Drawings-589A4-22-100-2023-02-15 BID Set-Part8-pages 9.pdf
PDF 5 MB Posted
- Solicitation number
- 36C25523R0072
About this file
This document package includes construction drawings and specifications for a federal contract opportunity to relocate a Physical Medicine and Rehabilitation department to the fourth floor of a VA medical center. The solicitation is for mechanical demolition and new work, including removal of existing piping, ductwork, equipment and installation of new systems. Drawings show demolition plans, new work plans, schedules and details. The opportunity is identified as solicitation number 36C25523R0072 to be awarded by the Department of Veterans Affairs Veterans Health Administration VISN 15. Products and services required include demolition of mechanical, plumbing and HVAC systems on the third and fourth floors, and installation of new piping, ductwork, terminal units and associated mechanical systems to support the relocated department. Construction is to take place at the VA Medical Center located at 800 Hospital Drive in Columbia, Missouri.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEC
EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb
7.3
8.2
9.1
6.7
10.2
9.8
8.9
8.3
7.2
7.1
8.0
7.5
2"W CAPPED
ABOVE CEILING
CAPPED ABOVE CEILING
EX 4"S-UP&DN
EX 2"W-UP
EX 4"S-UP
S
EX 4"S-DN
EX 3"W-UP
EX 2"W-UP
S
CHIRO. EXAM
ACUPUNCTURE
ACUPUNCTURE
PT/OT EXAM
PT/OT EXAM
PELVIC
PELVIC
PT/OT EXAM BARIATRIC
PT/OT STOR.
PT TLT.
PROST. STOCK RM.
PT GYM
OT TRAIN. RM.
OT TLT.
440A
ELEC.
CLEAN LINEN
450A
EQUIP.
CORR.
C44
ELEV. LOBBY / CORR.
ELEV. LOBBY
SOILED DISP
401A
PROST. CHECKIN
405A
CORR.
C45
P-422
P-302
P-529
P-117
P-116
EX 2"W-UP
P-528
P-528
P-532
P-532
P-528
P-528
EX 4"
EX 3"VS-UP&DN
EX HWR-UP&DN
EX 4"S-UP&DN
EX HW-UP&DN
EX CW-UP&DN
EX MV-UP&DN
EX MA-UP&DN
EX OX-UP&DN
EX ST-UP&DN
EX 4"
EX 4"S-UP
EX 3"V-UP&DNEX. 4"S-UP
CAPPED ABOVE CEILING
EX 1 1/2"HWR-UP&DN
EX 2 1/2"HW-UP&DN
3"CW-UP&DN
EX 4"S-DN
EX 4"S-DN
EX 4"S-UP
EX 3"W-UP
EX 4"S-UP
EX. 4"S-UP
EX. 4"S-UP
EX. 3"W-UP
EX 4"S-UP
EX 3"V-UP
4"S-DN
3"V-DN
3"V-DN
EX 3"V-UP
EX 4"V-UP
EX 4"S-UP
EX ST-UP&DN
EX 4"S-UP
EX 3"V-UP
AREA B
AREA A
AREA B
AREA A
P-528
P-414
FD-B
P-531
FD-B
P-532
P-405
FD-B
P-414
P-610
P-116
FD-B
4"S-DN
4"S-DN
4"V-DN
1/2"HW
2"W/V
1/2"CW
2"
1/2"CW
2"W/V
1/2"HW
2"V-DN
1/2"CW
2"W/V
1/2"HW
2"V/4"S-DN
1 1/4"CW
1/2" 1 1/2"
1/2"
1 1/2"
1/2"
1 1/2"
1/2"
1/2"CW
1/2"HW
2"W/V
1/2"HW
1/2"CW
1/2"HW
2"W/V
1/2"CW
1/2"HW
2"W/V
1/2"CW
2"V-DN
1/2"HW
2"W/V
1/2"CW
2"V/4"S-DN
1 1/4"CW
1/2"HW
2"W/V
1/2"CW
1/2"HW
1/2"CW
2"W/V
2"W-DN
1 1/4"CW
2"V/4"S-DN
2"V-DN
1/2"CW
2"W/V
1/2"HW
2"
1/2"
1/2"CW
2"W/V
3/4"
3/4"
1/2"
3"
4"
4"
1/2"
1/2"
1/2"
1/2"
1/2"
2"
2"
2"
2"
2"
2"
2"
2"
2"V-DN
2"
2"
1/2"HW
2"W/V
1/2"CW
4"
PT/OT SWAMP
REHAB. COOR.
STAFF TLT.
TELE HEALTH
PSA
OT SUPER.
AO
CHIEF PM&R EXAM
BREAK RM.
WAIT.
CORR.
C42
WC STOR./SHOP
CORR.
C41
CORR.
C43
CBV-2
2"V-DN
1/2"
1/2"
1 1/2"
1/2"
1/2"
1 1/2"
1 1/2"
3/4"
1 1/2"
1"
1 1/2" 1"
1 1/4"
1 1/2"
3/4"
1 1/2"
1/2"
2"
1 1/4"
3/4"
3/4"
1/2"
1 1/4"
1 1/2"
1/2"
2"
1 1/4"
1/2" 2"
1 1/4"
2 1/2"
2 1/2"
EX 2"W-UP
4"V-DN
CBV-1
CBV-3
CBV-5
1/2"
SET AT
0.5 GPM
SET AT
0.5 GPM
SET AT
0.5 GPM
SET AT
0.5 GPM
P-809 9
1/2"
4"S-DN
FOURTH FLOOR KEY PLAN
AREA B
N
B
A
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
VA FORM 08-6231
o n e e ig h th in c o n e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e rs e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e s e fo o t th re e in c h e e fo o t
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Office of Construction and Facilities ManagementApproved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
600 EAST 7TH STEET
SIOUX FALLS, SOUTH DAKOTA 57103
605.274.2893
6 SOUTH OLD ORCHARD
ST. LOUIS, MISSOURI 63119
800.404.7677
330 N MEAD
WICHITA, KANSAS 67202
316.262.2500
JOHN ERNEST SOMMERS, PE
#2015028399
PP106
PLUMBING NEW WORK PLAN - 4TH
FLOOR - AREA B
RELOCATE PHYSICAL
MEDICINE & REHAB. TO THE
4TH FLOOR
800 HOSPITAL DRIVE COLUMBIA, MO 65201
02-15-2023
589A4-22-100
BID DOCUMENTS
MASJDB
3/16" = 1'-0"
PLUMBING NEW WORK PLAN - 4TH FLOOR - AREA B
1. MATCH EXISTING RISER SIZES.
2. NOT USED.
3. NOT USED.
4. NOT USED.
5. NOT USED.
6. NOT USED.
7. CONNECT NEW SINK TO EXISTING PLUMBING SANITARY
AND VENT ROUGH-IN.
8. REFER TO DETAIL #8 ON SHEET P-501 FOR
DISHWASHER DRAIN AND WATER CONNECTION.
9. INSTALL FILTRATION EQUIPMENT ABOVE ICE MAKER
UNIT. REFER TO DETAIL #9 ON SHEET P-501 FOR
FILTRATION COMPONENTS.
SHEET KEYNOTES#
# Revision Date
02/13/2023
CALIBRATED
BALANCING VALVE
SHUTOFF VALVE WITH THREADED
END CONNECTIONS (TYPICAL)
SEE PLANS
FOR PIPE SIZE
UNION
CALIBRATION
CONNECTION
POINTS
CHECK VALVE
NOTE:
0.3 GPM TO 0.7 GPM - B&G 1/2" RF MODEL OR EQUAL
0.75 GPM TO 1.0 GPM - B&G 3/4" RF MODEL OR EQUAL
1.25 GPM TO 2.5 GPM - B&G CB-1/2" MODEL OR EQUAL
SHUTOFF
VALVE (TYP.)
DIELECTRIC UNION
(TYP.)
TEMPERED
WATER TO
FIXTURES
THERMOMETER
THERMOSTATIC
MIXING VALVE
NOTE:
PROVIDE CHECK VALVE ON INLETS TO MIXING VALVES WHEN
CHECK STOPS ARE NOT PROVIDED IN MIXING VALVE ASSEMBLY.
DIRECTION
OF FLOW
CAST IRON
EXTENSION SAME
SIZE AS SEWER
UP TO 4" DIA.
FINISHED FLOOR
CLEANOUT WITH
COVER FOR DUTY
REQUIRED - SEE
SPECIFICATIONS
SEE
PLANS
BUILDING DRAIN/SEWER
(SIZE AS SPECIFIED)
CAST IRON LONG SWEEP 1/4
BEND OR CAST IRON COMB, "Y"
& 1/8 BEND. (USE REDUCING
TYPE WHERE REQUIRED)
INSULATED PIPING
PIPE SHIELD
MINIMUM 12" LONG
PIPE INSULATION
CLEVIS HANGER
THREADED HANGER ROD
THREADED HANGER ROD
PIPE INSULATION
PIPE
PIPE SHIELD
INSULATION INSERT (CALCIUM
SILICATE OR MOLDED
FIBERGLASS) BETWEEN PIPING
AND FINISHING JACKET
SECTION THRU HANGER
REFER TO SPECS FOR INSULATION
AND HANGER SUPPORTS.
TRAP
ARM
INCHES
MAXIMUM DISTANCE
TRAP TO VENT
FEET SLOPE (IN./FT.)
GENERAL NOTES:
1. FOR PIPE SIZES REFER TO
PLUMBING FIXTURE SCHEDULE
SANITARY PIPE
V E
N T
P
IP
E
FINISHED FLOOR
TABLE
1 1/4 1 1/2
4 & >
1/4 1/4 1/4 1/8 1/8
IPC
F 154-330
E 114-154
D 61-113
C 33-60
B 12-32
1-11A
SINGLE/ DOUBLE FIXTURE
FIXTURE
UNIT LOAD
PIPE
SIZE
WHA
SIZE
1/2"
3/4"
1"
1 1/4"
1 1/2"
2"
HOT OR COLD
WATER SUPPLY IF BRANCH IS GREATER THAN 20'
LONG, PROVIDE AN ADDITIONAL WHA
IN MIDDLE OF RUN. EACH SIZED
FOR HALF THE FIXTURE UNITS.
IF HORIZONTAL BRANCH IS
LESS THAN 20' LONG, PROVIDE
ONE WHA AT END OF LINE.
FIXTURE (TYPICAL)
NOTE: INSTALL PER
MANUFACTURER'S
INSTRUCTIONS. PROVIDE A WHA AT
ALL QUICK-CLOSING VALVES.
THREADED
ROD
TYPICAL 10 GAUGE
GALVANIZED PIPE
SHIELD
DOUBLE LOCKING NUT
WITH SINGLE WASHER
AT TOP AND BOTTOM
OF CHANEL STRUT
(TYPICAL)
12 GAUGE UNISTRUT
CHANNEL WITH SLOTS
UNINSULATED
PIPING
INSULATED
PIPING
PIPING INSULATION
DO NOT CRUSH
STRUT MOUNTED
IPS PIPE STRAP
NOTE:
1. HANGER ROD, NUTS, WASHER AND
PIPE STRAPS SHALL BE OF ZINC
COATED GALVANIZED PLATED
MATERIAL
2. REFER TO SPECS FOR INSULATION.
USE ISOLATION TAPE WHEN
CLAMPING UNINSULATED
NON-FERROUS PIPE
BACKSPLASH
FINISHED
FLOOR
2 COMP. SINK
ANGLE STOP
NOTE:
SIMILAR FOR OPPOSITE HAND. VERIFY FIELD CONDITIONS
PRIOR TO INSTALLATION.
DUAL OUTLET
ANGLE STOP
1/2" HW TO
DISHWASHER
DRAIN PUMP
DISHWASHER
FLEXIBLE
DRAIN
DISHWASHER
AIR GAP FITTING
COUNTERTOP
FINISHED FLOOR
P-809 IN WALL
WATER FILTER (OWNER-
FURNISHED, CONTRACTOR-
INSTALLED)
15"
(APPROXIMATE)
P-809, PIPING AND WATER FILTER
LOCATED ABOVE ICE MACHINE.
ALLOW FOR SUFFICIENT SPACE FOR
COMPONENTS WHEN LOCATING
P-809.
ICE MACHINE (OWNER
FURNISHED, CONTRACTOR
INSTALLED)
FINISHED FLOOR
MOP BASIN
5'-0" MAXIMUM5'-6" MAXIMUM
MOP SINK FAUCET
3/8" WATTS LF009 SERIES RPZ
PIPING TO CHEMICAL DISPENISING
UNIT DOWNSTREAM OF RPZ BY
OWNER.
3/8" FLEXIBLE STAINLESS HOSE
SUPPLIED (TYP OF 3)
AIR GAP FITTING
TERMINATE OVER SINK
PROVIDE 1/2" STUB OUT WITH 1/2" BALL
VALVE AND THREADED END PIECE FOR
HOSE CONNECTION
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
VA FORM 08-6231
o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Office of Construction and Facilities ManagementApproved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
600 EAST 7TH STEET
SIOUX FALLS, SOUTH DAKOTA 57103
605.274.2893
6 SOUTH OLD ORCHARD
ST. LOUIS, MISSOURI 63119
800.404.7677
330 N MEAD
WICHITA, KANSAS 67202
316.262.2500
JOHN ERNEST SOMMERS, PE
#2015028399
P-501
PLUMBING DETAILS
RELOCATE PHYSICAL
MEDICINE & REHAB. TO THE
4TH FLOOR
800 HOSPITAL DRIVE COLUMBIA, MO 65201
02-15-2023
589A4-22-100
BID DOCUMENTS
MASJDB
NONE
CALIBRATED BALANCING VALVE
NONE
EMERGENCY EYEWASH THERMOSTATIC
MIXING VALVE
NONE
FLOOR CLEANOUT
NONE
INSULATED PIPE HANGER SUPPORT
NONE
TRAP TO VENT MAXIMUM DISTANCE
NONE
WATER HAMMER ARRESTOR SCHEMATIC
NONE
TRAPEZE PIPE SUPPORT
NONE
DISHWASHER DRAIN
NONE
NONE
CHEMICAL DISPENSING UNIT WATER SUPPLY AT MOP BASIN
# Revision Date
ICE MACHINE WATER SUPPLY DETAIL
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
VA FORM 08-6231
o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Office of Construction and Facilities ManagementApproved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
600 EAST 7TH STEET
SIOUX FALLS, SOUTH DAKOTA 57103
605.274.2893
6 SOUTH OLD ORCHARD
ST. LOUIS, MISSOURI 63119
800.404.7677
330 N MEAD
WICHITA, KANSAS 67202
316.262.2500
JOHN ERNEST SOMMERS, PE
#2015028399
NOT FOR
CONSTRUCTION P-601
PLUMBING SCHEDULES
RELOCATE PHYSICAL
MEDICINE & REHAB. TO THE
4TH FLOOR
800 HOSPITAL DRIVE COLUMBIA, MO 65201
02-15-2023
589A4-22-100
BID DOCUMENTS
MASJDB
PLUMBING FIXTURE SCHEDULE
PLAN
MARK
DESCRIPTION MANUFACTURER MODEL TRIM DRAIN / TRAP SUPPLIES CARRIER SEAT
HOT
WATER
COLD WATER
TEMPERED
WATER
SANITARY /
WASTE
VENT NOTES
P-116 FLOOR MOUNT WALL OUTLET WATER CLOSET - ADA ZURN Z5645-BWL
ZURN MODEL ZER6000AV-CPM-WS1, BATTERY POWERED, SENSOR OPERATED, FLUSH VALVE,
1.6 GPF
INTEGRAL - - BEMIS - 1-1/4" - 4" 2"
P-117
FLOOR MOUNT WALL OUTLET WATER CLOSET
STANDARD HEIGHT
ZURN Z5634-BWL
ZURN MODEL ZER6000AV-CPM-WS1, BATTERY POWERED, SENSOR OPERATED, FLUSH VALVE,
1.6 GPF
INTEGRAL - - BEMIS - 1-1/4" - 4" 2"
P-203 WALL HUNG URINAL ZURN Z5755-WS1-LL
ZURN MODEL ZER6003AV-CPM-WS1, BATTERY POWERED, SENSOR OPERATED, FLUSH VALVE,
1.0 GPF
INTEGRAL - WADE - - 3/4" - 2" 2"
P-204 WALL HUNG URINAL - ADA ZURN Z5755-WS1-LL
ZURN MODEL ZER6003AV-CPM-WS1, BATTERY POWERED, SENSOR OPERATED, FLUSH VALVE,
1.0 GPF
INTEGRAL - WADE - - 3/4" - 2" 2"
P-302 SINGLE-PIECE FIBERGLASS TUB / SHOWER MODULE BESTBATH STS6032A17 SYMMONS SHOWER / TUB SYSTEM MODEL S-9602-P-1.5, 1.5 GPM - - - - - - - - -
TUB / SHOWER TO NOT BE CONNECTED WITH DRAINAGE OR WATER SUPPLY. CONTRACTOR TO
PERMANTLY PLUG SHOWER DRAIN.
P-404 INTEGRAL BOWL LAVATORY BY OTHERS -
CHICAGO FAUCETS MODEL 895-317GN2AE72ABCP, 4" FIXED CENTERS, LAMINAR FLOW AT 0.5
GPM
PROVIDE WITH DRAIN PLUG - - - 1/2" 1/2" - 2" 2"
P-405 INTEGRAL LAVATORY BY OTHERS -
ARMSTRONG RADA FAUCET MODEL MX1-20, PROGRAMMABLE SENSOR OPERATED BATTERY
POWERED FAUCET
1 1/4" 17 GA CHROME PLATED BRASS P-TRAP W/ CLEANOUT 1/2" CHROME PLATED LOOSE KEY ANGLE STOPS WADE - 1/2" 1/2" - 2" 2"
INSULATE SUPPLY AND WASTE PIPING WITH TRUBRO #102 WHITE INSULATION KIT WITH #105 OFFSET
DRAIN INSULATION KIT. NON-AERATED OUTLET.
P-414 WALL HUNG LAVATORY - ADA ZURN Z5340
CHICAGO FAUCETS MODEL 895-317GN2AE72ABCP, 4" FIXED CENTERS, LAMINAR FLOW AT 0.5
GPM
1 1/4" 17 GA CHROME PLATED BRASS P-TRAP W/ CLEANOUT 1/2" CHROME PLATED LOOSE KEY ANGLE STOPS WADE - 1/2" 1/2" - 2" 2"
INSULATE SUPPLY AND WASTE PIPING WITH TRUBRO #102 WHITE INSULATION KIT WITH #105 OFFSET
DRAIN INSULATION KIT. 0.5 GPM NON-AERATED OUTLET.
P-422 WALL HUNG LAVATORY, BARIATRIC WILLOUGHBY BHS-3123-WB1-4CC-GW-AW PROVIDED WITH FIXTURE. 1 1/4" 17 GA CHROME PLATED BRASS P-TRAP W/ CLEANOUT 1/2" CHROME PLATED LOOSE KEY ANGLE STOPS WADE - 1/2" 1/2" - 2" 2"
P-502 MOP BASIN FIAT TSBCR1000 SERIES CHICAGO FAUCETS MODEL 897-CCP, WALL MOUNTED MANUAL FAUCET W/ 8" BODY 3" CAST IRON P-TRAP INTEGRAL SUPPLY STOPS - - 1/2" 1/2" - 3" 2" #T-35 HOSE AND WALL BRACKET. 36" HOSE WITH 3/4" CHROME COUPLING. TYPE 302 STAINLESS STEEL
BRACKET WITH SPRING LOADED RUBBER GRIP.
P-528 SINGLE BOWL S/S SINK ELKAY LRAD221965
CHICAGO FAUCETS MODEL 895-317GN8AE73ABCP, MANUAL FAUCET W/ 4" WRISTBLADE, ON 4"
FIXED CENTERS W/ 8" GOOSENECK LAMINAR FLOW 1.0 GPM
1 1/2" 17 GA CHROME PLATED BRASS P-TRAP W/ CLEANOUT 1/2" CHROME PLATED LOOSE KEY ANGLE STOPS - - 1/2" 1/2" - 2" 2" 1.0 GPM NON-AERATED
P-529 DOUBLE BOWL S/S SINK ELKAY LR3322PD
CHICAGO FAUCETS MODEL 786-GN8AE36ABCP, MANUAL FAUCET ON 8" CENTERS W/ 8"
GOOSENECK FAUCET, 4" WRISTBLADES, LAMINAR FLOW 1.5 GPM
1 1/2" 17 GA CHROME PLATED BRASS P-TRAP W/ CLEANOUT 1/2" CHROME PLATED LOOSE KEY ANGLE STOPS - - 1/2" 1/2" - 2" 2" 1.5 GPM NON-AERATED
P-531
SINGLE BOWL FLOOR MOUNT S/S SCULLERY SINK W/
DRAINBOARD
ELKAY WNSF8124R2
CHICAGO FAUCETS MODEL 631-GN10AE35SWGAB, WALL MOUNTED MANUAL FAUCET W/ 8"
BODY, 10" GOOSENECK SWING SPOUT W/ 4" WRISTBLADE, 1.5 GPM
1 1/2" 17 GA CHROME PLATED BRASS P-TRAP W/ CLEANOUT INTEGRAL SUPPLY STOPS - - 1/2" 1/2" - 2" 2"
P-532 SINGLE BOWL S/S SINK ELKAY LRAD221965
CHICAGO FAUCETS MODEL 895-317GN8AE73ABCP, MANUAL FAUCET W/ 4" WRISTBLADE, ON 4"
FIXED CENTERS W/ 8" GOOSENECK LAMINAR FLOW 1.0 GPM
1 1/2" 17 GA CHROME PLATED BRASS P-TRAP W/ CLEANOUT 1/2" CHROME PLATED LOOSE KEY ANGLE STOPS - - 1/2" 1/2" - 2" 2"
1.0 GPM NON-AERATED, PROVIDE WITH WADE LAVATORY CARRIER WITH ROUND UPRIGHTS,
RECTANGULAR BASE FEET, AND A.R.C. EXPOSED ARMS TOP SUPPORT COUNTERTOP, REFER TO
ARCHITECTURAL DRAWINGS FOR LAVATORY DETAIL.
P-533 SINGLE BOWL FLOOR MOUNT S/S SCULLER SINK ELKAY IC24X24-0-X
CHICAGO FAUCETS MODEL 631-GN10AE35SWGAB, WALL MOUNTED MANUAL FAUCET W/ 8"
BODY, 10" GOOSENECK SWING SPOUT W/ 4" WRISTBLADE, 1.5 GPM
1 1/2" 17 GA CHROME PLATED BRASS P-TRAP W/ CLEANOUT INTEGRAL SUPPLY STOPS - - 1/2" 1/2" - 2" 2"
P-610
ELECTRIC WATER COOLER - BI-LEVEL W/ BOTTLE
FILLER
ELKAY LVRCGRNTL8WSK - CHROME PLATED P-TRAP CHICAGO FAUCET LOOSE KEY ANGLE STOPS AND RISERS ELKAY - - 1/2" - 2" INSTALL BOTTLE FILLER ON LOWER BI-LEVEL WATER FOUNTAIN.
P-709 SINK MOUNTED DRENCH HOSE EYEWASH W/ TMV GUARDIAN G5022BP / G6020 - - - - - - - 1/2" - - TMV TO BE MOUNTED AND INSTALLED BELOW SINK CASEWORK IN AN ACCESSIBLE LOCATION.
P-809 OUTLET BOX WITH SINGLE WATER VALVE SIOUX CHEIF 696-G1010MF - - INTEGRAL - - - 1/2" - - -
DRAIN SCHEDULE
PLAN MARK DESCRIPTION MANUFACTURER MODEL BODY STRAINER NOTES
FD-B SQUARE FLOOR DRAIN WADE 1100-G-1-2NH-4405 CAST IRON
NICKEL
BRONZE
FD-E
SQUARE FLOOR DRAIN
W/ FUNNEL
WADE
1100-G-1-2NH-4405
/ EF4-39
CAST IRON
NICKEL
BRONZE
PROVIDE WITH TRAP GUARD.
BALANCING VALVE SCHEDULE
PLAN
MARK
DESCRIPTION SIZE
ADJUSTED
FLOW RATE
NOTES
CBV-1
CALIBRATED
BALANCING VALVE
1/2" 0.5 GPM
CBV-2
CALIBRATED
BALANCING VALVE
1/2" 0.5 GPM
CBV-3
CALIBRATED
BALANCING VALVE
1/2" 0.5 GPM
CBV-4
CALIBRATED
BALANCING VALVE
1/2" 0.5 GPM
CBV-5
CALIBRATED
BALANCING VALVE
1/2" 0.5 GPM
# Revision Date
JOHN ERNEST SOMMERS, PE
#2015028399
N
X
M
T
PIPE LINE SYMBOLS
SHUT OFF VALVE (SEE
SPECIFICATION FOR TYPE)
GATE VALVE
BALL VALVE
BUTTERFLY VALVE
VALVE IN RISE (SEE SPECIFICATION FOR TYPE)
MULTI-PURPOSE PUMP DISCHARGE VALVE
CHECK VALVE
SOLENOID VALVE
PRESSURE REDUCING VALVE (HYDRONIC)
PRESSURE REGULATING VALVE (STEAM)
CALIBRATED - ORIFICE BALANCING VALVE
ACTIVE FLOW-LIMITING VALVE
PLUG VALVE
IN-LINE PUMP
Y-PATTERN STRAINER
Y-PATTERN STRAINER W/ BLOWDOWN VALVE
UNION
AIR VENT (M - MANUAL, A - AUTOMATIC)
RELIEF VALVE
VACUUM BREAKER
PRESSURE AND TEMPERATURE TEST PORT
THERMOMETER
PRESSURE GAGE WITH COCK
FLEX PIPE COUPLING
PIPE ANCHOR
PIPE GUIDE
PITCH DOWN IN DIRECTION OF ARROW
WATER METER
STEAM TRAP
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
MOTORIZED BUTTER FLY VALVE
GLOBE VALVE
A
UNIT NUMBER
EQUIPMENT DESIGNATION
TYPE OF SERVICE: S = SUPPLY
R = RETURN
E = EXHAUST
T = TRANSFER
AIR QUANTITY
IN CFM
SCHEDULED
DEVICE NO
UNIT NUMBER
DAMPER TYPE DESIGNATION
AIRFLOW MEASURING STATION
EXISTING EQUIPMENT DESIGNATION
S-1
FSD
AHU
AHU-1
ID-#
HVAC SENSOR
SENSOR TYPE
OPTIONS
SPECIALTY SENSOR TYPE
I = INSULATED BASE
G= PROVIDE GUARD
CO = CARBON MONOXIDE
CO2= CARBON DIOXIDE
NG = NATURAL GAS
T = TEMPERATURE SENSOR
H = HUMIDITY SENSOR
O = OCCUPANCY SENSOR
R = REFRIGERANT SENSOR
P = PRESSURE SENSOR
MECHANICAL SYMBOLS
ASSOCIATED UNIT
X Y
Z
ACCESS PANEL, TOP OR SIDE
TURNING VANES
MOTORIZED DAMPER
GRAVITY BACKDRAFT DAMPER
MANUAL VOLUME DAMPER
FIRE DAMPER
SMOKE DAMPER
FIRE/SMOKE DAMPER
FLOW ARROW DOWNSTREAM OF FAN
FLOW ARROW UPSTREAM OF FAN
SUPPLY DIFFUSER AS SCHEDULED. ARROWS INDICATE
DIRECTION OF AIR DISCHARGE. IF NO ARROWS ARE
SHOWN ON PLAN, DEFAULT IS A 4-WAY THROW
RETURN GRILLE OR REGISTER AS SCHEDULED
EXHAUST GRILLE OR REGISTER AS SCHEDULED
SLOT DIFFUSER AS SCHEDULED. ARROWS INDICATE DIRECTION
OF AIR DISCHARGE. IF NO ARROWS ARE SHOWN ON PLAN,
DEFAULT IS 2-WAY THROW
SIDEWALL DIFFUSER AS SCHEDULED
SIDEWALL RETURN OR EXHAUST AS SCHEDULED
DUCT SYSTEM SYMBOLS
12x12
12ø
12x10ø
FLEXIBLE DUCT
ROUND DUCT SIZE, (ACTUAL SIZE INDICATED)
CHANGE OF ELEVATION - RISE (R) OR DROP (D)
FLEXIBLE DUCT CONNECTION
SUPPLY AND OUTSIDE AIR SECTION UP
RETURN AIR SECTION UP
SPIRAL FLAT-OVAL DUCT SIZE, FIRST FIGURE
IS SIDE SHOWN (ACTUAL SIZE INDICATED)
R
DUCT SIZE, FIRST FIGURE IS SIDE
SHOWN (CLEAR INSIDE, ADJUST FOR
LINER)
SUPPLY AND OUTSIDE AIR SECTION DOWN
RETURN AIR SECTION DOWN
EXHAUST AIR SECTION UP
EXHAUST AIR SECTION DOWN
REFRIGERANT VENTRV
CHEMICAL FEEDCF
V VENT
NATURAL GASG
LPG LIQUEFIED PETROLEUM GAS
CW COLD WATER, DOMESTIC
CWS
CA
CWR
GLS
FOV
FOR
FOS
CR
CS
GLYCOL SUPPLY
FUEL OIL VENT
FUEL OIL RETURN
FUEL OIL SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CHILLED WATER RETURN
CHILLED WATER SUPPLY
COMPRESSED AIR
CHR
CHS
LPS
HWS
HWR
HPR
HPS
GLR
LPR
HG
RS
RL
PC
CHILLED/HOT WATER RETURN
CHILLED/HOT WATER SUPPLY
REFRIGERANT HOT GAS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
PUMPED CONDENSATE
LOW PRESSURE CONDENSATE RETURN (15 PSIG)
LOW PRESSURE STEAM SUPPLY (15 PSIG)
HEATING WATER SUPPLY
HEATING WATER RETURN
HIGH PRESSURE CONDENSATE RETURN (100 PSIG)
HIGH PRESSURE STEAM SUPPLY (100 PSIG)
GLYCOL RETURN
SRV STEAM RELIEF VENT
PUMP DISCHARGE
DRAIND
PD
FUEL OIL FILLFOF
E EQUALIZING LINE
DOMESTIC HOT WATERHW
MU MAKE-UP WATER (NON-POTABLE)
PRIMARY CHILLED WATER RETURNPCWR
PRIMARY CHILLED WATER SUPPLYPCWS
PRIMARY HEATING WATER SUPPLY
PRIMARY HEATING WATER RETURN
PHWS
PHWR
SHWS SECONDARY HEATING WATER SUPPLY
SECONDARY HEATING WATER RETURNSHWR
SECONDARY CHILLED WATER SUPPLY
SECONDARY CHILLED WATER RETURN
SCWS
SCWR
BLOW DOWNBD
CD CONDENSATE (STEAM) DRAIN
MPS
MPR
MEDIUM PRESSURE CONDENSATE
RETURN (60 PSIG)
MEDIUM PRESSURE STEAM SUPPLY (60PSIG)
PIPE SYSTEM ABBREVIATIONS
HCR
HCS
INDUCTION UNIT RETURN
INDUCTION UNIT SUPPLY
MECH EQUIPMENT DESIGNATION
MECH EQUIPMENT DESIGNATION
AC AIR CURTAIN
ACC AIR COOLED CONDENSER
ACU AIR CONDITIONING UNIT
ACV AIR CONTROL VALVE
AF AIR FILTER
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
ATU AIR TERMINAL UNIT
B BOILER
BCU BLOWER COIL UNIT
BS BASKET STRAINER
BT BUFFER TANK
CAV CONSTANT AIR VOLUME
CB CHILLED BEAM
CC COOLING COIL
CFP CHEMICAL FEED PUMP
CH CHILLER
CP CONDENSER WATER PUMP
CRAC COMPUTER ROOM AIR CONDITIONING UNIT
CRP CONDENSATE RETURN PUMP
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CTF COOLING TOWER FILTER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CVR CONVECTOR
CWP CHILLED WATER PUMP
DFH DEAERATING FEEDWATER HEATER
DHU DESSICANT DEHUMIDIFICATION UNIT
DMC DUCT MOUNTED COIL
EAV EXHAUST AIR VALVE
EF EXHAUST FAN
EJ EXPANSION JOINT
ERU ENERGY RECOVERY UNIT
ET EXPANSION TANK
EVC EVAPORATIVE COOLER
F FAN
FAV FUME AIR VALVE
FC FLUID COOLER
FCU FAN COIL UNIT
FD FIRE DAMPER
FFU FAN FILTER UNIT
FSD COMBINATION FIRE/SMOKE DAMPER
FT FLASH TANK
FTR FIN-TUBE RADIATION
FTU FAN TERMINAL UNIT
FUR GAS FIRED FURNACE (*NEED APPROVAL)
GMU GLYCOL MAKEUP UNIT (*NEED APPROVAL)
GP GLYCOL PUMP
GV GRAVITY VENTILATOR
H HUMIDIFIER
HC HEATING COIL
HEV HOOD EXHAUST VALVE
HPU HEAT PUMP UNIT
HRU HEAT RECOVERY UNIT
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
L LOUVER
MAU MAKE-UP AIR UNIT
MD MOTORIZED DAMPER
P PUMP
PAC PACKAGED AIR CONDITIONING UNIT
PCWP PRIMARY CHILLED WATER PUMP
PG PIPE GUIDE
PHWP PRIMARY HEATING WATER PUMP
PHX PLATE HEAT EXCHANGER
PRV PRESSURE REGULATING VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
RF RETURN FAN
RHC TERMINAL REHEAT COIL
RP RADIANT PANEL
RTU ROOFTOP UNIT
RV ROOF VENTILATOR (*NEED APPROVAL)
SA SOUND ATTENUATOR
SAV SUPPLY AIR VALVE
SCWP SECONDARY CHILLED WATER PUMP
SD SMOKE DAMPER
SF SUPPLY FAN
SHWP SECONDARY HEATING WATER PUMP
SPP STEAM PRESSURE PUMP
SSCU SPLIT SYSTEM CONDENSING UNIT (*NEED APPROVAL)
SSFU SPLIT SYSTEM FAN/COIL UNIT (*NEED APPROVAL)
ST STEAM TRAP
T TANK
TCP TEMPERATURE CONTROL PANEL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VFD VARIABLE FREQUENCY DRIVE
VI VIBRATION ISOLATION
VRF VRF INDOOR UNIT
VRHU VRF HEAT RECOVERY UNIT (*NEED APPROVAL)
WCC WATER COOLED CONDENSER
WSHP WATER SOURCE HEAT PUMP
MECHANICAL ABBREVIATIONS
A AIR OR AMP (PER CONTEXT)
ACC ACCESSORIES
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AFS AIR FLOW SWITCH
AHRI AIR CONDITIONING, HEATING, AND
REFRIGERATION INSTITUTE
AI ANALOG SIGNAL INPUT
AMB AMBIENT
AO ANALOG SIGNAL OUTPUT
AP ACCESS PANEL
APD AIR PRESSURE DROP
APLV APPLICATION PART LOAD VALUE
APPROX APPROXIMATE
ARCH ARCHITECTURE/ARCHITECT
AUX AUXILIARY
AV AUTOMATIC VENT
AVG AVERAGE
BDD BACK DRAFT DAMPER
BFC BELOW FINISHED CEILING
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BI BINARY SIGNAL INPUT
BMS BUILDING MANAGEMENT SYSTEM
BO BINARY SIGNAL OUTPUT
BOB BOTTOM OF BEAM
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BS BEAM SPACE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
BWE BAKED WHITE ENAMEL
CAP CAPACITY
CAV CONSTANT AIR VOLUME
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CLG COOLING DUCT (COLD DUCT)
CO CLEAN OUT
COMP COMPRESSOR
CONC CONCRETE
COND CONDENSATE
CONN CONNECTION
CORR CORRIDOR
CV CONTROL VALVE
D DEPTH
DB DRY BULB
DBA A-WEIGHTED DECIBELS
DEFL DEFLECTION
DEG DEGREES
DEG F DEGREES FAHRENHEIT
DES DESIGN
DIA DIAMETER
DIM DIMENSION
DISCH DISCHARGE
DIV DIVISION
DN DOWN
DP DIFFERENTIAL PRESSURE SENSOR
DPS DIFFERENTIAL PRESSURE SWITCH
DPT DIFFERENTIAL PRESSURE TRANSMITTER
DTL DETAIL
DWG(S) DRAWING(S)
EA EXHAUST AIR OR EACH (PER CONTEXT)
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENT RATIO
EFF EFFICIENCY
ELEC ELECTRIC
ELEV ELEVATION
EQ EQUAL
ESP EXTERNAL STATIC PRESSURE
EWB ENTERING AIR WET BULB TEMPERATURE
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST, EX EXISTING
EXT EXTERNAL
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
FC FLEXIBLE CONNECTION
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FIN FINISHED
FLR FLOOR
FPF FINS PER FOOT
FPM FEET PER MINUTE
FS FLOW SWITCH
FT FEET
FT-HD HEAD IN FEET
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
H HEIGHT
HD HEAD
HEV HOSE END VALVE
HORIZ HORIZONTAL
HP HORSEPOWER
HR HOUR
HTG HEATING DUCT (HOT DECK)
HVAC HEATING, VENTILATING & AIR
CONDITIONING
HW HOT WATER
HZ HERTZ
IB INVERTED BUCKET
IE INVERT ELEVATION
IN INCH/INCHES
INDIC INDICATOR
IPLV INTEGRATED PART-LOAD VALUE
ISP INTERNAL STATIC PRESSURE
JS JOIST SPACE
KW KILOWATTS
L LENGTH
LAT LEAVING AIR TEMPERATURE
LB(S) POUNDS
LF LINEAR FEET
LRA LOCKED ROTOR AMPS
LS LIGHT SPACE
LVL LEVEL
LWT LEAVING WATER TEMPERATURE
MAN MANUAL
MANU MANUFACTURER
MAX MAXIMUM
MBH THOUSAND BRITISH THERMAL UNITS PER
HOUR
MCA MINIMUM CIRCUIT AMPS
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MERV MINIMUM EFFICIENCY REPORTING VALUE
(ASHRAE 52.2)
MFR MANUFACTURER
MIN MINIMUM OR MINUTE (PER CONTEXT)
MTD MOUNTED
MTL METAL
MV MANUAL VENT
NC NORMALLY CLOSED OR NOISE CRITERIA
(PER CONTEXT)
NIC NOT IN CONTRACT
NO NORMALLY OPEN OR NUMBER (PER CONTEXT)
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
OT OIL TRAP
PA PIPE ANCHOR
PBD PARALLEL BLADE DAMPER
PD PRESSURE DROP
PENT PENTHOUSE
PH PHASE
PHC PREHEAT COIL
PLBG PLUMBING
PNEU PNEUMATIC
PPH POUNDS PER HOUR
PRESS PRESSURE
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
QTY QUANTITY
RA RETURN AIR
RAD RADIATED
RD ROOF DRAIN
REFR REFRIGERANT
REQ REQUIRED
RH RELATIVE HUMIDITY
RLA RUNNING LOAD AMPS
RM ROOM
RND ROUND
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAN SANITARY
SEC'N SECTION
SEER SEASONAL ENERGY EFFICIENCY RATIO
SENS SENSIBLE
SF SQUARE FOOT
SH SENSIBLE HEAT
SHT SHEET
SND SOUND
SOL SOLENOID
SP STATIC PRESSURE
SPD STATIC PRESSURE DIFFERENTIAL
SPT STATIC PRESSURE TRANSMITTER
SQ SQUARE
SST STAINLESS STEEL
STL STEEL
STM STEAM
T&P TEMPERATURE AND PRESSURE
TC TEMPERATURE CONTROL
TD THERMODYNAMIC OR TEMPERATURE
DIFFERENTIAL (PER CONTEXT)
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TOT TOTAL
TPD TOTAL PRESSURE DROP
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UC UNDERCUT DOOR
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
V VOLTS
VAC VACUUM
VD VOLUME DAMPER (MANUAL)
VEL VELOCITY
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VTR VENT THRU ROOF
W WATT OR WIDTH (PER CONTEXT)
W/ WITH
W/O WITHOUT
WB WET BULB
WC WATER COLUMN
WG WATER GAUGE
WPD WATER PRESSURE DIFFERENTIAL
WT WEIGHT
MECHANICAL PROJECT GENERAL NOTES
1. ALL ELBOWS, FITTINGS, ETC., IN PIPING AND DUCTWORK REQUIRED
TO CLEAR ALL JOB OBSTRUCTIONS ARE NOT NECESSARILY
INDICATED. ALL NECESSARY TRANSITIONS, FITTINGS AND OFFSETS
ARE REQUIRED WHETHER SHOWN OR NOT.
2. BECAUSE OF THE LIMITED SPACE AVAILABLE TO INSTALL ALL OF THE
MECHANICAL WORK, COORDINATION BETWEEN THE VARIOUS
TRADES IS OF THE UTMOST IMPORTANCE. SEE SPECIFICATION
230100 FOR REQUIRED COORDINATION DRAWINGS.
3. THE CONTRACTOR SHALL COORDINATE STAGING AND SCHEDULING
WITH THE OWNER'S REPRESENTATIVE.
4. EXISTING CONDITIONS ARE BASED ON INFORMATION OBTAINED
FROM PREVIOUS CONSTRUCTION DOCUMENTS AND INFORMAL
FIELD OBSERVATION AND SHALL NOT BE CONSTITUTED AS "AS
BUILT." THE CONTRACTOR SHALL FIELD-VERIFY EXISTING
CONDITIONS BEFORE THE ONSET OF CONSTRUCTION.
5. DEMOLISH ALL PIPING, DUCTWORK EQUIPMENT, ETC., SHOWN TO BE
REMOVED, IN ITS ENTIRETY, INCLUDING ALL HANGERS AND
SUPPORTS.
6. WHERE CONTRACTOR IS REQUIRED TO CONCEAL NEW WORK,
REMOVE OR MODIFY EXISTING CONSTRUCTION OR EQUIPMENT, OR
ATTACH TO EXISTING CONSTRUCTION, THE CONTRACTOR SHALL
REPAIR OR REPLACE EXISTING CONSTRUCTION AND MATERIALS TO
MATCH CONDITIONS AT THE ONSET OF CONSTRUCTION. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO REMOVE AND REPLACE
EXISTING CEILINGS AND WALLS REQUIRED FOR INSTALLATION OF
MECHANICAL SYSTEMS.
7. THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF EQUIPMENT
AND MATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT
CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE PREMISES
BY THIS CONTRACTOR.
8. CONTRACTOR SHALL PROVIDE SEISMIC BRACING AND MOUNTING OF
EQUIPMENT AND MATERIALS IN COMPLIANCE WITH ALL LOCAL CODE
REQUIREMENTS AND THE REQUIREMENTS OF SPECIFICATION
SECTION SEISMIC PROTECTION.
9. ALL WORK SHALL BE INSTALLED PER THE REFERENCE DETAILS,
REGARDLESS OF WHETHER OR NOT THE DETAILS ARE CALLED OUT
ON THE PLANS.
10. PROVIDE VENTS AT ALL HYDRONIC PIPING HIGH POINTS, AND
DRAINS AT ALL PIPING LOW POINTS, REGARDLESS OF WHETHER
SHOWN OR NOT.
11. THE CONTRACTOR SHALL VERIFY ALL REFRIGERANT PIPE SIZING
AND ROUTINGS WITH THE EQUIPMENT MANUFACTURER. THE
CONTRACTOR SHALL ALSO PROVIDE ALL REQUIRED REFRIGERANT
ACCESSORIES AS RECOMMENDED BY THE EQUIPMENT
MANUFACTURER FOR COMPLETE AND FULLY FUNCTIONAL SYSTEMS.
12. DO NOT SCALE THE LOCATION OF HVAC CEILING ELEMENTS, SUCH
AS AIR INLETS AND OUTLETS, FROM THE M-SERIES DRAWINGS. SEE
ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT HVAC
CEILING ELEMENT LOCATIONS. REFLECTED CEILING PLANS GOVERN
THE LOCATION OF DIFFUSERS, REGISTERS, AND GRILLES. M-SERIES
DRAWINGS GOVERN TYPE, STYLE, AND SIZE OF DIFFUSERS,
REGISTERS, AND GRILLES.
13. ALL DUCTWORK SHALL COMPLY WITH "HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE," 3RD EDITION, SMACNA 2005,
EXCEPT WHERE MORE RESTRICTIVE REQUIREMENTS ARE
SPECIFIED. ANY PLAN REFERENCES TO "SMACNA FIGURE ---"
REFERS TO THIS STANDARD. SEE SPECIFICATIONS FOR SCHEDULE
OF DUCT PRESSURE CLASS AND SEAL CLASS.
14. IN GENERAL, THE FINAL FLEX DUCT RUNOUT TO EACH DIFFUSER,
REGISTER, OR GRILLE IS NOT SIZED ON PLANS. FLEX DUCT RUNOUT
SIZE SHALL MATCH AIR OUTLET NECK SIZE, UNO.
15. IT IS THE INTENT OF THESE DRAWINGS THAT A MANUAL BALANCING
DAMPER BE PROVIDED AT EVERY INDIVIDUAL DUCTED CONNECTION
TO AN AIR DEVICE, UNLESS A BALANCING DAMPER IS SCHEDULED
TO BE FURNISHED WITH AIR DEVICE. VAV BOXES WITH SINGLE
DIFFUSERS ARE NOT REQUIRED TO HAVE A BALANCING DAMPER.
16. ALL NEW DUCTWORK SIZES SHOWN ON PLANS ARE CLEAR INSIDE
DIMENSIONS. CONTRACTOR SHALL ADJUST SHEET METAL SIZES AS
NECESSARY TO ACCOMMODATE INTERNAL DUCT LINER, IF
SPECIFIED.
17. ALL EXISTING TEMPERATURE CONTROLS THAT ARE BEING
DEMOLISHED OR DISABLED AS WORK OF THIS CONTRACT SHALL BE
COMPLETELY REMOVED FROM BUILDING.
18. THE CONTRACTOR SHALL CONNECT THE NEW HVAC SYSTEM TO THE
OWNER'S EXISTING BUILDING CONTROL SYSTEM. REFER TO THE
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
19. CONTRACTOR SHALL HAVE THE DOCUMENTS REVIEWED
COMPLETELY BY A CERTIFIED BALANCING CONTRACTOR FOR THE
INCLUSION OF THE NECESSARY ADDITIONAL AIR AND HYDRONIC
SYSTEM BALANCING DEVICES NOT SHOWN IN THESE DOCUMENTS
FOR COMPLETE HVAC SYSTEM BALANCING. REFER TO
SPECIFICATION SECTION 230593 FOR CONSTRUCTION DOCUMENT
EXAMINATION REPORT.
20. IT SHOULD BE NOTED THAT SOME SYSTEMS (I.E. GENERAL AND
ISOLATION EXHAUST) ARE REQUIRED TO BE BALANCED MORE THAN
ONCE TO ASSURE DESIGN AIRFLOWS ARE PROVIDED.
21. THESE PLANS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR
SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO THE EXACT
LOCATION OF DUCTWORK, PIPING AND EQUIPMENT FROM THE
LOCATION INDICATED ON THESE DRAWINGS TO FIT ACTUAL JOB
CONDITIONS.
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
VA FORM 08-6231
o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Office of Construction and Facilities ManagementApproved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
600 EAST 7TH STEET
SIOUX FALLS, SOUTH DAKOTA 57103
605.274.2893
6 SOUTH OLD ORCHARD
ST. LOUIS, MISSOURI 63119
800.404.7677
330 N MEAD
WICHITA, KANSAS 67202
316.262.2500
NOT FOR
CONSTRUCTION
JOHN SOMMERS, PE MO #2015028399
M-000
MECHANICAL SYMBOLS AND
ABBREVIATIONS
RELOCATE PHYSICAL
MEDICINE & REHAB. TO THE
4TH FLOOR
800 HOSPITAL DRIVE COLUMBIA, MO 65201
02-15-2023
589A4-22-100
BID DOCUMENTS
RLCJES
# Revision Date
John Ernest Sommers, PE
PE-2015028399
TEMP.
WAIT.
TEMP. MSA
FOURTH FLOOR KEY PLAN
AREA A
N
B
A
PHASING LEGEND
AFFECTED AREA
NOTES:
1. PAIN CLINIC - NORTHWEST QUADRANT OF THE FLOOR - SHALL BE OPERATIONAL AT ALL
WORKING DAYS & HOURS (MON-FRI 7M - 5PM) DURING THE ENTIRE CONSTRUCTION
PERIOD. ANY REQUIRED WORK IN THIS CLINIC SHALL BE COORDINATED CLOSELY W/
COR.
TEMPORARY PARTITION
EXISTING PARTITIONS
DEMO PARTITION
EXISTING AREA
AFTER-HOURS AFFECTED AREA
5PM-6AM PLUS WEEKENDS & HOLIDAYS ONLY
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
VA FORM 08-6231
o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Office of Construction and Facilities ManagementApproved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
600 EAST 7TH STEET
SIOUX FALLS, SOUTH DAKOTA 57103
605.274.2893
6 SOUTH OLD ORCHARD
ST. LOUIS, MISSOURI 63119
800.404.7677
330 N MEAD
WICHITA, KANSAS 67202
316.262.2500
NOT FOR
CONSTRUCTION
JOHN SOMMERS, PE MO #2015028399
M-001
MECHANICAL PHASING PLANS
RELOCATE PHYSICAL
MEDICINE & REHAB. TO THE
4TH FLOOR
800 HOSPITAL DRIVE COLUMBIA, MO 65201
02-15-2023
589A4-22-100
BID DOCUMENTS
RLCJES
# Revision Date
1/16" = 1'-0"
MECHANICAL PHASING PLAN - 4TH FLOOR - PHASE 1
1/16" = 1'-0"
MECHANICAL PHASING PLAN - 4TH FLOOR - PHASE 2
1/16" = 1'-0"
MECHANICAL PHASING PLAN - 4TH FLOOR - PHASE 3
1/16" = 1'-0"
MECHANICAL PHASING PLAN - 4TH FLOOR - PHASE 4
John Ernest Sommers, PE
F E
C
ABCDEEaFGGaHJJbK BaBbH.5Ja F.1 Eb Aa
2.8
3.7
6.2
5.4
5.7
5.3
4.6
3.6
4.1
4.7
5.1
6.1
6.3
1.9
5.5
1.1
3.1
4.4
NOT IN SCOPE
3" UP
3"
EX 3" HCR
EX 2" V
EX 1" MPS
1. REFER TO M000 FOR MECHANICAL SYMBOLS AND
ABBREVIATIONS.
2. COORDINATE PHASING AND SHUTDOWN FOR SUPPLY
AIR, RETURN AIR, HEATING HOT WATER SUPPLY, AND
HEATING HOT WATER RETURN WITH OWNER.
SHUTDOWN AND REPLACEMENT TO OCCUR AFTER
HOURS OR OVER WEEKEND.
3. COORDINATE EXISTING CONDITIONS AND ASBESTOS
REMOVAL WITH EXISTING CONDITIONS. FOR EXISTING
ASBESTOS, REFER TO MOST RECENT REPORT
PROVIDED BY OWNER. COORDINATE ALL REMOVAL IN
COMPLIANCE WITH CURRENT VA ASBESTOS
ABATEMENT DESIGN MANUAL. REFER TO
SPECIFICATION 02 82 11 FOR ADDITIONAL
INFORMATION.
4. PAIN CLINIC - NORTHWEST QUADRANT OF THE FLOOR -
SHALL BE OPERATIONAL AT ALL WORKING DAYS &
HOURS (MON-FRI 7M - 5PM) DURING THE ENTIRE
CONSTRUCTION PERIOD. ANY REQUIRED WORK IN THIS
CLINIC SHALL BE COORDINATED CLOSELY W/ COR.
GENERAL NOTES#
1. VERIFY EXISTING CONDITIONS PRIOR TO
CONSTRUCTION.
2. DEMOLISH EXISTING PIPING FROM FLOOR ABOVE TO
DEMARCATION POINT SHOWN.
SHEET KEYNOTES#
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
VA FORM 08-6231
o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Office of Construction and Facilities ManagementApproved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
600 EAST 7TH STEET
SIOUX FALLS, SOUTH DAKOTA 57103
605.274.2893
6 SOUTH OLD ORCHARD
ST. LOUIS, MISSOURI 63119
800.404.7677
330 N MEAD
WICHITA, KANSAS 67202
316.262.2500
NOT FOR
CONSTRUCTION
JOHN SOMMERS, PE MO #2015028399
MD101
MECHANICAL DEMOLITION PLAN -
PIPING - 3RD FLOOR - AREA A
RELOCATE PHYSICAL
MEDICINE & REHAB. TO THE
4TH FLOOR
800 HOSPITAL DRIVE COLUMBIA, MO 65201
02-15-2023
589A4-22-100
BID DOCUMENTS
RLCJES
1/8" = 1'-0"
MECHANICAL DEMOLITION PLAN - PIPING - 3RD FLOOR - AREA A
# Revision Date
John Ernest Sommers, PE
FE
F E
T
T
T
T
ABCDEEaFGGaHHbJJbKLLaMNNa BaBbH.5Ja F.1 Eb AaMaNb
2.8
3.7
7.3
8.2
9.1
10.4
4.5
6.2
5.4
6.7
5.7
5.3
4.6
10.2
9.8
8.9
8.3
7.2
7.1
3.6
4.1
4.7
5.1
6.1
6.3
8.0
1.9
5.5
7.5
1.1
3.1
4.4
ROOF TOP EQUIPMENT
EXISTING TO REMAIN
HE
HE
HE
HE
HE
HE
E
MD103
1 1
MD106
MD104
1 1
MD107
NOT IN SCOPE
1. REFER TO M000 FOR MECHANICAL SYMBOLS AND
ABBREVIATIONS.
2. COORDINATE PHASING AND SHUTDOWN FOR SUPPLY
AIR, RETURN AIR, HEATING HOT WATER SUPPLY, AND
HEATING HOT WATER RETURN WITH OWNER.
SHUTDOWN AND REPLACEMENT TO OCCUR AFTER
HOURS OR OVER WEEKEND.
3. COORDINATE EXISTING CONDITIONS AND ASBESTOS
REMOVAL WITH EXISTING CONDITIONS. FOR EXISTING
ASBESTOS, REFER TO MOST RECENT REPORT
PROVIDED BY OWNER. COORDINATE ALL REMOVAL IN
COMPLIANCE WITH CURRENT VA ASBESTOS
ABATEMENT DESIGN MANUAL. REFER TO
SPECIFICATION 02 82 11 FOR ADDITIONAL
INFORMATION.
4. PAIN CLINIC - NORTHWEST QUADRANT OF THE FLOOR -
SHALL BE OPERATIONAL AT ALL WORKING DAYS &
HOURS (MON-FRI 7M - 5PM) DURING THE ENTIRE
CONSTRUCTION PERIOD. ANY REQUIRED WORK IN THIS
CLINIC SHALL BE COORDINATED CLOSELY W/ COR.
GENERAL NOTES#
FOURTH FLOOR KEY PLAN
N
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
VA FORM 08-6231
o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Office of Construction and Facilities ManagementApproved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
600 EAST 7TH STEET
SIOUX FALLS, SOUTH DAKOTA 57103
605.274.2893
6 SOUTH OLD ORCHARD
ST. LOUIS, MISSOURI 63119
800.404.7677
330 N MEAD
WICHITA, KANSAS 67202
316.262.2500
NOT FOR
CONSTRUCTION
JOHN SOMMERS, PE MO #2015028399
MD102
MECHANICAL DEMOLITION PLAN - 4TH
FLOOR - OVERALL
RELOCATE PHYSICAL
MEDICINE & REHAB. TO THE
4TH FLOOR
800 HOSPITAL DRIVE COLUMBIA, MO 65201
02-15-2023
589A4-22-100
BID DOCUMENTS
RLCJES
3/32" = 1'-0"
MECHANICAL DEMOLITION PLAN - 4TH FLOOR - OVERALL
# Revision Date
John Ernest Sommers, PE
1. REFER TO M000 FOR MECHANICAL SYMBOLS AND
ABBREVIATIONS.
2. COORDINATE PHASING AND SHUTDOWN FOR SUPPLY
AIR, RETURN AIR, HEATING HOT WATER SUPPLY, AND
HEATING HOT WATER RETURN WITH OWNER.
SHUTDOWN AND REPLACEMENT TO OCCUR AFTER
HOURS OR OVER WEEKEND.
3. COORDINATE EXISTING CONDITIONS AND ASBESTOS
REMOVAL WITH EXISTING CONDITIONS. FOR EXISTING
ASBESTOS, REFER TO MOST RECENT REPORT
PROVIDED BY OWNER. COORDINATE ALL REMOVAL IN
COMPLIANCE WITH CURRENT VA ASBESTOS
ABATEMENT DESIGN MANUAL. REFER TO
SPECIFICATION 02 82 11 FOR ADDITIONAL
INFORMATION.
4. PAIN CLINIC - NORTHWEST QUADRANT OF THE FLOOR -
SHALL BE OPERATIONAL AT ALL WORKING DAYS &
HOURS (MON-FRI 7M - 5PM) DURING THE ENTIRE
CONSTRUCTION PERIOD. ANY REQUIRED WORK IN THIS
CLINIC SHALL BE COORDINATED CLOSELY W/ COR.
GENERAL NOTES#EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb
2.8
3.7
4.5
6.2
5.4
6.7
5.7
5.3
4.6
7.1
3.6
4.1
4.7
5.1
6.1
6.3
5.5
3.1
4.4
3/4"
3/4"
2"
1 1/4"
1"
1" 3/4"
3/4" typical size VAV connection
1 1/4"
2"
1"
1"
1 1/2"
1 1/4"
1 1/4"
1 1/2"
3"
6" HCS UP &
DN
1"1"
3/4"
3/4"
HCR DN
2" AT.MOS.VENT
TO 6TH FL.
1" MPS(30#)
UP & DN
UP
UP
5"
3" 3"
5" HCR UP
HCR
HCR HCR
T
T
T
T
T
T
TT
T
T
T
T
T
T T
T
T
NOT IN SCOPE
3 3
1 1/4"
1 1/2"
22 2 2 2 2
EX 1/2" D
EX 1" HCS 5
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1/2" D
EX 1" HCS
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
1. DEMOLISH ALL EXISTING TERMINAL UNITS AND
ASSOCIATED PIPING, CONTROLS, AND ACCESSORIES
BACK TO DEMARCATION POINT SHOWN.
2. EXISTING INDUCTION UNIT TO BE REMOVED. REMOVE
CONTROLS AND ACCESSORIES. REMOVE PIPING BACK
ABOVE CEILING AND PREPARE FOR CONNECTION TO
NEW INDUCTION UNIT PIPING LOOP. REMOVE ALL
CONTROL WIRING BACK TO CENTRAL PANEL IN 401C.
REMOVE ALL PNEUMATIC CONTROL TUBING.
3. DEMOLISH EXISTING PIPING FROM FLOOR BELOW TO
DEMARCATION POINT SHOWN.
4. DEMOLISH EXISTING PIPING BACK TO DEMARCATION
POINT SHOWN.
5. DEMOLISH INDUCTION UNIT SUPPLY AND CONDENSATE
PIPING BACK TO 4TH FLOOR SLAB AND CEILING.
PREPARE FOR CONNECTION OF NEW PIPING. INSTALL
NEW INDUCTION UNIT SUPPLY AND CONDENSATE
PIPING PRIOR TO DEMOLITION OF EXISTING PIPING. SEE
NEW WORK FOR RELATED INFORMATION.
SHEET KEYNOTES#
FOURTH FLOOR KEY PLAN
AREA A
N
B
A
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
VA FORM 08-6231
o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Office of Construction and Facilities ManagementApproved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
600 EAST 7TH STEET
SIOUX FALLS, SOUTH DAKOTA 57103
605.274.2893
6 SOUTH OLD ORCHARD
ST. LOUIS, MISSOURI 63119
800.404.7677
330 N MEAD
WICHITA, KANSAS 67202
316.262.2500
NOT FOR
CONSTRUCTION
JOHN SOMMERS, PE MO #2015028399
MD103
MECHANICAL DEMOLITION PLAN -
PIPING - 4TH FLOOR - AREA A
RELOCATE PHYSICAL
MEDICINE & REHAB. TO THE
4TH FLOOR
800 HOSPITAL DRIVE COLUMBIA, MO 65201
02-15-2023
589A4-22-100
BID DOCUMENTS
RLCJES
3/16" = 1'-0"
MECHANICAL DEMOLITION PLAN - PIPING - 4TH FLOOR - AREA A
# Revision Date
John Ernest Sommers, PE
FE
F E
T
TT
T
TT
1. REFER TO M000 FOR MECHANICAL SYMBOLS AND
ABBREVIATIONS.
2. COORDINATE PHASING AND SHUTDOWN FOR SUPPLY
AIR, RETURN AIR, HEATING HOT WATER SUPPLY, AND
HEATING HOT WATER RETURN WITH OWNER.
SHUTDOWN AND REPLACEMENT TO OCCUR AFTER
HOURS OR OVER WEEKEND.
3. COORDINATE EXISTING CONDITIONS AND ASBESTOS
REMOVAL WITH EXISTING CONDITIONS. FOR EXISTING
ASBESTOS, REFER TO MOST RECENT REPORT
PROVIDED BY OWNER. COORDINATE ALL REMOVAL IN
COMPLIANCE WITH CURRENT VA ASBESTOS
ABATEMENT DESIGN MANUAL. REFER TO
SPECIFICATION 02 82 11 FOR ADDITIONAL
INFORMATION.
4. PAIN CLINIC - NORTHWEST QUADRANT OF THE FLOOR -
SHALL BE OPERATIONAL AT ALL WORKING DAYS &
HOURS (MON-FRI 7M - 5PM) DURING THE ENTIRE
CONSTRUCTION PERIOD. ANY REQUIRED WORK IN THIS
CLINIC SHALL BE COORDINATED CLOSELY W/ COR.
GENERAL NOTES#EaFGGaHHbJJbKLLaMNNa H.5Ja F.1 EbMaNb
7.3
8.2
9.1
6.7
9.8
8.9
8.3
7.2
7.1
8.0
7.5
2"
2"
3/4"
2"
2" 1 1/4"
1"
1" 3/4"
3/4"
2"
1" typical size VAV connection
2"
3/4"
2"
1"
2"
1"
1 1/4"
2"
1"
1"
1 1/2" 1 1/4"
3/4"
3/4"
EX 6" MPS UP &
DN
EX 8" CWR UP
& DN
EX 3" HWS UP
& DN
EX 3" HWR UP
& DN
EX 8" CWS UP
& DN
EX 1 1/4" EXP
UP & DN
4"
3/4"
3/4"
- 5' 0" LG x 1'-6" VERT.
EXP.LOOP AT CLG
1' - 0" RAD. BEND -
UP & DN
UP
UP
EX 4" MPC UP
& DN
T
22222222222222
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1" HCS
EX 1/2" D
EX 1/2" D
EX 1" HCS 4
FOURTH FLOOR KEY PLAN
AREA B
N
B
A
1. DEMOLISH ALL EXISTING TERMINAL UNITS AND
ASSOCIATED PIPING, CONTROLS, AND ACCESSORIES
BACK TO DEMARCATION POINT SHOWN.
2. EXISTING INDUCTION UNIT TO BE REMOVED. REMOVE
CONTROLS AND ACCESSORIES. REMOVE PIPING BACK
ABOVE CEILING AND PREPARE FOR CONNECTION TO
NEW INDUCTION UNIT PIPING LOOP. REMOVE ALL
CONTROL WIRING BACK TO CENTRAL PANEL IN 401C.
REMOVE ALL PNEUMATIC CONTROL TUBING.
3. VERIFY SHUTOFF VALVES EXIST AND ADD NEW AS
REQUIRED FOR NEW WORK.
4. DEMOLISH INDUCTION UNIT SUPPLY AND CONDENSATE
PIPING BACK TO 4TH FLOOR SLAB AND CEILING.
PREPARE FOR CONNECTION OF NEW PIPING. INSTALL
NEW INDUCTION UNIT SUPPLY AND CONDENSATE
PIPING PRIOR TO DEMOLITION OF EXISTING PIPING. SEE
NEW WORK FOR RELATED INFORMATION.
SHEET KEYNOTES#
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
VA FORM 08-6231
o n e e ig e fo o t o n e q u a rt e r i n c e fo o t th re e e ig h th s in c e fo o t o n e h a lf in c e fo o t th re e q u a rt e fo o t o n e in c e fo o t o n e a n d o n e h a lf in c h e e fo o t th re e in c h e e fo o t
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Office of Construction and Facilities ManagementApproved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
600 EAST 7TH STEET
SIOUX FALLS, SOUTH DAKOTA 57103
605.274.2893
6 SOUTH OLD ORCHARD
ST. LOUIS, MISSOURI 63119
800.404.7677
330 N MEAD
WICHITA, KANSAS 67202
316.262.2500
NOT FOR
CONSTRUCTION
JOHN SOMMERS, PE MO #2015028399
MD104
MECHANICAL DEMOLITION PLAN -
PIPING - 4TH FLOOR - AREA B
RELOCATE PHYSICAL
MEDICINE & REHAB. TO THE
4TH FLOOR
800 HOSPITAL DRIVE COLUMBIA, MO 65201
02-15-2023
589A4-22-100
BID DOCUMENTS
RLCJES
3/16" = 1'-0"
MECHANICAL DEMOLITION PLAN - PIPING - 4TH FLOOR - AREA B
# Revision Date
John Ernest Sommers, PE
File details come from the government source that posted it. Updated .