Attachment 16 - W3 LF TLS 450 PLUS Programming Instructions.pdf
PDF 87 KB Posted
- Attached to
- Veeder Root TLS 450 PLUS Upgrade Minot AFB, ND Federal contract opportunity
- Solicitation number
- FA4528-25-Q-SP02
About this file
The document is a detailed set of programming instructions for configuring a Veeder Root W3 LF 450PLUS system, specifically for a fuel monitoring installation at Minot Air Force Base. The instructions provide step-by-step guidance for system setup, including configuring system language, date and time settings, device configurations, tank parameters, and user administration. Key configuration steps include setting up a single diesel tank (TK-101), configuring probes, sump and interstitial sensors, relays, and establishing various system parameters such as tank volumes, test methods, and alarm settings.
The programming instructions cover comprehensive system initialization, including disabling various features like NPT, email relays, and web access, and setting up a user account with administrator privileges. Specific technical configurations include setting tank profile to four points, configuring leak test parameters, establishing tank limits (such as high/low product levels and water alarms), and defining relay behaviors for different alarm conditions. The document appears to be part of a specific Air Force contract for upgrading fuel monitoring systems across multiple missile alert and launch facilities, with precise technical specifications for system implementation.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W3 LF 450PLUS Programming Instructions
************************************************System Setup************************************************
1. Once the console has been installed and connected to the power panel boot the console and wait for the home screen to display.
2. Access Workflow Wizard Setup by touching MENU>SETUP> WORKFLOW WIZARD>SETUP
WORKFLOW
3. On the SETUP>DISPLAY>LANGUAGE/UNITS page, set System Language to English
4. Set System Units to US
5. Press checkmark to save any changes and press Next
6. Set Current Date
7. Set Current Time
8. Set Time Zone to (UTC -07:00) US/Mountain
9. Set NPT to DISABLED
10. Press checkmark to save any changes and press Next
11. Set Date Format to mm_dd_yyyy
12. Set Date Separator to /
13. Set Time Format to hh:mm AP
14. Press checkmark to save any changes and press Next
15. Set Decimal Separator to .
16. Set Thousands Separator to None.
17. Press checkmark to save any changes and press Next
18. Header 1: Enter site name (e.g. Alpha – 01)
19. Set Header 2: to street address
20. Set Header 3: to City, State, and ZIP code
21. Set Header 4: to Facility ID from state (e.g. XX-XXXX)
22. Press checkmark to save any changes and press Next
23. Set Alarm Filtering to Disabled
24. Press checkmark to save any changes and press Next
25. Enter System Hostname to TLS450
26. Press checkmark to save any changes and press Next
27. Set IP Default Gateway to Disabled
28. Press checkmark to save any changes and press Next
29. On Internal Modem menu, Press Next
30. On CDIM port menu, Press Next
31. Set TDIM Port configuration to Disabled.
32. Press checkmark to save any changes and press Next
33. Set TLG IFSF to disabled
34. Press checkmark to save any changes and press Next
35. Set Serial Port Configured to DISABLED
36. Press checkmark to save any changes and press Next
37. Ensure Email Relay Enabled is not checked
38. Press checkmark to save any changes and press Next
39. Set Gateway configuration to DISABLED
40. Press checkmark to save any changes and press Next
****************************************************Probe****************************************************
41. Set Up Devices Starting with Probe 1
42. Set Configuration to Enabled
43. Assign Address as B1.S1.x (x corresponds to the slot the Magnetostrictive probe was installed in)
44. Set Label to TK-101
45. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)
46. Set Water Minimum to [IN] to 0
47. Press Checkmark to save any changes
*************************************************Sump Sensor*************************************************
48. Select bottom left Probe icon to open the devices submenu
49. Select Liquid Sensor and begin configuring Liquid Sensor 1
50. Set configuration to enabled
51. Set address to B1.S1.x (x corresponds to the slot the Magnetostrictive probe was installed in)
52. Set label to Sump
53. Set Model to Tri-State (Single Float)
54. Set Category to Piping Sump
55. Press checkmark to save any changes
**********************************************Interstitial Sensor**********************************************
56. Select bottom left MAG Sensor icon to open devices submenu
57. Select Liquid Sensor and begin configuring Liquid Sensor 2
58. Set Configuration to enabled
59. Set address to B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)
60. Set label to Interstitial
61. Set Model to Tri-State (Single Float)
62. Set Category to Annular Space
63. Press checkmark to save any changes and press Next
****************************************************Relays****************************************************
64. Press the bottom left Liquid Sensor icon to open the devices submenu
65. Select Relay
66. Set configuration of Relay 1 to ENABLED
67. Set Address to B1.S7.1 (The relay address B1:S7:1 refers to the single input Power Bay relay)
68. Set Label to Overfill Alarm
69. Set type to Standard
70. Set Orientation to Normally Open
71. Press checkmark to save any changes
72. Select Relay 2 from bottom menu
73. Set configuration of Relay 2 to ENABLED
74. Set Address to B1.S2.5
75. Set Label to Alarm Output
76. Set type to Standard
77. Set Orientation to Normally Closed
78. Press checkmark to save any changes
79. Select Relay 3 from bottom menu
80. Set configuration of Relay 3 to ENABLED
81. Set Address to B1.S2.6
82. Set Label to Closed Loop
83. Set type to Standard
84. Set Orientation to Normally Open
85. Press checkmark to save any changes and press Next
****************************************************Tank 1****************************************************
86. Set up Tank 1
87. Set Tank 1 Configuration to enabled
88. Set tank label to TK – 101
89. Set product code to 1
90. Set Probe to Probe 1
91. Set Probe offset to 0.00 Inches
92. Set Full volume to 3782 GALLONS
93. Set Diameter to 72.0 Inches
94. Set tank tilt to 0.00 inches
95. Set Thermal Coefficient to 0.000450
96. Set Meter Data Present to DISABLED
97. Set Delivery Delay [min] to 1
98. Set Gross Test Fail to ENABLED
99. Set Periodic Test Fail to ENABLED
100. Set Annual test Fail to DISABLED
101. Set GOST Volume Correction to DISABLED
102. Press checkmark to save any changes and press Next
103. Setup Tank Limits for Tank 1
104. Set Max Volume (Label Vol.) [gal] to 3782
105. Set High Product (% of max. vol.) to 95%
106. Set Delivery Overfill to (% of max. vol.) 90%
107. Set Delivery Limit (% of Full vol.) to 10%
108. Set Low Product [gal] to 2600
109. Set High Water Warning [in.] to 2.0
110. Set High Water Alarm [in.] to 3.0
111. Set Water Alarm Filter Level to OFF
112. Set Water Alarm Filter Delay to 30 S
113. Set Leak Alarm Limit [gal] to 99
114. Set Sudden Loss Limit [gal] to 100
115. Set Fuel Temperature Low Limit [DEG F] to -58.0
116. Set Fuel Temperature High Limit to [DEG F] 140.0
117. Press checkmark to save any changes and press Next
118. Set Test Tank Method to SLD – this will change slightly depending if we get CSLD
119. Set Leak Test Rate to 0.2 gph Leak Test
120. Set Periodic Test Type to STANDARD
121. Set Test Frequency to Daily, 01:30 AM
122. Set Duration to 2
123. Set Leak Min Periodic (%full Vol) to 0.0
124. Set Leak Min Annual (%full Vol) to 0.0
125. Set Early Stop to DISABLED
126. Set Tank Test Notify to OFF
127. Set Tank Test Siphon Break to OFF
128. Press checkmark to save any changes and press Next
129. Set up Tank Profile for Tank 1
130. Set Tank Profile to FOUR POINTS
131. Set 54.0 INCHES [gal] to 3184
132. Set 36.0 INCHES [gal] to 2001
133. Set 18.0 INCHES [gal] to 781
134. Press checkmark to save any changes and press Next
135. Set up Tank charts
136. Press the check box next to entry 1
137. Press the actions menu
138. Select Apply chart check mark and press Next
**************************************************All Tanks***************************************************
139. On Siphon Sets page, press Next
140. Set up All Tanks
141. Set Ullage Display mode to USER ULLAGE
142. Set User Ullage % to 90
143. Set Print TC Volumes to DISABLED
144. Set Periodic Test Needed Warnings to DISABLED
145. Set Annual Test Needed Warnings to DISABLED
146. Set TC Density to DISABLED
147. Set Stick Height to DISABLED
148. Set Leak Test Report Format to STANDARD
149. Set Leak Test Region to EPA
150. Press checkmark to save any changes and press Next
**********************************************Product Mapping**********************************************
151. Check Product # 1 box
152. Press actions
153. Press edit label
154. Set product 1 label to DIESEL
155. Press checkmark to save any changes and press Next
156. Check tank # 1 box
157. Press actions
158. Press edit Tank(s) product mapping
159. Select Product 1 DIESEL
**************************************All else, Tasks, Custom Alarms**************************************
160. Press checkmark to save any changes and press Next
161. Set Pumps and Lines > Pumps, Configured to disabled
162. Press checkmark to save any changes and press Next
163. Set Pumps and Lines > Line, Configured to disabled
164. Press checkmark to save any changes and press Next
165. On PLLD, Press Next
166. Set Pumps and Lines > All Lines, Restart on Alarm Clear to DISABLED
167. Set Line Lockout Schedule to disabled
168. Press checkmark to save any changes and press Next
169. Set Pumps and Lines > All PLLD, set Line Re-Enable method to Pass Line Test
170. Set Periodic Test Warnings to DISABLED
171. Set Annual Test Warnings to DISABLED
172. Press checkmark to save any changes and press Next
173. On Inventory > Report Times, Set Reporting Interval to DISABLED
174. Press checkmark to save any changes and press Next
175. Set shift close method to TIMED
176. Press checkmark to save any changes and press Next
177. Set delivery method to Standard Automatic
178. Set Tank Idle Delivery to DISABLED
179. Press checkmark to save any changes and press Next
180. On Address Book menu select next
181. On Automatic Events > AutoXmit, set delay time (Secs) to 5
182. Set repeat time (mins) to 60
183. Set Leak Alarm to DISABLED
184. Set High Water Alarm to DISABLED
185. Set Overfill Alarm to DISABLED
186. Set Low Limit Alarm to DISABLED
187. Set Theft Alarm to DISABLED
188. Set Delivery Start to DISABLED
189. Set Delivery Stop to DISABLED
190. Set External Input On to DISABLED
191. Set External Input Off to DISABLED
192. Set Sensor Fuel Alarm to DISABLED
193. Set Sensor Water Alarm to DISABLED
194. Set Sensor Out Alarm to DISABLED
195. Press checkmark to save any changes and press Next
196. On Autoconnect Tasks menu select next
197. On Device tasks menu select Actions
198. Press Add Task
199. Set Device as RELAY 1: Overfill Alarm
200. In Event submenu, select TANK drop down
201. Check the following boxes
• OVERFILL ALARM
202. Press checkmark to save any changes.
203. On Device tasks menu select Actions
204. Press Add Task
205. Set Device as RELAY 2: Alarm Output
206. In Event submenu, select LIQUID SENSOR drop down
207. Check the following boxes
• FUEL ALARM
• SENSOR OUT ALARM
• SHORT ALARM
• WATER ALARM
• LIQUID WARNING
208. In Event submenu, select TANK drop down
209. Check the following boxes
• SETUP DATA WARNING
• LEAK ALARM
• HIGH WATER ALARM
• LOW PRODUCT ALARM
• SUDDEN LOSS ALARM
• PROBE OUT
• HIGH WATER WARNING
• DELIVER NEEDED
• GROSS TEST FAIL
• PERIODIC TEST FAIL
• NO CSLD IDLE TIME
• CSLD RATE INCR WARNING
210. Press checkmark to save any changes and press Next
211. On Print Tasks menu, Press next
212. On All Tasks menu, Press Next
213. On Roles Admin menu, Press Next
214. On Users Admin, select Actions
215. Press Add User
216. Set Username to WFSM
217. Set Fullname to Fuels
218. Set Role to Administrator
219. Set Email to Wing ORG email
220. Set Password to 450plus
221. Press checkmark to save any changes and press Next
222. On Security menu Set front panel security to DISABLED
223. Set Serial Command Port to DISABLED
224. Set SSH Port to DISABLED
225. Set serial command over SSH to DISABLED
226. Set HTTPS Port (WEB ACESS) to DISABLED
227. Set User admin via web to DISABLED
228. Press checkmark to save any changes and press Next
229. Exit Set up Wizard
230. Ensure printer has paper
File details come from the government source that posted it. Updated .