Drawings-589A4-22-100-2023-02-15 BID Set-Part11-pages 9.pdf

PDF 5 MB Posted

Attached to
Z2DA-- Relocate Physical Medicine and Rehabilitation to the 4th Floor PN: 589A4-22-100
Solicitation number
36C25523R0072
Issued by

About this file

This document package includes construction drawings and specifications for a federal construction project to relocate physical medicine and rehabilitation services to the fourth floor of a Veterans Affairs medical center. Key details include renovating areas A and B on the fourth floor to accommodate the relocated services, with demolition and new work shown on electrical plans for lighting, data networks, and nurse call systems. The project is identified as solicitation number 36C25523R0072 with a bid due date of December 31, 2023. Construction is slated to take place at the VA medical center located at 800 Hospital Drive in Columbia, Missouri.

View the file

Other files

File Type Posted
36C25523R0072 0004.docx DOCX document
AMENDMENT 3 - Drawings.pdf PDF
AMENDMENT 3 - Specifications.pdf PDF
36C25523R0072 0003.docx DOCX document
Prebid-site visit attendee list.pdf PDF
36C25523R0072 0002.docx DOCX document
589A4-22-100 Volume 2 Specifications- 494 pages.pdf PDF
36C25523R0072 0001.docx DOCX document
Drawings-589A4-22-100-2023-02-15 BID Set- Part5-pages 10.pdf PDF
Drawings-589A4-22-100-BID Set -2-15-2023- Part1-7 pages.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set -Part4-pages 10.pdf PDF
36C25523R0072.docx DOCX document
Drawings-589A4-22-100-2023-02-15 BID Set - Part12-pages 11.pdf PDF
Drawings-589A4-22-100- 2023-02-15 BID Set-Part2- Pages 6.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set- Part13-pages 1.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set-Part6-pages 6.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set- Part9-pages 8.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set - Part3-pages-12.pdf PDF
Specifications-589A4-22-100-2023-02-15 BID Set - VOL 1- Pages 785.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set-Part8-pages 9.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID Set-Part10-pages 13.pdf PDF
Drawings-589A4-22-100-2023-02-15 BID set - Part7-pages 9.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FE

F E

C R

P

CRP CRP

V

CRP

CR

TV

TV

T V

C R

P

TVTV

TV

CRP

TV

TV

TV

TV

CRP

TV

TV

TV

TV

CRP

TV

CRP

TV

TV

TV

T V

TV

TV

V

TV

TV

TV

TV

TV

TV

S S

S S

S

TV

A

V

PIR

S

S

SS

S

S

S

S

S

S

S

S

S

S

S S

S

S

S

S

S

S

S

S

S

S S

V

S

S

T

TT

EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb

2.8

3.7

7.3

8.2

9.1

4.5

6.2

5.4

5.7

5.3

4.6

10.2

9.8

8.9

8.3

7.2

7.1

3.6

4.1

4.7

5.1

6.1

6.3

8.0

5.5

7.5

3.1

4.4

4.5

5.4

6.2

F.1GHJKLMMa La Jb Hb Ga

6.7

1. DEVICES SHOWN AS DARK DASHED LINES SHALL BE

DEMO.

2. REMOVE ALL CABLES BACK TO SOURCE.

3. REMOVE ALL CONDUIT, CONDUCTORS, AND JUNCTION

BOXES FOR DEMO DEVICES BACK TO PANEL.

4. IF DEVICE IS TO BE DEMOED AND IS INSTALLED IN A

WALL INDICATED TO REMAIN, REMOVE CONDUCTORS

FROM DEVICES AND PROVIDE A BLANK COVER PLATE.

CONDUIT AND JUNCTION BOXES IN THE WALL MAY

REMAIN.

5. CONTRACTOR SHALL DISCONNECT ALL NURSE CALL

AND TV EQUIPMENT AND HAND OVER TO END USER.

6. DEMO ALL CABLE TRAY IN NEW WORK AREA.

7. WAP WORK:

A. CONTRACTOR TO MARK EACH EXISTING WAP WITH

A UNQUIC NUMBER.

B. CONTRACTOR TO PROVIDE RED LINE MARK UP OF

EACH WAP LOCATION.

C. CONTRACTOR TO DISCONNECT AND HAND OVER

WAP TO VA FOR STORAGE.

D. EXISTING FEEDERS FOR WAP SHALL BE COILED UP

AND PROTECTED.

E. WAP TO BE INSTALLED IN SAME LOCATION WHERE

WAP WAS REMOVED.

DATA DEMO NOTES

FOURTH FLOOR KEY PLAN

N

B

A

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig h th in c o n e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e rs e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e s e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

ED106

ELECTRICAL DEMOLITION PLAN -

DATA - 4TH FLOOR - OVERALL

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

TLKGF

1/8" = 1'-0"

ELECTRICAL 4TH FLOOR OVERALL DATA DEMO PLAN

# Revision Date

Date: 02-09-2023 Exp. Date: 12-31-2023

C R

P

CRP CRP

V

CRP

CR

TV

TV

T V

C R

P

TV

TV

TV

T V

Z L

Z L

Z L

TV

NC

TV

TV

D L

DL

NC

DL

D L

S

N C

N C

S

S

S

S

TVM

A

S

PIR

S

S

NC

N C

NC

SS

S

S

N C

S

S

NC

NC

NC

NC

NC

S

NC

NC

S

S

S

S

S S

NC

NC

NC

EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb

3.7

4.5

6.2

5.4

5.7

5.3

4.6

3.6

4.1

4.7

5.1

6.1

6.3

5.5

3.1

4.4

(2D, 1V)

(2D)

(2D, 1V)

(2D, 1V)

(2D, 1V)(1D)

TWO

ANTENNAE

TWO

ANTENNAE

SINGLE

ANTENNAE

4.5

5.4

6.2

F.1GHJKLMMa La Jb Hb Ga

6.7

WAPWAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

ETR

WAP

1. DEVICES SHOWN AS DARK DASHED LINES SHALL BE

DEMO.

2. REMOVE ALL CABLES BACK TO SOURCE.

3. REMOVE ALL CONDUIT, CONDUCTORS, AND JUNCTION

BOXES FOR DEMO DEVICES BACK TO PANEL.

4. IF DEVICE IS TO BE DEMOED AND IS INSTALLED IN A

WALL INDICATED TO REMAIN, REMOVE CONDUCTORS

FROM DEVICES AND PROVIDE A BLANK COVER PLATE.

CONDUIT AND JUNCTION BOXES IN THE WALL MAY

REMAIN.

5. CONTRACTOR SHALL DISCONNECT ALL NURSE CALL

AND TV EQUIPMENT AND HAND OVER TO END USER.

6. DEMO ALL CABLE TRAY IN NEW WORK AREA.

7. WAP WORK:

A. CONTRACTOR TO MARK EACH EXISTING WAP WITH

A UNQUIC NUMBER.

B. CONTRACTOR TO PROVIDE RED LINE MARK UP OF

EACH WAP LOCATION.

C. CONTRACTOR TO DISCONNECT AND HAND OVER

WAP TO VA FOR STORAGE.

D. EXISTING FEEDERS FOR WAP SHALL BE COILED UP

AND PROTECTED.

E. WAP TO BE INSTALLED IN SAME LOCATION WHERE

WAP WAS REMOVED.

DATA DEMO NOTES

FOURTH FLOOR KEY PLAN

AREA A

N

B

A

1. DEMO RACK AFTER ALL CABLES ARE DEMO'ED FROM

RENOVATIONS AREA.

2. RELOCATE EXISTING RACKS TO ALLOW FOR

INSTALLATION OF NEW RACKS. COORDINATE PHASING

WITH END USER.

3. PROTECT EXISTING WAP. REMOVE WAP FROM CEILING,

PROTECT FROM DUST, AND MOVE TO LOCATION TO

AVOID NEW WORK. WAP TO BE INSTALLED IN SAME

GENERAL LOCATION. COIL EXISTING CABLE TO BE RE-

INSTALLED.

4. DEMO EXISTING CABLE TRAY LADDER. SUPPORT

EXISTING CABLE TO BE INSTALLED IN NEW CABLE TRAY.

SHEET KEYNOTES#

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

ED107

ELECTRICAL DEMOLITION PLAN -

DATA - 4TH FLOOR - AREA A

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

TLKGF

3/16" = 1'-0"

ELECTRICAL 4TH FLOOR AREA A DATA DEMOLITION PLAN

# Revision Date

FE

F E

TVTV

TV

CRP

TV

TV

TV

TV

CRP

TV

TV

TV

TV

CRP

TV

CRP

TV

V

TV

N C

N C

N C

N C

N C

NCDL

N C

N C

DL

N C

D L

D L

N C

N C

N C

TV

DL

TV

DL

NC

N C

NC

NC

D L

D L

N C

N C

DL DL

DL

D L

N C

N C

N C

N C

N C

DL

D L

D L

NC

DLDL

N C

N C

D L

DL

TV

TV

TV

A

M A

S

V

D L

NC

NC

S

S

S

S

N C

S S

S

S

S

S

N C

NC

S

N C

N C

N C

S

NC

N C

N C

N C

S

NC

NC

NC

N C

NC

V

S

S

N

CN

C

T

TT

EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb

7.3

8.2

9.1

9.8

8.9

8.3

7.2

7.1

8.0

7.5

F.1GHJKLMMa La Hb Ga

PATIENT

MONITORING

CABINET

WAP

WAP

WAP WAP WAP

WAP

WAP

WAP

WAP

WAP

WAP

1. DEVICES SHOWN AS DARK DASHED LINES SHALL BE

DEMO.

2. REMOVE ALL CABLES BACK TO SOURCE.

3. REMOVE ALL CONDUIT, CONDUCTORS, AND JUNCTION

BOXES FOR DEMO DEVICES BACK TO PANEL.

4. IF DEVICE IS TO BE DEMOED AND IS INSTALLED IN A

WALL INDICATED TO REMAIN, REMOVE CONDUCTORS

FROM DEVICES AND PROVIDE A BLANK COVER PLATE.

CONDUIT AND JUNCTION BOXES IN THE WALL MAY

REMAIN.

5. CONTRACTOR SHALL DISCONNECT ALL NURSE CALL

AND TV EQUIPMENT AND HAND OVER TO END USER.

6. DEMO ALL CABLE TRAY IN NEW WORK AREA.

7. WAP WORK:

A. CONTRACTOR TO MARK EACH EXISTING WAP WITH

A UNQUIC NUMBER.

B. CONTRACTOR TO PROVIDE RED LINE MARK UP OF

EACH WAP LOCATION.

C. CONTRACTOR TO DISCONNECT AND HAND OVER

WAP TO VA FOR STORAGE.

D. EXISTING FEEDERS FOR WAP SHALL BE COILED UP

AND PROTECTED.

E. WAP TO BE INSTALLED IN SAME LOCATION WHERE

WAP WAS REMOVED.

DATA DEMO NOTES

FOURTH FLOOR KEY PLAN

AREA B

N

B

A

1. EXISTING WALL RACK TO REMAIN. PROTECT FROM

DUST.

2. PROTECT EXISTING WAP. REMOVE WAP FROM CEILING,

PROTECT FROM DUST, AND MOVE TO LOCATION TO

AVOID NEW WORK. WAP TO BE INSTALLED IN SAME

GENERAL LOCATION. COIL EXISTING CABLE TO BE RE-

INSTALLED.

SHEET KEYNOTES#

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

ED108

ELECTRICAL DEMOLITION PLAN -

DATA - 4TH FLOOR - AREA B

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

TLKGF

3/16" = 1'-0"

ELECTRICAL 4TH FLOOR AREA B DATA DEMOLITION PLAN

# Revision Date

FEC

OD OD

OD

ODODOD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

ODODODOD

OD

OD

OD

OD

OD

OD

OD

OD

OD OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD OD OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD OD

T

DSDSDSDS DS DS

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb

2.8

3.7

7.3

8.2

9.1

4.5

6.2

5.4

5.7

5.3

4.6

10.2

9.8

8.9

8.3

7.2

7.1

3.6

4.1

4.7

5.1

6.1

6.3

8.0

5.5

7.5

3.1

4.4

9' - 0"

9' - 0"

9' - 0"

9' - 0"

10' - 0"

9' - 0"

9' - 0"9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

440A

LP4-K7-120VN

LP4-Ga4-120VN-1 LP4-Ga4-120VN-2

B1

B1

B1

FOURTH FLOOR KEY PLAN

N

B

A

1. CROSS HATCH AREA IS NIGHTS AND WEEK END WORK.

REFER TO ARCHITECT DRAWINGS FOR ADDITIONAL

INFORMATION ON PHASING.

SHEET KEYNOTES#

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

EL100

ELECTRICAL REFLECTED CEILING

PLAN - LIGHTING - 4TH FLOOR -

OVERALL

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

TLKGF

1/8" = 1'-0"

ELECTRICAL 4TH FLOOR OVERALL LIGHTING NEW WORK

# Revision Date

OD OD

OD

ODODOD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

FOURTH FLOOR KEY PLAN

AREA A

N

B

A

EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb

2.8

3.7

4.5

6.2

5.4

5.7

5.3

4.6

7.1

3.6

4.1

4.7

5.1

6.1

6.3

5.5

3.1

4.4

9' - 0"

9' - 0"

9' - 0"9' - 0"

9' - 0"

9' - 0"

LP4-K7-120VN

LP4-Ga4-120VN-1 LP4-Ga4-120VN-2

B2

B1E

1b,1E

B1

1b

B1E

1b,1E

B1

1b

B1E

1b,1E

B1

1b

B1

1b

B1E

1b,1E

B1

1b

B1

1b

B1E

3a,1E

5B1

B1

3a

B1E

3a,1E

B1

3a

B1E

3a,1E

B1

3a

C1

3E 3E

B1

B1

B1

B1E

3a,1E

B1

3a

B1E

3a,1E

LC03

LC03

LC03

LC08

LC08

LC06

LC15

LC15

LC03

LC15

LC15

LC06

LC07

LC07 LC07

LC03

LC06

BREAK RM.

CORR.

C41

HSKPG.

CORR.

C43 CORR.

C42

WC STOR./SHOP

ELEV. LOBBY

ELEV. LOBBY / CORR.

SOILED DISP

401A

PROST. CHECKIN

405A

PROST. STOCK RM.

CORR.

C45

CHIRO. EXAM

CHIRO. EXAM

STOR.

426A

CORR.

C46

PROST. WAIT.

FITTING/EXAM RM.

PER. CLNC. GROUP RM.

PER. CLNC. MASSAGE

FITTING/EXAM RM.

PROST. PURCHASING

DUST RM.

FUME RM.

CLEAN LAB

PLASTER

MAINT.

421A

FITTING/EXAM RM.

PROST. ASST. CHIEF

CORR.

C47

PROST. REP

STAFF TLT.

PROST. CHIEF

WOMEN'S TLT

MEN'S TLT

MSA CHECKIN/OUT

C1

C1

C1

C1

B1

3a

B1

3a

B1E

3a

B1

3a

B1

3a

B1

3a

B1E

3a,1E

B2

B1

B1

B1

B1

B1E

1,1E

B1

B1

B1

B1

B1

B1

B1

B1

B1E

1,1E

B1

B1

B1

B1

B1

B1E

1,1E

B1

B1

B1

B1E

1,1E

B1

B1

B1

B1E

1,1E

B1

B1

B1

B2

B1E

1,1E

B1

B1

B1

B1

B1

B1

B1

B1E

1,1E

B1

B1E

1,1E

B1

B1

B1E

1,1E

B1

B1

B1E

1,1E B1

B1

B1E

1,1E

B1

B1

B1E

1,1E

B1

B1

B1

B1

B1

B1

B1

B1E

1,1E

B1E

1,1E

B1

B1

B1

B1E

1,1E

B1

B1

B1E

1,1E

B1

B1

1b

B1

1b

B1

B1E

1b,1E

B1

B1

B1

B1E

3,1E

B1

B1

B1

B1E

3,1E

B1E

1,1E

B1

SEE SHEET EL102

SEE SHEET EL102

1E

LC15

LC19

LC19

LC06

LC19

LC20

X2

X

X

1E

X2

1E

X

1E

X

X

X

FUME HOOD

BELOW

X a a a aa b b b bb a

B1

B1

B1

3E 3E b a,b

F F

1 1

PP4-Jb4.4-120VC

LC03

1. CIRCUIT NORMAL LIGHT FIXTURES TO PANEL LP4-

H9-277VN.

2. CIRCUIT EMERGENCY LIGHT FIXTURES AND ALL EXIT

SIGNS TO PANEL LP4-H9-277VE AND PROVIDE NORMAL

CIRCUIT FROM LP4-H9-277VN. EMERGENCY FIXTURES

CIRCUIT ENDS WITH AN "E". EXAMPLE 1, 2E MEANS

NORMAL CIRCUIT #1 AND EMERGENCY CIRCUIT #2.

3. CONTRACTOR TO COORDINATE WITH OTHER

DISCIPLINE PRIOR TO INSTALLATION. REFER TO

COORDINATION REQUIREMENTS IN SPECS.

LIGHTING GENERAL NOTES

1. RELOCATE EXISTING (2) EXISTING LIGHTS IN ROOM TO

AVOID NEW CABLE TRAY.

2. CIRCUIT LIGHT FIXTURES IN THE ROOM TO EXISTING

LIGHT SWITCH. CIRCUIT LIGHT FIXTURES TO EXISTING

PANEL CIRCUIT BREAKER.

3. PROVIDE TEMPORARY EXIT SIGN. REMOVE ONCE

PROJECT IS COMPLETE.

4. TEMPORARY ROTATE EXISTING EXIT SIGN. ROTATE EXIT

SIGN ONCE PROJECT IS COMPLETE.

SHEET KEYNOTES#

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

EL101

ELECTRICAL REFLECTED CEILING

PLAN - LIGHTING - 4TH FLOOR - AREA

A

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

TLKGF

3/16" = 1'-0"

ELECTRICAL 4TH FLOOR AREA A LIGHTING NEW WORK

# Revision Date

OD OD

OD

ODODOD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

ODODOD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD

OD OD OD

OD

OD

OD

OD

OD

OD

OD

OD OD

T

DSDSDSDS DS DS

OD

OD

OD

OD

OD

OD

OD

OD

FOURTH FLOOR KEY PLAN

AREA B

N

B

A

EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb

7.3

8.2

9.1

10.4

6.2

10.2

9.8

8.9

8.3

7.2

7.1

6.1

6.3

8.0

7.5

9' - 0"

9' - 0"

9' - 0"

9' - 0"

10' - 0"

9' - 0"

9' - 0"9' - 0"

9' - 0"

9' - 0"

9' - 0"

440A

LP4-K7-120VN

B1

B1

B1

B1

B1E

5,3E

B1

B1

B1

B1E

5,3E

B1E

5,3E

B1

B1

B1

B1

B1

B1

B1E

5,3E

B1

B1

B1

B1E

5,3E

B1

B1

B1E

5,3E

B1

B1

B1

B1E

5,3E

B1

B1E

5,3E,c

B1

5c

B1

5c

B1

5c

B1

5c

B1E

5,3E,c

C1

5E

B1

B1E

5,3E

B1

B1

B1

B1E

5,3E

B1

B1

B1

B1E

5,3E

B1

B1E

5,3E

B1

B1

B1

B2

B2

5B1E

5,3E

B1

B1

B1

B2

B1E

7,3E

B2

B2

B1

B1E

7,3E

B1

B1

B1E

7,3E

B1

B1

B1

B1E

7,3E

B1

B1

B1

B1

B1

B1E

7,3E

B1

B1

B1E

7,3E

B1

B1E

7,3E

B1

B1E

7,3E

B1

B1E

7,3E

7E

B1

7a

B1E

7,3E,a

B1

7a

B1E

7,3E,a,b

B2

B2E

5,3E

B2

B2

B2

B1

7a

B1

7a

B1E

7,3E,a

B1

7a

B1

7a

B1

7a

B1

7a

B1

7a

B1E

7,3E,a

B1

7a

B1

7a

B1

7a

B1E

7,3E,a

B1

7a

B1

7a,b

B1

7a,b

B1E

5,3E,a

B1

5a

B1

5a

B1E

5,3E,a

B1

5a

B1

5a

B1

5a B1E

5,3E,a

B1

5a

B1

5a

B1

5a

B1E

5,3E,a

B1

5a

B1

5a

B1

5a

B1E

5,3E,a

B1

5a

B1

5a

B1

5a

B1E

5,3E,a

B1

5a

B1E

5,3E,a

B1

5a

B1

5a

B1

5a,b

B1E

5,3E,a,b

B1

5a,b

B1

5a,b

B1

5a,b

B1E

5,3E,a,b

B1

5a,b

B1

5a,b

B1

5a,b

B1E

3,3E,a,b

B1

5a,b

B1

5a,b

B1E

5,3E,a,b

B1

5a,b

B1

5a,b

B1

5a

B1E

5,3E,a

LC15

LC15

LC15

LC15

LC15

LC15

LC15

LC15

LC06

LC06

LC06

LC07

LC07

LC16

LC16

LC03

LC21

LC05F

5,3E

OT TRAIN. RM.

PT GYM

PT GYM

PT GYM

PT/OT SWAMP

REHAB. COOR.

STAFF TLT.

TELE HEALTH

PSA

OT SUPER.

AO

CHIEF PM&R EXAM

CORR.

C43

PT/OT SWAMP

WAIT.

CORR.

C42

WC STOR./SHOP

CLEAN LINEN

450A

ELEV. LOBBY

PROST. STOCK RM.

PELVIC

PELVIC

PT TLT.

ACUPUNCTURE

ACUPUNCTURE

PT/OT EXAM

PT/OT EXAM

OT TLT.

440A

CORR.

C44

PT/OT STOR.

PT/OT EXAM BARIATRIC

B1E

7,3E

B1

B1E

5,3E

B1E

5,3E,c

B1

B1E

5,3E

B1

B1E

5,3E

B2E

5,3E

B2

B2

B1

5a

B1

5a

B1

5a

B1

5a

B1

5a

B1

5a

B1

7a

B1E

7,3E

B1

B1

7a

B1E

53E,c

SEE SHEETEL101

SEE SHEETEL101

LC06

X

3E

X2

3E

X

3E

X2

3E

X2

3E

X

3E

X2

3E

X2

3E

X

3E

DP4-H9-277VN

LP4-H9-277VE

B1

B1

5,3E

B1

C1

C1

LC15

B1E

5,3E,c

B1

LC07

LC03

LC03

LC03

LC03

LC03

LC15

LC17 LC14

LC08

LC08

LC06LC19

LC19

LC14

LC14

LC18

B1E

7,3E,a ba c c c a b b a b a b a b a c a aa a a

X

3E

X2

3E

LC16

5E

B1

B1

7a

B1

7a

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

C2

5a,b

1. CIRCUIT NORMAL LIGHT FIXTURES TO PANEL LP4-

H9-277VN.

2. CIRCUIT EMERGENCY LIGHT FIXTURES AND ALL EXIT

SIGNS TO PANEL LP4-H9-277VE AND PROVIDE NORMAL

CIRCUIT FROM LP4-H9-277VN. EMERGENCY FIXTURES

CIRCUIT ENDS WITH AN "E". EXAMPLE 1, 2E MEANS

NORMAL CIRCUIT #1 AND EMERGENCY CIRCUIT #2.

3. CONTRACTOR TO COORDINATE WITH OTHER

DISCIPLINE PRIOR TO INSTALLATION. REFER TO

COORDINATION REQUIREMENTS IN SPECS.

LIGHTING GENERAL NOTES

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

EL102

ELECTRICAL REFLECTED CEILING

PLAN - LIGHTING - 4TH FLOOR - AREA

B

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

TLKGF

3/16" = 1'-0"

ELECTRICAL 4TH FLOOR AREA B LIGHTING NEW WORK

# Revision Date

LIGHTING CONTROL SEQUENCE

S - "INDIVIDUAL ZONE WALL CONTROLLER". REFER TO FLOOR PLAN FOR QUANTITY OF ZONES SHOWN IN THE AREA. EACH ZONE SHALL HAVE A ITS OWN INDEPENDENT CONTROLLER WITHIN THE WALL CONTROLLER.

D - "INDIVIDUAL DIMMING ZONE WALL CONTROLLER". EACH ZONE SHALL ITS OWN INDEPENDENT CONTROLLER CAPABLE OF ON, OFF AND DIMMING WITH IN THE WALL CONTROLLER. REFER TO FLOOR PLAN FOR QUANTITY OF ZONES SHOWN IN THE AREA.

P -"PRESET SCENE CONTROLLER". NUMBER INDICATES QUATITY OF PRESET SCENE CONTROLS. EACH PRESET SCENE SHALL EACH BE CAPABLE OF TURNING SCENE ON, OFF AND DIM.

DL Ft. Cd. - "DAY LIGHT PHOTO SENSOR". MUST AUTOMATICALLY DIM INDICATED LUMNINAIRES SHOWN ON FLOOR PLANS WITH DAY LIGHT ZONES. MAINTAIN MAXIMUM FOOT CANDLE RATING INDICATED AS MEASURED FROM +30" AFF.

MAN - MANUAL CONTROL. OCC - OCCUPANCY ON AND / OR VACANCY OFF. TC - TIME CLOCK. ETD - EMERGENCY TRANSFER DEVICE.

SEQUENCE ID AREA DESCRIPTION

WALL AUTOMATIC CONTROLS

DL

Ft. Cd. ETD REMARKS

CONTROLLER ON (X=100%) OFF (X=0%)

S D P MAN OCC TC MAN OCC TC

LC03 OFFICES X X 50% X X X

LC05 ELEC/MECH X X X X

LC06 SUPPLY/ STORAGE X X X X

LC07 RESTROOMS X X X X X

LC08 CORRIDORS. X X 50% X

LC14 SWAMP X X X X X X

LC15 EXAM / TREATMENT X X 50% X X X

LC16 PHYSICAL THERAPY X X 50% X X X X

LC17 LOUNGE / BREAK (HEALTHCARE FACILITY) X X 50% X X X

LC18 GENERAL SEATING AREA X X X X X

LC19 WORKSHOP X X X X X

LC20 LABORATORY X X X X X X

LC21 ELEVATOR LOBBY X X X X X

LIGHTING CONTROL NOTES:

1. LIGHT FIXTURE SHOP DRAWING AND LIGHTING CONTROL SHOP DRAWING SUBMITTAL SHALL BE SUBMITTED AT THE SAME TIME. APPROVAL WILL NOT BE

GRANTED UNTIL BOTH ARE REVIEWED.

2. THE LIGHTING CONTROL SYSTEM SCHEDULE SHALL BE CONSIDERED A PERFORMANCE CRITERIA. PROVIDE ALL CONTROL DEVICES, WIRING, RACEWAY, PROGRAMMING, AND LABOR AS REQUIRED TO OBTAIN THE SEQUENCES IDENTIFIED FOR EACH SPACE.

3. PROVIDE CONTROL DRAWINGS, SEQUENCE DESCRIPTIONS, PUSHBUTTON CONFIGURATIONS (WITH LIGHITNG LOADS IDENTIFIED) AND WIRING DIAGRAMS INDICATING THE PROPOSED LIGHTING CONTROLS WITHIN THE SHOP DRAWING SUBMITTAL FOR APPROVAL.

4. COORDINATE ALL BUTTON ENGRAVING WITH OWNER PRIOR TO ORDERING.

5. MOUNT AREA CONTROLLERS AND POWER PACKS ABOVE CEILING, NEAR WALL CONTROLLERS IN THE INTERIOR SIDE OF THE SPACE SERVED. ROOM

CONTROLLERS SERVING CORRIDORS MAY BE LOCATED IN ELECTRICAL ROOMS.

6. PRIOR TO CONSTRUCTION CLOSEOUT, DEMONSTRATE LIGHTING CONTROLS TO OWNER FOR FINAL APPROVAL. MODIFY PROGRAMMING AND ILLUMINATION

AS REQUIRED TO MEET OWNERS FINAL REQUIREMENTS.

7. EACH SWITCH LEG SHOWN ON LIGHTING DRAWINGS IS A ZONE, PROVIDE A TOGGLE/DIMMER SWITCH FOR EACH SWITCH LEG/ZONE SHOWN ON LIGHTING

FLOOR PLANS.

CEILING MOUNTING:

REC - RECESSED

SUR - SURFACE

SEMI - SEMI RECESSED

STR - STRUT

SUSPENDED MOUNTING:

AC-# - AIRCRAFT CABLE

CH-# - CHAIN HUNG

RP-# - ROD PENDANT

CP-# - CONDUIT PENDANT

(#FT) - DISTANCE FROM CEILING

(#AFF) - ABOVE FINISH FLOOR

EXTERIOR MOUNTING:

W - WALL

P - POLE

BP - BOLLARD TOP

IG - IN-GRADE

EXTERIOR POLE:

AL - ALUMINUM

ST - STEEL

R - ROUND

SQ - SQUARE

SA - STRAIGHT

TA - TAPERED

(#FT) - POLE HEIGHT

(#IN) - DIAMETER POLE

CEILING TYPE:

ACT - ACOUSTIC CEILING TILE

GYP - GYPSUM BOARD CEILING

EXP - EXPOSED

EXAMPLE:

REC-GYP

RECESSED GYPSUM BOARD

CEILING

#FR - FIRE RATED

# - HOURS

IC - INSULATED CONTACT

CR - CHICAGO RATED

DAMP OR WET

EXAMPLE:

IC-1.5FR

INSULATED CONTACT WITH

FIRE RATED FOR 90 MINUTES.

#P - POLY LENS

#T - TEMPERED GLASS

#AC - ACYLIC

OPTIONS:

# - 0.125, 0.156, ETC

SG - SINGLE GASKET

DG - DOUBLE GASKET

IP - INGRESS PROTECTION

AM - ANTIMICROBIAL

K - KELIVN

RGB

WT (#K-#K) - WHITE TUNING

(#K-#K) COLOR RANGE

80+ MIN

TM-30 (CHROMATICITY):

( Rf / Rg / Rfh1 / Rcshr ) Rf - FIDELITY INDEX Rg - RELATIVE GAMUT INDEX Rfh1 - FIDELITY INDEX, HUE-BIM Rcsh1 - CHROMA SHIFT, HUE-BIM

UNV - 100V TO 277V

120V 208V 277V 480V

NA - ON / OFF

STEP (0%, 50%, 100%)

DIMMING:

W - WIRELESS

0-10V

DMX

DALI

PC - PHASE CONTROL

(#%) - MIN DIMMING

# WATT (90 MINUTES)

UL 924

UL 1008

MOUNTING: LISTING: LENS TYPE / COLOR: TRIM TYPE / COLOR: TEMPERATURE (K): COLOR RENDER INDEX (CRI): VOLTAGE: CONTROL: EMERGENCY CONTROL:

LIGHT FIXTURE SCHEDULE

Type Mark Manufacturer Model Description

FIXTURE INFOMATION

LUMENS

LED / LAMP INFOMATION

DRIVER /

BALLAST

INFOMATION

LOAD

DRIVER / BALLAST INFOMATION

REMARKSMOUNTING LISTING LENS TRIM DISTRIBUTION TEMP (K) CRI VOLTAGE CONTROL EMERGENCY

B1 CREE LIGHTING ZR22 2X2 RECESSED TROFFER RECESSED - - FROSTED WHITE WHITE 3500 - - 3500 80 UNV 25 W 0-10V (10%) - -

B1E CREE LIGHTING ZR22 2X2 RECESSED TROFFER RECESSED - - FROSTED WHITE WHITE 3500 - - 3500 80 UNV 25 W 0-10V (10%) UL 1008 WITH DIMMING OVERRIDE

B2 CREE LIGHTING ZR22 2X2 RECESSED TROFFER RECESSED - - FROSTED WHITE WHITE 4000 - - 3500 80 UNV 29 W 0-10V (10%) - -

B2E CREE LIGHTING ZR22 2X2 RECESSED TROFFER RECESSED - - FROSTED WHITE WHITE 4000 - - 3500 80 UNV 29 W 0-10V (10%) UL 1008 WITH DIMMING OVERRIDE

C1 CALCULITE GEN 3 6" 6" DOWNLIGHT RECESSED - - FROSTED WHITE WHITE 3000 WIDE 3500 80 UNV 15 W 0-10V (10%)

C2 CALCULITE GEN 3 6" 6" DOWNLIGHT RECESSED - - FROSTED WHITE WHITE 2000 WIDE 3500 80 UNV 15 W 0-10V (10%)

E COOPER LIGHTING BCLED 2' WALL MOUNT W - - FROSTED WHITE WHITE 2400 - - 3500 80 UNV 25 W 0-10V (10%) - -

F LITHONIA ZL1D 4' STRIP LIGHT CH - - FROSTED WHITE WHITE 5000 - - 3500 80 UNV 41 W 0-10V (10%) - -

X LITHONIA 202 LT0-EDG1R MR EXIT SIGN SINGLE FACE CEILING - - RED EXIT ALUMINUM - - - - - - - - UNV - - - -

X2 LITHONIA 202 LT0-EDG2R MR EXIT SIGN TWO FACE CEILING - - RED EXIT ALUMINUM - - - - - - - - UNV - - - -

LUMINAIRE SCHEDULE GENERAL NOTES:

1. UNLESS OTHERWISE STATED IN REMARKS. ALL FIXTURES ARE LED.

2. LIGHT FIXTURE SHOP DRAWING AND LIGHTING CONTROL SHOP DRAWING SUBMITTAL SHALL BE SUBMITTED AT THE SAME TIME. APPROVAL WILL NOT BE GRANTED UNTIL BOTH ARE REVIEWED.

3. REFER TO ARCHITECTURAL DOCUMENTS FOR EXACT MOUNTING LOCATIONS OF LUMINAIRES AND CEILING TYPES.

4. ALL RECESSED DOWNLIGHTS SHALL HAVE SELF-FLANGED REFLECTORS U.O.N. AND SHALL BE INSTALLED SO THAT THE BOTTOM OF THE THROAT IS EVEN WITH THE FINISHED CEILING PLANE. THE OVERLAPPING FLANGE MUST THEN FIT FLUSH TO THE CEILING PLANE/THROAT. NO LIGHT LEAK MUST BE VISIBLE. ALL MISCELLANEOUS HARDWARE ABOVE THE CEILING PLANE TO ACCOMPLISH THE ABOVE SHALL BE INCLUDED IN THE BASE BID.

5. ALL LUMINAIRES SHALL HAVE A U.L. LABEL.

6. IN ALL MECHANICAL ELECTRICAL EQUIPMENT AREAS, CONTRACTOR TO COORDINATE LUMINAIRE LOCATIONS SUCH THAT LIGHT LUMINAIRES RUN PARALLEL TO THE FACE OF THE EQUIPMENT AND OVER AISLES BETWEEN EQUIPMENT. INSTALL AT EXACT LOCATIONS AND AT EXACT HEIGHT TO ILLUMINATE ALL GAGES, PANELS, CONTROLS, VALVES, ETC. CHAIN HANGING, STEM HANGING, UNISTRUT HANGING, ETC. ARE ACCEPTABLE METHODS.

7. WHEN LUMINAIRES ARE INSTALLED IN CONTINUOUS ROWS OF TWO (2) OR MORE, LUMINAIRES SHALL BE APPROVED FOR USE AS WIREWAY.

8. COMPLETE CATALOG NUMBER IN THIS LIGHT FIXTURE SCHEDULE ARE NOT LISTED. ORDER LUMINAIRE BASED ON DESCRIPTION, PARTIAL CATALOG NUMBER AND SPECIFICATIONS. THE MANUFACTURER LISTED IS THE

BASIS-OF-DESIGN.

9. VERIFY COMPATIBILITY OF ALL DIMMING DRIVERS WITH SPECIFIED DIMMING CONTROLS PRIOR TO ORDERING AND PROVIDE APPROPRIATE COMPONENTS TO CREATE A COMPLETE AND FULLY FUNCTIONAL INSTALLATION.

10. ALL LUMINAIRES SHOWN ON THIS SCHEDULE MAY NOT BE USED ON THE VARIOUS PLANS. ALSO, THE USE OF ONLY CERTAIN NUMERICAL SUBSCRIPTS FOR LUMINAIRE TYPES (e.g. H2, H3, A2, A3, etc.) ON THIS PROJECT DOES

NOT NECESSARILY MEAN THAT ON H1 OR A1 IS USED OR MISSING.

11. CONTRACTOR IS RESPONSIBLE FOR ALL MISCELLANEOUS HARDWARE, CLIPS, ANGLES, FRAMES, ETC. AS REQUIRED TO MOUNT THE LUMINAIRES IN OR ON THE SURFACES THEY ARE TO BE INSTALLED.

12. WHEN VARYING FROM BASIS-OF-DESIGN LUMINAIRE, PROVIDE A LUMINAIRE UTILIZING ±10% OF THE LED LUMENS INDICATED IN LUMINAIRE SCHEDULE.

13. REFER TO SPECIFICATION SECTION 265100 LIGHTING FOR ADDITIONAL INFORMATION CONCERNING LUMINAIRES, FINISHES, DRIVERS, ETC.

14. ALL LUMINAIRES SHALL OPERATE AT 120 OR 277 VOLTS OR OTHER VOLTAGE AS REQUIRED BY THE CIRCUITS AND/OR PANELS TO WHICH THEY ARE CONNECTED.

15. WHEN INSTALLING LUMINAIRES, THE CONTRACTOR SHALL USE THE LUMINAIRE MANUFACTURER'S MOUNTING HARDWARE AND FOLLOW ALL MANUFACTURER'S INSTALLATION DIRECTIONS.

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

EL601

LIGHTING CONTROL SCHEDULE

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

TLKGF

# Revision Date

R E

F

F E

C

F E

C

F E

C

F E

C

F E

C

FEC

T

TT

N C

N C

NC NC

NC NC NCNC

N C

N C

N C

N C

N C

N C

N C

N C

N C

NC

NC

N C

N C

N C

N C

N C

N C

N C

NC

NC

NC

NC

N C

N C

N C

N C

N C

N C

NC

NC

N C

N C

NC

NC

NC

N C

NC

NC

EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb

2.8

3.7

7.3

8.2

9.1

4.5

6.2

5.4

5.7

5.3

4.6

10.2

9.8

8.9

8.3

7.2

7.1

3.6

4.1

4.7

5.1

6.1

6.3

8.0

5.5

7.5

3.1

4.4

8'-0"

4'-0"

8'-0" 8'-0"

4'-0" 4'-0" 4'-0"4'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

4'-0"

8'-0"

8'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

8'-0"

8'-0"

8'-0"

8'-0"

4'-0"

4'-0"

8'-0"

4'-0"

4'-0"

4'-0"

8'-0"

4'-0"

8'-0"

4'-0"

EXISTING

NCEQ

EXISTING

NCEQ

4'-0"

4'-0"

NCEQ

NURSE CALL SYSTEMS (ROUGH-IN ONLY)

PROVIDE (2) GANG BACK BOX WITH (1) GANG MUD RING AND

BLANK COVER PLATE. PROVIDE 1" CONDUIT WITH PULL STRING

FROM BACK BOX TO 6" ABOVE CEILING. CORRIDOR ACCESSIBLE

SPACE. END POINT OF CONDUIT, SHALL BE HAND ACCESSIBLE

AND REACHABLE.

NURSE CALL EQUIPMENT CABINET

RESPONSIBILITIES: RACEWAY AND BOXES: CONTRACTOR FURNISHED, INSTALLED

WIRING: BY OTHERS, NOT IN THIS CONTRACT

DEVICES: BY OTHERS, NOT IN THIS CONTRACT

NC

1. CONTRACTOR TO COORDINATE WITH OTHER

DISCIPLINE PRIOR TO INSTALLATION. REFER TO

COORDINATION REQUIREMENTS IN SPECS.

NURSE GENERAL NOTES

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

NOT FOR

CONSTRUCTION

GARY FISCHER, PE MO #2018021177

EN100

ELECTRICAL FLOOR PLAN - NURSE

CALL - 4TH FLOOR - OVERALL

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

TLKGF

1/8" = 1'-0"

ELECTRICAL 4TH FLOOR OVERALL NURSE CALL NEW WORK

# Revision Date

T

TT

J

J J

J

J J

J

J J J J

J

J

J

J

J

PS

PS

PS

PSPS

PS

PS

J J

PS

P S

J

JJ

J

J

J

J

J

JJ

J

J

J

J

J

EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb

2.8

3.7

7.3

8.2

9.1

4.5

6.2

5.4

5.7

5.3

4.6

10.2

9.8

8.9

8.3

7.2

7.1

3.6

4.1

4.7

5.1

6.1

6.3

8.0

5.5

7.5

3.1

4.4

EP400

FOURTH FLOOR KEY PLAN

N

B

A

1. CROSS HATCH AREA IS NIGHTS AND WEEK END WORK.

REFER TO ARCHITECT DRAWINGS FOR ADDITIONAL

INFORMATION ON PHASING.

SHEET KEYNOTES#

A

2 3 4 5 6

B

C

D

1 2 3 4 5 6

A

B

C

D

VA FORM 08-6231

o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title

Office of Construction and Facilities ManagementApproved: Project Director

Project Title

Location

Date Checked Drawn

Dwg.

Drawing Number

Building Number

Project Number

600 EAST 7TH STEET

SIOUX FALLS, SOUTH DAKOTA 57103

605.274.2893

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

800.404.7677

330 N MEAD

WICHITA, KANSAS 67202

316.262.2500

EP100

ELECTRICAL FLOOR PLAN - POWER -

4TH FLOOR - OVERALL

RELOCATE PHYSICAL

MEDICINE & REHAB. TO THE

4TH FLOOR

800 HOSPITAL DRIVE COLUMBIA, MO 65201

02-15-2023

589A4-22-100

BID DOCUMENTS

TLKGF

1/8" = 1'-0"

4TH FLOOR OVERALL NON-EQUIPMENT POWER NEW WORK

# Revision Date

File details come from the government source that posted it. Updated .