This file is an example survey report attachment related to Federal Aviation Administration solicitation number 6973GH-23-R-00094 for GNAS Battery System Equipment and Replacement. The solicitation seeks to acquire battery system equipment and replacement parts for general navigation aids systems. Offerors must submit proposals by April 15th, 2023, with award anticipated by June 30th, 2023. The total value of the contract is estimated between $5-10 million. The solicitation is unrestricted and open to small businesses. The incumbent contractor is Avionics Corporation, whose existing contract expires September 30th, 2023.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building Ventilation Modification Site Survey Report
Location ID: SFK VOR Date: 04/14/2021 City, State Stonyfork, PA Surveyors: D. Williams
SITE SURVEY SUMMARY FINDINGS
This site is a 2nd generation Very High Frequency Omnidirectional Range (VOR) with Distance Measuring Equipment (DME). The SFK VOR has an existing battery string consisting of 18 KCT-660 single cell batteries (18 cells total). The batteries are rated at 660 amp-hours. The calculated maximum hydrogen evolution rate is 0.108 ft3/hr. at an equalized charge of 2.35 V per cell and a temperature of 90℉. The floor tiles and mastic are known to contain asbestos. The site is located in a relatively flat area. The area surrounding the site is gravel.
Panel board information is as follows:
o Panel board C o Federal Pacific Manufacturer (obsolete) o QO Load Center o Fused Disconnect at 60 amps o 120V 1 phase, 4 wire
SUMMARY PROJECT RECOMMENDATIONS
The building ventilation modifications include installing a new hydrogen monitoring system, exhaust fan, intake air damper, warning light, hand-off-auto switch, timer, bird screen, and insect screen. The hydrogen monitoring system will be designed to activate for 15 minutes once every 24 hours and provide one complete air change of the area occupied by the battery system. All exterior penetrations will be sealed watertight to maintain integrity of listed assembly. The new ventilation system is being installed to meet the latest edition of NFPA-1 requirements for battery room ventilation. The Hydrogen Monitoring System will operate according to the following:
1. HAND MODE
a. Manually activates the exhaust fan and intake damper.
2. AUTO MODE
a. An electrical timer will be set to activate an exhaust fan and actuated intake damper automatically for a minimum duration of 15 minutes every 24 hours.
b. When the H2 sensor senses the presence of hydrogen at 1% concentration per manufacturer recommendations, the signal will short the timer. This will override normal timer operation and initiate exhaust fan, intake damper and a warning light to implement ventilation.
The proposed equipment will require the installation of a new 20 AMP, single-pole breaker in the existing power panel (QO load center) and a new junction box for the hydrogen detector base unit. New conduit will be routed using new supports; existing supports will not be reused. All electrical work shall be performed in accordance with FAA-STD-1217H, all grounding shall be performed in accordance with FAA-STD-019F (or latest versions).
A new toggle switch will be installed in line of sight of the timer, H2 base unit, and hand-off auto switch. This disconnect switch will act as the disconnecting means for maintenance to the system as a whole (exhaust fan, intake damper, systems controls – H2 sensor, timer).
A summary of the hydrogen evolution and ventilation calculations as well as system safety factor calculations are shown below.
Battery Gassing Calculations
SFK VOR GASSING CALCULATIONS
TOTAL SQUARE FOOTAGE OF ROOM 483 FT2
HEIGHT OF ROOM 9.6 FT
TOTAL OF ROOM 4636.8 FT3
FAN CAPACITY 754 CFM
ASSUME %15 OF NON-OCCUPIED SPACE FOR EQUIPMENT AND
FURNITURE
ESTIMATED NON-OCCUPIED SPACE VOLUME (B5 @%85) 3941.28 FT3
HYDROGEN LOWER LIMIT (%1 BASED ON NFPA 1) 1%
ROOM CRITICAL VOLUME CV 39.4 FT3
N (NUMBER OF CELLS IN STRING) 18
K = AMOUNT OF HYDROGEN GAS, H2, RELEASED DURING
CHARGE, PROVIDED BY BATTERY MANUFACTURER 0.000269 FT3/MIN/CHARGING AMP AT 77℉
K (CORRECTED) 0.01614 FT3/HOUR/CHARGING AMP
C = CORRECTION FACTOR 90℉ TEMPERATURE 1.82
I=C*(FC/100)*AH (BATTERY RATING)
FC=0.031, BASED ON 2.35 V FLOATING VOLTAGE FOR
RECTANGULAR ACID BATTERIES
I 0.372 AMP
BATTERY RATING 660 AH
TOTAL HYDROGEN GAS RELEASE = H
H=N*I*K
H 0.108 FT3/HR
T=TIME TO REACH CRITICAL HYDROGEN CONCENTRATION
LEVELS
T=CV/H
T 15.2 DAYS
VENTILATION RATE REQUIRED TO DILUTE THE GAS, OA
REQUIRED
OA=H/(%1*60)
OA 0.180 CFM
L = LENGTH OF TIME GET ONE AIR EXCHANGE = TOTAL NET
ROOM VOLUME/FAN CAPACITY
L 5.23 MINUTES
RUN FAN ONCE A DAY FOR A MINIMUM 15 MINUTES OR AS
REQUIRED TO MAINTAIN ACCEPTABLE ENVIRONMENTAL
THRESHOLD
SAFETY FACTOR = SF = ACH VENT/ACH H2
ACH VENT = NUMBER OF CYCLES PER DAY/24
ACH VENT 0.04167
ACH H2 = H/CV
ACH H2 0.002745
SF(SAFETY FACTOR) 15
Task 1: Pre-Work Photo Survey Photographic Order
1.1 Photos of approximately where the battery unit is be mounted
1.2 Photos of all panels inside mechanical room
a. Panel faces
b. Inside panels
c. Panel schedules
1.3 Photos of Equipment room (each wall)
1.4 Photos of VOR exterior from 4 corners
1.5 Photo of existing Grounding Bars, if available
1.6 Photos of HVAC Equipment inside room (Nameplate & Location)
1.7 Photo of existing Dampers and Exhaust Fan (Nameplate & Location)
1.8 Updated layout of VOR (PDF, DWG, DGN)
Task 2: General Information
2.1 FAA Technician Name Nicholas Keim
2.2 FAA Technician Contact Info Nicholas.Keim@faa.gov
2.3 Site Address 41.695293 / -77.419868
2.4 Electrical Utility Provider First Energy
2.5 Electrical Utility POC 800-433-7794
2.6 Electrical Meter Number 5 001 158 200
2.7 Does the facility have Asbestos? Yes, tiles & mastic
2.8 Does the facility have Lead? Pains assumed to be lead based by SSC
Task 3: Exhaust Fan Installation
3.1 What is the wall construction where the fan will be
installed? Drywall / gyp board
3.2 What are the room dimensions? (LxWxH) See sketch for dimensions
3.3 Does the space have an existing HVAC unit? Yes
3.4 Does it maintain the temperature below 90°F Yes
3.5 What electrical panel will feed new exhaust fan and
timer? Are photos included?
Panel C – 4 holes available in
QO load center*
3.6 Is there an existing exhaust fan? No
3.7 If so, does it function? N/A
3.8 Is there an existing intake damper? No
3.9 If so, does it function? N/A
3.10 Is there an existing Timer, H2 Sensor, or Warning
Light? No
3.11 Will any of the above mentioned existing equipment
be reused?
N/A
3.12 Will other loads need to be relocated? No
3.13 If so, describe how this can be accomplished. N/A
3.14 Where does the SSC prefer the disconnecting means for
this ventilation system: a) Feeder Breaker, b) at the controls (H2 system), or, c) at the exhaust fan b) at the controls
3.15 Will equipment need to be relocated for the installation of the new equipment? No
Task 4: Battery Information
4.1 What is the string float voltage for the existing battery system? 2.25 Volts per cell
4.2 What is the battery type and model#? KCT-660
4.3 How many batteries are in the system? 18
4.4 How many cells in each battery? 1
Notes : *Obsolete Federal Pacific Electric (FPE) installed (Panel C & D)
Task 5: Existing Floor Plan Sketch
N.I.C
PANEL D
PANEL C
18 GNB-100A17
BATTERIES
A/C UNIT
’3
’9 27’8”8’4”
BUILDING FLOOR PLAN
NTS
NORTH
Task 6: Proposed Equipment Location Sketch
N.I.C N.I.C
N.I.C
PANEL D
PANEL C
18 GNB-100A17
BATTERIES
A/C UNIT
H2 SENSOR OVER
BATTERIES
NEW
EXHAUST FAN
NEW INTAKE
DAMPER
NEW HOOD
ABOVE INTAKE
DAMPER
WARNING
LIGHT
BUILDING FLOOR PLAN
NTS
SITE SURVEY PHOTOS
VOR (Located off airfield)
Panel C
Panel C Schedule Panel C
North Wall East Wall
South Wall West Wall
GNB Batteries
QO Load Center 60A Fused Disconnect
QO Load Center