Design Drawings Telecommunications_654-212.pdf
PDF 3 MB Posted
- Solicitation number
- QSE--36C10F24R50000
About this file
This document appears to be design drawings for telecommunications and security systems at the VA Sierra Nevada Health Care System in Reno, Nevada. The drawings cover various aspects of the telecommunications infrastructure, including the telecommunications site plan, floor plans, enlarged plans, details, and riser diagrams. The drawings also include security-related floor plans, enlarged plans, details, and riser diagrams. The drawings indicate that this is part of the VA Project Number 654-212.
The related federal contract opportunity is for a Design Build Central Utilities Plant project at the same VA facility in Reno, Nevada. The solicitation number is QSE--36C10F24R50000, and the project scope includes replacing the seismically deficient boiler plant, building an approximately 11,000 GSF central utility plant, demolishing the existing boiler plant, and converting the boiler plant location into a paved parking lot. The contractor will provide all required design and construction services for this project.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. DEPARTMENT OF VETERANS AFFAIRS
TELECOMM 30x42 DRAWINGS
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
VA PROJECT NUMBER: 654-212
[08] TELECOM
78 TS101 TELECOMMUNICATIONS SITE PLAN
79 TS102 TELECOMMUNICATIONS SITE PLAN - CUP
80 T-000 TELECOMMUNICATIONS SYMBOLS AND LEGENDS
81 TN101 LEVEL 1 - TELECOMMUNICATIONS FLOOR PLAN
82 TN102 MEZZANINE LEVEL - TELECOMMUNICATIONS FLOOR PLAN
83 TN402 TELECOMMUNICATIONS ENLARGED PLANS
84 TN500 TELECOM DETAILS
85 TN600 TELECOM RISERS AND DIAGRAMS
86 TY101 LEVEL 1 - SECURITY FLOOR PLAN
87 TY102 MEZZANINE LEVEL - SECURITY FLOOR PLAN
88 TY402 SECURITY ENLARGED PLANS
89 TY500 SECURITY DETAILS
90 TY600 SECURITY RISER AND DIAGRAMS
CENTRAL UTILITY PLANT
1. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
2. FINAL LOCATION OF ALL DEVICES SHALL BE COORDINATED WITH FINAL
ROOM FURNITURE CONFIGURATIONS, ACCESSORIES, SPACE
ASSIGNMENTS, AND LAYOUTS.
3. ALL ICT OUTLETS WITHIN OCCUPIED SPACES SHALL BE LOCATED WITHIN
18” MAXIMUM FROM AN ELECTRICAL OUTLET; EXCEPTION: ICT OUTLETS
INDICATED FOR SPECIFIC DUTY.
4. ELECTRICAL OUTLETS INDICATED FOR REFERENCE PURPOSES ONLY;
REFER TO ELECTRICAL PLANS FOR ELECTRICAL REQUIREMENTS.
5. ALL LOCATIONS OF CATV CABLE, TERMINATION AND COMMON
EQUIPMENT TO BE COORDINATED WITH CATV SERVICES PROVIDER
PRIOR TO INSTALLATION.
6. ALL CABLING SHALL BE ROUTED TO AND TERMINATED IN THE
TELECOMMUNICATIONS ROOM.
7. FILL CAPACITIES: CATEGORY FILL CAPACITIES SHALL BE BASED ON AN
O.D. OF .25” OR AN AREA OF .04909 SQ. IN./CABLE; MAINTAIN A MINIMUM
25% SPARE CAPACITY IN ALL PATHWAYS; CONDUIT FILL CAPACITIES
MAXIMUM FILL = 30%; NON-CONTINUOUS (J-HOOK) AND CONTINUOUS
(CABLE TRAY) SUPPORTS MAXIMUM FILL = 35.5% FILL (INCLUDING SPARE
CAPACITIES); SLEEVES <24” IN LENGTH MAXIMUM FILL = 75%; IF CABLE IS
PROVIDED WITH LARGER O.D. ADJUST PATHWAYS ACCORDINGLY,
ROUNDED UP TO THE NEXT TRADE SIZE.
8. ALL CABLING SHALL HAVE A MINIMUM 10’ SERVICE-LOOP AT THE
COMMUNICATION ROOM.
9. ALL CABLING SHALL HAVE A MINIMUM 3’ SERVICE LOOP AT THE OUTLET
OR DEVICE.
10. MOUNTING HEIGHTS FOR DEVICES SHALL BE MEASURED FROM FINAL
FINISH FLOOR TO CENTER OF BOX.
11. VERIFY MOUNTING HEIGHT OF ALL COMMUNICATIONS DEVICES WITH
ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN. WHERE CONFLICTS
EXIST, CONTRACTOR SHALL NOTIFY ENGINEER AND ARCHITECT FOR
RESOLUTION.
12. VERIFY THE LOCATIONS OF ALL FIREPROOFING PRIOR TO THE
INSTALLATION OF CONDUIT AND BACKBOXES.
13. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE CONTRACTOR
SHALL DOCUMENT THE VARIATION AND REPORT IT TO THE GENERAL
CONTRACTOR FOR RESOLUTION WITH THE ENGINEER OF RECORD.
14. COORDINATE THE INSTALLATION REQUIREMENTS OF SYSTEM DEVICES,
EQUIPMENT, PATHWAYS, AND OTHER COMPONENTS WITH THE
GENERAL CONTRACTOR AND OTHER BUILDING TRADES PRIOR TO
INSTALLATION.
15. COORDINATE GROUNDING REQUIREMENTS WITH THE ELECTRICAL
CONTRACTOR AND ENSURE THE COMMUNICATIONS GROUNDING MEETS
SYSTEM REQUIREMENTS AND TIA J-STD-607 LATEST VERSION
STANDARDS PRIOR TO ENERGIZING ANY SYSTEMS EQUIPMENT.
SYMBOL
TELECOMMUNICATIONS SYMBOLS
DESCRIPTION
GENERAL NOTES
SYMBOL
SECURITY SYMBOLS
DESCRIPTION
P
DR
WR
M
EPT
ELR
DC
RR
PANIC / DURESS BUTTON
MOUNTED AT 48" A.F.F. UNLESS NOTED
OTHERWISE
PANIC / DURESS BUTTON MONITOR
DESK MOUNTED RADIO PHONE
SURFACE WALL MOUNTED RADIO
PHONE MOUNTED AT 48" A.F.F. UNLESS
NOTED OTHERWISE
VIDEO SURVEILLANCE MONITOR STATION
ACCESS CONTROL CARD READER/KEYPAD COMBINATION
DEVICE
INTRUSION DETECTION SYSTEM KEYPAD
ELECTRIC POWER TRANSFER
ELECTRIC LATCH RELEASE
DOOR CONTACT SWITCH - WIRED TO
ACCESS CONTROL SYSTEM ONLY
UNLESS OTHERWISE NOTED
INTRUSION DETECTION
PASSIVE
INFRARED MOTION DETECTOR -
WALL MOUNTED
RECESSED WALL MOUNTED RADIO
PHONE MOUNTED AT 48" A.F.F. UNLESS
NOTED OTHERWISE
REQUEST FOR EXIT/MOTION SENSOR
CR
DB
DB
DM
EL
EO
GB
KP
MD
PB
REX
EC
GO
C
DOOR BELL PUSHBUTTON
DOOR BELL CHIME
DOOR POSITION SWITCH
ELECTRIFIED LOCKING DEVICE,
LATCH BOLT MONITOR, AND DOOR
POSITION SWITCH
ELECTRIFIED LOCKING DEVICE
GLASS BREAK DETECTOR
EMERGENCY CALL STATION
GATE OPENER
A. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT) DESIGN
GUIDE, FEBRUARY 2011
B. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT)
INFRASTRUCTURE STANDARDS FOR TELECOMMUNICATION
SPACES, JULY 2021
C. INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS
SPACES, AUGUST 2020
D. VA PG-18-10 TELECOMMUNICATIONS AND SPECIAL
TELECOMMUNICATIONS SYSTEMS DESIGN MANUAL, FEBRUARY
E. BICSI AND EIA/TIA STANDARDS AS DEFINED IN VA PG-18-10
F. VA - PSRDM - PHYSICAL SECURITY AND RESILIENCY DESIGN
MANUAL, JULY 2022
G. ENSURE LATEST ADOPTED VERSIONS OF EACH STANDARD ARE
FOLLOWED.
PROJECT CODES AND STANDARDS
STANDARD MOUNTING HEIGHTS
ELECTRICAL: (AFF / AFG UNLESS NOTED OTHERWISE)
84" 48" 48" 84" 48" 80" 60"
120" 60" 36" 48" 72" 48"
144" 18" 24" 26" 48" 48"
CEILING
48" 48" 18" 84"
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS
ANNUNCIATOR PANELS
CLOCK OUTLETS (CENTERLINE)
CONTROLS (TOP)
EXIT SIGNS (WALL-MOUNTED, BOTTOM)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR)
FIRE ALARM CONTROL PANEL / UNIT (DISPLAY)
INTERCOM (AREA ONLY)
INTERCOM (TOP)
PANELS & PANELBOARDS (TOP)
PULL STATION (HANDLE)
PHOTOCELLS
RECEPTACLES (BOTTOM)
RECEPTACLES (EXTERIOR)
RECEPTACLES (GARAGES)
RECEPTACLES IN EQUIPMENT ROOMS (TOP)
REMOTE INDICATING LIGHT (EQUIPMENT ROOMS)
REMOTE INDICATING LIGHT (FINISHED AREAS)
SAFETY SWITCHES & STARTERS
SWITCHES (TOP)
TELEPHONE/DATA/TV OUTLETS (BOTTOM)
VISIBLE APPLIANCES (CENTERLINE)
IC
CATV
FO
T
T/D
D
S
IC
UC
S
WAP
#D/#TV
M
S
V
COMMUNICATIONS OUTLET, TYPE AS NOTED
#D = DATA, # = QUANTITY OF CABLES
#W = WALL PHONE, # = QUANTITY OF CABLES
#FMS = FACILITY MONITORING SYSTEM,
# = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED
#D = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
WIRELESS ACCESS POINT, CEILING MOUNTED
COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED
#D = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
SPEAKER, WALL MOUNTED
SPEAKER, CEILING MOUNTED
SERVER RACK, TWO-POST, FLOOR MOUNTED
3/4"x4'x8', FIRE-RATED PLYWOOD BACKBOARD
GROUND BAR, TYPE AS NOTED
SERVER RACK, WALL MOUNTED
CABLE TRAY, TYPE AS NOTED
CABLE TELEVISION LINE
FIBEROPTIC LINE
TELEPHONE LINE
TELEPHONE/DATA LINE
DATA LINE
SPEAKER LINE
INTERCOM LINE
INTERCOM, "M" DENOTES MASTER STATION
VOLUME CONTROL, WALL MOUNTED
MULTI-SERVICE POWER POLE WITH POWER / DATA,
TYPE AS NOTED AND / OR SCHEDULED
UNDERGROUND COMMUNICATIONS LINE,
CABLING TYPE AS NOTED
MULTI-SERVICE FLOOR BOX / POKE-THRU WITH POWER / DATA,
TYPE AS NOTED AND / OR SCHEDULED
SERVER RACK, FOUR-POST, FLOOR MOUNTED
SERVER CABINET, FLOOR MOUNTED
SSTV SECURITY SURVEILLANCE TELEVISION LINE, MIN. 1" RACEWAY
SINGLE VIEW SECURITY CAMERA
DUAL VIEW SECURITY CAMERA
180-DEGREE PANORAMIC VIEW SECURITY CAMERA
270-DEGREE PANORAMIC/MULTI-IMAGE VIEW
SECURITY CAMERA
360-DEGREE PANORAMIC/MULTI-IMAGE VIEW
SECURITY CAMERA
8P8C EIGHT POSITION, EIGHT CONTACT
AAP ALARM ANNUNCIATOR PANEL
AFG ABOVE FINISHED GRADE
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
ANSI THE AMERICAN NATIONAL STANDARDS
INSTITUTE
ARCH ARCHITECT
AV AUDIO VISUAL
BATT BATTERY
BOCT BOTTOM OF CABLE TRAY
BICSI BUILDING INDUSTRY CONSULTING
SERVICE INTERNATIONAL
C CONDUIT
CATV COMMUNITY ANTENNA TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
CLG CEILING
CM CEILING MOUNTED
CMR COMPUTER MACHINE ROOM
CMU CONCRETE MASONRY UNIT
COAX COAXIAL CABLE
COMM COMMUNICATION
CONT CONTINUE/ CONTINUOUS
CTR CENTER
CU COPPER
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEMO DEMOLISH/ DEMOLITION
DIA DIAMETER
DIM DIMENSION
DWG DRAWING
EA EACH
EH EXTRA HAZARD
EL ELEVATION
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EQPM EQUIPMENT
ETR EXISTING TO REMAIN
EX EXISTING
FA FIRE ALARM
FFE FINISHED FLOOR ELEVATION
FLEX FLEXIBLE METALLIC CONDUIT
FLR FLOOR
FT FEET
FO FIBER-OPTIC
GA GAUGE
GC GENERAL CONTRACTOR
GND GROUND
HCM HORIZONTAL CABLE MANAGER
HGT HEIGHT
HH HANDHOLE
HZ HERTZ
ICT INFORMATION COMMUNICATIONS AND
TECHNOLOGIES
ID INSIDE DIAMETER
IDF INTERMEDIATE DISTRIBUTION FRAME
IR INFRARED
JB JUNCTION BOX
KW KILOWATT
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LH LIGHT HAZARD
LOC LOCAL OPERATING CONSOLE
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MDF MAIN DISTRIBUTION FRAME
MH MANHOLE
MIN MINIMUM
MTD MOUNTED
MTG MOUNTING
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH ORDINARY HAZARD
PA PUBLIC ADDRESS
POE POWER OVER ETHERNET
PP PATCH PANEL
PWR POWER
R RISER/ RADIUS/ RETURN
RCDD REGISTERED COMMUNICATIONS
DISTRIBUTION DESIGNER
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
S SUPPLY
SCHED SCHEDULE
SD SMOKE DETECTOR
SIM SIMILAR
SP SPEAKER
SPEC SPECIFICATION
SP/ST SPEAKER/ STROBE
SQ SQUARE
ST STROBE
STP SHIELDED TWISTED PAIR
SURF SURFACE
SYST SYSTEM
TE TELECOMMUNICATIONS ENCLOSURE
TEF TELECOMMUNICATIONS ENTRANCE
FACILITY
TEL TELEPHONE
TEMP TEMPERATURE
TER TELECOMMUNICATIONS EQUIPMENT
ROOM
TGB TELECOMMUNICATIONS GROUNDING
BUSSBAR
TIA TELECOMMUNICATIONS INDUSTRY
ASSOCIATION
TMGB TELECOMMUNICATIONS MAIN
GROUNDING BUSSBAR
TR TELECOMMUNICATIONS ROOM
TP TWISTED PAIR
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
VCM VERTICAL CABLE MANAGER
W/ WITH
WM WALL MOUNTED
W/O WITHOUT
XP EXPLOSION PROOF
ABBREVIATIONS
DOOR AUTO-CLOSERAC
RF RFID KEY TAG READER
CONNECT TO EXISTING
ACCESS CONTROL CARD READER/KEYPAD COMBINATION
DEVICE. WATER PROOF/ WEATHER RESISTANT.
CR
WP
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :5
P
M
TELECOMMUNICATIONS SYMBOLS AND
LEGENDS
JPH 80KGH
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
T-000
No. REVISION DESCRIPTION DATE
82 9580
M S P
MSP
WMH
WMH
IC B
W
W
EXISTING VA HOSPITAL
EXISTING VA HOSPITAL
EXISTING PARKING
GARAGE
EXISTING BUILDING 7
BLDG. 16 (CUP)
TS102
TS101
PX1
PX1
PX1
PX1
PX1
PX1
PX2
NEW EMERGENCY
CALL BOX
1. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
2. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
3. ELECTRICAL OUTLETS/ DEVICES INDICATED ARE FOR COORDINATION
AND REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES
DRAWINGS FOR ELECTRICAL WORK REQUIREMENTS AND
SPECIFICATIONS.
4. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF FOURTEEN (14)
WORKING-DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS
DIRECTED OTHERWISE.
5. EXISTING PLANT TELECOMMUNICATIONS INFRASTRUCTURE SHALL
REMAIN IN PLACE AND OPERATIONAL UNTIL THE NEW PLANT CABLING
AND EQUIPMENT HAS BEEN INSTALLED, TESTED AND APPROVED.
6. ALL PENETRATIONS CREATED BY THIS PROJECT SHALL BE SEALED TO
MAINTAIN THE ARCHITECT SPECIFIED FIRE/SMOKE-RATING OF THE
ASSEMBLY PENETRATED.
7. BOND ALL METALLIC LADDER TRAY AND CABLE TRAY SECTIONS, AND
BOND LADDER TRAY AND CABLE TRAY SYSTEM, TO THE
TELECOMMUNICATIONS GROUNDING BUSBAR OR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR.
8. CEILING MOUNTED DEVICES SHALL BE INSTALLED TO ALIGN
AESTHETICALLY WITH THE CEILING LIGHTING, SPRINKLERS, AND OTHER
FIXTURES. COORDINATE INSTALLATION OF ALL CEILING MOUNTED
DEVICES WITH THE ARCHITECTURAL DRAWINGS AND ALL OTHER
TRADES PRIOR TO INSTALLATION.
9. PROVIDE LONG SWEEP CONDUIT BENDS AND DO NOT EXCEED THE
MANUFACTURER’S WRITTEN RECOMMENDATIONS FOR CABLE BEND
RADIUS.
10. INSTALL CABLING IN A MINIMUM OF 1-1/4" INCH CONDUIT UNLESS
APPROVED IN WRITING.
11. COPPER CIRCUITS FOR ETHERNET COMMUNICATIONS SHALL NOT
EXCEED 290 FEET IN LENGTH. THE CONTRACTOR SHALL FIELD SURVEY
ROUTES AND BRING TO THE ENGINEER’S ATTENTION ANY CIRCUIT THAT
MAY EXCEED THE MAXIMUM DISTANCE.
12. ALL PUBLIC ADDRESS SPEAKERS TO BE CIRCUITED TO RACK MOUNTED
HEAD-END AND AMPLIFIERS LOCATED IN TR N3203.
13. COORDINATE EQUIPMENT DATA CONNECTION POINTS WITH
MECHANICAL AND ELECTRICAL EQUIPMENT MANUFACTURERS. ALL ESS
CABLING AND PATHWAYS SHALL BE INSTALLED CONCEALED WITHIN
WALL CAVITIES.
14. CONTRACTOR TO FURNISH AND INSTALL ALL PASSIVE EQUIPMENT
NECESSARY TO COMPLETE A FULLY FUNCTIONING ENGINEERING
CONTROL CENTER (ECC). ALL ECC EQUIPMENT SHALL BE PLACED ON
SEGREGATED NETWORKS. COORDINATE ALL EQUIPMENT AND
INFRASTRUCTURE REQUIREMENTS WITH VA ENGINEERING PRIOR TO
PROCUREMENT AND INSTALLATION.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :0
P
M
TELECOMMUNICATIONS SITE PLAN
JPH 86KGH
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
TS101
No. REVISION DESCRIPTION DATE
N
1" = 40'-0"
ICT OVERALL SITE PLAN1
N
3/32" = 1'-0" 1/ TS101
ENLARGED ICT SITE PLAN - NEW PAVED PARKING LOT SITE2
CR
CR
CR
IC
IC
IC
IC
BLDG. 16 (CUP)
EXISTING PARKING
GARAGE
EXISTING BUILDING 7
PX2
PX1
PX2
PX1
PX2
G E
N E
R A
T O
R
NEW
EMERGENCY
CALL BOX.
UC
UC
UC
UC
HH
UC
UC
UC
UC
UC
UC
HH
HH
HH
CHILLED WATER
AND OXYGEN TUNNEL
MH
NEW
EMERGENCY
CALL BOX.
C-06
C-06
C-06
C-05
C-05
UC
UC
UCUC
1. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
2. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
3. ELECTRICAL OUTLETS/ DEVICES INDICATED ARE FOR COORDINATION
AND REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES
DRAWINGS FOR ELECTRICAL WORK REQUIREMENTS AND
SPECIFICATIONS.
4. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF FOURTEEN (14)
WORKING-DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS
DIRECTED OTHERWISE.
5. EXISTING PLANT TELECOMMUNICATIONS INFRASTRUCTURE SHALL
REMAIN IN PLACE AND OPERATIONAL UNTIL THE NEW PLANT CABLING
AND EQUIPMENT HAS BEEN INSTALLED, TESTED AND APPROVED.
6. ALL PENETRATIONS CREATED BY THIS PROJECT SHALL BE SEALED TO
MAINTAIN THE ARCHITECT SPECIFIED FIRE/SMOKE-RATING OF THE
ASSEMBLY PENETRATED.
7. BOND ALL METALLIC LADDER TRAY AND CABLE TRAY SECTIONS, AND
BOND LADDER TRAY AND CABLE TRAY SYSTEM, TO THE
TELECOMMUNICATIONS GROUNDING BUSBAR OR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR.
8. CEILING MOUNTED DEVICES SHALL BE INSTALLED TO ALIGN
AESTHETICALLY WITH THE CEILING LIGHTING, SPRINKLERS, AND OTHER
FIXTURES. COORDINATE INSTALLATION OF ALL CEILING MOUNTED
DEVICES WITH THE ARCHITECTURAL DRAWINGS AND ALL OTHER
TRADES PRIOR TO INSTALLATION.
9. PROVIDE LONG SWEEP CONDUIT BENDS AND DO NOT EXCEED THE
MANUFACTURER’S WRITTEN RECOMMENDATIONS FOR CABLE BEND
RADIUS.
10. INSTALL CABLING IN A MINIMUM OF 1-1/4" INCH CONDUIT UNLESS
APPROVED IN WRITING.
11. COPPER CIRCUITS FOR ETHERNET COMMUNICATIONS SHALL NOT
EXCEED 290 FEET IN LENGTH. THE CONTRACTOR SHALL FIELD SURVEY
ROUTES AND BRING TO THE ENGINEER’S ATTENTION ANY CIRCUIT THAT
MAY EXCEED THE MAXIMUM DISTANCE.
12. ALL PUBLIC ADDRESS SPEAKERS TO BE CIRCUITED TO RACK MOUNTED
HEAD-END AND AMPLIFIERS LOCATED IN TR N3203.
13. COORDINATE EQUIPMENT DATA CONNECTION POINTS WITH
MECHANICAL AND ELECTRICAL EQUIPMENT MANUFACTURERS. ALL ESS
CABLING AND PATHWAYS SHALL BE INSTALLED CONCEALED WITHIN
WALL CAVITIES.
14. CONTRACTOR TO FURNISH AND INSTALL ALL PASSIVE EQUIPMENT
NECESSARY TO COMPLETE A FULLY FUNCTIONING ENGINEERING
CONTROL CENTER (ECC). ALL ECC EQUIPMENT SHALL BE PLACED ON
SEGREGATED NETWORKS. COORDINATE ALL EQUIPMENT AND
INFRASTRUCTURE REQUIREMENTS WITH VA ENGINEERING PRIOR TO
PROCUREMENT AND INSTALLATION.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :1
P
M
TELECOMMUNICATIONS SITE PLAN -
CUP
JPH 87KGH
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
TS102
No. REVISION DESCRIPTION DATE
N
1/16" = 1'-0" 1/ TS101
ENLARGED ICT SITE PLAN - CENTRAL UTILITY PLANT1
TELECOM KEYNOTES
1 TELECOMMUNICATIONS CONDUITS AND CABLES TO ENTER INTO EXISTING
CHILLER TUNNEL. UTILIZING EXISTING MANHOLE FOR ACCESS.
2 TELECOMMUNICATIONS CONDUITS AND CABLES TO EGRESS FROM
EXISTING CHILLER TUNNEL INTO TEMPORARY CHILLER-OXYGEN TUNNEL.
3 FOUR (4) 4" CONDUITS. ONE WITH 24-STRANDS, SINGLE MODE FIBER OPTIC
CABLING INTERCEPTED FROM EXISTING MANHOLE FOR
TELECOMMUNICATIONS. ONE WITH 24-STRANDS, SINGLE MODE FIBER OPTIC
CABLING INTERCEPTED FROM EXISTING MANHOLE FOR ESS. ONE WITH 25
PAIR OF COPPER AS SECONDARY REDUNDANT FEED. AND ONE SPARE
PATHWAY FOR FUTURE CONNECTIONS FOR TELECOMMUNICATIONS AND
ESS WITH PULL CORD.
4 TWO (2) 4" CONDUITS TO FOLLOW EXISTING UTILITY TUNNEL AND BE
CAPPED IN IN CHILLED WATER AND OXYGEN TUNNEL VAULT.
5 TELECOMMUNICATIONS CABLING TO UTILIZE EXISTING
TELECOMMUNICATIONS AND SIGNAL TRENCHING.
6 PROVIDE GROUND LOOP FOR EXIT GATE CONTROL.
7 ENTRY GATE TO BE CONTROLLED VIA DUAL-AUTHENTICATION CARD
READER ON PEDESTAL.
8 PROVIDE CAMERAS CAPABLE OF FACIAL ANALYTICS.
9 PROVIDE CAMERAS CAPABLE OF FACIAL ANALYTICS, MOUNTED ON SECURE
CAMERA POLE. SEE SHEET TY500 DETAIL 5.
10 PROVIDE CAMERAS CAPABLE OF LICENSE PLATE ANALYTICS, MOUNTED ON
SECURE CAMERA POLE. SEE SHEET TY500 DETAIL 5.
S
S
S
S
S
S
S
S
S
S
S
S
S
S
2 5431
E
A
B
C
D
3.9
B.2
A.8
C.2
HH
W
2D +30"
AFF
2D +30"
AFF
2D +30"
AFF
2D +30"
AFF
2D
2D
2D
2D
BOILER AREA
N3101
STEAM PIT
N3102
STORAGE ROOM
N3103
HAC
N3104
CORRIDOR
N3105
ELEC
N3107
OFFICE
N3106
ELECTRICAL UTILITY ROOM
N3108 RESTROOM
N3117
RESTROOM
N3118
CONFERENCE / BREAK ROOM
N3116
CONTROL ROOM
N3115
PIT
N3109
RISER ROOM
N3110
CHILLERS
N3111
OXYGEN YARD
N3112
ELECTRICAL SWITCHGEAR
N3113
GENERATORS
N3114
2D 2D
2D
2D
2D
W
2D +60"
AFF
2D
2D +60"
AFF
2D
2D +60"
AFF
2D 2D +60"
AFF
2D
2D +60"
AFF
2D +60"
AFF
2D
2D 2D +30"
AFF 2D
2D
2D 2D 2D
3 2
2D +30"
AFF
2D
1. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
2. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
3. ELECTRICAL OUTLETS/ DEVICES INDICATED ARE FOR COORDINATION
AND REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES
DRAWINGS FOR ELECTRICAL WORK REQUIREMENTS AND
SPECIFICATIONS.
4. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF FOURTEEN (14)
WORKING-DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS
DIRECTED OTHERWISE.
5. EXISTING PLANT TELECOMMUNICATIONS INFRASTRUCTURE SHALL
REMAIN IN PLACE AND OPERATIONAL UNTIL THE NEW PLANT CABLING
AND EQUIPMENT HAS BEEN INSTALLED, TESTED AND APPROVED.
6. ALL PENETRATIONS CREATED BY THIS PROJECT SHALL BE SEALED TO
MAINTAIN THE ARCHITECT SPECIFIED FIRE/SMOKE-RATING OF THE
ASSEMBLY PENETRATED.
7. BOND ALL METALLIC LADDER TRAY AND CABLE TRAY SECTIONS, AND
BOND LADDER TRAY AND CABLE TRAY SYSTEM, TO THE
TELECOMMUNICATIONS GROUNDING BUSBAR OR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR.
8. CEILING MOUNTED DEVICES SHALL BE INSTALLED TO ALIGN
AESTHETICALLY WITH THE CEILING LIGHTING, SPRINKLERS, AND OTHER
FIXTURES. COORDINATE INSTALLATION OF ALL CEILING MOUNTED
DEVICES WITH THE ARCHITECTURAL DRAWINGS AND ALL OTHER
TRADES PRIOR TO INSTALLATION.
9. PROVIDE LONG SWEEP CONDUIT BENDS AND DO NOT EXCEED THE
MANUFACTURER’S WRITTEN RECOMMENDATIONS FOR CABLE BEND
RADIUS.
10. INSTALL CABLING IN A MINIMUM OF 1-1/4" INCH CONDUIT UNLESS
APPROVED IN WRITING.
11. COPPER CIRCUITS FOR ETHERNET COMMUNICATIONS SHALL NOT
EXCEED 290 FEET IN LENGTH. THE CONTRACTOR SHALL FIELD SURVEY
ROUTES AND BRING TO THE ENGINEER’S ATTENTION ANY CIRCUIT THAT
MAY EXCEED THE MAXIMUM DISTANCE.
12. ALL PUBLIC ADDRESS SPEAKERS TO BE CIRCUITED TO RACK MOUNTED
HEAD-END AND AMPLIFIERS LOCATED IN TR N3203.
13. COORDINATE EQUIPMENT DATA CONNECTION POINTS WITH
MECHANICAL AND ELECTRICAL EQUIPMENT MANUFACTURERS. ALL ESS
CABLING AND PATHWAYS SHALL BE INSTALLED CONCEALED WITHIN
WALL CAVITIES.
14. CONTRACTOR TO FURNISH AND INSTALL ALL PASSIVE EQUIPMENT
NECESSARY TO COMPLETE A FULLY FUNCTIONING ENGINEERING
CONTROL CENTER (ECC). ALL ECC EQUIPMENT SHALL BE PLACED ON
SEGREGATED NETWORKS. COORDINATE ALL EQUIPMENT AND
INFRASTRUCTURE REQUIREMENTS WITH VA ENGINEERING PRIOR TO
PROCUREMENT AND INSTALLATION.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :5
P
M
LEVEL 1 - TELECOMMUNICATIONS
FLOOR PLAN
JPH 81KGH
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
TN101
N
3/16" = 1'-0"
LEVEL 1 - TELECOMMUNICATIONS FLOOR PLAN1
TELECOM KEYNOTES
No. REVISION DESCRIPTION DATE
1 PROVIDE TWO (2) 4" CONDUIT STUBBED UP TO TR N3203 ON MEZZANINE
LEVEL. COORDINATE ROUTING WITH OTHER DISCIPLINES AND FIELD VERIFY
EXACT ROUTING LOCATION.
2 FURNISH AND INSTALL TRAFFIC RATED TELECOMMUNICATIONS HANDHOLE.
3 PROVIDE TWO (2) 4" CONDUITS; ONE (1) WITH 12-STRANDS, SINGLE-MODE
FIBER OPTIC CABLING INTERCEPTED FROM EXISTING MANHOLE, INSTALL
PULL CORD IN CONDUIT WHEN ROUTING CABLING. ONE (1) SPARE CONDUIT
WITH PULL CORD.
4 PROVIDE FOUR (4) 4" CONDUITS. ONE WITH 24-STRANDS, SINGLE MODE
FIBER OPTIC CABLING INTERCEPTED FROM EXISTING MANHOLE FOR
TELECOMMUNICATIONS. ONE WITH 24-STRANDS, SINGLE MODE FIBER OPTIC
CABLING INTERCEPTED FROM EXISTING MANHOLE FOR ESS. ONE WITH 25
PAIR OF COPPER AS SECONDARY REDUNDANT FEED. AND ONE SPARE
PATHWAY FOR FUTURE CONNECTIONS FOR TELECOM AND ESS WITH PULL
CORD. REFER TO TELECOMMUNICATIONS SITE PLANS ON SHEETS TS101
AND TS102 FOR CONTINUATION.
5 DATA DEDICATED FOR SECURITY MONITOR WORKSTATION.
6 COORDINATE HIGH CAPACITY AND PATHWAYS AND CABLING
REQUIREMENTS FOR ECC MONITORS AND WORKSTATIONS CONNECTIVITY
TO RACK MOUNTED EQUIPMENT IN TR N3203. ENSURE A NEAT AND
ORDERLY DISTRIBUTION. DROP LOCATIONS ON CMU RATED WALLS TO BE IN
SURFACE MOUNTED CONDUIT.
S
S
S
S
S
S
S
S
TN402
2 5431
E
A
B
C
D
3.9
B.2
A.8
C.2
TN402
ELECTRICAL AREA
N3201
SECURITY
N3204
TR
N3203
CORRIDOR
N3206
BOILER AREA
N3101
EMERGENCY PANELS
N3205
OXYGEN YARD
N3112
COOLER TOWERS & PUMPS
N3202
2D
2D
2D
2D
2D
2D
1. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
2. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
3. ELECTRICAL OUTLETS/ DEVICES INDICATED ARE FOR COORDINATION
AND REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES
DRAWINGS FOR ELECTRICAL WORK REQUIREMENTS AND
SPECIFICATIONS.
4. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF FOURTEEN (14)
WORKING-DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS
DIRECTED OTHERWISE.
5. EXISTING PLANT TELECOMMUNICATIONS INFRASTRUCTURE SHALL
REMAIN IN PLACE AND OPERATIONAL UNTIL THE NEW PLANT CABLING
AND EQUIPMENT HAS BEEN INSTALLED, TESTED AND APPROVED.
6. ALL PENETRATIONS CREATED BY THIS PROJECT SHALL BE SEALED TO
MAINTAIN THE ARCHITECT SPECIFIED FIRE/SMOKE-RATING OF THE
ASSEMBLY PENETRATED.
7. BOND ALL METALLIC LADDER TRAY AND CABLE TRAY SECTIONS, AND
BOND LADDER TRAY AND CABLE TRAY SYSTEM, TO THE
TELECOMMUNICATIONS GROUNDING BUSBAR OR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR.
8. CEILING MOUNTED DEVICES SHALL BE INSTALLED TO ALIGN
AESTHETICALLY WITH THE CEILING LIGHTING, SPRINKLERS, AND OTHER
FIXTURES. COORDINATE INSTALLATION OF ALL CEILING MOUNTED
DEVICES WITH THE ARCHITECTURAL DRAWINGS AND ALL OTHER
TRADES PRIOR TO INSTALLATION.
9. PROVIDE LONG SWEEP CONDUIT BENDS AND DO NOT EXCEED THE
MANUFACTURER’S WRITTEN RECOMMENDATIONS FOR CABLE BEND
RADIUS.
10. INSTALL CABLING IN A MINIMUM OF 1-1/4" INCH CONDUIT UNLESS
APPROVED IN WRITING.
11. COPPER CIRCUITS FOR ETHERNET COMMUNICATIONS SHALL NOT
EXCEED 290 FEET IN LENGTH. THE CONTRACTOR SHALL FIELD SURVEY
ROUTES AND BRING TO THE ENGINEER’S ATTENTION ANY CIRCUIT THAT
MAY EXCEED THE MAXIMUM DISTANCE.
12. ALL PUBLIC ADDRESS SPEAKERS TO BE CIRCUITED TO RACK MOUNTED
HEAD-END AND AMPLIFIERS LOCATED IN TR N3203.
13. COORDINATE EQUIPMENT DATA CONNECTION POINTS WITH
MECHANICAL AND ELECTRICAL EQUIPMENT MANUFACTURERS. ALL ESS
CABLING AND PATHWAYS SHALL BE INSTALLED CONCEALED WITHIN
WALL CAVITIES.
14. CONTRACTOR TO FURNISH AND INSTALL ALL PASSIVE EQUIPMENT
NECESSARY TO COMPLETE A FULLY FUNCTIONING ENGINEERING
CONTROL CENTER (ECC). ALL ECC EQUIPMENT SHALL BE PLACED ON
SEGREGATED NETWORKS. COORDINATE ALL EQUIPMENT AND
INFRASTRUCTURE REQUIREMENTS WITH VA ENGINEERING PRIOR TO
PROCUREMENT AND INSTALLATION.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :0
P
M
MEZZANINE LEVEL -
TELECOMMUNICATIONS FLOOR PLAN
JPH 82 95KGH
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
TN102
N
3/16" = 1'-0" 3/ TY402
MEZZANINE LEVEL - TELECOMMUNICATIONS FLOOR PLAN1
No. REVISION DESCRIPTION DATE
B
B.2
TR
N3203
B.2
ELECTRICAL
PANEL
B.2
3 3
FO PP
HCM
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
RACK MOUNTED PA
SYSTEM
RACK MOUNTED PA
SYSTEM
HCM
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
HCM
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
48 PORT ANGLED
PATCH PANEL
48 PORT SWITCH
4 4 4
10 10
VCMVCMVCMVCM
B
B.2
TR
N3203
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ALL CABINET AND RACK ELEVATIONS SHALL BE COORDINATED WITH
AND APPROVED BY COR PRIOR TO INSTALLATION.
C. VERIFY MOUNTING HEIGHT OF ALL COMMUNICATIONS DEVICES WITH
ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN. WHERE CONFLICTS
EXIST, CONTRACTOR SHALL NOTIFY ENGINEER AND ARCHITECT FOR
RESOLUTION.
D. ALL TELECOMMUNICATIONS SPACE WALLS SHALL BE COVERED WITH
3/4" FIRE-TREATED PLYWOOD. INSTALL PLYWOOD APPROXIMATELY 18"
AFF UTILIZING 4X8 SHEETS. PLYWOOD SHALL BE PAINTED WITH (2)
COATS OF FIRE RESISTANT PAINT LEAVING 3 FIRE RATING EXPOSED.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :0
P
M
TELECOMMUNICATIONS ENLARGED
PLANS
JPH 83 95KGH
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
TN402
N
1/2" = 1'-0" 1/ TN102
TELECOM ROOM ENLARGED FLOOR PLAN11/2" = 1'-0"
TELECOM ROOM ELEVATION PLAN EAST4
1/2" = 1'-0"
TELECOM ROOM ELEVATION PLAN SOUTH51/2" = 1'-0"
TELECOM ROOM ELEVATION PLAN WEST61/2" = 1'-0"
TELECOM ROOM ELEVATION PLAN NORTH7
3/4" = 1'-0"
TELECOM RACK ELEVATION3
N
1/2" = 1'-0" 1/ TN102
TELECOM ROOM ENLARGED CABLE TRAY PLAN2
TELECOM KEYNOTES
No. REVISION DESCRIPTION DATE
1 PROVIDE TWO (2) 4" CONDUIT STUBBED UP FROM GROUND LEVEL. ONE (1)
WITH 12-STRANDS, SINGLE-MODE FIBER OPTIC CABLING, INSTALL PULL
CORD IN CONDUIT WHEN ROUTING CABLING. ONE (1) SPARE CONDUIT WITH
PULL CORD.
2 MOUNT TELECOMMUNICATION MAIN GROUND BUSSBAR (TMGB) AT 6'-6" AFF.
3 ALL TELECOMMUNICATIONS SPACE WALLS SHALL BE COVERED WITH 3/4"
FIRE-TREATED PLYWOOD. INSTALL PLYWOOD APPROXIMATELY 18" AFF
UTILIZING 4X8 SHEETS. PLYWOOD SHALL BE PAINTED WITH TWO (2) COATS
OF FIRE RESISTANT PAINT, LEAVING FIRE RATING EXPOSED.
4 PROVIDE 19" EIA WIDTH FLOOR MOUNTED RACK, MINIMUM 45RU HEIGHT,
AND 29" DEPTH, BLACK IN COLOR.
5 PROVIDE 24-PORT FIBER ENCLOSURE WITH FIBER ADAPTERS FOR
INCOMING FIBER-OPTIC CABLING. COORDINATE EXACT REQUIREMENTS
WITH VA COR. PROVIDE MINIMUM 1RU HORIZONTAL CABLE MANAGER
ABOVE AND BELOW EACH ENCLOSURE.
6 PROVIDE RACK MOUNTED 48-PORT ANGLED PATCH PANELS FOR
TERMINATION OF DATA CAT-6A CABLES. QUANTITY SHOWN IS ESTIMATED,
PROVIDE PATCH PANELS REQUIRED FOR CABLING PLUS 50% GROWTH.
7 CONTRACTOR SHALL FURNISH AND CONTRACTOR SHALL INSTALL PUBLIC
ADDRESS (PA) SYSTEM HEAD-END EQUIPMENT AND AMPLIFIER(S).
8 PROVIDE 2RU HORIZONTAL CABLE MANAGERS (HCM).
9 GOVERNMENT FURNISHED, GOVERNMENT INSTALLED POE SWITCH.
10 DEDICATED RACK SPACE ALLOCATED FOR CONTRACTOR FURNISHED AND
INSTALLED ENGINEERING CONTROL CENTER (ECC) EQUIPMENT. ALL ACTIVE
AND PASSIVE ELECTRONICS, CABLING AND PATHWAY SHALL BE INCLUDED
BY CONTRACTOR. DEDICATED NETWORKS FOR ECC TO
INCLUDE:1.ENGINEERING ETHERNET NETWORKS (CUP CONTROL ROOM)
2. ECC / BMS (JCI METASYS)
3. BOILER BURNER CONTROLS AND BOILER PUMP CONTROL PANELS
4. UPS
5. FIRE ALARM
6. LIGHTING CONTROLS
7. ATS -EMERGENCY GENERATORS
8. LANDSCAPING SPRINKLER SYSTEM (RADIO CONTROLLED)
9. ELECTRICAL POWER MONITORING ELECTRONIC SECURITY SHALL BE
INCLUDED IN THE ECC, BUT WILL BE HOUSED IN SECURITY ROOM. ENSURE
INTEGRATION FROM SECURITY TO CONTROL ROOM ECC.
11 RACK SPACE TO BE UTILIZED FOR ADDITIONAL GOVERNMENT FURNISHED
AND GOVERNMENT INSTALLED RACK MOUNTED EQUIPMENT.
12 PROVIDE LADDER TRAY AS SHOWN, LADDER TRAY DIMENSIONS SHALL BE
12" X 6".
13 PROVIDE FOUR (4) 4" UL FIRE RATED FIRE SLEEVE ASSEMBLIES, FIRE STOP
AS NECESSARY TO MAINTAIN WALL RATING, FROM ABOVE CORRIDOR
CEILING INTO TELECOMMUNICATIONS ROOM.
14 PROVIDE TWO (2) 4" UL FIRE RATED FIRE SLEEVE ASSEMBLIES, FIRE STOP
AS NECESSARY TO MAINTAIN WALL RATING.
1A 1B
CAT 6ACAT 6A
NOTE:
PERMANENTLY LABEL ALL WALL JACKS IN THE FOLLOWING MANNER: BUILDING-FLOOR-JACK NUMBER-ROOM
NUMBER OF CLOSET. EXAMPLE: 1-1-33-148B (BUILDING 1, FLOOR 1, JACK 33, CLOSET ROOM NUMBER 148B). JACK
NUMBER INDICATES THE PUNCH DOWN POSITION OF THE CLOSET CONNECTION. ALL JACKS ON THE SAME PLATE
SHALL HAVE THE SAME NUMBER WHERE POSSIBLE. LABEL ALL JACKS IN ACCORDANCE WITH JCM VAMC IRM-70.
PROVIDE INSULATING
BUSHING ON ALL PATHWAYS
TO COMMUNICATIONS
BACKBOXES.
PROVIDE CATEGORY 6A,
8P8C KEYSTONE FOR DATA
CONNECTION "1B". TERMINATE
ALL DATA CABLES IN TR AT
RACK-MOUNTED 48-PORT
MODULAR PATCH PANELS.
PROVIDE CATEGORY 6A,
8P8C KEYSTONE FOR DATA
CONNECTION "1A". TERMINATE
ALL DATA CABLES IN TR AT
RACK-MOUNTED 48-PORT
MODULAR PATCH PANELS.
PROVIDE SINGLE-GANG,
6-PORT FACEPLATE WITH
IDENTIFICATION WINDOWS.
PROVIDE 1" RACEWAY,
UNLESS NOTED OTHERWISE.
PROVIDE INSULATION
BUSHING AT ENTRANCE TO
BACKBOX.
PROVIDE DOUBLE-GANG
BACKBOX WITH SINGLE-GANG
PLASTER RING.
FILL ALL UNUSED PORTS
WITH BLANK INSERTS. MATCH
COLOR OF FACEPLATE. (TYP.)
WALL MOUNTED BUS BAR KIT INCLUDES
COPPER GROUND BAR, INSULATORS,
AND STAND-OFF BRACKETS. MOUNTING
HEIGHT: 6'6" AFF.
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ALL CABINET AND RACK ELEVATIONS SHALL BE COORDINATED WITH
AND APPROVED BY COR PRIOR TO INSTALLATION.
C. VERIFY MOUNTING HEIGHT OF ALL COMMUNICATIONS DEVICES WITH
ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN. WHERE CONFLICTS
EXIST, CONTRACTOR SHALL NOTIFY ENGINEER AND ARCHITECT FOR
RESOLUTION.
D. ALL TELECOMMUNICATIONS SPACE WALLS SHALL BE COVERED WITH
3/4" FIRE-TREATED PLYWOOD. INSTALL PLYWOOD APPROXIMATELY 18"
AFF UTILIZING 4X8 SHEETS. PLYWOOD SHALL BE PAINTED WITH (2)
COATS OF FIRE RESISTANT PAINT LEAVING 3 FIRE RATING EXPOSED.
GENERAL NOTES
6" UNO (NOTE #4)
[152mm]
3"
[76mm]
TIE WIRE
INNERDUCT, SEE NOTE 5
DUCT BANK NOTES:
1.
2.
3.
4.
5.
6.
7.
3" UNO
[76mm]
CONCRETE SHALL BE 3000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
PROVIDE REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN
CROSSING OR PLACED UNDER ROADWAYS OR PARKING AREAS.
MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 36" [610mm].
PROVIDE MINIMUM 12" [152mm] SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
PROVIDE MAGNETICALLY-DETECTABLE WARNING-TAPE.
INSTALL A MINIMUM OF (3) SPACERS PER 10 LINER FEET OF CONDUIT.
3"
[76mm]
2-WAY DUCT LINE DUCT LINE TYPICAL
AS REQ'D
AS REQ'D
3"
[76mm]
36" MIN
12" MIN MAGNETIC
WARNING TAPE
RED DYE ADDED TO
TOP OF CONCRETE
PLASTIC SPACER
RESTORE SURFACE
DUCT [SIZE AS INDICATED ON DWGS.]
6-WAY DUCT LINE 4-WAY DUCT LINE
BACKFILL
3" UNO
3" UNO
[76mm]
3" UON
[76mm]
3"
[76mm]
[76mm]
3"
[76mm]
[7 m m
" U
N O
[7 m m
" U
N O
[7 m m
[7 m m
(T Y
P
[7 m m
[7 m m
" U
N O
[7 m m
[7 m m
HANDHOLE REQUIREMENTS
1. HOUSING SHALL BE POLYMER CONCRETE REINFORCED WITH A HEAVY WEAVE FIBERGLASS-REINFORCED POLYMER
WITH COMPRESSIVE STRENGTH OF NO LESS THAN 10,000 PSI.
2. COVER AND BOX SHALL WITHSTAND A SERVICE LOAD OF NO LESS THAN 22,500 LBS OVER A 10" x 10" AREA.
3. STRAIGHT-WALL OPEN BOTTOM CONSTRUCTION. CONDUITS SHALL ENTER FROM BOTTOM AND NOT SIDES OF
HANDHOLE.
4. PROVIDE STAINLESS STEEL BOLTS AND INSERTS.
5. PROVIDE WITH (2) 2 1/2" MOUSEHOLES.
6. PROVIDE LABEL "ELECTRICAL" FOR POWER HANDHOLES OR "TELECOMMUNICATIONS" FOR TELECOMMUNICATIONS
HANDHOLES, OR AS INDICATED.
22 24" X 36" X 24" DEEP
CONCRETE
RING AROUND BOX
BOX
AND
COVER
COMPACTED
EARTH
SECTIONAL BOX
WHEN REQUIRED
SKID
RESISTANT
SURFACE
STAINLESS
STEEL HEX
BOLT AND
WASHER
LABEL
PULL SLOT
CRUSHED ROCK
TYPE HANDHOLE SIZING
10"
6"
6"
6"
BELOW BOX
22 13" X 24" X 24" DEEP
22 24" X 24" X 24" DEEP
HANGER WIRE SECURED TO
STRUCTURE ABOVE 3/4" EMT CONDUIT WITH PULL STRING AND
COMPRESSION FITTINGS ROUTED TO
CABLE TRAY, SIZE AS NOTED ON PLANS
(TYP.).
PROVIDE PLASTIC THREADED CONDUIT
BUSHINGS ON EACH END OF CONDUIT.
SECONDARY SUPPORT POINT
NOTES:
1. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING AS
NECESSARY TO FACILITATE MOUNTING OF THE CEILING SPEAKER. REFER TO
MANUFACTURER INSTALLATION SPECIFICATIONS.
2. COORDINATE WITH GC PRIOR TO CONDUIT INSTALLATION.
3. CABLING AND TERMINATION AT SPEAKER TO BE PROVIDED BY CONTRACTOR.
EXPOSED CABLING BETWEEN CONDUIT AND SPEAKER ENCLOSURE SHALL NOT
EXCEED 6".
18"
ABOVE
CEILING
TILE
4. REFER TO MANUFACTURERS RECOMMENDED MOUNTING INSTRUCTIONS.
MOUNT TO ACCESSIBLE CEILING TILE OR UTILIZE CEILING TILE BRIDGE AS
NECESSARY.
TILE BRIDGE BY
CONTRACTOR
RECESSED CEILING
SPEAKER
CEILING TILE
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :0
P
M
TELECOMMUNICATIONS DETAILS
JPH 84 95KGH
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
TN500
NTS
TYPICAL DATA OUTLET1NTS
TYPICAL TELECOMMUNICATIONS MAIN GROUNDING BAR2
No. REVISION DESCRIPTION DATE
NTS
ESS DUCT BANK DETAILS3
NTS
HANDHOLE (TRAFFIC)4NTS
ACCESSIBLE CEILING MOUNTED SPEAKER DETAIL5
1 1
RACK EQUIPMENT FITTINGS KEY:
EXISTING RACK/CABINET
INSTALL NEW MANHOLE
EXISTING FIBER AND PATHWAY.
ONE (1) 4" CONDUIT WITH 12-STRANDS, SINGLE-MODE
FIBER OPTIC CABLING INTERCEPTED FROM EXISTING MANHOLE.
LEVEL 2
MCR IN VAMC BLDG 7
LEVEL 1
NEW CUP BUILDING 16
EXISTING HANDHOLE; INTERCEPT AND SPLICE 12-STRAND
FIBER OPTIC CABLING.
2 35
TWO (2) 4" CONDUITS; ONE (1) WITH 12-STRANDS, SINGLE-MODE
FIBER OPTIC CABLING INTERCEPTED FROM EXISTING MANHOLE,
INSTALL PULL CORD IN CONDUIT WHEN ROUTING CABLING.
ONE (1) SPARE CONDUIT WITH PULL CORD.
7 INSTALL NEW FLOOR MOUNTED RACK
NOTES: (THIS DETAIL ONLY)
1. DIAGRAM DOES NOT REFLECT ACTUAL PATHWAY CONDITIONS. REFER TO
FLOOR PLANS.
2. DIAGRAM DOES NOT REFLECT EXACT COMMUNICATION RACK LOCATIONS OR
QUANTITIES.
VC
LEVEL 02
VC
TELECOMMUNICATION ROOM
PUBLIC ADDRESS RISER LEGEND:
EQUIPMENT RACK/CABINET
RACK-MOUNTED AMPLIFIER.
SPEAKER WIRE
LEVEL 01
PA RISER NOTES:
1. THIS RISER IS DIAGRAMMATICAL IN NATURE AND INTENDED
TO PROVIDE DIRECTION ON CABLING TOPOLOGY FROM
TELECOMMUNICATIONS ROOM TO FIELD DEVICES.
2. ALL CABLING IS NEW UNLESS OTHERWISE NOTED.
3. FIELD DEVICES ARE NEW UNLESS OTHERWISE NOTED.
REFER TO RESPECTIVE FLOOR PLANS FOR ADDITIONAL DIRECTION.
ZONE 1
ZONE 2
ZONE 3
TELECOMMUNICATION ROOM
S S
S S
S S
ZONE 4
ZONE 5
ZONE 6
S S
S S
S S
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ALL CABINET AND RACK ELEVATIONS SHALL BE COORDINATED WITH
AND APPROVED BY COR PRIOR TO INSTALLATION.
C. VERIFY MOUNTING HEIGHT OF ALL COMMUNICATIONS DEVICES WITH
ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN. WHERE CONFLICTS
EXIST, CONTRACTOR SHALL NOTIFY ENGINEER AND ARCHITECT FOR
RESOLUTION.
D. ALL TELECOMMUNICATIONS SPACE WALLS SHALL BE COVERED WITH
3/4" FIRE-TREATED PLYWOOD. INSTALL PLYWOOD APPROXIMATELY 18"
AFF UTILIZING 4X8 SHEETS. PLYWOOD SHALL BE PAINTED WITH (2)
COATS OF FIRE RESISTANT PAINT LEAVING 3 FIRE RATING EXPOSED.
GENERAL NOTES
1 2
3 4
SECONDARY
BONDING BUSBAR
(BY DIV. 26)
WHERE ACCESSIBLE, BOND TGB
TO BUILDING STEEL WITHIN
COMMUNICATIONS ROOM. (BY DIV. 27)
PROVIDE SEPARATE, MINIMUM #6 AWG
STRANDED BONDING CONDUCTOR FROM
EACH RACK AND EQUIPMENT ENCLOSURE
TO TGB. (TYPICAL) (BY DIV. 27)
PROVIDE MINIMUM #6 AWG STRANDED
BONDING CONDUCTOR FROM CABLE TRAY
TO TGB. (BY DIV. 27)
PROVIDE MINIMUM #6 AWG STRANDED
BONDING CONDUCTOR OR BONDING STRAP
BETWEEN SECTIONS AND JUNCTIONS OF
CABLE TRAYS. (TYPICAL) (BY DIV. 27)
PROVIDE BONDING BUSHING AT
CONDUIT END AND MINIMUM #6 AWG
STRANDED BONDING CONDUCTOR
TO CABLE TRAY. (BY DIV. 27)
PROVIDE MINIMUM #6 AWG STRANDED
BONDING CONDUCTOR FROM CABLE
TRAY TO FIRE STOP CABLE PENETRATION
ON EACH SIDE OF WALL. (BY DIV. 27)
FLOORTR - COMMS ROOM CORRIDOR
TO ADDITIONAL TELECOM GROUND BAR TGB
(BY DIV. 26)
LISTED EXOTHERMIC WELD,
LISTED IRREVERSIBLE
COMPRESSION-TYPE CONNECTOR
OR EQUIVALENT (BY DIV. 26)
TO ADDITIONAL TELECOM GROUND BAR TGB
(BY DIV. 26)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :0
P
M
TELECOMMUNICATIONS RISERS AND
DIAGRAMS
JPH 85 95KGH
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
TN600
NTS
TELECOMMUNICATIONS INFRASTRUCTURE RISER1NTS
TYPICAL TELECOMMUNICATIONS PUBLIC ADDRESS RISER2
No. REVISION DESCRIPTION DATE
NTS
TYPICAL TECHNOLOGY GROUNDING AND BONDING RISER DIAGRAM3
DM DM
DM
DM DM
DM
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
DMDM
DM
DM
DM
DM
DM
DM
CR
CRCRCR
CRCRCR
IC
RF RF
RF
RF RF
RF
S
S
S
S
S
CRCR
DM
DM
CR RF
DM
CR
RF
E
A
B
C
D
3.9
B.2
A.8
C.2
M
1 1 1
C-01
C-04
C-01
C-01
C-02 C-02
C-02
C-01
C-02
WP
WP
WP
WP
WP WP WP WP
WP WP
WP
CONTROL ROOM
N3115
CONFERENCE / BREAK ROOM
N3116
RESTROOM
N3117
RESTROOM
N3118
ELECTRICAL UTILITY ROOM
N3108
ELECTRICAL SWITCHGEAR
N3113
GENERATORS
N3114
BOILER AREA
N3101
STORAGE ROOM
N3103
STEAM PIT
N3102
HAC
N3104
CORRIDOR
N3105
ELEC
N3107
CHILLERS
N3111
PIT
N3109
RISER ROOM
N3110
OXYGEN YARD
N3112
WP
WP
1. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
2. EXISTING CONDITIONS INDICATED ARE BASED ON GENERAL FIELD
NOTES AND HISTORICAL DATA AND DOCUMENTATION AND ARE FOR
REFERENCE PURPOSES ONLY TO DEFINE SCOPE OF WORK; FIELD
VERIFY ALL CONDITIONS.
3. ELECTRICAL OUTLETS/ DEVICES INDICATED ARE FOR COORDINATION
AND REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES
DRAWINGS FOR ELECTRICAL WORK REQUIREMENTS AND
SPECIFICATIONS.
4. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF FOURTEEN (14)
WORKING-DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS
DIRECTED OTHERWISE.
5. EXISTING PLANT TELECOMMUNICATIONS INFRASTRUCTURE SHALL
REMAIN IN PLACE AND OPERATIONAL UNTIL THE NEW PLANT CABLING
AND EQUIPMENT HAS BEEN INSTALLED, TESTED AND APPROVED.
6. ALL PENETRATIONS CREATED BY THIS PROJECT SHALL BE SEALED TO
MAINTAIN THE ARCHITECT SPECIFIED FIRE/SMOKE-RATING OF THE
ASSEMBLY PENETRATED.
7. BOND ALL METALLIC LADDER TRAY AND CABLE TRAY SECTIONS, AND
BOND LADDER TRAY AND CABLE TRAY SYSTEM, TO THE
TELECOMMUNICATIONS GROUNDING BUSBAR OR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR.
8. CEILING MOUNTED DEVICES SHALL BE INSTALLED TO ALIGN
AESTHETICALLY WITH THE CEILING LIGHTING, SPRINKLERS, AND OTHER
FIXTURES. COORDINATE INSTALLATION OF ALL CEILING MOUNTED
DEVICES WITH THE ARCHITECTURAL DRAWINGS AND ALL OTHER
TRADES PRIOR TO INSTALLATION.
9. PROVIDE LONG SWEEP CONDUIT BENDS AND DO NOT EXCEED THE
MANUFACTURER’S WRITTEN RECOMMENDATIONS FOR CABLE BEND
RADIUS.
10. INSTALL CABLING IN A MINIMUM OF 1-1/4" INCH CONDUIT UNLESS
APPROVED IN WRITING.
11. COPPER CIRCUITS FOR ETHERNET COMMUNICATIONS SHALL NOT
EXCEED 290 FEET IN LENGTH. THE CONTRACTOR SHALL FIELD SURVEY
ROUTES AND BRING TO THE ENGINEER’S ATTENTION ANY CIRCUIT THAT
MAY EXCEED THE MAXIMUM DISTANCE.
12. ALL PUBLIC ADDRESS SPEAKERS TO BE CIRCUITED TO RACK MOUNTED
HEAD-END AND AMPLIFIERS LOCATED IN TR N3203.
13. COORDINATE…