Drawings-589A4-22-100-BID Set -2-15-2023- Part1-7 pages.pdf

PDF 5 MB Posted

Attached to
Z2DA-- Relocate Physical Medicine and Rehabilitation to the 4th Floor PN: 589A4-22-100
Solicitation number
36C25523R0072
Issued by

About this file

This document package includes architectural drawings and specifications for a construction project to relocate a physical medicine and rehabilitation department to the fourth floor at a Veterans Affairs medical center. The project involves renovating spaces on the third and fourth floors, including demolishing existing walls, ceilings, and fixtures, and installing new mechanical, electrical and plumbing systems. Key areas of work include upgrading patient rooms, treatment spaces, and support areas to meet accessibility standards. The solicitation is issued by the VA Veterans Health Administration VISN 15 for the project located at 800 Hospital Drive in Columbia, Missouri. The procurement number is 589A4-22-100.

View the file

Other files

File Type Posted
36C25523R0072 0004.docx DOCX document
AMENDMENT 3 - Drawings.pdf PDF
AMENDMENT 3 - Specifications.pdf PDF
36C25523R0072 0003.docx DOCX document
Prebid-site visit attendee list.pdf PDF
36C25523R0072 0002.docx DOCX document
589A4-22-100 Volume 2 Specifications- 494 pages.pdf PDF
36C25523R0072 0001.docx DOCX document
Drawings-589A4-22-100-2023-02-15 BID Set- Part5-pages 10.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set -Part4-pages 10.pdf PDF
36C25523R0072.docx DOCX document
Drawings-589A4-22-100-2023-02-15 BID Set - Part12-pages 11.pdf PDF
Drawings-589A4-22-100- 2023-02-15 BID Set-Part2- Pages 6.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set- Part13-pages 1.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set-Part6-pages 6.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set- Part9-pages 8.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set - Part3-pages-12.pdf PDF
Specifications-589A4-22-100-2023-02-15 BID Set - VOL 1- Pages 785.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set-Part8-pages 9.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set-Part11-pages 9.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set-Part10-pages 13.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID set - Part7-pages 9.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

PROJ(D)

PLBG

PLYWD

PREFIN

RAD(R)

RESIL

REINF

REQ'D

SECT

SHWR

SPECS

REFRIG

GALVANIZEDGALVBMRK BENCHMARK

CONCRETE

MASONRY UNIT

CEILINGCLG

CLR

CMU

COL

CLO

CLEAR/CLEARANCE

COLUMN

CLOSET

CAB

CJ

CC

CB

BW

CL

BOC

BRZ

BRK

BO

BRG

BUR

BTM

BS

BUILT-UP ROOF

CENTER TO CENTER

CHALKBOARD

BOTTOM OF WALL

CENTER LINE

CONTROL JOINT/

CONSTRUCTION JOINT

CABINET

BACK OF CURB

BOTH SIDES

BOTTOM OF

BRONZE

BRICK

BEARING

BOTTOM

FOUNDATION

FLOOR DRAIN

FIRE EXTINGUISHER

FIRE

EXTINGUISHER

CABINET

FE

FEC

FDN

FD

EAST

EACH

EQUIPMENT

EXPOSED

EACH WAY

EXISTING

ELECTRICAL

EXTERIOR INSULATION

FINISH SYSTEM

ELEVATION/ELEVATOR

EXPANSION JOINT

EXISTING GRADE

ELECTRICAL CONTRACTOR

EXTERIOR

ETHYLENE PROPYLENE

DIENE TERPOLYMER

ELEV

EQUIP

EW

EPDM

EXP

EXIST

EXT

E

EA

EC

EG

EIFS

EJ

ELEC

INSULATION

INTERIOR

INSIDE DIAMETER

INSUL

IN(")

INT

ID

INCH

GRAB BAR

GENERAL CONTRACTOR

GYPSUM

GLASS/GLAZING

HOLLOW METAL

HIGH PRESSURE

DECORATIVE LAMINATE

HORIZONTAL

HARDWARE

HARDWOOD

HOSE BIB

HOT WATER

HEATING, VENTILATING

& AIR CONDITIONING

HDWR

HM

HORZ

HT

HPDL

HVAC

HW

HEIGHT

GB

GL

GRD

GYP

GC

HDWD

HB

GRADE

PART

PLAS

OVHD

PARTITION

PLASTER

OVERHEAD

SRT

SS

SQ

MISCELANEOUS

MASONRY OPENING

NOT IN CONTRACT

NOT APPLICABLE

OUTSIDE DIAMETER

NUMBERNO(#)

NTS

OC

OA

NOM

OFF

OPNG

OD

ON CENTER

OVERALL

NOMINAL

NOT TO SCALE

OFFICE

OPENING

MISC

N

MO

MULL

MTL

NIC

NA

NORTH

MULLION

METAL

SHT

SF

SB

SND

SIM

S

RM

ROW

RO

SAT

SAN

ARCHITECT/

ARCHITECTURAL

AB ANCHOR BOLT

APPROX

BLDG

BD

ARCH

BM

BLK

ADJ

AFF

AC

ACCU

ALUM

ANOD

ALT

APPROXIMATE

BLOCK/BLOCKING

AT

BOARD

BEAM

BUILDING

AIR COOLED

CONDENSING UNIT

ABOVE FINISHED FLOOR

ADJUSTABLE

ALTERNATE

ANODIZED

ACOUSTICAL

ALUMINUM

A/C AIR CONDITIONING

PLUS OR MINUS

CONSTRUCTIONCONST

COURSE

CERAMIC TILE

CONTINUOUS

CARPET

CORRIDOR

DIAMETER

DOOR

DOWN

DITTO

DIMENSION

DOUBLE

DRINKING FOUNTAIN

DETAIL

DRAWING

DOWNSPOUT

DIA

DR

DS

DN

DO

DIM

DTL

DWG

CRS

CT

CONT

CORR

CPT

DBL

DF

CONFERENCE

CONCRETE

CONF

CONC

FINISHFIN

FLUORESENT

FLOW LINE

FOLDING

FIELD VERIFY

FURNACE

FOOTING

FIRE RETARDANT

FOOT SCRAPER

FIBERGLASS

REINFORCED PLASTIC

FV

FT(')

FURR

FURN

FTG

G

GA

FOOT

FURRING

GAS

GUAGE

FRP

FLR

FLDG

FL

FRT

FS

FLUOR

FLOOR

FINISH GRADE

FINISH FLOOR

FG

FF

JOISTJST

LOW VOLUMN CHANGE

MASONRYMAS

MANUF

MATL

MAX

MECH

MEMB

MH

MIN

MIRR

MANUFACTURER

MATERIAL

MECHANICAL

MEMBRANE

MAXIMUM

MINIMUM

MANHOLE

MIRROR

LDR

LF

LAV

LAM

LVC

LOCN

LINEAL FEET

LADDER

LAVATORY

LAMINATE

LOCATION

REF

R

RAG

RD

PT

PR

QT

PTD

JT

JAN JANITOR

JOINT

PL

UNDER CABINET LIGHTREQUIRED

PHYSICAL THERAPY

RESPIRATORY CARE

SURGICAL INTENSIVE CARE UNIT

STUDDED RUBBER TILE

STAINLESS STEEL

SQUARE

SPECIFICATIONS

YD

SUSPENDED

ACOUSTICAL TILE

SIMILAR

SANITARY NAPKIN

DISPENSER

SECTION

SHOWER

SHEET

SQUARE FEET

SPLASH BLOCK

RESILIENT

SOUTH

SANITARY

RIGHT OF WAY

ROUGH OPENING

ROOM

WD

WNDW

WH

WNSCT

WC

WT

WWF

WP

VCT

VWC

VEST

VERT

W

W/

W/O

YARD

WATERPROOFING

/WATERPROOF

WELDED WIRE FABRIC

WATER HEATER

WATER CLOSET

WINDOW

WOOD

WAINSCOT

WEIGHT

VINYL COMPOSITION TILE

VINYL WALL COVERING

VERTICAL

VESTIBULE

WEST

WITH

WITH OUT

RC

SICU

CENTRAL STERILE

LONG TERM CARE

INTENSIVE CARE UNIT

OCCUPATIONAL THERAPY

MAGNETIC RESONANCE IMAGING

POST ANESTHETIC CARE UNIT

MEDICAL INTENSIVE CARE UNIT

LABOR-DELIVERY-RECOVERY-POST PARTUM

OPERATING ROOM

FOR MEDICAL

FACILITIES ONLY

EMERGENCY ROOM

COMPUTED TOMOGRAPHY

STORPLUMBING

PROJECT/(PROJECTED)

REFER/REFERENCE

ROOF DRAIN

RADIUS

RETURN AIR GRILLE

REINFORCING

REFRIGERATOR

RISER

PRESSURE TREATED

PAINTED

QUARRY TILE

PLYWOOD

PREFINISHED

PAIR

TLT

TV

TW

TOC

TPH

TO

TYP

UCL

T&B

T

SUSP

STRUCT

TEL

TB

T&G

PLATE/PLASTIC/

PROPERTY LINE STL

STD

STORAGE

TOILET PAPER HOLDER

TOP OF CURB

TOILET

TELEVISION

TOP OF

TYPICAL

TOP OF WALL

TONGUE & GROOVE

TOP & BOTTOM

STRUCTURE/STRUCTURAL

TREAD

TELEPHONE

TACKBOARD

SUSPENDED

ICU

OR

LDRP

MRI

MICU

LTC

PT

PACU

OT

CS

CT

ER

STEEL

STANDARD

CUT STONE

STEEL

PLYWOOD

FINISH WOOD

CONT WD FRAMING

WOOD BLOCKING

MATERIAL SYMBOLS

LVC FILL

GRANULAR FILL

CONCRETE MASONRY

FACE BRICK

CONCRETE

EARTH

EXISTING CONSTRUCTION

ASPHALT

GLASS

RIGID OR TAPERED

INSULATION, EIFS

BATT INSULATION

GYPSUM BOARD

DRAWING SYMBOLS

95.00

TOC

98.5

TOC

98.5 E

B

NEW ELEVATION

ELEVATION DESCRIPTION

EXISTING CONTOUR

NEW CONTOUR

TEST BORING (SITE PLANS ONLY)

EXISTING ELEVATION

ELEVATION DESCRIPTION

PROPERTY LINE

/1 A101

/1 A101 MATCHLINE

SHT. REFERENCE

ELEVATION DATUM

(SECTIONS, ELEVATIONS ONLY)

BUILDING SECTION

WALL SECTION

DETAIL DRAWING

BUILDING ELEVATION

AI-201

INTERIOR ELEVATION

A100

WINDOW ID TAG

DOOR NUMBER

ROOM NAME

ROOM NAME & NUMBER

PARTITION SYMBOL

1 REVISION TAG

COLUMN LINE GRID

ME100E EQUIPMENT NUMBER

SITE PLAN NOTES

DEMOLITION PLAN NOTES

VICINITY MAP

NO SCALE

PRECAST CONCRETE

WALL PANEL TAG

XXX

AE-101

A-4 ALTERNATE TAG

PT-XX PAINT COLOR TAG

# PLAN NOTES &

ROOF PLAN NOTES

PROJECT

LOCATION

AE-201

AE-301

AE-310

N

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

A

B

C

D on e e ig ht h in ch o ne fo ot on e q ua rt er i nc h th re e e ig ht hs o ne f oo t on e h al f ne f oo t th re e q ua rt er s on e in ch on e a nd on e h al f in ch es o ne f oo t th re e in es ne f oo t

1 2 3 4 5 6

A

B

C

D

1 2 3 4 5 6

VA FORM 08-6231

Office of Construction and Facilities Management

Department of Veterans AffairsDwg.

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

CONSULTANTS: ARCHITECT/ENGINEERS:

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

GI001

TITLE SHEET

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

RELOCATE PHYSICAL MEDICINE & REHAB. TO THE 4TH FLOOR

HARRY S. TRUMAN MEMORIAL VETERANS' HOSPITAL

DEPT OF VETERANS AFFAIRS

800 HOSPITAL DRIVE COLUMBIA, MO 65201

BID DOCUMENTS

BID DOCUMENTS

589A4-22-100

IEPJHK

SHEET INDEX

MECHANICAL

M-000 MECHANICAL SYMBOLS AND ABBREVIATIONS

M-001 MECHANICAL PHASING PLANS

MD101 MECHANICAL DEMOLITION PLAN - PIPING - 3RD FLOOR - AREA A

MD102 MECHANICAL DEMOLITION PLAN - 4TH FLOOR - OVERALL

MD103 MECHANICAL DEMOLITION PLAN - PIPING - 4TH FLOOR - AREA A

MD104 MECHANICAL DEMOLITION PLAN - PIPING - 4TH FLOOR - AREA B

MD105 MECHANICAL DEMOLITION PLAN - DUCTWORK - 4TH FLOOR - AREA A

MD106 MECHANICAL DEMOLITION PLAN - DUCTWORK - 4TH FLOOR - AREA B

MD107 MECHANICAL DEMOLITION PLAN - DUCTWORK - LOWER PENTHOUSE

MP101 MECHANICAL NEW WORK PLAN - PIPING - 3RD FLOOR - AREA A

MH102 MECHANICAL NEW WORK PLAN - 4TH FLOOR - OVERALL

MP103 MECHANICAL NEW WORK PLAN - PIPING - 4TH FLOOR - AREA A

MP104 MECHANICAL NEW WORK PLAN - PIPING - 4TH FLOOR - AREA B

MH105 MECHANICAL NEW WORK PLAN - DUCTWORK - 4TH FLOOR - AREA A

MH106 MECHANICAL NEW WORK PLAN - DUCTWORK - 4TH FLOOR - AREA B

MH107 MECHANICAL NEW WORK PLAN - DUCTWORK - LOWER PENTHOUSE

M-501 MECHANICAL DETAILS

M-601 MECHANICAL SCHEDULES

M-701 MECHANICAL CONTROLS SYMBOLS AND ABBREVIATIONS

M-702 MECHANICAL CONTROLS

MECHANICAL: 20

ELECTRICAL

E-000 ELECTRICAL SYMBOLS AND ABBREVIATIONS

ED100 ELECTRICAL DEMOLITION PLAN - LIGHTING - 4TH FLOOR - OVERALL

ED101 ELECTRICAL DEMOLITION PLAN - LIGHTING - 4TH FLOOR - AREA A

ED102 ELECTRICAL DEMOLITION PLAN - LIGHTING - 4TH FLOOR - AREA B

ED103 ELECTRICAL DEMOLITION PLAN - POWER - 4TH FLOOR - OVERALL

ED104 ELECTRICAL DEMOLITION PLAN - POWER - 4TH FLOOR - AREA A

ED105 ELECTRICAL DEMOLITION PLAN - POWER - 4TH FLOOR - AREA B

ED106 ELECTRICAL DEMOLITION PLAN - DATA - 4TH FLOOR - OVERALL

ED107 ELECTRICAL DEMOLITION PLAN - DATA - 4TH FLOOR - AREA A

ED108 ELECTRICAL DEMOLITION PLAN - DATA - 4TH FLOOR - AREA B

EL100 ELECTRICAL REFLECTED CEILING PLAN - LIGHTING - 4TH FLOOR - OVERALL

EL101 ELECTRICAL REFLECTED CEILING PLAN - LIGHTING - 4TH FLOOR - AREA A

EL102 ELECTRICAL REFLECTED CEILING PLAN - LIGHTING - 4TH FLOOR - AREA B

EL601 LIGHTING CONTROL SCHEDULE

EN100 ELECTRICAL FLOOR PLAN - NURSE CALL - 4TH FLOOR - OVERALL

EP100 ELECTRICAL FLOOR PLAN - POWER - 4TH FLOOR - OVERALL

EP101 ELECTRICAL FLOOR PLAN - POWER - 4TH FLOOR - AREA A

EP102 ELECTRICAL FLOOR PLAN - POWER - 4TH FLOOR - AREA B

EP103 ELECTRICAL FLOOR PLAN - POWER - 3RD FLOOR - PARTIAL ROOF

EP400 ELECTRICAL ENLARGED PLAN - 4TH FLOOR - ROOM 414B

EP600 ELECTRICAL PANEL SCHEDULE

EP601 ELECTRICAL PANEL SCHEDULE

EP602 ELECTRICAL PANEL SCHEDULE

EP701 ELECTRICAL ONE-LINE

ET100 ELECTRICAL FLOOR PLAN - DATA - 4TH FLOOR - OVERALL

ET101 ELECTRICAL FLOOR PLAN - DATA - 4TH FLOOR - AREA A

ET102 ELECTRICAL FLOOR PLAN - DATA - 4TH FLOOR - AREA B

ET500 DATA DETAILS

ELECTRICAL: 28

TOTAL SHEETS: 111

SHEET INDEX

GENERAL

GI001 TITLE SHEET

GI002 ABA SHEET

GI103 ABA SHEET

GI104 LIFE SAFETY PLAN - 4TH FLOOR

GI110 PHASING PLAN - 4TH FLOOR

HA100 HAZARDOUS MATERIAL PLANS

GENERAL: 6

ARCHITECTURAL

AD100 DEMOLITION RCP - 3RD FLOOR - ABOVE CEILING

AD101 DEMOLITION PLAN - 4TH FLOOR

AD102 DEMOLITION PLAN - 4TH FLOOR - FLOOR PENETRATIONS

AD111 DEMOLITION RCP - 4TH FLOOR

AE101 FLOOR PLAN - 4TH FLOOR - OVERALL

AE102 FLOOR PLAN - 4TH FLOOR - AREA A

AE103 FLOOR PLAN - 4TH FLOOR - AREA B

AE104 FLOOR PLAN - DIMENSIONS - 4TH FLOOR - AREA A

AE105 FLOOR PLAN - DIMENSIONS - 4TH FLOOR AREA B

AE120 REFLECTED CEILING PLAN - 4TH FLOOR - AREA A

AE121 REFLECTED CEILING PLAN - 4TH FLOOR - AREA B

AE401 ENLARGED PLANS - SLOPED FLOORS

AE501 DETAILS

AE601 SCHEDULES

ARCHITECTURAL: 14

ARCHITECTURAL INTERIORS

AI101 FINISH SCHEDULE

AI102 FINISH PLAN - 4TH FLOOR-AREA A

AI103 FINISH PLAN - 4TH FLOOR-AREA B

AI201 EQUIPMENT SCHEDULE

AI202 EQUIPMENT PLAN - 4TH FLOOR - AREA A

AI203 EQUIPMENT PLAN - 4TH FLOOR - AREA B

AI204 ENLARGED PLANS - EQUIPMENT

AI301 WALL PROTECTION PLAN - 4TH FLOOR - AREA A

AI302 WALL PROTECTION PLAN - 4TH FLOOR - AREA B

AI401 INTERIOR ELEVATIONS

AI402 INTERIOR ELEVATIONS

AI403 INTERIOR ELEVATIONS

AI501 MILLWORK SECTION DETAILS

AI601 SIGNAGE SCHEDULE AND DETAILS

AI602 SIGNAGE PLAN - 4TH FLOOR - AREA A

AI603 SIGNAGE PLAN - 4TH FLOOR - AREA B

ARCHITECTURAL INTERIORS: 16

FIRE SUPPRESSION AND ALARM

F-000 FIRE PROTECTION SYMBOLS AND ABBREVIATIONS

FD101 FIRE PROTECTION DEMOLITION PLAN - 4TH FLOOR - OVERALL

FD201 FIRE ALARM DEMOLITION PLAN - 4TH FLOOR - OVERALL

FD202 FIRE ALARM DEMOLITION PLAN - 4TH FLOOR - AREA A

FD203 FIRE ALARM DEMOLITION PLAN - 4TH FLOOR - AREA B

FX101 FIRE PROTECTION NEW WORK PLAN - 4TH FLOOR - OVERALL

FX501 FIRE PROTECTION - DETAILS

FA000 FIRE ALARM SYMBOLS AND ABBREVIATIONS

FA100 FIRE ALARM FLOOR PLAN - 4TH FLOOR - OVERALL

FA101 FIRE ALARM FLOOR PLAN - 4TH FLOOR - AREA A

FA102 FIRE ALARM FLOOR PLAN - 4TH FLOOR - AREA B

FIRE SUPPRESSION AND ALARM: 11

PLUMBING

P-000 PLUMBING SYMBOLS AND ABBREVIATIONS

PD100 PLUMBING PHASING PLAN - 4TH FLOOR

PD101 PLUMBING DEMOLITION PLAN - 3RD FLOOR - OVERALL

PD102 PLUMBING DEMOLITION PLAN - 3RD FLOOR - AREA A

PD103 PLUMBING DEMOLITION PLAN - 3RD FLOOR - AREA B

PD104 PLUMBING DEMOLITION PLAN - 4TH FLOOR - OVERALL

PD105 PLUMBING DEMOLITION PLAN - 4TH FLOOR - AREA A

PD106 PLUMBING DEMOLITION PLAN - 4TH FLOOR - AREA B

PP101 PLUMBING NEW WORK PLAN - 3RD FLOOR - OVERALL

PP102 PLUMBING NEW WORK PLAN - 3RD FLOOR - AREA A

PP103 PLUMBING NEW WORK PLAN - 3RD FLOOR - AREA B

PP104 PLUMBING NEW WORK PLAN - 4TH FLOOR - OVERALL

PP105 PLUMBING NEW WORK PLAN - 4TH FLOOR - AREA A

PP106 PLUMBING NEW WORK PLAN - 4TH FLOOR - AREA B

P-501 PLUMBING DETAILS

P-601 PLUMBING SCHEDULES

PLUMBING: 16

# Revision Date

Figure 302.2 Carpet Pile Height

Figure 303.2 Vertical Change in Level

1/ 2" m ax

1/ 4" m ax

Figure 302.3 Elongated Openings in Floor or

Ground Surfaces d ir ec ti o n o f tr av el lo n g d im d o m in an t p er p in d ic u la r to

1/2" max dominant direction of travel

Figure 303.3 Beveled Change in Level

1/

1/

1/

1/

Figure 304.3.1.2 Circular Turning Space - Existing

Buildings Size and Overlap

Figure 304.3.1.1 Circular Turning Space - New Buildings Size and Overlap m ax

Overlap of knee and toe clearnce Overlap of knee and toe clearnce

6.

2.

m ax

P er ø 5' - 7" min ø 5' - 0" min

Figure 304.3.2.2 T-Shaped Turning Space New Buildings - Size and Overlap ar m ar m base

Figure 304.3.2.1(A) T-Shaped Turning Space New Buildings - Option 1 ar m ar m base

68" min min

16" min

36" min

16" m in m in36 m in

Figure 304.3.2.1(B) T-Shaped Turning Space New Buildings - Option 2 ar m ar m base

64" min min

11" min

42" min

11" m in m in m in

Figure 304.3.2.1(C) T-Shaped Turning Space New Buildings - Option 3 ar m ar m base

64" min min

12" min

40" min

12" m in m in m in

60" min min

12" min

36" min

12" m in36 m in m in

Figure 305.3.2 Clear Floor or Ground

Space- Existing Buildings

Figure 305.5 Position of Clear Floor or Ground Space

Figure 305.7.1 Maneuvering Clearance in an

Alcove, Forward Approach

Figure 305.7.2 Maneuvering Clearance in an

Alcove, Parallel Approach

(a) forward

(b) parallel

Figure 305.3.1 Clear Floor or Ground Space- New Buildings

52" min m in

48" min m in

30" min m in

48" min m in

36" min

X

4"

60" min

X

5"

Figure 306.2 Toe Clearance

Figure 306.3 Knee Clearance

(b) plan

(a) elevation

9"

6" max m in

17"- 25"

(b) plan

(a) elevation m in

25" max

11" min

8" min m in

Figure 307.2 Limits of Protruding Objects

4" max

X

7"

X

0"

Figure 307.3 Post-Mounted Protruding Objects

(b)(a)

0"

12" max 12" max m ax X > 12"

X > 12" m in

Figure 307.4 Vertical Clearance

M ax

X

Figure 308.3.1 Unobstructed Side Reach

Figure 308.3.2 Unobstructed High Side Reach

Figure 308.2.2 Obstructed High Forward Reach

Figure 308.2.1 Unobstructed

Forward Reach

(a) (b)

(b)(a) m in m ax m ax

20" max m ax

20"- 25" max

10" max m in m ax

10" max 10" - 24" max m ax m ax m ax m ax

B U

IL

D

IN

G

B L

O C

K S

Figure 403.5.2 Clear Width at Turn Existing Buildings

Figure 403.5.1 Clear Width of an Accessible Route

(a) 180 degree turn

(b) 180 degree turn

(Exception)

Figure 403.5.2.1 Clear Width at Turn

(A) 180 degree turn

New Buildings - Option 1 m in

(B) 180 degree turn

New Buildings - Option 2 m in

(C) 180 degree turn

New Building - Option 3 m in

38" min m in

36" min m in

Figure 403.5.3.1 Clear Width At 90-Degree Turn

36" min m in

4" min 28" min

4" m in m in

Figure 403.5.3.2 Clear Width At 90-Degree Turn

Existing Buildings

36" min m in

Figure 403.5.3.1 Clear Width At 90-Degree Turn

Existing Buildings

36" min m in

36" min

X<52"

36" min 42" min

X<52"

42" min 43" min

X<52"

43" min m in m in

42" min

X<48"

42" min 36" min

X<48"

36" min

32" min

36" min

32" min

36" min m ax m in m ax

(a) 90 degree trun

New Building - Option 1

(b) 90 degree trun

New Building - Option 2

(c) 90 degree trun

New Building - Option 3

A C

C E

S S

IB

L

E R

O U

T E

S

Figure 404.2.4.3 Maneuvering Clearance at Recessed Doors and Gates

Figure 404.2.4.2 Maneuvering Clearance at Sliding and Folding Doors

Figure 404.2.4.1 Maneuvering Clearance at Manual Swinging Doors and Gates

Figure 404.2.3 Clear Width of Doorways

Figure 404.2.6 Doors in Series and Gates in Series

(e) hinge approach, pull side

(j) latch approach, push side

(k) latch approach, push side

*48 min if door provided with closer

(i) latch approach, pull side

*54 min if door provided with closer

(h) latch approach, pull side

(f) hinge approach, push side

(g) hinge approach, push side

*if door provided with both closer and latch ** 48 min if both closer and latch provided

(b) front approach, push side

(c) front approach, push side

*if door provided with both closer and latch

(a) front approach, pull side

(a) hinged door

(b) sliding door

(c) folding door

(d) doorways without doors

(a) pull side

(b) push side

(c) push side, door provided with both closer and latch

(a) front approach

(b) side approach

*48 min at front approach

(c) pocket or hinge approach

(d) stop or latch approach

(d) hinge approach, pull side

(a)

(c)

(b)

(d) front approach symbol

90.

32" min

32" min

32" min

36" min

18" min m in m in

*12" min

36" min 60 m in

42" min m in

2" m in

22" min* 12" min m in

24" min

24" min m in m in m in

22" min m in m in

24" min m in

18" min

X >8

X >8 m in m in

12" min

X >8

48" min

48" min

48" min m in

66" min D O

O R

S A

N D

G A

T E

S

Figure 703.6.1 Pictogram Field

MEN not in pictogram field

6" M in

Figure 705.1 Size and Spacing of Truncated Domes base diameter of 0.9"-1.4" top diameter of 50%-65% of the base diameter

(a) elevation (enlarged)

(b) plan

.6 5"

M in

1.6" - 2.4"

1.

6"

.4

Figure 707.6.2 Numeric Key Layout

(a) 12-key ascending

(b) 12-key descending

1 2 3

4 5 6

7 8 9

* 0 #

7 8 9

4 5 6

1 2 3

* 0 #

Figure 703.2.5 Height of Raised

Characters

LIBRARY

5/ 8"

"0.

2"

Figure 703.3.1 Braille Measurement single braille cell blank cell space between words raised dot no raised dot

Figure 703.3.2 Position of Braille

AREA OF

REFUGE

3/ 8" m in

3/ 8" m in

Figure 703.7.2.1 International Symbol of Accessibility

Figure 703.7.2.2 International TTY Symbol

Figure 703.7.2.3 Volume-Controlled Telephone

Figure 703.7.2.4 International Symbol of Access for

Hearing Loss

Figure 704.2.1.1 Parallel Approach to

Telephone

Figure 704.2.1.2 Forward Approach to

Telephone

Figure 703.4.1 Height of Tactile Characters

Above Floor or Ground

Figure 703.4.2 Location of Tactile Signs at Doors

AREA OF

REFUGE

centered on tactile characters

AREA OF

REFUGE

.00

M ax

M ax

M in

M ax

18" Min

M in distance between corresponding dots from one cell directly below distance between dots in the same cell distance between corresponding dots in adjacent cells distance between dots in the same cell base diameter

C O

M M

U N

IC

A

T

IO

N E

L E

M E

N T

S A

N D

F E

A T

U R

E S m in

48" min

Figure 1104.1.1 Clear Floor Space

For type B Unit

(a) front or rear entry

(b) side entry

Figure 802.1.3 Depth of Wheelchair Spaces in

Assembly Area

(a) single space

(b) two spaces

Figure 802.1.2 Width of Wheelchair Spaces in

Assembly Area

36" min 33" min 33" min m in m in

Figure 802.4(a) Depth of Wheelchair Spaces in Assembly Area - New Building m in

W H

E E

L C

H A

IR

S

P A

C E

S

Figure 903.3 Bench Size And Clear Space

42" min

Figure 903.4 Bench Back Support

(a) (b) m in

2" m ax

2 1/2" max

Figure 904.4.1 Sales And Service Counters - Parallel Approach

Figure 904.4.2 Sales And Service Counters - Forward Approach

Elevation

Plan

30" min m ax m ax

Elevation

Plan

36" min m ax m ax

B U

IL

T

IN

E L

E M

E N

T S

1. ALL CONSTRUCTION & RENOVATION SHALL MEET THE ARCHITECTURAL BARRIERS ACT

ACCESSIBILITY STANDARD (ABAAS).

2. SUPPLEMENTAL TO THE (ABAAS), CONSTRUCTION & RENOVATION IN HEALTH FACILITIES OF

THE DEPARTMENT OF VETERAN AFFAIRS (VA) SHALL COMPLY WITH THE VA BARRIER FREE

DESIGN STANDARD: A SUPPLEMENT TO THE ARCHITECTURAL BARRIERS ACT

ACCESSIBILITY STANDARDS (PG-18-13).

GENERAL NOTES

OVERRIDE BY VA BARRIER FREE

DESIGN STANDARD

MINIMUM REQUIREMENTS

• SITES - PARKING SPACES ACCESSIBLE 1% GREATER THAN ABAAS

• SPINAL CORD INJURY/DISORDER (SCI/D) FACILITIES: 0.2 ACCESSIBLE SPACES PER

INPATIENT BED; 0.5 PER LONG-TERM CARE BED; 5.6 PER OUTPATIENT EXAM ROOM.

DEDICATED FOR SCI/D PATIENTS

• HOSPITAL OUTPATIENT FACILITIES 10% OF TOTAL SPACES

• REHABILITATION AND OUTPATIENT

PHYSICAL THERAPY FACILITIES 20% OF TOTAL SPACES

• BUILDING-ACCESSIBLE SEATING, ASSEMBLY AREAS 1% GREATER THAN ABAAS

ACCESSIBLE ROUTE

• WIDTH, MIN. PATIENT CARE AREAS 6'-0"

• WIDTH, MIN. ADMINISTRATIVE AREA 5'-0"

• SLOPE, MAXIMUM (INCLUDING PARKING SPACES) 3%

• MINIMUM GRADIENT OF WALK REQUIRING REST

AREAS EVERY 200' 1:50

• TURNING RADIUS 5'-6"

• TURNING RADIUS, BARIATRIC 6'-0"

FLOOR SURFACES

• CHANGES IN LEVEL NOT PERMITTED ON SCI FLOORS

• CARPET CUSHION OR PADDING NOT PERMITTED

PARKING & PASSENGER LOADING ZONES

• ACCESS AISLE REQUIREMENT FOR ACCESSIBLE

PARKING SPACES 5'-0" EACH SIDE

• PASSENGER LOADING AREA

"COMMUNICATION SYSTEM" FOR ASSISTANCE AT SCI UNITS YES

CURB RAMPS

• WIDTH, MINIMUM 4'-0"

RAMPS

• MAXIMUM SLOPE 1:20

• MAXIMUM LENGTH, WITHIN RANGE OF 1:33 - 1:26 40'

• MAXIMUM LENGTH, WITHIN RANGE OF 1:25 - 1:20 35'

• MINIMUM CLEAR WIDTH 4'-0"

• MINIMUM SIZE LEVEL LANDING,

WHERE DOORS SWING INTO LANDING 6'-0" X 6'-0"

STAIRS

• HANDRAIL HEIGHT 34"

ELEVATOR (PASSENGER)

• MINIMUM WIDTH OF ELEVATOR DOORS 4'-0"

• MINIMUM CAR SIZE 8'-0" X 6'-2" PLATFORM SIZE

• DOUBLE SET OF HANDRAILS YES

WINDOWS

• SILL HEIGHT IN PATIENT BEDROOMS 24" MAXIMUM

DOORS & DOORWAYS

• PATIENT CARE DELIVERY AREAS WITH PATIENT BED,

STRETCHER OR GURNEY ACCESS, MINIMUM WIDTH 4'-0"

WATER CLOSETS - INPATIENT NURSING UNITS

• GRAB BAR CONFIGURATION: DOUBLE SWING-UP BARS FOR ALL PATIENT TOILETS/SHOWER

ROOMS ON NURSING UNITS.

TOILET STALLS

• MINIMUM ACCESSIBLE STALL SIZE 5'-6" X 6'-0"

• MINIMUM SIZE WHEELCHAIR "FRONT-TRANSFER" STALL 3'-6" X 6'-0"

• GRAB BARS REQUIRED IN ALL STALLS

SHOWER STALLS (PATIENT)

• MINIMUM STALL DIMENSIONS 4'-0" X 4'-0"

• GRAB BARS HORIZONTAL PLUS VERTICAL BARS

TOILET ROOMS

• INPATIENT BEDROOM TOILET ROOMS,

MINIMUM WIDTH OF TOILET ROOM ENTRANCE DOORS 48"

CAFETERIAS

• KNEE CLEARANCE, FOR MINIMUM 5% TABLES 2'-3" & 2'-5" FOR AT LEAST 5%

HEALTH CARE FACILITIES

• MEDICAL/SURGICAL NURSING UNITS,

PERCENT OF PATIENT BEDROOMS ACCESSIBLE 100%

• MEDICAL/SURGICAL NURSING UNITS,

PERCENT OF TOILET ROOMS ACCESSIBLE 100%

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig h th c n e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt rs e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e s e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

Department of Veterans Affairs

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

GI002

ABA SHEET

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

IEPJHK

Figure 611.4 Height of Laundry

Compartment Opening

(a) top loading

(b) front loading m ax

Figure 604.2 Water Closet

Location

(a) wheelchair accessible water closets

(b) ambulatory accessible

Water closets

Figure 604.3.1 Size of Clearance at

Water Closets

Figure 604.3.2 (exception) Overlap of Water Closet Clearance in Residential

Dwelling Units

Figure 604.5.1 Side Wall Grab Bar at

Water Closets

Figure 604.5.2 Rear Wall Grab Bar at Water Closets

Figure 1104.11.1.1 Swing-up Grab Bar for Water Closet

Figure 604.7 Dispenser Outlet Location

Figure 604.8.1.2 Wheelchair Accessible Toilet

Compartment Doors

Figure 604.8.1.4 Wheelchair Accessible Toilet Compartment Toe Clearance

Figure 604.8.2 Ambulatory Accessible

Toilet Compartment

Transfer Side comply with section 609.3

(a) adult wall hung water closet

(b) adult floor mounted water closet and children's water closet

(b) elevation children

(a) elevation adult

(c) plan alternate door location

Figure 604.9.2.3 Wheelchair Toilet Compartments Alternate

Wheelchair Toilet Compartment m in

60" min

Figure 604.8.1.1 Size of Wheelchair Accessible Toilet Compartments m in

60" min m in

60" min 42 m in

4" max

4" m ax m in m in

35" - 37"

6" m in

6" min

6" min

9" m in m in6" min

Partition m in m ax7" - 9"

18" min 18" min

15 3/4" 15 3/4"36" min

24" min min

12" 12" max 42" min

54" min

42" m in

39" - 41" m in m in

60" min

18" min m in

60" min

16" - 18"

17" - 19"

P L

U M

B

IN

G E

L E

M E

N T

S A

N D

F A

C

IL

IT

IE

S

Figure 602.2.1 (A) Clear Floor Space at Wheelchair Drinking

Fountains

Figure 602.2.1 (B) Clear Floor Space at Wheelchair Drinking Fountains Primarly for

Children's use Exception

Children Adults

Figure 602.2.3 Wheelchair Drinking

Fountain Spout Height and Location

-4 m ax

-4 m ax

Figure 602.3.2 Standing use Drinking Fountain Spout Height and Location

Figure 602.3.3 Drinking Fountain

Spout Location m ax m ax

Children Adults

5" max (602.2.4)

15" min for Adults

D R

IN

K

IN

G

F O

U N

T A

IN

S

Figure 609.2.2 Grab Bar Non-Circular Cross Section

4" - 4.8" perimeter

2" m ax 2" max

(a) (b)

Figure 607.2 Clearance for Bathtubs

Figure 607.4.1 Grab Bars for Bathtubs with

Permanent Seats

Figure 607.4.2 Grab Bars for Bathtubs with Removable In-Tub Seats

Figure 607.5 Bathtub Control

Location

Figure 610.2 Bathtub Seats back wall head end wallcontrol end wall back wall head end wall control end wall

(b) plan back wall head end wall control end wall back wall head end wall control end wall

(a) removable in-tub seat

(b) permanent seat control end wall

(a) Removable In-Tub seat

(b) Permanent seat

(a) elevation

(b) plan

Length of Bathtub m in

Length of Bathtub 12" min m in

(a) elevation

8"

0"

15" max12" max m in

8"

0" m in

24" min

12" max 24" max m in

15" min15" - 16"

Figure 608.3.1 Grab Bars for Transfer-

Type Showers

Figure 608.3.2 Grab Bars for Standard Roll-In Type Showers

Figure 608.3.3 Grab Bars for Alternate Roll-In Type Showers seat wall control wall back wall back wall side wall side wall back wall back wall front wall side wall side wall side wall side wall

(b) with seat

Figure 608.2.1.2(B) Transfer-Type Shower Compartment Clearances

New Buildings- Option 2 seat wall control wall back wall

52" max m ax

4" max

Figure 608.2.1.2(C) Transfer-Type Shower Compartment Clearances

Existing Buildings- Option 2 seat wall control wall back wall m ax

48" max

18"

4" M ax

6" m ax

6" m ax

6" max 6" max

6" max6" max

6" m ax

Figure 608.5.1 Transfer-Type Shower Compartment Control

Location

Figure 608.5.2 Standard Roll-In Type Shower Compartment

Control Location

Figure 608.5.3 Alternate Roll-In Type Shower Compartment Control Location

Figure 609.3 Spacing of Grab Bars side wall back wall can be located on any wall of shower

(a) without seat

(b) with seat

(a) projecting objects

(b) recessed objects side wall back wall

(a) with seat

(elevation)

(b) with seat

(elevation)

(d) with seat

(plan)

(c) without seat

(plan) side wall side wall side wall side wall back wallback wall front wall front wall

15" max m in m ax m in m ax m ax

Figure 610.3 Extent of Seat

Figure 610.3.1 Rectangular Shower Seat

Figure 610.3.2 L-Shaped Shower Seat seat wall seat wall

(a) size

(b) distance from wall seat wall

(a) rectangular

(b) L-shaped compartment entry compartment entry

15" max m in

1/

2" m ax

3" m ax

3" m ax

(a) without seat

2 1/2" max

15" - 16"

1/

2" m ax

2 1/2" max15" - 16"

22" - 23"

1/

2" m ax m in m ax

27" max m in m ax m in

6" m ax

6" max

" T U

B S

A N

D S

H O

W E

R S

Sanitary Napkin Disposal

Sanitary Napkin Dispenser m ax

Soap Dispenser

Paper Towel Dispenser

T .O

. d is p en se r

O P

G m ax

Baby Changing Station to B

.O m in to h ig h es t p ar t m ax

LINE OF WALL

Coat/Robe Hook

4' -0

A

C C

5' -4

T

Y P

Door Viewer

3' -7

A

C C

5' -0

T

Y P

Mirror Height to g la ss

Fire Extinguisher Cabinet m ax t o t h e h an d le m ax

Fire Extinguisher to t h e h an d le m ax

Hand Dryer

Trash Receptical m ax w o rk s u rf ac e o f w o rk s u rf ac e

T .O

. o p er ab le p o rt io n m ax

Toilet Seat Cover Dispensed

M O

U N

T

IN

G H

E

IG

H T

S

NOTE: MOUNTING HEIGHT OF OPERABLE PARTS OF ANY ACCESSORIES SHALL NOT EXCEED 48".

1. ALL CONSTRUCTION & RENOVATION SHALL MEET THE ARCHITECTURAL BARRIERS ACT

ACCESSIBILITY STANDARD (ABAAS).

2. SUPPLEMENTAL TO THE (ABAAS), CONSTRUCTION & RENOVATION IN HEALTH FACILITIES OF

THE DEPARTMENT OF VETERAN AFFAIRS (VA) SHALL COMPLY WITH THE VA BARRIER FREE

DESIGN STANDARD: A SUPPLEMENT TO THE ARCHITECTURAL BARRIERS ACT

ACCESSIBILITY STANDARDS (PG-18-13).

GENERAL NOTES

OVERRIDE BY VA BARRIER FREE

DESIGN STANDARD

MINIMUM REQUIREMENTS

• SITES - PARKING SPACES ACCESSIBLE 1% GREATER THAN ABAAS

• SPINAL CORD INJURY/DISORDER (SCI/D) FACILITIES: 0.2 ACCESSIBLE SPACES PER

INPATIENT BED; 0.5 PER LONG-TERM CARE BED; 5.6 PER OUTPATIENT EXAM ROOM.

DEDICATED FOR SCI/D PATIENTS

• HOSPITAL OUTPATIENT FACILITIES 10% OF TOTAL SPACES

• REHABILITATION AND OUTPATIENT

PHYSICAL THERAPY FACILITIES 20% OF TOTAL SPACES

• BUILDING-ACCESSIBLE SEATING, ASSEMBLY AREAS 1% GREATER THAN ABAAS

ACCESSIBLE ROUTE

• WIDTH, MIN. PATIENT CARE AREAS 6'-0"

• WIDTH, MIN. ADMINISTRATIVE AREA 5'-0"

• SLOPE, MAXIMUM (INCLUDING PARKING SPACES) 3%

• MINIMUM GRADIENT OF WALK REQUIRING REST

AREAS EVERY 200' 1:50

• TURNING RADIUS 5'-6"

• TURNING RADIUS, BARIATRIC 6'-0"

FLOOR SURFACES

• CHANGES IN LEVEL NOT PERMITTED ON SCI FLOORS

• CARPET CUSHION OR PADDING NOT PERMITTED

PARKING & PASSENGER LOADING ZONES

• ACCESS AISLE REQUIREMENT FOR ACCESSIBLE

PARKING SPACES 5'-0" EACH SIDE

• PASSENGER LOADING AREA

"COMMUNICATION SYSTEM" FOR ASSISTANCE AT SCI UNITS YES

CURB RAMPS

• WIDTH, MINIMUM 4'-0"

RAMPS

• MAXIMUM SLOPE 1:20

• MAXIMUM LENGTH, WITHIN RANGE OF 1:33 - 1:26 40'

• MAXIMUM LENGTH, WITHIN RANGE OF 1:25 - 1:20 35'

• MINIMUM CLEAR WIDTH 4'-0"

• MINIMUM SIZE LEVEL LANDING,

WHERE DOORS SWING INTO LANDING 6'-0" X 6'-0"

STAIRS

• HANDRAIL HEIGHT 34"

ELEVATOR (PASSENGER)

• MINIMUM WIDTH OF ELEVATOR DOORS 4'-0"

• MINIMUM CAR SIZE 8'-0" X 6'-2" PLATFORM SIZE

• DOUBLE SET OF HANDRAILS YES

WINDOWS

• SILL HEIGHT IN PATIENT BEDROOMS 24" MAXIMUM

DOORS & DOORWAYS

• PATIENT CARE DELIVERY AREAS WITH PATIENT BED,

STRETCHER OR GURNEY ACCESS, MINIMUM WIDTH 4'-0"

WATER CLOSETS - INPATIENT NURSING UNITS

• GRAB BAR CONFIGURATION: DOUBLE SWING-UP BARS FOR ALL PATIENT TOILETS/SHOWER

ROOMS ON NURSING UNITS.

TOILET STALLS

• MINIMUM ACCESSIBLE STALL SIZE 5'-6" X 6'-0"

• MINIMUM SIZE WHEELCHAIR "FRONT-TRANSFER" STALL 3'-6" X 6'-0"

• GRAB BARS REQUIRED IN ALL STALLS

SHOWER STALLS (PATIENT)

• MINIMUM STALL DIMENSIONS 4'-0" X 4'-0"

• GRAB BARS HORIZONTAL PLUS VERTICAL BARS

TOILET ROOMS

• INPATIENT BEDROOM TOILET ROOMS,

MINIMUM WIDTH OF TOILET ROOM ENTRANCE DOORS 48"

CAFETERIAS

• KNEE CLEARANCE, FOR MINIMUM 5% TABLES 2'-3" & 2'-5" FOR AT LEAST 5%

HEALTH CARE FACILITIES

• MEDICAL/SURGICAL NURSING UNITS,

PERCENT OF PATIENT BEDROOMS ACCESSIBLE 100%

• MEDICAL/SURGICAL NURSING UNITS,

PERCENT OF TOILET ROOMS ACCESSIBLE 100%

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

Department of Veterans Affairs

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

GI103

ABA SHEET

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

IEPJHK

F E

C

F E

C

F E

C

F E

C

F E

C

FEC

CODE NOTES

1. DRAWING PURPOSE: RENOVATION

2. FACILITY REVIEWED FOR COMPLIANCE WITH THE FOLLOWING

CODES:

2021 NFPA 101 LIFE SAFETY CODE

2021 INTERNATIONAL BUILDING CODE

2021 NATIONAL ELECTRICAL CODE

2021 INTERNATIONAL MECHANICAL CODE

2021 INTERNATIONAL PLUMBING CODE

2021 INTERNATIONAL FIRE CODE

2010 ARCHITECTURAL BARRIERS ACT (ABA)

3. OWNER:

HARRY S TRUMAN MEMORIAL HOSPITAL

800 HOSPITAL DR

COLUMBIA, MO 65201

PH (573) 814-6000

4. DATE DEVELOPED: SEE DATE IN TITLEBLOCK

6. ARCHITECTS SEAL: SEE STAMP IN TITLEBLOCK

7. FIRE SERVICE: CITY OF COLUMBIA FIRE DEPARTMENT

8. INSPECTION: VISN 15 SAFETY OFFICER

9. OCCUPANCY GROUP TYPE:

5. ARCHITECT:

STONE GROUP ARCHITECTS

600 EAST 7TH STREET

SIOUX FALLS, SD 57103

PH (605) 271-1144

RENOVATION: BUSINESS (NFPA); BUSINESS (IBC)

10. CONSTRUCTION TYPE: NFPA TYPE II (222)

11. HEIGHT & AREA LIMITATIONS:

ALLOWABLE AREA: UNLIMITED

HEALTH CARE OCCUPANCY (MOST RESTRICTIVE IN BUILDING)

ALLOWABLE HEIGHT /

STORIES

4 OR MORE

ACTUAL HEIGHT / STORIES 7 OCCUPIABLE STORIES

(UNCHANGED)

BUSINESS OCCUPANCY

ALLOWABLE HEIGHT /

STORIES

N/R

12. MINIMUM CONSTRUCTION REQUIREMENTS (A.8.2.1.2):

CONSTRUCTION

BUSINESS OCCUPANCY

BEARING WALLS:

A. EXTERIOR

B. INTERIOR

C. INT/EXT (ROOF ONLY)

TYPE II

(222)

2 HR

2 HR

1 HR

NON-BEARING WALLS:

A. EXTERIOR

B. INTERIOR

0 HR

NON-

COMBUSTIBLE

COLUMNS:

A. SUPPORT FLOORS

B. SUPPORT ROOF ONLY

2 HR

1 HR

BEAMS/GIRDERS/TRUSSES:

A. EXTERIOR:

B. INTERIOR:

2 HR

1 HR

FLOOR CONSTRUCTION: 2 HR

ROOF CONSTRUCTION: 1 HR

NOTE: ENTIRE FACILITY IS FULLY SPRINKLED

13. ACTIVE FIRE SAFETY FEATURES:

(A) AUTOMATIC SUPPRESSION SYSTEMS:

- SPRINKLER SYSTEM (FULLY SPRINKLED)

- EXHAUST HOOD IN KITCHEN - U.L. 300 COMPLIANT

- AUTOMATIC AIR-HANDLING SHUT-DOWN

(B) FIRE ALARM SYSTEM - SIMPLEX, ADDRESSABLE, AUTO DIAL-UP

(C) GENERATOR POWERED EMERGENCY LIGHTING, GENERATOR

POWERED EXIT LIGHTING.

(D) SMOKE DETECTORS AT ALL CORRIDORS, ALL SMOKE DOORS AND

MISC AREAS AS REQ'D (ALSO IN SOME DUCTS)

(E) PORTABLE EXTINGUISHERS

14. WATER SUPPLY: CITY OF COLUMBIA, MO/UMC (SECONDARY)

TYPE II

(000)

0 HR

0 HR

0 HR

0 HR

NON-

COMBUSTIBLE

0 HR

0 HR

0 HR

0 HR

0 HR

0 HR

14. SEWAGE TREATMENT: CITY OF COLUMBIA, MO

14. ACCESSIBILITY PROVISIONS (VA STANDARDS): ACCESSIBLE ROUTE,

TOILETS, LAVATORIES, SIGNAGE.

17. STORM SEWER: UMC/CITY OF COLUMBIA, MO

LEGEND

BUILDING & LIFE SAFETY REQUIREMENTS

DESCRIPTION

WALL

RATING

NEW

PARTITION KEY NFPA 101-2021

OPENINGS DAMPERS

RATING RFRNC. TYPE RFRNC.

BUILDING SEPARATION:

FIRE BARRIER

90 MIN

OCCUPANCY/AREA SEPARATION

FIRE BARRIER

2 HR

90 MIN

HORIZONTAL EXIT (& REFUGE AREA)

FIRE BARRIER

90 MIN

VERT. OPG. (EXIT ENCLSR/SHAFT)

FIRE BARRIER

(2 HR = 4 OR MORE STORIES)

(1 HR = LESS THAN 4 STORIES)1 HR

2 HR

60 MIN

90 MIN

HAZ./INCIDENTAL USE

FIRE BARRIER

45 MIN

HAZ./INCIDENTAL USE

SMOKE PARTITIONS

(SPRINKLERED)

NR-

RESIST

SMK

NR

SELF OR AUTO

CLOSING

SUBDIVIDING SPACES

SMOKE BARRIER (I-2 OCCUPANCY)

20 MIN

SUITE SEPARATION

SMOKE PARTITION

NR

*NR

SELF OR AUTO

CLOSING

EXIT ACCESS CORRIDORS (I-2)

SMOKE PARTITIONS (SPRINKLERED)

NR-

RESIST

SMK

NR

EXIT ACCESS CORRIDORS (B & AHC)

NON-RATED PARTITIONS

NR

NR

VERT. OPG. (SHAFT)

FIRE BARRIER 60 MIN

1 HR

2 HR

60 MIN

90 MINEXIT PASSAGEWAY (HORIZ.)

FIRE BARRIER

6.1.14.4.1

7.1.3.2

8.7.1.1

8.5

8.4.2

8.4.2

21.3.6

7.2.6

8.2.1.3

8.6

8.6

8.7.1.2

8.3.3.2.2 TBL

8.3

8.3.3.2.2 TBL

8.3 8.7.1.1

8.3.3.2.2 TBL

19.3.7.8

8.3.3.2.2 TBL

8.3

8.3.3.2.2 TBL

8.3

8.3.3.2.2 TBL

8.3

8.3.3.2.2. TBL

8.3

8.3.3.2.2TBL

8.7.1.2

8.3.3.2.2 TBL

8.4

8.4.3

N/A

FIRE

90 MIN

FIRE

90 MIN

FIRE

90 MIN

NOT

ALLOWED

UNLESS

SERVING

STAIR

ONLY

N/A

VARIES

SMOKE

90 MIN

VARIES

VARIES

NONE

N/A

NOT

ALLOWED

8.3.4.8 9.2.1

8.3.4.8 9.2.1

8.3.4.8 9.2.1

N/A

8.5.5.3

8.6.4

N/A

N/A

8.4.4

8.4.4 8.4.6.2

8.4.4 8.4.6.2

N/A

8.3.3.2.2 TBL

8.3

1 HROR

1 HR

2 HR

SYMBOLS

NO. OCC. EXITING

(SMALLER ROOMS)

MAXIMUM OCCUPANCY

AREA

OCC. LOAD

FACTOR

FIRE ALARM CONTROL PANEL

FIRE SYSTEM ANNUNCIATOR ALARM

ANNUNCIATOR PANEL

FACP

FSA

FAA

REQ'D. EXIT WIDTH

NO. OF OCC. EXITING

ACTUAL EXIT

WIDTH

NO. OF OCC./

NO. OF EXITS

1:50

10/1

2"

34"

FEC

FP

PROPERTY LINE

STARTING

LOCATION

TRAVEL DISTANCE

TRAVEL PATH

FE

FIRE EXTINGUISHER CABINET

FIRE PULL STATION

FIRE EXTINGUISHER

NOTES

[A] DAMPERS ARE NOT REQUIRED IN DUCT PENETRATIONS OF

SMOKE BARRIERS WHERE HVAC SYSTEMS ARE FULLY DUCTED

(18.3.7.3x2)

[B] AIR TRANSFER OPENINGS IN SMOKE PARTITIONS SHALL

HAVE DAMPERS (NFPA 8.2.4.4.3) (IBC 710.7)

[C] SMOKE DAMPERS ARE NOT REQUIRED WHERE OPENINGS IN

DUCT ARE LIMITED TO A SINGLE SMOKE COMPARTMENT &

DUCTS ARE MADE OF STEEL (IBC 716.5.5)

[D] TRANSFER GRILLES REGARDLESS OF WHETHER THEY ARE

PROTECTED

ARE NOT ALLOWED IN THESE DOORS OR WALLS (NFPA 18.3.6.4)

TD = XX

PSA

REHAB. COOR.

STAFF TLT.

BREAK RM.

OT SUPER.

AO

CHIEF PM&R

EXAM

PT/OT SWAMP

PT GYM

PT/OT EXAM

BARIATRIC

PT/OT STOR.

OT TRAIN. RM.

OT TLT.

440A

PT/OT EXAM

PT/OT EXAM

ACUPUNCTURE

ACUPUNCTURE

CHIRO. EXAM

CHIRO. EXAM

PELVIC

PELVIC

PROST. STOCK

RM.

CLEAN LINEN

450A

WC

STOR./SHOP

WOMEN'S TLT

MEN'S TLT

MSA

CHECKIN/OUT

HSKPG.

PER. CLNC.

GROUP RM.

PER. CLNC.

MASSAGE

STOR.

426A

FITTING/EXAM

RM.

FITTING/EXAM

RM.

PROST.

PURCHASING

PROST. REP

PROST. CHIEF

PROST. ASST.

CHIEF

STAFF TLT.

FUME RM.

PLASTER

CLEAN LAB

DUST RM.

MAINT.

421A

ANTE

FITTING/EXAM

RM.

PT TLT.

TELE HEALTH

247/2

24.8"

46"

247/2

24.8"

46"

ELEC.

ELEV. LOBBY

SOILED DISP

401A

PROST.

CHECKIN

405A

1:150

1:150

1:150

1:150

1:150

1:150

1:150

1:50

1:50

1:50

1:50

1:50

1:50

1:50

1:50

1:50 128

1:150

1:50

1:150

1:150

1:50

1:50

1:150

1:150

1:150

1:150

1:150

1:30

1:50

1:50

1:50

1:50

1:50

1:50

1:50

1:50

1:50

1:15

1:15

PROST. WAIT.

WAIT.

49/2

5"

80"

5"

48"

TRAVEL DISTANCE = 81'-6"

TRAVEL DISTANCE = 179'-6"

T R

A V

E L D

IS

T

A N

C E

T R

A V

E L D

IS

T

A N

C E

TRAVEL DISTANCE = 100'-0"

ELEC.

CLO.

439A

STG.

404A

OI&T RM.

FOURTH FLOOR KEY PLAN

N

SCOPE OF WORK LEGEND

SHADED AREA NOT IN SCOPE OF WORK

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

Department of Veterans Affairs

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

GI104

LIFE SAFETY PLAN - 4TH FLOOR

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

JHKJHK

1/8" = 1'-0" D3

LIFE SAFETY PLAN - 4TH FLOOR

0' 4'-0" 8'-0" 16'-0"

N

SEE GI110 FOR EGRESS PATH DURING

CONSTRUCTION PHASING.

PHASING LEGEND

AFFECTED AREA

NOTES:

1. TEMPORARY CONSTRUCTION BARRIERS SHALL BE MIN. 1 HOUR RATED FIRE BARRIER

ASSEMBLY.

2. PAIN CLINIC - NORTHWEST QUADRANT OF THE FLOOR - SHALL BE OPERATIONAL AT ALL

WORKING DAYS & HOURS (MON-FRI 7M - 5PM) DURING THE ENTIRE CONSTRUCTION

PERIOD. ANY REQUIRED WORK IN THIS CLINIC SHALL BE COORDINATED CLOSELY W/

COR.

3. ALL CEILINGS DISTURBED DURING AFTER-HOURS ABOVE CEILING WORK SHALL BE RE-

INSTALLED, CLEANED UP AND OPERATIONAL PRIOR TO END OF EACH WORK SHIFT.

4. ALL OPENINGS THROUGH CONCRETE FLOORS (RATED), MUST BE FIRESTOPPED OR

INFILLLED PRIOR TO END OF EACH WORK SHIFT.

TEMPORARY CONSTRUCTION BARRIER

EXISTING PARTITIONS

DEMO PARTITION

EXISTING AREA

AFTER-HOURS AFFECTED AREA

5PM-6AM PLUS WEEKENDS & HOLIDAYS ONLY

TEMPORARY UPGRADE OF EXISTING WALL TO 1-HR RATED FIRE BARRIER

FOURTH FLOOR KEY PLAN

N

TEMP. MSA

TEMP.

WAIT.

TRAVEL DISTANCE = 163'-6"

1.20

1.211.211.21

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

Department of Veterans Affairs

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

GI110

PHASING PLAN - 4TH FLOOR

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

IEPJHK

0' 8'-0" 16'-0" 32'-0"

N

0' 8'-0" 16'-0" 32'-0"

N

1/16" = 1'-0" B3

PHASING PLAN - 4TH FLOOR - PHASE 3

1/16" = 1'-0"

B4

PHASING PLAN - 4TH FLOOR - PHASE 1

0' 8'-0" 16'-0" 32'-0"

N

1/16" = 1'-0" D4

PHASING PLAN - 4TH FLOOR - PHASE 2

0' 8'-0" 16'-0" 32'-0"

N

1/16" = 1'-0" D3

PHASING PLAN - 4TH FLOOR - PHASE 4

KEYNOTES

KEY VALUE KEYNOTE TEXT

1.20 CONTRACTOR & VA TO COLLABORATE CLOSELY FOR IMPLEMENTING

APPROPRIATE ILSM OR PROVIDE ACCESS TO STAIR #2 IN CASE OF EMERGENCY.

1.21 THE NEW PUBLIC TOILETS & TEMPERORY WAITING NEED TO BE FULLY

FUCTIONAL BEFORE DEMOLITION OF EXISTING TOILET & WAITING.

HAZARDOUS MAT. LEGEND

ASBESTOS CONTAINING

PIPING WRAPS

APPROXIMATE QUANTITIES

*MATERIALS CONTAINING LESS THAN 1% ASBESTOS ARE NOT REQUIRED BY

NESHAP OR AHERA; HOWEVER THE OSHA PERSONAL EXPOSURE LIMITS (0.1 f/cc OF AIR AS AN EIGHT HOUR TIME WEIGHTED AVERAGE OR 1.0 f/cc OF AIR OVER 30

MINUTES) FOR ASBESTOS APPLY WHEN MATERIALS CONTAINING 1% ASBESTOS

OR LESS ARE DISTURBED DURING RENOVATIONS OR DEMOLITIONS. REFERENCE

ASBESTOS SURVEY FOR A LIST OF MATERIALS THAT CONTAIN 1% ASBESTOS OR

LESS WHICH WILL ENABLE THE RENOVATION/DEMOLITION CONTRACTOR TO MAKE

APPROPRIATE DECISIONS CONCERNING COMPLIANCE ISSUES WITH APPLICABLE

OSHA REGULATIONS

4TH FLOOR: 1,742 L.F.

ASBESTOS CONTAINING

FITTINGS

4TH FLOOR: 400

REF. MD103 & MD104

FOR POSSIBLE

LOCATIONS

GENERAL HAZARDOUS MATERIALS

NOTES

A. REMOVE ALL ASBESTOS PIPE FITTING INSULATION WITHIN THE ASBESTOS ABATEMENT

WORK SPACE, ABOVE AND BELOW CEILINGS AND IN THOSE CHASES SCHEDULED FOR

DEMOLITION. REMOVE ALL DEBRIS FOUND IN THE WORK AREA. USE TRADITIONAL ASBESTOS

ABATEMENT METHODS IN THOSE AREAS WHERE INSULATION MAY BE DAMAGED AND

SIGNIFICANT PORTIONS OF DEBRIS MAY EXIST. CHASE WALLS SHALL BE REMOVED USING

TRADITIONAL ASBESTOS ABATEMENT TO PRECLUDE ANY POSSIBLE RELEASE OF MATERIAL

INTO THE AREA DUE TO DEMOLITION ACTIVITIES.

B. REMOVE AND REPLACE WITH NEW ANY PLUMBING/MECHANICAL SYSTEM THAT IS TO REMAIN

IN USE. REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS. PLUMBING/MECHANICAL

SYSTEMS TO BE PERMANENTLY REMOVED, MAY BE CUT AND WRAPPED AND REMOVED IN

SECTIONS WITH THE INSULATION STILL ATTACHED.

C. ENCAPSULATE THE EXPOSED ENDS OF ANY PIPE INSULATION THAT ARE NOT REMOVED AT

ADJOINING FLOOR LEVELS.

D. SEE SPECIFICATIONS SECTIONS 028211 & 028213-19 FOR ASBESTOS ABATEMENT AND

ASBESTOS SURVEY.

FOURTH FLOOR KEY PLAN

N

PAIN EXAM

ROOM 4

PAIN EXAM

ROOM 3

PAIN EXAM

ROOM 2

PAIN PHARM

PAIN BH

PAIN & PMR

VVC/TM

NURSE

NAVIGATOR

EMG/SCI

PM&R EXAM

ROOM 4

PM&R EXAM

ROOM 3

PM&R EXAM

ROOM 2

PM&R EXAM

ROOM 1

471 MSA

CHECKIN/OUT

NURSES

PROCEDURE

ROOM

CLEAN SUPPLY

PROCEDURE

ROOM

OI&T RM.

STAIR #1

PAIN SWAMP

SOILED

HOLDING

492TOILET

PM&R SWAMP

PAIN EXAM

482 TOILET

EXISTING ELEC.

492A

WORKSTATION

ELEV. LOBBY

401 SOILED DISP

401A

ELEV. LOBBY /

CORR.

400-C41

STAIR #2

ELEV.

#5

ELEV.

#4

ELEV.

#3

ELEV.

#2

ELEV.

#1

ELEV.

#7

ELEV.

#8

CORRIDOR

C496

CORRIDOR

C499

CORRIDOR

C498

CORRIDOR

C495

CORRIDOR

C495

OIT/CLO.

439B

OIT/CLO.

439C

ELEC. RM.

414B

STAFF TLT.

451A

BREAK RM.

STAFF SLEEP

RM.

454A

OFF. SOCIAL

WRK.

CLEAN WRK.

RM.

W/C STG.

401C

CENTRAL JAN.

STG.

401B

NURSE

STATION

CORR.

C42

PAT. TLT.

NURSE

LOUNGE

PAT. TLT.

405A

PAT. RM.

PAT. RM.

PAT. RM./ ISO.

PAT. RM.

PAT. RM.

JAN.

454D

PAT. TLT.

455A

STAFF TLT.

454C

TEAM #1

454B

TEAM #3

OFF. SOCIAL

WRK.

OFF. SOCIAL

WRK.

TEAM WRK. RM.

NURSE

LOUNGE

N. MGT. OFF.

STAFF SHWR.

MED. RM.

PHARM. OFF.

416A

EQPM. STOR.

P.I. OFF

EQPM. STOR.

WAITING AREA

N. COORD. OFF.

427A

STAFF TLT.

TUB RM.

PAT. TLT.

411A

PAT. TLT.

413A

PAT. RM.

PAT. RM.

PAT. RM.

PAT. RM.

PAT. RM.

PAT. RM.

JAN.

DIALYSIS

PAT. TLT.

425A

PAT. TLT.

423A

PAT. TLT.

420A

PAT. TLT.

PAT. TLT.

417A

PAT. TLT.

415A

CORR.

C44PAT. TLT.

426A

PAT. RM.

PAT. RM.

PAT. TLT.

428A

PAT. RM.

PAT. RM.

PAT. TLT.

431A

PAT. RM.

CORRIDOR

C500

CONSULT RM.

WARD ADMIN.

PAT. TLT.

STAFF TLT.

463A

ON-CALL RM.

CORR.

C45

PAT. RM.

PAT. RM.

PAT. TLT.

407A

PAT. RM.

PAT. TLT.

410A

CORR.

C43

PAT. TLT.

457A

SCOPE OF WORK LEGEND

SHADED AREA NOT IN SCOPE OF WORK

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

Department of Veterans Affairs

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

HA100

HAZARDOUS MATERIAL PLANS

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

IEPJHK

1/8" = 1'-0" D3

HAZARDOUS MATERIAL PLAN - 4TH FLOOR

0' 4'-0" 8'-0" 16'-0"

N

T

T

GENERAL DEMOLITION NOTES

A. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO WORK BEGINNING. THE

CONTRACTOR IS RESPONSIBLE FOR INFORMING THE ARCHITECT OF ANY CONDITIONS THAT

DIFFER FROM THE INFORMATION INDICATED IN THE DRAWINGS.

B. PROTECT ALL EXISTING BUILDING COMPONENTS WHICH ARE TO REMAIN. REPAIR ANY

DAMAGED AREAS AS REQUIRED TO RETURN THEM TO THEIR ORIGINAL CONDITION.

C. VERIFY EXTENT OF DEMOLITION WORK WITH INFORMATION SHOWN IN THE DRAWINGS AND

WORK THAT IS NOT SHOWN AND MAY BE REQUIRED TO COMPLETE THE INTENDED WORK.

D. ALL WORK SHALL COMPLY WITH REQUIRED LOCAL CODES. CONTRACTOR IS RESPONSIBLE

FOR OBTAINING REQUIRED PERMITS AND INSPECTIONS FOR ALL WORK ASSOCIATED WITH

THIS CONTRACT.

E. CONTRACTOR SHALL REPAIR ALL DISTURBED AREAS AS REQUIRED TO MATCH

SURROUNDING EXISTING FINISHES NOT DISTURBED.

F. TYPES OF FLOOR, WALL, AND CEILING FINISHES INDICATED FOR REMOVAL BY DEMOLITION

NOTES ARE FOR GENERAL INFORMATION ONLY FROM INFORMATION OBTAINED FROM

EXISTING PLANS AND OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY MATERIAL TYPES

ONSITE PRIOR TO BID AND INCLUDE NECESSARY WORK IN HIS BID.

G. ALL APPLIANCES, FURNITURE, AND EQUIPMENT TO REMAIN THE PROPERTY OF THE

OWNER - CONTRACTOR TO COORDINATE REMOVAL, RELOCATION AND STORAGE OF

EQUIPMENT FROM DEMO AREAS WITH OWNER.

H. MISCELLANEOUS FLOOR PENETRATIONS AND DEMO FOR NEW MECHANICAL AND

ELECTRICAL WORK SHALL BE COORDINATED FROM ARCHITECTURAL, MECHANICAL, AND

ELECTRICAL PLANS.

I. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DEMO PLANS FOR DEMOLITION,

SALVAGE AND RE-USE OF EXISTING ITEMS.

J. PATCH FLOOR AT REMOVED WALLS AND CASEWORK, PREPARE FLOOR TO RECEIVE NEW

FLOORING AS REQUIRED.

K. ALL HOLES IN EXISTING SLAB LEFT FROM REMOVAL OF FIXTURES TO RECEIVE INFILL PER

STRUCTURAL DETAILS ON AD102.

L. REMOVE ALL STAINLESS STEEL CORNER GUARDS CAREFULLY AND RETURN TO OWNER.

M. ELEMENTS INDICATED WITH A DASHED LINE ARE TO BE DEMOLISHED AND DISPOSED OF AS

A PART OF THIS PROJECT, UNLESS NOTED OTHERWISE.

N. IN EXISTING AREAS, RENOVATION AND DEMOLITION WORK SHALL BE ACCOMPLISHED WITH

MINIMAL DISRUPTION TO OPERATIONS. IF REQUIRED, THE OWNER RESERVES THE RIGHT TO

TEMPORARILY STOP WORK OF SPECIFIC CONSTRUCTION OPERATIONS SHOULD THE

OWNER IDENTIFY AN EMERGENCY OR DANGER EXISTS TO THE WELFARE OF THE

OCCUPANTS ON ACCOUNT OF SUCH WORK OR OPERATIONS.

O. CONTRACTOR SHALL REMOVE AND DISPOSE OF IN A LEGAL MANNER ALL MATERIAL NOT

SCHEDULED FOR REUSE UNDER THIS PROJECT .

P. IN ALL WALLS AND CEILINGS THAT ARE TO BE REMOVED THE CONTRACTOR SHALL BE

RESPONSIBLE FOR DISCONNECTING AT SOURCE AND REMOVING OR CAPPING ELECTRICAL,

PLUMBING, GAS LINES AND MECHANICAL DUCTWORK THAT ARE NOT SCHEDULED FOR

REUSE. CONTRACTOR SHALL REROUTE AND CONTINUE ANY SYSTEM THAT MUST BE

RETAINED FOR NEW CONSTRUCTION. CONTRACTOR SHALL REROUTE AND KEEP

OPERATIONAL ALL SYSTEMS SERVING SPACES IN THE SURROUNDING AREAS TO THE

PROJECT.

Q. ALL ELECTRICAL CIRCUITS FOR EQUIPMENT THAT ARE TO BE REMOVED SHALL BE

DISCONNECTED AT SOURCE AND REMOVED BACK TO PANEL.

R. ALL PIPING GAS, WATER SUPPLY, VENT, DRAIN LINES, ETC. SUPPLYING EQUIPMENT THAT

ARE TO BE REMOVED SHALL BE DISCONNECTED, REMOVED AND CAPPED ABOVE CEILING

OR BELOW FLOOR. CONTRACTOR SHALL REROUTE AS NECESSARY, TO BE BEHIND NEW

CONSTRUCTION. (PATCH FLOOR BACK PRIOR TO TOPPING.)

S. ALL MED GASES AND PLUMBING TO BE REMOVED AT WALLS SCHEDULED FOR DEMOLITION.

T. REMOVE ALL PLUMBING FIXTURES AND EQUIPMENT WITHIN ROOMS SCHEDULED TO BE

DEMOLISHED. SEE MEP PIPING DRAWINGS.

U. RETURN ALL SIGNAGE AFFECTED BY CONSTRUCTION TO OWNER.

V. SECURITY CAMERAS TO BE FUNCTIONAL AT ALL TIME DURING CONSTRUCTION.

W. ALL UTILITY PENETRATIONS TO MATCH THE HOST WALL FIRE RATING AT ALL TIME.

2.57

2.58

2.57

2.57

2.58

2.57

2.57

2.57

2.57

2.57

2.57

2.572.57 2.58

2.57

2.57

2.58

2.57

2.57

2.57 2.58

2.58

2.58

2.57 2.57

2.57

2.57

2.58

2.13

2.13

2.13

THIRD FLOOR KEY PLAN

N

A301 A302 A302A A303A A303

A303B

A327A301BA301A

A325

A321

A320

C3A1

C3A3

A322

A323

A324

A328

A329

A305A

A305

C3A4

D303

D302

D345

D304A

D304

D344

D343

D342

D342A D342B D341

D343A

D343B

D339

D337

D335

D336

B318

B318A

B317B317A

A326

B345 A306A

A312

B341B316B

B316

B316A

B315

B315BB315A

B302

B302A

B338

B342

B343

C3B1

B323 B322

B321 C3B4

B300 B320

B301

B301A B303A

B303

C3C5

C334

C343

C341

C338

C339

D338

D340

C3D3

C345

C333

C332

C335 C336

C337

C348

C348A

C337A

C329

C328A

C328

C368

C321

C322

C327

C324

B348

C3A2C3B5

B344

A302B

SCOPE OF WORK LEGEND

SHADED AREA NOT IN SCOPE OF WORK

DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES NOT VACATED

AND THAT NEED TO REMAIN OPERATIONAL. COORDINATION WITH COR IS

NEEDED TO ACCOMPLISH WORK AFTER HOURS, NIGHTS AND WEEKENDS.

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

Department of Veterans Affairs

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

AD100

DEMOLITION RCP - 3RD FLOOR -

ABOVE CEILING

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

IEPJHK

KEYNOTES

KEY VALUE KEYNOTE TEXT

2.13 REMOVE PORTION OF WALL FOR NEW UTILITIES PENETRATION AND PATCH / FIRE

PROOF AS NECESSARY TO MAINTAIN WALL FIRE RATING AT ALL TIME DURING

CONSTRUCTION.

2.57 TEMPORARILY REMOVE EXISTING CEILING GRID AND TILES AS NECESSARY FOR

DEMO/INSTALL OF MECHANICAL(SEE MECH PLANS); REINSTALL GRID AND TILE AND

REPARE ANY DAMAGES THAT OCCURED DURING CONSTRUCTION.

2.58 REMOVE EXISTING GYP CEILING AS NECESSARY FOR DEMO/INSTALL OF

MECHANICAL(SEE MECH PLANS); REPLACE, PATCH AND PAINT CEILING WHERE

AFFFECTED BY CONSTRUCTION. ADD ACCESS PANELS AS REQUIRED TO SERVICE

NEW MECHANICAL.

1/8" = 1'-0" D3

DEMOLITION RCP - 3RD FLOOR

0' 4'-0" 8'-0" 16'-0"

N

NOTE:

ALL WORK ON THIS FLOOR SHALL FOLLOW ICRA (INFECTION

CONTROL RISK ASSESSMENT) LEVEL IV MEASURES.

Sheets
GI002 - ABA SHEET
GI103 - ABA SHEET
GI104 - LIFE SAFETY PLAN - 4TH FLOOR
GI110 - PHASING PLAN - 4TH FLOOR
HA100 - HAZARDOUS MATERIAL PLANS
AD100 - DEMOLITION RCP - 3RD FLOOR - ABOVE CEILING

File details come from the government source that posted it. Updated .