Attachment J.3 - J.11 Battery Technical Exhibits A-I.xls
XLS spreadsheet 163 KB Posted
- Attached to
- GNAS Battery System Equipment and Replacement Federal contract opportunity
- Solicitation number
- 6973GH-23-R-00094
About this file
This technical document contains specifications for battery system equipment and replacement parts required by the Department of Transportation Federal Aviation Administration Franchise Acquisition Services. The agency seeks flooded lead-acid, VRLA, and NiCad batteries for various applications including VOR, UPS, DC bus, control power, and emergency power. Battery voltages range from 12V to 480V. Required products include batteries, racks, monitors, harnesses, ventilation equipment, and spill response kits. Specifications define nominal voltages, runtimes, quantities, and OEM documentation for incumbent and proposed replacement equipment matching existing configurations. Dimensional and seismic requirements for racks align with existing infrastructure. The solicitation number is 6973GH-23-R-00094 for battery replacements supporting air traffic control facilities nationwide.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J.3 EXH A FCB VOR
| EXISTING EQUIPMENT | VENDOR PROPOSED PRODUCTS1,2 | ||||||||||||||||||||
| CLIN _________________ | |||||||||||||||||||||
| NAS FAC TYPE | FAC TYPE DETAILS | Nominal Voltage | Strings | Battery Type | End Voltage | Min. Runtime | Design Load | Battery Make/Model | Quantity | Rack Make/Model | Spill Containment Make/Model | CLIN # | Battery Make/Model3 | CLIN # | Rack (2 tier) Make/Model4 | CLIN # | Spill Containment (2 tier) Make/Model | CLIN # | Rack (1 tier) Make/Model4 | CLIN # | Spill Containment (1 tier) Make/Model |
| VOR w/ Supported Kohler EG | 2nd Gen VORTAC w/ LPTA | 36V (18 cells) | 1 | Flooded | 1.86V/c (33.48V) | 1 hour | 110A MAX | C&D KCT-450 | 18 modules | C&D RD05270-05EP2 | Enviroguard HawkHWK25-64-FA-N | N/A | N/A | ||||||||
| 2nd Gen VORTAC w/ dB-900e | 36V (18 cells) | 1 | Flooded | 1.86V/c (33.48V) | 1 hour | 73A MAX | C&D 3DJ-09HP | 6 modules (3 cells ea.) | C&D RD05270-03EP2 | Enviroguard Hawk HWK25-40- FA-N | C&D RDB0801-XXEP2 | Enviroguard Hawk HWK-23-64 FA-N | |||||||||
| 2nd Gen VORTAC w/o LPTA or 2nd Gen VOR with DME | 36V (18 cells) | 1 | Flooded | 1.86V/c (33.48V) | 1 hour | 69A MAX | C&D 3DJ-09HP | 6 modules (3 cells ea.) | C&D RD05270-03EP2 | Enviroguard Hawk HWK25-40- FA-N | C&D RDB0801-XXEP2 | Enviroguard Hawk HWK-23-64 FA-N | |||||||||
| 2nd Gen VOR, 2nd Gen DME, or 2nd Gen VOR being decommissioned | 36V (18 cells) | 1 | Flooded | 1.86V/c (33.48V) | 1 hour | 42A MAX | C&D 3DJ-09HP | 6 modules (3 cells ea.) | C&D RD05270-03EP2 | Enviroguard Hawk HWK25-40- FA-N | C&D RDB0801-XXEP2 | Enviroguard Hawk HWK-23-64 FA-N | |||||||||
| VOR w/o Supported Kohler EG | 2nd Gen VORTAC w/ LPTA | 36V (18 cells) | 1 | Flooded | 1.86V/c (33.48V) | 8 hours | 110A MAX | C&D LCM-17HP |
or
| LCT 1008 (if LCM 17HP is not available) | 18 modules (1 cell ea.) | C&D RDC0901-07-EP2 | ||||||||||||||
| (See C&D table and 3R2T-7 third rail kit) | Enviroguard Hawk HWK28-88-FA-N | N/A | N/A | |||||||||||||
| 2nd Gen VORTAC w/ dB-900e | 36V (18 cells) | 1 | Flooded | 1.86V/c (33.48V) | 8 hours | 73A MAX | C&D KCT-660 | 18 modules (1 cell ea.) | C&D RD05270-07EP2 | Enviroguard Hawk HWK25-88-FA-N | N/A | N/A | ||||
| 2nd Gen VORTAC w/o LPTA or 2nd Gen VOR with DME | 36V (18 cells) | 1 | Flooded | 1.86V/c (33.48V) | 8 hours | 69A MAX | C&D KCT-660 | 18 modules (1 cell ea.) | C&D RD05270-07EP2 | Enviroguard Hawk HWK25-88-FA-N | N/A | N/A | ||||
| 2nd Gen VOR | 36V (18 cells) | 1 | Flooded | 1.86V/c (33.48V) | 8 hours | 42A MAX | C&D KCT-450 | 18 modules (1 cell ea.) | C&D RD05270-05EP2 | Enviroguard Hawk HWK25-64-FA-N | N/A | N/A | ||||
| 2nd Gen DME or 2nd Gen VOR being decommissioned | 36V (18 cells) | 1 | Flooded | 1.86V/c (33.48V) | 8 hours | 35A MAX | C&D KCT-450 | 18 modules (1 cell ea.) | C&D RD05270-05EP2 | Enviroguard Hawk HWK25-52-FA-N | N/A | N/A | ||||
| 1 Product includes, covers straps and lifting straps/spreader blocks. | ||||||||||||||||
| CLIN # CYPHER | 2 Product includes applicable OEM documentation. | |||||||||||||||
| x | x | x | x | x | x | 3 Battery dimensions, runtime and ampacity must match existing battery. | ||||||||||
| Contract CLIN Section | Contract Period | Table | PRODUCT CONFIGURATION | 4 Battery rack dimensions must closely match existing rack. Seismic capability must meet IBC requirements. If space or other factors prevent meeting current IBC, seimic capability must be no less than existing battery/rack. |
&C&18Flooded Cell Battery VOR Exhibit A/Table 1 &L&18 09/21/2016&R&18 Attachment J.5 Page &P of &N
J.4 EXH B FCB UPS
| EXISTING EQUIPMENT | VENDOR PROPOSED PRODUCTS2 | |||||||||||||
| CLIN ________ | ||||||||||||||
| NAS FAC TYPE | FAC TYPE DETAILS | Nominal Voltage | Battery Type | End Voltage | Battery Make/Model | Quantity | Rack Make/Model | Spill Containment Make/Model | CLIN # | Battery Make/Model3 | CLIN # | Rack Make/Model4 | CLIN # | Spill Containment Make/Model |
| PCS (UPS) | ACEPS II and TRACONS | 480V (240 cells) | Flooded | 1.75V/c | C&D 4XTHC19 | 60 (modules 4 cells each) | RDB-0901-17EP2-P | (3) SP28-212P | C&D 4XTHC19 | |||||
| 1 Includes, covers straps and lifting straps/spreader blocks. | ||||||||||||||
| CLIN # CYPHER | 2 Includes applicable OEM documentation. | |||||||||||||
| X | X | X | X | X | X | 3 Battery dimensions, runtime and ampacity must match existing battery. | ||||||||
| Contract CLIN Section | Contract Period | Table/Exhibit | PRODUCT CONFIGURATION | 4 Battery rack dimensions must closely match existing rack. Seismic capability must meet IBC requirements. If space or other factors prevent meeting current IBC, seimic capability must be no less than existing battery/rack. |
J.5 EXH C FCB DC BUS
| EXISTING EQUIPMENT | VENDOR PROPOSED PRODUCTS2 | |||||||||||||||
| CLIN ________ | ||||||||||||||||
| NAS FAC TYPE | FAC TYPE DETAILS | Nominal Voltage | Battery Type | End Voltage | Battery Make/Model | Quantity | Rack Make/Model | Spill Containment Make/Model | CLIN # | Battery Make/Model3 | CLIN # | Rack Make/Model4 | CLIN # | Spill Containment Make/Model | ||
| DC BUS (Legacy) | Radio Communications | 24V (12 cells) | Flooded | 1.75V/c (21V) | KCT 660 | 12 cells/string | C&D RD05270-07EP2 | Enviroguard Hawk HWK25-64-FA-N | ||||||||
| Radio Communications | 24V (2 strings of 12 cells) | Flooded | 1.75V/c (21V) | KCT 360 | 12 cells/string | C&D RD05270-04EP2 | 2X Enviroguard Hawk HWK25-40-FA-N | |||||||||
| Radio Communications | 24V (2 strings of 12 cells) | Flooded | 1.75V/c (21V) | KCT 360 | 12 cells/string | C&D RD05270-04EP2 | Enviroguard Hawk HWK25-40-FA-N | |||||||||
| Radio Communications | 48V (24 cells) | Flooded | 1.75V/c (21V) | KCT 660 | 24 cells/string | C&D RD05270-07EP2 | Enviroguard Hawk HWK25-112-FA-N | |||||||||
| 1 Includes, covers straps and lifting straps/spreader blocks. | ||||||||||||||||
| CLIN # CYPHER | 2 Includes applicable OEM documentation. | |||||||||||||||
| x | x | x | x | x | x | 3 Battery dimensions, runtime and ampacity must match existing battery. | ||||||||||
| Contract CLIN Section | Contract Period | Table/Exhibit | PRODUCT CONFIGURATION | 4 Battery rack dimensions must closely match existing rack. Seismic capability must meet IBC requirements. If space or other factors prevent meeting current IBC, seimic capability must be no less than existing battery/rack. |
J.6 EXH D FCB CP NICD
| Equipment Configuration | VENDOR PROPOSED PRODUCTS2 | |||||||||||||
| CLIN _________ | ||||||||||||||
| NAS FAC TYPE | FAC TYPE DETAILS | Nominal Voltage | Battery Type | End Voltage | Battery Make/Model | Quantity | Rack Make/Model | Spill Containment Make/Model | CLIN # | Battery Make/Model3 | CLIN # | Rack Make/Model4 | CLIN # | Spill Containment Make/Model |
| DC BUS (Control Power) | DRPDS &CRPDS | string voltage 135 to 120 (1.4 - 1.25vpc) | FCB NICAD | 1.0 volts/cell | ALCAD XHP | 96/string | NICAD | |||||||
| 1 Product includes, covers straps and lifting straps/spreader blocks. | ||||||||||||||
| CLIN # CYPHER | 2 Product includes applicable OEM documentation. | |||||||||||||
| x | x | x | x | x | x | 3 Battery dimensions, runtime and ampacity must match existing battery facility. | ||||||||
| Contract Section | Contract Period | Table/Exhibit | PRODUCT CONFIGURATION | 4 Battery rack dimensions must closely match existing rack. Seismic capability must meet IBC requirements. If space or other factors prevent meeting current IBC, seimic capability must be no less than existing battery/rack. |
J.7 EXH E VRLA VOR
| EXISTING EQUIPMENT | VENDOR PROPOSED PRODUCTS 2 | |||||||||||
| CLIN ________ | ||||||||||||
| NAS FAC TYPE | FAC TYPE DETAILS | Nominal Voltage | Battery Type | End Voltage | Min. Runtime | Design Load | Battery Make/Model | Quantity | CLIN # | Battery Make/Model3 | CLIN # | Rack Make/Model4, 5 |
| VOR w/Supported Kohler EG | 2nd Gen VORTAC w/ LPTA | 36V (18 cells) | VRLA | 1.86V/c (36V) | 1 hour | 110A MAX | GNB Absolyte 90G07 | 3 modules | GNB Absolyte 90G07 | |||
| 2nd Gen VORTAC w/ dB-900e | 36V (18 cells) | VRLA | 1.86V/c (33.48V) | 1 hour | 73A MAX | GNB Absolyte 90G07 | 3 modules | GNB Absolyte 90G07 | ||||
| 2nd Gen VORTAC w/o LPTA or 2nd Gen VOR/DME | 36V (18 cells) | VRLA | 1.86V/c (36V) | 1 hour | 69A MAX | GNB Absolyte 50G07 | 3 modules | GNB Absolyte 50G07 | ||||
| 2nd Gen VOR, 2nd Gen DME, or 2nd Gen VOR being Decommissioned | 36V (18 cells) | VRLA | 1.86V/c (36V) | 1 hour | 42A MAX | GNB Absolyte 50G05 | 3 modules | GNB Absolyte 50G05 | ||||
| 3rd Gen | 48V (24 cells) | VRLA | 1.75V/c (42V) | 1 hour | 55A MAX | GNB Absolyte 50G05 | 4 modules | GNB Absolyte 50G05 | ||||
| VOR | 2nd Gen VORTAC w/ LPTA | 36V (18 cells) | VRLA | 1.86V/c (36V) | 8 hours | 110A MAX | GNB Absolyte 100G21 | 6 modules | GNB Absolyte 100G21 | |||
| 2nd Gen VORTAC w/ dB-900e | 36V (18 cells) | VRLA | 1.86V/c (33.48V) | 8 hours | 73A MAX | GNB Absolyte 100G13 | 6 modules | GNB Absolyte 100G13 | ||||
| 2nd Gen VORTAC w/o LPTA or 2nd Gen VOR/DME | 36V (18 cells) | VRLA | 1.86V/c (36V) | 8 hours | 69A MAX | GNB Absolyte 100G13 | 6 modules | GNB Absolyte 100G13 | ||||
| 2nd Gen VOR | 36V (18 cells) | VRLA | 1.86V/c (36V) | 8 hours | 42A MAX | GNB Absolyte 90G09 | 3 modules | GNB Absolyte 90G09 | ||||
| 2nd Gen DME or 2nd Gen VOR being Decommissioned | 36V (18 cells) | VRLA | 1.86V/c (36V) | 8 hours | 35A MAX | GNB Absolyte 50G13 | 3 modules | GNB Absolyte 50G13 | ||||
| 3rd Gen | 48V (24 cells) | VRLA | 1.75V/c (42V) | 8 hours | 55A MAX | GNB Absolyte 90G11 | 4 modules | GNB Absolyte 90G11 | ||||
| 1 Product includes covers, straps and other necessary rack parts. | ||||||||||||
| 2 Product includes applicable OEM documentation. | ||||||||||||
| CLIN # CYPHER | 3 Battery dimensions, runtime and ampacity must match existing battery. | |||||||||||
| X | X | X | X | X | X | 4 Battery rack dimensions must closely match existing rack. Seismic capability must meet IBC requirements. If space or other factors prevent meeting current IBC, seimic capability must be no less than existing battery/rack. | ||||||
| Contract CLIN Section | Contract Period | Table/Exhibit | PRODUCT CONFIGURATON | 5 Existing battery/modules are designed with an integral rack with the stackable modules. Other battery configurations with the same fit, form and function as the existing may have a separate rack. If the battery and rack are integral components in a stackable module configuration as the existing then insert "N/A" in the rack information. |
J.8 EXH VRLA UPS
| EXISTING EQUIPMENT | VENDOR PROPOSED PRODUCTS 1,2, 3, 4 CLIN ________ | ||||||||||||||||||
| NAS FAC TYPE | FAC TYPE DETAILS | UPS Nominal Voltage VAC | Battery Type and Voltage | End Voltage | UPS Size (KVA) | Battery Make/Model | Quantity | Existing Battery Rack | CLIN # | Battery Make/Model6 | CLIN # | Rack Zone 2 (standard) Make/Model6 | CLIN # | Rack Zone 4 (Seismic) Make/Model5,6 | |||||
| MAKE | MODEL | Seismic | |||||||||||||||||
| PCS (UPS) | AFSS, Large Consolidated TRACONS, ARSRs, ACEPS Test UPS, ASRs, ASDE and TDWR | 208 or 480 | VRLA 12 Volt | 1.75 v/c | 20 | East Penn HR3500ET | 18 | C&C | 62C1UF35-D216XXXXXXXXXXX | Zone 2 | |||||||||
| U5C1UF35-D216XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 30 | 30 | U4C1UF35ZD360XXXXXXXXXXX | Zone 4 | ||||||||||||||||
| 40 | 32 | 62C1UF35-D384XXXXXXXXXXX | Zone 2 | ||||||||||||||||
| U5C1UF35-D384XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 65 | 62C1UF35-D384XXXXXXXXXXX | Zone 2 | |||||||||||||||||
| U5C1UF35-D384XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 80 | 62C1UF35-D384XXXXXXXXXXX | Zone 2 | |||||||||||||||||
| U5C1UF35-D384XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 75 | 30 | 62C1UF35-D360XXXXXXXXXXX | Zone 2 | ||||||||||||||||
| U4C1UF35ZD360XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| U5C1UF35-D360XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 100 | U4C1UF35-D360XXXXXXXXXXX | Zone 4 | |||||||||||||||||
| U5C1UF35ZD360XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 40 | 36 | 62C1UF35-D432XXXXXXXXXXX | Zone 2 | ||||||||||||||||
| U5C1UF35-D432XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 65 | 62C1UF35-D432XXXXXXXXXXX | Zone 2 | |||||||||||||||||
| U5C1UF35-D432XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 80 | 62C1UF35-D432XXXXXXXXXXX | Zone 2 | |||||||||||||||||
| U5C1UF35-D432XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 40 | U5C1UF35ZD480XXXXXXXXXXX | Zone 4 | |||||||||||||||||
| 75 | 40 | 62C1UF35-D480XXXXXXXXXXX | Zone 2 | ||||||||||||||||
| U5C1UF35ZD480XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 75 | East Penn HR5500ET | 30 | 62C1UF55-D360XXXXXXXXXXX | Zone 2 | |||||||||||||||
| U6C1UF55ZD360XXXXXXXXXXX | Zone 4 | ||||||||||||||||||
| 100 | 62C1UF55-D360XXXXXXXXXXX | Zone 2 | |||||||||||||||||
| 120 | 62C1UF55-D360XXXXXXXXXXX | Zone 2 | |||||||||||||||||
| 100 | 32 | 62C1UF55-D384XXXXXXXXXXX | Zone 2 | ||||||||||||||||
| 120 | 62C1UF55-D384XXXXXXXXXXX | Zone 2 | |||||||||||||||||
| 100 | 36 | 62C1UF55-D432XXXXXXXXXXX | Zone 2 | ||||||||||||||||
| 120 | 62C1UF55-D432XXXXXXXXXXX | Zone 2 | |||||||||||||||||
| 150 | 40 | 62C1UF55-D480XXXXXXXXXXX | Zone 2 | ||||||||||||||||
| 100 | 62C1UF55-D480XXXXXXXXXXX | Zone 2 | |||||||||||||||||
| 75 | Northstar | ||||||||||||||||||
| NSB12-170RT | 30 | NorthStar | NSR0121XXXXXXXXX | Zone 2 | |||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 40 | Northstar | ||||||||||||||||||
| NSB12-245RT | 30 | NSR0121XXXXXXXXX | Zone 2 | ||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 32 | NSR0121XXXXXXXXX | Zone 2 | |||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 36 | NSR0121XXXXXXXXX | Zone 2 | |||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| Northstar | |||||||||||||||||||
| NSB12-170RT | 40 | NSR0121XXXXXXXXX | Zone 2 | ||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 50 | Northstar | ||||||||||||||||||
| NSB12-365RT | 32 | NSR0121XXXXXXXXX | Zone 2 | ||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| Northstar | |||||||||||||||||||
| NSB12-245RT | 36 | NSR0121XXXXXXXXX | Zone 2 | ||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 40 | NSR0121XXXXXXXXX | Zone 2 | |||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 65 | Northstar | ||||||||||||||||||
| NSB12-365RT | 30 | NSR0121XXXXXXXXX | Zone 2 | ||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 32 | NSR0121XXXXXXXXX | Zone 2 | |||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 36 | NSR0121XXXXXXXXX | Zone 2 | |||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 40 | NSR0121XXXXXXXXX | Zone 2 | |||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 80 | Northstar | ||||||||||||||||||
| NSB12-425RT | 30 | NSR0121XXXXXXXXX | Zone 2 | ||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 32 | NSR0121XXXXXXXXX | Zone 2 | |||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 36 | NSR0121XXXXXXXXX | Zone 2 | |||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| Northstar | |||||||||||||||||||
| NSB12-365RT | 40 | NSR0121XXXXXXXXX | Zone 2 | ||||||||||||||||
| NSR0008XXXXXXXXX | Zone 4 | ||||||||||||||||||
| 100 | Northstar | ||||||||||||||||||
| NSB12-650RT | 32 | NSR0113XXXXXXXXX | Zone 4 | ||||||||||||||||
| 36 | |||||||||||||||||||
| Northstar | |||||||||||||||||||
| NSB12-450RT | 40 | NSR0113XXXXXXXXX | Zone 4 | ||||||||||||||||
| 120 | Northstar | ||||||||||||||||||
| NSB12-650RT | 30 | NSR0113XXXXXXXXX | Zone 4 | ||||||||||||||||
| 32 | |||||||||||||||||||
| 36 | |||||||||||||||||||
| 40 | |||||||||||||||||||
| 160 | Northstar | ||||||||||||||||||
| NSB12-730RT | 40 | ||||||||||||||||||
| Popups | 208 and 480 | VRLA 12 Volt | 1.75V/c | NA | C&D UPS12-150MR | 30 | C&D | NA | NA | ||||||||||
| C&D UPS12-210MR | |||||||||||||||||||
| C&D UPS12-300MR | |||||||||||||||||||
| C&D UPS12-350MR | |||||||||||||||||||
| C&D UPS12-400MR | |||||||||||||||||||
| C&D UPS12-490MR | |||||||||||||||||||
| C&D UPS12-600MR | |||||||||||||||||||
| C&D UPS12-150MR | 40 | ||||||||||||||||||
| C&D UPS12-210MR | |||||||||||||||||||
| C&D UPS12-300MR | |||||||||||||||||||
| C&D UPS12-350MR | |||||||||||||||||||
| C&D UPS12-400MR | |||||||||||||||||||
| C&D UPS12-490MR | |||||||||||||||||||
| C&D UPS12-600MRX | |||||||||||||||||||
| ACEPS UPM | 480 | VRLA 2Volt | 1.75V/c | 450KW | C&D MS Endure II AT-23P | 192 Cells | C&D | SYS00288-ATP | Zone 4 | ||||||||||
| 1 Includes applicable OEM documentation. | |||||||||||||||||||
| 2 Rack includes battery covers and any necessary rack parts. | |||||||||||||||||||
| 3 Rack includes battery breaker and conductors sized to support the battery size at 1.75 vpc or full UPS load whichever is larger. Battery breaker must include aux and balo contacts as well as shunt trip or (24V or 48V as specified by customer) or UVR (24V or 48V as specified by customer). | |||||||||||||||||||
| CLIN # CYPHER | 4 Rack must be front facing. | ||||||||||||||||||
| X | X | X | X | X | X | 5 As required, seismic rack models must be shaker tested. Battery rack dimensions must closely match existing rack. Seismic capability must meet IBC requirements. If space or other factors prevent meeting current IBC, seimic capability must be no less than existing battery/rack. | |||||||||||||
| Contract CLIN Section | Contract Period | Table/Exhibit | PRODUCT CONFIGURATION | 6 Battery dimensions, runtime and ampacity must match existing battery. | |||||||||||||||
| 7 Rack dimensions must match existing rack. |
J.9 EXH G VRLA DC BUS
| EXISTING EQUIPMENT | VENDOR PROPOSED PRODUCTS2 | ||||||||
| CLIN ________ | |||||||||
| NAS FAC TYPE | FAC TYPE DETAILS | Nominal Voltage | Battery Type | End Voltage | Battery Make/Model | CLIN # | Battery Make/Model3 | CLIN # | Rack Make/Model4, 5 |
| DC BUS | Radio Communications National/Legacy | 24V (12 cells) | VRLA | 1.75V/c (21V) | GNB Absolyte GP 24 Volt 50G05 | GNB Absolyte GP 24 Volt 50G05 | |||
| GNB Absolyte GP 24 Volt 50G07 | GNB Absolyte GP 24 Volt 50G07 | ||||||||
| GNB Absolyte GP 24 Volt 50G09 | GNB Absolyte GP 24 Volt 50G09 | ||||||||
| GNB Absolyte GP 24 Volt 50G13 | GNB Absolyte GP 24 Volt 50G13 | ||||||||
| GNB Absolyte GP 24 Volt 90G07 | GNB Absolyte GP 24 Volt 90G07 | ||||||||
| GNB Absolyte GP 24 Volt 90G09 | GNB Absolyte GP 24 Volt 90G09 | ||||||||
| GNB Absolyte GP 24 Volt 90G11 | GNB Absolyte GP 24 Volt 90G11 | ||||||||
| GNB Absolyte GP 24 Volt 90G13 | GNB Absolyte GP 24 Volt 90G13 | ||||||||
| GNB Absolyte GP 24 Volt 90G15 | GNB Absolyte GP 24 Volt 90G15 | ||||||||
| GNB Absolyte GP 24 Volt 100G13 | GNB Absolyte GP 24 Volt 100G13 | ||||||||
| GNB Absolyte GP 24 Volt 100G15 | GNB Absolyte GP 24 Volt 100G15 | ||||||||
| GNB Absolyte GP 24 Volt 100G17 | GNB Absolyte GP 24 Volt 100G17 | ||||||||
| GNB Absolyte GP 24 Volt 100G19 | GNB Absolyte GP 24 Volt 100G19 | ||||||||
| GNB Absolyte GP 24 Volt 100G21 | GNB Absolyte GP 24 Volt 100G21 | ||||||||
| GNB Absolyte GP 24 Volt 100G23 | GNB Absolyte GP 24 Volt 100G23 | ||||||||
| GNB Absolyte GP 24 Volt 100G25 | GNB Absolyte GP 24 Volt 100G25 | ||||||||
| GNB Absolyte GP 24 Volt 100G27 | GNB Absolyte GP 24 Volt 100G27 | ||||||||
| GNB Absolyte GP 24 Volt 100G29 | GNB Absolyte GP 24 Volt 100G29 | ||||||||
| GNB Absolyte GP 24 Volt 100G31 | GNB Absolyte GP 24 Volt 100G31 | ||||||||
| GNB Absolyte GP 24 Volt 100G33 | GNB Absolyte GP 24 Volt 100G33 | ||||||||
| GNB Absolyte GP 24 Volt 100G39 | GNB Absolyte GP 24 Volt 100G39 | ||||||||
| GNB Absolyte GP 24 Volt 100G45 | GNB Absolyte GP 24 Volt 100G45 | ||||||||
| DC BUS | Radio Communications (Legacy) | 48V (24 cells) | VRLA | 1.75V/c (42V) | GNB Absolyte GP 24 Volt 50G05 | GNB Absolyte GP 24 Volt 50G05 | |||
| GNB Absolyte GP 24 Volt 50G07 | GNB Absolyte GP 24 Volt 50G07 | ||||||||
| GNB Absolyte GP 24 Volt 50G09 | GNB Absolyte GP 24 Volt 50G09 | ||||||||
| GNB Absolyte GP 24 Volt 50G13 | GNB Absolyte GP 24 Volt 50G13 | ||||||||
| GNB Absolyte GP 24 Volt 90G07 | GNB Absolyte GP 24 Volt 90G07 | ||||||||
| GNB Absolyte GP 24 Volt 90G09 | GNB Absolyte GP 24 Volt 90G09 | ||||||||
| GNB Absolyte GP 24 Volt 90G11 | GNB Absolyte GP 24 Volt 90G11 | ||||||||
| GNB Absolyte GP 24 Volt 90G13 | GNB Absolyte GP 24 Volt 90G13 | ||||||||
| GNB Absolyte GP 24 Volt 90G15 | GNB Absolyte GP 24 Volt 90G15 | ||||||||
| GNB Absolyte GP 24 Volt 100G13 | GNB Absolyte GP 24 Volt 100G13 | ||||||||
| GNB Absolyte GP 24 Volt 100G15 | GNB Absolyte GP 24 Volt 100G15 | ||||||||
| GNB Absolyte GP 24 Volt 100G17 | GNB Absolyte GP 24 Volt 100G17 | ||||||||
| GNB Absolyte GP 24 Volt 100G19 | GNB Absolyte GP 24 Volt 100G19 | ||||||||
| GNB Absolyte GP 24 Volt 100G21 | GNB Absolyte GP 24 Volt 100G21 | ||||||||
| GNB Absolyte GP 24 Volt 100G23 | GNB Absolyte GP 24 Volt 100G23 | ||||||||
| GNB Absolyte GP 24 Volt 100G25 | GNB Absolyte GP 24 Volt 100G25 | ||||||||
| GNB Absolyte GP 24 Volt 100G27 | GNB Absolyte GP 24 Volt 100G27 | ||||||||
| GNB Absolyte GP 24 Volt 100G29 | GNB Absolyte GP 24 Volt 100G29 | ||||||||
| GNB Absolyte GP 24 Volt 100G31 | GNB Absolyte GP 24 Volt 100G31 | ||||||||
| GNB Absolyte GP 24 Volt 100G33 | GNB Absolyte GP 24 Volt 100G33 | ||||||||
| GNB Absolyte GP 24 Volt 100G39 | GNB Absolyte GP 24 Volt 100G39 | ||||||||
| GNB Absolyte GP 24 Volt 100G45 | GNB Absolyte GP 24 Volt 100G45 | ||||||||
| 1 Product includes covers, straps and other necessary rack parts. | |||||||||
| 2 Product includes applicable OEM documentation. | |||||||||
| CLIN # CYPHER | 3 Battery dimensions, runtime and ampacity shall match existing facility. | ||||||||
| X | x | x | x | x | x | 4 Battery rack dimensions must closely match existing rack. Seismic capability must meet IBC requirements. If space or other factors prevent meeting current IBC, seimic capability must be no less than existing battery/rack. | |||
| Contract CLIN Section | Contract Period | Table | PRODUCT CONFIGURATION | 5 Existing battery/modules are designed with an integral rack with the stackable modules. Other battery configurations with the same fit, form and function as the existing may have a separate rack. If the battery and rack are integral components in a stackable module configuration as the existing then insert "N/A" in the rack information. |
J.10 EXH H VRLA CP ACEPS
| EXISTING EQUIPMENT | VENDOR PROPOSED PRODUCTS2 | ||||||||||
| CLIN _______ | |||||||||||
| NAS FAC TYPE | FAC TYPE DETAILS | Nominal Voltage | Battery Type | End Voltage | Battery Make/Model | Quantity | Battery Make/Model3 | CLIN # | Rack Make/Model4, 5 | CLIN # | |
| DC BUS (CONTROL POWER) | ACEPS Control Power | 48V or | |||||||||
| 120V | VRLA | 1.75V/c | Enersys DDm 50-13 | 22 | Enersys DDmP 50-13 | ||||||
| Enersys DDm 50-13 | 60 | Enersys DDmP 50-13 | |||||||||
| Enersys DDm 50-17 | 22 | Enersys DDmP 50-17 | |||||||||
| Enersys DDm 50-17 | 60 | Enersys DDmP 50-17 | |||||||||
| 1 Product includes covers, straps and other necessary rack parts. | |||||||||||
| 2 Product includes applicable OEM documentation. | |||||||||||
| CLIN # CYPHER | 3 Battery dimensions, runtime and ampacity shall match existing battery facility. | ||||||||||
| A | 0 | 8 | 0 | 1 | A | 4 Battery rack dimensions must closely match existing rack. Seismic capability must meet IBC requirements. If space or other factors prevent meeting current IBC, seimic capability must be no less than existing battery/rack. | |||||
| CONTRACT CLIN SECTION | Contract Period | Table | PRODUCT CONFIGURATION | 5 Existing battery/modules are designed with an integral rack with the stackable modules. Other battery configurations with the same fit, form and function as the existing may have a separate rack. If the battery and rack are integral components in a stackable module configuration as the existing then insert "N/A" in the rack information. |
J.11 EXH SECL
| EXISTING SUPPORT EQUIPMENT | VENDOR PROPOSED PRODUCTS1 | ||||||||
| CLIN _______ | |||||||||
| NAS FACILITY TYPE | FACILITY TYPE DETAIL | Equipment Category | Equipment Nominal Voltage | Battery Type and Configuration | Part Description | Make and Model | Make and Model2 | CLIN# | QUANTITY |
| PCS, DCBUS and VOR | NAS | Battery Lift | 36VDC - 48VDC | Flooded Single-cell or Multi-cell Modules | Battery Lift | Vermette Load Jockey | |||
| Spill Response Kit | 24VDC - 48VDC | Flooded Single-cell or Multi-cell Modules | Base for < 2 gallon jars | Grainger 3WMR4 | |||||
| Extra Neutralizer for 2+ gallon jars | Grainger 49Y378 | ||||||||
| Eyewash | 24VDC - 480VDC | VRLA Front-access, Multi-cell Modules OR Stackable Grid Multi-cell Modules | 1 gallon Eyewash (all VRLA) | 2X ENCON FIRSTEP FIRSTFLUSH Dual Bottle Station (128 Fl.Oz Total) | |||||
| 24VDC - 48VDC | Flooded Single-cell or Multi-cell Modules | Sealed Cartridge-based Gravity Fed Eyewash (15 Minute continuous flow) (All flooded - lead-acid and NiCad) | ENCON Aquarion AQ 100 | ||||||
| PCS | AFSS, Large Consolidated TRACONS, ARSRs, ACEPS Test UPS, ASRs, ASDE and TDWR | Flexible Bus Bars and Hardware | 360VDC - 480VDC | VRLA Front-access, Multi-cell Modules | 50 - 300A, 360VDC | C&C 430-00172 | |||
| 350 - 600A, 360VDC | C&C 430-00173 | ||||||||
| 50 - 300A, 384VDC | C&C 430-00174 | ||||||||
| 350 - 600A, 384VDC | C&C 430-00175 | ||||||||
| 50 - 300A, 432VDC | C&C 430-00176 | ||||||||
| 350 - 600A, 432VDC | C&C 430-00177 | ||||||||
| 50 - 300A, 480VDC | C&C 430-00178 | ||||||||
| 350 - 600A, 480VDC | C&C 430-00179 | ||||||||
| Front-Access Conversion Kit | Black 150Ah/550W - 100Ah/350W for 360-384VDC | C&C 430-00168-BT | |||||||
| Beige 150Ah/550W - 100Ah/350W for 360-384VDC | C&C 430-00168-QB | ||||||||
| Black 150Ah/550W - 100Ah/350W for 432-480VDC | C&C 430-00169-BT | ||||||||
| Beige 150Ah/550W - 100Ah/350W for 432-480VDC | C&C 430-00169-QB | ||||||||
| Black 100Ah/350W - 150Ah/550W for 360-384VDC | C&C 430-00170-BT | ||||||||
| Beige 100Ah/350W - 150Ah/550W for 360-384VDC | C&C 430-00170-QB | ||||||||
| Black 100Ah/350W - 150Ah/550W for 432-480VDC | C&C 430-00171-BT | ||||||||
| Beige 100Ah/350W - 150Ah/550W for 432-480VDC | C&C 430-00171-QB | ||||||||
| Disconnect Enclosure | Sidemount disconnect enclosure | C&C Racks | |||||||
| Automated Battery Monitor (ABM) | 360VDC - 480VDC | VRLA Front-access, Multi-cell Modules Single String | Voltage / Resistance / Conductance Monitor | Alber BDS-40 | |||||
| VRLA Front-access, Multi-cell Modules Additional Strings | Voltage / Resistance / Conductance Monitor Additional Unit | Alber BDS-40 Plus Unit | |||||||
| Temperature Sensor | Alber BDS-40 Temperature Sensor | ||||||||
| CT | Alber BDS-40 CT | ||||||||
| Laptop | Alber BDS-40 Laptop | ||||||||
| Laptop Workstation | Alber BDS-40 Laptop Workstation Atlantic Metal WLAP2016 (grainger item # 3CTD3) | ||||||||
| Laptop Lock | Office Depot 196957 or equivalent | ||||||||
| Mini-UPS | APC BN-4001 | ||||||||
| EATON 3S55 | |||||||||
| 30 Module Harness with perminantly mounted sense leads | C&C, NSR, Power Battery | ||||||||
| 32 Module Harness with perminantly mounted sense leads | C&C, NSR | ||||||||
| 36 Module Harness with perminantly mounted sense leads | C&C, NSR | ||||||||
| 40 Module Harness with perminantly mounted sense leads | C&C, NSR | ||||||||
| DC BUS and VOR | RADIO COMMUNICATIONS AND NAVAIDS | Automated Battery Monitor (ABM) | 24VDC - 48VDC | VRLA Stackable Grid Multi-cell Modules | Voltage / Resistance / Conductance Monitor | Alber UXTM | |||
| Voltage / Resistance / Conductance Monitor Additional Unit | Alber UXTM Plus Unit | ||||||||
| Software | Alber UXTM Xplorer Enterprise Software | ||||||||
| Installation Kit | Alber UXTM Installation Kit | ||||||||
| Temperature Sensor Ambinet | Alber UXTM Temperature Sensors | ||||||||
| Temperature Sensor Negative Post | Alber UXTM Temperature Sensors | ||||||||
| Laptop | Alber UXTM Laptop | ||||||||
| Laptop Lockbox | Alber UXTM Laptop Lockbox | ||||||||
| 12 Cell Harness with perminantly mounted sense leads | Alber UXTM 12 Cell Harness | ||||||||
| 18 Cell Harness with perminantly mounted sense leads | Alber UXTM 18 Cell Harness | ||||||||
| 24 Cell Harness with perminantly mounted sense leads | Alber UXTM 24 Cell Harness | ||||||||
| VOR | NAVAIDS | Battery Ventilation Modificaiton | 24VDC - 48VDC | VRLA, Flooded Single-cell or Multi-cell Modules | Wall-mount Updraft Exhaust fan with damper 1/6 HP | Dayton 7DF68 | |||
| 12"x12" Actuated Intake vent | Dayton 3HHP3 | ||||||||
| Hydrogen sensor and base unit with 1% and 2% dry contacts | SBS-H2 | ||||||||
| Red warning beacon | Federal Signal 141ST-120 | ||||||||
| H/O/A switch | Dayton 20C789 | ||||||||
| 2 channel 7 day programmable timer with remote override | TORK DGLC200A-NC | ||||||||
| 1 Products include applicable OEM documentation. | |||||||||
| CLIN # CYPHER | 2 Equipment characteristics shall match existing equipment. | ||||||||
| x | x | x | x | x | x | ||||
| Contract Section | Contract Period | Table | PRODUCT CONFIGURATION |