Exhibit B4- Section 16450 Grounding and Bonding.pdf
PDF 107 KB Posted
- Solicitation number
- 375108-CD
About this file
This technical specification section details grounding and bonding requirements for a 15kV cable installation project between P-F3 and P-F4. The document specifies technical standards for grounding systems, including copper grounding conductors, copper-clad steel ground rods (3/4" diameter by 120 inches), and exothermic-welded connections. Key installation requirements include routing conductors along the shortest paths, protecting grounding electrode conductors from physical damage, and installing ground rods in manholes, handholes, and pad-mounted switches.
The specification mandates rigorous quality control, including ground resistance testing using the fall-of-potential method per IEEE 81. Testing requirements specify maximum ground resistance of 5 ohms for pad-mounted switching equipment and 10 ohms for manhole grounds. The document also requires comprehensive documentation of ground rod locations, test results, and environmental conditions. Post-installation requirements include restoring surface features and vegetation disturbed during the work, ensuring the site is returned to its original condition.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GROUNDING AND BONDING 29 JANUARY 2020 16450-1
P-F3 TO P-F4 15KV CABLE INSTALLATION 3-7-103B
SECTION 16450 - GROUNDING AND BONDING
PART 1 - GENERAL
1.01 SECTION INCLUDES
A. Equipment grounding system B. Grounding electrode system
1.02 QUALITY ASSURANCE
A. Testing Agency Qualifications: Testing agency as defined by OSHA in 29 CFR
1910.7 or a member company of the International Electrical Testing Association and that is acceptable to authorities having jurisdiction.
B. Testing Agency's Field Supervisor: Person currently certified by the International Electrical Testing Association to supervise on-site testing specified in Part 3.
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
D. Comply with UL 467 Grounding and Bonding Equipment.
E. Comply with NFPA 70; for medium-voltage underground construction, comply with IEEE/ANSI C2 National Electrical Safety Code (NESC).
1.03 REFERENCES
A. NFPA 70 – National Electrical Code (NEC)
1.04 SUBMITTALS
A. Submit shop drawings under provisions of Section 16010
B. Product Data: For the following:
1. Ground rods.
C. Field Test Reports: Submit written test reports to include the following:
1. Test procedures used.
2. Test results that comply with requirements.
3. Results of failed tests and corrective action taken to achieve test results that comply with requirements.
1.05 SUMMARY
A. This section includes grounding of electrical systems and equipment. Grounding requirements specified in this Section may be supplemented by special requirements of systems described in other Sections.
GROUNDING AND BONDING 29 JANUARY 2020 16450-2
P-F3 TO P-F4 15KV CABLE INSTALLATION 3-7-103B
PART 2 - PRODUCTS
2.01 GROUNDING CONDUCTORS
A. Material: Copper.
B. Grounding Electrode Conductors: Stranded cable.
C. Underground Conductors: Bare, tinned, stranded, unless otherwise indicated.
2.02 CONNECTOR PRODUCTS
A. Comply with UL 467; listed for use for specific types, sizes, and combinations of conductors and connected items.
B. Connectors: Exothermic-welded type, in kit form, and selected per manufacturer’s written instructions.
2.03 GROUNDING ELECTRODES
A. Ground Rods: Copper-clad steel.
1. Size: 3/4" in diameter by 120 inches per section.
PART 3 - EXECUTION
3.01 CONNECTIONS
A. General: Make connections so galvanic action or electrolysis possibility is minimized. Select connectors, connection hardware, conductors, and connection methods so metals in direct contact will be galvanically compatible.
1. Use electroplated or hot-tin-coated materials to ensure high conductivity and to make contact points closer to order of galvanic series.
2. Make connections with clean, bare metal at points of contact.
B. Exothermic-Welded Connections: Comply with manufacturer's written instructions. Welds that are puffed up or that show convex surfaces indicating improper cleaning are not acceptable.
C. Underground Connections: Exothermic-welded connections
3.02 INSTALLATION
A. Use only copper conductors for both insulated and bare grounding conductors in direct contact with earth, concrete, masonry, crushed stone, and similar materials.
B. Grounding Conductors: Route along shortest and straightest paths possible, unless otherwise indicated. Avoid obstructing access or placing conductors
GROUNDING AND BONDING 29 JANUARY 2020 16450-3
P-F3 TO P-F4 15KV CABLE INSTALLATION 3-7-103B
where they may be subjected to strain, impact, or damage. Each grounding conductor that passes through a below grade wall must be provided with a waterstop.
C. Grounding electrode conductor (GEC) shall be protected from physical damage by rigid polyvinyl chloride conduit (PVC) in exposed locations.
3.03 UNDERGROUND DISTRIBUTION SYSTEM GROUNDING
A. Manholes and Handholes: Install a driven ground rod close to wall and set rod depth so 4 inches will extend above finished floor. If necessary, install ground rod before manhole is placed and provide a No. 1/0 AWG bare, tinned-copper conductor from ground rod into manhole through a waterproof sleeve in manhole wall. Protect ground rods passing through concrete floor with a double wrapping of pressure-sensitive tape or heat-shrunk insulating sleeve from 2 inches above to 6 inches below concrete. Seal floor opening with waterproof, non-shrink grout.
B. Connections to Manhole Components: Connect exposed-metal parts, such as inserts, cable racks, pulling irons, ladders, and cable shields within each manhole or handhole, to ground rod or grounding conductor. Make connections with No. 4 AWG minimum, stranded, hard-drawn copper conductor. Train conductors level or plumb around corners and fasten to manhole walls. Connect to cable armor and cable shields as recommended by manufacturer of splicing and termination kits.
C. Pad-Mounted Switches: Install ground rods and counterpoise circling pad.
Ground pad-mounted equipment and noncurrent-carrying metal items associated with substations by connecting them to underground cable and grounding electrodes. Use tinned-copper conductor not less than No. 500 MCM for counterpoise and for taps to equipment ground pad. Bury counterpoise not less than 18 inches below grade and 6 inches from the foundation. The pad rebar shall be attached to the counterpoise conductor at the four corners.
3.04 FIELD QUALITY CONTROL
A. Inspect grounding and bonding system conductors and connections for tightness and proper installation.
1. Measure ground resistance using suitable ground testing equipment..
2. Testing: Engage a qualified testing agency to perform the following field quality-control testing:
3. Testing: Perform the following field quality-control testing:
a. After installing grounding system but before permanent electrical circuitry has been energized, test for compliance with requirements.
b. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal, and at ground test wells.
GROUNDING AND BONDING 29 JANUARY 2020 16450-4
P-F3 TO P-F4 15KV CABLE INSTALLATION 3-7-103B
Measure ground resistance not less than two full days after the last trace of precipitation, and without the soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance. Perform tests, by the fall-of-potential method according to IEEE 81.
c. Provide drawings locating each ground rod and ground rod assembly and other grounding electrodes, identify each by letter in alphabetical order, and key to the record of tests and observations. Include the number of rods driven and their depth at each location and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results.
d. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect/Engineer promptly and include recommendations to reduce ground resistance.
1) Pad-Mounted Switching Equipment: 5 ohms.
2) Manhole Grounds: 10 ohms.
3.05 GRADING AND PLANTING
A. Restore surface features, including vegetation, at areas disturbed by Work of this Section. Reestablish original grades, unless otherwise indicated. If sod has been removed, replace it as soon as possible after backfilling is completed. Restore areas disturbed by trenching, storing of dirt, cable laying, and other activities to their original condition. Include application of topsoil, fertilizer, lime, seed, sod, sprig, and mulch. Comply with Division 2. Maintain restored surfaces. Restore disturbed paving.
END OF SECTION 16450