About this file

The document is a detailed set of programming instructions for configuring a Veeder Root W3 LF 450PLUS system, specifically for a fuel monitoring installation at Minot Air Force Base. The instructions provide step-by-step guidance for system setup, including configuring system language, date and time settings, device configurations, tank parameters, and user administration. Key configuration steps include setting up a single diesel tank (TK-101), configuring probes, sump and interstitial sensors, relays, and establishing various system parameters such as tank volumes, test methods, and alarm settings.

The programming instructions cover comprehensive system initialization, including disabling various features like NPT, email relays, and web access, and setting up a user account with administrator privileges. Specific technical configurations include setting tank profile to four points, configuring leak test parameters, establishing tank limits (such as high/low product levels and water alarms), and defining relay behaviors for different alarm conditions. The document appears to be part of a specific Air Force contract for upgrading fuel monitoring systems across multiple missile alert and launch facilities, with precise technical specifications for system implementation.

View the file

Other files for this federal contract opportunity

Other files attached to Veeder Root TLS 450 PLUS Upgrade Minot AFB, ND, newest first.
File Type Posted
Amendment 6 18 Aug 25 Q A Veeder Root TLS 450 PLUS upgrade.pdf PDF
Amendment 5 13 Aug 25 Q A Veeder Root TLS 450 PLUS upgrade.pdf PDF
Attachment 1 - Veeder Root TLS 450PLUSUpgrade Minot AFB Combo.pdf PDF
Attachment 16 - W3 LF 450PLUS Programming.pdf PDF
13 Aug 25 Q A Veeder Root TLS 450 PLUS upgrade.pdf PDF
Attachment 2 - Amendment 4 Statement of Work Veeder Root - 13 Aug 25.pdf PDF
Attachment 15 - W3 MAF 450 PLUS Programming.pdf PDF
Attachment 1 - AMENDMENT Veeder Root TLS 450 PLUS Upgrade Minot AFB Combo.pdf PDF
Attachment 1 - Veeder Root TLS 450 PLUS Upgrade Minot AFB Combo.pdf PDF
Attachment 15 - W3 MAF TLS 450 PLUS Programming Instructions.pdf PDF
Attachment 11 - LF Wire Routing with GMR 3 Alarm.pdf PDF
Attachment 3 - Quote Sheet Veeder Root TLS 450PLUS.xlsx XLSX spreadsheet
Attachment 17 - Typical LF Site Layout 3 Configurations Typical MAF Site Layout Exterior.pdf PDF
Attachment 19 - Mileage to MAFS.xlsx XLSX spreadsheet
Attachment 18 -Site Security.docx DOCX document
Attachment 14 - LF Electrical Schematic with GMR 5 Alarm.pdf PDF
Attachment 10 - TLS-450 Plus Component Locations.pdf PDF
Attachment 9 - LF EMC Enclosure Layout.pdf PDF
Attachment 8 - Relay 3 for GMR 3 Wiring.pdf PDF
Attachment 2 - Statement of Work Veeder Root.pdf PDF
Attachment 12 - LF Wire Routing with GMR 5 Alarm.pdf PDF
Attachment 7 - Junction and Conduit for Power and Relay Bay.pdf PDF
Attachment 5 - Financial Questionnaire Sheet.pdf PDF
Attachment 20 - WD 2015-6025 and WD 2015-5383.pdf PDF
Attachment 13 - LF Electrical Schematic with GMR 3 Alarm.pdf PDF
Attachment 6 - Past Performance Questionnaire.docx DOCX document
Attachment 4 - Limited Sources Justification - Veeder Root_Redacted.pdf PDF
Attachment 1 - Veeder Root TLS 450 PLUS Upgrade Minot AFB Combo.pdf PDF
Show all 28

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W3 LF 450PLUS Programming Instructions

************************************************System Setup************************************************

1. Once the console has been installed and connected to the power panel boot the console and wait for the home screen to display.

2. Access Workflow Wizard Setup by touching MENU>SETUP> WORKFLOW WIZARD>SETUP

WORKFLOW

3. On the SETUP>DISPLAY>LANGUAGE/UNITS page, set System Language to English

4. Set System Units to US

5. Press checkmark to save any changes and press Next

6. Set Current Date

7. Set Current Time

8. Set Time Zone to (UTC -07:00) US/Mountain

9. Set NPT to DISABLED

10. Press checkmark to save any changes and press Next

11. Set Date Format to mm_dd_yyyy

12. Set Date Separator to /

13. Set Time Format to hh:mm AP

14. Press checkmark to save any changes and press Next

15. Set Decimal Separator to .

16. Set Thousands Separator to None.

17. Press checkmark to save any changes and press Next

18. Header 1: Enter site name (e.g. Alpha – 01)

19. Set Header 2: to street address

20. Set Header 3: to City, State, and ZIP code

21. Set Header 4: to Facility ID from state (e.g. XX-XXXX)

22. Press checkmark to save any changes and press Next

23. Set Alarm Filtering to Disabled

24. Press checkmark to save any changes and press Next

25. Enter System Hostname to TLS450

26. Press checkmark to save any changes and press Next

27. Set IP Default Gateway to Disabled

28. Press checkmark to save any changes and press Next

29. On Internal Modem menu, Press Next

30. On CDIM port menu, Press Next

31. Set TDIM Port configuration to Disabled.

32. Press checkmark to save any changes and press Next

33. Set TLG IFSF to disabled

34. Press checkmark to save any changes and press Next

35. Set Serial Port Configured to DISABLED

36. Press checkmark to save any changes and press Next

37. Ensure Email Relay Enabled is not checked

38. Press checkmark to save any changes and press Next

39. Set Gateway configuration to DISABLED

40. Press checkmark to save any changes and press Next

****************************************************Probe****************************************************

41. Set Up Devices Starting with Probe 1

42. Set Configuration to Enabled

43. Assign Address as B1.S1.x (x corresponds to the slot the Magnetostrictive probe was installed in)

44. Set Label to TK-101

45. Set FLOAT TYPE [IN] to corresponding float kit installed on Magnetostrictive probe (e.g. 2)

46. Set Water Minimum to [IN] to 0

47. Press Checkmark to save any changes

*************************************************Sump Sensor*************************************************

48. Select bottom left Probe icon to open the devices submenu

49. Select Liquid Sensor and begin configuring Liquid Sensor 1

50. Set configuration to enabled

51. Set address to B1.S1.x (x corresponds to the slot the Magnetostrictive probe was installed in)

52. Set label to Sump

53. Set Model to Tri-State (Single Float)

54. Set Category to Piping Sump

55. Press checkmark to save any changes

**********************************************Interstitial Sensor**********************************************

56. Select bottom left MAG Sensor icon to open devices submenu

57. Select Liquid Sensor and begin configuring Liquid Sensor 2

58. Set Configuration to enabled

59. Set address to B1.S1. x (x corresponds to the slot the Magnetostrictive probe was installed in)

60. Set label to Interstitial

61. Set Model to Tri-State (Single Float)

62. Set Category to Annular Space

63. Press checkmark to save any changes and press Next

****************************************************Relays****************************************************

64. Press the bottom left Liquid Sensor icon to open the devices submenu

65. Select Relay

66. Set configuration of Relay 1 to ENABLED

67. Set Address to B1.S7.1 (The relay address B1:S7:1 refers to the single input Power Bay relay)

68. Set Label to Overfill Alarm

69. Set type to Standard

70. Set Orientation to Normally Open

71. Press checkmark to save any changes

72. Select Relay 2 from bottom menu

73. Set configuration of Relay 2 to ENABLED

74. Set Address to B1.S2.5

75. Set Label to Alarm Output

76. Set type to Standard

77. Set Orientation to Normally Closed

78. Press checkmark to save any changes

79. Select Relay 3 from bottom menu

80. Set configuration of Relay 3 to ENABLED

81. Set Address to B1.S2.6

82. Set Label to Closed Loop

83. Set type to Standard

84. Set Orientation to Normally Open

85. Press checkmark to save any changes and press Next

****************************************************Tank 1****************************************************

86. Set up Tank 1

87. Set Tank 1 Configuration to enabled

88. Set tank label to TK – 101

89. Set product code to 1

90. Set Probe to Probe 1

91. Set Probe offset to 0.00 Inches

92. Set Full volume to 3782 GALLONS

93. Set Diameter to 72.0 Inches

94. Set tank tilt to 0.00 inches

95. Set Thermal Coefficient to 0.000450

96. Set Meter Data Present to DISABLED

97. Set Delivery Delay [min] to 1

98. Set Gross Test Fail to ENABLED

99. Set Periodic Test Fail to ENABLED

100. Set Annual test Fail to DISABLED

101. Set GOST Volume Correction to DISABLED

102. Press checkmark to save any changes and press Next

103. Setup Tank Limits for Tank 1

104. Set Max Volume (Label Vol.) [gal] to 3782

105. Set High Product (% of max. vol.) to 95%

106. Set Delivery Overfill to (% of max. vol.) 90%

107. Set Delivery Limit (% of Full vol.) to 10%

108. Set Low Product [gal] to 2600

109. Set High Water Warning [in.] to 2.0

110. Set High Water Alarm [in.] to 3.0

111. Set Water Alarm Filter Level to OFF

112. Set Water Alarm Filter Delay to 30 S

113. Set Leak Alarm Limit [gal] to 99

114. Set Sudden Loss Limit [gal] to 100

115. Set Fuel Temperature Low Limit [DEG F] to -58.0

116. Set Fuel Temperature High Limit to [DEG F] 140.0

117. Press checkmark to save any changes and press Next

118. Set Test Tank Method to SLD – this will change slightly depending if we get CSLD

119. Set Leak Test Rate to 0.2 gph Leak Test

120. Set Periodic Test Type to STANDARD

121. Set Test Frequency to Daily, 01:30 AM

122. Set Duration to 2

123. Set Leak Min Periodic (%full Vol) to 0.0

124. Set Leak Min Annual (%full Vol) to 0.0

125. Set Early Stop to DISABLED

126. Set Tank Test Notify to OFF

127. Set Tank Test Siphon Break to OFF

128. Press checkmark to save any changes and press Next

129. Set up Tank Profile for Tank 1

130. Set Tank Profile to FOUR POINTS

131. Set 54.0 INCHES [gal] to 3184

132. Set 36.0 INCHES [gal] to 2001

133. Set 18.0 INCHES [gal] to 781

134. Press checkmark to save any changes and press Next

135. Set up Tank charts

136. Press the check box next to entry 1

137. Press the actions menu

138. Select Apply chart check mark and press Next

**************************************************All Tanks***************************************************

139. On Siphon Sets page, press Next

140. Set up All Tanks

141. Set Ullage Display mode to USER ULLAGE

142. Set User Ullage % to 90

143. Set Print TC Volumes to DISABLED

144. Set Periodic Test Needed Warnings to DISABLED

145. Set Annual Test Needed Warnings to DISABLED

146. Set TC Density to DISABLED

147. Set Stick Height to DISABLED

148. Set Leak Test Report Format to STANDARD

149. Set Leak Test Region to EPA

150. Press checkmark to save any changes and press Next

**********************************************Product Mapping**********************************************

151. Check Product # 1 box

152. Press actions

153. Press edit label

154. Set product 1 label to DIESEL

155. Press checkmark to save any changes and press Next

156. Check tank # 1 box

157. Press actions

158. Press edit Tank(s) product mapping

159. Select Product 1 DIESEL

**************************************All else, Tasks, Custom Alarms**************************************

160. Press checkmark to save any changes and press Next

161. Set Pumps and Lines > Pumps, Configured to disabled

162. Press checkmark to save any changes and press Next

163. Set Pumps and Lines > Line, Configured to disabled

164. Press checkmark to save any changes and press Next

165. On PLLD, Press Next

166. Set Pumps and Lines > All Lines, Restart on Alarm Clear to DISABLED

167. Set Line Lockout Schedule to disabled

168. Press checkmark to save any changes and press Next

169. Set Pumps and Lines > All PLLD, set Line Re-Enable method to Pass Line Test

170. Set Periodic Test Warnings to DISABLED

171. Set Annual Test Warnings to DISABLED

172. Press checkmark to save any changes and press Next

173. On Inventory > Report Times, Set Reporting Interval to DISABLED

174. Press checkmark to save any changes and press Next

175. Set shift close method to TIMED

176. Press checkmark to save any changes and press Next

177. Set delivery method to Standard Automatic

178. Set Tank Idle Delivery to DISABLED

179. Press checkmark to save any changes and press Next

180. On Address Book menu select next

181. On Automatic Events > AutoXmit, set delay time (Secs) to 5

182. Set repeat time (mins) to 60

183. Set Leak Alarm to DISABLED

184. Set High Water Alarm to DISABLED

185. Set Overfill Alarm to DISABLED

186. Set Low Limit Alarm to DISABLED

187. Set Theft Alarm to DISABLED

188. Set Delivery Start to DISABLED

189. Set Delivery Stop to DISABLED

190. Set External Input On to DISABLED

191. Set External Input Off to DISABLED

192. Set Sensor Fuel Alarm to DISABLED

193. Set Sensor Water Alarm to DISABLED

194. Set Sensor Out Alarm to DISABLED

195. Press checkmark to save any changes and press Next

196. On Autoconnect Tasks menu select next

197. On Device tasks menu select Actions

198. Press Add Task

199. Set Device as RELAY 1: Overfill Alarm

200. In Event submenu, select TANK drop down

201. Check the following boxes

• OVERFILL ALARM

202. Press checkmark to save any changes.

203. On Device tasks menu select Actions

204. Press Add Task

205. Set Device as RELAY 2: Alarm Output

206. In Event submenu, select LIQUID SENSOR drop down

207. Check the following boxes

• FUEL ALARM

• SENSOR OUT ALARM

• SHORT ALARM

• WATER ALARM

• LIQUID WARNING

208. In Event submenu, select TANK drop down

209. Check the following boxes

• SETUP DATA WARNING

• LEAK ALARM

• HIGH WATER ALARM

• LOW PRODUCT ALARM

• SUDDEN LOSS ALARM

• PROBE OUT

• HIGH WATER WARNING

• DELIVER NEEDED

• GROSS TEST FAIL

• PERIODIC TEST FAIL

• NO CSLD IDLE TIME

• CSLD RATE INCR WARNING

210. Press checkmark to save any changes and press Next

211. On Print Tasks menu, Press next

212. On All Tasks menu, Press Next

213. On Roles Admin menu, Press Next

214. On Users Admin, select Actions

215. Press Add User

216. Set Username to WFSM

217. Set Fullname to Fuels

218. Set Role to Administrator

219. Set Email to Wing ORG email

220. Set Password to 450plus

221. Press checkmark to save any changes and press Next

222. On Security menu Set front panel security to DISABLED

223. Set Serial Command Port to DISABLED

224. Set SSH Port to DISABLED

225. Set serial command over SSH to DISABLED

226. Set HTTPS Port (WEB ACESS) to DISABLED

227. Set User admin via web to DISABLED

228. Press checkmark to save any changes and press Next

229. Exit Set up Wizard

230. Ensure printer has paper