Design Drawings Fire Protection_654-212.pdf
PDF 3 MB Posted
- Solicitation number
- QSE--36C10F24R50000
About this file
This document contains construction drawings for a fire protection system and fire suppression system as part of a design-build project to construct a new Central Utility Plant (CUP) at the VA Sierra Nevada Health Care System in Reno, Nevada.
The drawings show the layout and details for the fire alarm system, including fire alarm control unit, annunciator, devices, riser diagrams, and input/output matrices. The fire suppression system drawings depict the wet pipe sprinkler system layout, hazard classifications, and sprinkler riser details. The scope of work for the overall design-build project includes constructing the new CUP building, demolishing the existing boiler plant, and converting the boiler plant site into a parking lot. The contractor will be responsible for all required professional design services and construction activities to complete the project in accordance with VA Technical Design Library requirements.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. DEPARTMENT OF VETERANS AFFAIRS
FIRE PROTECTION 30x42 DRAWINGS
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
VA PROJECT NUMBER: 654-212
[09] FIRE PROTECTION
91 FA001 FIRE ALARM NOTES, MATRIX, RISERS
92 FA101 FIRE ALARM FLOOR PLAN
93 FA500 FIRE ALARM DETAILS
94 FX101 FIRE SUPPRESSION FLOOR PLAN
95 FX500 FIRE SPRINKLER DETAILS
CENTRAL UTILITY PLANT
1. SYSTEM DESCRIPTION
A. THIS SYSTEM INDICATED HEREIN IS AN IN-BUILDING FIRE EMERGENCY VOICE/ALARM
COMMUNICATIONS SYSTEM AS DEFINED BY NFPA 72. UPON AUTOMATIC OR MANUAL
ACTIVATION, THE SYSTEM MUST AUTOMATICALLY COMMUNICATE EMERGENCY INFORMATION
THROUGHOUT THE PROTECTED PREMISES. THE PROTECTED PREMISES ONLY INCLUDES THE
NEW CENTRAL UTILITY PLANT (BUILDING 16).
B. THE SYSTEM MUST ALSO PASS AUDIO SIGNALS FROM THE EXISTING CAMPUS-WIDE
EMERGENCY NOTIFICATION SYSTEM INTO THE PROTECTED PREMISES SYSTEM AND
AUTOMATICALLY SEND STATUS SIGNALS TO THE PROPRIETARY SUPERVISING STATION.
2. PURPOSE OF PLANS
A. THESE PLANS ARE INTENDED TO DEMONSTRATE CRITERIA, DEMONSTRATE CODE
COMPLIANCE, AND PROVIDE BRIDGING SUPPORT FOR SUBSEQUENT DESIGN SUBMITTALS.
B. THESE PLANS ARE INTENDED TO DEMONSTRATE PROPOSED AND COMPLIANT LOCATIONS,
TYPES, AND SETTINGS OF INITIATING DEVICES, NOTIFICATION APPLIANCES, ANNUNCIATORS, CONTROL UNITS, AND ASSOCIATED MAJOR COMPONENTS.
C. THESE PLANS ARE NOT INTENDED TO BE USED FOR CONSTRUCTION.
D. THESE PLANS ARE NOT INTENDED TO SHOW ALL CIRCUITS, COMPONENTS, ACCESSORIES,
AND OTHER DETAILS WHICH MUST BE DOCUMENTED IN THE CONTRACTOR'S SHOP
DRAWINGS, CALCULATIONS, AND PRODUCT DATA SELECTIONS.
E. MODIFICATIONS MADE BY THE CONTRACTOR RESULTANT FROM COORDINATION,
CALCULATIONS, OR CONTRACTOR ROUTING AND INSTALLATION PREFERENCES MUST BE
PERFORMED AT NO ADDITIONAL COST TO THE OWNER.
F. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL MANUFACTURER AND MODEL DATA
INDICATED HEREIN IS A BASIS OF DESIGN AND IS NOT SOLE-SOURCED. THE CONTRACTOR
MAY SELECT THEIR OWN MANUFACTURER AND MODEL, EXCEPT WHERE EXPLICITLY NOTED
OTHERWISE.
a. NOTE: THE EXISTING FIRE ALARM SYSTEM HEAD END IS EDWARDS SYSTEMS
TECHNOLOGY (EST3) LOCATED IN BUILDING 1.
3. APPLICABLE CRITERIA
A. SUBSEQENT DESIGN SHALL INCORPORATE THE LATEST AND GREATEST CRITERIA AT TIME
DESIGN IS AWARED PER ADOPTED VA STANDARDS.
a. INTERNATIONAL BUILDING CODE, 2022
b. NFPA 30 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE, 2021
c. NFPA 55 COMPRESSED GASES AND CRYOGENIC FLUIDS, 2023
d. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2022
e. NFPA 70 NATIONAL ELECTRICAL CODE, 2023
f. NFPA 99 HEALTH CARE FACILITIES CODE, 2021
g. NFPA 101 LIFE SAFETY CODE, 2021
h. VA FIRE PROTECTION DESIGN MANUAL - 2021 EDITION
4. SPECIFICATIONS
A. REFER TO PROJECT SPECIFICATIONS FOR MANY QUALIFICATIONS, SUBMITTAL, PRODUCT,
INSTALLATION, TESTING, AND DOCUMENTATION CRITERIA. THE PROJECT SPECIFICATIONS
ARE WRITTEN WITH INTENT AND WILL BE ENFORCED.
B. SPECIFICATION CRITERIA STATED ON THESE PLANS IS INTENDED TO SUMMARIZE MAJOR
SYSTEM CRITERIA. REFER TO SPECIFICATIONS FOR ALL DETAILS.
5. BUILDING BASICS
A. INFORMATION STATED HEREIN IS FOR REFERENCE ONLY.
B. THE BUILDING IS A COMBINATION OF SPECIAL PURPOSE INDUSTRIAL AND NEW BUSINESS
OCCUPANCY.
C. THE BUILDING IS TWO STORIES ABOVE GRADE PLUS A ROOFTOP PENTHOUSE WHICH IS NOT
CONSIDERED A THIRD STORY.
D. THE BUILDING CONSTRUCTION TYPE IS NONCOMBUSTIBLE.
E. WET PIPE SPRINKLER SYSTEMS PROVIDE BUILDING AUTOMATIC FIRE SUPPRESSION.
6. SUPERVISING STATION COMMUNICATIONS
A. THE METHOD OF SUPERVISING STATION COMMUNICATION IS A CLASS A CAMPUS LOOP ON
THE EXISTING EST NETWORK.
B. SUPERVISING COMMUNICATION MEANS MUST BE COMPATIBLE WITH THE EXISTING EST
NETWORK. DESIGN TEAM AND CONTRACTOR MUST COORDINATE WITH VA CAMPUS FIRE
DEPARTMENT AND COTR TO ENSURE COMPLIANT AND COMPATIBLE EQUIPMENT.
7. NOTIFICATION
A. THIS SYSTEM IS DESIGNED TO PROVIDE TOTAL EVACUATION. NEITHER PARTIAL EVACUATION
NOR OCCUPANT RELOCATION ARE SPECIFIED.
B. PUBLIC MODE AUDIBLE NOTIFICATION IS REQUIRED THROUGHOUT ALL "OCCUPIABLE AREAS"
AS DEFINED BY NFPA 72.
C. INTELLIGIBLE VOICE NOTIFICATION IS REQUIRED THROUGHOUT ALL PUBLIC, COMMON, AND
EMPLOYEE WORK AREAS.
D. VISUAL NOTIFICATION IS REQUIRED THROUGHOUT ALL PUBLIC AND COMMON WORK AREAS.
E. NOTIFICATION ZONING IS TOTAL EVACUATION, BUT WITH ZONES FOR MANUAL CONTROL BY
FLOOR.
8. CIRCUITS AND PATHWAYS
A. CIRCUITS MUST BE CLASS B OR MORE RESILIENT; NETWORK RISERS MUST BE CLASS X.
B. ALL CIRCUITS MUST BE PROVIDED IN 3/4-INCH MINIMUM METALLIC CONDUIT.
C. FLEXIBLE METALLIC CONDUIT IS PERMITTED IN LENGTHS NOT EXCEEDING 6 FEET WHERE
CONNECTING TO CEILING-MOUNT DEVICES OR SPRINKLER SYSTEM DEVICES.
9. INSTALLATION
A. ALL COMPONENTS MUST BE COORDINATED WITH OTHER TRADES AND INSTALLED PARALLEL
OR PERPINDICULAR TO THE BUILDING STRUCTURE.
B. SYSTEM INSTALLATION MUST BE PERFORMED IN A NEAT, WORKMAN-LIKE MANNER.
C. ALL INSTALLATION AND TESTING MUST COMPLY WITH THE APPLICABLE CRITERIA AND
MANUFACTURER'S INSTRUCTIONS.
D. THE SYSTEM MUST BE TURNED OVER TO THE OWNER IN LIKE-NEW CONDITION. THE
CONTRACTOR MUST REPLACE DAMAGED COMPONENTS WITH NEW COMPONENTS IF
DAMAGED BEFORE TURNOVER.
10. SUBSEQUENT DESIGN
A. DESIGN TEAM SHALL COORDINATE FINAL LOCATION OF CARBON MONOXIDE AND DUCT
DETECTION TO ENSURE ACCESSIBLE MAINTENANCE AS REQUESTED BY CLIENT.
B. DESIGN TEAM SHALL COORDINATE WITH ONGOING EHERM FIBER LOOP UPGRADES TO
ENSURE NEW CUP IS CONNECTING TO NEW FIBER LOOP FOR FIRE ALARM COMMUNICATION.
C. ENSURE ALL SIGNALS REQUIRED TO BE PASSED ALONG TO FIRE DEPARTMENT ARE INCLUDED
IN FINAL DESIGN. CURRENTLY CUP FIRE ALARM TRANSMITS ALL FIRE ALARM, SUPERVISORY
AND TROUBLE CONDITIONS TO BUILDING 1 HEAD END. AS PART OF THIS SCOPE OF WORK
BUILDING 1 HEAD END SHALL BE REPROGRAMMED AS NECESSARY TO TRANSMIT NECESSARY
SIGNALS TO FIRE DEPARTMENT.
SYMBOL MODIFIER
FIRE ALARM LEGEND
FACU
FAA
SPD
AHU
F
AIM
AOM
CO
WF
VS
RTS
F
S
S
FIRE ALARM MASS NOTIFICATION CONTROL UNIT
FIRE ALARM ANNUNCIATOR
SURGE PROTECTIVE DEVICE
AIR HANDLING UNIT
MANUAL PULL STATION
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
GAS DETECTOR - CARBON MONOXIDE
WATERFLOW SWITCH
VALVE SUPERVISORY SWITCH
REMOTE TEST SWITCH
HORN/STROBE
STROBE - WALL MOUNT
VIBRATING BELL
SMOKE DETECTOR - SPOT TYPE
SMOKE DETECTOR - DUCT TYPE
SYMBOL MODIFIERS
ncd CANDELA RATING nW
C
WATT TAP
CEILING MOUNT
WP WEATHER PROOF
EXTINGUISHER - TYPE A:B:C
EXTINGUISHER - CO2
GCCFW
PRN
GRAPHICAL COMMAND AND CONTROL FIREWORKS WORKSTATION.
FURNISHED BY OTHERS.
PRINTER.
FURNISHED BY OTHERS.
MASTER MASTER (FIRE ALARM CONTROL UNIT)
FACU
SPD
PRN
S F
WF VS
COC
RISER NOTES:
1. THIS RISER DIAGRAMMATIC AND INDICATES DESIGN INTENT. CONTRACTOR
MUST PROVIDE ALL EQUIPMENT, CONNECTIONS, CONDUCTORS, AND
ACCESSORIES AS NECESSARY TO COMPLY WITH DESIGN INTENT SPECIFIED
HEREIN INCLUDING APPLICABLE CODES AND STANDARDS.
2. TO 120VAC CIRCUIT DEDICATED TO FIRE ALARM SYSTEM
3. NEW FIBER OPTIC FIRE ALARM COMMUNICATION LOOP TO MASTER FIRE
ALARM CONTROL UNIT LOCATED IN BUILDING 1, ROOM C1234 AND REMOTE
FIREWORKS WORKSTATION LOCATED IN BUILDING zzzzzzzz, ROOM zzzzzzz.
UTILIZE EXISTING PATHWAYS FOR FIBER OPTIC CIRCUIT.
4. 24VDC AUXILIARY POWER
WP
S
RTS
AIM AIM
FWP
FAA
GCCFWGCCFW
FACU
MASTER
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I N
D
IC
A T
O R
A C
T
IV
A T
E A
U D
IB
L E
A L
A R
M S
IG
N
A L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L
I N
D
IC
A T
O R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
A R
B O
N M
O N
O X
ID
E
S U
P E
R V
IS
O
R Y
S
IG
N A
L I N
D
IC
A T
O R
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I N
D
IC
A T
O R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L
E S
IG
N
A L
D
IS
P L
A Y
/P R
IN
T
C H
A N
G E
O F
S T
A T
U S N
O T
IF
IC
A T
IO
N
A C
T
IV
A T
E T
E M
P O
R A
L
A L E
R T
T O
N E
A N
D P
R E
-R E
C O
R D
E D
F
IR
E E
V A
C U
A T
IO
N
M
E S
S A
G E
T H
R O
U G
H O
U T
B U
IL
D
IN
G
A C
T
IV
A T
E S
T R
O B
E S
T H
R O
U G
H O
U T
B U
IL
D
IN
G
A C
T
IV
A T
E T
-4 A
L E
R T
T O
N E
A N
D U
N
IQ
U E
C A
R B
O N
M O
N O
X
ID
E M
E S
S A
G
T
H R
O U
G H
O U
T B
U
IL
D
IN
G
A C
T
IV
A T
E E
X T
E R
IO
R
W A
T E
R F
L O
W H
O R
N /S
T R
O B
E
T R
A N
S M
IT
F
IR
E
A L
A R
M S
IG
N
A L
T O
M A
S T
E R
F A
C U
I N
B U
IL
D
IN
G
R
O O
M C
B
Y
D
V
IC
E T
Y P
E
T R
A N
S M
IT
G
E N
E R
A L S
U P
E R
V
IS
O R
Y S
IG
N
A L T
O M
A S
T E
R F
A C
U I N
B U
IL
D
IN
G
R O
O M
C
T R
A N
S M
IT
G
E N
E R
A L T
R O
U B
L E
S
IG
N A
L T
O M
A S
T E
R F
A C
U I N
B U
IL
D
IN
G
R
O O
M
C
A U
X
IL
IA
R
Y F
U N
C T
IO
N
S
S H
U T
D O
W N
A S
S O
C
IA
T E
D A
IR
H
A N
D L
IN
G
U N
IT
ALARM CONDITIONS A B C D E F G H I J K L M N O P
1 MANUAL ALARM PULL STATION X X X X X X
2 SMOKE DETECTOR - SPOT TYPE X X X X X X
3 SMOKE DETECTOR - DUCT TYPE X X X X X
4 WATERFLOW/PRESSURE SWITCH X X X X X X X
5 GAS DETECTOR - CARBON MONOXIDE X X X X X X X
SUPERVISORY CONDITIONS A B C D E F G H I J K L M N O P
6 CONTROL VALVE SUPERVISORY SWITCH X X X X
TROUBLE CONDITIONS A B C D E F G H I J K L M N O P
7 AC POWER FAILURE X X X X
8 LOW BATTERY X X X X
9 OPEN CIRCUIT X X X X
10 GROUND FAULT X X X X
11 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X X
12 REMOTE POWER SUPPLY COMMON TROUBLE X X X X
13 ANY OTHER SYSTEM TROUBLE X X X X
A B C D E F G H I J K L M N O P
X PERFORM OPERATION/REPORT DEVICE STATUS
RATEDENGINEERING.COMRATEDENGINEERING.COMRATEDENGINEERING.COM
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # 91 OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :3
P
M
FIRE ALARM NOTES MATRIX AND RISER
DIAGRAM
JCP 95DBN
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
05/16/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
FA001
SPUR #: 1791.06
FIRE ALARM GENERAL NOTES
NTS
E3
FIRE ALARM RISER DIAGRAM
NTS
C3
FIRE ALARM INPUT/OUTPUT MATRIX
No. REVISION DESCRIPTION DATE
F F
F F
CO
c d c d c d
75cd
C
75cd
C
75cd
C
15cd
15cd
C 15cd
C
30cd
30cd
30cd1 c d
WP
30cd
W P c d c d
110cd110cd c d
110cd
F W
P c d
CO
F
75cd
F
F
WP
F
F c d c d c d
WP
75cd
WP
75cd
WP
15cd
15cd c d c d
30cd
COCOCO
c d
E
A
B
C
D
2 5431 3.9
B.2
A.8
C.2
HAC
N3104
ADS: C
CONFERENCE
/ BREAK
ROOM
N3116
ADS: G
OFFICE
N3106
ADS: A
RESTROOM
N3117
ADS: F
RESTROOM
N3118
ADS: F
PIT
N3109
ADS: C
RISER ROOM
N3110
ADS: C
STEAM PIT
N3102
ADS: C
ELEC
N3107
ADS: J
ELECTRICAL
UTILITY
ROOM
N3108
ADS: J
OXYGEN
YARD
N3112
ADS: C
STORAGE
ROOM
N3103
ADS: B
CORRIDOR
N3105
ADS: A
STAIR
ENCLOSURE
N3119
ADS: K
BOILER AREA
N3101
ADS: C
GENERATORS
N3114
ADS: C
ELECTRICAL
SWITCHGEAR
N3113
ADS: J
CHILLERS
N3111
ADS: C
CONTROL
ROOM
N3115
ADS: A
F A
C U
F A
A
WF
VSVSVS
S
G C
C F
W
E
A
B
C
D
2 5431 3.9
B.2
A.8
C.2
SECURITY
N3204
ADS: A
CORRIDOR
N3206
ADS: A
TR
N3203
ADS: C
ELECTRICAL
AREA
N3201
ADS: J
EMERGENCY
PANELS
N3205
ADS: J
BOILER AREA
N3101
ADS: C
OXYGEN
YARD
N3112
ADS: C
COOLER
TOWERS &
PUMPS
N3202
ADS: C
RATEDENGINEERING.COMRATEDENGINEERING.COMRATEDENGINEERING.COM
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # 92 OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :0
P
M
FIRE ALARM FLOOR PLAN
JCP 95DBN
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
05/16/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
FA101
SPUR #: 1791.06
0 4' 8' 16'
N
No. REVISION DESCRIPTION DATE
1/8" = 1'-0" F1
FIRE ALARM PLAN - LEVEL 1
1/8" = 1'-0"
F5
FIRE ALARM PLAN - MEZZANINE
ADS ROOM SCHEDULE
NUMBER NAME ADS CODE
N3106 OFFICE A
N3105 CORRIDOR A
N3115 CONTROL ROOM A
N3204 SECURITY A
N3206 CORRIDOR A
N3103 STORAGE ROOM B
N3104 HAC C
N3109 PIT C
N3110 RISER ROOM C
N3102 STEAM PIT C
N3112 OXYGEN YARD C
N3101 BOILER AREA C
N3114 GENERATORS C
N3111 CHILLERS C
N3203 TR C
N3101 BOILER AREA C
N3112 OXYGEN YARD C
N3202 COOLER TOWERS & PUMPS C
N3117 RESTROOM F
N3118 RESTROOM F
N3116 CONFERENCE / BREAK ROOM G
N3107 ELEC J
N3108 ELECTRICAL UTILITY ROOM J
N3113 ELECTRICAL SWITCHGEAR J
N3201 ELECTRICAL AREA J
N3205 EMERGENCY PANELS J
N3119 STAIR ENCLOSURE K
ADS LEGEND
ADS
CODE DESCRIPTION
CEILING
HEIGHT CEILING MATERIAL WALL FINISH FLOOR FINISH
A TYPICAL OFFICE / CIRCULATION SPACE ≤10' ABSORBING (ACOUSTICAL TILE, E.G.) REFLECTIVE (GYPSUM, METAL, CONCRETE, E.G.) ABSORBING (CARPET, E.G.)
B TYPICAL STORAGE SPACE > 10' REFLECTIVE (NON-ACOUSTIC TILE, OPEN TO STRUCTURE, E.G.) REFLECTIVE (GYPSUM, METAL, CONCRETE, E.G.) REFLECTIVE (VCT, CONCRETE, E.G.)
C TYPICAL LOUD MECHANICAL SPACE > 10' REFLECTIVE (NON-ACOUSTIC TILE, OPEN TO STRUCTURE, E.G.) REFLECTIVE (GYPSUM, METAL, CONCRETE, E.G.) REFLECTIVE (VCT, CONCRETE, E.G.)
F TYPICAL RESTROOM ≤10' REFLECTIVE (NON-ACOUSTIC TILE, OPEN TO STRUCTURE, E.G.) REFLECTIVE (GYPSUM, METAL, CONCRETE, E.G.) REFLECTIVE (VCT, CONCRETE, E.G.)
G TYPICAL CLASSROOM / CONFERENCE AREA ≤10' ABSORBING (ACOUSTICAL TILE, E.G.) REFLECTIVE (GYPSUM, METAL, CONCRETE, E.G.) ABSORBING (CARPET, E.G.)
J TYPICAL COMM / ELECTRICAL ROOM > 10' REFLECTIVE (NON-ACOUSTIC TILE, OPEN TO STRUCTURE, E.G.) REFLECTIVE (GYPSUM, METAL, CONCRETE, E.G.) REFLECTIVE (VCT, CONCRETE, E.G.)
K NOT REQUIRED
2' - 0"
2' - 0"
DETAIL NOTES:
1. DETAIL TYPICAL FOR ALL CEILING-MOUNT FIRE ALARM
DEVICES, NOT JUST THE INDICATED SPEAKER/STROBE.
2. INSTALL FIRE ALARM DEVICES IN 2' X 4' AND 2' X 2' CEILING
TILES AS INDICATED ABOVE.
3. ALIGN FIRE ALARM DEVICES AMONGST ADJACENT CEILING
TILES WHERE IN THE SAME FIELD OF VIEW INCLUDING
THROUGH OPEN DOORS AND GLASS PARTITIONS.
4. WHERE FIRE ALARM DEVICES ARE INSTALLED IN CEILINGS
OTHER THAN 2' X 4' AND 2' X 2' CEILING TILES, ALIGN WITH
LIGHTS, DIFFUSERS, AND ARCHITECTURAL FEATURES.
1' - 0"
1' - 0"
FINISHED FLOOR
FIRE ALARM
CONTROL UNIT
OR
TRANSPONDER
OR
NETWORK NODE
BATTERY
CABINET
M A
X
REMOTE
POWER
SUPPLY
M A
X
DOCUMENT
CABINET
M A
X
NOTES:
1. THIS DETAIL IS DIAGRAMMATIC. PANELS MAY BE INSTALLED ABOVE AND BELOW EACH OTHER WHERE NECESSARY DUE TO LIMITED WALL SPACE.
S
M
IN
T
O T
O P
F
T
O
T O
H A
N D
L E
WALL
M
IN
A
N D
M
A X
REMOTE
POWER
SUPPLY
LOCAL
OPERATORS
CONSOLE
RATEDENGINEERING.COMRATEDENGINEERING.COMRATEDENGINEERING.COM
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing 93 OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :0
P
M
FIRE ALARM DETAILS
JCP 95DBN
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
05/16/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
FA500
SPUR #: 1791.06
1" = 1'-0" C2
FIRE ALARM DEVICE CEILING TILE INSTALLATION DETAIL
1" = 1'-0"
C5
FIRE ALARM EQUIPMENT MOUNTING HEIGHTS
No. REVISION DESCRIPTION DATE
A
B
C
D
2 5431 3.9
B.2
A.8
C.2
HAC
N3104
CONFERENCE
/ BREAK
ROOM
N3116
OFFICE
N3106
RESTROOM
N3117
RESTROOM
N3118
PIT
N3109
STEAM PIT
N3102
ELEC
N3107
ELECTRICAL
UTILITY
ROOM
N3108
OXYGEN
YARD
N3112
STORAGE
ROOM
N3103
CORRIDOR
N3105
STAIR
ENCLOSURE
N3119
BOILER AREA
N3101
GENERATORS
N3114
ELECTRICAL
SWITCHGEAR
N3113
CHILLERS
N3111
CONTROL
ROOM
N3115
RISER ROOM
N3110
D2
FX500
D4
FX500
TO REMOTE FDC.
SEE CIVIL SHEET
CU-101.
E
A
B
C
D
2 5431 3.9
B.2
A.8
C.2
SECURITY
N3204
CORRIDOR
N3206
TR
N3203
ELECTRICAL
AREA
N3201
EMERGENCY
PANELS
N3205
BOILER AREA
N3101
OXYGEN
YARD
N3112
COOLER
TOWERS &
PUMPS
N3202
FIRE SUPPRESSION
LEGEND
RISER
REMOTE FIRE DEPARTMENT CONNECTION - SIAMESE
TEST HEADER - WALL MOUNT
HAZARD CLASSIFICATION
HATCH LEGEND
LIGHT HAZARD
SPRINKLER: 0.1/1500 GPM/SF
HOSE: 100GPM FOR 30 MINUTES
ORDINARY HAZARD (GROUP 1)
SPRINKLER: 0.15/1500 GPM/SF
HOSE: 250GPM FOR 60 MINUTES
EXTRA HAZARD (GROUP 1)
SPRINKLER: 0.3/2500 GPM/SF
HOSE: 500GPM FOR 90 MINUTES
ORDINARY HAZARD (GROUP 2)
SPRINKLER: 0.2/1500 GPM/SF
HOSE: 250GPM FOR 90 MINUTES
NON-SPRINKLERED
1. SYSTEM DESCRIPTION
A. THE AUTOMATIC FIRE SUPPRESSION SYSTEMS IN THIS BUILDING
CONSIST AUTOMATIC WET PIPE SPRINKLER SYSTEMS.
2. PURPOSE OF PLANS
A. THESE PLANS ARE INTENDED TO DEMONSTRATE CRITERIA,
DEMONSTRATE CODE COMPLIANCE, AND BRIDGING TOWARDS
SUBSEQUENT DESIGN AND CONSTRUCTION SUBMITTALS.
B. THESE PLANS ARE NOT INTENDED TO BE USED FOR CONSTRUCTION.
C. THE CONTRACTOR MUST PERFORM THEIR OWN COORDINATED LAYOUT
WITH OTHER TRADES AS PART OF THE SHOP DRAWING PROCESS AS
FURTHER DETAILED IN THE SPECIFICATIONS.
D. MODIFICATIONS MADE BY THE CONTRACTOR RESULTANT FROM
COORDINATION, CALCULATIONS, OR CONTRACTOR ROUTING AND
INSTALLATION PREFERENCES MUST BE PERFORMED AT NO ADDITIONAL
COST TO THE OWNER.
E. THESE PLANS ARE NOT INTENDED TO SHOW ALL HANGERS,
COMPONENTS, ACCESSORIES, AND OTHER DETAILS WHICH WILL BE
DOCUMENTED IN THE CONTRACTOR'S SHOP DRAWINGS,
CALCULATIONS, AND PRODUCT DATA SELECTIONS.
F. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL MANUFACTURER AND
MODEL DATA INDICATED HEREIN IS A BASIS OF DESIGN AND IS NOT
SOLE-SOURCED. THE CONTRACTOR MAY SELECT THEIR OWN
MANUFACTURER AND MODEL, EXCEPT WHERE EXPLICITLY NOTED
OTHERWISE.
G. AS THE CONTRACTOR REVISES AND COORDINATES THEIR LAYOUT WITH
OTHER TRADES, THE NUMBER OF TRAPPED SECTIONS MUST BE AS
MINIMAL AS FEASIBLE.
3. APPLICABLE CRITERIA
A. SUBSEQENT DESIGN SHALL INCORPORATE THE LATEST AND GREATEST
CRITERIA AT TIME DESIGN IS AWARED PER ADOPTED VA STANDARDS.
a. INTERNATIONAL BUILDING CODE, 2022
b. NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS, 2022
c. NFPA 30 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE, 2021
d. NFPA 55 COMPRESSED GASES AND CRYOGENIC FLUIDS, 2023
e. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2022
f. NFPA 70 NATIONAL ELECTRICAL CODE, 2023
g. NFPA 99 HEALTH CARE FACILITIES CODE, 2021
h. NFPA 101 LIFE SAFETY CODE, 2021
i. VA FIRE PROTECTION DESIGN MANUAL - 2021 EDITION
4. SPECIFICATIONS
A. REFER TO PROJECT SPECIFICATIONS FOR MANY QUALIFICATIONS,
SUBMITTAL, PRODUCT, INSTALLATION, TESTING, AND DOCUMENTATION
CRITERIA. THE PROJECT SPECIFICATIONS ARE WRITTEN WITH INTENT
AND WILL BE ENFORCED.
B. SPECIFICATION CRITERIA STATED ON THESE PLANS IS INTENDED TO
SUMMARIZE MAJOR SYSTEM CRITERIA. REFER TO SPECIFICATIONS FOR
ALL DETAILS.
5. BUILDING BASICS
A. INFORMATION STATED HEREIN IS FOR REFERENCE ONLY.
B. THE BUILDING IS A COMBINATION OF SPECIAL PURPOSE INDUSTRIAL
AND NEW BUSINESS OCCUPANCY.
C. THE BUILDING IS TWO STORIES ABOVE GRADE PLUS A ROOFTOP
PENTHOUSE WHICH IS NOT CONSIDERED A THIRD STORY.
D. THE BUILDING CONSTRUCTION TYPE IS NONCOMBUSTIBLE.
6. INSTALLATION
A. ALL COMPONENTS MUST BE COORDINATED WITH OTHER TRADES AND
INSTALLED PARALLEL OR PERPINDICULAR TO THE BUILDING
STRUCTURE.
B. SYSTEM INSTALLATION MUST BE PERFORMED IN A NEAT, WORKMAN-
LIKE MANNER.
C. ALL INSTALLATION AND TESTING MUST COMPLY WITH THE APPLICABLE
CRITERIA AND MANUFACTURER'S INSTRUCTIONS.
D. THE SYSTEM MUST BE TURNED OVER TO THE OWNER IN LIKE-NEW
CONDITION. THE CONTRACTOR MUST REPLACE DAMAGED
COMPONENTS WITH NEW COMPONENTS IF DAMAGED BEFORE
TURNOVER.
E. ENSURE STANDARD RESPONSE SPRINKLERS ARE UTILIZED AS
REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL.
F. ALL PIPING TO BE PAINTED RED.
G. ALL SPRINLKER SUBJECT TO MECHANICAL DAMAGE SHALL BE PROVIDED
WITH GUARDS/CAGES.
7. AUTOMATIC AIR VENTS
A. THE CONTRACTOR MUST INCLUDE AT LEAST TWO AUTOMATIC AIR
VENTS PER SYSTEM PER FLOOR.
B. THE VENTS MUST BE LOCATED TO MAXIMIZE THE VOLUME OF PIPING
VENTED.
RATEDENGINEERING.COMRATEDENGINEERING.COMRATEDENGINEERING.COM
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #94 OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :4
P
M
FIRE SUPPRESSION FLOOR PLAN
JCP 95DBN
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
05/16/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
FX101
SPUR #: 1791.06
No. REVISION DESCRIPTION DATE
1/8" = 1'-0" F1
FIRE SUPPRESSION PLAN - LEVEL 1
1/8" = 1'-0"
F5
FIRE SUPPRESSION PLAN - MEZZANINE
0 4' 8' 16'
N
FIRE SUPPRESSION GENERAL NOTES
2' - 0"
2' - 0"
1' - 0"
1' - 0"
DETAIL NOTES:
1. INSTALL SPRINKLERS IN 2' X 4' AND 2' X 2' CEILING TILES AS
INDICATED ABOVE.
2. ALIGN SPRINKLERS AMONGST ADJACENT CEILING TILES
WHERE IN THE SAME FIELD OF VIEW INCLUDING THROUGH
OPEN DOORS AND GLASS PARTITIONS.
3. WHERE SPRINKLERS ARE INSTALLED IN CEILINGS OTHER
THAN 2' X 4' AND 2' X 2' CEILING TILES, ALIGN WITH LIGHTS,
DIFFUSERS, AND ARCHITECTURAL FEATURES.
LEVEL 1
0' - 0"
A
D4
FX500
LEVEL 1
0' - 0"
D2
FX500
RATEDENGINEERING.COMRATEDENGINEERING.COMRATEDENGINEERING.COM
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #95 OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:3 :4
P
M
FIRE SPRINKLER DETAILS
JCP 95DBN
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
05/16/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
FX500
SPUR #: 1791.06
1" = 1'-0" B6
FIRE SPRINKLER CEILING TILE INSTALLATION DETAIL
No. REVISION DESCRIPTION DATE
1/2" = 1'-0" D2
SECTION 1 - TYPICAL WET RISER
1/2" = 1'-0"
D4
SECTION 2 - TYPICAL WET RISER
KEYNOTES
1 TO FIRE WATER TIE IN. COORDINATE WITH CIVIL
2 TO FIRE SPRINKLER SYSTEM
3 WATERFLOW SWITCH
4 EXTERIOR WATERFLOW HORN/STROBE
5 FORWARD FLUSH TEST HEADER WITH (3) 2-1/2" HOSE VALVES
6 DOUBLE-CHECK BACKFLOW PREVENTER
7 CHECK VALVE
8 BUTTERFLY VALVE - SUPERVISED CLOSED
9 EXTERIOR DRAIN
10 MAIN DRAIN
11 WATERFLOW TEST VALVE WITH DRAIN TO EXTERIOR
12 TO REMOTE FIRE DEPARTMENT CONNECTION. COORDINATE WITH CIVIL.
File details come from the government source that posted it. Updated .