermal Coefficient to 0.000450
112. Set Meter Data Present to DISABLED
113. Set Delivery Delay [min] to 1
114. Set Gross Test Fail to ENABLED
115. Set Periodic Test Fail to ENABLED
116. Set Annual test Fail to DISABLED
117. Set GOST Volume Correction to DISABLED
118. Press checkmark to save any changes
119. Setup Tank Limits for Tank 1
120. Set Max Volume (Label Vol.) [gal] to 2319
121. Set High Product (% of max. vol.) to 95%
122. Set Delivery Overfill to (% of max. vol.) 90%
123. Set Delivery Limit (% of Full vol.) to 10%
124. Set Low Product [gal] to 800
125. Set High Water Warning [in.] to 1.5
126. Set High Water Alarm [in.] to 2.0
127. Set Water Alarm Filter Level to OFF
128. Set Water Alarm Filter Delay to 30 S
129. Set Leak Alarm Limit [gal] to 99
130. Set Sudden Loss Limit [gal] to 100
131. Set Fuel Temperature Low Limit [DEG F] to -58.0
132. Set Fuel Temperature High Limit to [DEG F] 140.0
133. Press checkmark to save any changes and press Next
134. Set Test Tank Method to CSLD
135. Set Probability of Detection to 95%.
136. Set Climate Factor to MODERATE
137. Set CSLD evaporation compensation to DIABLED
138. Set Stage II Vapor Recover to DISABLED
139. Press checkmark to save any changes and press Next
140. Set up Tank Profile for Tank 1
141. Set Tank Profile to FOUR POINTS
142. Set 54.0 INCHES [gal] to 1965
143. Set 36.0 INCHES [gal] to 1229
144. Set 18.0 INCHES [gal] to 467
145. Press checkmark to save any changes and press Next
146. Set up Tank charts
147. Press the check box next to entry 1
148. Press the actions menu
149. Select Apply chart check mark
****************************************************Tank 2****************************************************
150. Set up Tank 2
151. Set Tank 2 Configuration to enabled
152. Set tank label to TK – 107
153. Set product code to 1
154. Set Probe to Probe 2
155. Set Probe offset to 0.00 Inches
156. Set Full volume to 14272 GALLONS
157. Set Diameter to 95.0 Inches
158. Set tank tilt to 0.00 inches
159. Set Thermal Coefficient to 0.000450
160. Set Meter Data Present to DISABLED
161. Set Delivery Delay [min] to 1
162. Set Gross Test Fail to ENABLED
163. Set Periodic Test Fail to ENABLED
164. Set Annual test Fail to DISABLED
165. Set GOST Volume Correction to DISABLED
166. Press checkmark to save any changes
167. Setup Tank Limits for Tank 2
168. Set Max Volume (Label Vol.) [gal] to 14272
169. Set High Product (% of max. vol.) to 95%
170. Set Delivery Overfill to (% of max. vol.) 90%
171. Set Delivery Limit (% of Full vol.) to 83%
172. Set Low Product [gal] to 11400
173. Set High Water Warning [in.] to 1.5
174. Set High Water Alarm [in.] to 2.0
175. Set Water Alarm Filter Level to OFF
176. Set Water Alarm Filter Delay to 30 S
177. Set Leak Alarm Limit [gal] to 99
178. Set Sudden Loss Limit [gal] to 100
179. Set Fuel Temperature Low Limit [DEG F] to -58.0
180. Set Fuel Temperature High Limit to [DEG F] 140.0
181. Press checkmark to save any changes and press Next
182. Set Test Tank Method to CSLD
183. Set Probability of Detection to 95%.
184. Set Climate Factor to MODERATE
185. Set CSLD evaporation compensation to DIABLED
186. Set Stage II Vapor Recover to DISABLED
187. Press checkmark to save any changes and press Next
188. Set up Tank Profile for Tank 2
189. Set Tank Profile to FOUR POINTS
190. Set 71.2 INCHES [gal] to 11473
191. Set 47.5 INCHES [gal] to 7136
192. Set 23.7 INCHES [gal] to 2782
193. Press checkmark to save any changes and press Next
194. Set up Tank charts
195. Press the check box next to entry 2
196. Press the actions menu
197. Select Apply chart check mark
****************************************************Tank 3****************************************************
198. Set up Tank 3
199. Set Tank 3 Configuration to enabled
200. Set tank label to MUR
201. Set product code to 2
202. Set Probe to Probe 3
203. Set Probe offset to 0.00 Inches
204. Set Full volume to 612 GALLONS
205. Set Diameter to 64.0 Inches
206. Set tank tilt to 0.00 inches
207. Set Thermal Coefficient to 0.000720
208. Set Meter Data Present to DISABLED
209. Set Delivery Delay [min] to 1
210. Set Gross Test Fail to ENABLED
211. Set Periodic Test Fail to ENABLED
212. Set Annual test Fail to DISABLED
213. Set GOST Volume Correction to DISABLED
214. Press checkmark to save any changes
215. Setup Tank Limits for Tank 3
216. Set Max Volume (Label Vol.) [gal] to 612
217. Set High Product (% of max. vol.) to 95%
218. Set Delivery Overfill to (% of max. vol.) 90%
219. Set Delivery Limit (% of Full vol.) to 10%
220. Set Low Product [gal] to 200
221. Set High Water Warning [in.] to 1.5
222. Set High Water Alarm [in.] to 2.0
223. Set Water Alarm Filter Level to OFF
224. Set Water Alarm Filter Delay to 30 S
225. Set Leak Alarm Limit [gal] to 99
226. Set Sudden Loss Limit [gal] to 100
227. Set Fuel Temperature Low Limit [DEG F] to -58.0
228. Set Fuel Temperature High Limit to [DEG F] 140.0
229. Press checkmark to save any changes and press Next
230. Set Test Tank Method to CSLD
231. Set Probability of Detection to 95%.
232. Set Climate Factor to MODERATE
233. Set CSLD evaporation compensation to DIABLED
234. Set Stage II Vapor Recover to DISABLED
235. Press checkmark to save any changes and press Next
236. Set up Tank Profile for Tank 3
237. Set Tank Profile to ONE POINT
238. Press checkmark to save any changes and press Next
239. Set up Tank charts
240. Press the check box next to entry 3
241. Press the actions menu
242. Select Apply chart check mark
****************************************************Tank 4****************************************************
243. Set up Tank
244. Set Tank 4 Configuration to enabled
245. Set tank label to DL
246. Set product code to 1
247. Set Probe to Probe 4
248. Set Probe offset to 0.00 Inches
249. Set Full volume to 2005 GALLONS
250. Set Diameter to 64.0 Inches
251. Set tank tilt to 0.00 inches
252. Set Thermal Coefficient to 0.000450
253. Set Meter Data Present to DISABLED
254. Set Delivery Delay [min] to 1
255. Set Gross Test Fail to ENABLED
256. Set Periodic Test Fail to ENABLED
257. Set Annual test Fail to DISABLED
258. Set GOST Volume Correction to DISABLED
259. Press checkmark to save any changes
260. Setup Tank Limits for Tank 4
261. Set Max Volume (Label Vol.) [gal] to 2005
262. Set High Product (% of max. vol.) to 95%
263. Set Delivery Overfill to (% of max. vol.) 90%
264. Set Delivery Limit (% of Full vol.) to 10%
265. Set Low Product [gal] to 800
266. Set High Water Warning [in.] to 1.5
267. Set High Water Alarm [in.] to 2.0
268. Set Water Alarm Filter Level to OFF
269. Set Water Alarm Filter Delay to 30 S
270. Set Leak Alarm Limit [gal] to 99
271. Set Sudden Loss Limit [gal] to 100
272. Set Fuel Temperature Low Limit [DEG F] to -58.0
273. Set Fuel Temperature High Limit to [DEG F] 140.0
274. Press checkmark to save any changes and press Next
275. Set Test Tank Method to CSLD
276. Set Probability of Detection to 95%.
277. Set Climate Factor to MODERATE
278. Set CSLD evaporation compensation to DIABLED
279. Set Stage II Vapor Recover to DISABLED
280. Press checkmark to save any changes and press Next
281. Set up Tank Profile for Tank 4
282. Set Tank Profile to ONE POINT
283. Press checkmark to save any changes and press Next
284. Set up Tank charts
285. Press the check box next to entry 4
286. Press the actions menu
287. Select Apply chart check mark and press Next
**************************************************All Tanks***************************************************
288. On Siphon Sets page, press Next
289. Set up All Tanks
290. Set Ullage Display mode to USER ULLAGE
291. Set User Ullage % to 90
292. Set Print TC Volumes to DISABLED
293. Set Periodic Test Needed Warnings to DISABLED
294. Set Annual Test Needed Warnings to DISABLED
295. Set TC Density to DISABLED
296. Set Stick Height to DISABLED
297. Set Leak Test Report Format to STANDARD
298. Set Leak Test Region to EPA
299. Press checkmark to save any changes and press Next
**********************************************Product Mapping**********************************************
300. Check Product # 1 box
301. Press actions
302. Press edit label
303. Set product 1 label to DIESEL
304. Press checkmark to save any changes
305. Check Product # 2 box
306. Press actions
307. Press edit label
308. Set product 2 label to MUR
309. Press checkmark to save any changes and press Next
310. Check Tank #1, #2, and #4 boxes
311. Press actions
312. Press edit Tank(s) product mapping
313. Select Product 1 DIESEL
314. Press checkmark to save any changes
315. Check Tank #3 box
316. Press actions
317. Press edit Tank(s) product mapping
318. Select Product 2 MUR
319. Press checkmark to save any changes and press Next
**************************************All else, Tasks, Custom Alarms**************************************
320. Set Pumps and Lines > Pumps, Configured to disabled
321. Press checkmark to save any changes and press Next
322. Set Pumps and Lines > Line, Configured to disabled
323. Press checkmark to save any changes and press Next
324. On PLLD, Press Next
325. Set Pumps and Lines > All Lines, Restart on Alarm Clear to DISABLED
326. Set Line Lockout Schedule to DISABLED
327. Press checkmark to save any changes and press Next
328. Set Pumps and Lines > All PLLD, set Line Re-Enable method to Pass Line Test
329. Set Periodic Test Warnings to DISABLED
330. Set Annual Test Warnings to DISABLED
331. Press checkmark to save any changes and press Next
332. On Inventory > Report Times, Set Reporting Interval to DISABLED
333. Press checkmark to save any changes and press Next
334. Set shift close method to TIMED
335. Press checkmark to save any changes and press Next
336. Set delivery method to Standard Automatic
337. Set Tank Idle Delivery to disabled
338. Press checkmark to save any changes and press Next
339. On Address Book menu select next
340. On Automatic Events > AutoXmit, set delay time (Secs) to 5
341. Set repeat time (mins) to 60
342. Set Leak Alarm to DISABLED
343. Set High Water Alarm to DISABLED
344. Set Overfill Alarm to DISABLED
345. Set Low Limit Alarm to DISABLED
346. Set Theft Alarm to DISABLED
347. Set Delivery Start to DISABLED
348. Set Delivery Stop to DISABLED
349. Set External Input On to DISABLED
350. Set External Input Off to DISABLED
351. Set Sensor Fuel Alarm to DISABLED
352. Set Sensor Water Alarm to DISABLED
353. Set Sensor Out Alarm to DISABLED
354. Press checkmark to save any changes and press Next
355. On Autoconnect Tasks menu select next
356. On Device tasks menu select Actions
357. Press Add Task
358. Set Device as RELAY 1: Overfill Alarm
359. In Event submenu, select TANK drop down
360. Check the following boxes
• OVERFILL ALARM
361. Press checkmark to save any changes.
362. On Device tasks menu select Actions
363. Press Add Task
364. Set Device as RELAY 2: Alarm Output
365. In Event submenu, select MAG SENSOR drop down
366. Check the following boxes
• COMMUNICATION ALARM
• SENSOR FAULT ALARM
• FUEL WARNING
• FUEL ALARM
• WATER WARNING
• WATER ALARM
• HIGH LIQUID WARNING
• HIGH LIQUID ALARM
• INSTALL FAULT
367. In Event submenu, select LIQUID SENSOR drop down
368. Check the following boxes
• FUEL ALARM
• SENSOR OUT ALARM
• SHORT ALARM
• WATER ALARM
• LIQUID WARNING
369. In Event submenu, select TANK drop down
370. Check the following boxes
• SETUP DATA WARNING
• LEAK ALARM
• HIGH WATER ALARM
• LOW PRODUCT ALARM
• SUDDEN LOSS ALARM
• PROBE OUT
• HIGH WATER WARNING
• DELIVER NEEDED
• GROSS TEST FAIL
• PERIODIC TEST FAIL
• CSLD IDLE TIME
• CSLD RATE INCR WARNING
371. Press checkmark to save any changes and press Next
372. On Print Tasks Menu Press next
373. On All tasks menu Press Next
374. On Roles Admin menu Press Next
375. On Users Admin Menu, select Actions
376. Press Add User
377. Set Username to WFSM
378. Set Fullname to Fuels
379. Set Role to Administrator
380. Set Email to Wing ORG email
381. Set Password to 450plus
382. Press checkmark to save any changes and press Next
383. On Security menu Set front panel security to DISABLED
384. Set Serial Command Port to DISABLED
385. Set SSH Port to DISABLED
386. Set serial command over ssh to DISABLED
387. Set HTTPS Port (WEB ACESS) to DISABLED
388. Set User admin via web to DISABLED
389. Press checkmark to save any changes and press Next
390. Exit Set up Wizard
391. Select Menu
392. Ensure printer has paper