Attachment J.14b DC BUS & VOR Installation Battery Monitoring System UXTM CAI Checklist.docx
DOCX document 46 KB Posted
- Attached to
- GNAS Battery System Equipment and Replacement Federal contract opportunity
- Solicitation number
- 6973GH-23-R-00094
About this file
This document is a checklist for contractor acceptance inspection of battery monitoring system installations. The checklist covers inspection of UXTM battery monitor equipment installation, documentation and familiarization materials, and setup of the UXTM system. Key items inspected include the battery monitor, harness and tab washers, laptop and security box, alarm cable connection, and facility cleanup. Documentation includes startup reports, product guides, installation guides, interface guides, protocol references, and on-site training materials. Battery configuration and setup is inspected, including resistance test interval, temperature scale, and voltage, current, temperature and resistance thresholds. Signatures are required from the SSC facility representative and contractor representative to confirm inspection.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Contract 693KA8-20-D-00011 Contract 693KA8-20-D-00011
DC BUS & VOR Installation Battery Monitoring System UXTM Contractor Acceptance Inspection (CAI) Checklist
| Inspection Date: __________________ |
| City:___________________ |
State:__________________
LOC
ID
FAC
Type
Equipment Type:
| Verification |
| Meets Requirements |
| Does Not Meet Requirements |
I. UXTM Equipment Installation
1. UXTM Battery Monitor, Harness, and Tab Washers
2. Laptop and Security Box
3. Alarm cable to DCBUS LMS-1000 Binary Channel 8 / DCBUS Config. (DCBUS Sites Only)
4. Facility Cleanup
II. UXTM Documentation and Familiarization
1. UXTM Startup Report
2. UXTM Product Description Guide (Alber)
3. UXTM Installation Guide (Alber)
4. UXTM Getting Started Guide (Alber)
5. DIM Getting Started Guide
6. UXTM Modbus Protocol Reference Guide (Alber)
8. UXTM Web Interface Guide (Alber)
9. UXTM Configurator Overview (Alber)
10. UXTM Wiring Schematic (Alber)
11. BXE System Installation Guide (Alber)
12. Battery Xplorer Enterprise Quick Start Instructions (Alber)
13. Battery Monitoring On Site Training
14. Site Drawings
III. UXTM Set Up
A. Battery Configuration and Setup Information
1. Resistance Test Day Interval (90 Days)
2. Cell Temperature Enable (Yes)
3. Cell Temperature Scale (Celsius required for DCBUS, Fahrenheit ok for VOR )
B. Thresholds
| String Alarm Thresholds |
| Value |
| Major |
| Minor |
Enable
| Latch |
| Enable |
| Latch |
| 1. High Ambient Temperature °C (°F) |
| 29 (84) |
| No |
| No |
| Yes |
| No |
| 2. Low Ambient Temperature °C (°F) |
| 18 (64) |
| No |
| No |
| Yes |
| No |
| 3. High Overall Voltage V DC DCBUS (2nd Gen VOR) [3rd Gen VOR] |
| 28.5 (42.8) [57] |
| No |
| No |
| Yes |
| No |
| 4. Low Overall Voltage V DC DCBUS (2nd Gen VOR) [3rd Gen VOR] |
| 22.5 (35.7) [45] |
| No |
| No |
| Yes |
| No |
| 5. High Discharge Current A DC DCBUS (2nd Gen VOR) [3rd Gen VOR] |
| 201 (110) [100] |
| No |
| No |
| Yes |
| No |
| 6. High Ripple Current A DC |
| 5 |
| No |
| No |
| Yes |
| No |
| 7. High Float Current mA DC |
| 5000 |
| No |
| No |
| Yes |
| No |
| 8. Low Float Current mA DC |
| 0 |
| No |
| No |
| Yes |
| No |
| 9. Cell to Ambient Delta °C (°F) |
| 11 (20) |
| No |
| No |
| Yes |
| No |
| Cell Alarm Thresholds |
| Value |
| Major |
| Minor |
Enable
| Latch |
| Enable |
| Latch |
| 1. High Cell Voltage (V DC) |
| 2.35 |
| No |
| No |
| Yes |
| No |
| 2. Low Cell Voltage (V DC) |
| 2.18 |
| No |
| No |
| Yes |
| No |
| 3. High Resistance (microhms) |
| 150% of avg. |
| Yes |
| No |
| No |
| No |
| 4. Low Resistance (microhms) |
| 0 |
| No |
| No |
| Yes |
| No |
| 5. High Cell Temperature °C (°F) |
| 32 (90) |
| Yes |
| Yes |
| No |
| No |
| 6. Low Cell Temperature °C (°F) |
| 10 (50) |
| No |
| No |
| Yes |
| No |
| 7. High Intercell Resistance (microhms) |
| 150% of avg. |
| No |
| No |
| Yes |
| No |
| Charger Cable / Intertier |
| Value |
| Major |
| Minor |
| 1. Charger Cable Measurement |
| N/A |
| No |
| No |
| No |
| No |
| 2. Intertier 1 -4 |
| Not |
| No |
| No |
| No |
| No |
Comments / Actions:
| Make: |
| Model: |
| Serial #: |
| kVA: |
UXTM DatakW:
Is Site using Local MDT instead of dedicated monitor?:_________________________ BXE Software Key:___________________________ UXTM Firmware Version:________________________ Configurator Tool Version Installed:________________________ BXE Software Version Installed:___________________________ Monitor Laptop Information Make:
Model:
Operating System (OS):
OS Version:
Hard Drive Size:
RAM:
Screen Size:
Processor:___________________________________
SIGNATURES:
SSC Facility Representative Name and SSC (or Center):
Signature:
Phone Number:
Contractor Representative Name and Company:
Signature:
Phone Number:
SEC J ATT J.14b 07/13/21 image1.emf image10.emf