Design Drawings Architectural_654-212.pdf
PDF 14 MB Posted
- Solicitation number
- QSE--36C10F24R50000
About this file
This document appears to be design drawings for a federal contract opportunity to design and build a new Central Utilities Plant (CUP) for the VA Sierra Nevada Health Care System in Reno, Nevada. The solicitation number is QSE--36C10F24R50000, and the opportunity is for a Design Build contract to replace the existing seismically deficient boiler plant, Building 8.
The key scope of work includes: 1) Improvements to an existing gravel parking lot, 2) Construction of an approximately 11,000 GSF CUP building to house new boilers, chillers, cooling towers, and a bulk oxygen system, 3) Testing and final connection of the new CUP to existing utility feeds, 4) Demolition of the existing Boiler Plant, 5) Conversion of the Boiler Plant site to a new paved and lighted parking lot. The contractor will be responsible for all design and construction activities, and must be properly licensed in the State of Nevada. The final design and construction must comply with VA Technical Design Library requirements. No deviations will be allowed without prior approval from the VA Contracting Officer.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. DEPARTMENT OF VETERANS AFFAIRS
ARCHITECTURAL 30x42 DRAWINGS
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
VA PROJECT NUMBER: 654-212
[04] ARCHITECTURAL
33 AS000D ARCHITECTURAL SITE PLAN - DEMO
34 AS000 ARCHITECTURAL SITE PLAN - REFERENCE
35 AS002D ARCHITECTURAL SITE PLAN - NEW
36 AE021 PARTITION TYPES
37 AE101 REFERENCE PLANS
38 AE111 DIMENSION PLANS
39 AE121 ROOF PLAN
40 AC131 REFLECTED CEILING PLANS
41 AE201 BUILDING ELEVATIONS
42 AE301 BUILDING SECTIONS
43 AE311 WALL SECTIONS
44 AE401 INTERIOR ELEVATIONS AND ENLARGED PLANS
45 AE402 INTERIOR ELEVATIONS AND ENLARGED PLANS
46 AE403 INTERIOR DETAILS - TYP.
47 AE601 DOOR SCHEDULE
48 AF701 FINISH FLOOR PLANS
49 AE901 3D BUILDING SECTION VIEWS
50 AE902 PERSPECTIVE VIEWS
CENTRAL UTILITY PLANT
BELLI DR.
K
IR
M A
N A
V E
EXISTING
BOILER PLANT
EXISTING YARD
TO BE
DEMOLISHED
AND PREPARED
FOR NEW
CONSTRUCTION
EXISTING
PARKING
GARAGE
BUILDING 8
MAINTENANCE
BUILDING
2.05
EXISTING YARD
TO BE
DEMOLISHED
AND PREPARED
FOR NEW
CONSTRUCTION
K
IR
M A
N A
V E
E TAYLOR ST.
2.05 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:5 :4
A
M
ARCHITECTURAL SITE PLAN - DEMO
NR 33 95-
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AS000D
SPUR #: 1791.06
N
1/16" = 1'-0"
SITE PLAN - DEMOLITION1
N
1/16" = 1'-0"
SITE PLAN - DEMOLITION2
KEYNOTE LEGEND
2.05 EXISTING PARKING TO BE DEMOLISHED AND PREPARED
FOR NEW CONSTRUCTION
No. REVISION DESCRIPTION DATE
MATCH SHEET 2
MATCH SHEET 1
M S P
MSP
WMH
WMH
ICB
ICB
ICB
W
W
BELLI DR.
K
IR
M A
N A
V E
EXISTING
PARKING
GARAGE
79'-0"
EXISTING VA
HOSPITAL
EXISTING VA
HOSPITAL
AS002D
NEW CUP
BUILDING 16
AS002D
E TAYLOR ST.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:4 :5
A
M
ARCHITECTURAL SITE PLAN -
REFERENCE
CAB 34 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AS000
SPUR #: 1791.06
N
1/32" = 1'-0"
SITE PLAN1
BELLI DR.
K
IR
M A
N A
V E
EXISTING
PARKING
GARAGE
79'-0"
PARKING
PARKING
RESTRICTED
PARKING
NEW CUP
BUILDING 16
10.30
10.31
8.94
10.32
10.32
8.94
MAINTENANCE
BUILDING
FF=4458.51
K
IR
M A
N A
V E
E TAYLOR ST.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:3 :2
A
M
ARCHITECTURAL SITE PLAN - NEW
CAB 35 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AS002D
SPUR #: 1791.06
N
1/16" = 1'-0"
SITE PLAN1
N
1/16" = 1'-0"
SITE PLAN2
KEYNOTE LEGEND
8.94 PEDESTRIAN GATE WITH PACS CONTROLLED ACCESS
10.30 SLIDING ANTI-CLIMB / ANTI-RAM SECURITY GATE
10.31 PERIMETER FENCING
10.32 DROP ARM GATE
C 4
FRAMING UNIT SIZE CATEGORY
BASIC PARTITION ASSEMBLY CATEGORY
PARTITION TAG:
UNDERSIDE OF STRUCTURE
CONCRETE MASONRY UNIT
(REF: STRUCTURAL)
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
DIM DIMDIM DIM
WIDTH
ACTUAL
BASE
PLAN
HEAD
METAL STUD U-TRACK (TOP AND BOTTOM)
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
5/8"
WIDTH
STUD 5/8"
BASE
PLAN
HEAD
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
5/8" GYPSUM BOARD EACH SIDE
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE - (REF: ROOM FINISH SCHEDULE)
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
BATT INSULATION WHERE
SPECIFIED IN SCHEDULE
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
METAL RUNNER (FASTENED 24" O.C. MAX)
WALL FINISH (REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
5/8"TYPE X
5/8"TYPE X
2 LAYERS "TYPE X" GYPSUM BOARD
METAL RUNNER "J"
(FASTENED 24" O.C. MAX)
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
CH STUD PER SCHEDULE
ROOM SIDE SHAFT SIDE
1" TYPE X GYPSUM BOARD LINER PANEL
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
5/8"TYPE X
WIDTH
STUD 5/8"TYPE X
5/8" "TYPE X" GYPSUM
BOARD EACH SIDE
FINISH FLOOR
(REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
METAL STUD PER SCHEDULE
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
1"TYPE X
FIN FLOOR- (REF: ROOM FINISH SCHEDULE)
BASE - (REF: ROOM FINISH SCHEDULE)
ROOM SIDE SHAFT SIDE
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
ACTUAL
5/8"TYPE X
5/8"TYPE X
WIDTH
STUD
5/8"TYPE X
5/8"TYPE X
2 LAYERS "TYPE X" GYPSUM
BOARD EACH SIDE
FINISH FLOOR
(REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
BATT INSULATION
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
LINE OF CEILING (REF: RCP FOR HEIGHT & TYPE)
WALL FINISH (REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
5/8"
WIDTH
STUD VARIES
WIDTH
STUD 5/8"
5/8" GYPSUM BOARD EACH SIDE
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE - (REF: ROOM FINISH SCHEDULE)
METAL STUD PER SCHEDULE
BATT INSULATION WHERE SPECIFIED
IN SCHEDULE
METAL STUD PER SCHEDULE
FIRE RATED SEALANT AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
BATT INSULATION
FIRE RATED SEALANT
AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
ACOUSTICAL SEALANT AROUND
PERIMETER (INSULATED WALLS)
ACOUSTICAL SEALANT AROUND
PERIMETER (INSULATED WALLS)
NOTE: INSULATED WALLS AROUND
RESTROOMS EXTEND OUTSIDE LAYER
OF GYPSUM BOARD TO DECK
ACOUSTICAL SEALANT AROUND
PERIMETER (INSULATED WALLS)
WIDTH
STUD5/8"
WIDTH
ACTUAL
BATT INSULATION WHERE
SPECIFIED IN SCHEDULE
DIM DIMDIM DIMDIM DIM
DIM DIMDIM DIM
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
DIM DIM DIM DIM
BASE
PLAN
HEAD
DIM DIM
WIDTH
ACTUAL
5/8"
WIDTH
STUD 5/8"
1"TYPE XWIDTH
STUD
5/8"TYPE X
WIDTH
STUD
CH STUD PER SCHEDULE
METAL STUD PER SCHEDULE METAL STUD PER SCHEDULE
5/8" GYPSUM WALLBOARD
METAL STUD U-TRACK (TOP AND BOTTOM)
METAL STUD U-TRACK (TOP AND BOTTOM)
METAL STUD U-TRACK (TOP AND BOTTOM)
1" GYPSUM SHAFT LINER
METAL STUD U-TRACK (TOP AND BOTTOM)
UNDERSIDE OF STRUCTURE
LINE OF CEILING (REF: RCP FOR HEIGHT & TYPE)
WALL FINISH (REF: ROOM FINISH SCHEDULE)
5/8" GYPSUM BOARD EACH SIDE
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
METAL STUD PER SCHEDULE
FIRE-RATED SEALANT AROUND PERIMETER
METAL STUD U-TRACK (TOP AND BOTTOM)
BATT INSULATION
5/8" TYPE X GYPSUM BOARD
UNDERSIDE OF STRUCTURE
CONCRETE MASONRY UNIT
(REF: STRUCTURAL)
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
DIM DIM
WIDTH
ACTUAL
UNDERSIDE OF STRUCTURE
CONCRETE MASONRY UNIT
(REF: STRUCTURAL)
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
1. PAINT CONTINUOUS 4" TALL, STENCILED LETTERS, ABOVE CEILING, ON BOTH SIDES OF ALL FIRE AND
SMOKE WALLS DESIGNATING THE PARTITION RATING INDICATED ON THE LIFE SAFETY PLAN.
2. REFER TO FINISH SCHEDULE AND INTERIOR ELEVATIONS FOR LOCATIONS OF ALL WALL TILE.
PROVIDE AND INSTALL CEMENTITIOUS BACKER BOARD IN LIEU OF GWB AT ALL SCHEDULED TILE LOCATIONS. UNLESS NOTED OTHERWISE, TILE SHALL BE INSTALLED PER TILE COUNCIL OF AMERICA LATEST STANDARDS FOR EACH TYPE OF BACKING MATERIAL REPRESENTED IN WALL/PARTITION.
3. ALL SUSPENDED WALLS AND PARTITIONS SHALL HAVE GYPSUM BOARD WHICH EXTENDS A MINIMUM
OF 6" ABOVE THE SUSPENDED CEILING UNLESS SHOWN AND/OR NOTED OTHERWISE BY THE
ARCHITECT.
4. REFER TO STRUCTURAL DRAWINGS FOR ALL LOAD BEARING WALL CONDITIONS IN REGARDS TO
STRUCTURAL REQUIREMENTS.
5. "ALIGN" MEANS SIMILAR COMPONENTS OF CONSTRUCTION, E.G. WALLS, JAMBS, ETC. SHALL ALIGN
ACROSS VOIDS AND JOINTS.
6. PARTITIONS SHALL BE CONTINUOUS OVER DOORS SAME ADJACENT WALLS (UNLESS NOTED
OTHERWISE) WHERE DRYWALL CONTINUES ABOVE CEILING AND ABOVE THE CEILING LEVEL UP TO
THE STRUCTURE ABOVE. ALL GYPSUM BOARD RETURNS SHALL HAVE CORNER BEADS MINIMUM
FLOOR TO CEILING. ALL PENETRATIONS IN DRYWALL CONSTRUCTION ABOVE FINISHED CEILING SHALL BE EFFECTIVELY SEALED TO PREVENT SOUND LEAKAGE AND FIRE STOPPING TAPE/CAULK AT ALL
RATED PARTITIONS.
7. ALL MECHANICAL CHASES AND OTHER NOTED CHASES ARE TO EXTEND UP TO THE UNDERSIDE OF THE DECK STRUCTURE ABOVE. ALL PLUMBING CHASES UNLESS OTHERWISE NOTED, SHALL EXTEND
ABOVE THE HIGHEST ADJOINING CEILING AND BE BRACED TO STRUCTURE.
8. ALL CONSTRUCTION DESIGNATED TO BE SUPPORTED BY ROOF STRUCTURE SHALL BE SUPPORTED
BY TOP CHORD OF STRUCTURAL JOISTS AND NOT FROM THE METAL DECK.
9. COORDINATE WITH MILLWORK DRAWINGS FOR PLACEMENT OF BLOCKING IN WALLS/PARTITIONS. ALL
WOOD BLOCKING IS TO BE FIRE RETARDANT TREATED.
10. IMPACT RESISTANT GYPSUM BOARD, WHERE NOTED, IS OPTIONAL ABOVE 8' AFF AND BEHIND
LOCKERS.
11. SEAL THE TOP AND BOTTOM OF WALL AS WELL AS ALL PENETRATIONS WHERE SMOKE PARTITIONS
ARE DESIGNATED ON THE LIFE SAFETY PLAN TO ELIMINATE THE PASSAGE OF SMOKE.
12. USE DEFLECTION TRACKS WHERE STUD WALLS ATTACH DIRECTLY TO METAL DECK.
GENERAL PARTITION NOTES
UNDERSIDE OF STRUCTURE
FIRE RATED SEALANT AROUND PERIMETER
DIM DIM
DEFLECTION TRACK WHERE NEEDED
TYPICAL DEFLECTION TRACK
*FIRESTOP ALL PENETRATIONS
WALL PRIORITY PLAN & LEGEND
2- H
R R
A T
E D
W A
LL
NON-RATED
WALL
RATED WALL
N O
N -R
A T
E D
W
A
LL
1-HR RATED
WALL
2-HR RATED
WALL
1-HR RATED
WALL
ONE (1) LAYER
OF GYP. BD. AT
1-HR RATED
WALL
HOLLOW METAL FRAME
JAMB STUDS AS
REQUIRED
HIGHER PRIORITY WALL
METAL STUDS PER
WALL TYPE
TWO HOUR FIRE & SMOKE WALL PRIORITY 1 (HIGHEST)
TWO HOUR FIRE WALL PRIORITY 2
TWO HOUR SHAFT WALL PRIORITY 2
ONE HOUR FIRE & SMOKE WALL PRIORITY 3
ONE HOUR FIRE WALL PRIORITY 4
NON-RATED WALL PRIORITY 5 (LOWEST)
2" M
A X
2"MAX.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :0
A
M
PARTITION TYPES
CAB 36 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AE021
SPUR #: 1791.06
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
A1 NON-INSULATED
5/8" GYPSUM BOARD ONE SIDE 7/8" HAT CHANNEL
SPACED AT 16" O.C.
1 1/2" --
A2 NON-INSULATED
5/8" GYPSUM BOARD ONE SIDE OF 2 1/2" METAL STUD
AT 16" O.C.
3 1/8" <varies>
A3 NON-INSULATED
5/8" GYPSUM BOARD ONE SIDE OF 3 5/8" METAL STUD
AT 16" O.C.
4 1/4" --
A6 NON- INSULATED
5/8" GYPSUM BOARD ONE SIDE OF 6" METAL STUD AT
16" O.C.
6 5/8" --
B2 INSULATED
5/8" GYPSUM BOARD ONE SIDE OF 2 1/2" METAL STUD
AT 16" O.C. W/ BATT INSULATION
3 1/8" --
B3 INSULATED
5/8" GYPSUM BOARD ONE SIDE OF 3 5/8" METAL STUD
AT 16" O.C. W/ BATT INSULATION
4 1/4" --
B6 INSULATED
5/8" GYPSUM BOARD ONE SIDE OF 6" METAL STUD AT
16" O.C. W/ BATT INSULATION
6 5/8" --
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
C2 NON-INSULATED
5/8" GYPSUM BOARD EACH SIDE OF 2 1/2" METAL STUD
AT 16" O.C.
3 3/4" --
C3 NON-INSULATED
5/8" GYPSUM BOARD EACH SIDE OF 3 5/8" METAL STUD
AT 16" O.C.
4 7/8" --
C6 NON-INSULATED
5/8" GYPSUM BOARD EACH SIDE OF 6" METAL STUD AT
16" O.C.
7 1/4" --
D2 INSULATED
5/8" GYPSUM BOARD EACH SIDE OF 2 1/2" METAL STUD
AT 16" O.C. W/ BATT INSULATION
3 3/4" --
D3 INSULATED
5/8" GYPSUM BOARD EACH SIDE OF 3 5/8" METAL STUD
AT 16" O.C. W/ BATT INSULATION
4 7/8" --
D6 INSULATED
5/8" GYPSUM BOARD EACH SIDE OF 6" METAL STUD AT
16" O.C. W/ BATT INSULATION
7 1/4" --
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
E3 CARRIER
5/8" GYPSUM BOARD ONE SIDE OF (2) 3 5/8" METAL
STUD AT 16" O.C. WALLS W/ BATT INSULATION ONE
SIDE
1'-8" --
E6 CARRIER
5/8" GYPSUM BOARD ONE SIDE OF (2) 6" METAL STUD
AT 16" O.C. WALLS W/ BATT INSULATION
2'-0 3/4" --
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
F3 1 HR (U419)
5/8" TYPE X GYPSUM BOARD EACH SIDE OF 3 5/8"
METAL STUD AT 16" O.C.
4 7/8" 48 STC
F6 1 HR (U419)
5/8" TYPE X GYPSUM BOARD EACH SIDE OF 6" METAL
STUD AT 16" O.C.
7 1/4" 48 STC
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
G2 1 HR (U415/U469)
5/8" TYPE X GYPSUM BOARD ONE SIDE & 1" TYPE X
GYPSUM BOARD OPPOSITE SIDE OF 2 1/2" CH METAL
STUD AT 16" O.C. W/ BATT INSULATION
3 1/8" --
G4 1HR (U415/U438)
5/8" TYPE X GYPSUM BOARD ONE SIDE & 1" TYPE X
GYPSUM BOARD OPPOSITE SIDE OF 4" CH METAL STUD
AT 16" O.C. W/ BATT INSULATION
4 5/8" 45 STC
G6 1 HR (U415/U469)
5/8" TYPE X GYPSUM BOARD ONE SIDE & 1" TYPE X
GYPSUM BOARD OPPOSITE SIDE OF 6" CH METAL STUD
SPACED AT 16" O.C. W/ BATT INSULATION
6 5/8" 45 STC
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
H3 1 HR / SMOKE
5/8" TYPE X GYPSUM BOARD ON EACH SIDE OF 3 5/8"
METAL STUD AT 16" O.C.
4 7/8" 45 STC
H6 1 HR / SMOKE
5/8" TYPE X GYPSUM BOARD ON EACH SIDE OF 6"
METAL STUD AT 16" O.C.
7 1/4" 45 STC
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
J2 2 HR (U411)
2 LAYERS 5/8" TYPE X GYPSUM BOARD EACH SIDE OF 2
1/2" METAL STUD AT 16" O.C.
5" 51 STC
J3 2 HR (U404)
2 LAYERS 5/8" TYPE X GYPSUM BOARD EACH SIDE OF 3
5/8" METAL STUD AT 16" O.C.
6 1/8" 51 STC
J6 2 HR (U404)
2 LAYERS 5/8" TYPE X GYPSUM BOARD EACH SIDE OF 6"
METAL STUD AT 16" O.C.
8 1/2" 51 STC
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
K2 2 HR (U415/U438)
2 LAYERS 1/2" TYPE X GYPSUM BOARD ONE SIDE & 1"
TYPE X GYPSUM BOARD ONE SIDE OF 2 1/2" CH METAL
STUD AT 16" O.C.
3 1/2" 47 STC
K4 2 HR (U415/U438)
2 LAYERS 1/2" TYPE X GYPSUM BOARD EACH SIDE OF 4"
CH METAL STUD AT 16" O.C.
5" 47 STC
K6 2 HR (U415)
2 LAYERS 5/8" TYPE X GYPSUM BOARD EACH SIDE OF 4"
CH METAL STUD AT 16" O.C.
7 1/4" 47 STC
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
L8 NON RATED
1 WYTHE 8" CONCRETE MASONRY UNITS. EXTEND
FROM FINISH FLOOR TO UNDERSIDE OF STRUCTURE
ABOVE.
8" --
L12 NON RATED
1 WYTHE 12" CONCRETE MASONRY UNITS. EXTEND
FROM FINISH FLOOR TO UNDERSIDE OF STRUCTURE
ABOVE.
1'-0" --
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
M8 1 HR
1 WYTHE 8" CONCRETE MASONRY UNITS. EXTEND
FROM FINISH FLOOR TO UNDERSIDE OF STRUCTURE
ABOVE.
8" --
No. REVISION DESCRIPTION DATE
TYPE MARK WALL TYPE DESCRIPTION WIDTH MIN. STC
N8 2 HR (U913)
1 WYTHE 8" CONCRETE MASONRY UNITS. EXTEND
FROM FINISH FLOOR TO UNDERSIDE OF STRUCTURE
ABOVE.
8" --
N12 2 HR (U913)
1 WYTHE 12" CONCRETE MASONRY UNITS. EXTEND
FROM FINISH FLOOR TO UNDERSIDE OF STRUCTURE
ABOVE.
1'-0" --
UP
DN
DN
1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT
WALL UNLESS NOTED OTHERWISE.
2. ALL WALLS ARE TYPE L12 PARTITIONS UNLESS OTHERWISE NOTED. REFER TO PARTITION TYPE
SHEET FOR WALL TYPES.
3. REFER TO DOOR SCHEDULE & DETAILS SHEET (41-AS-601) FOR DOOR INFORMATION.
4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.
5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW TOLERANCE
FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.
6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.
GENERAL PLAN NOTES
E
A
B
C
D
2 543
AE201
AE201
AE201
AE201
1298 SF
CHILLERS
N3111
194 SF
STEAM PIT
N3102
2529 SF
BOILER AREA
N3101
507 SF
ELECTRICAL
UTILITY ROOM
N3108
AE301
AE301
AE301
AE301
137 SF
OFFICE
N3106
804 SF
CONTROL
ROOM
N3115
587 SF
GENERATORS
N3114
296 SF
OXYGEN YARD
N3112
131 SF
STORAGE
ROOM
N3103
3.9
369 SF
ELECTRICAL
SWITCHGEAR
N3113
59 SF
RISER ROOM
N3110
71 SF
RESTROOM
N3117
72 SF
RESTROOM
N3118
193 SF
CONFERENCE /
BREAK ROOM
N3116
66 SF
HAC
N3104
147 SF
CORRIDOR
N3105
87 SF
ELEC
N3107
62 SF
PIT
N3109
B.2
A.8
C.2
N
N3111
N
A
N
B
N
C
N
A
N
N3117
N3118
N
B
N
B
N3114A
N
B
N3101A
N3101BN3101CN3101D
N3103
N
N
AE401
N3111A N3111B N3112
AE311
AE311
FEC
N
AE401
N3105
AE402
AE311
N3113A
FEC
F E
C
23.05 23.05 23.05 23.05
23.0423.04 23.04
23.06
23.09
26.06
26.06
26.05
26.05
23.10
23.10
23.10
23.10
23.10
23.10
23.1023.10
26.07
23.10
23.10
5.21
7' -1
1/
E
A
B
C
D
2 543
AE201
AE301
AE301
AE301
AE301
3.9
1629 SF
COOLER
TOWERS &
PUMPS
N3202
516 SF
EMERGENCY
PANELS
N3205
1357 SF
ELECTRICAL
AREA
N3201
178 SF
TR
N3203
100 SF
SECURITY
N3204
254 SF
CORRIDOR
N3206
B.2
A.8
C.2
N3201A
N3206
AE201
AE201
AE201
BOILER AREA
N3101
AE311
AE311
1.02
1.02
F E
C
N
C
N
D
AE311
N
A
N3203
N
N3205
N3202
N
B
N3207
F E
C
7.88
23.08 23.08
23.04 23.04 23.04
26.07
26.07
26.07
5.30
26.07
26.07
26.07
26.07
23.10
23.06
5.18
5.18
NEW 1 HOUR FIRE RATED WALLS
NEW 2 HOUR FIRE RATED WALLS
NEW NON-RATED WALLS
PARTITION LEGEND
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :3
A
M
REFERENCE PLANS
CAB 37 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AE101
SPUR #: 1791.06
N
1/8" = 1'-0"
LEVEL 1 - REFERENCE PLAN1
KEYNOTE LEGEND
1.02 OPEN TO BELOW
5.18 METAL GUARDRAIL
5.21 METAL STAIR TREADS AND NOSINGS
5.30 WALL MOUNTED ROOF ACCESS LADDER WITH CAGE
7.88 ROOF WALK PADS
23.04 BOILER, SEE MECHANICAL DRAWINGS
23.05 CHILLER, SEE MECHANICAL DRAWINGS
23.06 STEAM TRAP, SEE MECHANICAL DRAWINGS
23.08 COOLER TOWER, SEE MECHANICAL DRAWINGS
23.09 VACUUM PUMP, SEE MECHANICAL DRAWINGS
23.10 MECHANICAL EQUIPMENT, SEE MECHANICAL DRAWINGS
26.05 GENERATOR, SEE ELECTRICAL DRAWINGS
26.06 SWITCHBOARD, SEE ELECTRICAL DRAWINGS
26.07 ELECTRICAL EQUIPMENT, SEE ELECTRICAL DRAWINGS
N
1/8" = 1'-0"
MEZZANINE - REFERENCE PLAN2
UPDN
DN
1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT
WALL UNLESS NOTED OTHERWISE.
2. ALL WALLS ARE TYPE L12 PARTITIONS UNLESS OTHERWISE NOTED. REFER TO PARTITION TYPE
SHEET FOR WALL TYPES.
3. REFER TO DOOR SCHEDULE & DETAILS SHEET (41-AS-601) FOR DOOR INFORMATION.
4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.
5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW TOLERANCE
FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.
6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.
GENERAL PLAN NOTES
E
A
B
C
D
2 543
4'
-0
2' -0
'-3
'-9
'-6
'-6
2'
-0
75'-0"
2'-0" 14'-6" 26'-4" 18'-8" 15'-6" 2'-0"
OXYGEN YARD
N3112
STORAGE
ROOM
N3103
ELECTRICAL
UTILITY ROOM
N3108
CHILLERS
N3111
BOILER AREA
N3101
STEAM PIT
N3102
137 SF
OFFICE
N3106
GENERATORS
N3114
CONTROL
ROOM
N3115
RISER ROOM
N3110
3.9
CONFERENCE /
BREAK ROOM
N3116
RESTROOM
N3117
RESTROOM
N3118
66 SF
HAC
N3104
ELEC
N3107
CORRIDOR
N3105
PIT
N3109
ELECTRICAL
SWITCHGEAR
N3113
B.2
A.8
C.2
20'-8"
21'-6"
17'-10"17'-0"
8'-4"
8' -1
7'
-8
6'-4" 10'-6"
'-8
8'
-8
'-4
'-6
/2
7' -8
/2
8' -7
8'
-4
/2
'-1
3'-10" 8'-11"
4' -0
4'
-0
15'-2"
'-1
1/
2"
'-9
10'-4"
'-2
/8
'-6
/1 6"
7'-0"
2' -1
4'
-0
'-1
/2
'-2
2'-4"G2
G2
G2 G2
1' -1
/2
1'-6"
8"
1'-0"
1'-10"
9' -7
5/
1' -2
1 2 3 4 5
A
B
C
D
E
A.8
3.9
B.2
C.2
C.5
N8
L8
L8
L8
L8L8
M8
N8 L8
L8
L8
L8
L8
L8
N8
1.01
1.01
6'-5"
2' -1
/2
EQ EQ
10"7'-11"
3'-1" 3'-1"
8' -0
12'-10"
'-0
/1
6"
14'-10"
5'-7"
3'-1"
10'-4"
6' -0
1.01
1.01
21'-6"
1.01
N8
L8
N12
1'-0"
A2
A2
E
A
B
C
D
2 5431
75'-0"
2'-0" 14'-6" 26'-4" 18'-8" 15'-6" 2'-0"
4'
-0
2' -0
'-3
'-9
'-6
'-6
2'
-0
1357 SF
ELECTRICAL
AREA
N3201
COOLER
TOWERS &
PUMPS
N3202
516 SF
EMERGENCY
PANELS
N3205
3.9
178 SF
TR
N3203
100 SF
SECURITY
N3204
CORRIDOR
N3206
B.2
A.8
C.2
'-7
/2
34'-10" 6'-8" 14'-0"
'-1
1/
2"
2' -2
17'-2" 7'-0"
8' -0
'-8
/2
'-7
15'-6"
15'-2"
'-6
/2
16'-10"
'-1
1"
21'-6"
1'-4"
1' -7
7'-11" 6'-5"
2' -1
/2
1/
2"
1'-2"
1'-4"
1' -2
1' -2
1'-10"
L8
N8
D3
L8
N8
N8
1.01
1.01
1.
'-6
8' -6
7'-6 3/4"
1'-11"
NEW 1 HOUR FIRE RATED WALLS
NEW 2 HOUR FIRE RATED WALLS
NEW NON-RATED WALLS
PARTITION LEGEND
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :3
A
M
DIMENSION PLANS
CAB 38 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AE111
SPUR #: 1791.06
N
1/8" = 1'-0"
LEVEL 1 - DIMENSION PLAN1
KEYNOTE LEGEND
1.01 ALIGN
N
1/8" = 1'-0"
MEZZANINE - DIMENSION PLAN2
E
A
B
C
D
2 5431
2'-0" 14'-6" 26'-4" 18'-8" 15'-6" 2'-0"
75'-0"
'-0
'-0
'-3
'-9
'-6
'-6
'-0
3.9
AE311
1/4" / 1'-0"
/4
'-0
/4
/4
'-0
/4
/4
'-0
/4
1/4" / 1'-0"
/4
'-0
/4
/4
'-0
/4
/4
'-0
/4
7.87
5.30
7.88
23.01
23.01
23.01
23.0123.01 23.01
A
B
2 5431
2'-0" 14'-6" 26'-4" 18'-8" 15'-6" 2'-0"
75'-0"
'-0
'-3
AE301
AE301
AE311
1/4" / 1'-0"
/4
'-0
1/4" / 1'-0"
1/4" / 1'-0"
/4
'-0
1/4" / 1'-0" 1/4" / 1'-0"
AE311
7.88 5.30
ROOF WALKWAY PADX / XX ROOF PITCH
VENT PIPE EXHAUST FANVP EF
ROOF PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED.
1. ALL ROOFING WORK SHALL BE PERFORMED BY CONTRACTOR APPROVED BY EXISTING ROOF
MANUFACTURER TO PATCH AND REPAIR EXISTING ROOFING SYSTEM. CONTRACTOR SHALL BE
RESPONSIBLE FOR CHECKING EXISTING ROOFING SYSTEM WARRANTY STATUS AND FURNISHING A
COMPLETE ROOF REWORK, REPAIR AND PATCHING SYSTEM THAT WILL BE IN COMPLIANCE WITH ANY
EXISTING REMAINING ROOF WARRANTIES. NEW WORK SHALL PROVIDE FULL NEW SYSTEM
WARRANTIES.
2. PROVIDE PIPE BOOTS FLASHED INTO EXISTING ROOF AT ALL SANITARY VENT LINES, ELECTRICAL
SERVICE STANCHIONS AND WEATHERHEADS, CHILLED WATER LINES, AND OTHER MISCELLANEOUS
PENETRATIONS NOT ILLUSTRATED ON ARCHITECTURAL ROOF PLAN. SEE MECHANICAL.
3. SUPPORTS ALLOWED TO SIT DIRECTLY ON ROOF SYSTEM FOR PIPING AND SIMILAR SHALL BE
PURPOSE MADE BY MANUFACTURER FOR APPLICATION AND SUPPORT ROOF SYSTEM EXISTING AND
NEW WARRANTIES. SEE MECHANICAL.
4. PROVIDE ROOF WALKWAY FROM NEW ACCESS POINT TO NEW ROOFTOP MECHANICAL EQUIPMENT
WHERE INDICATED.
5. REFER TO ELECTRICAL DRAWINGS FOR LIGHTNING PROTECTION SYSTEMS.
GENERAL ROOF PLAN NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :0
A
M
ROOF PLAN
CAB 39 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AE121
SPUR #: 1791.06
KEYNOTE LEGEND
5.30 WALL MOUNTED ROOF ACCESS LADDER WITH CAGE
7.87 TPO ROOFING
7.88 ROOF WALK PADS
23.01 ROOFTOP MECH. EQUIPMENT, SEE MECHANICAL DRAWINGS
N
1/8" = 1'-0"
HIGH ROOF PLAN1
N
1/8" = 1'-0"
LOWER ROOF PLAN2
EXIT LIGHT
REFLECTED CEILING PLAN LEGEND
RETURN AIR GRILLE
SUPPLY AIR DIFFUSER
EXHAUST AIR GRILLE
SUSPENDED LIGHT FIXTURE
RE: ELECTRICAL
WALL MOUNTED VAPOR TIGHT
LIGHT FIXTURE, RE: ELECTRICAL
6" DIA. RECESSED CAN LIGHT
RE: ELECTRICAL
GYPSUM BOARD CEILING
1. ALL ROOMS ARE OPEN TO STRUCTURE UNLESS OTHERWISE NOTED ON PLAN.
2. ALL SURFACES OF FURRDOWNS TO BE PAINTED P1 U.N.O.
3. ALL EXPOSED CEILING STRUCTURE TO BE PAINTED P1 U.N.O.
GENERAL REFLECTED CEILING PLAN NOTES
E
A
B
C
D
2 5431
14'-6" 26'-4" 18'-8" 15'-6"
'-3
'-9
'-6
'-6
'-0
3.9
B.2
A.8
C.2
OXYGEN YARD
N3112
ELECTRICAL
SWITCHGEAR
N3113
GENERATORS
N3114
CONTROL
ROOM
N3115
CONFERENCE /
BREAK ROOM
N3116
RESTROOM
N3117
RESTROOM
N3118
ELECTRICAL
UTILITY ROOM
N3108
RISER ROOM
N3110
PIT
N3109
CHILLERS
N3111
OFFICE
N3106
ELEC
N3107
CORRIDOR
N3105
HAC
N3104
STEAM PIT
N3102
STORAGE
ROOM
N3103
BOILER AREA
N3101
2'-0" 2'-0"
75'-0"
AE311
AE311
4'-8" 10'-0" 10'-0" 10'-0" 10'-0" 7'-8"
'-7
/8
'-0
'-6
'-1
E Q
E Q
'-5
'-8
EQ EQ
7'-8"
'-0
'-1
4'-8"
4'-3" 7'-6" 4'-7"4 '-1
'-1
EQ EQ
EQ EQ
'-7
'-5
/2
'-0
'-8
3'-4"
'-0
'-0
'-7
/2
6'-9" 13'-0" 5'-4"
3'-9"
4'-10"
4'-6" 7'-10" 4'-10"
5'-4" 10'-4" 5'-6"
'-0
'-0
'-0
'-2
/8
7'-8" 8'-0" 5'-6"
'-6
8'-6"
9'-0"
9'-0"
E Q
E Q
EQ EQ
E Q
E Q
E Q
E Q
2'-5"
E Q
E Q
AE311
E
A
B
C
D
2 5431
75'-0"
2'-0" 14'-6" 26'-4" 18'-8" 15'-6" 2'-0"
'-0
'-3
'-9
'-6
'-6
3.9
TR
N3203
SECURITY
N3204
EMERGENCY
PANELS
N3205
ELECTRICAL
AREA
N3201
CORRIDOR
N3206
B.2
A.8
C.2
AE311
AE311
OXYGEN YARD
N3112
COOLER
TOWERS &
PUMPS
N3202
BOILER AREA
N3101
7'-6" 17'-0" 15'-6" 14'-9" 4'-7"
'-9
'-1
'-9
/2
'-9
/2
'-1
6'-6" 11'-6" 11'-0" 5'-6"
'-7
'-6
'-5
/2
'-4
EQ EQ
'-4
E Q
E Q
7'-7"
'-1
EQ EQ
E Q
E Q
EQ EQ
'-8
'-8
'-9
'-1
5'-2"
'-3
/2
'-9
7'-5" 7'-11"
AE311
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :5
A
M
REFLECTED CEILING PLANS
CAB 40 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AC131
SPUR #: 1791.06
N
1/8" = 1'-0"
LEVEL 1 - REFLECTED CEILING PLAN1
N
1/8" = 1'-0"
MEZZANINE - REFLECTED CEILING PLAN2
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
2 543
2'-0" 14'-6" 26'-4" 18'-8" 15'-6" 2'-0"
75'-0"
AE301
AE301
3.9
'-0
'-0
4.20
8.32 8.328.32
'-8
'-8
4.21
'-4
AE311
N3101D N3101C N3101B
26.04
26.04
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
E ABCD
104'-0"
2'-0" 29'-6" 21'-6" 26'-9" 26'-3" 2'-0"
AE301
AE301
B.2 A.8C.2
'-0
'-0
'-0
4.20
8.918.91
8.91
AE311
AE311
'-4
"4.21
4.21
N A
N A
N A
26.0426.04 4.21
4.21 4.21
'-8
'-8
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
EA B C D
104'-0"
2'-0" 26'-3" 26'-9" 21'-6" 29'-6" 2'-0"
AE301
AE301
B.2A.8 C.2
'-0
'-0
'-0
4.20
8.33
8.33
8.918.91
AE311
AE311
4.21
'-4
'-8
'-8
8.33
N
N
N C
N3201D
N3201Q N3201P
26.04
26.04
26.04
26.0426.04 13.10
'-6
26.04
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
25 4 3
2'-0"14'-6"26'-4"18'-8"15'-6"2'-0"
75'-0"
AE301
AE301
3.9
4.20
8.33
8.33
8.33
'-0
'-0
'-0
8.91 8.91 8.91 8.91 8.91 8.91
4.21
'-4
AE311
N
N T
N3111AN3111BN3112
26.04
26.04 26.04
26.04
'-8
'-8 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :3
A
M
BUILDING ELEVATIONS
CAB 41 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AE201
SPUR #: 1791.06
1/8" = 1'-0" 1/ AE101
ELEVATION - SOUTH11/8" = 1'-0" 1/ AE101
ELEVATION - EAST2
1/8" = 1'-0" 1/ AE101
ELEVATION - WEST31/8" = 1'-0" 1/ AE101
ELEVATION - NORTH4
KEYNOTE LEGEND
4.20 SMOOTH FACE CONCRETE MASONRY UNIT WALL
4.21 SPLIT FACE CONCRETE MASONRY UNIT WALL
8.32 BLAST RATED VERTICAL LIFT OVERHEAD DOOR
8.33 BLAST RATED OVERHEAD COILING DOOR
8.91 LOUVER
13.10 EXIT STAIR SECURITY ENCLOSURE
26.04 LIGHT FIXTURE, SEE ELECTRICAL DRAWINGS
MEZZANINE
15'-0"
ROOF
33'-0"
25 4 3 1
PIT
-10'-0"
AE301
AE301
BOILER AREA
N3101
3.9
ELECTRICAL
AREA
N3201
OFFICE
N3106
2'-0" 15'-6" 3'-2" 15'-6" 26'-4" 14'-6" 2'-0"
75'-0"
ELEC
N3107
CONTROL
ROOM
N3115
GENERATORS
N3114
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
2 5431
PIT
-10'-0"
AE301
AE301
ELECTRICAL
AREA
N3201
EMERGENCY
PANELS
N3205
CONTROL
ROOM
N3115
ELECTRICAL
UTILITY ROOM
N3108
3.9
TR
N3203
RESTROOM
N3117
CORRIDOR
N3206
2'-0" 14'-6" 26'-4" 15'-6" 3'-2" 15'-6" 2'-0"
75'-0"
AE311
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
EA B C D
PIT
-10'-0"
AE301
AE301
CONTROL
ROOM
N3115
CHILLERS
N3111
COOLER
TOWERS &
PUMPS
N3202
BOILER AREA
N3101
SECURITY
N3204
CORRIDOR
N3206
TR
N3203
B.2A.8 C.2
2'-0" 21'-3" 5'-0" 4'-6" 22'-3" 3'-6" 18'-0" 29'-6" 2'-0"
104'-0"
AE311
AE311
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
E ABCD
PIT
-10'-0"
AE301
AE301
BOILER AREA
N3101
CONTROL
ROOM
N3115
CHILLERS
N3111
COOLER
TOWERS &
PUMPS
N3202
C.22'-0" 29'-6" 21'-6" 26'-9" 26'-3" 2'-0"
TR
N3203
104'-0"
SECURITY
N3204
CORRIDOR
N3206 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :4
A
M
BUILDING SECTIONS
CAB 42 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AE301
SPUR #: 1791.06
1/8" = 1'-0" 1/ AE101
BUILDING SECTION 11
1/8" = 1'-0" 1/ AE101
BUILDING SECTION 44
1/8" = 1'-0" 1/ AE101
BUIDLING SECTION 22
1/8" = 1'-0" 1/ AE101
BUILDING SECTION 33
MEZZANINE
15'-0"
ROOF
33'-0"
4.21
8.91
4.20
8.91
OXYGEN YARD
N3112
CHILLERS
N3111
4.20
7.88
COOLER
TOWERS &
PUMPS
N3202
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
PIT
-10'-0"
4.20
4.21
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
TOP OF PARAPET
36'-8"
7.54
8.91
EMERGENCY
PANELS
N3205
4.20
4.21
GENERATORS
N3114
/2
/2
LEVEL 1
0"
MEZZANINE
15'-0"
ROOF
33'-0"
A
TOP OF PARAPET
36'-8"
"8.91
4.20
9.85
5.29
CHILLERS
N3111
4.21
/4
/8
/8
COOLER
TOWERS &
PUMPS
N3202
9.85
5.01 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :4
A
M
WALL SECTIONS
CAB 43 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AE311
SPUR #: 1791.06
1/2" = 1'-0" 1/ AC131
WALL SECTION AT OXYEGEN YARD11/2" = 1'-0"
WALL SECTION AT PIT21/2" = 1'-0" 1/ AC131
WALL SECTION AT GENERATORS3
KEYNOTE LEGEND
4.20 SMOOTH FACE CONCRETE MASONRY UNIT WALL
4.21 SPLIT FACE CONCRETE MASONRY UNIT WALL
5.01 STRUCTURAL STEEL. SEE STRUCT. DWG'S
5.29 METAL STUD FRAMING
7.54 SHEET METAL DOWNSPOUT
7.88 ROOF WALK PADS
8.91 LOUVER
9.85 STUCCO
1/2" = 1'-0"
WALL SECTION AT CHILLERS4
B
C
AE40111
RESTROOM
N3117
RESTROOM
N3118
AE401
AE401
N3117
N3118
CONFERENCE /
BREAK ROOM
N3116
N
3' -3
8'
-0
3' -4
'-9
'-3
7' -9
7'
-8
/2
'-3
'-0
/2
3'-10" 5'-6" 2'-9"
11'-1 3/8"
10.33
10.34
10.33
22.08
10.34
10.3410.34 22.06
22.06
22.06
11.05
11.04
10.3410.34
6' -0
6'
-0
22.09
22.09
10.07
10.07
10.36
10.38
10.38
10.36
10.37
10.36
10.37
10.37
L8
L8
L8
L8
L8
L8
12.20
10.38
PT3
PTB1
3'-0 1/2" 8'-2 1/2"
FV
11'-2 1/2"
F V
9' -0
8' -6
6"
1' -6
22.06
10.34
10.33
10.35
22.09
10.38
10.36
10.07
N
PT3
PTB1
6" 8'
-6
F V
9' -0
FV
7'-8 1/2"
22.06
10.37
PT3
PTB1
1'-6"
3' -0
3'
-6
3' -6
6" 8'
-6
F V
9' -0
FV
11'-2 1/2"
22.08
6' -6
10.34
PT3
PTB1
3'-3" 4'-5 1/2"
FV
7'-8"
6" 8'
-6
1' -6
10.33 10.34
22.09
F V
9' -0
PT2
PT3
PTB1
8'-2 1/2" 3'-0 1/2"
FV
11'-2 1/2"
6" 8'
-6
F V
9' -0
1' -6
10.33
10.35
22.06
10.34
22.09
10.38
10.36
10.07
PT3
PTB1
4'-5 3/4" 3'-2 7/8"
6" 8'
-6
1' -6
10.3310.34
22.09
PT2
F V
9' -0
FV
7'-9"
PT3
PTB1
8' -6
6"
FV
11'-2 1/2"
1'-6"
3' -6
3' -6
3'
-0
22.08
10.34
F V
6' -6
F V
9' -0
N
PT3
PTB1
F V
9' -0
6" 8'
-6
22.06
10.37
FV
7'-9" 3'-0"
2 EQ
5'-0" 3'-3"
FV
11'-3"
PL1
PL1
SS1
26.01
1.03
11.04
11.05
6.58
22.06
10.37
10.36
8" 3'
-0
2' -0
2'
-1 0"
8' -6
8" 1'
-1 0"
6' -0
8' -6
RB1
1. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATION OF MILLWORK.
2. COORDINATE LOCATION OF RECEPTACLES WITH ELECTRICAL DRAWINGS.
3. NO PLASTIC HARDWARE, BRACKETS OR CLIPS WILL BE ACCEPTED.
4. ALL DRAWERS SHALL BE ON HEAVY DUTY FULL EXTENSION METAL GLIDES WITH SOFT CLOSERS
UNLESS NOTED OTHERWISE.
5. USE CONCEALED CABINET HINGES UNLESS NOTED OTHERWISE.
6. MILLWORK SHALL MEET THE QUALITY AND GRADE CONSTRUCTION STANDARDS AS SPECIFIED IN
THE PROJECT MANUAL. STRICT ADHERENCE TO THIS STANDARD SHALL BE ENFORCED. ANY
DEVIATIONS FROM THIS BASE STANDARD, IF NOT SPECIFICALLY SHOWN WITHIN THESE DRAWINGS
WILL NOT BE ACCEPTED.
7. ALL SURFACES EXPOSED TO VIEW, INCLUDING THOSE SURFACES EXPOSED TO VIEW WHILE IN A
SEATED POSITION, SHALL HAVE A FINISHED SURFACE TO MATCH OTHER ADJACENT FINISHED
SURFACES.
8. ALL COUNTERTOPS TO BE CONSTRUCTED OF SOLID SURFACING WITH 1/4" RADIUS DOUBLE ROUND
UNLESS NOTED OTHERWISE.
9. ALL CABINETS TO HAVE CABINET LINERS ON ALL SURFACES.
10. FURNITURE AND APPLIANCES ARE SHOWN FOR SPACE PLANNING PURPOSES.
GENERAL MILLWORK NOTES
N
OFFICE
N3106
9'-8"
'-2
12.19
LVT1 (LUXURY VINYL TILE)
PT2 (PORCELAIN FLOOR TILE)
PT1 (PORCELAIN FLOOR TILE)
FINISH FLOOR PLAN LEGEND
SC1 (SEALED CONCRETE)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:0 :5
A
M
INTERIOR ELEVATIONS AND ENLARGED
PLANS
CAB 44 95NR
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AE401
SPUR #: 1791.06
N
1/4" = 1'-0" 1/ AE101
ENLARGED PLAN - RESTROOM N3117 AND N311813/8" = 1'-0" 1/ AE401
RESTROOM N3117 NORTH ELEVATION23/8" = 1'-0" 1/ AE401
RESTROOM N3117 EAST ELEVATION33/8" = 1'-0" 1/ AE401
RM N3117 SOUTH ELEVATION4
3/8" = 1'-0" 1/ AE401
RESTROOM N3117 WEST ELEVATION53/8" = 1'-0" 1/ AE401
RESTROOM N3118 SOUTH ELEVATION63/8" = 1'-0" 1/ AE401
WEST ELEVATION7
3/8" = 1'-0" 1/ AE401
NORTH ELEVATION93/8" = 1'-0" 1/ AE401
EAST ELEVATION103/8" = 1'-0" 1/ AE401
WEST ELEVATION11 1/4" = 1'-0" 1/ AE101
OFFICE ENLARGED PLAN8
KEYNOTE LEGEND
1.03 OPEN TO STRUCTURE
6.58 SLOPE TOP OF MILLWORK
10.07 TOILET TISSUR ROLL DISPENSER, SURFACE MOUNTED, CONTRACTOR PROVIDED / CONTRACTOR
INSTALLED
10.33 ABA SHOWER STALL BENCH, CONTRACTOR PROVIDED / CONTRACTOR INSTALLED
10.34 1-1/4" DIA. GRAB BARS, CONTRACTOR PROVIDED / CONTRACTOR INSTALLED
10.35 MIRROR, CONTRACTOR PROVIDED / CONTRACTOR INSTALLED
10.36 SOAP DISPENSER, VA PROVIDED / VA INSTALLED
10.37 PAPER TOWEL DISPENSER, SURFACE MOUNTED, CONTRACTOR PROVIDED / CONTRACTOR
INSTALLED
10.38 WASTE BASKET, VA PROVIDED / VA INSTALLED
11.04 REFRIGERATOR, VA PROVIDED / VA INSTALLED
11.05 MICROWAVE, VA PROVIDED / VA INSTALLED
12.19 SYSTEMS FURNITURE TO BE DETERMINED.
12.20 FURNITURE TO BE DETERMINED.
22.06 SINK, AS SCHEDULED, SEE PLUMBING DRAWINGS
22.08 SHOWER AND CONTROL VALVE, CONTRACTOR PROVIDED / CONTRACTOR INSTALLED
22.09 TOILET, AS SCHEDULED, SEE PLUMBING DRAWINGS
26.01 LIGHT FIXTURE, AS SCHEDULED, SEE ELECTRICAL DRAWINGS
B
C
C.2
AE402 2
AE4024
'-9
3'
-6
N
N
A
N3115B
N3117
N3118
CONTROL
ROOM
N3115
5'-1" 4'-9" 2'-3" 12'-10"
24'-11"
6'-11" 4'-10" 13'-4"
25'-1"
'-5
5/
'-5
/2
'-1
'-3
'-0
/1
6" 2'
-0
'-6
/1
6" 6'
-0
4' -6
/2
'-1
3/ 4"
'-0
/1
6"
FV
14'-0"
F V
'-8
FV
12'-0"
8'-0"
4' -0
12.19
12.19
12.19
12.19
10.40
10.39
1. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATION OF MILLWORK.
2. COORDINATE LOCATION OF RECEPTACLES WITH ELECTRICAL DRAWINGS.
3. NO PLASTIC HARDWARE, BRACKETS OR CLIPS WILL BE ACCEPTED.
4. ALL DRAWERS SHALL BE ON HEAVY DUTY FULL EXTENSION METAL GLIDES WITH SOFT CLOSERS
UNLESS NOTED OTHERWISE.
5. USE CONCEALED CABINET HINGES UNLESS NOTED OTHERWISE.
6. MILLWORK SHALL MEET THE QUALITY AND GRADE CONSTRUCTION STANDARDS AS SPECIFIED IN
THE PROJECT MANUAL. STRICT ADHERENCE TO THIS STANDARD SHALL BE ENFORCED. ANY
DEVIATIONS FROM THIS BASE STANDARD, IF NOT SPECIFICALLY SHOWN WITHIN THESE DRAWINGS
WILL NOT BE ACCEPTED.
7. ALL SURFACES EXPOSED TO VIEW, INCLUDING THOSE SURFACES EXPOSED TO VIEW WHILE IN A
SEATED POSITION, SHALL HAVE A FINISHED SURFACE TO MATCH OTHER ADJACENT FINISHED
SURFACES.
8. ALL COUNTERTOPS TO BE CONSTRUCTED OF SOLID SURFACING WITH 1/4" RADIUS DOUBLE ROUND
UNLESS NOTED OTHERWISE.
9. ALL CABINETS TO HAVE CABINET LINERS ON ALL SURFACES.
10. FURNITURE AND APPLIANCES ARE SHOWN FOR SPACE PLANNING PURPOSES.
GENERAL MILLWORK NOTES
LVT1 (LUXURY VINYL TILE)
PT2 (PORCELAIN FLOOR TILE)
PT1 (PORCELAIN FLOOR TILE)
FINISH FLOOR PLAN LEGEND
SC1 (SEALED CONCRETE)
26.01 26.0126.01
RB1 RB1RB1
12.19
12.19
N
A
26.0126.01
RB1
12.19
26.01
RB1
12.20
26.01
RB1
10.40
10.39 2" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
CODY DOUGLAS
ARCH - SETH A. CAVIN #7580 EXP. 12/31/2023
MECH - JAMES R. MYLES #027005 EXP. 12/31/2023
ELEC - BRADY MERZ #027238 EXP. 12/31/2023
CIVIL ENGINEER
CALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH, CO 80129
(303) 730-0434
BEN MURPHY
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVENUE, SUITE 100
KANSAS CITY, MO. 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
STRUCTURAL ENGINEER
DEGENKOLD ENGINEERS
375 BEALE STEET, SUITE 500
SAN FRANCISCO, CA 94105
(415) 354-6439
ROBERT GRAFF
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
FRANK FINLEY
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:0 :1
A
M
INTERIOR ELEVATIONS AND ENLARGED
PLANS
CLW 45 95Checker
LEVEL 1 SD2 RFP
CENTRAL UTILITY PLANT
04/21/2023
654-212
VA SIERRA NEVADA HEALTH CARE SYSTEM
975 KIRMAN AVE
RENO, NV 89502
AE402
SPUR #: 1791.06
N
1/4" = 1'-0" 1/ AE101
ENLARGED PLAN - CONTROL ROOM N311513/8" = 1'-0" 1/ AE402
CONTROL ROOM N3115 - EAST ELEVATION2
3/8" = 1'-0" 1/ AE401
CONTROL ROOM N3115 - NORTH ELEVATION3
3/8" = 1'-0" 1/ AE402
CONTROL ROOM N3115 - SOUTH ELEVATION5
3/8" = 1'-0" 1/ AE402
CONTROL ROOM N3115 - WEST ELEVATION4
No. REVISION DESCRIPTION DATE
KEYNOTE LEGEND
10.39 PEDESTAL BENCH
10.40 LOCKERS
12.19 SYSTEMS FURNITURE TO BE DETERMINED.
12.20 FURNITURE TO BE DETERMINED.
26.01 LIGHT FIXTURE, AS SCHEDULED, SEE ELECTRICAL DRAWINGS
SOLID SURFACE COUNTERTOP
SS-01 WITH EASED EDGE
3/4" PLYWOOD SUBSTRATE
2' - 0"
1-1/4"x1-1/4"x11 GA. TUBE
STEEL BRACE WELDED TO
STRAP. GRIND WELDS AND
EXPOSED TUBE END
SMOOTH PREPARE FOR
PAINT FINISH TO MATCH
WALL. BRACES TO BE SPAC-
ED AT 30" O.C. MAX.
LINE OF P-LAM PEDESTAL UNIT
WHERE OCCURS.
REFER TO ELEVATION.
TRANSITION STRIP (TR3)
SEALED CONCRETE (SC)
LUXURY VINYL TILE (LVT) AS SCHEDULED
NOTE: ALL TRANSITIONS BETWEEN FLOORING TO MEET AT CENTER OF
DOOR JAMBS.
2"
2'-0"
(TYP)
/2
P-LAM CLAD TOE SPACE
PAINTED DRYWALL
SCRIBE TO WALL
(PULL-1)
P-LAM CLAD (PL- ) 3/4"
MEDIUM DENSITY
FIBERBOARD DRAWER WITH
3-1/2" BENTWIRE PULLS AND
MELAMINE INTERIORS ON
HEAVY DUTY FULL
EXTENSION DRAWER
GUIDES
(75LB AT BOXES, 150LB AT
FILE DRAWERS) PROVIDE (1)
LOCKING MECHANISM TO
CONTROL ALL (3) DRAWERS
1/4" HARDWOOD BOTTOMS
MELAMINE CLAD
1/4"
HARDBOARD BACK
P-LAM CLAD COUNTER
2"
2'-0"
(TYP)
/2
P-LAM CLAD TOE SPACE
PAINTED DRYWALL
SCRIBE TO WALL
MELAMINE CLAD
1/4"
HARDBOARD BACK
1/4" HARDWOOD BOTTOMS
P-LAM CLAD 3/4" MEDIUM
DENSITY FIBERBOARD
DRAWER WITH BENTWIRE
PULLS AND MELAMINE
INTERIORS ON HEAVY
DUTY
FULL EXTENSION DRAWER
GUIDES (150LB AT FILE
DRAWERS) PROVIDE (1)
LOCKING MECHANISM TO
CONTROL ALL (2)
DRAWERS
(PULL-1)
P-LAM COUNTER
PAINTED PARTITION
P-LAM CLAD 3/4"
MEDIUM
DENSITY FIBERBOARD
DOORS W/CONCEALED
HINGES (TYP)
MELAMINE CLAD
1/4"
HARDBOARD BACK
MELAMINE CLAD 3/4"
FIBERBOARD
ADJUSTABLE
SHELF WITH VINYL EDGE
5MM IN-LINE BORED
HOLES
AT 32MM O.C.
(PULL-1)
1' TYP
'-0
SLOPED TOP
INTERIOR PARTITION AS
SCHEDULED
SS TRANSITION STRIP, FINISH: TR1
EPOXY BASE,…