Attachment G - 1362850dwg12of15_FIRE SUPPRESSION.pdf

PDF 506 KB Posted

Attached to
Small Projects MACC MCAS Beaufort Federal contract opportunity
Solicitation number
N4008523R2575
Issued by
Department of the Navy Naval Facilities Engineering Command

View the file

Other files for this federal contract opportunity

Other files attached to Small Projects MACC MCAS Beaufort, newest first.
File Type Posted
AMENDMENT 0008.pdf PDF
23R2575 AMENDMENT 0007.pdf PDF
Amendment 0007 - Attachment E - Price Proposal Form REV 3.docx DOCX document
Amendment 0006 - Attachment E - Price Proposal Form REV 2.docx DOCX document
Amendment 0006 - BLDG-P485-1362850-AE531 - MISCELLANEOUS DETAILS_REV3.pdf PDF
23R2575 AMENDMENT 0006.pdf PDF
Amendment 0005 - Attachment E - Price Proposal Form REV 1.docx DOCX document
Amendment 0005 - Site Visit Sign-In Sheet.pdf PDF
23R2575 AMENDMENT 0005.pdf PDF
N4008523R2575 AMENDMENT 0004.pdf PDF
N4008523R2575 AMENDMENT 0003.pdf PDF
N4008523R2575 AMENDMENT 0002.pdf PDF
N4008523R2575 AMENDMENT 0001.pdf PDF
Attachment I - ASO 5510.14 Installation Access Control Measures.pdf PDF
Attachment G - 1362850dwg15of15_ELEC.pdf PDF
Attachment G - 1362850dwg8of15_STRUCT.pdf PDF
Attachment G - 1362850dwg4of15_CIVIL.pdf PDF
Attachment G - 1362850dwg11of15_FIRE ALARM.pdf PDF
Attachment H - P485 OSF_SPECIFICATIONS_VOL 2.pdf PDF
Attachment G - 1362850Amend0002dwg_ELECTRICAL.pdf PDF
Attachment G - 1362850dwg5of15_ENV.pdf PDF
Attachment D - PIEE Vendor Access Instructions.pdf PDF
Attachment A - Construction and Design Experience Project Data Sheet.docx DOCX document
Attachment E - Price Proposal Form.docx DOCX document
Attachment G - 1362850dwg1of15_GENERAL.pdf PDF
Attachment G - 1362850dwg7of15_LANDSCAPE.pdf PDF
Attachment G - 1362850dwg13of15_PLUMBING.pdf PDF
Attachment G -1362850Amend0001dwg_ARCHITECTURAL.pdf PDF
Attachment G - 1362850Amend0001dwg_ENVIRONMENTAL.pdf PDF
N4008523R2575.pdf PDF
Attachment H - P485 OSF_SPECIFICATIONS_VOL 1.pdf PDF
Attachment G - 1362850dwg9of15_ARCH.pdf PDF
Attachment G - 1362850dwg6of15_CIVIL.pdf PDF
Attachment G - 1362850dwg3of15_GEOTECHNICAL.pdf PDF
Attachment G - 1362850Amend0001dwg_CIVIL.pdf PDF
Attachment G - 1362850dwg10of15_SIGNAGE.pdf PDF
Attachment G - 1362850dwg14of15_MECH.pdf PDF
Attachment G - 1362850dwg2of15_LIFE SAFETY.pdf PDF
Attachment F - SECNAV 5512.pdf PDF
Attachment C - Pre-Proposal Inquiry Form.xlsx XLSX spreadsheet
Attachment B - Past Performance Questionnaire (PPQ).pdf PDF
Show all 41

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ESFR SPRINKLERS FOR PALLETIZED AND SOLID-PILED STORAGE OF CLASS IV

COMMODITIES STORED UP TO 25-FT UNDER 30-FT CEILING. USE K-25.2

PENDENT SPRINKLERS AT MINIMUM 15 PSI. DESIGN AREA MUST BE THE MOST

HYDRAULICALLY DEMANDING AREA OF 12 SPRINKLERS, CONSISTING OF 4

SPRINKLERS ON EACH OF 3 BRANCH LINES (2019 NFPA 13 TABLE 23.3.1). HOSE

ALLOWANCE NOT REQUIRED. SPRINKLER LAYOUT MUST COMPLY WITH NFPA

13 ESFR SPRINKLER SPACING (NFPA 13 TABLE 14.2.8.2.1).

NOTE: NFPA 13 DESIGN AREA REDUCTION FOR QUICK RESPONSE SPRINKLERS IS NOT

PERMITTED.

SPRINKLER HAZARD LEGEND

STO

FIRE SPRINKLER LEGEND

SPRINKLER PIPE

OS&Y VALVE

SUPERVISED CONTROL VALVE

CHECK VALVE

WATERFLOW SWITCH

BACKFLOW PREVENTER

WALL MOUNT TEST HEADER

WATERFLOW ALARM BELL

FIRE DEPARTMENT CONNECTION

SYSTEM RISER

HAZARD CLASSIFICATIONxx

N

0 200' 400'

SITE FIRE SUPPRESSION WATER DISTRIBUTION SYSTEM PLANA1

SCALE: 1" = 200'-0"FX001

24"

24"

24"

14"

8"

P-485PIV

24" - 3060'

24" - 1755'

14" - 800'

8" - 435'

24" - 220'

Lic. No. 044409

AARON P FREIDC

O M M O

N W

EAL

THOF

V

IR

G

IN

IA

P R O F

E

SSIONAL EN

G

IN

E E R

12/17/2021

ENGINEERS + SURVEYORS

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

F

O

P E

R A

TI

O

N A

L S

U P

P O

R T

FA

C

IL

IT

Y (O

S F)

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1362850

DRAWFORM REVISION: 07 AUG 2018

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

CJW / SVR

Approved by J. Scott Roberts, Asset Management Branch Head

& Supervisory Facility Planner, PWD Beaufort, SC via email

EJA

DSN

DSN

12/17/2021

B

IM

- P -4

F

-3

O pe ra tio na l S up po rt F ac ili ty /B

LD

G

P

5_ O

S F

-F P

.r vt

/1

6/

1:

:0

A M

As indicated

F

IR

E S

U P

P R

E S

S

IO

N G

E N

E R

A L

N O

T E

S A

N D

L E

G E

N D

FX001

APF AHE AJW

12854119

98 129

FIRE SPRINKLER GENERAL NOTES:

PROVIDE OSF WITH WET-PIPE SPRINKLER SYSTEM.

APPLICABLE CRITERIA:

NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS, 2019.

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES (CHANGE 6), 6 MAY 2021

UFC 4-440-01 WAREHOUSE AND STORAGE FACILITIES (CHANGE 1, 1 APRIL 2019)

CONTRACTOR MUST HAVE A DESIGNER WITH A NICET LEVEL III CERTIFICATION IN WATER-BASED SYSTEMS LAYOUT OR A LICENSED PROFESSIONAL FIRE PROTECTION ENGINEER IN RESPONSIBLE CHARGE OF THE SYSTEM DESIGN.

SPRINKLER PIPE MUST BE U.L. LISTED BLACK STEEL, MINIMUM SCHEDULE 40 FOR PIPE DIAMETERS 2-IN

AND LESS AND MINIMUM SCHEDULE 10 FOR PIPE DIAMETER LARGER THAN 2-IN.

SPRINKLER PIPE MUST BE SEISMICALLY BRACED IN ACCORDANCE WITH NFPA 13.

PIPING ENTERING INTO THE BUILDING MUST HAVE A PENETRATION THAT HAS A DIAMETER 6 INCHES LARGER THAN THE PIPE

DIAMETER TO ALLOW FOR SETTLEMENT.

PROVIDE QUICK-RESPONSE UPRIGHT SPRINKLERS WITH ORDINARY TEMPERATURE RATING IN NON-STORAGE AREAS. PROVIDE

PENDENT ESFR SPRINKLERS IN STORAGE AREAS.

PROVIDE AT LEAST SIX SPARE SPRINKLERS WITH A MINIMUM OF TWO SPARE SPRINKLERS OF EACH TYPE AND TEMPERATURE CLASSIFICATION. PROVIDE SPARE SPRINKLER CABINET, WRENCHES, AND POSTED LIST OF ITEMS WITHIN THE CABINET. INSTALL

IN LOCATION AS DIRECTED BY BUILDING MAINTENANCE PERSONNEL.

SPRINKLER SYSTEM MUST BE HYDRAULICALLY DESIGNED.

THESE DRAWINGS DEMONSTRATE THE CONFIGURATION OF MAJOR SYSTEM COMPONENTS. THEY ARE DIAGRAMMATIC IN NATURE AND ARE NOT INTENDED TO SHOW EXACT LOCATIONS. PIPE LENGTHS AND ELEVATIONS INDICATED ON THE DRAWINGS (IF SHOWN) ARE APPROXIMATE. COORDINATE FINAL INSTALLATION WITH ACTUAL FIELD CONDITIONS AND OTHER CONSTRUCTION TRADES. THE CONTRACTOR MUST DESIGN THE SPRINKLER SYSTEM TO PROVIDE COMPLETE PROTECTION THROUGHOUT IN

ACCORDANCE WITH NFPA 13.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

WATER SUPPLY

OSF FIRE SUPPRESSION SYSTEMS MUST BE SUPPLIED BY SITE FIRE SUPPRESSION WATER DISTRIBUTION SYSTEM. THIS SYSTEM IS SERVED BY FOUR EXISTING FIRE PUMPS IN PARALLEL. EXISTING PUMPS ARE LOCATED IN BUILDING 1277.

PUMPS ARE CONFIGURED TO START AT 130 PSI.

BUILDING 1277 PUMP TEST DATA WAS RECORDED 3/3/2020 BY EAGLE FIRE INC.

1.

2.

3.

PUMP

FLOW (MEASURED)

% RATED FLOW

CHURN

107% 150%

3,750 5,300

CHURN

107% 151%

3,750 5,300

CHURN

107% 151%

3,750 5,300

PRESSURE (MEASURED)

NET SUCTION DISCHARGE

173.2 139.2 96.2

-1.2 -1.2 -1.2

SPEED

(RPM)

1,793 1,785 1,780

1,789 1,784 1,779

1,783 1,781 1,779

174.2 149.2 92.2

175.2 146.2 91.2

-1.2 -1.2 -1.2

-1.2 -1.2 -1.2

4 (OUT OF SERVICE)

STORAGE 1

STORAGE 2

STO

STO

INCOMING 8"

FIRE SERVICE

FX401

A3

1 2 3 6

F

E

D

C

B

4 5

Lic. No. 044409

AARON P FREIDC

O M M O

N W

EAL

THOF

V

IR

G

IN

IA

P R O F

E

SSIONAL EN

G

IN

E E R

12/17/2021

A B

KEYPLAN

A B

KEYPLAN

ENGINEERS + SURVEYORS

SHEET NOTES:

0 5'

1/8" = 1'-0" GRAPHIC SCALE

10' 20' 30'

N PLAN

NORTH

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

F

O

P E

R A

TI

O

N A

L S

U P

P O

R T

FA

C

IL

IT

Y (O

S F)

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1362850

DRAWFORM REVISION: 07 AUG 2018

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

CJW / SVR

Approved by J. Scott Roberts, Asset Management Branch Head

& Supervisory Facility Planner, PWD Beaufort, SC via email

EJA

DSN

DSN

12/17/2021

B

IM

- P -4

F

-3

O pe ra tio na l S up po rt F ac ili ty /B

LD

G

P

5_ O

S F

-F P

.r vt

/1

6/

1:

:1

A M

1/8" = 1'-0"

F

IR

E S

U P

P R

E S

S

IO

N F

LO

O

R P

LA

N

F

IR

S

T F

L O

O R

FX101

APF AHE AJW

12854120

99 129

1/8" = 1'-0" A1

FIRE SUPPRESSION FLOOR PLAN - FIRST FLOOR

A. PIPING ENTERING INTO THE BUILDING MUST HAVE A

PENETRATION THAT HAS A DIAMETER 6 INCHES LARGER THAN

THE PIPE DIAMETER TO ALLOW FOR SETTLEMENT.

8" DOUBLE CHECK BACKFLOW

PREVENTER WITH OS&Y VALVES

WITH TAMPER SWITCHES

OS&Y VALVE WITH

TAMPER SWITCH

8" INCOMING

FIRE SERVICE

TO SPRINKLER SYSTEM

FIRE DEPARTMENT

CONNECTION

BACKFLOW TEST HEADER.

MANIFOLD 5 HOSE VALVES

W/CAP AND CHAIN

NORMALLY CLOSE

BUTTERFLY VALVE

CHECK VALVE

Lic. No. 044409

AARON P FREIDC

O M M O

N W

EAL

THOF

V

IR

G

IN

IA

P R O F

E

SSIONAL EN

G

IN

E E R

12/17/2021

ENGINEERS + SURVEYORS

SHEET NOTES:

1/2" = 1'-0" GRAPHIC SCALE

1' 2' 4' 8'6'

N PLAN

NORTH

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

F

O

P E

R A

TI

O

N A

L S

U P

P O

R T

FA

C

IL

IT

Y (O

S F)

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1362850

DRAWFORM REVISION: 07 AUG 2018

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

CJW / SVR

Approved by J. Scott Roberts, Asset Management Branch Head

& Supervisory Facility Planner, PWD Beaufort, SC via email

EJA

DSN

DSN

12/17/2021

B

IM

- P -4

F

-3

O pe ra tio na l S up po rt F ac ili ty /B

LD

G

P

5_ O

S F

-F P

.r vt

/1

6/

1:

:1

A M

1/2" = 1'-0"

F

IR

E S

U P

P R

E S

S

IO

N E

N

LA

R G

E D

P

LA

N

FX401

APF AHE AJW

12854121

100 129

1/2" = 1'-0" A3

FIRE SUPPRESSION ENLARGED PLAN

A. PIPING ENTERING INTO THE BUILDING MUST HAVE A

8" DOUBLE CHECK BACKFLOW

PREVENTER WITH OS&Y VALVES

WITH TAMPER SWITCHES

SAND BACKFILL (TYP)

CONCRETE THRUST BLOCK

ROD PIPE-TYPICAL JOINT RESTRAINT

AT INCOMING WATER SERVICE PER

NFPA 24, COAT WITH ASPHALTUM

UNDERGROUND DUCTILE

IRON CEMENT LINED

3'-0" MINIMUM

COVER UNDER

COMPACTED SOIL BACKFILL

GRADE

UNDERGROUND DUCTILE

IRON CEMENT LINED

DRAIN

VALVE

INSPECTOR'S TEST

AND SIGHT GLASS

TO SPRINKLER SYSTEM

OS&Y VALVE WITH

TAMPER SWITCH

RISER CHECK VALVE

VANE-TYPE

FLOW SWITCH

EXTERIOR ELECTRIC SPRINKLER ALARM BELL

PROVIDED BY FIRE ALARM CONTRACTOR

CONCRETE SPLASH BLOCK

GRADE

NOTE: PORTIONS OF THE DETAIL ARE ROTATED FOR CLARITY

SPRINKLER RISER DETAILC3

SCALE: NOT TO SCALEFX501

TO FIRE

DEPARTMENT

CONNECTION

BACKFLOW TEST HEADER.

MANIFOLD 5 HOSE VALVES

W/CAP AND CHAIN

NORMALLY CLOSE

BUTTERFLY VALVE

1" -1

2"

FLOOR SLAB/ROOF DECK

DEFELCTOR TO BE ALIGNED

PARALLEL TO CEILING/ROOF

UPRIGHT SPRINKLER

BRANCH LINE

REDUCING TEE

TYPICAL UPRIGHT SPRINKLERA1

SCALE: NOT TO SCALEFX501

Lic. No. 044409

AARON P FREIDC

O M M O

N W

EAL

THOF

V

IR

G

IN

IA

P R O F

E

SSIONAL EN

G

IN

E E R

12/17/2021

ENGINEERS + SURVEYORS

SHEET NOTES:

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

F

O

P E

R A

TI

O

N A

L S

U P

P O

R T

FA

C

IL

IT

Y (O

S F)

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1362850

DRAWFORM REVISION: 07 AUG 2018

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

CJW / SVR

Approved by J. Scott Roberts, Asset Management Branch Head

& Supervisory Facility Planner, PWD Beaufort, SC via email

EJA

DSN

DSN

12/17/2021

B

IM

- P -4

F

-3

O pe ra tio na l S up po rt F ac ili ty /B

LD

G

P

5_ O

S F

-F P

.r vt

/1

6/

1:

:1

A M

As indicated

F

IR

E S

U P

P R

E S

S

IO

N D

E T

A

IL

S

FX501

APF AHE AJW

12854122

101 129

A. PIPING ENTERING INTO THE BUILDING MUST HAVE A

FIRE SUPPRESSION
FX001 - FIRE SUPPRESSION GENERAL NOTES AND LEGEND
FX101 - FIRE SUPPRESSION FLOOR PLAN - FIRST FLOOR
FX401 - FIRE SUPPRESSION ENLARGED PLAN
FX501 - FIRE SUPPRESSION DETAILS

2022-01-27T07:50:31-0500

2022-01-27T07:51:30-0500

2022-01-27T07:51:31-0500

2022-01-27T07:51:32-0500

2022-02-16T19:33:40-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-02-16T19:34:05-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-02-16T19:34:05-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-02-16T19:34:06-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-02-16T19:34:14-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-02-16T19:34:28-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-02-16T19:34:28-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-02-16T19:34:28-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.

File details come from the government source that posted it. Updated .