Design Drawings Electrical_654-212.pdf
PDF 3 MB Posted
- Solicitation number
- QSE--36C10F24R50000
About this file
This document appears to be a set of electrical design drawings for a central utility plant (CUP) project at the VA Sierra Nevada Health Care System in Reno, Nevada. The drawings cover the overall electrical site plan, electrical power and lighting plans, and electrical one-line diagrams for the new CUP facility.
The key details include:
- Design and construction of a new approximately 11,000 GSF CUP building to house boilers, chillers, cooling towers, and bulk oxygen system to provide utilities for the entire VASNHCS campus
- Relocation of the main electrical service from the existing boiler plant to the new CUP
- Demolition of the existing boiler plant and conversion of that site into a paved parking lot
- Improvement of an existing gravel parking lot to create a new paved, lighted, and striped parking area for the facility
The drawings provide detailed electrical layouts, one-line diagrams, feeder/branch circuit schedules, and equipment details to support the CUP project.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. DEPARTMENT OF VETERANS AFFAIRS
ELECTRICAL 30x42 DRAWINGS
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
VA PROJECT NUMBER: 654-212
[07] ELECTRICAL
68 E-000 ELECTRICAL LEGEND AND ABBREVIATIONS
69 ES101 ELECTRICAL SITE PLANS
70 ES102 ELECTRICAL SITE PLAN - CUP
71 EP101 ELECTRICAL POWER FLOOR PLAN - LEVEL 1
72 EP102 ELECTRICAL POWER FLOOR PLAN - MEZZANINE LEVEL
73 EP103 ELECTRICAL POWER FLOOR PLAN - ROOF
74 EL201 ELECTRICAL LIGHTING PLAN
75 EL202 ELECTRICAL LIGHTING PLAN - MEZZANINE LEVEL
76 E-600 NEW ELECTRICAL ONE-LINE DIAGRAM
77 E-601 NEW ELECTRICAL ONE-LINE DIAGRAM
CENTRAL UTILITY PLANT
UE
OE
M/G 400A/3P
M/G 400A/3P
C
PC
R
TS
T
100/3
100/3/70
100/3/70/1
100/3/CB
PP
J
GF
OR
OR
OR
EPO
AM
VM
DM
ST
KK
GFR
M
SPD
R
1,3,5
LP1
A1
LIGHT FIXTURE, CEILING MOUNTED
A1 = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
= ARROW INDICATES AIMING DIRECTION
a
LIGHTING TRACK WITH TRACK LIGHT FIXTURES
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
LIGHT FIXTURE, POLE MOUNTED
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
LIGHT FIXTURE, WALL MOUNTED
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
EMERGENCY BATTERY PACK LIGHT FIXTURE,
WALL MOUNTED
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULe
EMERGENCY BATTERY PACK LIGHT FIXTURE,
CEILING MOUNTED
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
EMERGENCY LIGHT FIXTURE, CEILING MOUNTED
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
A1E a
A1 a
A1
A1
X1E
X1E
Y1E
Y1E
HOMERUN TO PANELBOARD
TICK MARKS INDICATE NUMBER OF CONDUCTORS.
DESIGNATIONS ARE PANELBOARD AND
CIRCUIT NUMBERS.
UNSWITCHED HOT CONDUCTORS SHOWN LEADING
NEUTRAL CONDUCTOR
NEUTRAL CONDUCTOR
SWITCHED HOT CONDUCTORS SHOWN TRAILING
GROUND CONDUCTOR
EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY
ISOLATED GROUNDING CONDUCTOR IN RACEWAY
CONCEALED RACEWAY
EXPOSED RACEWAY
RACEWAY TURNING DOWN
RACEWAY TURNING UP
EQUIPMENT TERMINATION
LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
LIGHT FIXTURE, BOLLARD
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
A1
RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, SPECIAL PURPOSE
RECEPTACLE, TWIST-LOCK
RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO
RECEPTACLE, MOUNTED 6" ABOVE COUNTER,
TYPE AS INDICATED ABOVE
RECEPTACLE DESIGNATIONS AS FOLLOWS:
C = CLOCK HANGER
E = EMERGENCY POWER
GF = GROUND FAULT CIRCUIT INTERRUPTER
IG = ISOLATED GROUND
S = SWITCHED
TR = TAMPER RESITANT
WP = WEATHER PROOF COVER
WR = WEATHER RESISTANT
XP = EXPLOSION PROOF
SWITCH, SINGLE POLE
SWITCH DESIGNATIONS AS FOLLOWS:
2 = TWO-POLE WALL SWITCH
3 = THREE-WAY WALL SWITCH
4 = FOUR-WAY WALL SWITCH
D = DIMMER SWITCH
OS# = OCCUPANCY SENSOR WALL SWITCH, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT
WALL SWITCH
K = KEYED WALL SWITCH
M = MOTOR RATED SWITCH
WP = WEATHER PROOF SWITCH AND COVER
OCCUPANCY SENSOR, CEILING MOUNTED
OS# = CEILING MOUNTED OCCUPANCY SENSOR, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
POWER PACK FOR LIGHTING CONTROL
JUNCTION BOX
RECEPTACLE ON EMERGENCY POWER
RECEPTACLE, ISOLATED GROUND TYPE
MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,
NEMA 5-20R, UNO
SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION
PANELBOARD ON HOUSEKEEPING PAD
PANELBOARD, RECESS MOUNTED
PANELBOARD, SURFACE MOUNTED
TRANSFORMER
DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES
AMPERES/POLES, CB = CIRCUIT BREAKER TYPE
DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES
AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE
COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER
100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER
SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,
3-POLE, UNO
CONTACTOR
PHOTOCELL
RELAY
TIME SWITCH
LOW-VOLTAGE TRANSFORMER
PUSH BUTTON, TYPE AS NOTED
VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH
100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,
NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
UNDERGROUND ELECTRIC LINE
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
CABINET, RECESS MOUNTED
CABINET, SURFACE MOUNTED
RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT
INTERRUPTER, NEMA 5-20R, UNO
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
OVERHEAD ELECTRIC LINE
MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED
TRANSFER SWITCH, RATINGS AS INDICATED
ATS = AUTOMATIC TRANSFER SWITCH
MTS = MANUAL TRANSFER SWITCH
TX#
600AF
500AT
3P
400AS
3P
225AF
LPS-R
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, NON-SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
DRAWOUT CIRCUIT
BREAKER, RATINGS
AS INDICATED
600AF
500AT
3P
CIRCUIT BREAKER,
RATINGS AS
INDICATED
FUSED DISCONNECT
SWITCH, RATINGS
AS INDICATED
400AS
3P
225AF
LPS-R
NEMA 1
COMBINATION FUSED
SWITCH AND STARTER,
RATINGS AS
INDICATED
PANELBOARD,
SINGLE-SECTION,
RATINGS PER
SCHEDULES
PANELBOARD,
MULTI-SECTION,
RATINGS PER
SCHEDULES
AMMETER
VOLTMETER
COMBINATION DIGITAL
AMMETER/VOLTMETER
SHUNT-TRIP RELAY
KIRK-KEY INTERLOCK
GROUND-FAULT RELAY
UTILITY METER
RELAY
SURGE PROTECTION
DEVICE
AUTOMATIC TRANSFER SWITCH WITH BYPASS
TYPE AND RATINGS AS INDICATED
VARIABLE FREQUENCY
DRIVE WITH
DISCONNECT, RATINGS
AS INDICATED
GROUND CONNECTION
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
GROUND CONNECTION
WITH TEST WELL
CONTACT, OPEN
CONTACT, CLOSED
MOTOR
FEEDER TAGCAPACITOR
SURGE ARRESTER
HEATER
225A 3P
NEMA 1
COMBINATION CIRCUIT
BREAKER AND
STARTER, RATINGS AS
INDICATED
225A 3P
200A 3P
ATS#
200A 3P
ATS#
TRANSFORMER
TX#
TRANSFORMER,
SHIELDED
200A DEAD-FRONT ELBOW
600A DEAD-FRONT ELBOW
DEAD-FRONT SPLITTER
FAULT INDICATOR
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CABLE CONNECTION
LIGHTNING PROTECTION GROUND ROD
LIGHTNING PROTECTION CONDUCTOR
LIGHTNING PROTECTION SYMBOLS
ELECTRICAL ONE-LINE DIAGRAM SYMBOLS
LIGHTING SYMBOLS
POWER EQUIPMENT SYMBOLS
WIRING DEVICE SYMBOLS
CIRCUITING SYMBOLS
ES EMERGENCY SHUNT RELAY
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY, OR FIRE ALARM
PLAN NOTE CALL OUT
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL REFERENCE
SECTION CUT DESIGNATION
ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)
EP-101
EP-101
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS (TOP)
ANNUNCIATOR PANELS (TOP)
CLOCK OUTLETS (CENTERLINE)
CONTROLS (TOP)
EXIT SIGNS (WALL-MOUNTED, BOTTOM)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR)
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)
GROUND BAR
INTERCOM (AFEA ONLY)
INTERCOMS (TOP)
PANELS & PANELBOARDS (TOP)
PULL STATIONS (TOP)
PHOTOCELLS
RECEPTACLES (BOTTOM)
RECEPTACLES, EXTERIOR (BOTTOM)
RECEPTACLES, GARAGES (BOTTOM)
RECEPTACLES IN EQUIPMENT ROOMS (TOP)
RECEPTACLES ABOVE COUNTERTOPS (TOP)
REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP)
REMOTE INDICATING LIGHT, FINISHED AREAS (TOP)
SAFETY SWITCHES & STARTERS
SWITCHES (TOP)
TELEPHONE/DATA/TV OUTLETS (BOTTOM)
VISIBLE APPLIANCES (CENTERLINE)
ANNOTATION STANDARD MOUNTING HEIGHTS
ABBREVIATIONS
1P SINGLE-POLE
1PH SINGLE-PHASE
3P THREE-POLE
3PH THREE-PHASE
3W THREE-WIRE
4W FOUR-WIRE
A OR AMP AMPERE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, OR
AUTOMATIC FREQUENCY CONTROL,
OR AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AIP ABANDONED IN PLACE
ALT ALTERNATE
AMB AMBIENT
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY-PASS
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS OR
CANDELA
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED /
OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAXIAL CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUED
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
ETL EXISTING TO BE RELOCATED
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G GROUND OR GENERATOR
GND GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IC INSULATION CONTACT
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
JB OR J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAH KILOVOLT-AMPERE-HOUR
KVAR KILOVOLT-AMPERE-REACTIVE
KW KILOWATT
KWH KILOWATT-HOUR
KWHM KILOWATT-HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTCP LOCAL TEMPERATURE CONTROL PANEL
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MT MOUNT
MTD MOUNTED
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NC NORMALLY CLOSED
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, OR PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PNLBD PANELBOARD
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
RELO RELOCATED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SES SERVICE ENTRANCE SECTION
SF SQUARE FEET (FOOT)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT-AMPERE
VAR VOLT-AMPERE-REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
84" 48" 48" 84" 48" 80" 60"
120" 60" 72" 36" 48" 72" 48"
144" 18" 24" 26" 48" 44" 48"
CEILING
48" 48" 18" 84"
A
# E (CONTINUED) M (CONTINUED)
B
C
D
E
F
N
G
H
I
J
K
L
M
O
P
R
S
T
U
V
W
X
A. ELECTRICAL PLANS AND SECTIONS ARE INTENDED TO
ACCURATELY ILLUSTRATE THE SCOPE OF WORK, BUT ARE STILL
DIAGRAMMATIC IN NATURE.
B. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE
INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING
THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND COMPLIANT
WITH APPLICABLE CODES.
C. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS
WITH BUILDING DISCIPLINES. HOWEVER, COORDINATION WITH
OTHER TRADES IS REQUIRED.
D. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL
INFORMATION REGARDING SCHEDULE AND PHASING
REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF
SERVICES.
E. COORDINATE WITH SCHEDULE WITH THE CONTRACTING
OFFICER'S REPRESENTATIVE BEFORE THE START OF WORK.
F. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE
SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL
EQUIPMENT WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND
TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES
SHALL HAVE DIVIDERS BETWEEN DEVICES.
H. UPDATE ALL PANELBOARD SCHEDULES AFFECTED AT THE
COMPLETION OF THE PROJECT.
GENERAL NOTES
PROJECT CODES AND STANDARDS
A. ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS 2015
B. VA PG-18-13 VA BARRIER FREE DESIGN STANDARD 2018
(SUPPLEMENT TO ABA STANDARDS)
C. ASHRAE STANDARD 90.1-2019 – ENERGY STANDARD FOR
BUILDINGS EXCEPT LOW RISE RESIDENTIAL BUILDINGS
D. IECC 2021 – INTERNATIONAL ENERGY CONSERVATION CODE
E. JCAHO EC 7.40 – EMERGENCY ELECTRICAL POWER SYSTEM
INSPECTION, MAINTENANCE, AND TESTING
F. NFPA 70-2023 - NATIONAL ELECTRICAL CODE (NEC)
G. NFPA 99-2021 – HEALTH CARE FACILITIES CODE
H. NFPA 101-2021 – LIFE SAFETY CODE
I. NFPA 110-2022 – STANDARD FOR EMERGENCY AND STANDBY
POWER SYSTEMS
J. VA PG-18-10 ELECTRICAL DESIGN MANUAL, DECEMBER 2019
K. VA H-18-8 SEISMIC DESIGN REQUIREMENTS
L. VA PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL 2020
(1 JULY 22 REVISION)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :0
A
M
ELECTRICAL LEGEND AND
ABBREVIATIONS
IGM 70ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
E-000
No. REVISION DESCRIPTION DATE
M S P
MSP
WMH
WMH
IC B
W
W
ES101
ES102
EXISTING VA HOSPITAL
EXISTING VA HOSPITAL
EXISTING PARKING
GARAGE
EXISTING BUILDING 7
BLDG. 16 (CUP)
PX1
PX1
PX1
PX1
PX1
PX1
PX2
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :2
A
M
ELECTRICAL SITE PLANS
IGM 71ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
ES101
N
1" = 40'-0"
ELECTRICAL OVERALL SITE PLAN1
N
3/32" = 1'-0"
ENLARGED ELECTRICAL SITE PLAN - NEW PAVED PARKING LOT SITE2
ELECTRICAL GENERAL NOTES:
A. OVERALL SITE PLAN INDICATES AREAS OF WORK. REFER TO ENLARGED PLANS
INDICATED FOR MORE INFORMATION.
B. PARKING LOT PLAN INDICATES SCHEMATIC LAYOUT OF SITE LIGHTING FOR UPGRADE OF
THE EXISTING STORAGE LOT TO A FULLY COMPLIANT STAFF AREA.
C. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
D. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.
E. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK.
REVIEW GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT
BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS.
NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
F. REFER TO ONE-LINE DRAWING SHEETS FOR ADDITIONAL NOTES.
ELECTRICAL KEYNOTES
8 CONNECT NEW NORTH PARKING LOT POLE LIGHTS TO EXISTING 125A,
208Y/120V, 3PH, 4W PANEL PB11A IN BUILDING 6 ELECTRICAL ROOM F1477.
TYPICAL.
12 LIGHTING LAYOUT IS ALSO INTENDED FOR TEMPORARY ADA PARKING LOT.
REFER TO/COORDINATE WITH CIVIL PLANS FOR TEMPORARY ADA PARKING
LOT AND PROVIDE LIGHTING AS SHOWN. MAINTAINED LIGHTING FOR FINAL
PARKING LOT.
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
BLDG. 16 (CUP)
EXISTING PARKING
GARAGE
EXISTING BUILDING 7
EP EXISTING
MEDIUM
VOLTAGE POLE
EP
EXISTING
MEDIUM
VOLTAGE POLE
UE
NEW ELEC
VAULT
NEW ELEC
VAULT
MH-3
MH-4
MH-F
NEW ELEC
VAULT
LV
L V
L V
L V
L V
L V
L V
L V
L V
L V
L V
LV
LVLV LVLVLVLV LV
LV LVLVLV
L V
L V
EXISTING 1MW
GENERATOR
TO REMAIN
NEW FEEDER
ROUTE FROM
EXISTING 1MW
GENERATOR
TO CUP.
NEW FEEDER
ROUTE TO
BLDG. 7
EXISTING MEDIUM
VOLTAGE LINES TO
VASNHCS CAMPUS
TO REMAIN
PX2
PX1
PX2
NEW MEDIUM VOLTAGE
LINES FROM CUP TO
EXISTING ELECTRICAL
VAULT
PX1
PX2
NEW TRAFFIC
RATED PULLBOX
NEW TRAFFIC
RATED PULLBOX
NEW TRAFFIC
RATED PULLBOX
EXISTING
ELEC VAULT
EXISTING
ELEC VAULT
U E
UE
U E
UE
U E
U E
EXISTING
ELEC VAULT
UTILITY MV
SWITCH (SW-1)
UTILITY MV
SWITCH (SW-2)
UEUE
U E
U E
G E
N E
R A
T O
R
N+1
FUTURE
GEN.
(750KW)
LV
LVLV
L V
L V
LV
L V
L V
L V
L V
L V
L V
PX2
NEW ELEC
VAULT
MH-5NEW ELEC
VAULT
MH-6
NEW ELEC
VAULT
MH-7
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :2
A
M
ELECTRICAL SITE PLAN - CUP
IGM 72 92ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
ES102
N
1/16" = 1'-0"
ENLARGED ELECTRICAL SITE PLAN - CENTRAL UTILITY PLANT1
ELECTRICAL GENERAL NOTES:
A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.
C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK.
REVIEW GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT
BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS.
NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
D. UTILITIES PRESENTED ON THESE DRAWINGS ARE SHOWN BASED ON THE BEST
AVAILABLE INFORMATION. FIELD VERIFY THE EXACT LOCATIONS IN THE FIELD PRIOR TO
COMMENCING CONSTRUCTION.
E. REFER TO ONE-LINE DRAWING SHEETS AND FLOOR PLANS FOR ADDITIONAL NOTES.
F. REFER TO CIVIL PLANS FOR LOCATIONS OF MANHOLES, UNDERGROUND CONCRETE
ENCASED CONDUIT ROUTES AND COORDINATION WITH OTHER UTILITIES.
ELECTRICAL KEYNOTES
5 UNDERGROUND ELECTRICAL LINE LOCATIONS ARE APPROXIMATE, FIELD VERIFY
EXISTING UTILITY LINES AND/OR COORDINATE WITH CIVIL PRIOR TO CONSTRUCTION.
6 CONTRACTOR SHALL PERFORM UNDERGROUND SITE SURVEY AND COORDINATE
CROSSINGS OF NEW UTILITY CONDUITS WITH EXISTING UNDERGROUND UTILITIES.
REFER TO CIVIL PLANS FOR ADDITIONAL NOTES ON SITE SURVEYS AND CROSSING OF
UTILITIES.
7 PROVIDE TRAFFIC RATED PULLBOX FOR POWER CONNECTION AND COMMUNICATION
CABLING TO AUTOMATIC GATE. COORDINATE EXACT REQUIREMENTS AND LOCATION
WITH LIFT GATE SUPPLIER PRIOR TO ROUGH-IN.
10 COORDINATE WITH OR REFER TO CIVIL DRAWINGS AND BOND NEW GROUNDING
SYSTEM OF CUP WITH EXISTING GROUNDING COUNTERPOISE LEFTOVER FROM
EXISTING BOILER PLANT (BP). FIELD VERIFY EXISTING BP GROUNDING COUNTERPOISE
PRIOR TO COMMENCEMENT OF WORK.
J
JJ
J
J
J J J
750KW
GENERATOR
16-2
750KW
GENERATOR
16-1
PSG-16-EG
PNL-16-NL1-1
TX-16-NL1-1
PNL-16-NH1-1
TX-16-EL1-1
PNL-16-EL1-1
PNL-16-EH1-1
PNL-16-EL1-2
TX-16-EL1-02
(STACKED)
PNL-16UPS-2
PROVIDE ELECTRICAL
MANHOLE/VAULT FOR
FUTURE POWER SUPPLY
FROM MV SWGR MS-1.
ELEC MH-F
UE UE
UE UE
POWER
DOCKING
STATION
2 5431
E
A
B
C
D
3.9
B.2
A.8
C.2
+48"
WP/WR
USB
USB
USB
WP/WR
WP/WR
WP/WR
WP/WR
WP/WR
GENERATOR
ANNUNCIATOR
EPO 1
EPO 2
EPO 3
16-CH-1
16-CH-2 16-CH-3
16-CH-4
16-PCWP-1
16-PCWP-2
16-PCWP-3
16-PCWP-4
16-CWP-1
16-ST-2
16-ST-1
16-VP-1
16-B-3 16-B-2 16-B-1
16-DA-1
16-AC-1
16-CP-2
16-TT-1
16-FP-1
16-SCWP-3 16-SCWP-2 16-SCWP-1
16-CWHX-1
UTILITY MV
SWITCH W/
METER (SW-1)
UTILITY MV
SWITCH W/
METER (SW-2)
CHILLERS
N3111
STEAM PIT
N3102
BOILER AREA
N3101
ELECTRICAL UTILITY ROOM
N3108
OXYGEN YARD
N3112
STORAGE ROOM
N3103
CONTROL ROOM
N3115
GENERATORS
N3114
OFFICE
N3106
RISER ROOM
N3110
ELECTRICAL SWITCHGEAR
N3113
RESTROOM
N3117
RESTROOM
N3118
CONFERENCE / BREAK ROOM
N3116
HAC
N3104
CORRIDOR
N3105
ELEC
N3107
PIT
N3109
STAIR ENCLOSURE
N3119
WP/WR
(TYP)
USB
USB
15 15 15
15 15 15 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :1
A
M
ELECTRICAL POWER FLOOR PLAN -
LEVEL 1
IGM 73ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
EP101
N
3/16" = 1'-0"
ELECTRICAL POWER FLOOR PLAN - LEVEL 11
ELECTRICAL KEYNOTES
2 PROVIDE CONDUIT FOR FUTURE POWER CONNECTION TO MV SWGR MS-1. REFER
TO SHEET E-601 FOR CONDUIT SIZES AND SHEET EP100 FOR ADDITIONAL NOTES.
9 PROVIDE EPO SWITCHES FOR GENERATORS.
11 MOUNT TRANSFORMER ON STRUCTURE AT 10'+ AFF.
15 PROVIDE POWER CONNECTION TO MOTORIZED ROLL UP DOORS. COORDINATE
EXACT REQUIREMENTS AND LOCATION WITH ROLL UP DOOR SUPPLIER.
ELECTRICAL GENERAL NOTES:
A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.
C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK.
REVIEW GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT
BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS.
NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
D. REFER TO ONE-LINE DRAWING SHEETS FOR ADDITIONAL NOTES.
J
PNLBD
16-EH2-1
MCC
16-EQUIP-2
SWBD 16
ATS-16-MCC-EQUIP-1
ATS-16-MCC-EQUIP-2
ATS-SWBD-16
ATS-16-EQUIP-1
ATS-16-EQUIP-2
ATS-16-EQUIP-3
ATS-16-EQUIP-4
SWBD
08-EG-EM
PNL-16UPS-1
TIE-BKR
TO (P)
CONDUIT IN
STEAM PIT
TO (Q)
CONDUIT IN
STEAM PIT
FROM (P)
CONDUIT IN
MV SWGR
MS-1
FROM (Q)
CONDUIT IN
MV SWGR
MS-1
OE OE
OE OE
OE
OE
FUTURE (Q) AND (P)
CONDUITS WITH PULL
STRING TO ELEC MH-F
MAIN
BKR (P)
MAIN
BKR (Q)
TO
SS-P
TO
SS-Q
OE
2 5431
E
A
B
C
D
3.9
B.2
A.8
C.2
WP/WR
WP/WR
TX-16-EL2-1
PNL-16-EL2-1
16-CT-1
16-ST-1
16-FE-3 16-FE-2 16-FE-1
MCC
16-EQUIP-1
UPS
MV SWGR
MS-1
SWBD SE 16
TX-SE16
SS-Q
SS-P
BOILER AREA
N3101
OXYGEN YARD
N3112
ELECTRICAL AREA
N3201
COOLER TOWERS & PUMPS
N3202
EMERGENCY PANELS
N3205
TR
N3203
SECURITY
N3204
CORRIDOR
N3206 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :2
A
M
ELECTRICAL POWER FLOOR PLAN -
MEZZANINE LEVEL
IGM 74ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
EP102
N
3/16" = 1'-0"
ELECTRICAL FLOOR PLAN - MEZZANINE LEVEL1
ELECTRICAL KEYNOTES
1 PROVIDE OVERHEAD CONDUITS FOR POWER CONNECTION TO EXISTING MEDIUM
VOLTAGE ELECTRICAL VAULT SERVING THE VASNHCS MAIN CAMPUS. REFER TO SHEET
E-600 FOR CONDUIT AND CONDUCTOR QUANTITIES.
14 CONNECT ATS's TO EXISTING ATS CONTROL PANELBOARD/NETWORK IN THE VASNHCS
MEDICAL CENTER. COORDINATE WITH THE VA ENGINEERING MAINTENANCE
DEPARTMENT PRIOR TO ROUGH-IN.
15 PROVIDE POWER CONNECTION TO MOTORIZED ROLL UP DOORS. COORDINATE EXACT
REQUIREMENTS AND LOCATION WITH ROLL UP DOOR SUPPLIER.
ELECTRICAL GENERAL NOTES:
A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.
C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK.
REVIEW GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT
BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS.
NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
D. REFER TO ONE-LINE DRAWING SHEETS FOR ADDITIONAL NOTES.
2 5431
A
B
C
D
3.9
B.2
A.8
C.2
WP/WR
WP/WR
WP/WR
16-VRF-1
16-CU-1
16-CU-2
16-MAU-3 16-MAU-2 16-MAU-1
16-EF-3 16-EF-2 16-EF-1
16-GV-1
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :2
A
M
ELECTRICAL POWER FLOOR PLAN -
ROOF
IGM 75ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
EP103
N
3/16" = 1'-0"
ELECTRICAL FLOOR PLAN - ROOF1
ELECTRICAL GENERAL NOTES:
A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.
C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK.
REVIEW GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT
BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS.
NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
A
B
C
D
3.9
B.2
A.8
C.2
S2S2
S2S2
S2S2
S2 S2
S2S2
S2S2
S2S2
S2S2
S2
S2
S2
S2 S2
S2
S2
S2
S2
S2
S2
S2
S2
S2
S2
S2
S2
S2
S2S2
S2
W1E
W1E
W1E
W1EW1E
W1EW1E
W2E
W2E
W1E
W1E
W2E
W2E
W1E
X1E
X1E
X1E
X1E
X1E
X1E
S2
C1
C1
C1
C1
W2E
X1E
X1E
CHILLERS
N3111
STEAM PIT
N3102
BOILER AREA
N3101
ELECTRICAL UTILITY ROOM
N3108
OXYGEN YARD
N3112
STORAGE ROOM
N3103
CONTROL ROOM
N3115
GENERATORS
N3114
OFFICE
N3106
RISER ROOM
N3110
ELECTRICAL SWITCHGEAR
N3113
RESTROOM
N3117
RESTROOM
N3118
CONFERENCE / BREAK ROOM
N3116
HAC
N3104
CORRIDOR
N3105
ELEC
N3107
PIT
N3109
STAIR ENCLOSURE
N3119
S2
S2 S2
W2E
W2E
S2
X1E
X1E
X1E
X1E th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :1
A
M
ELECTRICAL LIGHTING PLAN - LEVEL 1
IGM 76ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
EL201
N
3/16" = 1'-0"
ELECTRICAL LIGHTING PLAN - LEVEL 11
ELECTRICAL GENERAL NOTES:
A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.
C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK.
REVIEW GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT
BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS.
NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
D. CONTRACTOR TO PROVIDE UNSWITCHED HOT TO POWER ALL EXIT SIGNS AND BYPASS
ANY LIGHTING CONTROLS.
E. ALL EMERGENCY/EGRESS LIGHTS FIXTURES INDICATED ON PLANS SHALL BE PROVIDED
WITH A MINIMUM OF 90 MINUTES BATTERY BACKUP.
A
B
C
D
3.9
B.2
A.8
C.2
S2 S2
S2
S2
S1 S1 S1 S1
S1S1S1S1
S1 S1 S1 S1
S1 S1 S1 S1
W1E
W1E
W1E
W1E W1E
W1E X1E X1E
X1E
X1E
X1E
S2 S2 S2
S2
S2
S2
S2
S2
S3
S3
S3
S2
S2
S2
X1E
W1E
BOILER AREA
N3101
OXYGEN YARD
N3112
ELECTRICAL AREA
N3201
COOLER TOWERS & PUMPS
N3202
EMERGENCY PANELS
N3205
TR
N3203
SECURITY
N3204
CORRIDOR
N3206
STAIR ENCLOSURE
N3119 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :1
A
M
ELECTRICAL LIGHTING PLAN -
MEZZANINE LEVEL
IGM 77ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
EL202
N
3/16" = 1'-0"
ELECTRICAL LIGHTING PLAN - MEZZANINE LEVEL1
ELECTRICAL GENERAL NOTES:
A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.
C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK.
REVIEW GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT
BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS.
NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
D. CONTRACTOR TO PROVIDE UNSWITCHED HOT TO POWER ALL EXIT SIGNS AND BYPASS
ANY LIGHTING CONTROLS.
E. ALL EMERGENCY/EGRESS LIGHTS FIXTURES INDICATED ON PLANS SHALL BE PROVIDED
WITH A MINIMUM OF 90 MINUTES BATTERY BACKUP.
4000AF
4000AT
3P
480Y/277V, 3PH, 4W4000 AMPS
ELECTRICAL ROOM N3201 NEMA 1 ENCLOSURE
SWBD SE16
600AF
600AT
3P
ST
G F
R
DM
800AF
800AT
3P
ATS-SWBD-16
3P
600A
480Y/277V, 3PH, 4W
750KW STANDBY (NEW)
1200A/3P M/G
480Y/277V, 3PH, 4W4000 AMPS
EMERGENCY PNL RM N3205 NEMA 1 ENCLOSURE
SWBD 16-EG-EM
ATS-16-MCC-EQUIP-1
3P
800A
800AF
800AT
3P
S
ATS-16-EQUIP-1
3P
800A
TIE
BREAKER
1200AF
200AT
3P
1200AF
200AT
3P
1200AF
200AT
3P
1200AF
200AT
3P
M
1200AF
200AT
3P
M
M M
24.9KV, 3PH, 3W1200AMPS
ELECTRICAL ROOM N3201 NEMA 1 ENCLOSURE
MV SWGR MS-1
E T
D
E T
D
E T
D
E T
D
800AF
800AT
3P
1600AF
1200AT
3P
1600AF
1200AT
3P
480Y/277V, 3PH, 4W
750KW STANDBY (NEW)
1200A/3P M/G
S
480Y/277V, 3PH, 4W4000 AMPS
ELECTRICAL SWGR RM N3113 NEMA 1 ENCLOSURE
PSG-16-EG
800AF
800AT
3P
600AF
600AT
3P
Y
/2 V
P N
L -1
-N
H -1
A
TX-16-NL1-1
45 KVA
480V- 208Y/120V
3PH, 4W
T
G
Y
/1 V
P N
L -1
-N
L -1
A
200AF
200AT
3P
1200AF
200AT
3P
4000AF
4000AT
3P
TX-SE16
2500 KVA
PAD-MTD XFMR
24.9KV-
480Y/277V
3PH, 4W2
A
PE
T
D
E T
D
3P
VFD
E T
R
E T
R
1200AF
200AT
3P
1200AF
200AT
3P
800AF
800AT
3P
800AF
800AT
3P
800AF
800AT
3P
600AF
600AT
3P
800AF
800AT
3P
800AF
800AT
3P
3P
VFD
3P
VFD
3P
VFD
800AF
800AT
3P
800AF
800AT
3P
800AF
800AT
3P
ATS-16-MCC-EQUIP-2
3P
600A
600AF
600AT
3P
600AF
600AT
3P
480Y/277V, 3PH, 4W
1000KW STANDBY (ETR)
1600A/3P M/G
S
DM
4000AF
4000AT
3P
E T
D
E T
D
SPDSPD
KK
3200AF
3200AT
3P
KK
480Y/277V, 3PH, 4W2500 AMPS
NE EXTERIOR WALL NEMA 3R ENCLOSURE
POWER DOCKING STATION
DM
A
P
ATS-16-EQUIP-2
3P
800A
ATS-16-EQUIP-3
3P
800A
ATS-16-EQUIP-4
3P
800A
1600AF
1600AT
3P
1600AF
1200AT
3P
S
NO
FEEDER (Q)
NC
NV ENERGY
UTILITY
METER
NV ENERGY
UTILITY
METER
NV ENERGY
SUTRO 241
SUBSTATION
NV ENERGY
HOLCOMB 241
SUBSTATION
NV ENERGY UTILITY
EQUIPMENT
1200AF
200AT
(2) SPARES
METERING
SECTION
MV SWITCH (SW-1)
(BY NV ENERGY )
MV SWITCH (SW-2)
(BY NV ENERGY )
M V
M V
M V
M V
FEEDER (P)
FEEDER (P)FEEDER (Q)
SS-P
(SELECTOR
SWITCH P)
SS-Q
(SELECTOR
SWITCH Q)
M V
FEEDER (P)FEEDER (Q)
M V
16-CH-1
EXISTING MV
ELECTRICAL
VAULT
EXISTING 24.9KV
BUSBARS IN ELECTRIC
VAULT
EXISTING 24.9KV
BUSBARS IN ELECTRIC
VAULT
BUS (P)BUS (Q)
TO BUS (P) IN OTHER
24.9kV ELECTRIC VAULT
(NOT IN SCOPE)
TO BUS (Q) IN OTHER
24.9kV ELECTRIC VAULT
(NOT IN SCOPE)
SIDE (P)SIDE (Q)
NC
PROVIDED
BY DIV. 23
TO EXISTING
SWITCH GEAR
NORTH EXTEROR
OF BUILDING 7
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
SWBD 16 MCC 16-
EQUIP-1
MCC 16-
EQUIP-2
ELECTRICAL UTILITY
ROOM NC108
ELECTRICAL ROOM N3201
PROVIDE CONDUITS
TO ELEC MH-F FOR
FUTURE POWER
CONNECTION (REF.
SHEETS
EP101/EP102 )
M C
M C
16-CH-2 16-CH-3 16-CH-4
GENERATOR
CONNECTION
LOAD BANK
CONNECTION
GENERATOR 6
GENERATOR 16-2
GENERATOR 16-1
(2) SPARES
TO FUTURE N+1
GENERATOR
CONNECTION
C th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :1
A
M
NEW ELECTRICAL ONE-LINE DIAGRAM
IGM 78ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
E-600
FEEDER/BRANCH CIRCUIT SCHEDULE
TAG AMPS DESCRIPTION
23 20A (3)#12, (1)#12G, 3/4 IN. C
33 30A (3)#10, (1)#10G, 3/4 IN. C
43 40A (3)#8, (1)#10G, 3/4 IN. C
53 50A (3)#8, (1)#10G, 3/4 IN. C
63 60A (3)#6, (1)#10G, 1 IN. C
73 70A (3)#4, (1)#8G, 1 IN. C
74 70A (4)#4, (1)#8G, 1-1/4 IN. C
104 100A (4)#3, (1)#8G, 1-1/4 IN. C
153 150A (3)#1/0, (1)#6G, 1-1/2 IN. C
154 150A (4)#1/0, (1)#6G, 1-1/2 IN. C
173 175A (3)#2/0, (1)#6G, 1-1/2 IN. C
174 175A (4)#2/0, (1)#6G, 2 IN. C
204 200A (4)#3/0, (1)#6G, 2 IN. C
603 600A (2) 3 IN. C, EACH W/ (3) 350KCMIL, (1)#1G
604 600A (2) 3 IN. C, EACH W/ (4) 350KCMIL, (1)#1G
803 800A (3) 3 IN. C, EACH W/ (3) 300KCMIL, (1)#1/0G
804 800A (3) 3 IN. C, EACH W/ (4) 300KCMIL, (1)#1/0G
1204 1200A (4) 3 IN. C, EACH W/ (4) 350KCMIL, (1)#3/0G
1604 1600A (6) 3 IN. C, EACH W/ (4) 300KCMIL, (1)#4/0G
2004 2000A (6) 3 IN. C, EACH W/ (4) 400KCMIL, (1) 250KCMIL G
2504 2500A (7) 3-1/2 IN. C, EACH W/ (4) 500KCMIL, (1) 350KCMIL G
4004 4000A (12) 3-1/2 IN. C, EACH W/ (4) 400 KCMIL, (1) 500KCMIL G
ETD N/A EXISTING TO DEMO
ETR N/A EXISTING TO REMAIN
G150 GND #6 COPPER GROUND, 3/4 IN. C
G300 GND #2 COPPER GROUND, 3/4 IN. C
S804 800A (3) 3 IN. C, EACH W/ (4) 300KCMIL
S1004 1000A (3) 3 IN. C, EACH W/ (4) 400KCMIL
S1204 1200A (4) 3 IN. C, EACH W/ (4) 350KCMIL
S1604 1600A (6) 3 IN. C, EACH W/ (4) 300KCMIL
S2004 2000A (6) 3 IN. C, EACH W/ (4) 400KCMIL
T104 100A (4)#3, (1)#6G, 1-1/4 IN. C
T154 150A (4)#1/0, (1)#6G, 2 IN. C
T224 225A (4)#4/0, (1)#2G, 2-1/2 IN. C
T404 400A (2) 2 IN. C, EACH W/ (4)#3/0, (1)#2G
NOTE:
ALL CONDUCTOR SIZES ARE BASED ON 75 DEGREE C RATED TERMINATION AND COPPER
CONDUCTORS WITH TYPE THHN/THWN-2 INSULATION. FOR TERMINATION OR INSULATION
TYPES RATED LESS THAN 75 DEGREE C, MODIFY SIZES ACCORDING TO NFPA 70.
MV203 200A (3) SETS OF 4IN. C, EACH W/ (1) 25KV 2/0, & (1) 4 IN. SPARE C. WITH PULL STRING
NTS
NEW ELECTRICAL ONE-LINE DIAGRAM - CENTRAL UTILITY PLANT1
ELECTRICAL KEYNOTES
3 CONNECT EXISTING 1MW GENERATOR (#6 GENERATOR) TO PSG 16-EG AFTER
DEMOLITION OF EXISTING BOILER PLANT. FIELD VERIFY EXISTING CONDUCTOR
TERMINATIONS IN BOILER PLANT AND COORDINATE DISCONNECTION OF
GENERATOR WITH THE MAINTENANCE DEPARTMENT. RE-ROUTE
CONDUITS/CONDUCTORS TO PSG 16-EG IN ROOM 149 OF NEW CUP.
13 REFER TO EQUIPMENT ELEVATION DRAWING (2/E-600) ON THIS SHEET FOR
EQUIPMENT SECTION DETAILS. BASIS OF DESIGN ASCO POWER TECHNOLOGIES;
APPLICATION #OP-230223-12940570. CONTACT JUSTON VOGT (TEL: 913-444-3132).
MC203 200A (4) SETS OF 4IN. C WITH PULL STRING
No. REVISION DESCRIPTION DATE
C1204 --- (4) 3 IN. C
NTS
PSG EQUIPMENT ELEVATION DETIALS2
480Y/277V, 3PH, 4W600 AMPS
EMERGENCY PNL RM N3205 NEMA 1 ENCLOSURE
MCC 16-EQUIP-2
TX-16-EL1-1
75 KVA
480V- 208Y/120V
3PH, 4W
G
TX-16-EL1-2
75 KVA
480V- 208Y/120V
3PH, 4W
T
G
480Y/277V, 3PH, 4W800 AMPS
EMERGENCY PNL RM N3205 NEMA 1 ENCLOSURE
MCC 16-EQUIP-1
P N
L -1
-E
L -1
P N
L -1
-E
L -2
Y
/2 V
P N
L -1
-E
H -1
A
200AF
175AT
3P
200AF
150AT
3P
60AF
60AT
3P
100AF
70AT
3P
60AF
60AT
3P
60AF
60AT
3P
3P
VFD
3P
VFD
60AF
50AT
3P
60AF
50AT
3P
3P
VFD
3P
VFD
3P
VFD
Y
/1 V
P N
L -1
U
P S
-1
A
Y
/1 V
P N
L -1
U
P S
-2
A
30AF
20AT
3P
3P
VFD
60AF
60AT
3P
60AF
60AT
3P
3P
VFD
3P
VFD
60AF
60AT
3P
300AF
20AT
3P
3P
VFD
3P
VFD
60AF
40AT
3P
3P
VFD
60AF
40AT
3P
3P
VFD
P N
L -1
-E
H -1
T
100AF
100AT
3P
60AF
60AT
3P
3P
VFD
60AF
50AT
3P
3P
VFD
60AF
60AT
3P
3P
VFD
30AF
20AT
3P
3P
VFD
60AF
40AT
3P
3P
VFD
600AF
600AT
3P
DM
480Y/277V, 3PH, 4W600 AMPS
EMERGENCY PNL RM N3205 NEMA 1 ENCLOSURE
SWBD 16
SPD SPD
TX-16-EL2-1
30 KVA
480V- 208Y/120V
3PH, 4W
T
G
P N
L -1
-E
L -1
30AF
25AT
3P
30AF
25AT
3P
3P
VFD
3P
VFD
3P
VFD
3P
VFD
30AF
25AT
3P
30AF
25AT
3P
800AF
800AT
3P
DM
600AF
600AT
3P
DM
SPD
30AS
3P
15AT
30AF
15AT
3P
30AS
3P
15AT
30AF
15AT
3P
30AS
3P
15AT
30AF
15AT
3P
30AS
3P
20AT
30AF
20AT
3P
30AS
3P
15AT
30AF
15AT
3P
30AS
3P
15AT
30AF
15AT
3P
30AS
3P
15AT
30AF
15AT
3P
16-PCWP-1
16-CWP-2
16-SCWP-1
16-CWP-4
UPS BATTERY
CABINET
45KVA UPS 480V- 208Y/120V
16-CT-1 16-AC-1
16-AC-216-CT 2 16-CT-4
16-B-1
(2) 100A
EQUIP.
SPACE
(2) 100A
EQUIP.
SPACE
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
16-PCWP-3 16-AC-316-CT-3
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
PROVIDED
BY DIV. 23
(2) 100A
EQUIP.
SPACE
ATS-SWB-16
16-SCWP-3
16-SCWP-2
16-B-3
16-B-2
16-CWP-1
PROVIDED
BY DIV. 23
16-CWP-3
PROVIDED
BY DIV. 23
16-PCWP-2
PROVIDED
BY DIV. 23
16-PCWP-4
PROVIDED
BY DIV. 23
ATS-16-MCC-
EQUIP-1
ATS-16-MCC-
EQUIP-2
16-MAU-1 16-MAU-3
16-MAU-2
16-VRF-1 16-EF-1 16-EF-3
16-EF-3
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :1
A
M
NEW ELECTRICAL ONE-LINE DIAGRAM
IGM 79ES
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
IOANNIS A. LOUGARIS VA
975 KIRMAN AVE
RENO, NV 89502
E-601
NTS
NEW ELECTRICAL ONE-LINE DIAGRAM - CENTRAL UTILITY PLANT1
FEEDER/BRANCH CIRCUIT SCHEDULE
TAG AMPS DESCRIPTION
23 20A (3)#12, (1)#12G, 3/4 IN. C
33 30A (3)#10, (1)#10G, 3/4 IN. C
43 40A (3)#8, (1)#10G, 3/4 IN. C
53 50A (3)#8, (1)#10G, 3/4 IN. C
63 60A (3)#6, (1)#10G, 1 IN. C
73 70A (3)#4, (1)#8G, 1 IN. C
74 70A (4)#4, (1)#8G, 1-1/4 IN. C
104 100A (4)#3, (1)#8G, 1-1/4 IN. C
153 150A (3)#1/0, (1)#6G, 1-1/2 IN. C
154 150A (4)#1/0, (1)#6G, 1-1/2 IN. C
173 175A (3)#2/0, (1)#6G, 1-1/2 IN. C
174 175A (4)#2/0, (1)#6G, 2 IN. C
204 200A (4)#3/0, (1)#6G, 2 IN. C
603 600A (2) 3 IN. C, EACH W/ (3) 350KCMIL, (1)#1G
604 600A (2) 3 IN. C, EACH W/ (4) 350KCMIL, (1)#1G
803 800A (3) 3 IN. C, EACH W/ (3) 300KCMIL, (1)#1/0G
804 800A (3) 3 IN. C, EACH W/ (4) 300KCMIL, (1)#1/0G
1204 1200A (4) 3 IN. C, EACH W/ (4) 350KCMIL, (1)#3/0G
1604 1600A (6) 3 IN. C, EACH W/ (4) 300KCMIL, (1)#4/0G
2004 2000A (6) 3 IN. C, EACH W/ (4) 400KCMIL, (1) 250KCMIL G
2504 2500A (7) 3-1/2 IN. C, EACH W/ (4) 500KCMIL, (1) 350KCMIL G
4004 4000A (12) 3-1/2 IN. C, EACH W/ (4) 400 KCMIL, (1) 500KCMIL G
ETD N/A EXISTING TO DEMO
ETR N/A EXISTING TO REMAIN
G150 GND #6 COPPER GROUND, 3/4 IN. C
G300 GND #2 COPPER GROUND, 3/4 IN. C
S804 800A (3) 3 IN. C, EACH W/ (4) 300KCMIL
S1004 1000A (3) 3 IN. C, EACH W/ (4) 400KCMIL
S1204 1200A (4) 3 IN. C, EACH W/ (4) 350KCMIL
S1604 1600A (6) 3 IN. C, EACH W/ (4) 300KCMIL
S2004 2000A (6) 3 IN. C, EACH W/ (4) 400KCMIL
T104 100A (4)#3, (1)#6G, 1-1/4 IN. C
T154 150A (4)#1/0, (1)#6G, 2 IN. C
T224 225A (4)#4/0, (1)#2G, 2-1/2 IN. C
T404 400A (2) 2 IN. C, EACH W/ (4)#3/0, (1)#2G
NOTE:
ALL CONDUCTOR SIZES ARE BASED ON 75 DEGREE C RATED TERMINATION AND COPPER
CONDUCTORS WITH TYPE THHN/THWN-2 INSULATION. FOR TERMINATION OR INSULATION
TYPES RATED LESS THAN 75 DEGREE C, MODIFY SIZES ACCORDING TO NFPA 70.
No. REVISION DESCRIPTION DATE
MV203 200A (3) SETS OF 4IN. C, EACH W/ (1) 25KV 2/0, & (1) 4 IN. SPARE C. WITH PULL STRING
MC203…