SYMBOL DESCRIPTION
SITE ELECTRICAL LEGEND
EXISTING MANHOLE. SUBSCRIPT INDICATES THE MANHOLE NUMBER.
EMH1
EUE REMOVE UNDERGROUND ELECTRICAL DUCT BANK
EUC EXISTING UNDERGROUND TELECOMMUNICATIONS DUCT BANK
EUC REMOVE UNDERGROUND TELECOMMUNICATIONS DUCT BANK
EXISTING TELECOMMUNICATIONS HANDHOLE. SUBSCRIPT INDICATES THE HANDHOLE
NUMBER.ECHH1
EUE EXISTING UNDERGROUND ELECTRICAL DUCT BANK
UE UNDERGROUND ELECTRICAL DUCT BANK
UC UNDERGROUND TELECOMMUNICATIONS DUCT BANK
ELECTRICAL HANDHOLE. SEE A3/EP502 FOR DETAIL.
HH
SYMBOL DESCRIPTION
SINGLE LINE DIAGRAM
PANELBOARD. WHEN ADDITIONAL SYMBOL(S) ARE INCLUDED, THEY INDICATE
THE FOLLOWING:
1H1
DRAW-OUT TYPE CIRCUIT BREAKER WITH NUMBER OF POLES AND TRIP
RATING AS INDICATED.
ADDITIONAL CIRCUIT BREAKER SUBSCRIPTS INDICATE THE FOLLOWING:
3P 100 A
PARALLEL CONNECTED SURGE PROTECTIVE DEVICE. SEE SURGE
PROTECTIVE DEVICE SCHEDULE ON SHEET EP701.
SPD
MULTIFUNCTION DIGITAL POWER CIRCUIT MONITOR.
KEY INTERLOCK
POWER TRANSFORMER WITH DELTA CONNECTED PRIMARY, WYE
CONNECTED SECONDARY AND RATING AS INDICATED.
M
K
SOLID STATE ELECTRONIC TRIP CIRCUIT BREAKER WITH FIELD
ADJUSTABLE LONG TIME PICKUP, SHORT TIME PICKUP, SHORT TIME
DELAY, AND INSTANTANEOUS TRIP FUNCTIONS. INCLUDE ADJUSTABLE
GROUND FAULT PICKUP AND GROUND FAULT DELAY TRIP FUNCTIONS
WHERE GROUND FAULT PROTECTION IS INDICATED.
GFP - CIRCUIT BREAKER EQUIPPED WITH INTEGRAL GROUND FAULT
PROTECTION.
MAIN CIRCUIT BREAKER. SEE PANEL SCHEDULE FOR SIZE. IF
NOT PRESENT, PANELBOARD WITH MAIN LUGS ONLY.
ET -
DRY TYPE TRANSFORMER. SUBSCRIPT INDICATES THE
TRANSFORMER SIZE. SEE TRANSFORMER SCHEDULE ON SHEET
EP701. SEE A1/EP601 FOR GROUNDING DIAGRAM. SEE SINGLE
LINE DIAGRAM FOR TRANSFORMER SIZE.
T T30
MOUNTINGSYMBOL DESCRIPTION
POWER DISTRIBUTION
SURFACE MOUNTED PANELBOARD
GROUNDING BUS BAR, SUBSCRIPT INDICATES NAME.
REFER TO A3/EP501 FOR DETAIL.
72" AFF TO TOP
18" AFF TO TOP
NA
COMBINATION MAGNETIC STARTER/DISCONNECT SWITCH IN
NEMA 1 ENCLOSURE UNLESS OTHERWISE INDICATED. SEE
MOTOR STARTER SCHEDULE ON SHEET EP701 FOR STARTER
CHARACTERISTICS, AND HOME RUN MOTOR BRANCH CIRCUIT
SIZE. MOTOR BRANCH CIRCUIT SIZE SHALL BE THE SAME FROM
THE STARTER TO MOTOR. MINIMUM SHORT CIRCUIT RATING
SHALL MATCH THE UPSTREAM OVERCURRENT PROTECTIVE
DEVICE. SEE SHEET EP501 FOR STARTER WIRING DIAGRAMS.
SUBSCRIPTS INDICATE THE FOLLOWING:
H-30-3Φ 3R
600V, 3P, NON-FUSED DISCONNECT SWITCH. ALL DISCONNECT
SWITCHES SHALL BE NEMA 1 UNLESS OTHERWISE INDICATED.
SUBSCRIPTS INDICATE THE FOLLOWING:
30A - 3R -
30A 3R
H-30-3Φ
PHASE
MOTOR HP RATING
H - 480V L1- 120V L2 - 208V
72" AFF TO TOP
72" AFF TO TOP
NEMA ENCLOSURE OTHER THAN NEMA 1 (3R, 4X, ETC...)
AMPERE RATING
3R - NEMA ENCLOSURE OTHER THAN NEMA 1 (3R, 4X, ETC...)
POWER DISTRIBUTION EQUIPMENT CODES
1 H 1
1,2,3 - SEQUENCE
H - 480Y/277V L - 208Y/120V
FLOOR LEVEL
EQUIPMENT CODE:
GENERAL NOTES
A. SEE REFLECTED CEILING PLANS FOR EXACT LOCATION OF LUMINAIRES AND DEVICES.
B. INSTALL ALL EQUIPMENT AND DEVICES AT THE HEIGHT INDICATED. REFER TO ARCHITECTURAL
INTERIOR ELEVATIONS FOR SPECIAL MOUNTING HEIGHTS AND LOCATIONS OF ELECTRICAL AND
COMMUNICATIONS DEVICES. MOUNTING HEIGHTS AND LOCATIONS INDICATED ON
ARCHITECTURAL ELEVATIONS TAKE PRECEDENCE OVER OTHER MOUNTING HEIGHTS AND
LOCATIONS.
C. LUMINAIRE TYPES INDICATED AS FOLLOWS: UPPER CASE LETTER WITH NUMERAL DENOTES
FIXTURE TYPE (SEE LUMINAIRE SCHEDULE), LOWER CASE LETTER (IF SHOWN) DENOTES
SWITCHING ARRANGEMENT.
D. ALL MATERIALS AND EQUIPMENT SHALL BE LISTED AS COMPLYING WITH THE APPLICABLE
STANDARDS OF UNDERWRITER'S LABORATORIES, INC OR OTHER APPROVED LISTING
AGENCIES.
E. CONDUCTOR AMPACITIES ARE BASED ON 60° C COPPER FOR #12 AWG THROUGH #1 AWG
CONDUCTORS. CONDUCTOR AMPACITIES ARE BASED ON 75° C COPPER FOR CONDUCTORS
LARGER THAN #1 AWG.
F. ALL CONDUIT SIZES ARE BASED ON ELECTRICAL METALLIC TUBING (EMT) WITH TYPE
THHN/THWN COPPER CONDUCTORS. ADJUST CONDUIT SIZE AS REQUIRED FOR OTHER
CONDUIT MATERIALS AND CONDUCTOR TYPES.
G. THE PANELBOARD SUPPLIER SHALL BE RESPONSIBLE FOR PROVIDING OVERCURRENT
PROTECTIVE DEVICES THAT ARE SELECTIVELY COORDINATED. REFER TO SPECIFICATION
SECTION 26 28 01.00 10 FOR REQUIREMENTS.
H. COORDINATE LOCATION AND ROUTING OF ALL CONDUITS WITH OTHER TRADES AND SYSTEMS
TO PROVIDE A COORDINATED INSTALLATION AND TO ASSURE MAXIMUM ACCESSIBILITY TO ALL
SYSTEMS. ALL JUNCTION BOXES AND PULL BOXES SHALL REMAIN ACCESSIBLE.
I. WHEN CONTRACTOR FURNISHED EQUIPMENT INCLUDING BUT NOT LIMITED TO ARCHITECTURAL
HARDWARE (IE WINDOW SHADES, OVERHEAD COILING DOORS AND GRILLS, POWER OPERATED
DOORS, ETC...), AND HVAC EQUIPMENT SIZE OR ELECTRICAL CHARACTERISTICS PROVIDED
DIFFERS FROM SIZE OR ELECTRICAL CHARACTERISTICS INDICATED OR SPECIFIED, MAKE ALL
NECESSARY ADJUSTMENTS TO ELECTRICAL BOXES, CONDUIT, WIRING, DISCONNECT DEVICES,
BRANCH CIRCUIT PROTECTION, AND RELATED ELECTRICAL DISTRIBUTION EQUIPMENT
INCLUDING ANY ELECTRICAL REDESIGN AS REQUIRED TO ACCOMMODATE EQUIPMENT
ACTUALLY PROVIDED.
J. PROVIDE SEPARATE NEUTRAL CONDUCTOR FOR EACH 277V AND 120V BRANCH CIRCUIT, UON.
MULTIPLE 20A BRANCH CIRCUITS FROM THE SAME PANELBOARD MAY BE COMBINED IN A
SINGLE 1/2" CONDUIT HOME RUN, MAXIMUM OF (3) CIRCUIT PER HOME RUN.
K. ALL CEILING MOUNTED LIGHTING OCCUPANCY SENSORS AND FIRE ALARM SMOKE DETECTORS
SHALL BE LOCATED SUCH THAT THERE IS A MINIMUM OF 36” BETWEEN THE SENSOR AND ANY
HVAC RETURN/SUPPLY DIFFUSERS.
ABBREVIATIONS
A AMPERES
AFC
AFF
HV
AFG
INC
AIC
JB
ATS
KAIC
AWG
KV
BFC
KVA
BFG
KVAR
C
KW
CAB
KWH
CATV
LAN
CCTV
LED
CKT
LTG
CL
m
CLG
mm
CT's
MAX
CU
MCB
DISC
MCC
DWG
MCP
EA
MFR
EF
MIN
EMT
MISC
EQUIP
MTR
EUH
MTD
EWC
MTS
EWH
N.C.
EXH
N.O.
EXIST
NA
FA
NC
FLUOR
NEC
GEN
NFPA
GFI
PNL
GFGI
PVC
GFP
REC
RGS
GND
TEL
HGT
TYP
HOA
UON
HP
V
VAV
W
G
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
HIGH VOLTAGE
ABOVE FINISHED GRADE
INCANDESCENT
AMPERES INTERRUPTING CAPACITY
JUNCTION BOX
AUTOMATIC TRANSFER SWITCH
KILO-AMPERES INTERRUPTING
CAPACITY
AMERICAN WIRE GAUGE
KILO-VOLTS
BELOW FINISHED CEILING
KILO-VOLTS-AMPERES
BELOW FINISHED GRADE
KILO-VOLTS-AMPERES REACTIVE
CONDUIT
KILO-WATTS
CABINET
KILO-WATT-HOURS
CABLE TELEVISION
LOCAL AREA NETWORK
CLOSED CIRCUIT TELEVISION
LIGHT-EMITTING DIODE
CIRCUIT
LIGHTING
CENTERLINE
METER
CEILING
MILLIMETER
CURRENT TRANSFORMERS
MAXIMUM
COPPER
MAIN CIRCUIT BREAKER
DISCONNECT(ING)
MOTOR CONTROL CENTER
DRAWING(S)
MOTOR CIRCUIT PROTECTOR
EACH
MANUFACTURER
EXHAUST FAN
MINIMUM
ELECTRICAL METALLIC TUBING
MISCELLANEOUS
EQUIPMENT
MOTOR
ELECTRIC UNIT HEATER
MOUNTED
ELECTRIC WATER COOLER
MOUNTING
ELECTRIC WATER HEATER
MANUAL TRANSFER SWITCH
EXHAUST
NORMALLY CLOSED
EXISTING
NORMALLY OPEN
FIRE ALARM
NOT APPLICABLE
FLUORESCENT
NURSE CALL
GROUND
NATIONAL ELECTRICAL CODE
ENGINE GENERATOR SET
NATIONAL FIRE PROTECTION
ASSOCIATION
GROUND FAULT INTERRUPTER
GROUND FAULT CIRCUIT INTERRUPTER
PANEL
GOVERNMENT FURNISHED,
GOVERNMENT INSTALLED
POLYVINYL CHLORIDE
GROUND
RECEPTACLE
HEIGHT
RIGID GALVANIZED STEEL
HAND-OFF-AUTOMATIC
TELEPHONE
HORSEPOWER
TYPICAL
UNLESS OTHERWISE NOTED
VOLTS
GFCI
GROUND FAULT PROTECTION
WAP
VARIABLE AIR VOLUME UNIT
WP
WATTS
XFMR
WIRELESS ACCESS POINTHVAC HEATING/VENTILATING / AIR
CONDITIONING WEATHER PROOF
MTG
TRANSFORMER
AHU AIR HANDLING UNIT
CH CHILLER
UH UNIT HEATER
VA VOLT-AMPERES
SF SUPPLY FAN
SYMBOL DESCRIPTION MOUNTING
MISCELLANEOUS
KEY NOTE SYMBOL. 00
ELECTRICAL GROUND
CONDUCTOR CONNECTION
LIGHTING CONTACTOR.
POINT OF REMOVAL, DEMOLITION.
POINT OF CONNECTION, EXISTING TO NEW WORK.
NA
NA
NA
5'-0" AFF TO TOP
NA
NA
LC
FCU/A
AS INDICATED
SYMBOL DESCRIPTION MOUNTING
EQUIPMENT CONNECTIONS
JUNCTION BOX OR PULL BOX
NAMOTOR CONNECTION
AS REQUIREDCONNECTION TO EQUIPMENT LEADS, TERMINAL STRIPS OR
CONTROL PANEL INCLUDING ALL CONDUCTORS, CONDUIT,
FLEXIBLE CONDUIT, JUNCTION BOXES, CONNECTORS, FITTINGS,
ETC., REQUIRED FOR PROPER CONNECTION. COORDINATE
EXACT LOCATION WITH THE SUPPLIED EQUIPMENT. SUBSCRIPT
INDICATES EQUIPMENT IDENTIFICATION.
J
M
E
SYMBOL DESCRIPTION
LIGHTNING PROTECTION SYSTEM
LIGHTNING PROTECTION SYSTEM ROOF CONDUCTOR.
GL
DN1
A - STANDING SEAM METAL ROOF MOUNTED AIR TERMINAL.
SEE A2/EQ501 FOR DETAIL.
AIR TERMINAL.
SUBSCRIPTS INDICATE THE FOLLOWING:
LIGHTNING PROTECTION SYSTEM GROUND LOOP CONDUCTOR. BURY IN DIRECT
CONTACT WITH EARTH AT 24" BELOW FINISHED GRADE.
GROUND RODS BONDED TO GROUND LOOP CONDUCTOR. SEE A1/EQ501 FOR DETAIL.
BONDING CONNECTION.
THROUGH ROOF CONDUCTOR DETAIL "DN1". SEE C3/EQ501 FOR DETAIL.
DN2 ROUTE LIGHTNING PROTECTION CONDUCTOR EXPOSED DOWN TO LOWER ROOF.
PANELBOARD DESIGNATION.
CIRCUIT DESIGNATION.
SYMBOL DESCRIPTION
CONDUIT AND CONDUCTORS
BRANCH CIRCUIT WIRING IN CONDUIT. 1/2"C - 2#12 + 1#12 GND UON. PROVIDE
ADDITIONAL SWITCHED CONDUCTORS OR TRAVELER CONDUCTORS FOR LIGHTING
CIRCUITS AS REQUIRED TO SUPPORT THE INDICATED SWITCHING.
HOMERUN TO PANELBOARD: 1ALN1 - 1,3,5
WIRING DEVICES
DESCRIPTION MOUNTING
18" AFF
SYMBOL
NOTES: ALL MOUNTING HEIGHTS ARE TO TOP, UON
SUBSCRIPTS FOR RECEPTACLES INDICATE THE FOLLOWING:
G - +48" -
WP - IN-USE WEATHER-PROOF COVER.
MOUNT AT 48" AFF TO CENTER. OTHER MOUNTING HEIGHTS AS INDICATED.
INTEGRAL GFCI.
20A, 125V DUPLEX RECEPTACLE.
48" AFF TO
CENTER
ROTARY COUNTDOWN TIMER FOR CEILING FAN
CONTROL. MAXIMUM TIME SETTING OF 30 MINUTES.
120V, 20A. SWITCH SHALL BE RATED TO DRIVE TWO FANS
MINIMUM AT FULL SPEED.
S T a,b SWITCH LEG(S). PROVIDE SEPARATE PUSHBUTTON FOR
EACH SWITCH LEG.
DIGITAL LIGHTING CONTROL DEVICES
NOTES:
1. THE DIGITAL LIGHTING CONTROL SYSTEM SHALL CONSIST OF LOCAL RELAY PACKS,
OCCUPANCY SENSORS, AND DIGITAL SWITCHES. THE NUMBER OF RELAYS SHALL MATCH THE
NUMBER OF LIGHTING SWITCH LEGS IN EACH ROOM.
2. PROVIDE JUNCTION BOX FOR RELAY PACKS. ALL JUNCTION BOXES CONTAINING ELECTRICAL
COMPONENTS SHALL BE LOCATED IN AN ACCESSIBLE LOCATION ABOVE ACCESSIBLE CEILINGS.
LABEL EACH JUNCTION BOX CONTAINING ELECTRICAL COMPONENTS TO INDICATE ITS
FUNCTION. PROVIDE BOX DIVIDER FOR EACH BOX CONTAINING LINE VOLTAGE AND LOW
VOLTAGE WIRING.
3. IN ROOMS WITH TILED FINISHED CEILINGS, PROVIDE IDENTIFICATION PLATE ON THE CEILING
SYSTEM T-FRAME INDICATING LOCATION OF JUNCTION BOXES ABOVE CONTAINING ELECTRICAL
COMPONENTS.
4. LOW VOLTAGE CONTROL WIRING SHALL BE IN ACCORDANCE WITH THE MANUFACTURERS
RECOMMENDATIONS.
5. ALL LINE VOLTAGE WIRING SHALL BE #12 AWG IN 1/2” CONDUIT.
6. ALL LOW VOLTAGE WIRING, INCLUDING 0-10V DIMMING WIRING CABLE SHALL BE IN 1/2” CONDUIT.
7. THE LINE VOLTAGE AND LOW VOLTAGE WIRING SHALL BE SEPARATED IN ACCORDANCE WITH
NFPA 70.
8. PROVIDE ADDITIONAL OCCUPANCY SENSORS AS REQUIRED TO PROVIDE ADEQUATE COVERAGE
OF CONTROLLED AREA.
9. SETTINGS OF OCCUPANCY SENSORS: MANUAL “ON”, AUTO “OFF”, 10 MINUTE TIME DELAY UON.
10. PROVIDE ALL COMPONENTS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM.
11. INSTALL COMPONENTS PER MANUFACTURER'S APPROVED SHOP DRAWINGS.
12. REFER TO SHEET EL601 FOR TYPICAL LIGHTING CONTROL SYSTEM WIRING DIAGRAM.
48" AFF TO
CENTER
SYMBOL DESCRIPTION MOUNTING
DIGITAL SWITCH. SUBSCRIPTS INDICATE THE FOLLOWING:
DIGITAL, DUAL-TECHNOLOGY OCCUPANCY SENSOR. SUBSCRIPT
INDICATES THE FOLLOWING:
CEILING
a,b SWITCH LEG(S)-
DIGITAL, LOCAL LIGHTING RELAY PACK WITH CONTACT FOR FIRE
ALARM INTERFACE. SUBSCRIPT INDICATES THE FOLLOWING:
CEILING
SWITCH LEG(S)-
LR
DIGITAL LIGHTING CONTROL SYSTEM SEQUENCE
OF OPERATIONS
SYMBOL DESCRIPTION
A
LIGHTING
MANUAL “ON” VIA DIGITAL WALL SWITCH(ES).
AUTO “OFF” VIA ROOM DIGITAL OCCUPANCY SENSOR(S).
DESCRIPTION MOUNTINGSYMBOL
LUMINAIRES
PENDANT MOUNT FIXTURE, UON. PENDANT
PENDANT
WALL MOUNTED LUMINAIRE. WALL
EXIT SIGN. SHADED PORTION DENOTES FACE(S). DIRECTIONAL
ARROWS AS INDICATED.
4" ABOVE TOP OF
DOOR FRAME TO
BOTTOM OF
FIXTURE
NOTES:
1. SEE LIGHTING FIXTURE SCHEDULE FOR FIXTURE TYPES.
2. OTHER FIXTURE DIMENSIONS AND SHAPES ARE AS INDICATED ON LIGHTING PLANS.
PENDANT MOUNT FIXTURE, UON.
NORMAL POWER.
EMERGENCY POWER / INVERTER POWER
SYMBOL DESCRIPTION
SITE LIGHTING
EXISTING POLE MOUNTED AREA LUMINAIRE, SINGLE HEAD.
EX
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
As indicated
E
LE
C T
R
IC
A L
LE
G
E N
D A
N D
A B
B R
E V
IA
T
IO
N
S
EG001
RLW RLW NGZ
12854135
UG ELEC
10 W
21.9
EUE
EMH839
BUILDING 2146
EUC
EUC
EUC
EUC
E U
C
EUC
EUC
EUC
X
EUE
X
X
X
X
X
X X
X
EUE
ECHH1
EUE
EUE
X X X X X X X X X X X X X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
EUE
EXISTING HANDHOLE
SERVING VEHICLE
GATE POWER
CIRCUIT.
X X X
X
X
X X
X X
X X
EX EX
EX
EX
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
SHEET NOTES:
NOTES:
1'-0" = 1'-0" GRAPHIC SCALE
0 3"2"1" 4"½"
N PLAN
NORTH
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
1" = 20'-0"
S
IT
E U
T
IL
IT
Y
P
LA
N
E
LE
C T
R
IC
A L
D E
M O
LI
T
IO
N
ED101
RLW RLW NGZ
12854136
1" = 20'-0"A1
SITE PLAN - ELECTRICAL UTILITY - DEMOLITION
1 APPROXIMATE LOCATION OF ELECTRICAL ROOM HOUSING PANEL DP-1E
SERVING EXISTING TRAILERS.
2 REMOVE 2 1/2" CONDUIT WITH (3) 350KCMIL + (1)#3G SERVING EXISTING
TRAILER 150KVA TRANSFORMERS, ASSOCIATED DISCONNECT, AND PANELS
QUANTITY OF TWO. CONDUITS MAY BE ABANDONED WHERE ROUTED
UNDER THE FIRE LANE AND EXISTING BUILDING 2146. REMOVE FEEDERS
BACK TO PANEL DP-1E LOCATED IN BUILDING 2146. UPDATE PANEL
SCHEDULE FOR PANEL DP-1ETO IDENTIFY BREAKERS AS "SPARE".
3 REMOVE 200A, 600V, 3P DISCONNECT, METER SOCKET ENCLOSURE AND
400A, 208Y/120V, 3 PHASE, 4 WIRE PANELBOARD SERVING EXISTING
TRAILERS.
4 REMOVE AND PROTECT EACH 150KVA, 480V-208Y/120V, 3 PHASE, 4 WIRE DRY
TYPE TRANSFORMER SERVING THE EXISTING TRAILERS. DELIVER THE
TRANSFORMERS TO PUBLIC WORKS WAREHOUSE AT BUILDING 617 AFTER
REMOVAL.
5 REMOVE EXISTING POLE TOP LIGHT FIXTURE, POLE AND BASE. POLE TOP
FIXTURES ARE SERVED FROM THE 400A PANELS SERVING THE EXISTING
TRAILERS SCHEDULED FOR DEMOLITION. REMOVE ALL UNDERGROUND
CONDUIT AND WIRING BACK TO THE PANEL SERVING THE POLE TOP
LIGHTING FIXTURES.
6 EXISTING PERIMETER FENCE SECURITY LIGHT TO REMAIN.
7 REMOVE UNDERGROUND TELECOMMUNICATIONS DUCT SERVING TRAILERS.
REMOVE OUTSIDE PLANT COPPER AND FIBER OPTIC CABLES BACK TO HAND
HOLE ECHH1.
8 EXISTING 1"C - (2)#4 + (1) #8 GND. SERVING VEHICLE GATE CONTROLLER.
REMOVE EXISTING CIRCUIT AS INDICATED AND RE-FEED VEHICLE GATE AS
INDICATED ON SHEET ES100. GATE CONTROLLER IS FED FROM PANEL LP-1E
IN BUILDING 2146 VIA A 40A, 2P CIRCUIT BREAKER.
9 EXISTING 1"C - (2)#4 + (1)#8 GND TO VEHICLE GATE.
10 EXISTING TRAILER TO BE REMOVED BY OTHERS.
11 REMOVE 2 1/2" CONDUIT WITH (3) #10 + (1)#10G SERVING EXITING PUMP
STATION.
12 REMOVE 2 1/2" CONDUIT WITH (3) 350KCMIL + (1)#3G SERVING EXITING
TRAILER 150KVA TRANSFORMERS, QUANTITY OF TWO. CONDUITS MAY BE
ABANDONED WHERE ROUTED UNDER THE FIRE LANE AND EXISTING
BUILDING 2146. REMOVE FEEDERS BACK TO PANEL DP-1E LOCATED IN
B2146. UPDATE PANEL SCHEDULES FOR DP-1E.
KEY NOTES: 00 A. THE LOCATION AND COMPOSITION OF EXISTING UTILITIES ARE SHOWN IN AN
APPROXIMATE MANNER ONLY. FIELD VERIFY THE EXACT LOCATION OF
EXISTING UTILITIES PRIOR TO ANY EXCAVATION WORK.
B. PRIOR TO PENETRATING CONDUITS INTO EXISTING MANHOLES, INVESTIGATE
THE CONDITION OF THE EXISTING STRUCTURE AND DETURMINE THE
APPROPRIATE MEANS AND METHODES TO AVOID ANY DAMAGE TO THE
EXISTING STRUCTURE AND UTILITIES ROUTED WITHIN IT.
E
B
1 6
EUE
UE
EMH839
UC
EUE
OSF BUILDING
EUC
EUC
BUILDING 2146
ECHH1
EUE
HH
HH
HH
EXISTING HANDHOLE
SERVING VEHICLE
GATE POWER
CIRCUIT.
EX
HH
LEVEL 2 SECURITY FENCE
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
KEY NOTES 00
NOTES:
1" = 20' GRAPHIC SCALE
20'0 60'40' 80'10'
N PLAN
NORTH
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 9:
A
M
1" = 20'-0"
S
IT
E U
T
IL
IT
Y
P
LA
N
E
LE
C T
R
IC
A L
E
A S
T
ES100
RLW RLW NGZ
12854137
1" = 20'-0"A1
SITE PLAN - ELECTRICAL UTILITY - EAST
1 EXISTING PERIMETER FENCE SECURITY LIGHT TO REMAIN.
2 2-WAY CONCRETE ENCASE DUCTBANK FOR OUTSIDE PLANT
TELECOMUNICATIONS CABLES TO TELECOMUNICATIONS TERMINATION
EQUIPMENT. SEE C1/EP502 FOR DETAIL. CONCRETE ENCASEMENT IS NOT
REQUIRED WHERE ROUTED UNDER BUILDING CONCRETE SLAB. ONE DUCT
SHALL REMAIN EMPTY.
3 2-WAY CONCRETE ENCASE DUCTBANK. SEE C4/EP502 FOR DETAIL. SEE
SHEET EP600 FOR FEEDER SIZE.
4 EXTEND DUCTBANK TO TELECOMMUNICATIONS TERMINATION EQUIPMENT.
SEE SHEET EP101 FOR TERMINATION LOCATION. PROVIDE WATER TIGHT
SEAL ON SPARE CONDUIT. SEE A4/EP600 FOR OUTSIDE PLANT CABLE
TERMINATION REQUIREMENTS. COORDINATE EXACT ROUTING WITH
STRUCTURAL FOUNDATIONS.
5 EXTEND DUCTBANK TO PANEL 1H1 LOCATION. TURN CONDUITS UP
BENEATH PANEL 1H1. SEE SHEET EP600 FOR SIZE AND QUANTITY OF
CONDUCTORS. ONE DUCT SHALL REMAIN EMPTY. PROVIDE CONDUIT CAP
ON SPARE CONDUIT. COORDINATE EXACT ROUTING WITH STUCTURAL
FOUNDATIONS.
6 EXISTING 8-WAY CONCRETE ENCASED DUCTBANK. UTILIZE ONE OF THE
TWO 4" SPARE CONDUITS TO ROUTE NEW FEEDER FROM SWITCHGEAR 2146
TO PANEL 1H1. SEE SHEET EP600 FOR FEEDER CONDUCTOR SIZE AND
QUANTITY.
7 SPLICE TO EXISTING 50 PAIR OUTSIDE PLANT COPPER AND 48 STRAND
SINGLE MODE FIBER IN EXISTING HANDHOLE. COORDINATE ALL WORK IN
EXISTING HANDHOLE WITH CONTRACTING OFFICER.
8 SEE SHEET ES101 FOR CONTINUATION.
9 INTERCEPT AND SPLICE TO EXISTING (2)#4 + (1)#8 GND BRANCH CIRCUIT
SERVING VEHICLE GATE. EXTEND CIRCUIT TO SECOND SPLICE POINT AS
INDICATED.
10 1"C - (2)#4 + (1)#8 GND FOR VEHICLE GATE. DIRECT BURY CONDUIT AT 36"
BFG TO TOP.
11 EXISTING 1"C - (2)#4 + (1)#8 GND TO VEHICLE GATE.
EXISTING SWGR 2146
EUE
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
KEY NOTES 00
NOTES:
1" = 20' GRAPHIC SCALE
20'0 60'40' 80'10'
N PLAN
NORTH
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 9:
A
M
1" = 20'-0"
S
IT
E U
T
IL
IT
Y
P
LA
N
E
LE
C T
R
IC
A L
W
E S
T
ES101
RLW RLW NGZ
12854138
1" = 20'-0"
A1
SITE PLAN - ELECTRICAL UTILITY - WEST
1 EXISTING 8-WAY CONCRETE ENCASED DUCTBANK. UTILIZE ONE OF THE TWO
4" SPARE CONDUITS TO ROUTE NEW FEEDER FROM SWITCHGEAR 2146 TO
PANEL 1H1. SEE SHEET EP600 FOR FEEDER CONDUCTOR SIZE AND
QUANTITY.
2 SEE SHEET ES100 FOR CONTINUATION.
T
LR
PE
LR
LR
LR
STORAGE
C1C1B C1 C1 C1
C1 C1 C1C1B C1
C1C1 C1B C1 C1B
C1B C1 C1C1 C1B
C1C1B C1 C1 C1B
C1B C1 C1C1 C1B
C1C1 C1B C1 C1
C1 C1 C1C1B C1
C1C1B C1 C1 C1B
C1B C1 C1C1 C1B
C1C1B C1 C1 C1B
C1B C1 C1C1 C1B
C1C1 C1B C1 C1
C1 C1 C1C1B C1
C1C1B C1 C1 C1B
C1B C1 C1C1 C1B
C1B C1
C1B
C1
C1
C1C1B C1
C1C1 C1B ab b a b d c cd d ba a b a c d dc c ab b a b d c cd d ba a b a c d dc c ab b a b d c cd d ba a b a c d dc c ab b a b d c cd d ba a b a c d dc c c d d c c ba a ab a,b c,dc,d a,b a,b c,dc,d a,ba,b c,dc,d a,ba,b c,dc,d a,b
X1
X1
X1 c,d a,b a,b c,d
W1DB
W1DB
W1DB
W1DB
W1DB
W1DB
W1DB
W1DB
W1DB
W1DB
W1DB W1DB
W1DBW1DB
W1DB
W1DB
1L1-12 c,d
1L1-14
1L1-16
1L1-18
(VIA LC-1)
(VIA LC-1)
STORAGE
C1 C1B b a
C1
1 2 3 6
F
E
D
C
B
A
4 5
C1 b aa a,b
X1
C1 C1B C1C1 C1B d c cd d a,b
1L1-21 c,d
1L1-23
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
KEY NOTES 00
SHEET NOTES:
NOTES:
0 5'
1/8" = 1'-0" GRAPHIC SCALE
10' 20' 30'
N PLAN
NORTH
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
1/8" = 1'-0"
LI
G
H T
IN
G
P
LA
N
F
IR
S T
F
LO
O R
EL101
RLW RLW NGZ
12854139
1/8" = 1'-0"A1
LIGHTING PLAN - FIRST FLOOR
A. EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED VIA LIGHTING
CONTACTOR 'LC-1' LOCATED IN ROOM 101.
B. ALL INTERIOR WALL MOUNTED DEVICES SHALL BE SURFACE MOUNTED.
C. ALL INTERIOR LIGHTS IN ROOM 101 SHALL BE CONNECTED TO EITHER SWITCH
LEG 'A' OR SWITCH LEG 'B' AS INDICATED. ALL ASSOCIATED LIGHTING RELAYS IN
ROOM 101 SHALL BE NETWORKED TOGETHER AND PROGRAMMED SO THEY
RESPOND TO ALL THE DIGITAL SWITCHES AND OCCUPANCY SENSORS WITHIN
ROOM 101.
D. ALL INTERIOR LIGHTS IN ROOM 102 SHALL BE CONNECTED TO EITHER SWITCH
LEG 'B' OR SWITCH LEG 'C' AS INDICATED. ALL ASSOCIATED LIGHTING RELAYS IN
ROOM 102 SHALL BE NETWORKED TOGETHER AND PROGRAMMED SO THEY
RESPOND TO ALL THE DIGITAL SWITCHES AND OCCUPANCY SENSORS WITHIN
ROOM 102.
E. PROVIDE A MEANS TO OVERRIDE ALL AUTOMATIC MEANS OF LIGHTING
CONTROLS IN ROOMS 101 AND 102 UPON ACTIVATION OF THE FIRE ALARM
SYSTEM. ALL INTERIOR LIGHT FIXTURES WITHIN THE WAREHOUSE SHALL TURN
ON AT FULL OUTPUT UPON ACTIVATION OF THE FIRE ALARM SYSTEM.
1 MOUNT PHOTOCELL ON EXTERIOR WALL AT 1'- 0" BELOW TOP
OF WALL TO TOP OF DEVICE. ORIENT TO FACE NORTH.
2 RADIANT HEATER, TYPICAL.
LED INDUSTRIAL STRIP
REVISED: APRIL 2016 NL-7LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR
RIGIDITY AND SPECULAR ALUMINUM OR HIGHLY-REFLECTIVE PAINTED STEEL
REFLECTORS. 4FT LENGTH.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH
HIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.
3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70,
4000K CCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING
TOLERANCE FOR COLOR CONSISTENCY, AND MINIMUM EFFICACY OF 100 LUMENS/WATT.
INITIAL LUMEN OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC
DISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.
COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED
WITH EMERGENCY BATTERY BACK-UP.
6. MOUNTING - SURFACE ON CEILING OR SUSPENDED.
7. STEM HANGERS.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE
THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-CAST ALUMINUM WITH INTEGRAL PASSIVE COOLING MECHANISM.
HEAT SINK SHALL BE INCORPORATED DIRECTLY INTO HOUSING OR DRIVER
COMPARTMENT TO ENSURE MAXIMUM HEAT TRANSFER AND DISSIPATION.
2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON POLYESTER
POWDER COAT. FINISH SHALL PASS 2500 HOUR SALT SPRAY TEST PER ASTM B117.
CUSTOM SILK GREY (RAL 7044) POWDER COAT FINISH.
3. POWER SUPPLY/LED DRIVER - CLASS 1 DRIVER SHALL OPERATE AT 120/277 VOLTS,
50/60 HZ; POWER FACTOR GREATER THAN 0.9 AND THD LESS THAN 20% AT FULL
LOAD. MINIMUM EFFICACY SHALL BE 60 LM/W AT MAXIMUM 600mA OPERATING
CURRENT.
4. LED OPTICAL ASSEMBLY - PRECISION MOLDED ACRYLIC LENS PROVIDED FOR
MULTIPLE HIGH-POWERED LEDS PRODUCING NEMA DISTRIBUTION TYPE AS NOTED
ON FIXTURE SCHEDULE. BUG UPLIGHT RATING OF U0, WITH GLARE RATING AS
DETERMINED BY LIGHTING ZONE INSTALLED.
5. CERTIFICATION - UL AND/OR ETL LISTED FOR WET LOCATIONS, AND RoHS
COMPLIANT.
6. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETY GRAPHIC REPRESENTATION OF A
LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS AND IS NOT
INTENDED TO INDICATE A CERTAIN MANUFACTURER'S PREFERENCE. ALL
DIMENSIONS ARE NOMINAL AND VARY PER MANUFACTURER.
LED WALL PACK
REVISED: MARCH 2013 XL-17LIGHTING PLATE:
7. OPTIONS - MOTION SENSOR AND 0-10 VOLT DIMMING DRIVER.
1.
2.
3.
4.
5.
LUMINAIRE REQUIREMENTS:
HOUSING - HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED THERMOPLASTIC. SINGLE
OR DOUBLE-FACED AS INDICATED.
LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. GREEN LETTERS AS
INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH
DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS
REQUIRED.
FINISH (ON CAST ALUMINUM HOUSING ONLY) - TEXTURED POWDER COAT FINISH
OPTIONS INCLUDE WHITE, WHITE WITH BRUSHED ALUMINUM FACE, BLACK, OR BLACK
WITH BRUSHED ALUMINUM FACE.
EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER WITH
MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND TEST
SWITCH.
MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE
MOUNTING.
ILLUMINATION - PROVIDED GREEN HIGH-OUTPUT LEDS INSIDEOF FIXTURE HOUSING.
PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH FREQUENCY-MATCHED
SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.
CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.
6.
LED EXIT SIGN
REVISED: AUGUST 2004 XL-63LIGHTING PLATE:
7.
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
NTS
LI
G
H T
IN
G
F
IX
T U
R E
D E
T A
IL
S
EL501
RLW RLW NGZ
12854140
NOT TO SCALE
C2
FIXTURE DETAIL FOR C1, C1B
NOT TO SCALEC3
FIXTURE TYPES W1DB
NOT TO SCALEC4
FIXTURE DETAIL FOR X1
120V LIGHTING CIRCUIT #1
6 LR
FA8
LR
120V LIGHTING CIRCUIT #2
H
A
O
CR
CR UNLATCH
LATCH
CR
B
A
C
C
C
PE
PE
COIL CLEARING
CONTACTS
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
LC1
120V
1L1-16
1L1-18
W. BLDG EXTERIOR
LIGHTING
E. BLDG EXTERIOR LIGHTING
RM. 101
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
12" = 1'-0"
LI
G
H T
IN
G
C O
N T
R O
L D
IA
G
R A
M S
A N
D S
C H
E D
U
LE
S
EL601
RLW RLW NGZ
12854141
NOT TO SCALEC3
TYPICAL DIGITAL LIGHTING CONTROL SYSTEM
CONNECTION DIAGRAM
1 TYPICAL, DIGITAL, LOCAL LIGHTING RELAY PACK.
2 3/4" CONDUIT WITH LOW VOLTAGE CONTROL WIRING AS
REQUIRED.
3 TYPICAL CONTROLLED LIGHT FIXTURES.
4 TYPICAL DIGITAL LIGHTING CONTROL SWITCH.
5 CONTROLLED LIGHTING CIRCUIT AS INDICATED ON PLANS.
6 TYPICAL DIGITAL OCCUPANCY SENSOR.
7 1/2" CONDUIT WITH DIMMING WIRING AS INDICATED ON PLANS.
8 TYPICAL FIRE ALARM CONTROL RELAY TO BYPASS
AUTOMATIC LIGHTING CONTROLS AND SHUNT IGHTING
FIXTURES TO FULL OUTPUT UPON FIRE ALARM SYSTEM
ACTIVATION.
KEY NOTES: 00 (C3/EL601)
1 CONTACTS SHALL BE RATED FOR 20A, 120V.
2 PROVIDE 120V COILS.
3 ASSEMBLY SHALL HAVE A MINIMUM 10,000A SHORT CIRCUIT
RATING.
4 PROVIDE INTEGRAL H-O-A SELECTOR SWITCH.
5 PROVIDE MECHANICALLY HELD CONTACTOR.
LIGHTING FIXTURES SCHEDULE NOTES:
A. LIGHTING FIXTURES SHALL NOT BE USED AS A RACEWAY UNLESS
UL LISTED AS SUCH.
B. DIMMING DRIVERS SHALL BE COMPATIBLE WITH ASSOCIATED
LIGHTING CONTROL SWITCH OR RELAY AND SHALL ALLOW FOR 10%
TO 100% DIMMING RANGE OR STEP DIMMING AS REQUIRED.
LIGHTING FIXTURES SCHEDULE
FIXTURE
TYPE FIXTURE DESCRIPTION VOLTAGE LAMP LUMEN CCT CRI MOUNTING NOTES
DETAIL
REFERENCE
POLE
C1 4' LOW BAY LED STRIP FIXTURE WITH COLD ROLLED STEEL HOUSING, WIDE SYMMETRIC OPTICAL DISTRIBUTION, MATTE WHITE
ENAMEL FINISH, AND FROSTED ACRYLIC LENS.
120V LED 9000 4000K 80 SUSPENDED SUSPEND AT 12'-6" AFF TO BOTTOM UON. FIXTURE SHALL BE UL LSITED
AS A RACEWAY SUITABLE FOR THROUGH WIRING. FIXTURE SHALL BE UL
LISTED FOR DAMP LOCATION.
C2/EL501
C1B 4' LOW BAY LED STRIP FIXTURE WITH COLD ROLLED STEEL HOUSING, WIDE SYMMETRIC OPTICAL DISTRIBUTION, MATTE WHITE
ENAMEL FINISH, AND FROSTED ACRYLIC LENS. PROVIDE WITH EMERGENCY BATTERY.
120V LED 9000 4000K 80 SUSPENDED SUSPEND AT 12'-6" AFF TO BOTTOM UON. FIXTURE SHALL BE UL LSITED
AS A RACEWAY SUITABLE FOR THROUGH WIRING. FIXTURE SHALL BE UL
LISTED FOR DAMP LOCATION.
C2/EL501
W1DB EXTERIOR WALL MOUNTED FIXTURE WITH DIE CAST ALUMINUM ENCLOSURE, IP66 RATED HOUSING, 2.5MIL THICKNESS, CUSTOM SILK GREY (RAL 7044) POWDER COAT FINISH, AND TYPE IV WIDE DISTRIBUTION. PROVIDE WITH INTEGRAL OCCUPANCY SENSOR AND EMERGENCY BATTERY. INTEGRAL CONTROLS SHALL BE PROGRAMMED SUCH THAT LIGHT OUTPUT IS AT 70% FULL BRIGHTNESS FROM DUSK TO DAWN, UNLESS MOTION IS DETECTED, WHICH SHALL TRIGGER THE FIXTURE TO SWITCH TO 100%
FULL BRIGHTNESS WITH A 10 MINUTE VACANCY TIMEOUT.
120 LED 6458 4000K 70 WALL MOUNTED AT 10'-0" AFF TO BOTTOM UON. FIXTURE SHALL BE UL LISTED
FOR WET LOCATION.
C3/EL501
X1 SINGLE FACE LED EXIT SIGN WITH ALUMINUM HOUSING, INTEGRAL NICKEL CADMIUM BATTERY AND GREEN LETTERS. 120V LED N/A N/A N/A UNIVERSAL WHERE WALL-MOUNTED ABOVE DOOR, MOUNT AT 1" ABOVE DOOR FRAME
TO BOTTOM OF SIGN. FIXTURE SHALL BE UL LISTED FOR DAMP LOCATION.
C4/EL501
12" = 1'-0"C1
LIGHTING CONTACTOR 'LC1' WIRING DIAGRAM
LIGHTING CONTACTOR NOTES:
NOTE:
ALL LIGHTING CONTROL WIRING SHALL BE #12AWG COPPER INSTALLED IN 3/4" CONDUIT.
M
M
E
E
E E
1.5
1.5
E
E
E
E
E
E
T E E
E
E
EE
E
E
+48"
+48"
+48" +48"
+48"
+48"
+48"
+48"
+48"+48"
+48"
+48"
G/WP
G/WP
G/WP
G/WP
G/WP
STORAGE
1 1
30A30A
30A
30A
2 2
RGH
RGH
RGH
RGH
RGH
RGH
EF
EF
H-1 1/2-3Φ
H-1 1/2-3Φ
1L1-3
1L1-1
1L1-5
1H1-7,9,11
1H1-1,3,5
1H1-8,10,12
1H1-20,22,24
1H1-26,28,30
12 13
TGB-1
1L1-6
STORAGE
1L1-9
1L1-13
+48" +48"
+48"
+48"
1H1 1L1
LC1
1L1-7
+48"
1H1-14,16,18
1 2 3 6
F
E
D
C
B
A
4 5
T
T
1L1-11
1L1-2
+48"+48"+48"+48"
1L1-15
1L1-17
1L1-4
+48"
+48"
1L1-20
1L1-19
G 1L1-10
1L1-8
1H1-13,15
1L1-22
CT CABINET
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
KEY NOTES 00
SHEET NOTES:
NOTES:
0 5'
1/8" = 1'-0" GRAPHIC SCALE
10' 20' 30'
N PLAN
NORTH
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
1/8" = 1'-0"
P O
W E
R P
LA
N
F
IR
S
T F
LO
O
R
EP101
RLW RLW NGZ
12854142
1/8" = 1'-0" A1
POWER PLAN - FIRST FLOOR
1 AUTOMATIC ROLL UP DOOR CONTROLLER PROVIDED WITH AUTOMATIC ROLL
UP DOOR. MOUNT AT 48" AFF TO BOTTOM. PROVIDE 3/4" EMPTY CONDUIT
WITH PULL STRING FROM CONTROLLER TO AUTOMATIC ROLL UP DOOR
MOTOR CONTROL SECTION. TERMINATE CONDUIT AS DIRECTED BY THE
AUTOMATIC ROLL UP DOOR PROVIDER.
2 CONNECTION TO AUTOMATIC ROLL UP DOOR.
3 1/2"C - (3)#12 + (1) #12 GND.
4 ADVANCED METERING INFRASTRUCTURE EQUIPMENT CABINET.
5 CONNECTION TO CEILING FAN.
6 BUILDING ENTRANCE PRIMARY PROTECTORS.
7 SEE MOTOR STARTER SCHEDULE ON SHEET EP701 FOR CONDUIT AND WIRE
SIZE.
8 ADVANCED ELECTRIC METER.
9 CONNECTION TO RADIANT HEATER IGNITER. PROVIDE 20A, 120V, TOGGLE
SWITCH DISCONNECT ADJACENT TO RADIANT HEATER IGNITER ENCLOSURE.
CONTROLS BY DIVISION 23.
10 4" HIGH CONCRETE PAD WITH ½ " BEVEL ON ALL EDGES.
EXTEND PAD 4" BEYOND EQUIPMENT.
11 MOUNT GROUND BUS GB-E1 AT 18" AFF TO TOP. SEE A1/EP601 FOR
GROUNDING DIAGRAM.
12 WALL MOUNTED DOUBLE HINGED TELECOMMUNICATIONS CABINET WITH 48
PORT FIBER OPTIC PATCH PANEL AND NETWORK SWITCH.
13 2'-0" SQUARE 100% VOID FREE, FIRE RATED, 3/4" PLYWOOD BACKBOARD.
MOUNT AT 6'-0" AFF TO TOP. PAINT ALL SIDES AND EDGES WITH TWO COATS
OF FIRE RETARDANT PAINT. DO NOT PAINT OVER FIRE RATING LABEL.
14 TWO 4" CONDUITS FROM TELECOMMUNICATIONS HANDHOLE ECHH1. STUB
CONDUITS 4" AFF. PROVIDE WATER TIGHT SEAL AFTER
TELECOMMUNICATIONS CABLES ARE INSTALLED.
15 RECEPTACLE FOR WALL MOUNTED DOUBLE HINGED TELECOMMUNICATIONS
CABINET. COORDINATE MOUNTING LOCATION WITH CABINET INSTALLER.
16 CONNECTION TO FACP. COORDINATE ROUGHIN REQUIREMENTS WITH FIRE
ALARM SYSTEM INSTALLER.
17 CONNECTION TO FIRE ALARM SYSTEM RADIO TRANSMITTER. COORDINATE
ROUGHIN REQUIREMENTS WITH FIRE ALARM SYSTEM INSTALLER.
18 RECEPTACLE FOR FACP ENCLOSURE COOLING UNIT. COORDINATE EXACT
MOUNTING LOCATION WITH FIRE ALARM SYSTEM INSTALLER.
19 CONNECTION TO CONTROL PANEL DC/01.
A. ALL ELECTRICAL EQUIPMENT AND DEVICES IN THE BUILDING INTERIOR SHALL
BE SURFACE MOUNTED.
COMBINATION
STARTER
ENCLOSURE
OPERATING
HANDLE
3-POLE ADJUSTABLE
MAGNETIC MOTOR
CIRCUIT PROTECTOR
STARTER
CONTACTS
ELECTRONIC
OVERLOAD RELAY
REMOTE
DISCONNECT
WHERE INDICATED
ON POWER PLANS
TO CONTROL
CIRCUIT, SEE
C2/EP501 FOR
DIAGRAM
X1
X2
T1 T2 T3
L1 L2 L3
CONTROL
TRANSFORMER
MOTOR
OL
H
O
A
C
R
120V CONTROL CIRCUIT
DEVICE
INCLUDED WITH
MOTOR STARTER
PILOT LIGHT SHALL
ILLUMINATE WHEN
MOTOR IS RUNNING
DIGITAL CONTROLER
BY DIVISION 23
DEVICE INCLUDED
WITH MOTOR
STARTER
TOP VIEW
FRONT VIEW
GROUNDING ELECTRODE
CONDUCTORS DO NOT REMOVE
ENGRAVED LAMINATED PLASTIC SIGN
WITH 1/2" HIGH WHITE LETTERS ON RED
BACKGROUND. FASTEN SIGN TO WALL
ADJACENT TO GROUND BUS.
TYPICAL INSULATED GROUNDING
ELECTRODE CONDUCTOR TO
TRANSFORMER. INSTALLED IN CONDUIT,
REFER TO DRY TYPE TRANSFORMER
SCHEDULE FOR REQUIREMENTS.
HUB GROUND CLAMP
(TYPICAL)
STANDOFF
INSULATOR
(TYPICAL)
304 STAINLESS
STEEL BRACKET, 1/8"
THICK (TYPICAL)
TYPICAL INSULATED GROUNDING
ELECTRODE CONDUCTOR TO
GROUNDING ELECTRODE
SYSTEM. INSTALL IN CONDUIT.
REFER TO A1/EP601 FOR
CONNECTIONS.
IRREVERSIBLE BUSBAR
CONNECTOR,
TYPICAL FOR CONNECTIONS TO
GROUNDING ELECTRODE
SYSTEM.
TWO HOLE LUG, FOR
TRANSFORMER
CONNECTIONS ONLY.T-GLN1
C O
L D
W A
T E
R
ENGRAVED LAMINATED PLASTIC TAG WITH
GREEN FACE AND WHITE LETTERS TO IDENTIFY
THE DESTINATION OF EACH GROUNDING
ELECTRODE CONDUCTOR. FASTEN TO
GROUNDING ELECTRODE CONDUCTOR.
FASTEN TO GROUNDING ELECTRODE
CONDUCTOR WITH ZIP TIE (TYPICAL).
2"1/ 4"
2"
1'-6"
2'-0"
CONDUIT FITTING AS REQUIRED (TYPICAL)
COPPER GROUND BUS WITH PRE-DRILLED
HOLES AS REQUIRED.
TOP VIEW
FRONT VIEW
SEE A1/EP601 FOR
CONNECTIONS
HUB GROUND CLAMP (TYPICAL)
STANDOFF
INSULATOR
(TYPICAL)
304 STAINLESS
STEEL BRACKET, 1/8"
THICK (TYPICAL)
TWO HOLE
LUG
ENGRAVED LAMINATED PLASTIC TAG WITH GREEN
FACE AND WHITE LETTERS TO IDENTIFY THE
DESTINATION OF EACH GROUNDING CONDUCTOR.
FASTEN TO GROUNDING ELECTRODE CONDUCTOR
WITH ZIP TIE (TYPICAL).
2"1/ 4"
4"
1'-6"
2'-5"
CONDUIT FITTING AS
REQUIRED (TYPICAL)
COPPER GROUND BUS WITH
PRE-DRILLED HOLES AS
REQUIRED.
BICSI PATTERN COPPER GROUND BUS.
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
As indicated
E
LE
C T
R
IC
A L
D E
T A
IL
S
EP501
RLW RLW NGZ
12854143
NOT TO SCALE
C4
STARTER DIAGRAM - THREE PHASE MOTORS
NOT TO SCALE
C2
MOTOR CONTROL DIAGRAM - SINGLE SPEED MOTORS
NOT TO SCALE
A3
TYPICAL ELECTRICAL ROOM GROUND BUS DETAIL
NOT TO SCALE
A2
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB) DETAIL
LA
B
EL
WIDTH
HEIGHT
NOTES:
PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT
TO WARN OF ARC FLASH HAZARDS.
THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.
THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE
TO QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING,
OR MAINTENANCE OF THE EQUIPMENT.
THE SIZE OF THE LABEL SHALL BE MINIMUM:
EQUIPMENT TYPE HEIGHT WIDTH
INDOOR 2'' 3''
OUTDOOR 3'' 4.5''
ARC FLASH WARNING LABEL
1.
2.
3.
4.
SKETCH DATE APRIL 2015 STYLE AF - 1
KEY NOTES: (C3/EP502)
ADVANCED ELECTRIC METER MOUNTED ADJACENT TO SERVICE ENTRANCE PANELBOARD.1
WALL MOUNTED WATER METER. REFER TO PLUMBING DRAWINGS FOR LOCATION AND
MOUNTING HEIGHT.
EXTERIOR WALL
FIRST FLOOR
AMI
ADVANCED METERING INFRASTRUCTURE EQUIPMENT CABINET. SEE SHEET EP101
FOR LOCATION.
1/2" CONDUIT WITH NETWORKING WIRING AS REQUIRED. COORDINATE WITH PUBLIC
WORKS AMI SYSTEM REPRESENTATIVE FOR WIRING REQUIREMENTS.
1/2" CONDUIT. STUB CONDUIT TO FIBER OPTIC PATCH PANEL. SEE SHEET EP101 FOR
LOCATION.
6-STRAND SINGLE MODE FIBER OPTIC CABLE TO FIBER OPTIC NEWTWORK SWITCH IN
ROOM 101.
WALL MOUNTED GAS METER. REFER TO PLUMBING DRAWINGS FOR LOCATION AND
MOUNTING HEIGHT.
RM. 101
1/2"C WITH CT WIRING AS REQUIRED.8
SERVICE FEEDER CT CABINET, SIZE AS REQUIRED. CABINET SHALL BE LOCKABLE
WITH HINGED DOOR.
FINISHED GRADE
WARNING
TAPE
CONCRETE ENVELOPE
D E
P T
H A
S R
E Q
U
IR
E D
(3
M
IN
IM
U
M
#4 REBAR AT 8" ON CENTER
#8 WIRE LOOP AT 8" ON
CENTER
3" TYPICAL
6" TYPICAL
#4/0 BARE COPPER
5" CONDUIT
(TYPICAL FOR 4)
NOTE:
1. #4/0 BARE COPPER CONDUCTOR
SHALL BOND TO THE GROUND
RING BUS IN EACH MANHOLE THE
DUCTBANK ENTERS. BOND TO THE
LIGHTNING PROTECTION SYSTEM
WHERE THE DUCTBANK ENTERS
THE BUILDING.
HANDHOLE REQUIREMENTS:
1. HOUSING SHALL BE A POLYMER CONCRETE REINFORCED WITH A HEAVY WEAVE FIBERGLASS REINFORCING
WITH COMPRESSIVE STRENGTH OF NO LESS THAN 10,000 PSI.
2. COVER AND BOX SHALL WITHSTAND A SERVICE LOAD OF NO LESS THAN 22,500 LBS OVER A 10" x 20" AREA AND
MUST PASS A STATIC LOAD TEST OF 2,500 LBS.
3. PROVIDE STAINLESS STEEL BOLTS AND INSERTS.
4. PROVIDE WITH (2) 2 1/2" MOUSEHOLES.
5. PROVIDE LABEL "LIGHTING" FOR LIGHTING HANDHOLES.
6. PROVIDE TIER 22 RATING PER ANSI/ SCTE 77.
7. HANDHOLE SHALL BE 17"W x 30"L x 18"DP.
SECTIONAL BOX
WHEN REQUIRED
CRUSHED ROCK
SKID RESISTANT
SURFACE
PULL SLOT
STAINLESS STEEL HEX BOLT
AND WASHER
BOX AND
COVER
CONCRETE RING
AROUND BOX
COMPACTED
EARTH
10"
6"
6"
6"
FINISHED GRADE
WARNING TAPE
CONCRETE ENVELOPE
A S
R E
Q U
IR
E
D
3" TYPICAL ALL SIDES
3" TYPICAL
5" CONDUIT, TYPICAL
FOR TWO
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
As indicated
E
LE
C T
R
IC
A L
D E
T A
IL
S
EP502
RLW RLW NGZ
12854144
NOT TO SCALEA4
ARC FLASH WARNING LABEL
NOT TO SCALEC3
METERING CONNECTION DIAGRAM
NOT TO SCALEC4
2-WAY CONCRETE POWER DUCT BANK DETAIL
NTS
A3
TYPICAL ELECTRICAL HANDHOLE DETAIL
NOT TO SCALEC1
2-WAY TELECOMMUNICATIONS DUCT BANK DETAIL
3P
ET
600 A
5000A, 3ø, 4W, 480Y/277V, 65KAIC
3P
ET
1200 A
3P
ET
225 A
3P
ET
400 A
EXISTING SWITCHGEAR 2146
3P
ET
1200 A
3P
ET
1200 A
3P
ET
1200 A
3P
ET
800 A
3P
ET
GFP
5000 A 3P
ET
GFP
5000 A
3P E T
G F
P
A
N .O
N.C.N.C.
M M
K K
K
NEUTRAL BUS
GROUND BUS
5000A, 3ø, 4W, 480Y/277V, 65KAIC
EXISTING
ATS-1
EXISTING
SPARE
EXISTING
SPARE
EXISTING
DP-HW
EXISTING
DP-HE
EXISTING
ATS-2
EXISTING
MP-HE
EXISTING
MH ES-2
3750 KVA,
12470-480Y/277V, 5.8%IZ
3750 KVA,
12470-480Y/277V, 5.8%IZ
TO 15KV
SECTIONALIZING
SWITCH
TO 15KV
SECTIONALIZING
SWITCH
1H1
RM. 101
1L1
RM.101
T T-1L1
30KVA
SPD
SE
SPD
BL
RM. 101
RM 101 LEVEL 1
48 STRAND SINGLE
MODE FIBER OPTIC
CABLE
50 PAIR
OUTSIDE PLANT
COPPER CABLE
BUILDING
ENTRANCE
PRIMARY
PROTECTORS
WALL MOUNTED DOUBLE
HINGED
TELECOMMUNICATIONS
CABINET WITH 48 PORT FIBER
OPTIC PATCH PANEL AND
NETWORK SWITCH.
EXISTING HANDHOLE ECHH1.
SPLICE TO EXISTING 50 PAIR
OUTSIDE PLANT CABLE AND 48
STRAND SINGLE MODE FIBER
IN HANDHOLE. SEE SHEET
ES100 FOR LOCATION.
DUCTBANK
SPARE CONDUIT
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
KEY NOTES 00
NOTES:
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
NTS
S
IN
G
LE
L
IN
E D
IA
G
R A
M
EP600
RLW RLW NGZ
12854145
NOT TO SCALEA1
SINGLE LINE DIAGRAM
NOT TO SCALEA4
BACKBONE CABLE RISER
1 SEE DRY TYPE TRANSFORMER SCHEDULE ON SHEET EP701 FOR CONDUIT
AND WIRE SIZE.
2 SEE SHEET EP601 FOR GROUNDING REQUIREMENTS.
3 EXISTING SIEMENS 225A, 480V, 3 POLE, 65KAIC, TYPE WLS CIRCUIT BREAKER
WITH ETU745 ADJUSTABLE TRIP UNIT. REVISE SETTING AS INDICATED: LTPU:
1.0, LTD: 30, STPU: 6.0, STD: 0.1 ON, INST: 6.0.
4 (4)#300KCMIL + (1)#1/0 GND (ALUMINUM). ROUTE FEEDER IN EXISTING
DUCTBANK. SEE SHEET ES100 FOR ADDITIONAL INFORMATION.
5 (4)#300KCMIL + (1)#1/0 GND (ALUMINUM). ROUTE FEEDER IN NEW DUCTBANK.
SEE SHEET ES100 FOR ADDITIONAL INFORMATION.
6 THE AVAILABLE SHORT CIRCUIT AT SWGR 2146 IS 50,000A BASED ON
AS-BUILT DRAWINGS. THE EXISTING METERED PEAK LOAD FOR SWGR 2146
IS 425KVA.
7 CIRCUIT BREAKER SHALL BE 100% RATED AND SERVE AS THE MEANS OF
DISCONNECT FOR THE BUILDING.
8 3"C - (4)#300KCMIL + (1)#1/0 GND (ALUMINUM).
9 TO ADVANCED METERING EQUIPMENT CABINET. SEE C3/EP502 FOR
CONNECTION DIAGRAM.
10 DO NOT BOND THE NEUTRAL BUS AND GROUND BUS IN THIS PANEL.
LINE TYPE LEGEND
INDICATES EXISTING EQUIPMENT TO REMAIN
INDICATES NEW EQUIPMENT
GND BUS
C B AN
NEUT BUS
G
C B AG
480Y/277V MAIN SERVICE PANELBOARD
GND BUS
NEUT BUS
DISTRIBUTION SECTION
GND LUGS
TYPICAL 480V - 208Y/120V
DRY TYPE TRANSFORMER
GND BUS
NEUT BUS
ANG
TYPICAL 208Y/120V PANELBOARD
A
B
C
N
G
TYPICAL BRANCH
CIRCUIT
A
B
C
N
MAIN BREAKERTRANSFORMER SECTIONSWITCH SECTION
TYPICAL UNIT SUBSTATION
GND BUS
GFP
TYPICAL BRANCH
CIRCUIT BREAKER
TYPICAL MAIN
CIRCUIT BREAKER
TYPICAL
BONDING JUMPER
TYPICAL BONDING
JUMPER
TYPICAL
BONDING
JUMPER
TYPICAL DISTRIBUTION
CIRCUIT BREAKER
TYPICAL BONDING
JUMPER
A
B
C
G
MEDIUM VOLTAGE
PRIMARY FEEDERS
TYPICAL
SURGE
ARRESTOR
EXISTING
MAIN
BONDING
JUMPER
TYPICAL MAIN
CIRCUIT BREAKER
TYPICAL DISTRIBUTION
CIRCUIT BREAKER
LEGEND
PHASE CONDUCTOR "A"
PHASE CONDUCTOR "B"
PHASE CONDUCTOR "C"
NEUTRAL CONDUCTOR
POINT OF CONNECTION
A EQUIPMENT GROUND CONDUCTOR ROUTED
IN CONDUIT WITH PHASE CONDUCTORS.
GROUNDING ELECTRODE
GROUND FAULT PROTECTIVE DEVICE, CAUSES
CIRCUIT BREAKER TO TRIP.
G
GFP
B
C
N
GROUNDING ELECTRODE CONDUCTOR IN
CONDUIT. SEE DRY TYPE TRANSFORMER
SCHEDULE ON SHEET EP701 FOR SIZE.
GROUND BUS "GB-E1" LOCATED IN ROOM 101 FOR
BONDING OF DRY TYPE TRANSFORMER IN THE
SAME ROOM.
1" C WITH 1#3/0 AWG
CONTINUOUS COPPER
GROUNDING ELECTRODE
CONDUCTOR
NEAREST EFFECTIVELY
GROUNDED STRUCTURAL
STEEL MEMBER
NEAREST AVAILABLE INTERIOR METAL
COLD WATER PIPE LOCATED IN AREA
THAT THE TRANSFORMER SERVES
PROVIDE GROUNDING ELECTRODE CONNECTIONS AS
INDICATED IN THE GROUNDING ELECTRODE CONNECTION
SCHEDULE ON THIS SHEET. PROVIDE BUSHING AT BOTH
ENDS OF METALLIC CONDUIT RUNS. PROVIDE SCHEDULE
40 PVC FOR UNDERGROUND CONDUIT.
GROUNDING ELECTRODE SYSTEM SCHEDULE
CONNECTION CONDUCTOR
SIZE
CONDUIT
SIZE
(3)-3/4" x 10'-0" GROUND RODS. SPACE THE GROUNDS AT 10'-0" ON
CENTER IN TRIANGULAR MANNER. PROVIDE TEST WELL FOR EACH
GROUND ROD. UTILIZE EXOTHERMIC WELD CONNECTIONS.
#3/0 1"
LIGHTNING PROTECTION SYSTEM GROUND LOOP CONDUCTOR. UTILIZE
EXOTHERMIC WELD CONNECTIONS.
#3/0 1"
INTERIOR COLD WATER PIPE SYSTEM AT A POINT LOCATED NOT MORE
THAN 5'-0" FROM THE POINT OF ENTRANCE INTO THE BUILDING.
#3/0 1"
WHERE PRESENT, BOND TO THE NEAREST STRUCTURAL STEEL COLUMN.
UTILIZE AN EXOTHERMIC WELD CONNECTION AT INACCESSIBLE
LOCATIONS.
#3/0 1"
BUILDING'S FOUNDATION REINFORCING BARS. UTILIZE EXOTHERMIC
WELD CONNECTIONS. TYPICAL FOR THE REMOTE ELECTRICAL BUILDING
AND MAIN BUILDING.
#3/0 1"
GROUND BUS "TGB-1"
#6 AWG INSULATED COPPER BONDING
CONDUCTOR TO WALL MOUNTED
TELECOMMUNICATIONS EQUIPMENT CABINET.
#6 AWG INSULATED COPPER BONDING
CONDUCTOR TO BUILDING ENTRANCE
PRIMARY PROTECTORS.
No 64299
STATE OF
S G
CY
ZRLA BUZ
OH
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
/1
5/
:5 8:
A
M
12" = 1'-0"
O V
E R
A
LL
G R
O U
N D
IN
G
D
IA
G R
A M
EP601
RLW RLW NGZ
12854146
NOT TO SCALE
A1
NORMAL SYSTEM OVERALL GROUNDING DIAGRAM
MOTOR STARTER SCHEDULE - 480V, 3Φ MOTORS
DESIGNATION HP FLA
MOTOR CIRCUIT PROTECTOR
BRANCH CIRCUIT SIZE
H-1/2 1/2 1.1A 3A 1/2"C - 3#12 + 1#12 GND
H-3/4 3/4 1.6A 1/2"C - 3#12 + 1#12 GND
RATING POLES
3A 3
H-1 1 2.1A 1/2"C - 3#12 + 1#12 GND3A 3
NEMA
STARTER SIZE
H-1 1/2 1 1/2 3A 1/2"C - 3#12 + 1#12 GND7A 3 0
H-2 2 3.4A 1/2"C - 3#12 + 1#12 GND7A 3 0
H-3 3 4.8A 1/2"C - 3#12 + 1#12 GND7A 3 0
H-5 5 7.6A 1/2"C - 3#12 + 1#12 GND15A 3 0
H-7 1/2 7 1/2 11A 1/2"C - 3#12 + 1#12 GND15A 3 1
H-10 10 14A 3/4"C - 3#10 + 1#10 GND30A 3 1
H-15 15 21A 3/4"C - 3#10 + 1#10 GND30A 3 2
H-20 20 27A 34"C - 3#8 + 1#8 GND50A 3 2
H-25 25 34A 1"C - 3#6 + 1#8 GND50A 3 2
H-30 30 40A 1"C - 3#6 + 1#8 GND50A 3 3
H-40 40 52A 1"C - 3#4 + 1#6 GND100A 3 3
H-50 50 65A 1 1/4"C - 3#3 + 1#6 GND100A 3 3
H-60 60 77A 1 1/2"C - 3#1 + 1#6 GND150A 3 4
H-75 75 96A 1 1/2"C - 3#1/0 + 1#4 GND250A 3 4
H-100 100 124A 1 1/2"C - 3#2/0 + 1#3 GND250A 3 4
H-125 125 156A 2"C - 3#3/0 + 1#3 GND250A 3 5
H-150 150 180A 2"C - 3#4/0 + 1#2 GND250A 3 5
3Φ DRY TYPE STEP DOWN TRANSFORMER SCHEDULE
DESIGNATION KVA
PRIMARY
VOLTAGE PRIMARY FEEDER SECONDARY FEEDER
T15 15 480V 1"C - 4#6 + 1#8 GND
T30 30
T45 45
GROUNDING ELECTRODE
CONDUCTOR SIZE
1/2"C - #8
1/2"C - #6
1/2"C - #6
T75 75 3/4"C - #2
T112.5 112.5 1"C - #1/0
T225 225 1"C - #2/0
480V
480V
480V
480V
480V
3/4"C - 3#10 + 1#10 GND 208Y/120V
SECONDARY
VOLTAGE
208Y/120V
208Y/120V
208Y/120V
208Y/120V
208Y/120V
1"C - 3#6 + 1#10 GND
1"C - 3#3 + 1#8 GND
1 1/2"C - 3#1/0 + 1#6 GND
2"C - 3#4/0 + 1#4 GND
TWO 2"C WITH 3#250 + 1#3 GND…