UPS SEC-J ATT J.18 Alber Monitor BVM-40 User's Guide.pdf

PDF 908 KB Posted

Attached to
Uninterruptible Power Supply (UPS) equipment, Integrated Logistics and Technical Services
Solicitation number
DTFAAC-17-R-00013
Issued by

About this file

UPS SEC-J ATT J.18 Alber Monitor BVM-40 User's Guide (pdf)

View the file

Other files

File Type Posted
UPS SEC-J ATT J.6 MBP EXH C.xlsx XLSX spreadsheet
UPS SEC-L ATT L.2 Performance.docx DOCX document
UPS SEC-J ATT J.23 SCADA Comp.xls XLS spreadsheet
UPS SEC-J ATT J.22 UPS Comp.xls XLS spreadsheet
UPS SEC-J ATT J.20 UPS Performance.doc DOC document
UPS SEC-G Admin.docx DOCX document
DTFAAC-17-R-00013.pdf PDF
UPS SEC-J ATT J.5 Exhibit B FCB.xlsx XLSX spreadsheet
UPS SEC-J ATT J.2 CDRL.doc DOC document
UPS SEC-D Pkg.doc DOC document
Questions as of 01_31_2018.docx DOCX document
UPS SEC-J ATT J.17 DID M002 ATT 2 Warranty Report.xls XLS spreadsheet
UPS SEC-E Insp.doc DOC document
UPS SEC-J ATT J.12 Load Bank Site Spares EXH I.xlsx XLSX spreadsheet
UPS SEC-J ATT J.10 Load Bank RSPL EXH G.xlsx XLSX spreadsheet
UPS SEC-M Evaluation_02142018.docx DOCX document
UPS SEC-J ATT J.15 CDLS User Guide 103008.pdf PDF
UPS SEC-J ATT J.1a SCADA_02142018.doc DOC document
Q&As11162017.xlsx XLSX spreadsheet
UPS SEC-J ATT J.11 UPS Site Spares EXH H.xlsx XLSX spreadsheet
UPS SEC-J ATT J.21 Spec Comp.xls XLS spreadsheet
UPS Section-M ATT M.2 Log-Train.doc DOC document
UPS SEC-L ATT L.3 Ltr.doc DOC document
UPS SEC-J ATT J.7 Bat Disc EXH D.xlsx XLSX spreadsheet
UPS SEC-L Instructions 02142018.docx DOCX document
UPS SEC-J ATT J.19 BOM CLINs 020142018.xls XLS spreadsheet
UPS SEC-J ATT J.24 SCADA Comp.xls XLS spreadsheet
UPS SEC-J ATT J.4 Exhibit A VRLA_02142018.xlsx XLSX spreadsheet
UPS SEC-J ATT J.3 DID.doc DOC document
UPS SEC-J ATT J.8 Load Bank EXH E_02142018.xlsx XLSX spreadsheet
UPS SEC-L ATT L.1 Expereince.docx DOCX document
DTFAAC-17-R-00013 amendment 0002.pdf PDF
UPS SEC-J ATT J.1 SPEC_02142018.docx DOCX document
UPS SEC-J ATT J.16 DID M002 ATT 1 Cost Report.xls XLS spreadsheet
UPS SEC-J ATT J.13 SECL EXH J.xlsx XLSX spreadsheet
UPS SEC-J ATT J.1b MBP.doc DOC document
DTFAAC-17-R-00013_Amendment 0001.pdf PDF
UPS Section-M ATT M.1 Test.doc DOC document
UPS SEC-J ATT J.14 STD 028C 11-16-2000.pdf PDF
Q_A_11202017.docx DOCX document
DTFAAC-17-R-00013 Questions.xlsx XLSX spreadsheet
QA's from draft solicitation.xlsx XLSX spreadsheet
UPS SEC-J ATT J.9 UPS RSPL EXH F.xlsx XLSX spreadsheet
UPS SEC-L ATT L.3 Ltr.doc DOC document
UPS SEC-E Insp.doc DOC document
UPS SEC-J ATT J.6 MBP EXH C.xlsx XLSX spreadsheet
DTFAAC-17-R-00013_Amendment 0001.pdf PDF
UPS Section-M ATT M.1 Test.doc DOC document
UPS SEC-J ATT J.17 DID M002 ATT 2 Warranty Report.xls XLS spreadsheet
UPS SEC-J ATT J.21 Spec Comp.xls XLS spreadsheet
Show 40 more

Latest 50 of 198 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BVM-40

Battery Voltage Monitor

User's Guide

990 South Rogers Circle, Suite 11 Boca Raton, FL 33487

Tel: (561) 997-2299 Fax: (561) 997-5588 www.alber.com

Battery Voltage Monitor

User's Guide

990 South Rogers Circle, Suite 11 Boca Raton, FL 33487

Tel: (561) 997-2299 Fax: (561) 997-5588 www.alber.com i

1. WARRANTY AND LIMITATION OF LIABILITY

LIMITED WARRANTY. Albércorp warrants that the software product will perform in accordance with the accompanying written materials for a period of ninety (90) days from the date of receipt. Some states and jurisdictions do not allow limitations on duration of an implied warranty, so the above limitation may not apply to you. To the extent allowed by applicable law, implied warranties on the software product, if any, are limited to ninety (90) days.

CUSTOMER REMEDIES. Albércorp's entire liability and your exclusive remedy shall be, at Albércorp's option, either return of the price paid, or replacement of the software product that is returned to Albércorp with proof of purchase. This Limited Warranty is void if failure of the software product has resulted from accident, abuse or misapplication. Any replacement software product will be warranted for the remainder of the original period or thirty (30) days, whichever is longer.

Albércorp shall not be liable for any data or programs stored in or used in conjunction with this software product. Without prejudice to the foregoing generality, Albércorp shall not be liable for the loss or corruption of data or programs stored in or used in conjunction with this or any other software product, nor shall Albércorp be liable for the cost of retrieving or replacing lost or corrupted data.

Albércorp's sole and exclusive liability, for any and all losses and damages arising out of any cause whatsoever, shall in no event exceed the purchase price of the software product purchased.

NO LIABILITY FOR CONSEQUENTIAL DAMAGES. Albércorp shall not in any case be liable for any damages, including special, incidental, indirect, exemplary, collateral or consequential, arising from breach of warranty, breach of contract, negligence or under any other legal theory arising from the warranty herein stated or the purchase of product, including, without limitation, loss of profits, use or goodwill.

Some states and countries do not allow the exclusion or limitation of incidental or consequential damages;

therefore, the above exclusion or limitation may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary state to state and country to country.

2. SOFTWARE LICENSE AGREEMENT

THIS IS A LEGAL AGREEMENT. PLEASE READ BEFORE INSTALLING SOFTWARE.

Any use of this media other than to review this Software License Agreement constitutes your acceptance of and agreement with the terms of this Software License Agreement with respect to the Albércorp Software.

If you do not accept and agree to these terms, you must return the full product with proof of purchase to Albércorp within thirty (30) days for a full refund. Installation or use of this software product constitutes your acceptance of and agreement with the terms of this Software License Agreement.

LICENSORS. All software on this media is licensed to you by Albércorp.

GRANT OF LICENSE. You are granted the right to use the Albércorp Software on a single personal computer. You may copy the software to use with this personal computer to any one hard disk drive of this personal computer and to the memory of this personal computer, provided that you reproduce all copyright and trademark notices, restricted rights legends, and other proprietary markings.

RESTRICTIONS. You may not sublicense, rent or lease the Albércorp Software. You may not reverse engineer, decompile, disassemble, modify, translate or create derivative works of the Software.

LIMITED WARRANTIES AND LIMITATION OF LIABILITY. The limited warranties and limitation of liability in Section 1 of this file apply to, are incorporated in, and are made a part of this Software License Agreement.

ii

EXPORT LAW ASSURANCES. You acknowledge and agree that the Software is subject to restrictions and controls imposed by the United States Export Administration Act (the "Act") and the regulations thereunder. You agree and certify that neither the Software nor any direct product thereof is being or will be acquired, shipped, transferred or exported, directly or indirectly, into any country, or used for any purpose, except as authorized by the Act and the regulations.

GOVERNMENT LICENSEE. If you are acquiring the software on behalf of any unit or agency of the United States Government, the provisions of Section 3 apply to, are incorporated in, and are made a part of this Software License Agreement.

GENERAL. This Software License Agreement will be governed by the laws of the State of Florida, except for that body of law dealing with conflicts of law. Should you have any questions concerning this Software License Agreement, or if you desire to contact Albércorp for any reason, please contact:

Albércorp, 990 South Rogers Circle, Suite 11, Boca Raton, FL 33487, email: alber@alber.com.

3. GOVERNMENT PROVISIONS

The Government acknowledges the representations of the Albércorp software as "Restricted Computer Software" as the term is defined in Clause 52.227-19 of the Federal Acquisition Regulations (FAR) and is "Commercial Computer Software" as that term is defined in Clause 52.227-7013(a)(1) of the Department of Defense Federal Acquisition Regulation Supplement (DFARS). The Government agrees that:

(i) if the software is supplied to the Department of Defense (DOD), the software is classified as "Commercial Computer Software" and the Government is acquiring only "restricted rights" in the software and its documentation as that term is defined in Clause 252.227-7013(c)(1) of the DFARS, and

(ii) if the software is supplied to any unit or agency of the United States Government other than DOD, the Government's rights in the software and its documentation will be as defined in Clause 51.227-19(c)(2) of the FAR.

RESTRICTED RIGHTS LEGEND. Use, duplication, or disclosure by the Government is subject to restrictions as set forth in subparagraph (c)(1)(ii) of the Rights in Technical Data and Computer Software clause at DFARS 252.227-7013.

Albércorp 990 South Rogers Circle, Suite 11, Boca Raton, FL 33487

Information in this document is subject to change without notice.

BVM-40 Battery Voltage Monitor User's Guide, Part Number 4200-043R1.0, Book Revision 1.0

2004 Albércorp, 990 South Rogers Circle, Suite 11, Boca Raton, FL 33487.

This manual may not be copied in whole or in part without express written permission from Albércorp.

Microsoft Windows is a registered trademark of Microsoft Corporation.

Pentium is a registered trademark of Intel Corporation.

Printed in the United States of America.

iii

Table of Contents

1. SAFETY INFORMATION

2. SYSTEM REQUIREMENTS

2.1. Components

2.2. Wiring

2.3. Disconnect Device

2.4. Ventilation

2.5. If You Have Questions

3. GENERAL DESCRIPTION

3.1. Definitions

4. PANEL CONTROLS AND INDICATORS

4.1. Symbols

5. INSTALLING THE BVM

5.1. Mounting the BVM

5.2. Voltage Sense Lead Harness Routing

5.3. Voltage Sense Lead Connections

6. USING THE BVM

6.1. Viewing the Setup Menu

6.2. Setting the Total Jar Number

6.3. Viewing Jar Voltages

7. CALIBRATING THE BVM

7.1. Selecting the Calibration Option

8. PREVENTIVE MAINTENANCE

9. BVM-40 SPECIFICATIONS

Table of Figures

Figure 1. Version Number Screen Figure 2. Summary Screen Figure 3. Setup Menu Screen Figure 4. Total Jars Screen Figure 5. Jar Voltage Screen Figure 6. Calibration Screen

Table of Drawings

General Assembly, BVM-40 ..................................................................................................BDS-362-B945 General Assembly, Cabinet Mounting, BVM-40 ...................................................................BDS-363-A572 Wiring Schematic, BVM-40 to 40 12V Module Battery......................................................BDS-2268-B946 Subassembly, Sense Lead Connection Details, BDS .................................................BDS-120-A373, Rev E Installation Details, Sense Lead Connection Options, BVM-40 ..........................................BDS-1165-A568 Subassembly, Module 1 - 15, Sense Lead Harness, BVM-40 ..................................BDS-1166-A569, Rev A Subassembly, Module 16 - 24, Sense Lead Harness, BVM-40 ................................BDS-1167-A570, Rev A Subassembly, Module 25 - 40, Sense Lead Harness, BVM-40 ...............................BDS-1168- A571, Rev A Cabinet Mounting Template, BVM-40..........................................................................................................– iv

Safety Information

1. Safety Information

• Except as explained in this manual, do not attempt to service Albér equipment yourself.

Opening the equipment may expose you to dangerous voltages. Refer servicing beyond that described in this manual to authorized personnel.

• Do not allow liquids or moisture to get into the equipment. If liquid does get into the equipment, unplug it immediately and contact your nearest authorized service center or Albér directly.

• Ensure equipment is provided adequate ventilation. Do not block equipment ventilation openings.

• Do not exceed equipment voltage or power ratings and capabilities.

• Make sure that equipment is properly grounded.

• Do not let unauthorized persons operate the equipment.

• Do not energize the system or any component with 115VAC or battery voltage until after the installation is complete.

• Use of this product in a manner not specified could compromise the designed-in safety of this product.

• The BVM-40 is designed to connect to systems with jars that have a nominal voltage of 12VDC.

• High voltage or current may be present inside the equipment and on the equipment terminals.

Only qualified personnel should perform the operations described in this manual. Calibration must be performed only by technically qualified persons. Observe electrical safety precautions when removing and installing equipment covers, and when connecting leads and making adjustments.

• Proper installation is essential to the correct functioning of your system. If you have any questions about installation, please contact Albér for assistance.

• This manual describes the general installation and use of the BVM-40 Battery Voltage Monitor. If your system has features or accessories not addressed in this manual, please contact Albér.

System Requirements

2. System Requirements The following are requirements for a typical BVM-40 system.

2.1. Components

Alber BVM-40 Battery Voltage Monitor.

Voltage sense leads.

Alber BVM-40 Battery Voltage Monitor User's Guide, 4200-043 (this manual).

Wiring diagrams for BVM to jar connection (as required).

Tools for installing cabling and connecting the BVM to the jars.

2.2. Wiring

The BVM-40 is designed to connect to jars that have a nominal voltage of 12VDC.

The receptacle for the AC cord from the BVM-40 must have protective earth connection (three prong). Do not defeat the use of the earth connection prong.

2.3. Disconnect Device

The three prong AC cord from the cabinet, which connects to the 115VAC receptacle, is considered the primary disconnect device.

2.4. Ventilation

You must provide adequate ventilation to prevent equipment overheating. Only the top of the BVM has ventilation holes. If mounting the BVM from the top, use the standoffs provided to ensure adequate ventilation. Do not block the ventilation ports, and ensure the equipment is operated within the temperature and humidity ranges described in this manual.

2.5. If You Have Questions

Proper installation is essential to the correct functioning of your system. If you have questions about installation, contact Albér at (561) 997-2299 or fax (561) 997-5588. Request BVM-40 assistance.

General Description

3. General Description The Albér BVM-40 Battery Voltage Monitor helps ensure that jars used in battery backup systems will perform when needed. The BVM continually reads the voltages of up to 40 jars that each have a nominal voltage of 12VDC. An easily readable, backlit LCD (liquid crystal display) screen indicates each jar voltage, minimum, maximum and average jar voltage, and overall string voltage.

Two front panel push buttons are used to light the LCD screen, view readings, set up the unit, and calibrate the unit when necessary. The buttons are either pressed independently or together to enable the various functions. The light on the LCD goes off after about one minute. Pressing the up or down button turns the light back on.

The power switch is on the rear panel. The BVM may be left powered on continuously with no adverse effects.

3.1. Definitions

Jar – The container that holds a cell or group of cells. In this manual, the term jar refers to one 12 volt battery consisting of six cells.

Cell – The basic electrochemical unit that delivers electrical energy. Common usage permits the use of the word battery when referring to a cell, although it is technically incorrect. The nominal voltage of a cell is 2 volts.

Battery – Two or more cells (or jars) connected together electrically.

Panel Controls and Indicators

4. Panel Controls and Indicators This section describes the front and rear panels of the BVM-40. Additional descriptions may appear elsewhere in this manual or related manuals.

Front Panel Indicators LCD Display Screen.................. Displays all functions, including jar voltage, string voltage, setup, and calibration.

Front Panel Connectors None

Front Panel Controls Jar Select switches..................... Two up/down push button switches for illuminating the LCD display, stepping through readings, selecting screens and menu items, and setting parameters.

Rear Panel Indicators None

Rear Panel Connectors DB-37 ........................................ Four DB-37 connectors for connecting the BVM to 40 jars or less for voltage monitoring.

AC Power .................................. AC power cord receptacle with user-replaceable fuse.

BVM Rear Panel Controls Power switch ............................. Rocker switch for BVM AC power on and off.

4.1. Symbols

This symbol, which may appear on equipment panels and cabinets, indicates:

CAUTION. Refer to accompanying documents. Be sure to read and understand the documents that relate to the particular unit. If you do not understand the documentation, stop and contact Albér or an authorized Albér representative.

Installing the BVM

5. Installing the BVM This section describes how to mount the BVM, install the voltage sense leads, and terminate the wires at the BVM and jar ends. The BVM-40 system consists of the BVM-40 unit and cables that connect the unit to the jars being monitored. Refer to the system drawings and verify all components are available before starting installation.

WARNING: Do not energize the BVM or any component with 115VAC or battery voltage until after the installation is complete.

The maximum length for each voltage sense lead is 100 feet (≈30.5 meters) from BVM to jar.

Consider this length and locate the BVM reasonably close to the jars (batteries). Mount the BVM to allow for front and rear panel access. You will need the following tools (or equivalents) to mount and connect the BVM:

• Panduit CT-260 crimper for terminals.

• Flat blade and Phillips screwdrivers for BVM connectors and mounting hardware.

• Drill and 7/32" (0.218") drill bit.

5.1. Mounting the BVM

Normally, mount the BVM directly to the outside top or inside top of the battery cabinet.

Four threaded mounting holes on the BVM top and bottom allow mounting from either side.

Refer to drawing BDS-363-A572 for typical installation.

If you are securing the BVM to the inside top of the cabinet, use the four standoffs provided to ensure adequate ventilation through the top cover. A template drawing (included) identifies where to drill the holes in the battery cabinet. Using the template, drill the holes using a 7/32" (0.218") drill bit, remove any burrs from the drilled holes, and mount the unit with the supplied screws (and standoffs if required).

WARNING: The four mounting screws must not hit the internal components in the BVM-40.

Do not substitute the four screws supplied (#10-32x3/8"). The screws must not go more than 3/8" into the unit. The supplied screws will provide sufficient holding strength for mounting the BVM-40 to surfaces up to 1/8" thick.

After mounting, ensure the ventilation holes on the top of the BVM are not blocked.

5.2. Voltage Sense Lead Harness Routing

The installer normally determines the wire routing. If the BVM is not located directly on or in the battery cabinet, do not route the wires in the same conduit as other wires in the facility.

Use a Panduit (or equivalent) insulated, slotted cable tray with cover to distribute wires to the jars. Suggested cable trays and covers are Panduit E1X1L66 with C1L66, or E5X5L66 with C5L66. When installing the tray along the length of each battery tier, make sure the tray does not interfere with jar replacement and the jars remain accessible for servicing after installation.

Installing the BVM

If the BVM is located on or in the battery cabinet, a cable tray is not needed. Neatly tie wrap the wires in bundles, with appropriate service lengths available.

5.3. Voltage Sense Lead Connections

The supplied wiring harness is for batteries with up to 40 jars. Some batteries will have fewer than 40 jars, and all the sense leads will not be needed. In this case, you should remove and discard the extra leads (see below).

Route each sense lead from the BVM to the jar and cut to length. Before connecting to the jar, install a tab washer or "C" clamp on the battery for making connection; refer to drawing BDS-1165-A568 for details. Also, you must install a current limiting resistor (supplied) at the end of each lead nearest the battery; refer to BDS-120-A373. Use drawing BDS-2268-B946 for identifying harness assemblies and locating sense leads.

If the battery has fewer than 40 jars, connect the lead that would normally connect to the positive post of the next jar to the negative post of the last jar. For example, if the battery has 32 jars, connect the lead that normally connects to jar 33 positive to the negative post of jar

32. Albér recommends you remove the connector cover and cut off and discard any unused harness leads.

Using the BVM

6. Using the BVM After installation, connect the BVM-40 AC cord to a 115VAC source. To power on the unit, set the rear panel rocker switch to On. The front panel LCD screen lights up and the Version Number and Summary screens appear.

VERSION – 1.0

Figure 1. Version Number Screen

STRING V AVG JAR V

247.8V 12.39V

MAX JAR V MIN JAR V

29:12.41V 05:12.33V

Figure 2. Summary Screen

The light on the LCD goes off after about one minute. Pressing either Jar Select up or down button turns the light back on. The Summary screen displays the following parameters:

String V – The overall voltage (OV) of the string.

Avg Jar V – The average voltage of the jars in the string.

Max Jar V – The maximum jar voltage, in the format: jar number: voltage.

Min Jar V – The minimum jar voltage, in the format: jar number: voltage.

6.1. Viewing the Setup Menu

Use the Setup Menu to set the number of jars and select calibration. At the Summary screen, to display the Setup Menu, press both Jar Select up/down buttons at the same time. The Setup Menu appears.

SETUP MENU

>> TOTAL JARS ( 20 )

CALIBRATION

EXIT

Figure 3. Setup Menu Screen

The >> cursor points to the item ready to be selected. Press the up or down button to move the cursor. To return to the Summary screen, position the cursor at Exit and press both up/down buttons simultaneously.

Using the BVM

6.2. Setting the Total Jar Number

At the Setup Menu screen, to select Total Jars, press the up or down button so the cursor points to Total Jars, then press both buttons simultaneously. The Total Jars screen displays the number of jars selected.

TOTAL JARS

( 20 )

Figure 4. Total Jars Screen

To change the number of jars, press the up or down button. To save and exit, press both buttons at the same time. At the message Save Setting? Yes No, to confirm save, point the cursor to Yes and press both buttons simultaneously. After the message Sending setup data.

Please wait, the Summary screen appears.

6.3. Viewing Jar Voltages

To view voltage readings for each jar, at the Summary screen, press the Jar Select up or down button to display the Jar Voltage screen and step through the readings.

JAR VOLTAGE

JAR 01: 12.39V

Figure 5. Jar Voltage Screen

To advance rapidly through the readings, press and hold either button. To return to the Summary screen, press both buttons at the same time.

Calibrating the BVM

7. Calibrating the BVM Calibration of the BVM-40 is done at the factory. This function is usually not accessed by the user. If the BVM needs calibration, contact Albér.

WARNING: High voltage or current may be present inside the equipment and on the equipment terminals. Calibration must be performed only by technically qualified persons. Observe electrical safety precautions when removing and installing equipment covers, and when connecting leads and making adjustments.

WARNING: Dangerous voltages may be present in the jar/battery area. Only qualified personnel should perform calibration or use the DVM to measure the voltage of Jar 1.

7.1. Selecting the Calibration Option

To calibrate the BVM-40, first use a calibrated DVM to measure the voltage of Jar 1. The BVM power may be on or off when you take the measurement. Write down the value measured.

At the Setup Menu screen, press the up or down button so the cursor points to Calibration, then press both Jar Select buttons simultaneously. The Calibration screen displays A/D Counts and Voltage for Jar 1. The A/D Counts value is used during manufacturing and is not user adjustable.

ADJUST VOLTAGE TO

MATCH JAR 1 VOLTAGE

A/D CNTS VOLTAGE

3963 12.392V

Figure 6. Calibration Screen

To change the BVM displayed voltage to match the measured reading, press the up or down button. To advance rapidly, press and hold the button. To save and exit, press both buttons at the same time. At the message Save Setting? Yes No, to confirm save, point the cursor to Yes and press both buttons simultaneously. After the message Sending calibration data. Please wait, the Summary screen appears.

Preventive Maintenance

8. Preventive Maintenance Visual Inspection - Visually inspect all BVM system components for damaged or frayed power cords and cables, and damaged panels, controls, and connectors. If you detect any damage, remove the equipment from service until the damage is repaired.

WARNING: Before cleaning equipment, ensure the system is disconnected and power to the unit has been shut off. You must disconnect the BVM system components from any DC voltage sources and from any AC power sources.

Cleaning System Components - When necessary, clean the exterior of the BVM using a soft cloth, slightly moistened with water. Do not use commercial or industrial cleaners that may attack the housing. Never expose any system component to water, high humidity or dampness.

Vents - Remove dust from vents using a small brush or hand held vacuum. If vents have dust filters, clean the filters according to manufacturer's instructions.

Sense Leads - Clean the sense leads as required. The acid to which the sense lead clips are exposed during testing should be neutralized often, using a water and baking soda mixture. Brush this mixture onto the sense lead clip, then rinse well with clean, cool tap water. Before cleaning the sense lead clips, ensure the system is disconnected and power to the system has been shut off.

Dry with a clean, soft cloth.

Internal Components - The BVM system has no user-replaceable components. Because high voltage exists in several areas in the unit, only knowledgeable users should remove the cover when required. Failure to comply with this restriction could pose a safety hazard and/or void the system warranty.

WARNING: High voltages exist inside the BVM system components and on the terminals.

Calibration must be performed only by technically qualified persons. Observe electrical safety precautions when removing and installing equipment covers and when connecting leads and making adjustments.

Shipping - Protect the BVM system from bumps and bangs during normal use or storage, and provide protection during shipment between test sites.

Specifications

9. BVM-40 Specifications Viewable Parameters

• Maximum jar voltage.

• Minimum jar voltage.

• Selected jar voltage

• Overall string voltage.

Display

• Backlit LCD, 4 x 20 characters.

Power

• Less than 0.2 amps at 115VAC ±10% 60Hz

Fuses

• One MDL 0.5 Amp, located in the rear panel AC power block.

Inputs

• Up to 40 12VDC jars.

Outputs

• LCD (liquid crystal display).

Reading Accuracy

• ± 0.1% ± 3mv

Control Switches

• Power on/off: Main BVM rocker switch on rear panel.

• Jar Select Two front panel momentary push button switches.

Operating Environment

• Temperature range: 5°C to 40°C (41°F to 104°F)

• Humidity range: 0% to 80% RH (non condensing) at 5°C to 31°C

0% to 50% RH (non condensing) at 32°C to 40°C

• Indoor use only.

• Installation category II

• Pollution degree 2.

Packaging

• 7" width, 3.5" height, 14" depth.

• Weight 7.3 lbs.

Index

A/D counts AC power receptacle average jar voltage battery defined cable cable tray maximum length sense leads calibration A/D counts calibration screen cell defined connectors described controls described current limiting resistor description disconnect device earth ground flame proof resistor grounding the equipment indicators described installation jar defined jar select buttons jar voltage jar voltage screen jars selecting total number viewing voltages

LCD display described

LCD light maintenance maximum jar voltage minimum jar voltage overall voltage power switch power switch described preventive maintenance resistor safety information sense lead cleaning connection connectors described length routing servicing equipment setup menu specifications string voltage summary screen switches described symbols described system requirements total jars screen up/down switches described ventilation voltages viewing wire tray......................................... See cable tray