Attachment 15 - W3 MAF TLS 450 PLUS Programming Instructions.pdf
PDF 123 KB Posted
- Attached to
- Veeder Root TLS 450 PLUS Upgrade Minot AFB, ND Federal contract opportunity
- Solicitation number
- FA4528-25-Q-SP02
About this file
The document is a detailed programming instruction manual for configuring a Veeder Root TLS 450PLUS fuel monitoring system, specifically for a Missile Alert Facility (MAF). The instructions provide step-by-step guidance for system setup, including configuring system settings, probes, sensors, tanks, products, relays, and alarm parameters. The manual covers four tanks with different volumes and products (Diesel and MUR), and includes specific configuration details such as tank profiles, test methods, leak detection settings, and relay configurations.
Key technical aspects include setting up four tanks (TK-115, TK-107, MUR, and DL) with volumes ranging from 612 to 14,272 gallons, configuring probes, setting water and leak alarm parameters, and establishing tank-specific settings like high/low product limits, temperature ranges, and test frequencies. The system is configured with multiple safety and monitoring features disabled, including various alarm types, external inputs, and web access. A user account "WFSM" is created with administrator privileges, and the system is set to use standard leak detection and testing protocols.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W3 MAF 450PLUS Programming Instructions
************************************************System Setup************************************************
1. Once the console has been installed and connect to the power panel boot the console and wait for the home screen to display.
2. Access Workflow Wizard Setup by touching MENU>SETUP> WORKFLOW WIZARD>SETUP
WORKFLOW
3. On the SETUP>DISPLAY>LANGUAGE/UNITS page, set System Language to English
4. Set System Units to US
5. Press checkmark to save any changes and press Next
6. Set Current Date
7. Set Current Time
8. Set Time Zone to (UTC -07:00) US/Mountain
9. Set NPT to DISABLED
10. Press checkmark to save any changes and press Next
11. Set Date Format to mm_dd_yyyy
12. Set Date Separator to /
13. Set Time Format to hh:mm AP
14. Press checkmark to save any changes and press Next
15. Set Decimal Separator to .
16. Set Thousands Separator to None.
17. Press checkmark to save any changes and press Next
18. Header 1: Enter site name (e.g. Alpha – 01)
19. Set Header 2: to street address
20. Set Header 3: to City, State, and ZIP code
21. Set Header 4: to Facility ID from state (e.g. XX-XXXX)
22. Press checkmark to save any changes and press Next
23. Set Alarm Filtering to Disabled
24. Press checkmark to save any changes and press Next
25. Enter System Hostname to TLS450
26. Press checkmark to save any changes and press Next
27. Set IP Default Gateway to Disabled
28. Press checkmark to save any changes and press Next
29. On Internal Modem menu, Press Next
30. On CDIM port menu, Press Next
31. Set TDIM Port configuration to Disabled.
32. Press checkmark to save any changes and press Next
33. Set TLG IFSF to disabled
34. Press checkmark to save any changes and press Next
35. Set Serial Port Configured to DISABLED
36. Press checkmark to save any changes and press Next
37. Ensure Email Relay Enabled is not checked
38. Press checkmark to save any changes and press Next
39. Set Gateway configuration to Disabled
40. Press checkmark to save any changes and press Next
****************************************************Probes****************************************************
41. Set Up Devices Starting with Probe 1
42. Set Configuration to Enabled
43. Assign Address as B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
44. Set Label to TK-115
45. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
46. Set Water Minimum to [IN] to 0
47. Press Checkmark to save any changes
48. Select Probe 2
49. Set Configuration to Enabled
50. Assign Address as B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
51. Set Label to TK-107
52. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
53. Set Water Minimum to [IN] to 0
54. Press Checkmark to save any changes
55. Select Probe 3
56. Set Configuration to Enabled
57. Assign Address as B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
58. Set Label to MUR
59. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
60. Set Water Minimum to [IN] to 0
61. Press Checkmark to save any changes
62. Select Probe 4
63. Set Configuration to Enabled
64. Assign Address as B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
65. Set Label to DL
66. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
67. Set Water Minimum to [IN] to 0
68. Press Checkmark to save any changes
*************************************************Sump Sensor*************************************************
69. Select bottom left Probe icon to open the devices submenu
70. Select Liquid Sensor and begin configuring Liquid Sensor 1
71. Set configuration to enabled
72. Set address to B1.S1.x (x corresponds to the slot the Magnetostrictive probe was installed in)
73. Set label to Sump
74. Set Model to Tri-State (Single Float)
75. Set Category to Piping Sump
76. Press checkmark to save any changes
*********************************************Interstitial Sensors*********************************************
77. Select bottom left MAG Sensor icon to open devices submenu
78. Select Liquid Sensor and begin configuring Liquid Sensor 2
79. Set Configuration to enabled
80. Set address to B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
81. Set label to Interstitial 115
82. Set Model to Tri-State (Single Float)
83. Set Category to Annular Space
84. Press checkmark to save any changes and press Next
****************************************************Relays****************************************************
85. Press bottom left menu to open list of probes
86. Press the bottom left “Probe” icon to open the devices submenu
87. Select Relay
88. Set configuration of Relay 1 to ENABLED
89. Set Address to B1.S7.1
90. Set Label to Overfill Alarm
91. Set type to Standard
92. Set Orientation to Normally Open
93. Press checkmark to save any changes
94. Select Relay 2
95. Set configuration to ENABLED
96. Set Address to B1.S2.5
97. Set Label to Bell
98. Set Type to Standard
99. Set Orientation to Normally Open
100. Press checkmark to save any changes and press Next
****************************************************Tank 1****************************************************
101. Set up Tank 1
102. Set Tank 1 Configuration to enabled
103. Set tank label to TK – 115
104. Set product code to 1
105. Set Probe to Probe 1
106. Set Probe offset to 0.00 Inches
107. Set Full volume to 2319 GALLONS
108. Set Diameter to 72.0 Inches
109. Set tank tilt to 0.00 inches
110. Set Thermal Coefficient to 0.000450
111. Set Meter Data Present to DISABLED
112. Set Delivery Delay [min] to 1
113. Set Gross Test Fail to ENABLED
114. Set Periodic Test Fail to ENABLED
115. Set Annual test Fail to DISABLED
116. Set GOST Volume Correction to DISABLED
117. Press checkmark to save any changes
118. Setup Tank Limits for Tank 1
119. Set Max Volume (Label Vol.) [gal] to 2319
120. Set High Product (% of max. vol.) to 95%
121. Set Delivery Overfill to (% of max. vol.) 90%
122. Set Delivery Limit (% of Full vol.) to 10%
123. Set Low Product [gal] to 800
124. Set High Water Warning [in.] to 1.5
125. Set High Water Alarm [in.] to 2.0
126. Set Water Alarm Filter Level to OFF
127. Set Water Alarm Filter Delay to 30 S
128. Set Leak Alarm Limit [gal] to 99
129. Set Sudden Loss Limit [gal] to 100
130. Set Fuel Temperature Low Limit [DEG F] to -58.0
131. Set Fuel Temperature High Limit to [DEG F] 140.0
132. Press checkmark to save any changes and press Next
133. Set Test Tank Method to SLD – this will change slightly depending if we get CSLD
134. Set Leak Test Rate to 0.2 gph Leak Test
135. Set Periodic Test Type to STANDARD
136. Set Test Frequency to Daily, 01:30 AM
137. Set Duration to 2
138. Set Leak Min Periodic (%full Vol) to 0.0
139. Set Leak Min Annual (%full Vol) to 0.0
140. Set Early Stop to DISABLED
141. Set Tank Test Notify to OFF
142. Set Tank Test Siphon Break to OFF
143. Press checkmark to save any changes and press Next
144. Set up Tank Profile for Tank 1
145. Set Tank Profile to FOUR POINTS
146. Set 54.0 INCHES [gal] to 1965
147. Set 36.0 INCHES [gal] to 1229
148. Set 18.0 INCHES [gal] to 467
149. Press checkmark to save any changes and press Next
150. Set up Tank charts
151. Press the check box next to entry 1
152. Press the actions menu
153. Select Apply chart check mark
****************************************************Tank 2****************************************************
154. Set up Tank 2
155. Set Tank 2 Configuration to enabled
156. Set tank label to TK – 107
157. Set product code to 1
158. Set Probe to Probe 2
159. Set Probe offset to 0.00 Inches
160. Set Full volume to 14272 GALLONS
161. Set Diameter to 95.0 Inches
162. Set tank tilt to 0.00 inches
163. Set Thermal Coefficient to 0.000450
164. Set Meter Data Present to DISABLED
165. Set Delivery Delay [min] to 1
166. Set Gross Test Fail to ENABLED
167. Set Periodic Test Fail to ENABLED
168. Set Annual test Fail to DISABLED
169. Set GOST Volume Correction to DISABLED
170. Press checkmark to save any changes
171. Setup Tank Limits for Tank 2
172. Set Max Volume (Label Vol.) [gal] to 14272
173. Set High Product (% of max. vol.) to 95%
174. Set Delivery Overfill to (% of max. vol.) 90%
175. Set Delivery Limit (% of Full vol.) to 83%
176. Set Low Product [gal] to 11400
177. Set High Water Warning [in.] to 1.5
178. Set High Water Alarm [in.] to 2.0
179. Set Water Alarm Filter Level to OFF
180. Set Water Alarm Filter Delay to 30 S
181. Set Leak Alarm Limit [gal] to 99
182. Set Sudden Loss Limit [gal] to 100
183. Set Fuel Temperature Low Limit [DEG F] to -58.0
184. Set Fuel Temperature High Limit to [DEG F] 140.0
185. Press checkmark to save any changes and press Next
186. Set Test Tank Method to SLD – this will change slightly depending if we get CSLD
187. Set Leak Test Rate to 0.2 gph Leak Test
188. Set Periodic Test Type to STANDARD
189. Set Test Frequency to Daily, 01:30 AM
190. Set Duration to 2
191. Set Leak Min Periodic (%full Vol) to 0.0
192. Set Leak Min Annual (%full Vol) to 0.0
193. Set Early Stop to DISABLED
194. Set Tank Test Notify to OFF
195. Set Tank Test Siphon Break to OFF
196. Press checkmark to save any changes and press Next
197. Set up Tank Profile for Tank 2
198. Set Tank Profile to FOUR POINTS
199. Set 71.2 INCHES [gal] to 11473
200. Set 47.5 INCHES [gal] to 7136
201. Set 23.7 INCHES [gal] to 2782
202. Press checkmark to save any changes and press Next
203. Set up Tank charts
204. Press the check box next to entry 2
205. Press the actions menu
206. Select Apply chart check mark
****************************************************Tank 3****************************************************
207. Set up Tank 3
208. Set Tank 3 Configuration to enabled
209. Set tank label to MUR
210. Set product code to 2
211. Set Probe to Probe 3
212. Set Probe offset to 0.00 Inches
213. Set Full volume to 612 GALLONS
214. Set Diameter to 64.0 Inches
215. Set tank tilt to 0.00 inches
216. Set Thermal Coefficient to 0.000720
217. Set Meter Data Present to DISABLED
218. Set Delivery Delay [min] to 1
219. Set Gross Test Fail to ENABLED
220. Set Periodic Test Fail to ENABLED
221. Set Annual test Fail to DISABLED
222. Set GOST Volume Correction to DISABLED
223. Press checkmark to save any changes
224. Setup Tank Limits for Tank 3
225. Set Max Volume (Label Vol.) [gal] to 612
226. Set High Product (% of max. vol.) to 95%
227. Set Delivery Overfill to (% of max. vol.) 90%
228. Set Delivery Limit (% of Full vol.) to 10%
229. Set Low Product [gal] to 200
230. Set High Water Warning [in.] to 1.5
231. Set High Water Alarm [in.] to 2.0
232. Set Water Alarm Filter Level to OFF
233. Set Water Alarm Filter Delay to 30 S
234. Set Leak Alarm Limit [gal] to 99
235. Set Sudden Loss Limit [gal] to 100
236. Set Fuel Temperature Low Limit [DEG F] to -58.0
237. Set Fuel Temperature High Limit to [DEG F] 140.0
238. Press checkmark to save any changes and press Next
239. Set Test Tank Method to SLD – this will change slightly depending if we get CSLD
240. Set Leak Test Rate to 0.2 gph Leak Test
241. Set Periodic Test Type to STANDARD
242. Set Test Frequency to Daily, 01:30 AM
243. Set Duration to 2
244. Set Leak Min Periodic (%full Vol) to 0.0
245. Set Leak Min Annual (%full Vol) to 0.0
246. Set Early Stop to DISABLED
247. Set Tank Test Notify to OFF
248. Set Tank Test Siphon Break to OFF
249. Press checkmark to save any changes and press Next
250. Set up Tank Profile for Tank 3
251. Set Tank Profile to ONE POINT
252. Press checkmark to save any changes and press Next
253. Set up Tank charts
254. Press the check box next to entry 3
255. Press the actions menu
256. Select Apply chart check mark
****************************************************Tank 4****************************************************
257. Set up Tank
258. Set Tank 4 Configuration to enabled
259. Set tank label to DL
260. Set product code to 1
261. Set Probe to Probe 4
262. Set Probe offset to 0.00 Inches
263. Set Full volume to 2005 GALLONS
264. Set Diameter to 64.0 Inches
265. Set tank tilt to 0.00 inches
266. Set Thermal Coefficient to 0.000450
267. Set Meter Data Present to DISABLED
268. Set Delivery Delay [min] to 1
269. Set Gross Test Fail to ENABLED
270. Set Periodic Test Fail to ENABLED
271. Set Annual test Fail to DISABLED
272. Set GOST Volume Correction to DISABLED
273. Press checkmark to save any changes
274. Setup Tank Limits for Tank 4
275. Set Max Volume (Label Vol.) [gal] to 2005
276. Set High Product (% of max. vol.) to 95%
277. Set Delivery Overfill to (% of max. vol.) 90%
278. Set Delivery Limit (% of Full vol.) to 10%
279. Set Low Product [gal] to 800
280. Set High Water Warning [in.] to 1.5
281. Set High Water Alarm [in.] to 2.0
282. Set Water Alarm Filter Level to OFF
283. Set Water Alarm Filter Delay to 30 S
284. Set Leak Alarm Limit [gal] to 99
285. Set Sudden Loss Limit [gal] to 100
286. Set Fuel Temperature Low Limit [DEG F] to -58.0
287. Set Fuel Temperature High Limit to [DEG F] 140.0
288. Press checkmark to save any changes and press Next
289. Set Test Tank Method to SLD – this will change slightly depending if we get CSLD
290. Set Leak Test Rate to 0.2 gph Leak Test
291. Set Periodic Test Type to STANDARD
292. Set Test Frequency to Daily, 01:30 AM
293. Set Duration to 2
294. Set Leak Min Periodic (%full Vol) to 0.0
295. Set Leak Min Annual (%full Vol) to 0.0
296. Set Early Stop to DISABLED
297. Set Tank Test Notify to OFF
298. Set Tank Test Siphon Break to OFF
299. Press checkmark to save any changes and press Next
300. Set up Tank Profile for Tank 4
301. Set Tank Profile to ONE POINT
302. Press checkmark to save any changes and press Next
303. Set up Tank charts
304. Press the check box next to entry 4
305. Press the actions menu
306. Select Apply chart check mark and press Next
**************************************************All Tanks***************************************************
307. On Siphon Sets page, press Next
308. Set up All Tanks
309. Set Ullage Display mode to USER ULLAGE
310. Set User Ullage % to 90
311. Set Print TC Volumes to DISABLED
312. Set Periodic Test Needed Warnings to DISABLED
313. Set Annual Test Needed Warnings to DISABLED
314. Set TC Density to DISABLED
315. Set Stick Height to DISABLED
316. Set Leak Test Report Format to STANDARD
317. Set Leak Test Region to EPA
318. Press checkmark to save any changes and press Next
**********************************************Product Mapping**********************************************
319. Check Product # 1 box
320. Press actions
321. Press edit label
322. Set product 1 label to DIESEL
323. Press checkmark to save any changes
324. Check Product # 2 box
325. Press actions
326. Press edit label
327. Set product 2 label to MUR
328. Press checkmark to save any changes and press Next
329. Check Tank #1, #2, and #4 boxes
330. Press actions
331. Press edit Tank(s) product mapping
332. Select Product 1 DIESEL
333. Press checkmark to save any changes
334. Check Tank #3 box
335. Press actions
336. Press edit Tank(s) product mapping
337. Select Product 2 MUR
338. Press checkmark to save any changes and press Next
**************************************All else, Tasks, Custom Alarms**************************************
339. Set Pumps and Lines > Pumps, Configured to disabled
340. Press checkmark to save any changes and press Next
341. Set Pumps and Lines > Line, Configured to disabled
342. Press checkmark to save any changes and press Next
343. On PLLD, Press Next
344. Set Pumps and Lines > All Lines, Restart on Alarm Clear to DISABLED
345. Set Line Lockout Schedule to DISABLED
346. Press checkmark to save any changes and press Next
347. Set Pumps and Lines > All PLLD, set Line Re-Enable method to Pass Line Test
348. Set Periodic Test Warnings to DISABLED
349. Set Annual Test Warnings to DISABLED
350. Press checkmark to save any changes and press Next
351. On Inventory > Report Times, Set Reporting Interval to DISABLED
352. Press checkmark to save any changes and press Next
353. Set shift close method to TIMED
354. Press checkmark to save any changes and press Next
355. Set delivery method to Standard Automatic
356. Set Tank Idle Delivery to disabled
357. Press checkmark to save any changes and press Next
358. On Address Book menu select next
359. On Automatic Events > AutoXmit, set delay time (Secs) to 5
360. Set repeat time (mins) to 60
361. Set Leak Alarm to DISABLED
362. Set High Water Alarm to DISABLED
363. Set Overfill Alarm to DISABLED
364. Set Low Limit Alarm to DISABLED
365. Set Theft Alarm to DISABLED
366. Set Delivery Start to DISABLED
367. Set Delivery Stop to DISABLED
368. Set External Input On to DISABLED
369. Set External Input Off to DISABLED
370. Set Sensor Fuel Alarm to DISABLED
371. Set Sensor Water Alarm to DISABLED
372. Set Sensor Out Alarm to DISABLED
373. Press checkmark to save any changes and press Next
374. On Autoconnect Tasks menu select next
375. On Device tasks menu select Actions
376. Press Add Task
377. Set Device as RELAY 1: Overfill Alarm
378. In Event submenu, select TANK drop down
379. Check the following boxes
• OVERFILL ALARM
380. Press checkmark to save any changes.
381. On Device tasks menu select Actions
382. Press Add Task
383. Set Device as RELAY 2: Alarm Output
384. In Event submenu, select LIQUID SENSOR drop down
385. Check the following boxes
• FUEL ALARM
• SENSOR OUT ALARM
• SHORT ALARM
• WATER ALARM
• LIQUID WARNING
386. In Event submenu, select TANK drop down
387. Check the following boxes
• SETUP DATA WARNING
• LEAK ALARM
• HIGH WATER ALARM
• LOW PRODUCT ALARM
• SUDDEN LOSS ALARM
• PROBE OUT
• HIGH WATER WARNING
• DELIVER NEEDED
• GROSS TEST FAIL
• PERIODIC TEST FAIL
• NO CSLD IDLE TIME
• CSLD RATE INCR WARNING
388. Press checkmark to save any changes and press Next
389. On Print Tasks Menu Press next
390. On All tasks menu Press Next
391. On Roles Admin menu Press Next
392. On Users Admin Menu, select Actions
393. Press Add User
394. Set Username to WFSM
395. Set Fullname to Fuels
396. Set Role to Administrator
397. Set Email to Wing ORG email
398. Set Password to 450plus
399. Press checkmark to save any changes and press Next
400. On Security menu Set front panel security to DISABLED
401. Set Serial Command Port to DISABLED
402. Set SSH Port to DISABLED
403. Set serial command over ssh to DISABLED
404. Set HTTPS Port (WEB ACESS) to DISABLED
405. Set User admin via web to DISABLED
406. Press checkmark to save any changes and press Next
407. Exit Set up Wizard
408. Select Menu
409. Ensure printer has paper