SYMBOL DESCRIPTION
SITE ELECTRICAL LEGEND
EXISTING MANHOLE. SUBSCRIPT INDICATES THE MANHOLE NUMBER.
EMH1
DUE REMOVE UNDERGROUND ELECTRICAL DUCT BANK
EUC EXISTING UNDERGROUND TELECOMMUNICATIONS DUCT BANK
DUC REMOVE UNDERGROUND TELECOMMUNICATIONS DUCT BANK
EXISTING TELECOMMUNICATIONS HANDHOLE. SUBSCRIPT INDICATES THE HANDHOLE
NUMBER.ECHH1
EUE EXISTING UNDERGROUND ELECTRICAL DUCT BANK
UE UNDERGROUND ELECTRICAL DUCT BANK
UC UNDERGROUND TELECOMMUNICATIONS DUCT BANK
UTILITY HANDHOLE. SEE A3/EP502 FOR ELECTRICAL HANDHOLE DETAIL. SEE
A1/EP502 FOR TELECOMMUNICATIONS HANDHOLE DETAIL.HH
SYMBOL DESCRIPTION
SINGLE LINE DIAGRAM
PANELBOARD. WHEN ADDITIONAL SYMBOL(S) ARE INCLUDED, THEY INDICATE
THE FOLLOWING:
1H1
DRAW-OUT TYPE CIRCUIT BREAKER WITH NUMBER OF POLES AND TRIP
RATING AS INDICATED.
ADDITIONAL CIRCUIT BREAKER SUBSCRIPTS INDICATE THE FOLLOWING:
3P
100 A
PARALLEL CONNECTED SURGE PROTECTIVE DEVICE. SEE SURGE
PROTECTIVE DEVICE SCHEDULE ON SHEET EP701.
SPD
MULTIFUNCTION DIGITAL POWER CIRCUIT MONITOR.
KEY INTERLOCK
POWER TRANSFORMER WITH DELTA CONNECTED PRIMARY, WYE
CONNECTED SECONDARY AND RATING AS INDICATED.
M
K
SOLID STATE ELECTRONIC TRIP CIRCUIT BREAKER WITH FIELD
ADJUSTABLE LONG TIME PICKUP, SHORT TIME PICKUP, SHORT TIME
DELAY, AND INSTANTANEOUS TRIP FUNCTIONS. INCLUDE ADJUSTABLE
GROUND FAULT PICKUP AND GROUND FAULT DELAY TRIP FUNCTIONS
WHERE GROUND FAULT PROTECTION IS INDICATED.
GFP - CIRCUIT BREAKER EQUIPPED WITH INTEGRAL GROUND FAULT
PROTECTION.
MAIN CIRCUIT BREAKER. SEE PANEL SCHEDULE FOR SIZE. IF
NOT PRESENT, PANELBOARD WITH MAIN LUGS ONLY.
ET -
DRY TYPE TRANSFORMER. SUBSCRIPT INDICATES THE
TRANSFORMER SIZE. SEE TRANSFORMER SCHEDULE ON SHEET
EP701. SEE A1/EP601 FOR GROUNDING DIAGRAM. SEE SINGLE
LINE DIAGRAM FOR TRANSFORMER SIZE.
T
T30
MOUNTINGSYMBOL DESCRIPTION
POWER DISTRIBUTION
SURFACE MOUNTED PANELBOARD
GROUNDING BUS BAR, SUBSCRIPT INDICATES NAME.
REFER TO A3/EP501 FOR DETAIL.
72" AFF TO TOP
18" AFF TO TOP
NA
COMBINATION MAGNETIC STARTER/DISCONNECT SWITCH IN
NEMA 1 ENCLOSURE UNLESS OTHERWISE INDICATED. SEE
MOTOR STARTER SCHEDULE ON SHEET EP701 FOR STARTER
CHARACTERISTICS, AND HOME RUN MOTOR BRANCH CIRCUIT
SIZE. MOTOR BRANCH CIRCUIT SIZE SHALL BE THE SAME FROM
THE STARTER TO MOTOR. MINIMUM SHORT CIRCUIT RATING
SHALL MATCH THE UPSTREAM OVERCURRENT PROTECTIVE
DEVICE. SEE SHEET EP501 FOR STARTER WIRING DIAGRAMS.
SUBSCRIPTS INDICATE THE FOLLOWING:
H-30-3Φ 3R
600V, 3P, NON-FUSED DISCONNECT SWITCH. ALL DISCONNECT
SWITCHES SHALL BE NEMA 1 UNLESS OTHERWISE INDICATED.
SUBSCRIPTS INDICATE THE FOLLOWING:
30A - 3R -
30A 3R
H-30-3Φ
PHASE
MOTOR HP RATING
H - 480V L1- 120V L2 - 208V
72" AFF TO TOP
72" AFF TO TOP
NEMA ENCLOSURE OTHER THAN NEMA 1 (3R, 4X, ETC...)
AMPERE RATING
3R - NEMA ENCLOSURE OTHER THAN NEMA 1 (3R, 4X, ETC...)
POWER DISTRIBUTION EQUIPMENT CODES
1 H 1
1,2,3 - SEQUENCE
H - 480Y/277V L - 208Y/120V
FLOOR LEVEL
EQUIPMENT CODE:
GENERAL NOTES
A. SEE REFLECTED CEILING PLANS FOR EXACT LOCATION OF LUMINAIRES AND DEVICES.
B. INSTALL ALL EQUIPMENT AND DEVICES AT THE HEIGHT INDICATED. REFER TO ARCHITECTURAL
INTERIOR ELEVATIONS FOR SPECIAL MOUNTING HEIGHTS AND LOCATIONS OF ELECTRICAL AND
COMMUNICATIONS DEVICES. MOUNTING HEIGHTS AND LOCATIONS INDICATED ON
ARCHITECTURAL ELEVATIONS TAKE PRECEDENCE OVER OTHER MOUNTING HEIGHTS AND
LOCATIONS.
C. LUMINAIRE TYPES INDICATED AS FOLLOWS: UPPER CASE LETTER WITH NUMERAL DENOTES
FIXTURE TYPE (SEE LUMINAIRE SCHEDULE), LOWER CASE LETTER (IF SHOWN) DENOTES
SWITCHING ARRANGEMENT.
D. ALL MATERIALS AND EQUIPMENT SHALL BE LISTED AS COMPLYING WITH THE APPLICABLE
STANDARDS OF UNDERWRITER'S LABORATORIES, INC OR OTHER APPROVED LISTING
AGENCIES.
E. CONDUCTOR AMPACITIES ARE BASED ON 60° C COPPER FOR #12 AWG THROUGH #1 AWG
CONDUCTORS. CONDUCTOR AMPACITIES ARE BASED ON 75° C COPPER FOR CONDUCTORS
LARGER THAN #1 AWG.
F. ALL CONDUIT SIZES ARE BASED ON ELECTRICAL METALLIC TUBING (EMT) WITH TYPE
THHN/THWN COPPER CONDUCTORS. ADJUST CONDUIT SIZE AS REQUIRED FOR OTHER
CONDUIT MATERIALS AND CONDUCTOR TYPES.
G. THE PANELBOARD SUPPLIER SHALL BE RESPONSIBLE FOR PROVIDING OVERCURRENT
PROTECTIVE DEVICES THAT ARE SELECTIVELY COORDINATED. REFER TO SPECIFICATION
SECTION 26 28 01.00 10 FOR REQUIREMENTS.
H. COORDINATE LOCATION AND ROUTING OF ALL CONDUITS WITH OTHER TRADES AND SYSTEMS
TO PROVIDE A COORDINATED INSTALLATION AND TO ASSURE MAXIMUM ACCESSIBILITY TO ALL
SYSTEMS. ALL JUNCTION BOXES AND PULL BOXES SHALL REMAIN ACCESSIBLE.
I. WHEN CONTRACTOR FURNISHED EQUIPMENT INCLUDING BUT NOT LIMITED TO ARCHITECTURAL
HARDWARE (IE WINDOW SHADES, OVERHEAD COILING DOORS AND GRILLS, POWER OPERATED
DOORS, ETC...), AND HVAC EQUIPMENT SIZE OR ELECTRICAL CHARACTERISTICS PROVIDED
DIFFERS FROM SIZE OR ELECTRICAL CHARACTERISTICS INDICATED OR SPECIFIED, MAKE ALL
NECESSARY ADJUSTMENTS TO ELECTRICAL BOXES, CONDUIT, WIRING, DISCONNECT DEVICES,
BRANCH CIRCUIT PROTECTION, AND RELATED ELECTRICAL DISTRIBUTION EQUIPMENT
INCLUDING ANY ELECTRICAL REDESIGN AS REQUIRED TO ACCOMMODATE EQUIPMENT
ACTUALLY PROVIDED.
J. PROVIDE SEPARATE NEUTRAL CONDUCTOR FOR EACH 277V AND 120V BRANCH CIRCUIT, UON.
MULTIPLE 20A BRANCH CIRCUITS FROM THE SAME PANELBOARD MAY BE COMBINED IN A
SINGLE 1/2" CONDUIT HOME RUN, MAXIMUM OF (3) CIRCUIT PER HOME RUN.
K. ALL CEILING MOUNTED LIGHTING OCCUPANCY SENSORS AND FIRE ALARM SMOKE DETECTORS
SHALL BE LOCATED SUCH THAT THERE IS A MINIMUM OF 36” BETWEEN THE SENSOR AND ANY
HVAC RETURN/SUPPLY DIFFUSERS.
ABBREVIATIONS
A AMPERES
AFC
AFF
HV
AFG
INC
AIC
JB
ATS
KAIC
AWG
KV
BFC
KVA
BFG
KVAR
C
KW
CAB
KWH
CATV
LAN
CCTV
LED
CKT
LTG
CL
m
CLG
mm
CT's
MAX
CU
MCB
DISC
MCC
DWG
MCP
EA
MFR
EF
MIN
EMT
MISC
EQUIP
MTR
EUH
MTD
EWC
MTS
EWH
N.C.
EXH
N.O.
EXIST
NA
FA
NC
FLUOR
NEC
GEN
NFPA
GFI
PNL
GFGI
PVC
GFP
REC
RGS
GND
TEL
HGT
TYP
HOA
UON
HP
V
VAV
W
G
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
HIGH VOLTAGE
ABOVE FINISHED GRADE
INCANDESCENT
AMPERES INTERRUPTING CAPACITY
JUNCTION BOX
AUTOMATIC TRANSFER SWITCH
KILO-AMPERES INTERRUPTING
CAPACITY
AMERICAN WIRE GAUGE
KILO-VOLTS
BELOW FINISHED CEILING
KILO-VOLTS-AMPERES
BELOW FINISHED GRADE
KILO-VOLTS-AMPERES REACTIVE
CONDUIT
KILO-WATTS
CABINET
KILO-WATT-HOURS
CABLE TELEVISION
LOCAL AREA NETWORK
CLOSED CIRCUIT TELEVISION
LIGHT-EMITTING DIODE
CIRCUIT
LIGHTING
CENTERLINE
METER
CEILING
MILLIMETER
CURRENT TRANSFORMERS
MAXIMUM
COPPER
MAIN CIRCUIT BREAKER
DISCONNECT(ING)
MOTOR CONTROL CENTER
DRAWING(S)
MOTOR CIRCUIT PROTECTOR
EACH
MANUFACTURER
EXHAUST FAN
MINIMUM
ELECTRICAL METALLIC TUBING
MISCELLANEOUS
EQUIPMENT
MOTOR
ELECTRIC UNIT HEATER
MOUNTED
ELECTRIC WATER COOLER
MOUNTING
ELECTRIC WATER HEATER
MANUAL TRANSFER SWITCH
EXHAUST
NORMALLY CLOSED
EXISTING
NORMALLY OPEN
FIRE ALARM
NOT APPLICABLE
FLUORESCENT
NURSE CALL
GROUND
NATIONAL ELECTRICAL CODE
ENGINE GENERATOR SET
NATIONAL FIRE PROTECTION
ASSOCIATION
GROUND FAULT INTERRUPTER
GROUND FAULT CIRCUIT INTERRUPTER
PANEL
GOVERNMENT FURNISHED,
GOVERNMENT INSTALLED
POLYVINYL CHLORIDE
GROUND
RECEPTACLE
HEIGHT
RIGID GALVANIZED STEEL
HAND-OFF-AUTOMATIC
TELEPHONE
HORSEPOWER
TYPICAL
UNLESS OTHERWISE NOTED
VOLTS
GFCI
GROUND FAULT PROTECTION
WAP
VARIABLE AIR VOLUME UNIT
WP
WATTS
XFMR
WIRELESS ACCESS POINTHVAC HEATING/VENTILATING / AIR
CONDITIONING WEATHER PROOF
MTG
TRANSFORMER
AHU AIR HANDLING UNIT
CH CHILLER
UH UNIT HEATER
VA VOLT-AMPERES
SF SUPPLY FAN
SYMBOL DESCRIPTION MOUNTING
MISCELLANEOUS
KEY NOTE SYMBOL. 00
ELECTRICAL GROUND
CONDUCTOR CONNECTION
LIGHTING CONTACTOR.
POINT OF REMOVAL, DEMOLITION.
POINT OF CONNECTION, EXISTING TO NEW WORK.
NA
NA
NA
5'-0" AFF TO TOP
NA
NA
LC
FCU/A
AS INDICATED
SYMBOL DESCRIPTION MOUNTING
EQUIPMENT CONNECTIONS
JUNCTION BOX OR PULL BOX
NAMOTOR CONNECTION
AS REQUIREDCONNECTION TO EQUIPMENT LEADS, TERMINAL STRIPS OR
CONTROL PANEL INCLUDING ALL CONDUCTORS, CONDUIT,
FLEXIBLE CONDUIT, JUNCTION BOXES, CONNECTORS, FITTINGS,
ETC., REQUIRED FOR PROPER CONNECTION. COORDINATE
EXACT LOCATION WITH THE SUPPLIED EQUIPMENT. SUBSCRIPT
INDICATES EQUIPMENT IDENTIFICATION.
J
M
E
SYMBOL DESCRIPTION
LIGHTNING PROTECTION SYSTEM
LIGHTNING PROTECTION SYSTEM ROOF CONDUCTOR.
GL
DN1
A - STANDING SEAM METAL ROOF MOUNTED AIR TERMINAL.
SEE A2/EQ501 FOR DETAIL.
AIR TERMINAL.
SUBSCRIPTS INDICATE THE FOLLOWING:
LIGHTNING PROTECTION SYSTEM GROUND LOOP CONDUCTOR. BURY IN DIRECT
CONTACT WITH EARTH AT 24" BELOW FINISHED GRADE.
GROUND RODS BONDED TO GROUND LOOP CONDUCTOR. SEE A1/EQ501 FOR DETAIL.
BONDING CONNECTION.
THROUGH ROOF CONDUCTOR DETAIL "DN1". SEE C3/EQ501 FOR DETAIL.
DN2 ROUTE LIGHTNING PROTECTION CONDUCTOR EXPOSED DOWN TO LOWER ROOF.
PANELBOARD DESIGNATION.
CIRCUIT DESIGNATION.
SYMBOL DESCRIPTION
CONDUIT AND CONDUCTORS
BRANCH CIRCUIT WIRING IN CONDUIT. 1/2"C - 2#12 + 1#12 GND UON. PROVIDE
ADDITIONAL SWITCHED CONDUCTORS OR TRAVELER CONDUCTORS FOR LIGHTING
CIRCUITS AS REQUIRED TO SUPPORT THE INDICATED SWITCHING.
HOMERUN TO PANELBOARD: 1ALN1 - 1,3,5
WIRING DEVICES
DESCRIPTION MOUNTING
18" AFF
SYMBOL
NOTES: ALL MOUNTING HEIGHTS ARE TO TOP, UON
SUBSCRIPTS FOR RECEPTACLES INDICATE THE FOLLOWING:
G - +48" -
WP - IN-USE WEATHER-PROOF COVER.
MOUNT AT 48" AFF TO CENTER. OTHER MOUNTING HEIGHTS AS INDICATED.
INTEGRAL GFCI.
20A, 125V DUPLEX RECEPTACLE.
48" AFF TO
CENTER
ROTARY COUNTDOWN TIMER FOR CEILING FAN
CONTROL. MAXIMUM TIME SETTING OF 30 MINUTES.
120V, 20A. SWITCH SHALL BE RATED TO DRIVE TWO FANS
MINIMUM AT FULL SPEED.
S T a,b SWITCH LEG(S). PROVIDE SEPARATE PUSHBUTTON FOR
EACH SWITCH LEG.
DIGITAL LIGHTING CONTROL DEVICES
NOTES:
1. THE DIGITAL LIGHTING CONTROL SYSTEM SHALL CONSIST OF LOCAL RELAY PACKS,
OCCUPANCY SENSORS, AND DIGITAL SWITCHES. THE NUMBER OF RELAYS SHALL MATCH THE
NUMBER OF LIGHTING SWITCH LEGS IN EACH ROOM.
2. PROVIDE JUNCTION BOX FOR RELAY PACKS. ALL JUNCTION BOXES CONTAINING ELECTRICAL
COMPONENTS SHALL BE LOCATED IN AN ACCESSIBLE LOCATION ABOVE ACCESSIBLE CEILINGS.
LABEL EACH JUNCTION BOX CONTAINING ELECTRICAL COMPONENTS TO INDICATE ITS
FUNCTION. PROVIDE BOX DIVIDER FOR EACH BOX CONTAINING LINE VOLTAGE AND LOW
VOLTAGE WIRING.
3. IN ROOMS WITH TILED FINISHED CEILINGS, PROVIDE IDENTIFICATION PLATE ON THE CEILING
SYSTEM T-FRAME INDICATING LOCATION OF JUNCTION BOXES ABOVE CONTAINING ELECTRICAL
COMPONENTS.
4. LOW VOLTAGE CONTROL WIRING SHALL BE IN ACCORDANCE WITH THE MANUFACTURERS
RECOMMENDATIONS.
5. ALL LINE VOLTAGE WIRING SHALL BE #12 AWG IN 1/2” CONDUIT.
6. ALL LOW VOLTAGE WIRING, INCLUDING 0-10V DIMMING WIRING CABLE SHALL BE IN 1/2” CONDUIT.
7. THE LINE VOLTAGE AND LOW VOLTAGE WIRING SHALL BE SEPARATED IN ACCORDANCE WITH
NFPA 70.
8. PROVIDE ADDITIONAL OCCUPANCY SENSORS AS REQUIRED TO PROVIDE ADEQUATE COVERAGE
OF CONTROLLED AREA.
9. SETTINGS OF OCCUPANCY SENSORS: MANUAL “ON”, AUTO “OFF”, 10 MINUTE TIME DELAY UON.
10. PROVIDE ALL COMPONENTS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM.
11. INSTALL COMPONENTS PER MANUFACTURER'S APPROVED SHOP DRAWINGS.
12. REFER TO SHEET EL601 FOR TYPICAL LIGHTING CONTROL SYSTEM WIRING DIAGRAM.
48" AFF TO
CENTER
SYMBOL DESCRIPTION MOUNTING
DIGITAL SWITCH. SUBSCRIPTS INDICATE THE FOLLOWING:
DIGITAL, DUAL-TECHNOLOGY OCCUPANCY SENSOR. SUBSCRIPT
INDICATES THE FOLLOWING:
CEILING
a,b SWITCH LEG(S)-
DIGITAL, LOCAL LIGHTING RELAY PACK WITH CONTACT FOR FIRE
ALARM INTERFACE. SUBSCRIPT INDICATES THE FOLLOWING:
CEILING
SWITCH LEG(S)-
LR
DIGITAL LIGHTING CONTROL SYSTEM SEQUENCE
OF OPERATIONS
SYMBOL DESCRIPTION
A
LIGHTING
MANUAL “ON” VIA DIGITAL WALL SWITCH(ES).
AUTO “OFF” VIA ROOM DIGITAL OCCUPANCY SENSOR(S).
DESCRIPTION MOUNTINGSYMBOL
LUMINAIRES
PENDANT MOUNT FIXTURE, UON. PENDANT
PENDANT
WALL MOUNTED LUMINAIRE. WALL
EXIT SIGN. SHADED PORTION DENOTES FACE(S). DIRECTIONAL
ARROWS AS INDICATED.
4" ABOVE TOP OF
DOOR FRAME TO
BOTTOM OF
FIXTURE
NOTES:
1. SEE LIGHTING FIXTURE SCHEDULE FOR FIXTURE TYPES.
2. OTHER FIXTURE DIMENSIONS AND SHAPES ARE AS INDICATED ON LIGHTING PLANS.
PENDANT MOUNT FIXTURE, UON.
NORMAL POWER.
EMERGENCY POWER / INVERTER POWER
SYMBOL DESCRIPTION
SITE LIGHTING
EXISTING POLE MOUNTED AREA LUMINAIRE, SINGLE HEAD.
EX
SOLID LINES INDICATE EQUIPMENT PROVIDED IN THIS CONTRACT.
SCREENED LINES INDICATE EXISTING EQUIPMENT.
LINE TYPE DESCRIPTION
LINE TYPES
DASHED LINES INDICATE EQUIPMENT REMOVED IN THIS CONTRACT.
HATCH LINES INDICATE EQUIPMENT REMOVED IN THIS CONTRACT.
No 64299
STATE OF
S G
CY
Z
RLA BUZ
O
H
CI
N
P R
O F
N
SS
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
2/
/2
:2 0:
A
M
As indicated
E
LE
C T
R
IC
A L
LE
G
E N
D A
N D
A B
B R
E V
IA
T
IO
N
S
EG001
RLW RLW NGZ
12854135
B
Y A
M E
N D
M E
N T
F
E B
UG ELEC
10 W
21.9
EUE
EMH839
BUILDING 2146
EUC
EUC
EUC
EUC
E U
C
EUC
EUC
DUC
X
DUE
X
X
X
X
X
X X
X
EUE
ECHH1
DUE
DUE 8
X X X X X X X X X X X X X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
EUE
EXISTING HANDHOLE
SERVING VEHICLE
GATE POWER
CIRCUIT.
X X X
X
X
X X
X X
X X
EX
EX
EX
EX
EUC
DUC
DUC
ECHH4
ECHH4A
X
X
X
X
X
X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X
EUC
No 64299
STATE OF
S G
CY
Z
RLA BUZ
O
H
CI
N
P R
O F
N S
S
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
SHEET NOTES:
NOTES:
1" = 20' GRAPHIC SCALE
20'0 60'40' 80'10'
N PLAN
NORTH
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
2/
/2
:2 0:
A
M
1" = 20'-0"
S
IT
E U
T
IL
IT
Y
P
LA
N
E L
E C
T R
IC
A
L D
E M
O L
IT
IO
N
ED101
RLW RLW NGZ
12854136
1" = 20'-0"
A1
SITE PLAN - ELECTRICAL UTILITY - DEMOLITION
KEY NOTES: 00 A. THE LOCATION AND COMPOSITION OF EXISTING UTILITIES ARE SHOWN IN AN
APPROXIMATE MANNER ONLY. FIELD VERIFY THE EXACT LOCATION OF
EXISTING UTILITIES PRIOR TO ANY EXCAVATION WORK.
B. PRIOR TO PENETRATING CONDUITS INTO EXISTING MANHOLES, INVESTIGATE
THE CONDITION OF THE EXISTING STRUCTURE AND DETURMINE THE
APPROPRIATE MEANS AND METHODES TO AVOID ANY DAMAGE TO THE
EXISTING STRUCTURE AND UTILITIES ROUTED WITHIN IT.
C. PROVIDE 30 DAYS NOTICE TO THE CONTRACTING OFFICER FOR ANY
SCHEDULED SERVICE OUTAGES RELATED TO REMOVAL OF EXISTING
CABLES.
D. WHERE UNDERGROUND POWER AND COMMUNICATIONS DUCT BANKS AND
CABLING ARE INDICATED TO BE REMOVED, PROVIDE AS MUCH REPLACEMENT
WORK AS POSSIBLE PRIOR TO REMOVAL TO MINIMIZE THE DURATION OF
REQUIRED SERVICE OUTAGES.
1 APPROXIMATE LOCATION OF ELECTRICAL ROOM HOUSING PANEL DP-1E
SERVING EXISTING TRAILERS.
2 REMOVE 2 1/2" CONDUIT WITH (3) 350KCMIL + (1)#3G SERVING EXISTING
TRAILER 150KVA TRANSFORMERS, ASSOCIATED DISCONNECT, AND PANELS
QUANTITY OF TWO. CONDUITS MAY BE ABANDONED WHERE ROUTED
UNDER THE FIRE LANE AND EXISTING BUILDING 2146. REMOVE FEEDERS
BACK TO PANEL DP-1E LOCATED IN BUILDING 2146. UPDATE PANEL
SCHEDULE FOR PANEL DP-1ETO IDENTIFY BREAKERS AS "SPARE".
3 REMOVE 200A, 600V, 3P DISCONNECT, METER SOCKET ENCLOSURE AND
400A, 208Y/120V, 3 PHASE, 4 WIRE PANELBOARD SERVING EXISTING
TRAILERS.
4 REMOVE AND PROTECT EACH 150KVA, 480V-208Y/120V, 3 PHASE, 4 WIRE DRY
TYPE TRANSFORMER SERVING THE EXISTING TRAILERS. DELIVER THE
TRANSFORMERS TO PUBLIC WORKS WAREHOUSE AT BUILDING 617 AFTER
REMOVAL.
5 REMOVE EXISTING POLE TOP LIGHT FIXTURE, POLE AND BASE. POLE TOP
FIXTURES ARE SERVED FROM THE 400A PANELS SERVING THE EXISTING
TRAILERS SCHEDULED FOR DEMOLITION. REMOVE ALL UNDERGROUND
CONDUIT AND WIRING BACK TO THE PANEL SERVING THE POLE TOP
LIGHTING FIXTURES.
6 EXISTING PERIMETER FENCE SECURITY LIGHT TO REMAIN.
7 REMOVE UNDERGROUND TELECOMMUNICATIONS DUCT SERVING TRAILERS.
REMOVE OUTSIDE PLANT COPPER AND FIBER OPTIC CABLES BACK TO HAND
HOLE ECHH1.
8 EXISTING 1"C - (2)#4 + (1) #8 GND. SERVING VEHICLE GATE CONTROLLER.
REMOVE EXISTING CIRCUIT AS INDICATED AND RE-FEED VEHICLE GATE AS
INDICATED ON SHEET ES100. GATE CONTROLLER IS FED FROM PANEL LP-1E
IN BUILDING 2146 VIA A 40A, 2P CIRCUIT BREAKER.
9 EXISTING 1"C - (2)#4 + (1)#8 GND TO VEHICLE GATE.
10 EXISTING TRAILER TO BE REMOVED BY OTHERS.
11 REMOVE 2 1/2" CONDUIT WITH (3) #10 + (1)#10G SERVING EXITING PUMP
STATION.
12 REMOVE 2 1/2" CONDUIT WITH (3) 350KCMIL + (1)#3G SERVING EXITING
TRAILER 150KVA TRANSFORMERS, QUANTITY OF TWO. CONDUITS MAY BE
ABANDONED WHERE ROUTED UNDER THE FIRE LANE AND EXISTING
BUILDING 2146. REMOVE FEEDERS BACK TO PANEL DP-1E LOCATED IN
B2146. UPDATE PANEL SCHEDULES FOR DP-1E.
13 REMOVE 48 STRAND SINGLE MODE DIRECT BURIED FIBER OPTIC CABLE TO
POINTS INDICATED. REFER TO B3/EP600 FOR ADDITIONAL INFORMATION.
14 REMOVE EXISTING HANDHOLE.
B
Y A
M E
N D
M E
N T
F
E B
2"
2"
2"
14.38'
.0 1'
.2 0'
.3 4'
.7 1'
B
E (3)
C
C
C
E(2)
J
J (2
(2)
E.
UG
UT
IL.
T.B.M. #1
ELEVATION = 17.22
PT# 1
P T#
E
B
1 6
EUE
UE
EMH839
UC
EUE
OSF BUILDING
EUC
EUC
BUILDING 2146
ECHH1
EUE
PHH1
PHH2
PHH3
EXISTING HANDHOLE
SERVING VEHICLE
GATE POWER
CIRCUIT.
EX
HH
LEVEL 2 SECURITY FENCE
EUC
EUC
UC
UC
ECHH4
CHH1
No 64299
STATE OF
S G
CY
Z
RLA BUZ
O
H
CI
N
P R
O F
N S
S
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
KEY NOTES 00
NOTES:
1" = 20' GRAPHIC SCALE
20'0 60'40' 80'10'
N PLAN
NORTH
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
2/
/2
:2 0:
A
M
1" = 20'-0"
S
IT
E U
T
IL
IT
Y
P
LA
N
E
LE
C T
R
IC
A L
E
A S
T
ES100
RLW RLW NGZ
12854137
1" = 20'-0" A1
SITE PLAN - ELECTRICAL UTILITY - EAST
1 EXISTING PERIMETER FENCE SECURITY LIGHT TO REMAIN.
2 2-WAY CONCRETE ENCASE DUCTBANK FOR OUTSIDE PLANT
TELECOMUNICATIONS CABLES TO TELECOMUNICATIONS TERMINATION
EQUIPMENT. SEE C1/EP502 FOR DETAIL. CONCRETE ENCASEMENT IS NOT
REQUIRED WHERE ROUTED UNDER BUILDING CONCRETE SLAB. ONE DUCT
SHALL REMAIN EMPTY.
3 2-WAY CONCRETE ENCASE DUCTBANK. SEE C4/EP502 FOR DETAIL. SEE
SHEET EP600 FOR FEEDER SIZE.
4 EXTEND DUCTBANK TO TELECOMMUNICATIONS TERMINATION EQUIPMENT.
SEE SHEET EP101 FOR TERMINATION LOCATION. PROVIDE WATER TIGHT
SEAL ON SPARE CONDUIT. SEE A4/EP600 FOR OUTSIDE PLANT CABLE
TERMINATION REQUIREMENTS. COORDINATE EXACT ROUTING WITH
STRUCTURAL FOUNDATIONS.
5 EXTEND DUCTBANK TO PANEL 1H1 LOCATION. TURN CONDUITS UP
BENEATH PANEL 1H1. SEE SHEET EP600 FOR SIZE AND QUANTITY OF
CONDUCTORS. ONE DUCT SHALL REMAIN EMPTY. PROVIDE CONDUIT CAP
ON SPARE CONDUIT. COORDINATE EXACT ROUTING WITH STUCTURAL
FOUNDATIONS.
6 EXISTING 8-WAY CONCRETE ENCASED DUCTBANK. UTILIZE ONE OF THE
TWO 4" SPARE CONDUITS TO ROUTE NEW FEEDER FROM SWITCHGEAR 2146
TO PANEL 1H1. SEE SHEET EP600 FOR FEEDER CONDUCTOR SIZE AND
QUANTITY.
7 SPLICE TO EXISTING 50 PAIR OUTSIDE PLANT COPPER AND 48 STRAND
SINGLE MODE FIBER IN EXISTING HANDHOLE. COORDINATE ALL WORK IN
EXISTING HANDHOLE WITH CONTRACTING OFFICER.
8 SEE SHEET ES101 FOR CONTINUATION.
9 INTERCEPT AND SPLICE TO EXISTING (2)#4 + (1)#8 GND BRANCH CIRCUIT
SERVING VEHICLE GATE. EXTEND CIRCUIT TO SECOND SPLICE POINT AS
INDICATED.
10 1"C - (2)#4 + (1)#8 GND FOR VEHICLE GATE. DIRECT BURY CONDUIT AT 36"
BFG TO TOP.
11 EXISTING 1"C - (2)#4 + (1)#8 GND TO VEHICLE GATE.
12 (2) 4" CONDUITS FOR VEHICLE GATE CONTROLS. PROVIDE 3-CELL FABRIC
MESH INNERDUCT WITH 48 STRAND SINGLE MODEL FIBER OPTIC CABLE IN
ONE OF THE TWO CONDUITS, THE REMAINING CONDUIT WILL BE SPARE.
DIRECT BURY CONDUIT AT 36" BFG TO TOP.
B
Y A
M E
N D
M E
N T
F
E B
3P
ET
600 A
5000A, 3ø, 4W, 480Y/277V, 65KAIC
3P
ET
1200 A
3P
ET
225 A
3P
ET
400 A
EXISTING SWITCHGEAR 2146
3P
ET
1200 A
3P
ET
1200 A
3P
ET
1200 A
3P
ET
800 A
3P
ET
GFP
5000 A
3P
ET
GFP
5000 A
P
E T
G F
P
A
N .O
N.C.N.C.
M M
K K
K
NEUTRAL BUS
GROUND BUS
5000A, 3ø, 4W, 480Y/277V, 65KAIC
EXISTING
ATS-1
EXISTING
SPARE
EXISTING
SPARE
EXISTING
DP-HW
EXISTING
DP-HE
EXISTING
ATS-2
EXISTING
MP-HE
EXISTING
MH ES-2
3750 KVA,
12470-480Y/277V, 5.8%IZ
3750 KVA,
12470-480Y/277V, 5.8%IZ
TO 15KV
SECTIONALIZING
SWITCH
TO 15KV
SECTIONALIZING
SWITCH
1H1
RM. 101
1L1
RM.101
T T-1L1
30KVA
SPD
SE
SPD
BL
RM. 101
RM 101 LEVEL 1
48 STRAND SINGLE
MODE FIBER OPTIC
CABLE
50 PAIR
OUTSIDE PLANT
COPPER CABLE
BUILDING
ENTRANCE
PRIMARY
PROTECTORS
WALL MOUNTED DOUBLE
HINGED
TELECOMMUNICATIONS
CABINET WITH 48 PORT FIBER
OPTIC PATCH PANEL AND
NETWORK SWITCH.
EXISTING HANDHOLE ECHH1.
SPLICE TO EXISTING 50 PAIR
OUTSIDE PLANT CABLE AND 48
STRAND SINGLE MODE FIBER
IN HANDHOLE. SEE SHEET
ES100 FOR LOCATION.
DUCTBANK
SPARE CONDUIT
3-CELL FABRIC MESH
INNERDUCT WITH 48 STRAND
SINGLE MODE FIBER OPTIC
CABLE
(2) 4" CONDUITS
ECHH4 CHH1
SPLICE TO EXISTING 48
STRAND SINGLE MODE FIBER
IN HANDHOLE. SEE SHEET
ES100 FOR LOCATION.
SPLICE TO EXISTING 48
STRAND SINGLE MODE FIBER
IN HANDHOLE. SEE SHEET
ES100 FOR LOCATION.
EXISTING 48 STRAND
SINGLE MODE FIBER
OPTIC CABLE
ECHH4
EXISTING HANDHOLE ECHH4. PULL
BACK EXISTING 48 STRAND SINGLE
MODE FIBER TO THIS HANDHOLE TO
SPLICE TO NEW CABLE. SEE SHEET
ED101 FOR LOCATION.
ECHH4A
INTERCEPT DUCTBANK AND PROVIDE
NEW HANDHOLE. PULL BACK EXISTING
48 STRAND SINGLE MODE FIBER TO
THIS POINT TO SPLICE TO NEW CABLE.
SEE ED101 FOR LOCATION.
SPLICE CLOSURE IN
EXISTING
HANDHOLE
SPLICE CLOSURE IN
NEW HANDHOLE
CUT CABLE IN THIS
HANDHOLE AND PULL BACK
TO EACH SPLICE POINT.
DEMOLITION
REPLACEMENT WORK
No 64299
STATE OF
S G
CY
Z
RLA BUZ
O
H
CI
N
P R
O F
N S
S
OI
E
LA ENG
IN
E E
R
LICENSE
F LORI DA
I K
ENGINEERS + SURVEYORS
KEY NOTES 00
NOTES:
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
T
IO
N S
S U
P P
O R
T F
A C
IL
IT
Y
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 25 AUG 2020
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
DJD
EJA
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
-P
5-
0- E
L_ R
.rv t
2/
/2
:2 0:
A
M
NTS
S
IN
G
LE
L
IN
E D
IA
G
R A
M
EP600
RLW RLW NGZ
12854145
NOT TO SCALE
A1
SINGLE LINE DIAGRAM
NOT TO SCALE
A4
BACKBONE CABLE RISER
1 SEE DRY TYPE TRANSFORMER SCHEDULE ON SHEET EP701 FOR CONDUIT
AND WIRE SIZE.
2 SEE SHEET EP601 FOR GROUNDING REQUIREMENTS.
3 EXISTING SIEMENS 225A, 480V, 3 POLE, 65KAIC, TYPE WLS CIRCUIT BREAKER
WITH ETU745 ADJUSTABLE TRIP UNIT. REVISE SETTING AS INDICATED: LTPU:
1.0, LTD: 30, STPU: 6.0, STD: 0.1 ON, INST: 6.0.
4 (4)#300KCMIL + (1)#1/0 GND (ALUMINUM). ROUTE FEEDER IN EXISTING
DUCTBANK. SEE SHEET ES100 FOR ADDITIONAL INFORMATION.
5 (4)#300KCMIL + (1)#1/0 GND (ALUMINUM). ROUTE FEEDER IN NEW DUCTBANK.
SEE SHEET ES100 FOR ADDITIONAL INFORMATION.
6 THE AVAILABLE SHORT CIRCUIT AT SWGR 2146 IS 50,000A BASED ON
AS-BUILT DRAWINGS. THE EXISTING METERED PEAK LOAD FOR SWGR 2146
IS 425KVA.
7 CIRCUIT BREAKER SHALL BE 100% RATED AND SERVE AS THE MEANS OF
DISCONNECT FOR THE BUILDING.
8 3"C - (4)#300KCMIL + (1)#1/0 GND (ALUMINUM).
9 TO ADVANCED METERING EQUIPMENT CABINET. SEE C3/EP502 FOR
CONNECTION DIAGRAM.
10 DO NOT BOND THE NEUTRAL BUS AND GROUND BUS IN THIS PANEL.
LINE TYPE LEGEND
INDICATES EXISTING EQUIPMENT TO REMAIN
INDICATES NEW EQUIPMENT
NOT TO SCALE
B3
ACCESS GATE FIBER OPTIC CABLE REPLACEMENT RISER DIAGRAM
COIL 50' OF
SLACK CABLE
IN HANDHOLE
COIL 50' OF
SLACK CABLE
IN HANDHOLE
B
Y A
M E
N D
M E
N T
F
E B
| ELECTRICAL_R2 |
| EG001 - ELECTRICAL LEGEND AND ABBREVIATIONS |
| ED101 - SITE UTILITY PLAN - ELECTRICAL DEMOLITION |
| ES100 - SITE UTILITY PLAN - ELECTRICAL - EAST |
| EP600 - SINGLE LINE DIAGRAM |
| 2023-02-13T10:31:31-0500 | |
| Orlando | |
| Nick Zubrzycki | |
| I am signing to certify the authenticity of this document. |
| 2023-02-13T10:32:07-0500 | |
| Orlando | |
| Nick Zubrzycki | |
| I am signing to certify the authenticity of this document. |
| 2023-02-13T10:32:07-0500 | |
| Orlando | |
| Nick Zubrzycki | |
| I am signing to certify the authenticity of this document. |
| 2023-02-13T10:32:07-0500 | |
| Orlando | |
| Nick Zubrzycki | |
| I am signing to certify the authenticity of this document. |
File details come from the government source that posted it. Updated .