Design Drawings Plumbing_654-212.pdf

PDF 2 MB Posted

Attached to
Design Build Central Utilities Plant - Reno NV -- Y1NB
Solicitation number
QSE--36C10F24R50000
Issued by

About this file

This document is a set of design drawings for the plumbing system of a Central Utility Plant (CUP) project at the VA Sierra Nevada Health Care System in Reno, Nevada. The project scope includes replacing the existing seismically deficient boiler plant, demolishing the existing Boiler Plant (Building 8), and constructing a new approximately 11,000 GSF CUP structure to house boilers, chillers, cooling towers, and a bulk oxygen system. The drawings provide details on the plumbing piping, fixtures, and equipment, including domestic water, waste, storm, and medical gas systems. Key equipment shown includes water heaters, air compressors, sump pumps, and backflow preventers. The drawings also include general notes, pipe routing, and installation details. This information is provided for reference and the selected design-build contractor is not obligated to incorporate the conceptual design.

View the file

Other files

File Type Posted
SolicitationAmendment0003.pdf PDF
S05 Response to Solicitation 36C10F24R50000 RFI No. 25.docx DOCX document
SolicitationAmendment0002.pdf PDF
S05 Response to Solicitation 36C10F24R50000 RFIs.docx DOCX document
SolicitationAmendment0001.pdf PDF
QSE 36C10F24R50000.pdf PDF
Design Drawings General_654-212.pdf PDF
Construction Specifications Volume 2_654-212.pdf PDF
Design Drawings Electrical_654-212.pdf PDF
Design Drawings Mechanical_654-212.pdf PDF
Construction Specifications Volume 3_654-212.pdf PDF
Lead Paint Survey Building 8_ 2014_654-212.pdf PDF
Design Drawings Telecommunications_654-212.pdf PDF
Design Drawings Civil_654-212.pdf PDF
Geotechnical Engineering Report_654-212.pdf PDF
Design Drawings Structural_654-212.pdf PDF
P07 Wage Determination Washoe County Nevada Mar 22 2024.pdf PDF
Construction Specifications Volume 1_654-212.pdf PDF
Design Drawings Architectural_654-212.pdf PDF
Design Drawings Fire Protection_654-212.pdf PDF
Solicitation.pdf PDF
Asbestos Survey Building 8_2014_654-212.pdf PDF
Supplemental Comments to Design Drawings and Narratives_654-212.pdf PDF
Design Discipline Narratives_654-212.pdf PDF
Structural Calculations Report_654-212.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. DEPARTMENT OF VETERANS AFFAIRS

PLUMBING 30x42 DRAWINGS

VA SIERRA NEVADA HEALTH CARE SYSTEM

975 KIRMAN AVE

RENO, NV 89502

VA PROJECT NUMBER: 654-212

[05] PLUMBING

51 P-000 PLUMBING LEGEND

52 P-101 PLUMBING PLANS

53 P-501 PLUMBING DETAILS

54 P-502 PLUMBING DETAILS

55 P-503 PLUMBING DETAILS

56 P-601 PLUMBING SCHEDULES

CENTRAL UTILITY PLANT

MA

MV

CO

VEAI

FOV

FOR

FOS

LPG

NPW

NO

O

N

G

MPG

CA

CD

ACD

VAV

AW

ST

OST

GW

SS

SCW

140°ORAL EVACUATION

LABORATORY VACUUM

LABORATORY AIR

INDUSTRIAL AIR

LA

LV

OA

IA

FILTERED COLD WATERFCW

FUEL OIL DISCHARGEFOD

SQUARE FLOOR DRAIN (FD)

ROOF DRAIN (RD), SIZE & TYPESQUARE FLOOR SINK (FS)

CONDENSATE DRAIN

NATURAL GAS

NITROUS OXIDE

LIQUIFIED PETROLEUM GAS

COMPRESSED AIR

NITROGEN

MEDICAL AIR

OXYGEN

DOMESTIC HOT WATER RECIRC.

STORM DRAIN

ACID WASTE

DOMESTIC COLD WATER

DOMESTIC HOT WATER

140° DOMESTIC HOT WATER (140°)

SANITARY SEWER

GREASE WASTE

SOFTENED COLD WATER (SCW)

ACID VENT VENT

WALL CLEANOUT (WCO)

FLOOR CLEANOUT (FCO)

OVERFLOW STORM DRAIN

NON POTABLE WATER (NPW)

FUEL OIL SUPPLY

FUEL OIL RETURN

FUEL OIL VENT

AUXILIARY CONDENSATE DRAIN

CARBON DIOXIDE

MEDICAL VACUUM

MEDICAL VACUUM EXHAUSTMEDICAL AIR INTAKE

MEDIUM PRESSURE NATURAL GAS

END OF LINE CLEANOUT

PLUMBING EQUIPMENT DESIGNATIONXX-1

A. ALL PIPING SHALL BE COORDINATED WITH CIVIL UTILITY PIPING, FIRE PROTECTION,

DUCTWORK, MECHANICAL PIPING, LIGHTING, STRUCTURAL AND ARCHITECTURAL SYSTEMS.

B. PIPE CLEANOUTS SHALL BE LINE SIZE (6" MAX.). LOCATE 100' APART MAXIMUM FOR SIZES UP

THROUGH 6".

C. PLUMBING VENTS THROUGH ROOF (VTR) SHALL BE 3" MINIMUM. SMALLER VTR'S INDICATED

SHALL INCREASE TO 3" PIPE, 12" BELOW ROOF.

D. ACCESS PANELS SHALL BE PROVIDED FOR ALL WATER HAMMER ARRESTORS LOCATED IN

WALLS TO ACCESS EQUIPMENT. PANEL SHALL BE AS LARGE AS PRACTICAL FOR THE

FUNCTION THEY ARE INTENDED.

E. DO NOT SCALE DRAWINGS, SEE ARCHITECTURAL FLOOR PLAN FOR DIMENSIONS.

F. ALL PLUMBING WORK SHALL COMPLY WITH THE 2021 INTERNATIONAL PLUMBING CODE.

G. PIPE ROUTING IS SCHEMATIC AS SHOWN AND IS NOT INTENDED TO INDICATE EXACT

ROUTING. CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSET AND FITTINGS REQUIRED

FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES.

H. CONCEAL PIPING ABOVE CEILING AND WITHIN WALLS OR CHASES, EXCEPT IN MECHANICAL

SPACES OR WHEN OTHERWISE NOTED.

DHWR

DHW

DCW

ABBREVIATIONS

PLUMBING PIPING TYPES

A/E ARCHITECT / ENGINEER

B

BFP REDUCED PRESSURE BACKFLOW

PREVENTER

BHP BRAKE HORSEPOWER

BT BATHTUB

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

DA

F FAHRENHEIT

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

E

ET EXPANSION TANK

FD FLOOR DRAIN

FM FLOW METER

FOP FUEL OIL PUMP

FOV FUEL OIL VENT

G

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GT GREASE TRAP

K

J

J INTENTIONALLY LEFT BLANK

ID INSIDE DIAMETER

H

H&CW HOT & COLD WATER

HB HOSE BIBB

HD HUB DRAIN

HP HORSEPOWER

HWP HOT WATER PUMP

I

L

L/s LITERS PER SECOND (OR LITERS/SECOND)

LA LABORATORY AIR

LBS/HR POUNDS PER HOUR

NTS NOT TO SCALE

N

NC NORMALLY CLOSED

NG NATURAL GAS

M

M METER, SI UNIT

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH 1000 BTUH

P

PP PLUMBING PUMP

PA PASCAL

PD PRESSURE DROP

PG PRESSURE GAGE

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PTRV PRESSURE TEMPERATURE RELIEF VALVE

O

O OXYGEN

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

Q

Q INTENTIONALLY LEFT BLANK

TCV TEMPERATURE CONTROL VALVE

TD TEMPERATURE DIFFERENCE, TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TSTAT THERMOSTAT

TWR TEMPERED WATER RETURN

SAN SANITARY SEWER

SCFM STANDARD CUBIC FEET PER MINUTE

SQ FT SQUARE FOOT (FEET)

SS SANITARY SEWER, STAINLESS STEEL

ST STORM SEWER, STORAGE TANK

R

RD ROOF DRAIN

RO REVERSE OSMOSIS

T

X INTENTIONALLY LEFT BLANK

W

W WASTE

WC WATER CLOSET

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

V VENT

VP VACUUM PUMP

VSD VARIABLE SPEED DRIVE

X

V

DEMOLITION GENERAL NOTES:

PL-100

DETAIL NUMBER

SHEET NUMBER

SHEET NUMBER

SECTION NUMBER

1 OWNER FURNISHED, CONTRACTOR

INSTALLED EQUIPMENT DESIGNATION

EXISTING TO BE DEMOLISHED

EXISTING TO REMAIN

NEW PIPE

CONNECT NEW TO EXISTING

LIMIT OF DEMOLITION

GENERAL PIPING SYMBOLS

GENERAL ANNOTATIONS

AV

STRAINER

FLOAT & THERMOSTATIC

STEAM TRAP

INVERTED BUCKET

STEAM TRAP

FLANGE CONNECTION PIPE DROP

PIPE RISER

TEE DOWN

TEE UP UNION

PRESSURE REDUCING

VALVE

BALL VALVE

ANGLE GLOBE VALVE SAFETY RELIEF VALVE

GLOBE VALVE

MANUAL OR

AUTOMATIC AIR VENT

PRESSURE AND

TEMPERATURE TEST PLUG

FLOW METER

PLUMBING PIPING SYMBOLS

CAP

REDUCER (ECCENTRIC)

Name

XX-XX

ANCHOR

TEE

DIRECTION OF FLOW

S

DIRECTION OF PIPE

PITCH (DOWN)

FM

MV

PLUMBING VALVE SYMBOLS

ROOM TAG

PUMP

REDUCER (CONCENTRIC)

BUTTERFLY VALVE

CHECK VALVE

THERMOMETER

PRESSURE GAUGE

YCO YARD CLEANOUT

Y

Z INTENTIONALLY LEFT BLANK

Z

AD AREA DRAIN

AFF ABOVE FINISHED FLOOR

AG AIR GAP

AFG ABOVE FINISHED GRADE

AP ACCESS PANEL

AS AUTOMATIC SPRINKLER

ASD ADJUSTABLE SPEED DRIVES

ASD AUTOMATIC SPRINKLER DRAIN

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATION, AIR CONDITIONING

ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING

ENGINEERS

ASR AUTOMATIC SPRINKLER RISER

AV ACID VENT

AW ACID WASTE

BSP BLACK STEEL PIPE

C

C CENTIGRADE (CELSIUS)

CFM CUBIC FEET PER MINUTE

CV CONTROL VALVE

CO CLEANOUT

CA COMPRESSED AIR

CGA COMPRESSED GAS ASSOCIATION

CI CAST IRON

CS CLINICAL SINK

DCW DOMESTIC COLD WATER

DFU DRAINAGE FIXTURE UNITS

DHW DOMESTIC HOT WATER

DI DEIONIZED WATER

DW DISHWASHER

DHWR DOMESTIC HOT WATER RETURN

DHWS DOMESTIC HOT WATER SUPPLY

DN DOWN

DS DOWNSPOUT

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

EX. EXISTING

EWS/SH EYE WASH/ DRENCH SHOWER

EWS EYE WASH STATION

EWH ELECTRIC WATER HEATER

ETR EXISTING TO REMAIN

ESH EMERGENCY SHOWER

ESC ESCUTCHEON

EPACT ENERGY POLICY ACT

EMCS ENERGY MONOSERRAT AND

CENTRAL SYSTEM

EPA ENVIRONMENTAL PROTECTION AGENCY

EL ELEVATION

F

FDC FIRE DEPARTMENT (HOSE) CONNECTION

FFA FROM FLOOR ABOVE

FFB FROM FLOOR BELOW

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FS FLOOR SINK

FS FLOW SWITCH

FU FIXTURE UNITS

GAL GALLONS

GCO GRADE CLEANOUTS

GPS GAS REGULATOR STATION

GVTR GAS VENT THROUGH ROOF

GWH GAS FIRED UNIT HEATER

HX HEAT EXCHANGER

HS HAND SINK

HST HOT WATER STORAGE TANK (DOMESTIC)

HWB HOT WATER BOILER

HWCP HOT WATER CIRCULATING PUMP

HYD HYDRANT

IE INVERT ELEVATION

ICW INDUSTRIAL COLD WATER

IHW INDUSTRIAL HOT WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

kW KILOWATT kWh KILOWATT HOUR

LAV LAVATORY

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LV LABORATORY VACUUM

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LW LOW WATER

MED MEDICAL

MER MECHANICAL EQUIPMENT ROOM

MH MANHOLE

MOU MEMORANDUM OF UNDERSTANDING

MSB MOP SERVICE BASIN

MV MEDICAL VACUUM

N2 NITROGEN

N2O NITROUS OXIDE

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM. NOMINAL

NPW NON POTABLE WATER

OC ON CENTER

OR OPERATING ROOM

OVFL OVERFLOW

PDI PLUMBING AND DRAINAGE INSTITUTE

PO POTABLE WATER

RDL ROOF DRAIN LEADER

RL ROOF LEADER

RP RECIRCULATION PUMP

RWL RAIN WATER LEADER

SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL

ASSOCIATION

SCW SOFTENED COLD WATER

SDMH STORM DRAIN MANHOLE

SMH SANITARY MANHOLE

SP SUMP PUMP

SPR SPRINKLER LINE

SW STORM WATER

TEMP TEMPERATURE

TFA TO FLOOR ABOVE

TFB TO FLOOR BELOW

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

U

U INTENTIONALLY LEFT BLANK

VS VENT STACK

VTR VENT THROUGH ROOF

VAC VACUUM

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

WCO WALL CLEANOUT

WH WALL HYDRANT, WATER HEATER

WHA WATER HAMMER ARRESTER

WL WATER LINE

WM WATER METER

WS WASTE STACK

WSFU WATER SUPPLY FIXTURE UNITS

YH YARD HYDRANT

BACKFLOW PREVENTER (BFP, RPBP)

NONFREEZE WALL

HYDRANT

PLUMBING CLEANOUT AND DRAIN SYMBOLS

MODULATING CONTROL

VALVE

THERMOSTATIC MIXING

VALVE

M MOTOR OPERATED VALVE

I. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.

J. PROVIDE TRAP PROTECTION FOR ALL FLOOR DRAINS.

K. PROVIDE AN AIR GAP, WHEN REQUIRED BY CODE, SERVING INDIVIDUAL FIXTURES, DEVICES, APPLIANCES AND APPARATUS.

L. COORDINATE PIPING WITH ELECTRICAL EQUIPMENT PRIOR TO INSTALLATION. ROUTE PIPING

TO AVOID ELECTRICAL EQUIPMENT AND CLEARANCE AREAS.

M. ANY DEVIATIONS IN ELECTRICAL REQUIREMENTS FROM THE BASIS OF DESIGN FOR THE

PLUMBING EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR TO

ENSURE COORDINATION WITH THE ELECTRICAL CONTRACTOR FOR PROPER SIZE

ELECTRICAL MATERIAL AND EQUIPMENT AT NO ADDITIONAL COST.

N. PROVIDE SHOCK ARRESTORS PER STANDARD PDI-WH-201.

O. SEAL ALL FIRE AND SMOKE BARRIER PENETRATIONS IN ACCORDANCE WITH THE APPLICABLE

BUILDING CODE, SPECIFICATIONS, AND DETAILS. REFER TO ARCHITECTURAL DRAWINGS FOR

LOCATIONS AND RATINGS OF FIRE AND SMOKE WALLS, BARRIERS, AND PARTITIONS.

ROUND FLOOR DRAIN (FD)

GENERAL NOTES:

A. VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY GENERAL CONTRACTOR

REGARDING CONFLICTS BEFORE PROCEEDING WITH WORK.

B. VERIFY SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION.

RELOCATE, REMOVE AND ADJUST MECHANICAL AND ELECTRICAL ITEMS AS NECESSARY TO

COORDINATE WITH NEW WORK.

C. AFTER DEMOLITION IS COMPLETE, PATCH AND REPAIR FINISHES TO MATCH EXISTING

CONDITIONS.

D. COORDINATE DEMOLITION WITH GENERAL CONTRACTOR. NOTIFY GENERAL CONTRACTOR

AND OWNER IF A SHUDTOWN OF UTILITIES IS REQUIRED.

E. PROTECT EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING DEMOLITION.

F. TEMPORARILY MOVE OR TAKE EQUIPMENT OUT OF SERVICE AS NECESSARY TO COMPLETE

WORK.

G. SAWCUT CONCRETE FLOOR AS REQUIRED FOR DEMOLITION WORK INDICATED. COORDINATE

WITH NEW PLUMBING BEFORE CUTTING ANY FLOOR. CONTRACTOR TO X-RAY FLOORS FOR

ALL STRUCTURAL FLOORS.

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

RPBP REDUCED PRESSURE BACKFLOW PREVENTER

MEDICAL GAS SYMBOLS

O WALL OUTLET - OXYGEN

MA WALL OUTLET - MEDICAL AIR

MV WALL OUTLET - MEDICAL VACUUM

N WALL OUTLET - NITROGEN

NO WALL OUTLET - NITROUS OXIDE

CO WALL OUTLET - CARBON DIOXIDE

LA WALL OUTLET - LABORATORY AIR

LV WALL OUTLET - LABORATORY VACUUM

AREA ALARM PANEL (AAP-X)

MASTER ALARM PANEL (MAP-X)

ZONE VALVE BOX (ZVB-X)

AAP-X

MAP-X

ZVB-X

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

CODY DOUGLAS

ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022

MECH - JAMES R. MYLES #027005 EXP. 12/31/2023

ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023

CIVIL ENGINEER

CALIBRE ENGINEERING

9090 S. RIDGELINE BLVD, SUITE 105

HIGHLANDS RANCH, CO 80129

(303) 730-0434

BEN MURPHY

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

2519 MADISON AVENUE, SUITE 100

KANSAS CITY, MO. 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

STRUCTURAL ENGINEER

DEGENKOLD ENGINEERS

375 BEALE STEET, SUITE 500

SAN FRANCISCO, CA 94105

(415) 354-6439

ROBERT GRAFF

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

FRANK FINLEY

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:5 :1

P

M

PLUMBING LEGEND

CMT 48JRM

LEVEL 1 SD2 RFP

CENTRAL UTILITY PLANT

02/28/2023

654-212

VA SIERRA NEVADA HEALTH CARE SYSTEM

975 KIRMAN AVE

RENO, NV 89502

P-000

SPUR #: 1791.06

No. REVISION DESCRIPTION DATE

51 95

2 5431 3.9

CHILLERS

N3111

OXYGEN YARD

N3112

ELECTRICAL SWITCHGEAR

N3113

GENERATORS

N3114

CONTROL ROOM

N3115

CONFERENCE / BREAK ROOM

N3116

RESTROOM

N3117

RESTROOM

N3118

ELECTRICAL UTILITY ROOM

N3108

PIT

N3109

RISER ROOM

N3110

OFFICE

N3106

ELEC

N3107

CORRIDOR

N3105

HAC

N3104

STORAGE ROOM

N3103

STEAM PIT

N3102

E

A

B

C

D

P-528

P-103

P-414

P-103

P-414

P-707

P-502

16-WH-1

P-701

P-701

P-812

FD

FD

NATURAL GAS & DOMESTIC

WATER ENTRANCE LOCATION

WATER TESTING LOCATION

WATER TREATMENT

LOCATION

P-512

FD

FD

FD

FD

FDFD

FD

FD

FD

GENERAL AREA FOR FLOOR

TRENCH LOCATED AROUND

AND BEHIND THE BOILERS FOR

BLOWDOWN AND FUEL PIPING.

SPECIFIC CONFIGURATION

SHALL BE COORDINATED WITH

FINAL BOILER SELECTION.

P-804

P-804

P-804

P-804

2 5431 3.9

E

A

B

C

D

16-MAU-116-MAU-216-MAU-3

16-EF-3 16-EF-2 16-EF-1

P-815

FD-CFD-C

P-804

P-804 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

CODY DOUGLAS

ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022

MECH - JAMES R. MYLES #027005 EXP. 12/31/2023

ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023

CIVIL ENGINEER

CALIBRE ENGINEERING

9090 S. RIDGELINE BLVD, SUITE 105

HIGHLANDS RANCH, CO 80129

(303) 730-0434

BEN MURPHY

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

2519 MADISON AVENUE, SUITE 100

KANSAS CITY, MO. 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

STRUCTURAL ENGINEER

DEGENKOLD ENGINEERS

375 BEALE STEET, SUITE 500

SAN FRANCISCO, CA 94105

(415) 354-6439

ROBERT GRAFF

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

FRANK FINLEY

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:5 :2

P

M

PLUMBING PLANS

CMT 49JRM

LEVEL 1 SD2 RFP

CENTRAL UTILITY PLANT

02/28/2023

654-212

VA SIERRA NEVADA HEALTH CARE SYSTEM

975 KIRMAN AVE

RENO, NV 89502

P-101

SPUR #: 1791.06

N

1/8" = 1'-0"

PLUMBING PLAN - FIRST FLOOR1

N

1/8" = 1'-0"

PLUMBING PLAN - ROOF LEVEL2

52 95

WALL LINE

FINISHED FLOOR

WATER LINE

FROM METER

T O

B

T

T

M

F

R E

LI

E

P

E N

IN

G

S

AIR GAP

FITTING

PIPE TO DRAIN

(TYPICAL)

ELEVATION

PLAN

COLD WATER TO

SYSTEM

PIPE SUPPORT

REDUCED PRESSURE PRINCIPLE

BACKFLOW PREVENTER WITH

GATE VALVES

M

IN

2"

FLOAT &

THERMOSTATIC TRAP

ASSEMBLY

THERMOMETER

GRAVITY STEAM

CONDENSATE

RETURN

DIELECTRIC

FITTING

NOTES:

1. VERTICAL COIL TYPE DOMESTIC WATER HEATER IS SHOWN. IF HORIZONTAL TUBE BUNDLE TYPE IS FURNISHED, PIPING SHALL BE

SIMILAR.

2. SEE PLUMBING DRAWINGS FOR PIPING CONNECTIONS.

3. PIPING TO UPPER HEATER HEAD SHOULD BE PROVIDED WITH UNION OR FLANGES, LOCATED OUTSIDE THE OUTER DIAMETER OF

HEAD TO FACILITATE REMOVAL OF HEAD AND SHELL.

4. PIPING BETWEEN CONTROL VALVE AND HEATER CONNECTION SHOULD BE AS SHORT AS POSSIBLE.

5. PROVIDE INTEGRAL OR EXTERNAL HEAT TRAPS.

6. PROVIDE HOSE CONNECTION TO DRAIN.

TRAP OR ORIFICED UNION FITTING FURNISHED

BY MANUFACTURER OF DOMESTIC WATER

HEATER, SEE PLUMBING DWGS.

SCALE POCKET

DRAIN FLOOR

DCW

DHWR

CONTROL VALVE BY

MANUFACTURER OF DOMESTIC

WATER HEATER

STEAM SUPPLY LPS

OR MPS

TEMPERATURE & PRESSURE RELIEF VALVE

BY MANUFACTURER OF DOMESTICWATER

HEATER ROUTE TO NEAREST FLOOR DRAIN

PRESSURE GAUGE

D H

W

DOMESTIC WATER

HEATER

M

IN

6"

H E

A T

E R

A B

O V

LO

O R

, S

P

LU

M B

IN

G

D

R A

W

IN

G S

M

1"

1"

1"

1"

1"

2" INTAKE

TYP.

PRESS.

GA.

RECEIVER/DRYER

MUFFLER/FILTER

TYP. METAL BRAID

FLEX CONNECTION

AIR COMPRESSORS

HOUSEKEEPING PAD

MASON ISOLATORS

FLOOR

1/2" TO F.D.

TYP.

PRESS.

REG.

DUPLEX SUMP PUMP

BASEMENT

FLOOR

84"

12"

PUMP OFF

FLOAT

36"

PUMP ON

12"

HIGH WATER

ALARM

6" INLET HUB F.L.

ELEV. = XXX.XX'

CHECK VALVE

AUTOMATIC FLOAT

SWITCH

SHUT-OFF VALVE

3" UP

PROVIDE U-BOLT CLAMPED

LOOSELY AROUND GAS PIPE

TO ALLOW EXPANSION

ROOFING CONTRACTOR SHALL PROVIDE 10"x30"

SHEETS OF ROOFING MEMBRANE BETWEEN CONC.

BLOCK AND ROOF SYSTEM.

6"x6"x24" CONCRETE SUPPORT POURED OFF OF

ROOF AND MOVED INTO LOCATION AFTER SETUP.

PROVIDE SUPPORTS AT 8'-0" CENTERS MAXIMUM.

GAS MAIN SEE ROOF PLAN ON

SHEET P2.06

EXPANSIONLOOP

TAKE-OFF (TYPICAL)GAS PIPE

UNISTRUT EMBEDDED IN

CONCRETE

EXTERIOR WALL

6" GAS, SEE PLAN

FOR CONTINUATION

SLEEVE CAULKING AND

SEALANT (LINKBELT SEAL

OPTIONAL)

SIZE SLEEVE TO PROVIDE A MIN.

OF 2" CLEARANCE ALL AROUND.

FLOOR

GRADE

GAS METER, SEE PLAN

FOR LOCATION.

GAS LINE SLEEVE,

SEE SITE PLAN FOR

CONT.

3" (OR AS SIZED BY

UTILITY COMPANY).

GAS LINE

SLEEVE VENT

STANDARD FLAT-HEAD GAS

COCK WITH BRASS PLUG AND

WASHER.

GAS PRESSURE REGULATOR

6000 CFH FROM 35 LBS.

TO 15 INCHES W.C.

UNION (TYP).

3"

6"

BALANCING

DEVICE

NOTES:

1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.

BALL OR BUTTERFLY

TYP.

FLEXIBLE

CONNECTION

STRAINER

1/2"

PRESSURE GAGE

PIPE HANGERS - PROVIDE DOUBLE

DEFLECTION NEOPRENE (TYPE HN)

FORFIRST TWO ON EACH SIDE OF PUMP

(SEENOTE NO. 1)

1/4" Ø MOLLY BOLT HOLLOW WALL

ANCHOR (1 EA. SIDE OF LAV)

STEEL WALL PLATE

WALL ANCHOR

STUDS

STEEL HANGER BY LAV MFGR

SECTION A

PLAN

NOTE:

1. AT LAVS WITH FOOT PEDAL CONTROLS PROVIDE AN ADDITIONAL 16 GAGE GALVANIZED

STEELPLATE 12"x16" SECURED TO A MINIMUM OF 2 STUDS PER FOOT PEDAL.

2. PROVIDE 20 GAGE STUDS WHEN HEIGHT EXCEEDS 12'-0".

FOR FIXTURE HEIGHT

SEE ARCHITECTURAL

DRAWINGS

MIN. (3) 1/4" MACHINE

BOLTS W/DOUBLE LOCK

NUTS ON BACK SIDE

MIN. 5 1/4" Ø GALV. MACHINE

BOLTS WELDED TO PLATE

TYP. 1/8"

MINIMUM 16 GAGE GALVANIZED

STEELPLATE 12"x48" MIN. SECURED

TO A MIN. 4 STUDS PER LAVATORY

1/4"

A A

T O

F

LO

O R

3' -3

V A

R

IE

S

12"x16" [300x400mm]

STAINLESS STEEL ACCESS

DOOR WITH OPERATED

CYLINDER LOCK

SOLENOID

[8 m m

][1

5m m

F O

R F

IX

T

U R

E H

E

IG

H T

S

S E

E A

R C

H

IT

E C

T U

R A

L

D R

A W

IN

G

S

[4 m m

FINISHED FLOOR

FINISHED WALL

GRAB BAR,

SEE ARCH.

DRAWINGS

BACK CHECK

ANGLE STOP

SOLENOID

OPERATED FLUSH

VALVE

MOUNT ELECTRONIC SENSOR

IN 12"x16" [300x400mm] PANEL

TRANSFORMER IN

JUNCTION BOX

3' -5

2' -9

T O

C E

N T

E R

LI

N

E S

U P

P

LY

E

LL

T O

C E

N T

E R

LI

N

E O

F O

U

TL

E T

[1

0m m

24" [600mm] SLIDE

BAR

SHOWER CONTROL TYPE

T/P

WARP ENTIRE FLOOR

(ASSUMES TOPPING

SLAB)

DRAIN

[1

0m m

[8 m m

GRAB BAR

[8 m m

] [1

0m m

[2

0m m

[1

0m m

[150mm] [225mm]

VACUUM

BREAKER

CURTAIN ROD

SHOWER HEAD

[225mm] [150mm]

5' -4

[1

0m m

6' -6

[1

0m m

3' -4

6' -0

2' -9

3' -6

2' -9

5' -6

6' -8

6" 9" 9" 6" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

CODY DOUGLAS

ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022

MECH - JAMES R. MYLES #027005 EXP. 12/31/2023

ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023

CIVIL ENGINEER

CALIBRE ENGINEERING

9090 S. RIDGELINE BLVD, SUITE 105

HIGHLANDS RANCH, CO 80129

(303) 730-0434

BEN MURPHY

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

2519 MADISON AVENUE, SUITE 100

KANSAS CITY, MO. 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

STRUCTURAL ENGINEER

DEGENKOLD ENGINEERS

375 BEALE STEET, SUITE 500

SAN FRANCISCO, CA 94105

(415) 354-6439

ROBERT GRAFF

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

FRANK FINLEY

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:5 :2

P

M

PLUMBING DETAILS

CMT 50JRM

LEVEL 1 SD2 RFP

CENTRAL UTILITY PLANT

02/28/2023

654-212

VA SIERRA NEVADA HEALTH CARE SYSTEM

975 KIRMAN AVE

RENO, NV 89502

P-501

SPUR #: 1791.06

NTS

BACKFLOW PREVENTER PIPING DETAIL1

NTS

CONNECTIONS TO DOMESTIC WATER HEATER2

NTS

AIR COMPRESSOR PIPING DETAIL3NTS

DUPLEX SUMP-PUMP-DETAIL4

NTS

GAS LINE ROOF SUPPORT DETAIL5NTS

GAS METER / REGULATOR / ENTRY DETAIL6

NTS

IN-LINE PUMPS - CONNECTIONS7

NTS

LAVATORY MOUNTING DETAIL8

NTS

P-112 WATER CLOSET DETAIL - SENSOR OPERATED9

NTS

P-701 SHOWER DETAIL10

53 95

HOT PIPECOLD PIPE

REFER TO SPECIFICATIONS FOR INSULATION TYPES, INSULATION

THICKNESSES, HANGER TYPES, HANGER ROD CONNECTIONS TO SRUCTURE

AND HANGER SPACING.

CUT INSULATION TO FIT AROUND

HANGER. SEAL EXPOSED

INSULATION ENDS WITH JOINT

SEALANT.

PROVIDE A SECTION OF HIGH

DENSITY INSULATION OR

STYROFOAM BILLETS AT EACH

HANGER OF COLD INSULATED PIPE.

THREADED STEEL ROD WITH

NUT AND WASHER BOTH

SIDES (TYP.).

CLEVIS HANGER, SHOWN FOR CLARITY.

SIZE HANGER FOR COLD PIPE OUTSIDE

DIAMETER PLUS INSULATION THICKNESS.

DO NOT PENETRATE INSULATION WITHE

HANGER.

CLEVIS HANGER, SHOWN FOR

CLARITY. SIZE HANGER FOR HOT

PIPE OUTSIDE DIAMETER.

SECURE PIPE HANGER TO

STRUCTURE (TYP.)

PROVIDE SHORT INSULATION SHIELD

FOR LAPPING INSULATION JACKET

OVER HIGH DENSITY INSULATION OR

STYROFOAM BILLETS. MAINTAIN

VAPOR BARRIER.

EXTERIOR SIDE OF CONCRETE WALL

1/4" [6mm] STEEL PLATE WATER STOP &

ANCHOR COLLAR

FLEXIBLE EXPANSION JOINT MIN.

DEFLECTION 15" [375mm] MIN.

EXPANSION 4" [100mm]

STAINLESS STEEL BOLTS, NUTS &

WASHERS

RESILIENT

WATERPROOF

CAULKING

5/8" [16mm] ROD

WELD

PIPE CENTERED IN

SLEEVE

[5 0m m

MODULAR TYPE WALL

PENETRATION SEAL

FLANGED CONNECTION

[1 m m

1/4"x1/4" [6x6mm] IRON

PIPE CLAMP

STANDARD WEIGHT GAL. STEEL

PIPE SLEEVE

1/4"x1/4" [6x6mm] IRON

PIPE STRAP

INTERIOR SIDE OF

WALL

4"

3/4"

PRESSURE REDUCING VALVE

SET AT 12 PSI

INSULATING

UNION

1 1/2" STEEL TO

H.H.W. SYSTEM1 1/2" G.V. FOR

QUICK FILL

1 1/2" COPPER

DOM. C.W.

RAW WATER

FILTERED

WATER

LT

2" DRAIN TO

FLOOR SINK

1" CPVC PIPE PIPE

TAPPING

1" CPVC PIPE TAPPING WITH NC

SHUTOFF VALVE PIPED TO DRAIN.

1" CPVC PIPE

TAPPING AND 1"

CPVC PIPE TO

CIRCULATING PUMP

LEVEL TRANSMITTER 2"

NPT FOR CONTROL STACK.

SEE DETAIL

SOV

1" CPVC PIPE RO SUPPLY TO

STEAM GENERATORS

1" CPVC PIPE RO RETURN FROM RO

DISTRIBUTION LINE

SOFTENER

TANK #2

1" CPVC FROM WATER

SOFTENER TO CARBON

FILTERS

BRINE TANK

2" VENT PIPE TO

DRAIN

2" CPVC PIPE PIPE

TAPPING

RO UNIT

LAL

LT

LAH

LAH

ENGAGE, WITHIN 8 INCHES

OF BOTTOM

LOW LEVEL ALARM, 4"

INCHES OF BOTTOM

LAH HIGH LEVEL ALARM #2, WITHIN 3"

INCHES OF TOP HIGH LEVEL

ALARM #1, WITHIN 6" INCHES OF

TOP DISENGAGE, WITHIN 10"

INCHES OF TOP

2" OVERFLOW PIPE

TO DRAIN

TWO 0.5" GAGE GLASS

TAPPINGS WITH ISOLATION

BALL VALVES

DUPLEX

CARBON

WATER

FILTER #1

DUPLEX

CARBON

WATER

FILTER #2

DUPLEX

WATER

SOFTENER

TANK #1

RO BUFFER TANK 4 HOUR

MIN. STORAGE

[1 m m

6" M

IN

UNDERDECK CLAMP

NOTE:

CAST INTO CONCRETE ROOF. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

INSULATE ROOF DRAIN SUMP AND PIPE PER SPECIFICATIONS. LOCATE DRAINS WHERE

SHOWN ON ARCHITECTURAL PLANS; VERIFY WITH STRUCTURAL PLANS FOR ROOF

LOW POINTS. COORDINATE WITH STRUCTURAL DRAWINGS REGARDING PROVISION

FOR SUPPLEMENTARY STEEL FRAMING AROUND ROOF OPENING.

LONG RADIUS ELBOWS

PROVIDE PIPE HANGER AS

CLOSE TO JOINT AS POSSIBLE

TO TAKE WEIGHT OFF ROOF

DRAINS.

INSULATED ROOF

STRUCTURE

GRAVEL STOP AND

MEMBRANE CLAMP TO

SECURE FLASHING

OVERFLOW (SECONDARY)

DRAIN. REFER TO PLANS

FOR OUTLET SIZE.

DO NOT OVERLAP

SUMP RECEIVERS

SLOPE HORIZONTAL PIPE AS

INDICATED ON FLOOR PLAN

OR IN SPECIFICATIONS

PRIMARY ROOF DRAIN. REFER

TO PLANS FOR OUTLET SIZE

WEIR - APPROXIMATELY

2" HIGHER THAN

PRIMARY DRAIN

2" SCH. 40 STEEL PIPE FOR

PHYSICAL PROTECTION

2" THREADED

CONN. WELDED TO

PLATE

12"x12"x1/2"

STEEL PLATE

8" ISLAND CURB

EARTH

POROUS FILL

PER SPEC'S.

3/4" CW

VALVE BODY

1" GALVANIZED

STEEL PIPE

1/2" ANCHOR BOLT

(TYP. OF 4)

CONCRETE

DRIVE

1/4" WEEP HOLES

3/4" HOSE

CONN.

/2

FINISHED FLOOR

SURFACE

WALL

ROUGH FLOOR SLAB

DRAIN BODY POURED IN

PLACE - RECESSED 1/2"

BELOW ROUGH SLAB

SURFACE

CLAMP PAN TIGHTLY

INTO DRAIN COLLAR

CURB

LEAD PAN

SHOWER DRAIN

STRAINER

3/4" PIPE FROM COLD

WATER SUPPLY TO WATER

HEATER, WITH NO CHECK

VALVES INTERVENING

FDA-COMPLIANT BUTYL

DIAPHRAGM

WELDED STEEL

EXPANSION TANK WITH

POLYPROPYLENE

LINING, NSF APPROVED

FOR DOMESTIC WATER

SERVICE

NOTE:

PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS.

FOLLOW MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION PROCEDURE.

VERIFY PROPER OPERATION WHEN INSTALLED. PROVIDE SEISMIC STRAP OR

BRACING WHEN REQUIRED BY LOCAL AUTHORITIES.

PIPE HANGER NEXT TO

ELBOW

PROVIDE DIELECTRIC

PIPE UNION AT TANK

CONNECTION FOR

CONNECTION OF

DISSIMILAR METALS

AIR CHARGING VALVE, FILL

TANK WITH AIR PRESSURE

TO MATCH WATER

PRESSURE.

TO MAIN BUILDING

WASTE DRAIN

WATERPROOF SEALANT

SLEEVE THROUGH SLAB

SEALANT BACKING

MATERIAL

FLOOR SLAB

FLOOR DRAIN WITH

TRAP PRIMER ADAPTER

1/2" TRAP PRIMER LINE

DISTRIBUTION UNIT. AVAILABLE FOR 4

ADDITIONAL LINES. PROVIDE ACCESS

PANEL BENEATH LAVATORY.

TRAP PRIMER VALVE

DOMESTIC COLD WATER (DCW) LINE

1/2" TRAP PRIMER SUPPLY SEDIMENT LOOP

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

CODY DOUGLAS

ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022

MECH - JAMES R. MYLES #027005 EXP. 12/31/2023

ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023

CIVIL ENGINEER

CALIBRE ENGINEERING

9090 S. RIDGELINE BLVD, SUITE 105

HIGHLANDS RANCH, CO 80129

(303) 730-0434

BEN MURPHY

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

2519 MADISON AVENUE, SUITE 100

KANSAS CITY, MO. 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

STRUCTURAL ENGINEER

DEGENKOLD ENGINEERS

375 BEALE STEET, SUITE 500

SAN FRANCISCO, CA 94105

(415) 354-6439

ROBERT GRAFF

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

FRANK FINLEY

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:5 :2

P

M

PLUMBING DETAILS

CMTJRM

LEVEL 1 SD2 RFP

CENTRAL UTILITY PLANT

02/28/2023

654-212

VA SIERRA NEVADA HEALTH CARE SYSTEM

975 KIRMAN AVE

RENO, NV 89502

P-502

SPUR #: 1791.06

NTS

PIPE HANGER DETAIL2NTS

PIPE PENETRATION THROUGH WALLS BELOW GRADE3

NTS

PRESSURE REDUCING VALVE FOR COLD WATER MAKE-UP4

NTS

REVERSE OSMOSIS PACKAGE DETAIL5NTS

ROOF AND OVERFLOW DRAIN DETAIL6

NTS

ROOF HYDRANT DETAIL7

NTS

SHOWER DRAIN DETAIL8NTS

EXPANSION TANK DETAIL9

NTS

TRAP PRIMER1

54 95

NOTE:

PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITONS. REFER TO SPECIFICATIONS FOR MORE INFORMATION. PIPE AND CONDUIT OF ALL TRADES MAY BE COMBINED ON THE SAME SUPPORT CHANNEL. COORDINATE SUPPORT CHANNEL LENGTH WITH PIPING AND CONDUIT TO BE SUPPORTED. SUPPORT CHANNEL SPACING SHALL BE DETERMINED BY SMALLEST PIPE TO BE SUPPORTED. CHANNEL SUPPORT MAY BE USED AS A WALL BRACKET, ATTACH TO WALL WITH ANCHOR BOLTS PER SPECIFICATIONS. FOR HORIZONTAL INSULATED PIPING, ATTACH CLAMPS AS INDICATED ABOVE, FOR VERTICAL INSULATED PIPING, ATTACH CLAMPS TO THE PIPE AND SEAL INSULATION AT BOTH CLAMP ENDS

SUPPORT WASHERS AND

LOCKNUTS (TYP.).

UNINSULATED STEEL OR

PLASTIC PIPE.

PROVIDE PLASTIC GALVANIC

ISOLATOR FOR COPPER PIPE

(TYP.)

UNINSULATED COPPER PIPE.

COLD INSULATED PIPE.

PIPE INSULATION (TYP.)

HOT INSULATED PIPE.

PROVIDE 1-5/8"x1-5/8" 14 GA.

CHANNEL SUPPORT.

CUT INSULATION TO FIT AROUND

TRAPEZE HANGER. SEAL BOTH ENDS OF

EXPOSED INSULATION WITH JOINT

SEALANT.

PROVIDE METAL 360° INSULATION SHIELD

AND HIGH DENSITY INSULATION OR PRE-

ENGINEERED THERMAL HANGER-SHIELD

INSERT OF CALCIUM SILICATE

INSULATION. FOR PIPES 4" AND SMALLER,

PRE-ENGINEERED THERMAL HANGER-

SHIELD INSERT OF FLEXIBLE

UNICELLULAR INSULATION MAY BE

PROVIDED.

SIZE AND QUANTITY OF HANGER RODS

PER MANUFACTURER'S

RECOMMENDATIONS.

PROVIDE TWO-PIECE PIPE

CLAMP (TYP.).

PROVIDE A METAL SUPPORT

PLATE WHEN DRAIN IS INSTALLED

IN AN EXISTING FLOOR - CAULK

AROUND DRAIN PRIOR TO RE-

GROUTING

NOTE:

1. SLOPE MEMBRANE LINER 2% TO DRAIN.

THREADED, CAULKED OR NO-HUB

CONNECTION

FLASHING CLAMP

WITH WEEP HOLES

STRUCTURAL SLAB

TILE FLOOR

CONCRETE FILL

NICKLE BRONZE

ADJUSTABLE

STRAINER (FLUSH

WITH FINISHED

FLOOR)

CEMENT BED

LOOSE GRAVEL AT

WEEP HOLES 3mm to 6mm SIZE

WATERPROOF

MEMBRANE

CLAMP WATERPROOF

MEMBRANE INSIDE OF DRAIN

BODY TO DRAIN TO WEEP

HOLES

FINISHED FLOOR

CHROME WALL COVER

AND SCREW

STANDARD 1/8 BEND

PLUGGED TEE WITH

CLEANOUT

NOTE:

1. LOCATE VTR MINIMUM 3'-0" FROM PROPERTY LINE, 10'-0" HORIZONTAL, OR 3'-0" VERTICAL ABOVE ANY BUILDING OPENING OR FRESH AIR INTAKE, 25'-0" FROM ANY OPENING OR FRESH AIR INTAKE IN MEDICAL FACILITIES AND 1'-0" FROM ANY VERTICAL SURFACE.

2. REFER TO LOCAL CODES FOR OTHER VENT TERMINATION REQUIREMENTS.

3. LOCATE VTR MINIMUM 18" FROM ADJACENT WALL, PARAPET, EXPANSION JOINT, ROOF DRAIN, EQUIPMENT CURB, OR OTHER ROOF FEATURE

4. OFFSET IN CEILING SPACE WHERE REQUIRED TO MEET THESE CONDITIONS.

5. INSULATE LAST 6'-0" OF VENT PIPE INSIDE BUILDING PER SPECIFICATIONS.

COORDINATE INSTALLATION OF

FLASHING AND COUNTERFLASHING

ROOF INSULATION

PROVIDE FIRE STOP SEAL

BETWEEN PIPE AND SLEEVE

OR DECK.

MINIMUM 12" BELOW ROOF

ROOF DECK

CORE DRILL ROOF OR

PROVIDE SLEEVE IF

REQUIRED BY TYPE OF

ROOF DECK.

MINIMUM 12" ABOVE ROOF. EXTEND TO

HEIGHT OF PARAPET WHEN WITHIN 10' OF

PARAPET, OR ABOVE MAXIMUM LOCAL

SNOW DEPTH, WHICHEVER IS HIGHER.

ANCHOR PIPE TO

STRUCTURE.

PROVIDE PIPE INCREASER ON

SMALLER VENT WHERE CODE

REQUIRED MINIMUM VTR IS 3"

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

CODY DOUGLAS

ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022

MECH - JAMES R. MYLES #027005 EXP. 12/31/2023

ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023

CIVIL ENGINEER

CALIBRE ENGINEERING

9090 S. RIDGELINE BLVD, SUITE 105

HIGHLANDS RANCH, CO 80129

(303) 730-0434

BEN MURPHY

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

2519 MADISON AVENUE, SUITE 100

KANSAS CITY, MO. 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

STRUCTURAL ENGINEER

DEGENKOLD ENGINEERS

375 BEALE STEET, SUITE 500

SAN FRANCISCO, CA 94105

(415) 354-6439

ROBERT GRAFF

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

FRANK FINLEY

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:5 :2

P

M

PLUMBING DETAILS

CMT 52JRM

LEVEL 1 SD2 RFP

CENTRAL UTILITY PLANT

02/28/2023

654-212

VA SIERRA NEVADA HEALTH CARE SYSTEM

975 KIRMAN AVE

RENO, NV 89502

P-503

SPUR #: 1791.06

NTS

TRAPEZE PIPE HANGER1

NTS

TYPE "C" FLOOR DRAIN DETAIL2

NTS

TYPICAL INTERIOR WALL CLEANOUT3

NTS

VENT THROUGH ROOF DETAIL4

55 95 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

CODY DOUGLAS

ARCH - SETH A. CAVIN #7580 EXP. 12/31/2022

MECH - JAMES R. MYLES #027005 EXP. 12/31/2023

ELEC - BENJAMIN E. NOE #027238 EXP. 12/31/2023

CIVIL ENGINEER

CALIBRE ENGINEERING

9090 S. RIDGELINE BLVD, SUITE 105

HIGHLANDS RANCH, CO 80129

(303) 730-0434

BEN MURPHY

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

2519 MADISON AVENUE, SUITE 100

KANSAS CITY, MO. 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

STRUCTURAL ENGINEER

DEGENKOLD ENGINEERS

375 BEALE STEET, SUITE 500

SAN FRANCISCO, CA 94105

(415) 354-6439

ROBERT GRAFF

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

FRANK FINLEY

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:5 :2

P

M

PLUMBING SCHEDULES

CMT 53JRM

LEVEL 1 SD2 RFP

CENTRAL UTILITY PLANT

02/28/2023

654-212

VA SIERRA NEVADA HEALTH CARE SYSTEM

975 KIRMAN AVE

RENO, NV 89502

P-601

SPUR #: 1791.06

PLUMBING FIXTURE SCHEDULE

MARK FIXTURE

BASIS OF DESIGN PIPING ROUGH-IN WASTE FIXTURE

UNITS

WATER FIXTURE

UNITS DESCRIPTIONMANUFACTURER MODEL WASTE (IN) VENT (IN) CW (IN) HW (IN)

P-103 Water Closet, Flush Valve, Public American Standard AFWALL Millenium Flowwise 4 2 1 1/4 - 12 20 Wall hung, manual flush valve, elongated bowl, wall outlet. Sloan Regal 111-1.28 XL. Bemis Commercial Model 1655SSCT open elongated heavy duty plastic.

P-414 Lavatory, Public American Standard Lucerne 2 1-1/2 1/2 1/2 4 4 Straight back, first quality vitreous china with punching for faucet. Set rim 864 mm (34 inches) above finished floor.

Faucet - Chicago #895-31. Provide thermostatic tempering valve.

P-502 Service Sink ACORN TNC24-TF2 0 0

P-512 Sturdibilt Triple Compartment Scullery Sinks, Drainboard both

Elkay Manufacturer Sturdibilt 0 0

P-528 Sink, CRS Elkay LRAD191965PD 2 1-1/2 1/2 1/2 2 2 Single compartment, counter top, self-rimming, 18 Gauge Stainless Steel.

P-701 SHOWER 0 0

P-707 Emergency Shower Eye & Face Wash Acorn Safety S2330-CS1 1 1/4 - 1 1/4 1 8 8 Provide with manufacturer emergency thermostatic mixing valve

P-804 Hose Bibb Prier Products C-158 - - 1/2 1/2 0 0 Cast or wrought copper alloy. Integral vacuum breaker.

P-812 Ice Maker/ Water Supply Box Guy Gray SSIB1 - - 1/2 - 0 0 Stainless Steel Ice Maker Box with quarter turn sweat valves.

P-815 Non-Freeze Roof Hydrant Mapa Products MPH-24FP - - 3/4 - 0 0 Cast aluminum weather resistant dome control handle, 304 stainless steel shroud, bronze globe angle valve, quick disconnect with built in vacuum breaker, stainless steel reservoir.

WATER HEATER SCHEDULE

MARK

BASIS OF DESIGN

LOCATION

RECOVERY (GPH AT 100°

RISE) CAPACITY (GAL) NATURAL GAS INPUT (BTU/HR) NOTESMANUFACTURER MODEL

16-WH-1

9256 95

File details come from the government source that posted it. Updated .