This is a Closeout and Operation & Maintenance (O&M) Requirements template for National Park Service construction projects, issued by the Denver Service Center on January 27, 2021. The document establishes comprehensive requirements for project completion deliverables organized into six main categories: Project Record Drawings, System Demonstration and Training, Tools/Spare Parts/Equipment, Extra Stock, Reports, and Keys & Keying Schedule.
Key requirements include final project record drawings for all building systems (fire sprinkler, plumbing, mechanical, electrical, communications, fire alarm, and sanitary sewer), along with documentation of embedded utilities and concealed components. The contractor must provide system training for fire sprinkler operations, mechanical equipment, electrical systems, and fire alarm systems, including minimum 2-8 hours of hands-on instruction. Essential deliverables encompass spare parts (fire sprinkler cabinet with three spare heads of each type, 50 spare bricks, 20 square feet of each tile combination, one gallon of each paint color), commissioning reports, test and balance reports, environmental documentation, and comprehensive O&M manuals. The template also specifies extensive warranty requirements ranging from 1-20 years for various building components including roofing systems (20-year TPO membrane warranty), door hardware (2-3 years), windows (5 years), and specialized equipment warranties. All deliverables require tracking through submittal dates, completion status, and Park receipt confirmation, with final changeover of permanent locks and key delivery to the Contracting Officer.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Closeout and Operation & Maintenance (O&M) Requirements National Park Service (NPS) - Denver Service Center (DSC) | 1-27-21
Topic Specification
Section Requirement
Submittal
Date Completed
Received by Park
01770 Final Project Record Drawings.
Record locations of embedded utilities and components concealed from view.
21 13 00 Fire Sprinkler Shop level drawings with calculations
22 00 00 Plumbing record drawings
Project Record 23 00 00 Mechanical record drawings
Drawings 26 00 00 Electrical Record Drawings
26 24 16 Record changes in panelboard schedules and circuiting plans
27 00 00 Communications Record Drawings
28 00 00 Electronic Safety and Security Basic Requirements
28 31 00 Fire Alarm record drawings
33 31 00 Sanitary Sewer Project Record Documents
21 00 00 Fire Sprinkler system training: operations, scheduled inspissation times, hands-on instructions
23 81 29 Owner Training of mechanical equipment.
26 00 00 Electrical equipment and system demonstration and training.
System 26 09 24 Provide minimum of 2-hour training session to Government at a time approved by Contracting Officer. Training to include discussion of operation, adjustment, and replacement of sensors, photocells and control.
Demonstration 28 00 00 Training of Operating Personnel and Training 28 10 00 Provide eight hours of training of operational instruction and two hours of maintenance instruction.
28 31 00 Fire alarm system training: basic operation, detailed operation, hands-on instruction, classroom instruction.
10 31 00 Fireplace Tools: Provide shovel, brush, poker, and tongue tool set, finished to match hearth enclosure.
Tools, Spare Parts and Equipment 21 13 00
Fire Suppression: Spare Fire Sprinkler Cabinet - Sized to accommodate a minimum of three spare sprinklers of each type and temperature. Welded steel with hinged steel cover. Polyester coated finish inside and out. Attach to wall at the main sprinkler system riser. Locate so cover is easy to open and readily accessible. Locate in an area with a temperature between
40 and 100 degrees Fahrenheit. Locate sprinkler wrenches inside cabinet. Inside the cabinet, provide a list of sprinklers installed in the property, including sprinkler identification number, manufacturer, model, orifice, deflector type, thermal sensitivity and pressure rating, quantity of each type to be contained in the cabinet and issue or revision date of the list.
31 05 19 Geotextiles for Earthwork: Furnish two seam repair kits, special and other devices for Owner to maintain and repair geotextile material.
04 03 00 Spare parts: Provide 50 bricks for Park’s use in maintenance of project.
09 30 00 Maintenance Materials: 20 square feet of each tile size, color, and surface finish combination.
09 91 13 Extra Paint and Finish Materials: 1 gallon of each color; from the same product run.
Extra Stock 09 91 23 Extra Paint and Finish Materials: 1 gallon of each color; from the same product run.
21 13 00 Stock of spare sprinkler heads with associated wrench.
31 05 19.13 Furnish two seam repair kits.
01 32 33 Complete set of digital image electronic files
01 74 19 Project Waste Management Plan worksheet for solid waste disposal and diversion
01 77 00 NPS Required forms for occupancy, Fire Alarm acceptance, and other similar forms or certificates
01 77 00 Environmental Record Documents: IAQ Management Plan
01 77 00 Environmental Record Documents: Moisture Control Inspection and Reports
01 77 00 Environmental Record Documents: Material Safety Data Sheets
01 77 00 Pest Control Report
01 77 00 Test and Balance Report
01 91 14 Commissioning Reports
02 82 00 Final Visual Inspection and Clearance Testing, Certificate of Completion
Closeout and Operation Maintenance (O) Requirements Template | National Park Service (NPS) - Denver Service Center (DSC) page 1 of 4
Topic Specification
Section Requirement
Submittal
Date Completed
Received by Park
02 82 00 Final Visual Inspection and Clearance Testing, Certificate of Completion
02 84 00 Final Visual Inspection, Certificate of Completion
Reports 02 87 00 Final Visual Inspection, Certificate of Completion
21 00 00 Commissioning Report
22 33 00 Leak test, Operational test, Test to adjust control and safeties.
23 05 00 MFG technical representative/ Factory-authorized service representatives field reports
23 05 93 Certified TAB reports
26 00 00 Commissioning Report
26 05 19 Cable Insulation test reports
26 05 26 Grounding and Bonding test reports
26 05 73 Electrical Distribution Systems Study, submit report showing final adjusted settings of protective devices.
26 09 20 Prepare and complete report of test procedures and results.
26 09 23 Provide complete report of test procedures and results.
26 41 13 Final Inspection Report
27 15 00 Horizontal Cabling Test Report
27 53 20 Cable Television Cabling Test Report
28 00 00 Commissioning Report
28 31 00 Fire alarm test reports, certification of installation
01 77 00 Make final changeover of permanent locks and deliver keys to Contracting Officer. Advise Park personnel of changeover in security provisions.
08 71 00 Door Hardware: Submit (3) copies of Keying Schedule in compliance with requirements established during Keying
Requirement Meeting unless otherwise indicated.
Keys & Keying 28 31 00 Fire alarm keys
Schedule
01 56 39 Tree and other plant maintenance during and after completion of construction
O&M Data, Warranties and
Guarantees
07 54 23
TPO Membrane Roofing: Material Warranty: See Section 01 7800 - Closeout Submittals for additional warranty requirements. Provide membrane manufacturer's warranty agreeing to replace material that shows manufacturing defects within 10 years after installation. System Warranty: Provide manufacturer's system warranty agreeing to repair or replace roofing that leaks or is damaged due to wind or other natural causes.
1. Warranty Term: 20 years.
2. For repair and replacement include costs of both material and labor in warranty.
3. Include accidental punctures according to the manufacturer's standard warranty terms.
4. Include hail damage according to the manufacturer's standard warranty terms.
07 62 00
Sheet metal flashing and trim: Installers warranty: The contractor shall warrant that the work will remain free from defects of labor and materials used in conjunction with his work in accordance with the general conditions for this project or a maximum of three (3) years.
1. Warranty includes installation, leaks, displacement, failed joints, and damages to other building components impacted by failure.
Special Finish Warranty: Submit a written warranty, signed by manufacturer, covering failure of the factory-applied exterior finish on metal wall panels within the specified warranty period and agreeing to repair finish or replace panels that show evidence of finish deterioration. Deterioration of finish includes, but is not limited to, color fade, chalking, cracking, peeling, and loss of film integrity.
1. Finish Warranty Period: 20 years from date of Substantial Completion.
07 92 00
Join Sealants: See Section 01 78 00 - Closeout Submittals for additional warranty requirements.
Manufacturer Warranty: Provide 2-year manufacturer warranty for installed sealants and accessories that fail to achieve a watertight seal, exhibit loss of adhesion or cohesion, or do not cure. Complete forms in Contracting Officer's name and register with manufacturer.
Extended Correction Period: Correct defective work within 2-year period commencing on Date of Substantial Completion.
08 14 33
Stile and Rail Wood Doors: See Section 01 77 00 - Closeout Procedures for additional warranty requirements.
Interior Doors: Provide manufacturer's warranty for the life of the installation. Include coverage for delamination of veneer, warping beyond specified installation tolerances, defective materials, and telegraphing core construction.
Closeout and Operation Maintenance (O) Requirements Template | National Park Service (NPS) - Denver Service Center (DSC) page 2 of 4
Section Requirement
Submittal
Date Completed
Received by Park
08 52 00
Wood Windows: Correct defective Work within a five year period after Date of Substantial Completion. Manufacturer
Warranty: Provide 5-year manufacturer warranty for insulated glass units against seal failure, interpane dusting or misting, and replacement of same. Complete forms in Owner's name and register with manufacturer. Manufacturer Warranty:
Provide 2-year manufacturer warranty against defects listed. Complete forms in Owner's name and register with manufacturer or warrantor.
1. Degradation of color finish.
2. Delamination or separation of finish cladding from window member.
08 71 00
Door Hardware: See Section 01 78 00 - Closeout Submittals for additional warranty requirements. Manufacturer's Warranty:
Provide warranty against defects in material and workmanship for period indicated. Complete forms in Contracting Officer's name and register with manufacturer.
1. Locksets and Cylinders: Three years, minimum.
2. Other Hardware: Two years, minimum.
08 80 00
Glazing: See Section 01 77 00 - Closeout Submittals for additional warranty requirements. Insulating Glass Units: Provide a five (5) year manufacturer warranty to include coverage for seal failure, interpane dusting or misting, including providing products to replace failed units
10 31 00
Manufacture Fireplaces: Manufacturer Warranty: Provide Limited lifetime manufacturer warranty. Complete forms in
Owner's name and register with manufacture. Catalyst Combustor: Provide 10-year manufacturer warranty. Complete forms in Owner's name and register with manufacturer
11 30 13 Residential Appliance: Provide five (5) year manufacturer warranty on refrigeration system of refrigerators. Provide ten (10) year manufacturer warranty on tub and door liner of dishwashers.
12 24 00
Window Shades: Provide manufacturer's warranty from Date of Substantial Completion, covering the following:
1. Shade Hardware: One year.
2. Fabric: One year.
3. Aluminum and Steel Coatings: One year.
12 35 30 Residential Casework: Correct defective Work within a five year period after Date of Substantial Completion.
21 00 00 Operation and Maintenance Manuals for devices valves and sprinkler heads, including air compressor and associated parts
21 00 00 Installing contractor warranty and guaranty certificates; 1-year labor.
22 05 00 O&M Manuals
22 05 19 O&M Manuals
22 11 19 O&M Manuals
22 13 19 O&M Manuals
22 14 29 O&M Manuals
22 33 00 O&M Manuals
22 41 00 O&M Manuals
23 33 00 O&M Manuals
23 34 23 O&M Manuals
23 81 29 O&M Manuals
23 81 29 Warranty
23 82 39 O&M Manuals
26 00 00 Electrical Contractor 1-year Warranty and O&M Data
26 24 16 O&M Data.
26 27 13 O&M Data.
26 43 00 O&M Data. 10-year warranty, incorporating unlimited replacements of SPD if they are destroyed by transients within warranty period.
26 51 00
O&M Data. Not less than 5 years for luminaire based on date of substantial completion. Includes cost of labor to replace luminaire. Replacement luminaire will match physical dimensions, physical appearance, chromaticity, lumen output and photometric characteristics of original installed equipment.
27 00 00 Contractor 1-year Warranty and O&M Data
28 00 00 Contractor 1-year Warranty and O&M Data
Closeout and Operation Maintenance (O) Requirements Template | National Park Service (NPS) - Denver Service Center (DSC) page 3 of 4
Section Requirement
Submittal
Date Completed
Received by Park
28 10 00 O&M Data
28 31 00
Warranty covering fire alarm system for one year. Operation and maintenance manual with catalog cut sheets, installation sheets, manufacturer O&M manuals, data file printout, record drawings, warranty, record of completion, test reports, instruction charts.
31 10 00 Acceptance