Design Drawings Structural_654-212.pdf
PDF 5 MB Posted
- Solicitation number
- QSE--36C10F24R50000
About this file
This document appears to be a set of structural design drawings and general notes for a new Central Utility Plant to be constructed at the VA Sierra Nevada Health Care System in Reno, Nevada under a design-build contract.
The key details are:
- The project scope includes demolishing the existing seismically deficient boiler plant, constructing a new 11,000 GSF Central Utility Plant to house boilers, chillers, cooling towers, and a bulk oxygen system, and converting the boiler plant site into a paved parking lot.
- The new Central Utility Plant will provide steam, heating, and cooling services for the entire VA campus. The contractor will be responsible for all design services, obtaining required professional engineering licenses, and performing construction activities under a Nevada contractor's license.
- The design must comply with the VA Technical Design Library. No deviations will be allowed without prior approval from the VA Contracting Officer.
- A geotechnical report is provided, but the contractor must complete their own geotechnical analysis as part of the design development.
The structural drawings and general notes provide technical details on the design of the new utility plant, including requirements for concrete, masonry, steel, metal decking, and mechanical anchors.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. DEPARTMENT OF VETERANS AFFAIRS
STRUCTURAL 30x42 DRAWINGS
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
VA PROJECT NUMBER: 654-212
[03] STRUCTURAL
22 S-001 GENERAL NOTES
23 S-002 SYMBOLS AND ABBREVIATIONS
24 SB111 FOUNDATION AND GROUND LEVEL PLAN
25 SF112 MEZZANINE AND ROOF LEVEL FRAMING PLAN
26 S-201 BUILDING ELEVATIONS
27 S-301 BUILDING SECTIONS
28 S-501 TYPICAL CONCRETE DETAILS
29 S-502 TYPICAL MASONRY DETAILS
30 S-503 TYPICAL MASONRY DETAILS
31 S-504 TYPICAL STEEL DETAILS
32 S-505 TYPICAL DECK DETAILS
CENTRAL UTILITY PLANT
GENERAL NOTES
I. GENERAL
1. MATERIALS AND WORKMANSHIP TO CONFORM WITH THE MAY 2020
EDITION VA SEISMIC DESIGN REQUIRMENTS DOCUMENT H-18-8, THE
2018 INTERNATIONAL BUILDING CODE WITH WASHOE COUNTY
AMENDMENTS, AND THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
2. THESE GENERAL NOTES SUPPLEMENT THE REQUIREMENTS OF THE
PROJECT SPECIFICATIONS. IN CASE OF CONFLICT BETWEEN THE PLANS
AND SPECIFICATIONS, CONTACT THE RESIDENT ENGINEER.
3. REFERENCE TO CODES, RULES, REGULATIONS, STANDARDS,
MANUFACTURER’S INSTRUCTIONS OR REQUIREMENTS OF REGULATORY
AGENCIES IS TO THE LATEST PRINTED EDITION OF EACH IN EFFECT AT THE
DATE OF SUBMISSION OF BID UNLESS THE DOCUMENT DATE IS SHOWN.
4. MATERIAL-SPECIFIC DESIGN IS PER THE FOLLOWING STRUCTURAL
STANDARDS, THE LATEST VERSIONS REFERENCED BY THE 2018 IBC:
CONCRETE:
• ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE
STEEL:
• AISC 360 SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS
• AISC 341 SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS
MASONRY:
• TMS 402 BUILDING CODE REQUIREMENTS AND SPECIFICATION FOR
MASONRY STRUCTURES
5. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION.
WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF
SIMILAR CHARACTER TO DETAILS SHOWN, USE SIMILAR DETAILS OF
CONSTRUCTION, SUBJECT TO REVIEW BY THE RESIDENT ENGINEER.
6. DETAILS ON SHEETS TITLED “TYPICAL DETAILS” APPLY TO SITUATIONS
OCCURRING ON THE PROJECT THAT ARE THE SAME OR SIMILAR TO THOSE
SPECIFICALLY REFERENCED. SUCH DETAILS ARE NOT NOTED AT EACH
LOCATION THAT THEY OCCUR.
7. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE WORK OF
ALL TRADES AND FOR CHECKING DIMENSIONS. NOTIFY THE RESIDENT
ENGINEER OF ANY DISCREPANCIES AND RESOLVE BEFORE PROCEEDING
WITH THE WORK.
8. DO NOT SCALE THE DRAWINGS.
9. PROVIDE MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING
CONSTRUCTION. SUCH MEASURES INCLUDE, BUT MAY NOT BE LIMITED TO,
BRACING AND SHORING FOR LOADS DURING CONSTRUCTION. RETAIN A
REGISTERED CIVIL ENGINEER WHOM IS PROPERLY QUALIFIED TO DESIGN
BRACING, SHORING, ETC. VISITS TO THE SITE BY THE OWNER’S
REPRESENTATIVE WILL NOT INCLUDE OBSERVATION OF THE ABOVE
NOTED ITEMS.
10. REFER TO ARCHITECTURAL DRAWINGS FOR SIZE AND LOCATION OF
FLOOR, ROOF AND WALL OPENINGS NOT SHOWN ON THE STRUCTURAL
DRAWINGS. COORDINATE THE SIZE AND LOCATION OF OPENINGS
ASSOCIATED WITH, BUT NOT LIMITED TO, ELECTRICAL, MECHANICAL AND
PLUMBING TRADES. SUBMIT FINAL SIZING AND LOCATION REQUIREMENTS
OF OPENINGS TO THE OWNER’S REPRESENTATIVE FOR REVIEW.
11. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR PROVIDING A SAFE
PLACE TO WORK AND MEETING THE REQUIREMENTS OF ALL APPLICABLE
JURISDICTIONS. EXECUTE WORK TO ENSURE THE SAFETY OF PERSONS
AND ADJACENT PROPERTY AGAINST DAMAGE BY FALLING DEBRIS AND
OTHER HAZARDS IN CONNECTION WITH THIS WORK.
II. FOUNDATION AND SITE WORK
1. THE DESIGN OF THE FOUNDATION SYSTEM IS BASED UPON THE CRITERIA
AND RECOMMENDATIONS CONTAINED IN THE GEOTECHNICAL
INVESTIGATION REPORT ENTITLED “GEOTECHNICAL INVESTIGATION
REPORT, IOANNIS LOUGARIS MEDICAL CENTER BOILER PLANT NO. 654-877”
BY TERRACON, DATED OCTOBER 12, 2022.
3. LOCATE AND PROTECT EXISTING UTILITIES TO REMAIN DURING AND/OR
AFTER CONSTRUCTION.
4. REMOVE ABANDONED FOOTINGS, UTILITIES, ETC. WHICH INTERFERE WITH
NEW CONSTRUCTION, UNLESS OTHERWISE INDICATED.
5. NOTIFY THE RESIDNET ENGINEER IF ANY BURIED STRUCTURES NOT
INDICATED, SUCH AS CESSPOOLS, CISTERNS, FOUNDATIONS, ETC., ARE
FOUND.
6. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR EXCAVATION
PROCEDURES INCLUDING LAGGING, SHORING, UNDERPINNING AND
PROTECTION OF EXISTING CONSTRUCTION.
7. REMOVE LOOSE SOIL AND STANDING WATER FROM FOUNDATION
EXCAVATIONS PRIOR TO PLACING CONCRETE.
8. EXCAVATIONS FOR FOUNDATIONS MUST BE ACCEPTED BY THE
GEOTECHNICAL ENGINEER PRIOR TO PLACING REINFORCING AND
CONCRETE. NOTIFY THE RESIDENT ENGINEER WHEN EXCAVATIONS
ARE READY FOR INSPECTION.
9. PLACE BACKFILL BEHIND RETAINING WALLS AFTER CONCRETE OR
MASONRY HAS ATTAINED FULL DESIGN STRENGTH. BRACE BUILDING AND
PIT WALLS BELOW GRADE FROM LATERAL LOADS UNTIL ATTACHED
FLOORS AND SLABS ON GRADE ARE COMPLETE AND HAVE ATTAINED
FULL DESIGN STRENGTH.
10. MECHANICALLY COMPACT EXCAVATION BACKFILLS IN ACCORDANCE WITH
THE GEOTECHNICAL REPORT.
III. FORMWORK
1. PROVIDE POUR POCKETS IN FORMS AND UNDER EXISTING STRUCTURAL
MEMBERS AS REQUIRED TO PREVENT AIR POCKETS AND/OR
“HONEYCOMB” UNDER OR AROUND THE EXISTING MEMBERS. CONCRETE
CAST WITH AIR POCKETS AND/OR “HONEYCOMB” UNDER OR AROUND THE
MEMBERS IS NOT ACCEPTABLE.
2. REMOVE FORMS AND SHORES IN ACCORDANCE WITH THE FOLLOWING:
LOCATION
UON BOTTOM FORMS AND
SHORES FOR MILDLY
REINFORCED SLABS, BEAMS
AND GIRDERS
WALLS
FOOTINGS, PILE CAPS, AND
GRADE BEAMS
REMOVE FORMS AND SHORES
NO SOONER THAN
7 DAYS, AND F’C = 3500 PSI
MINIMUM
72 HOURS
48 HOURS
3. PROVIDE CURING WHERE FORMS ARE REMOVED IN LESS THAN 7 DAYS,
INCLUDING BUT NOT LIMITED TO WALLS, COLUMNS, AND UNDERSIDE OF
ELEVATED SLABS.
IV. REINFORCING STEEL
1. REINFORCING TO CONFORM TO THE FOLLOWING, UNLESS OTHERWISE
NOTED:
LOCATION
REINFORCING STEEL #7 AND SMALLER
REINFORCING STEEL #8 AND LARGER AND
REINFORCING STEEL TO BE WELDED
WELDED STEEL WIRE FABRIC
TYPE
ASTM A615, 60 KSI
ASTM A706, 60 KSI
ASTM A185, 70 KSI
2. ACCURATELY POSITION, SUPPORT, AND SECURE REINFORCEMENT FROM
DISPLACING DUE TO FORMWORK, CONSTRUCTION, OR CONCRETE
PLACEMENT OPERATIONS. LOCATE AND SUPPORT REINFORCING BY
METAL CHAIRS, RUNNERS, BOLSTERS, SPACERS, AND HANGERS AT A
MAXIMUM 3-FOOT SPACING.
3. MECHANICALCOUPLERS: LENTON THREADED OR INTERLOCK COUPLERS
BY ERICO, ICBO #3967, CADWELD BY ERICO, ICBO #3967, OR XTENDER BY
HEADED REINFORCEMENT CORPORATION, ICBO #5309. COUPLERS FOR
BEAM AND SLAB BARS AT FORMED CONSTRUCTION JOINTS MAY BE
LENTON FORM SAVERS BY ERICO, ICBO #3967. CONTRACTOR TO SUBMIT
LOCATIONS WHERE COUPLERS ARE PROPOSED EXCEPT WHERE
SPECIFICALLY DETAILED BY THE DRAWINGS.
4. WELD REINFORCING STEEL IN ACCORDANCE WITH AWS D1.4 USING
QUALIFIED WELDERS.
5. TERMINATE REINFORCING STEEL IN STANDARD HOOKS, UNLESS
OTHERWISE SHOWN.
6. PROVIDE REINFORCING SHOWN OR NOTED CONTINUOUS IN LENGTHS AS
LONG AS PRACTICABLE.
V. CAST-IN-PLACE CONCRETE
1. CONCRETE IS REINFORCED AND CAST-IN-PLACE UNLESS OTHERWISE
NOTED. WHERE REINFORCING IS NOT SPECIFICALLY SHOWN OR WHERE
DETAILS ARE NOT GIVEN, PROVIDE REINFORCING SIMILAR TO THAT SHOWN
FOR SIMILAR CONDITIONS, SUBJECT TO REVIEW BY THE OWNER’S
REPRESENTATIVE.
2. ROUGHEN CONCRETE SURFACES OF CONSTRUCTION JOINTS TO 1/4 INCH
AMPLITUDE AND CLEAN OF LAITANCE, FOREIGN MATTER, AND LOOSE
PARTICLES. LOCATE CONSTRUCTION JOINTS AS SHOWN ON THE
DRAWINGS. SUBMIT ALTERNATE JOINT LOCATIONS OR JOINTS NOT SHOWN
TO THE OWNER’S REPRESENTATIVE FOR REVIEW AND APPROVAL PRIOR TO
PROCEEDING WITH THE WORK.
3. AT LOCATIONS WHERE CONCRETE IS CAST AGAINST EXISTING CONCRETE,
ROUGHEN CONTACT SURFACES TO ¼ INCH AMPLITUDE AND CLEAN OF
LAITANCE, FOREIGN MATTER, AND LOOSE PARTICLES.
4. AT LOCATIONS WHERE CONCRETE IS CAST AGAINST EXISTING MASONRY,
THOROUGHLY ROUGHEN CONTACT SURFACES BY LIGHT SANDBLASTING OR
OTHER SUITABLE MEANS AND CLEAN OF LAITANCE, FOREIGN MATTER, AND
LOOSE PARTICLES.
5. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR LOCATIONS
OF ADDITIONAL CONCRETE CURBS AND HOUSEKEEPING PADS NOT SHOWN.
6. CONCRETE CLEAR COVER TO REINFORCING BARS IS AS FOLLOWS, UNLESS
OTHERWISE NOTED:
LOCATION
CONCRETE PLACED AGAINST EARTH
FORMED SURFACES EXPOSED TO
WEATHER OR IN CONTACT WITH EARTH:
#6 BARS AND LARGER
#5 BARS AND SMALLER
SLABS ON GRADE (TOP CLEARANCE)
BEAMS, GIRDERS AND COLUMNS NOT
EXPOSED TO WEATHER OR EARTH
WALL OR SLAB SURFACES NOT EXPOSED
TO WEATHER OR EARTH:
#5 & SMALLER
#6 & #7 #8,#9, #10 & #11 #14 & #18
CLEAR COVER
3 INCHES
2 INCHES
1 ½ INCHES
1 ½ INCHES
1 ½ INCHES
¾ INCH
1 INCH
1 ½ INCHES
2 ½ INCHES
7. CONCRETE TYPES:
CLASS
A
B
C
D
28-DAY
STRENGTH
4000 PSI
4000 PSI
4000 PSI
4000 PSI
TYPE
NORMAL
WEIGHT
NORMAL
WEIGHT
NORMAL
WEIGHT
NORMAL
WEIGHT
LOCATION
FOUNDATIONS, MISC. CURBS,
HOUSE –KEEPING PADS, ETC.
SLABS ON GRADE
WALLS AND COLUMNS
FILL ON METAL DECK
8. CONCRETE FILL THICKNESS SHOWN ON THE FRAMING PLANS ARE MINIMAL
THICKNESSES. NO ALLOWANCES HAVE BEEN SHOWN FOR ADDITIONAL
CONCRETE FILL REQUIRED TO COMPENSATE FOR FRAME, DECK, OR
FORMWORK DEFLECTIONS TO MAINTAIN SURFACE TOLERANCES
SPECIFIED.
9. NON-SHRINK GROUT, 7000 PSI: MIN AT FLOWABLE MIXING
RECOMMENDATIONS. MUST MEET 7000 PSI MIN.
VI. UNIT MASONRY
1. MINIMUM COMPRESSIVE STRENGTH OF MASONRY, F’M, EQUAL TO 1500 PSI
AT 28 DAYS.
2. MASONRY UNITS: ASTM C-90, GRADE N, TYPE 1, MEDIUM WEIGHT, HOLLOW,
LOAD BEARING UNITS. MINIMUM COMPRESSIVE STRENGTH: 1900 PSI.
3. MORTAR: ASTM C-270, TYPE S.
4. GROUT: ASTM C-476, MINIMUM COMPRESSIVE STRENGTH: 2000 PSI.
5. REINFORCING STEEL:
LOCATION
REINFORCING TO BE WELDED
ALL OTHER REINFORCING
JOINT REINFORCING
TYPE
ASTM A706, GRADE 60
ASTM A615, GRADE 60
UBC STD 21-10
6. CENTER VERTICAL REINFORCING IN WALL UNLESS NOTED OTHERWISE.
7. LAY UNITS IN RUNNING BOND AND MAINTAIN VERTICAL CONTINUITY OF
CORES OR CELL CAVITIES. USE OPEN END UNITS AT LOCATIONS OF
VERTICAL REINFORCING. PLACE HORIZONTAL REINFORCING IN BOND
BEAM UNITS.
8. FILL ALL CELLS SOLIDLY WITH GROUT. CLEAN CELLS AND BOND BEAMS
OF MORTAR PROTRUSIONS AND DEBRIS BEFORE GROUTING.
9. DOWELS FROM THE FOUNDATION TO MATCH SIZE AND LOCATION OF
VERTICAL REINFORCING IN MASONRY, UNLESS NOTED OTHERWISE.
10. PROVIDE VERTICAL CONTROL JOINTS IN THE WALLS AT LOCATIONS
SHOWN ON THE DRAWINGS.
11. LOW-LIFT GROUTING: LAY UNITS A MAXIMUM OF 2 FEET HIGH BEFORE
GROUTING. PLACE GROUT IN A CONTINUOUS PLACEMENT IN GROUT LIFTS
NOT EXCEEDING 2 FEET. COMPLETELY GROUT THE FULL HEIGHT OF THE
WALL SECTION IN ONE DAY WITH NO INTERRUPTIONS GREATER THAN ONE
HOUR.
12. HIGH-LIFT GROUTING: LAY UNITS A MAXIMUM OF 12 FEET HIGH BEFORE
GROUTING. PLACE GROUT IN A CONTINUOUS PLACEMENT IN GROUT LIFTS
NOT EXCEEDING 6 FEET. COMPLETELY GROUT THE FULL HEIGHT OF THE
WALL SECTION IN ONE DAY WITH NO INTERRUPTIONS GREATER THAN ONE
HOUR. PROVIDE CLEANOUTS AT EVERY CELL ALONG THE BOTTOM
COURSE OF EACH GROUT LIFT. USE SIKA GROUT AID TYPE II OR E-Z MIX
ADMIXTURE IN THE GROUT TO REDUCE EARLY WATER LOSS AND PRODUCE
AN EXPANSIVE ACTION.
VII. STRUCTURAL STEEL
1. STRUCTURAL STEEL TO CONFORM TO THE FOLLOWING UNLESS
OTHERWISE NOTED:
SECTIONS
ROLLED SHAPES
WIDE FLANGES
CHANNELS, ANGLES, & OTHER
PLATES
COLUMN BASE PLATES
BRACE GUSSET PLATES
BEAM SHEAR CONNECTION PLATES
COLUMN CONTINUITY PLATES
BEAM STIFFENER PLATES
DECK CLOSURE PLATES
OTHER
STEEL PIPE
COLD FORMED HOLLOW STRUCTURAL
SECTION (HSS)
STAINLESS STEEL SHAPES, PLATES
AND BARS
BOLTS
MACHINE BOLTS
ANCHOR RODS & BOLTS
THREADED AND HANGER ROD
WELDED SHEAR CONNECTORS
WELDED THREADED STUDS
NUTS FOR BOLTS AND MACHINE BOLTS
HARDENED WASHERS
UNHARDENDED WASHERS
PLAIN WASHERS
BEVELED WASHERS
TYPE UON
ASTM A992
ASTM A36
ASTM A572, GR 50
ASTM A572, GR 50
ASTM A36
ASTM A572, GR 50
ASTM A36
ASTM A36
ASTM A572, GR 50
ASTM A53 GRADE B
ASTM A500 GRADE B
ASTM A276
ASTM A325X
ASTM A307
ASTM F1554-GR105
ASTM A572, GR50
ASTM A 108, GRADE
1015 THROUGH 1020
ASTM A 108, GRADE
1015 THROUGH 1020
ASTM A563
ASTM F436
ASTM F844
ANSI B18.22.1
ANSI B18.23.1
2. HOT DIP GALVANIZE IN ACCORDANCE WITH ASTM A123 AND ASTM A153
STRUCTURAL STEEL AND FASTENERS THAT ARE PERMANENTLY EXPOSED
TO THE WEATHER. REPAIR GALVANIZING AFTER WELDING IN ACCORDANCE
WITH ASTM A780.
3. STRUCTURAL STEEL AND CONNECTIONS EXPOSED TO VIEW IN THE
COMPLETED BUILDING ARE DESIGNATED ARCHITECTUALLY EXPOSED
STRUCTURAL STEEL (AESS) IN THE DRAWINGS. AESS TO MEET THE
REQUIREMENTS OF AISC 303-16 AND THE DESIGNATION GIVEN IN THE
DRAWINGS.
4. ARC-WELDING ELECTRODES/FILLER METALS TO BE LOW HYDROGEN
TYPES E7XTX, E7XTXX OR E70XXX MINIMUM AS APPLICABLE.
5. WELDERS TO BE CERTIFIED BY AWS AND THE GOVERNING JURISDICTION.
6. WHERE FIELD WELDING IS NOTED, THE DESIGNATION IS GIVEN AS A
SUGGESTED CONSTRUCTION PROCEDURE ONLY.
7. PROVIDE NATURAL CAMBER UP, UNLESS NOTED OTHERWISE, EXCEPT AT
CANTILEVERS. AT CANTILEVERS PROVIDE CAMBER SUCH THAT TIP OF
CANTILEVER IS ABOVE FINAL ELEVATION.
8. SPLICE MEMBERS ONLY WHERE INDICATED.
VIII. METAL DECKING
1. METAL FLOOR AND ROOF DECK TO HAVE MINIMUM SECTION PROPERTIES
SHOWN ON SHEET “TYPICAL DECK DETAILS.”
2. ALL FLOOR AND ROOF DECK TO BE GALVANIZED IN ACCORDANCE WITH
ASTM A653 COATING CLASS G60. REPAIR DAMAGED COATING.
3. WHERE POSSIBLE, LAYOUT METAL DECK TO SPAN AT LEAST THREE SPANS
CONTINUOUSLY. TERMINATE ENDS OVER SUPPORTS EXCEPT AT OPENINGS
OR BUILDING EDGES WHERE METAL DECKS MAY BE CANTILEVERED AS
SHOWN.
XI. STRUCTURAL TESTS, INSPECTIONS, AND OBSERVATIONS
1. AN INDEPENDENT TESTING AGENCY AND SPECIAL INSPECTORS WILL BE RETAINED BY
THE CONTRACTOR TO PERFORM THE FOLLOWING TESTS AND INSPECTION. PROVIDE
ACCESS AND FURNISH SAMPLES TO THE AGENCY AS REQUIRED BY THE CONTRACT
DOCUMENTS.
2. IF INITIAL TESTS OR INSPECTIONS MADE BY THE TESTING AGENCY REVEAL THAT ANY
PORTION OF THE WORK DOES NOT COMPLY WITH THE CONTRACT DOCUMENTS,
ADDITIONAL TESTS, INSPECTIONS, AND NECESSARY REPAIRS WILL BE MADE AT THE
CONTRACTOR’S EXPENSE.
3. THE FOLLOWING ITEMS REQUIRE TESTS AND INSPECTIONS IN ACCORDANCE WITH THE
REQUIREMENTS OF THE CHAPTER “STRUCTURAL TESTS AND INSPECTIONS” OF THE CODE
OF THE GOVERNING JURISDICTION AS NOTED IN THE GENERAL SECTION OF THESE
GENERAL NOTES. ADDITIONAL ITEMS AND REQUIREMENTS FOR TESTS AND INSPECTIONS
ARE IDENTIFIED IN THE SPECIFICATIONS.
4. NOTIFY THE ENGINEER AT SIGNIFICANT CONSTRUCTION STAGES 72 HOURS
IN ADVANCE AND PROVIDE ACCESS FOR THE FOLLOWING STRUCTURAL
OBSERVATIONS:
A. FOUNDATIONS
1. REINFORCEMENT
B. STEEL FRAMING
1. GENERAL
2. METAL DECKING AND SHEAR CONNECTORS
C. CONCRETE
1. SLABS AND SLABS-ON-GRADE
2. SLAB ON DECK REINFORCING
D. MASONRY
1. ALL REINFORCEMENT AND BOUNDARY ELEMENTS
XII. DESIGN CRITERIA
1. APPLICABLE CODE: VA MAY 2020 H-18-8 SEISMIC DESIGN REQUIREMENTS
2018 INTERNATIONAL BUILDING CODE
2. FOUNDATIONS HAVE BEEN DESIGNED WITH THE FOLLOWING CRITERIA:
SPREAD AND CONTINIOUS FOOTINGS
ALLOWABLE NET SOIL PRESSURE FOR DL + LL = 3000* PSF
ALLOWABLE NET SOIL PRESSURE FOR DL + LL + EQ = 4000* PSF
PASSIVE PRESSURE = 350 PCF
FRICTION = 35%
MODULUS OF SUBGRADE REACTION, k = 200 PCI
3. NEW SOIL RETAINING STRUCTURES HAVE BEEN DESIGNED WITH THE
FOLLOWING CRITERIA:
ACTIVE EQUIVALENT FLUID PRESSURES = 40 PCF
AT-REST EQUIVALENT FLUID PRESSURE = 55 PCF
EARTHQUAKE LATERAL PRESSURE (UNIFORM DISTRIBUTION) = 11XH^2 PLF
APPLIED AT 0.33H FROM THE BASE OF THE WALL.
4. GRAVITY LOADS:
A. DEAD LOADS - VARY BASED ON ACTUAL BUILDING AND EQUIPMENT
OPERATING WEIGHTS. APPROXIMATE OPERATING WEIGHTS ARE AS
FOLLOWS, BUT ARE SUBJECT TO CHANGE:
• FLX WATERTUBE BOILERS - 40,000 LBS EA
• DEAERATOR - 17,500 LBS
• CHILLERS - 8,600 LBS EA
• FRAME-MOUNTED SUCTION PUMPS - 1,500 LBS EA
• COOLING TOWER - 83,000 LBS
B. LIVE LOADS:
ROOF 20 PSF + 30 PSF MIN EQUP
FLOOR 150 PSF
CATWALKS 40 PSF
C. DEFLECTIONS
LL = L/360
DL + LL = L/240
5. SEISMIC DESIGN:
METHOD PER ASCE 7-16 TABLE 12.6-1: MODAL RESPONSE SPECTRUM
ANALYSIS PROCEDURE
SITE SEISMISITY
SS = 1.652
S1 = 0.585
TL = 6
SITE CLASS C
SDS = 1.322
SD1 = 0.552
CUP: R = 5.5 FOR SPECIAL CMU SHEAR WALLS
CD = 4.0
OMEGA = 2.5
I = 1.5 FOR OCCUPANCY CATEGORY IV (CRITICAL)
DRIFT LIMIT = 0.5% x STORY HEIGHT
SEISMIC DESIGN CATEGORY = D
BASE SHEAR V = 0.397 W FOR NORTH-SOUTH DIR.
V = 0.397 W FOR EAST-WEST DIR.
6. NON-STRUCTURALANCHORAGE: ITEMS SUCH AS EQUIPMENT, UTILITIES,
AND ARCHITECTURAL COMPONENTS ARE TO BE ANCHORED AND
SUPPORTED FOR SEISMIC FORCES PER ASCE 7-10 AND VA H 18-8. IT IS
THE CONTRACTOR’S RESPONSIBILITY TO HIRE A PROFESIONAL ENGINEER
TO DESIGN THE ANCHORAGE OF THESE ITEMS. SEE SPEC 130541.
ANCHORAGE DESIGN AND INSTALLATION FOR CONTRACTOR SUPPLIED
/ CONTRACTOR INSTALLEDAND VA FURNISHED / CONTRACTOR INSTALLED
EQUIPMENT ARE THE RESPONSIBILITY OF THE CONTRACTOR.
7. THE DESIGN IS BASED UPON THE CRITERIA AND RECOMMENDATIONS
CONTAINED IN THE REPORT ENTITLED "INITIAL BLAST PROTECTION DESIGN
GUIDANCE, PROJECT 654-212" BY FORCE PROTECT SECURITY
CONSULTANTS, DATED JULY 6, 2022.
8. THE STRUCTURE IS DESIGNED TO THE VA PHYSICAL SECURITY AND
RESILIENCY DESIGN MANUAL (PSRDM) 2020, JULY 2022 REVISION.
9. DO NOT HANG UTILITIES, EQUIPMENT, ETC ECCENTRICALLY FROM BEAMS
OR BRACE TO THE LOWER 2/3 OF THE BEAM DEPTH.
10. WIND DESIGN:
RISK CATEGORY: IV CUP
EXPOSURE CATEGORY: C
BASIC WIND SPEED: 135 MPH, PER SPECIAL WIND REGION DEFINED
BY WASHOE COUNTY AMENDMENTS TO THE
INTERNATIONAL BUILDING CODE
VELOCITY PRESSURE EXPOSURE COEFFICIENT, Kz = 1.0 TOPOGRAPHIC FACTOR, Kzt = 1.0 WIND DIRECTIONALITY FACTOR, Kd = 0.85 GROUND ELEVATION FACTOR, Ke = 1.0, PER WASHOE COUNTY
AMENDMENTS TO THE INTERNATIONAL
BUILDING CODE
VELOCITY PRESSURE, qz = 39.7psf
GUST-EFFECT FACTOR, G = 0.85
ENCLOSURE CLASSIFICATION: ENCLOSED
INTERNAL PRESSURE, GCpi = ±0.18
COMPONENTS AND CLADDING LOADS: DETERMINE FROM ASCE 7-16
CHAPTER 30, PART 1: LOW RISE BUILDINGS
WALLS: FIGURE 30.3-1
FLAT ROOF: FIGURE 30.3-2A
11. DRAWINGS INDICATE GENERAL LAYOUT AND POSSIBLE DESIGN
SOLUTIONS. THE FINAL DESIGN IS THE RESPONSIBLITY OF THE DESIGN
BUILD CONTRACTOR AND THEIR DESIGN PROFESIONALS.
12. DESIGN TEAM
ROBERT GRAFF PROJECT MANAGER
PETER FOBEL PROJECT ENGINEER
MUSTAFA AMIN PROJECT CAD SPECIALIST
IX. MECHANICAL ANCHORS
1. EXPANSION OR WEDGE ANCHORS INTO CONCRETE: HILTI KB-TZ2 (ICC-ESR-4266),
SIMPSON STRONG-BOLT 2 (ICC-ESR-3037) OR DEWALT POWER-STUD+ SD2 (ICC-
ESR-2502), UNLESS SPECIFICALLY NOTED OTHERWISE.
2. HEAVY DUTY SLEEVE ANCHORS INTO CONCRETE: HILTI HSL-3 ANCHORS (ICC-ESR-1545)
OR DEWALT POWER-BOLT+ (ICC-ESR-3260)
3. UNDERCUT ANCHORS: HILTI HDA (ICC-ESR-1546)[, SIMPSON STRONG-TIE TORQ-CUT (ICC-
ESR-2705); DEWALT/POWERS ATOMIC+ UNDERCUT (ICC-ESR-3067).]
4. SCREW ANCHORS: HILTI HUS-EZ (ICC-ESR-3027), SIMPSON STRONG-TIE TITEN-HD (ICC-
ESR-2713), OR DEWALT SCREW-BOLT + (ICC-ESR-3889)
5. ANCHORS INTO CMU: [HILTI KB-3 (ICC-ESR-1385); HILTI KB-TZ (ICC-ESR-3785)]
[SIMPSON STRONG-TIE WEDGE-ALL (ICC-ESR-1396); SIMPSON STRONG-TIE TITEN-HD
(ICC-ESR-1056)], OR DEWALT POWER STUD+ SD1 (ICC-ESR-9266).
6. ALL EMBEDMENT DEPTHS NOTED ON DRAWINGS ARE EFFECTIVE EMBEDMENT PER
MANUFACTURER.
7. INSTALL ANCHORS IN ACCORDANCE WITH LATEST ICC-ESR REPORT AND
MANUFACTURER INSTRUCTIONS.
8. PROVIDE STAINLESS STEEL FASTENERS FOR EXTERIOR USE OR WHEN EXPOSED TO
WEATHER. PROVIDE GALVANIZED CARBON STEEL ANCHORS AT OTHER LOCATIONS,
UNLESS OTHERWISE NOTED.
9. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE
HOLE LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR
DIAMETERS OR 1 INCH, WHICHEVER IS LARGER, OF SOUND CONCRETE BETWEEN THE
ANCHOR AND THE ABANDONED HOLE. FILL THE ABANDONED HOLE WITH NON-SHRINK
GROUT. IF THE ANCHOR MAY NOT BE SHIFTED AS NOTED ABOVE, THE ENGINEER WILL
DETERMINE A NEW LOCATION.
10. LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO
FABRICATING PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES ATTACHED WITH
MECHANICAL ANCHORS.
11. ALL ANCHORS REQUIRE SPECIAL INSPECTION BY OWNER’S TESTING AND INSPECTION
AGENCY IN ACCORDANCE WITH THE ICC REPORTS AND THE CODE.
12. WEDGE, SLEEVE AND UNDERCUT ANCHORS REQUIRE PROOF TESTING. TEST 25% OF
ANCHORS TO THE MANUFACTURER’S RECOMMENDED INSTALLATION TORQUE OR
RECOMMENDED TORQUE IN ICC-ESR REPORT.
5. ANCHORS AND DOWELS INSTALLED INTO UNREINFORCED BRICK MASONRY (URM): HILTI-
HY 270 (ICC-ESR-4144), SIMPSON STRONG-TIE SET (ICC-ESR-1772), OR DEWALT AC100+
GOLD (ICC-ESR-4105). USE SCREENS AS SPECIFIED BY THE MANUFACTURER.
6. THE TESTING LABORATORY IS TO PERFORM TENSION TESTS ON 25% OF ANCHORS AND
DOWELS TO THE FOLLOWING TEST LOADS:
ROD DIA OR BAR SIZE EMBEDMENT TEST LOAD BASE MATERIAL
5/8” 12” 3000 # URM
3/4” 12” 3000 # URM
7. ANCHORS: ASTM A36 THREADED RODS WITH ASTM A563 GRADE A NUTS AND ANSI
B18.22.1 TYPE A WASHERS, UNLESS OTHERWISE NOTED. ANCHORS DESIGNATED AS
ASTM A193 GRADE B7 THREADED RODS TO USE ASTM A563 GRADE DH HEAVY HEX NUTS
AND ASTM F436 WASHERS.
8. REBAR DOWELS: ASTM A615 GRADE 60 REINFORCING STEEL.
9. INSTALL ANCHORS IN ACCORDANCE WITH LATEST ICC-ESR REPORT AND
MANUFACTURER INSTRUCTIONS.
10. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE
HOLE LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR
DIAMETERS OR 1 INCH, WHICHEVER IS LARGER, OF SOUND CONCRETE BETWEEN THE
DOWEL AND THE ABANDONED HOLE. FILL THE ABANDONED HOLE WITH NON-SHRINK
GROUT. IF THE ANCHOR OR DOWEL MAY NOT BE SHIFTED AS NOTED ABOVE, THE
ENGINEER WILL DETERMINE A NEW LOCATION.
11. LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO
FABRICATING PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES ATTACHED WITH
ADHESIVE ANCHORS.
ROD DIA
OR BAR
SIZE
CMIN
TEST LOAD (LBS)
ANCHOR
LOCATED > CMIN &
< 12" FROM EDGE
ANCHOR
LOCATED ≥ 12”
FROM EDGE
3/8", #3
1/2", #4
5/8", #5
3/4", #6
7/8", #7
1", #8
2"
2 1/2"
3"
4"
4 1/2"
5"
1,300
2,000
2,800
3,700
3,700
4,800
1,600
3,400
4,200
5,000
5,000
6,100
X. ADHESIVE ANCHORS AND DOWELS
1. ANCHORS AND DOWELS INSTALLED INTO CONCRETE: HILTI HIT-RE-500-V3 (ICC-
ESR-3814), SIMPSON STRONG-TIE SET-3G (ICC-ESR-4057) OR DEWALT PURE 110+ (ICC-
ESR-3298). ALL EMBEDMENT DEPTHS NOTED ON DRAWINGS ARE EFFECTIVE
EMBEDMENT PER MANUFACTURER.
2. ANCHORS AND DOWELS INSTALLED INTO CONCRETE MASONRY UNITS (CMU):
HILTI HIT-HY 270 (ICC-ESR-4143), SIMPSON STRONG-TIE SET-XP (IAPMO UES ER-265) OR
DEWALT AC100+ GOLD (ICC-ESR-3200).
3. ALL ANCHORS REQUIRE SPECIAL INSPECTION BY THE OWNER'S TESTING AND
INSPECTION AGENCY IN ACCORDANCE WITH THE ICC-ESR REPORTS AND THE CODE.
4. THE TESTING LABORATORY IS TO PERFORM TENSION TESTS ON 25% OF ANCHORS AND
DOWELS INSTALLED INTO CONCRETE TO THE FOLLOWING TEST LOADS:
STRUCTURAL STEEL
REVIEW MILL CERTIFICATE & TEST REPORTS�
REVIEW WELDING PROCEDURE SPECIFICATION & WELDER CERTIFICATION
SAMPLE & TEST SECTIONS AS SPECIFIED AS REQUIRED
SAMPLE & TEST HIGH-STRENGTH BOLTS & WASHERS
SHOP MATERIAL IDENTIFICATION
FIELD ERECTION INSPECTION
FABRICATION INSPECTION
WELDING INSPECTION
NON-DESTRUCTIVE WELD TEST
BOLTING INSPECTION
COMPOSITE STUD INSPECTION & TESTING
METAL DECK
REVIEW MILL CERTIFICATE & TEST REPORTS
PLACEMENT INSPECTION
WELDING & FASTENING INSPECTION
REINFORCING STEEL
REVIEW MILL CERTIFICATE & TEST REPORTS
SHOP FIELD
SHOP FIELD
SHOP FIELD
SHOP FIELD
SAMPLE & TEST REINFORCING BARS WELDED WIRE FABRIC
PLACEMENT INSPECTION
WELDING INSPECTION
MASONRY
REVIEW MILL CERTIFICATE & TEST REPORTS
SAMPLE & TEST
PLACEMENT INSPECTIONS OF UNITS
CORE TEST
EARTHWORK/FOUNDATION
ACCEPTANCE TESTS OF MATERIALS
REVIEW OF IMPORT MATERIAL TEST REPORTS
PLACEMENT & EXCAVATION INSPECTION CONTINUOUS AS ORDERED
COMPACTION TEST
BEARING CAPACITY TEST
PIER & CAISSON DRILLING INSPECTION
MISCELLANEOUS
DRILLED-IN CONCRETE ANCHORS
EPOXY OR GROUTED DOWELS
BOLTS CAST IN CONCRETE
CONCRETE, SHOTCRETE, GROUT & MORTAR
CONCRETE SHOTCRETE
AGGREGATE TESTS
CEMENT TEST
MIX DESIGN REVIEW
CONTINUOUS BATCH PLANT INSPECTION
BATCH PLANT INSPECTIONS
CAST, PICK-UP, AND COMPRESSION TEST SAMPLES
SHRINKAGE TEST (SLAB ON GRADE)
PLACEMENT INSPECTION
CORE & TEST
SLUMP, ENTRAINED AIR, & TEMPERATURE TEST
CEILING HANGER & BRACING WIRES�
COLD FORM METAL FRAMING WELDING�
GROUT MORTAR
UNIT WEIGHT TEST WET DRY�
FOR OFFICIAL USE ONLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:0 :4
P
M
GENERAL NOTES
PF 19 88RG
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLAN
4/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
S-001
No. REVISION DESCRIPTION DATE
REFERENCE SYMBOLS
DETAIL/SECTION
SECTION NUMBER
LINE OF SECTION CUT
DIRECTION OF VIEW
S3.1
DETAIL
DETAIL PLAN OR ELEVATION
SINGLE ELEVATION
GRID LINES
LEVEL LINE
WORK POINT
REVISION
CENTER POINT OF CURVE
REFERENCED ELEVATION
METAL DECK & FILL
PLAN SYMBOLS
CONCRETE FILL
FLOOR DEPRESSIONS
SHEAR CONNECTIONS
COLUMNS
SLAB OPENING
BRACED FRAME OR DIAGONAL BRACE
BAR COUPLERS
DRAWING SHEET NUMBER,
HYPHEN INDICATES SAME
SHEET
S5.2
DETAIL NUMBER
DRAWING SHEET NUMBER,
HYPHEN INDICATES SAME
SHEET
LINE OF SECTION CUT
DIRECTION OF VIEW
S6.3 AREA OF DETAIL
S5.1
AREA OF ENLARGED
PLAN OR ENLARGED
ELEVATION
DIRECTION OF VIEW
ELEVATION NUMBER
A
INDICATES HEIGHT ABOVE
DATUM
WP
WORK POINT OF CONNECTION,
POINT WHERE FORCES ARE
RESOLVED
REVISION NUMBER-
SEE REVISION HISTORY ON
TITLE BLOCK OF EACH SHEET
CURVE TO BE LOCATED
RADIUS OF CURVE
CENTER POINT OF CURVE
TOW
EL 98'-0"
DESCRIPTION OF REFERENCED
POINT
ELEVATION OF POINT
ABOVE DATUM
SINGLE ARROW INDICATES
EDGE OF DECK
EXTENT TO EDGE OF SLAB OR WALL, TYP.
SLAB TYPE, SEE SHEET NOTES FOR
DETAIL REFERENCE
ORIENTATION OF METAL
DECK
CONCRETE FILL
CONCRETE SLAB OR WALL
EXTENT TO EDGE OF SLAB
OR WALL, TYP.
SINGLE ARROW INDICATES
EDGE OF CONCRETE
DEPTH OF DEPRESSION OR
STEP IN SLAB
EXTENT OF DEPRESSION IN
SLAB. S.A.D. FOR DIMENSIONS
TYPICAL SHEAR CONNECTION
WIDE-FLANGE COLUMN, SEE
COLUMN SCHEDULE
TUBE COLUMN, SEE COLUMN
SCHEDULE
LIMITS OF SLAB OPENING
BRACE ABOVE
MECHANICAL COUPLER SPLICE
REINF. BARS
BEAM DESIGNATIONS
W16X31 [22]
(-4 1/2") <3/4">
BEAM SIZE
INDICATES NO. SHEAR STUDS
TOP OF STEEL RELATIVE
TO REFERENCE ELEVATION
INDICATES BEAM CAMBER
KEY NOTE
SEE LIST OF NOTES ON
EACH SHEET
MATERIAL SYMBOLS
CONCRETE (NEW)
CONCRETE (EXISTING)
EARTH, UNDISTURBED
ROCK FILL OR GRAVEL
EARTH, COMPACTED
GROUT OR SAND
S3.1
DRAWING SHEET NUMBER,
HYPHEN INDICATES SAME
SHEET
S#
MOMENT CONNECTIONS
MOMENT RESISTING BEAM-COLUMN
CONNECTION SEE DETAILS
BEAM-BEAM MOMENT CONNECTION
BEAM TO BEAM MOMENT
CONNECTION PER DETAILS
BEAM PENETRATIONS
TYPE A-1
10"x18" (-8")
VERT x HORIZ WEB OPENING
CENTERLINE OF OPENING TO TOP OF
STEEL
WEB OPENING TYPE, SEE
DETAILS
BRACE BELOW
X'-X"
STEEL
MASONRY (BRICK / CMU)
CONCRETE, ELEVATED OR
DEPRESSED
DEMO
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:0 :4
P
M
SYMBOLS AND ABBREVIATIONS
PF 20 88RG
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLAN
4/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
S-002
(E) EXISTING
# NUMBER
& AND
@ AT
Ø DIAMETER OR ROUND
ℓd DEVELOPMENT LENGTH ℓdh HOOK DEVELOPMENT LENGTH ℓs LAP SPLICE LENGTH
AA ADHESIVE ANCHOR
AB ANCHOR BOLT
ABV ABOVE
AC ASPHALT CONCRETE
ADDL ADDITIONAL
ADJ ADJACENT
AGGR AGGREGATE
ALT ALTERNATE
ALUM ALUMINUM
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL / ARCHITECT
ASPH ASPHALT
ASTM AMERICAN SOCIETY for TESTING and MATERIALS
AWG AMERICAN WIRE GAUGE
B. O. BOTTOM OF
BF BOTH FACES
BF BRACED FRAME
BLDG BUILDING
BLK, BLKG BLOCK OR BLOCKING
BLW BELOW
BM, BMS BEAM, BEAMS
BN BOUNDARY NAILING
BOF BOTTOM OF FOOTING
BOT BOTTOM
BRBF BUCKLING RESTRAINED BRACE FRAME
BRG BEARING
BS BOTH SIDES
BSMT BASEMENT
BTWN BETWEEN
BW BOTH WAYS
C CHANNEL
CIP CAST IN PLACE
CJ CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUOUS
CSK COUNTERSINK
CTR CENTER
d PENNY (NAIL SIZE)
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEMO DEMOLITION
DET, DETS DETAIL, DETAILS
DIA, DIAM DIAMETER
DIAG DIAGONAL
DIM, DIMS DIMENSION, DIMENSIONS
DIST DISTANCE
DK, DKG DECK OR DECKING
DN DOWN
DO DITTO
DP DEEP
DS DIAGONAL SHEATHING
DSA DIVISION OF THE STATE ARCHITECT
DWG, DWGS DRAWING, DRAWINGS
DWL, DWLS DOWEL, DOWELS
EA EACH
EBF ECCENTRIC BRACE FRAME
EF EACH FACE
EJ EXPENSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT
EN EDGE NAILING
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EW EACH WAY
EXCAV EXCAVATION
EXP EXPANSION
EXT EXTERIOR
FDN FOUNDATION
FF FAR FACE
FIN FINISH
FLG FLANGE
FLR, FLRS FLOOR, FLOORS
FN FIELD NAILING
FO FACE OF
FOC FACE OF CONCRETE
FOS FACE OF STUD
FP FIREPROOF
FRMG FRAMING
FS FAR SIDE
FT FOOT OR FEET
FTG, FTGS FOOTING, FOOTINGS
GA GAUGE
GALV GALVANIZED
GL GLU-LAM
GLB GLU-LAM BEAM
GR GRADE
GRND GROUND
GYP GYPSUM
HDG HOT DIPPED GALVANIZED
HDR HEADER
HK, HKS HOOK, HOOKS
HORIZ, (H) HORIZONTAL
HP HIGH POINT
HSB HIGH STRENGTH BOLTS
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
ID INSIDE DIAMETER/DIMENSION
INFO INFORMATION
ABBREVIATIONS SHEET INDEX
NO DESCRIPTION
S-001 GENERAL NOTES
S-002 SYMBOLS AND ABBREVIATIONS
SB111 FOUNDATION AND GROUND LEVEL PLAN
SF112 MEZZANINE AND ROOF LEVEL FRAMING PLAN
S-201 BUILDING ELEVATIONS
S-301 BUILDING SECTIONS
S-501 TYPICAL CONCRETE DETAILS
S-502 TYPICAL MASONRY DETAILS
S-503 TYPICAL MASONRY DETAILS
S-504 TYPICAL STEEL DETAILS
S-505 TYPICAL DECK DETAILS
JH JOIST HANGER
JST,JSTS JOIST, JOISTS
JT JOINT
KO KNOCK-OUT
L ANGLE
LEV LEVEL
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION
LONGIT LONGITUDINAL
LP LOW POINT
LT LIGHT
LWC LIGHTWEIGHT CONCRETE
MAX MAXIMUM
MB MACHINE BOLT
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING DOCUMENTS
MEZZ MEZZANINE
MF MOMENT FRAME
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
NF NEAR FACE
NIC NOT IN CONTRACT
NOM NOMINAL (DIAMETER)
NS NEAR SIDE
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OBF ORDINARY BRACED FRAMES
OC ON CENTER
OD OUTSIDE DIAMETER
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
P-T POST-TENSION
PC, PCS PIECE, PIECES
PCC PRECAST CONCRETE
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLYWD PLYWOOD
PT PRESSURE TREATED
PTN PARTITION
R RADIUS
REBAR REINFORCING BAR
REF REFERENCE
REINF REINFORCING
REQD REQUIRED
REV REVISION
RFG ROOFING
RO ROUGH OPENING
RSJ ROLLED STEEL JOIST
S.A.D. SEE ARCHITECTURAL DOCUMENTS/DRAWINGS
S.M.D. SEE MECHANIAL DRAWINGS
SCHED SCHEDULE
SECT SECTION
SEOR STRUCTURAL ENGINEER OF RECORD
SFRS SEISMIC FORCE RESISTING SYSTEM
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SL SLOPE
SMF SPECIAL MOMENT FRAME
SMS SHEET METAL SCREW
SOG SLAB ON GRADE
SP STRUCTURAL PLYWOOD
SPEC, SPECS SPECIFICATION, SPECIFICATIONS
SPSW SPECIAL PLATE SHEAR WALL
SQ SQUARE
SS STAINLESS STEEL
STAG STAGGER or STAGGERED
STD STANDARD
STIF STIFFENER
STIR STIRRUP OR STIRRUPS
STL STEEL
STRUCT STRUCTURAL
SUB SUBSTITUTE
SUSP SUSPENDED
SYMM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE and GROOVE
T.O. TOP OF
THK THICK
THRD THREADED
THRU THROUGH
TN TOE NAIL
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TOW TOP OF WALL
TR TREAD
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
URM UNREINFORCED MASONRY
VENT VENTILATE
VERT, (V) VERTICAL
VIF VERIFY IN FIELD
W or WF WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WP WORK POINT
WS WOOD SCREW
WT WEIGHT/TEE SECTION
WWM WELDED WIRE MESH
X HVY EXTRA HEAVY
X STR EXTRA STRONG
XX HVY DOUBLE EXTRA HEAVY
XX STR DOUBLE EXTRA STRONG
1 2 3 4 5
A A
B
C
D
E
A.8 A.8
75'-0"
14'-6" 26'-4" 18'-8" 15'-6"
C1
S-301
3.9
B.2 B.2
C.2
NOTES:
1. SEE GEOTECH FOR SUBGRADE PREP, VAPOR BARRIER, ETC.
2. PROVIDE CONCRETE HOUSEKEEPING PADS AT ALL EQUIPMENT TYP. SEE
DETAIL F2/S-501
3. AT DESIGN TEAM'S OPTION, WALLS SHOWN AS CMU MAY BE
SUBSTITUTED FOR CONCRETE WALLS WITH SAME THICKNESS AND
REINFORCEMENT.
4. ALL DIMENSION AND SIZES ARE APROX.
EXISTING TUNNEL
TIE INTO NEW PIT.
DEMOLISH REMAINDER
OF TUNNEL.
DEMOLISH EXISITNG
UTILITY TUNNEL AND
BACKFILL WITH
ENGINEERED FILL OR
LEAN CONCRETE.
HSS COLUMNS,
SEE 2/SF112
C6
S-301
F6
S-301
8"
2'-0" x 2'-0"
TYPICAL FOOTING
AT CMU WALLS
5'-0" x 5'-0" x 2'-0" DEEP SPREAD
FOOTING AT COLUMNS, U.N.O.
6'-0" x 6'-0" x 2'-0" DEEP
SPREAD FOOTING
C6
S-201
F1
S-201
C1
S-201
F6
S-201
TEMPORARY UTILITY TRENCH
T E
M P
O R
A R
Y U
T
IL
IT
Y
T R
E N
C H
EXISTING UTILITY
TUNNEL TO REMAIN
C.5
1 2 3 4 5
A
B
C
D
E
A.8
-10'-0"
-10'-0"
75'-0"
14'-6" 26'-4" 18'-8" 15'-6"
C1
S-301
3.9
B.2
C.2
5" MIN SLAB ON GRADE
W/ #4 @ 12" OC EW MIN.
NOTES:
1. SEE GEOTECH FOR SUBGRADE PREP, VAPOR BARRIER, ETC.
2. PROVIDE CONCRETE HOUSEKEEPING PADS AT ALL EQUIPMENT TYP SEE DETAIL
F2/S-501
3. AT DESIGN TEAM'S OPTION, WALLS SHOWN AS CMU MAY BE SUBSTITUTED FOR
CONCRETE WALLS WITH SAME THICKNESS AND REINFORCEMENT.
4. ALL DIMENSION AND SIZES ARE APROX.
5. PROVIDE TRENCH DRAINS AND DEPRESSIONS AS NEEDED. SEE D2/S501
3'-2"
8"
2'-4"
C6
S-301
F6
S-301
CMU OR METAL
STUD PARTITIONS
SEE ARCH PLANS.
16" CMU WALLS AT
TWO STORY SPACE.
12" CMU WALLS
TYP UON.
CMU PILASTER AT
OPENINGS IN WALL
SEE 12 & 18 / S503
C6
S-201
F1
S-201
C1
S-201
F6
S-201
16" CMU WALL
16" CMU WALL
16" CMU WALL
8" CMU WALL
8" CMU WALL
16" CMU WALL
C.5 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:0 :5
P
M
FOUNDATION AND GROUND LEVEL
PLAN
PF 21 88RG
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLAN
4/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
SB111
1/8" = 1'-0"
2 GROUND LEVEL FOUNDATION
1/8" = 1'-0"
1 GROUND LEVEL
1 2 3 4 5
A
B
C
D
E
A.8
W18x
W x
W x
W18x W21x
W30x
W21x W21x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W16x W18x W18x
W18x W21x W18x
W x
W21xW16x W18x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W16x
W x
W x
W x
75'-0"
14'-6" 26'-4" 18'-8" 15'-6"
C1
S-301
3.9
W12x
W x
W16x B.2
C.2
C6
S-301
F6
S-301
C6
S-201
F1
S-201
C1
S-201
F6
S-201
NOTES:
1. ALL DIMENSION ARE APROX.
2. ALL CMU WALL THICKNESSES MATCH WALL THICKNESS AT
GROUND LEVEL
3. AT DESIGN TEAM'S OPTION, WALLS SHOWN AS CMU MAY BE
SUBSTITUTED FOR CONCRETE WALLS WITH SAME THICKNESS AND
REINFORCEMENT.
4. PROVIDE HOUSEKEEPING PADS UNDER EQUIPMENT.
STEEL STAIR,
TYP
STEEL STAIR,
TYP
S1
W8x
W x
HSS 10X10
COLUMNS, U.N.O.
HSS 12X12
COLUMNS AT
GRIDS C, C.2, D
HSS 14X14 COLUMNS
AT GRIDS E
CMU BELOW
CMU BELOW
ALIGN BEAMS WITH
CHILLER RAILS
W16x
W x
W x
W x
C.5 W18xW16x
W21x
W x
W x
W x
W x
W x
W x
W x
1 2 3 4 5
A
B
C
D
E
A.8
75'-0"
14'-6" 26'-4" 18'-8" 15'-6"
W14x
W21x W18x
W x
W x
W x
W21x
W x
W16x
W x
W30x W30x W21x
W30x
W30x
W16x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x W x
W x
W x
C1
S-301
3.9
W18x
W x
W x
W x
W24x
W12x
B.2
C.2
NOTES:
1. CHORDS AND COLLECTORS NOT SHOWN.
2. ALL DIMENSION ARE APROX.
3. SEE 2/SF112 FOR COLUMN SIZES
4. PROVIDE HOUSEKEEPING PADS UNDER EQUIPMENT.
BEAM REMOVABLE
FOR CHILLER
REPLACMENT.
S1
C6
S-301
F6
S-301
W16x
W x
W x
58'-10"
C6
S-201
F1
S-201
C1
S-201
F6
S-201
CONTINUOUS FLAT
C O
N T
IN
U
O U
S F
L A
T
W8x
W x
C.5
W12x
W x th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:0 :5
P
M
MEZZANINE AND ROOF LEVEL FRAMING
PLAN
PF 22 88RG
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLAN
4/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
SF112
1/8" = 1'-0"
2 MEZZANINE FRAMING PLAN
1/8" = 1'-0"
1 ROOF FRAMING PLAN
GROUND LEVEL
0"
MEZZANINE
15'-0"
ROOF
33' - 0"
12345
C1
S-301
BLAST RATED METAL STUD
FRAME WALL ABOVE AND
BETWEEN LOUVERS
LOUVER LOUVER LOUVER LOUVER LOUVER LOUVER
CMU OR CAST IN PLACE
CONCRETE WALLS. SEE
PLAN FOR SIZES. SEE
SHEETS S502 AND S503
BLAST RATED LOUVERS
BLAST RATED DOORS
ON EXTERIOR, TYP
STANDARD COILING DOORS
WITH BLAST CATCHMENT
SYSTEM. PROVIDE
SUPPLEMENTAL STEEL
SUPPORTS AS NEEDED, TYP
GROUND LEVEL
0"
MEZZANINE
15'-0"
ROOF
33' - 0"
ABCDE
C6
S-301
F6
S-301
LOUVER
LOUVER
BLAST RATED
LOUVERS
BLAST RATED
LOUVERS
BLAST RATED DOORS
ON EXTERIOR, TYP
CMU OR CAST IN PLACE CONCRETE
WALLS. SEE PLANS FOR SIZES. SEE
SHEETS S502 AND S503
C.5
GROUND LEVEL
0"
MEZZANINE
15'-0"
ROOF
33' - 0"
A B C D EA.8
C6
S-301
F6
S-301
BLAST RATED METAL
STUD FRAMED WALL
ABOVE AND BETWEEN
LOUVERS
LOUVER LOUVER
BLAST RATED
LOUVERS
STANDARD COILING DOORS
WITH BLAST CATCHMENT
SYSTEM. PROVIDE
SUPPLEMENTAL STEEL
SUPPORTS AS NEEDED, TYP
BLAST RATED
DOORS ON
EXTERIOR, TYP
CMU OR CAST IN PLACE
CONCRETE WALLS. SEE
PLAND FOR SIZES. SEE
SHEETS S502 AND S503
C.5
GROUND LEVEL
0"
MEZZANINE
15'-0"
ROOF
33' - 0"
1 2 3 4 5
C1
S-301
BLAST RATED GUILITTINE TYPE
DOOR INTERIOR OF EXTERIOR
WALL. CMU PILASTERS OR
SUPPLEMENTAL STEEL ON
INTERIOR TO SUPPORT DOORS
CMU OR CAST IN PLACE CONCRETE
WALLS. SEE PLANS FOR SIZES. SEE
SHEETS S502 AND S503
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:0 :4
P
M
BUILDING ELEVATIONS
PF 23 88RG
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLAN
4/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
S-201
1/8" = 1'-0"
C6 ELEVATION
1/8" = 1'-0"
F1 ELEVATION
1/8" = 1'-0"
C1 ELEVATION
1/8" = 1'-0"
F6 ELEVATION
GROUND LEVEL
0"
MEZZANINE
15'-0"
ROOF
33' - 0"
1 2 3 4 53.9
SCREEN WALL AND
LOUVER BRACING BEAMS.
SUPPLEMENTAL TUBE STEEL
FRAMING TO SUPPORT
BLAST RATED SCREEN WALL
AND LOUVERS.
LOUVERS
METAL STUD FRAMING
ABOVE LOUVERS
LOUVERS
CONCRETE ON METAL
DECK OVER STEEL
FRAMING, SEE PLANS
GROUND LEVEL
0"
MEZZANINE
15'-0"
ROOF
33' - 0"
A B C D E
SCREEN WALL AND
LOUVER BRACING BEAMS.
SUPPLEMENTAL TUBE
STEEL FRAMING TO
SUPPORT SCREEN WALL
AND LOUVERS.
LOUVERS
METAL STUD FRAMING
ABOVE LOUVERS
CONCRETE ON METAL DECK
OVER FRAMING, SEE PLANS
C.5
GROUND LEVEL
0"
MEZZANINE
15'-0"
ROOF
33' - 0"
1 2 3 4 53.9
CONCRETE ON METAL
DECK OVER STEEL
FRAMING, SEE PLANS
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:0 :4
P
M
BUILDING SECTIONS
PF 24 88RG
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLAN
4/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
S-301
1/8" = 1'-0"
C6 SECTION
1/8" = 1'-0"
C1 SECTION
1/8" = 1'-0"
F6 SECTION
NOTES:
1. TABULATED VALUES ARE BASED ON GRADE 60 REINFORCING BARS. FOR GRADE 75 REINFORCING BARS, MULTIPLY THE ABOVE LENGTHS BY 1.25.
2. CASES 1 AND 2 DEPEND ON THE TYPE OF STRUCTURAL MEMBER, CONCRETE COVER, AND CENTER-TO-CENTER SPACING OF THE BARS. THEY ARE
DEFINED IN THE FOLLOWING TABLE, WHERE "db" IS BAR DIAMETER:
CASE 2
CASE 1
CASE 2
CASE 1
CONCRETE COVER AT LEAST 1.0db AND CENTER LINE TO CENTER LINE SPACING AT LEAST 2.0db.
CONCRETE COVER LESS THAN 1.0db OR CENTER LINE TO CENTER LINE SPACING LESS THAN 2.0db.
BEAMS, COLUMNS,
GRADE BEAMS
ALL OTHERS
CONCRETE COVER AT LEAST 1.0db AND CENTER LINE TO CENTER LINE SPACING AT LEAST 3.0db.
CONCRETE COVER LESS THAN 1.0db OR CENTER LINE TO CENTER LINE SPACING LESS THAN 3.0db.
3. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12 INCHES OF CONCRETE CAST BELOW THE BARS.
4. TENSION LAP SPLICES NOT ALLOWED FOR #14 AND #18 BARS.
5. MULTIPLY THE ABOVE LENGTHS BY 1.5 FOR EPOXY COATED REINFORCEMENT.
6. FOR LIGHTWEIGHT AGGREGATE CONCRETE, MULTIPLY THE TABULATED VALUES BY 1.33.
7. Ld = DEVELOPMENT LENGTH
Ls = ACI CLASS 'B' LAP SPLICE LENGTH
8. WHEN SPLICING BARS OF DIFFERENT SIZES, USE THE GREATER OF Ld OF THE LARGER BAR AND Ls OF THE SMALLER BAR.
Ls
Ld
SAD FOR LOCATION OF
DEPRESSION, TYP
SEE TYP SOG DETAIL FOR SLAB
THICKNESS 't', REINF & SUBGRADE
PREPARATION, TYP
A 'd' ≤ 3"
PROVIDE SLAB REINF @
INSIDE OF ALL BAR
BENDS, TYP
EL: SEE PLAN
TO SLAB
B 3" < 'd' ≤ 12"
EL: SEE PLAN
TO SLAB
C 12" < 'd' ≤ 42"
OPTIONAL
CONSTRUCTION
JOINT @ T&B
HORIZ #4 @ 12" OC, (1)
BAR MIN
SLAB REINF
PER PLAN
S.A.D. FOR EDGE CONDITION
AND / OR INSERTS.
SEE TYP REINF CORNER
DETAIL AS REQ'D
SLAB REINF
PER PLAN
VERT REINF, MATCH SLAB
REINF SIZE & SPACING
(#4 @ 18" OC MIN)
NOTE:
1. COORDINATE LOCATION, DEPTH, EXTENT, AND EDGE CONDITIONS WITH
ARCHITECTURAL DRAWINGS.
2. CONCRETE SLABS WITH DOUBLE LAYERS OF REINFORCEMENT ARE SIMILAR.
VERT REINF, MATCH SLAB
REINF SIZE & SPACING
EL: SEE PLAN
TO SLAB P
L A
N 'd
' P E
R
't'
't'
P L A
N
'd ' P
E R
't'
't'
M
IN
't'
P L A
N
'd ' P
E R
't'
EQ EQ
UON
8" MIN,
MIN
1'-0"
MIN
8"
MIN
1'-0"
TYP
Ldh
INTERMEDIATE WALLS
@ 8'-0" OC, EW MAX
FOAM FILL
OMIT IF < 8"
#4 EPOXY DWLS
@ 12" OC, TYP
4 SIDES EMBED 2 3/4"
#4 @ 12" OC, EW
ROUGHEN SURFACE TO
1/4" MIN AMPLITUDE
#4 EPOXY DWLS @
12" OC, TYP EMBED 2 3/4"
ROUGHEN SURFACE TO
1/4" MIN AMPLITUDE
#4 @ 12" OC, EW
8'-0” MAX. 8'-0” MAX.
TYP.
2'-0"
P L A
N
S E
E M A
X
P L A
N S
E E h
8" TYP.
E Q
E Q
SOG REINF PER PLAN
#4 CONT
#4 CONT
#3 @ 12" OC
NOTES:
1. SEE ARCH AND MECH DWGS FOR CURB LOCATIONS, DIMENSIONS, CHAMFERS, AND
INSERTS.
2. COORDINATE REINF LOCATION TO AVOID INTERFERENCE W/ INSTALLATION OF EXP
ANCHORS IF USED.
A 4" ≤ 'W' ≤ 10"
B 10" < 'W' ≤ 24"
#3 @ 12" OC
SOG REINF
PER PLAN
1'-0"
TYP
1'-0"
'W'
P L A
N S
E E
C L R
M A
X
C L R
CLR, TYP
1 1/2"
'W'
M A
X
S E
E S
C H
E D
T Y
P
IC
A L
STD HK, ALL SIDES
SEE PLAN FOR
SLAB & REINF
SLAB BLOCKOUT
AT COL, TYP
SLAB DWLS W/ STD HK,
SEE SCHEDULE
LONGIT. REINF,
SEE SCHED
B A
R S
W S
T D
H K
E A
E N
D
COLUMN & BASE PLATE,
SEE SCHEDULE
TRANSVERSE REINF, SEE
SCHEDULE
EL.: SEE PLAN
T.O. SLAB
EL.: SEE PLAN
T.O. FTG.
'H
T Y
P
L d
O R
L d h
SEE SCHED
'B'
TYP
3" CLR
C L
R
6" MAX.
EQ EQ
STAIR STRINGER
ADD'L BENT BAR
TO MATCH SOG REINF
SIZE & SPACING
SOG PER PLAN
THICKEN SLAB 2'-0" PAST
STRINGER, EA SIDE
ADD'L (2) #4
TYP
1'-0"
1'-0" f 'c=3000 psi (NWC)
BAR
SIZE
#3 6
#4
#5
#6
CASE 1
NOTES:
1. TABULATED VALUES ARE BASED ON GRADE 60 REINFORCING BARS. FOR GRADE 75 REINFORCING
BARS, MULTIPLY THE TABULATED VALUES BY 1.25.
2. CASES 1 AND 2 ARE DEFINED BELOW:
CASE 1: FOR #11 BARS AND SMALLER HKS WITH SIDE COVER NOT LESS THAN 2.5 INCHES
AND COVER ON BAR EXTENSION BEYOND HK NOT LESS THAN 2 INCHES.
CASE 2: ALL OTHER CASES
3. FOR EPOXY COATED ERINFORCEMENT, MULTIPLY THE TABULATED VALUES BY 1.2
4. FOR LIGHT WEIGHT CONCRETE, MULTIPLY THE TABULATED VALUES BY 1.33.
5. Ldh = HOK DEVELOPMENT LENGTH.
CASE 2
f 'c=4000 psi (NWC)
CASE 1
CASE 2
f 'c=5000 psi (NWC)
CASE 1
CASE 2
f 'c=6000 psi (NWC)
CASE 1
CASE 2
#7 14 20 12 17 11 15 10 14
#8 16 22 14 19 12 17 11 16
#9 18 25 15 22 14 20 13 18
#10 20 28 17 25 16 22 14 20
#11 22 31 19 27 17 24 16 22
#14 - 38 - 33 - 29 - 27
#18 - 50 - 43 - 39 - 35
DEVELOPMENT LENGTH OF STANDARD HK IN TENSION FOR CONCRETE REINFORCEMENT
CONT REINF THRU JT.,
DO NOT SPLICE WITHIN
2'-0" OF JT.
NOTE:
CONSTRUCTION JOINTS TO BE USED ONLY WHERE SHOWN ON PLAN
OR SPECIFICALLY APPROVED BY THE OWNER'S REPRESENTATIVE.
BULLNOSE EDGE
TYP CONT
CONSTRUCTION
JOINT KEY TYPE 2
SEE TYPICAL DETAILS
FOR SLAB THICKNESS,
REINF, & SUBGRADE
PREPARATION
3/4"Ø GREASED DWLS
TO MATCH SPACING OF
SLAB REINF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:0 :5
P
M
TYPICAL CONCRETE DETAILS
PF 25 88RG
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLAN
4/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
S-501
D6 REINFORCEMENT DEVELOPMENT & SPLICE LENGTHS
#18 ℓd 162 242 124 186 141 210 108 161 125 188 96 144 115 172 88 132
#14 ℓd 121 182 93 140 106 158 81 121 94 141 72 108 86 129 66 99 ℓs 133 197 102 151 115 172 88 132 102 153 78 117 94 140 72 107 #11 ℓd 102 151 78 116 88 132 67 101 78 117 60 90 72 107 55 82 ℓs 119 179 91 137 104 155 80 119 93 138 71 106 85 127 65 97 #10 ℓd 91 137 70 105 80 119 61 91 71 106 54 81 65 97 50 74 ℓs 106 158 81 121 93 138 71 106 82 123 63 94 76 112 58 86 #9 ℓd 81 121 62 93 71 106 54 81 63 94 48 72 58 86 44 66 ℓs 94 141 72 108 82 123 63 94 73 110 56 84 67 101 51 77 #8 ℓd 72 108 55 83 63 94 48 72 56 84 43 64 51 77 39 59 ℓs 82 123 63 94 72 107 55 82 65 95 50 73 59 88 45 67 #7 ℓd 63 94 48 72 55 82 42 63 50 73 38 56 45 67 34 51 ℓs 56 85 43 65 50 73 38 56 45 67 34 51 42 60 32 46 #6 ℓd 43 65 33 50 38 56 29 43 34 51 26 39 32 46 24 35 ℓs 49 72 37 55 42 62 32 47 38 55 29 42 34 51 26 39 #5 ℓd 37 55 28 42 32 47 24 36 29 42 22 32 26 39 20 30 ℓs 38 56 29 43 33 50 25 38 30 45 23 34 28 42 21 32 #4 ℓd 29…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .