FIRE ALARM LEGEND
FIRE ALARM CONTROL PANEL
KINGFISHER RADIO TRANSMITTER
REMOTE ANNUNCIATOR PANEL
FIRE ALARM DOCUMENT CABINET
WALL MOUNTED COMBINATION HORN/CLEAR STROBE
(SUPERSCRIPT INDICATES CANDELA RATING)
WALL MOUNTED HORN
WATER FLOW ALARM BELL
CONTROL MODULE
MONITOR MODULE
MANUAL PULL STATION
SURGE SUPPRESSOR
TAMPER SWITCH
WATER FLOW SWITCH
AREA SMOKE DETECTOR
MM
P
FACP
SS
ANN
CD
KF
DC
CM
Lic. No. 044409
AARON P FREIDC
O M M O
N W
EAL
THOF
V
IR
G
IN
IA
P R O F
E
SSIONAL EN
G
IN
E E R
12/17/2021
ENGINEERS + SURVEYORS
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
TI
O
N A
L S
U P
P O
R T
FA
C
IL
IT
Y (O
S F)
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V A
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 07 AUG 2018
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
EJA
DSN
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
P
5_ O
S F
-F P
.r vt
/1
6/
1:
:0
A M
12" = 1'-0"
F
IR
E A
LA
R
M G
E N
E R
A L
N O
T E
S A
N D
L E
G E
N D
FA001
APF AHE AJW
12854116
95 129
FIRE ALARM SYSTEM GENERAL NOTES:
PROVIDE OSF WITH AN ADDRESSABLE FIRE ALARM SYSTEM.
APPLICABLE CRITERIA:
NFPA 70 NATIONAL ELECTRICAL CODE (NEC), 2020
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2019
UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES (CHANGE 6), 6 MAY 2021
UFC 4-440-01 WAREHOUSE AND STORAGE FACILITIES (CHANGE 1, 1 APRIL 2019)
INSTALLATION DRAWINGS, SHOP DRAWINGS OR WORKING PLANS, CALCULATIONS, OTHER REQUIRED PRE-CONSTRUCTION DOCUMENTATION AND AS-BUILT DRAWINGS MUST BE PREPARED BY, OR UNDER THE DIRECT SUPERVISION OF A LICENSED PROFESSIONAL FIRE PROTECTION ENGINEER OR A NICET ENGINEERING TECHNICIAN CERTIFIED IN THE FIELD OF FIRE PROTECTION ENGINEERING TECHNOLOGY WITH A MINIMUM LEVEL III IN
THE APPROPRIATE SUBFIELD.
DEVICES MUST BE UL LISTED.
INITIATING DEVICE CIRCUITS, NOTIFICATION APPLIANCE CIRCUITS, AND SIGNALING LINE CIRCUITS MUST BE CLASS B.
CONDUIT, JUNCTION/BACK BOXES, COVERS AND COUPLINGS, WHEN PROVIDED, MUST BE FACTORY PAINTED RED.
SYSTEM POWER AND GROUND CIRCUITS MUST BE TYPE "THHN" SOLID OR STRANDED COPPER SIZED ACCORDING TO THE MANUFACTURER'S
RECOMMENDATIONS AND THE APPLICABLE CODES AND BE INSTALLED IN CONDUIT.
WIRING, CABLES, BOXES, TROUGHS AND OTHER RELATED EQUIPMENT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE NATIONAL
ELECTRICAL CODE (NEC).
WALL-MOUNTED VISIBLE AND COMBINATION AUDIBLE/VISIBLE ALARM NOTIFICATION APPLIANCES MUST BE MOUNTED SUCH THAT THE ENTIRE LENS IS 80-IN ABOVE THE FINISHED FLOOR AND NOT GREATER THAN 96-IN ABOVE THE FINISHED FLOOR. WHERE LOW CEILINGS HEIGHTS DO NOT PERMIT DEVICES AT A MINIMUM OF 80-IN, DEVICES MUST BE MOUNTED WITHIN 6-IN OF THE CEILING.
AUDIBLE DEVICES AND VISIBLE/AUDIBLE DEVICES MUST UTILIZE A CLEAR STROBE AND BE MARKED "ALERT" FOR FIRE ALARM USE.
HORNS MUST BE SET AT THE HIGH DECIBEL SETTING. SOUND PRESSURE LEVEL FROM AUDIBLE ALARM APPLIANCES MUST NOT EXCEED 110 DBA
IN ANY OCCUPIED AREA.
SECONDARY POWER SUPPLY MUST BE VIA BATTERIES CAPABLE OF SATISFYING THE FOLLOWING CONDITION: THE FIRE ALARM SYSTEM ON STANDBY FOR 48 HOURS FOLLOWED BY 15 MINUTES IN ALARM. CHARGING AND METERING MUST BE PROVIDED IN ACCORDANCE WITH NFPA 72.
DEDICATED BATTERY CABINETS MUST BE MOUNTED NO MORE THAN 3-FT FROM THE FINISHED FLOOR.
PROVIDE SYSTEM RECORD DOCUMENT CABINET ADJACENT TO FIRE ALARM CONTROL PANEL.
PROVIDE LABELS FOR ADDRESSABLE DEVICES AND NOTIFICATION APPLIANCES.
DRAWINGS ARE CONCEPTUAL IN NATURE. THEY DO NOT SHOW THE EXACT LOCATIONS OF COMPONENTS NOR SHOW ALL SYSTEM COMPONENTS.
CONTRACTOR MUST PROVIDE ADDITIONAL COMPONENTS FOR A PROPERLY INSTALLED AND FUNCTIONAL SYSTEM IN ACCORDANCE WITH
APPLICABLE CODES.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
P
N N
FACP KF
P
P P
DCCM
CM
STORAGE 1
STORAGE 2
x2x2
135 cd
135 cd 135 cd
110 cd
1 2 3 6
F
E
D
C
B
4 5
Lic. No. 044409
AARON P FREIDC
O M M O
N W
EAL
THOF
V
IR
G
IN
IA
P R O F
E
SSIONAL EN
G
IN
E E R
12/17/2021
A B
KEYPLAN
A B
KEYPLAN
ENGINEERS + SURVEYORS
KEY NOTES 00
0 5'
1/8" = 1'-0" GRAPHIC SCALE
10' 20' 30'
N PLAN
NORTH
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
TI
O
N A
L S
U P
P O
R T
FA
C
IL
IT
Y (O
S F)
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V A
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 07 AUG 2018
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
EJA
DSN
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
P
5_ O
S F
-F P
.r vt
/1
6/
1:
:0
A M
1/8" = 1'-0"
F
IR
E A
LA
R
M F
LO
O
R P
LA
N
F
IR
S
T F
L O
O R
FA101
APF AHE AJW
12854117
96 129
1/8" = 1'-0" A1
FIRE ALARM FLOOR PLAN - FIRST FLOOR
1 PROVIDE CONDITIONED PANEL ENCLOSURE FOR THE FIRE ALARM
CONTROL PANEL AND KINGFISHER RADIO TRANSMITTER. PANEL
ENCLOSURE MUST BE NEMA TYPE 12. ENCLOSURE COOLER MUST
PROVIDE A MINIMUM COOLING CAPACITY OF 8,000 BTU/HR.
ENCLOSURE COOLER POWER MUST BE 480-V/1-PH. PANEL SMOKE
DETECTOR MUST BE MOUNTED WITHIN THE ENCLOSURE. PROVIDE
CONDENSATE DRAIN FROM CONDENSER COOLER TO EXTERIOR AND
DISCHARGE ON A SPLASH BLOCK.
PROVIDE CONTROL MODULE TO INTERFACE WITH LIGHTING RELAY.
LIGHTING RELAY MUST ENERGIZE EGRESS LIGHTING UPON
ACTIVATION OF FIRE ALARM. COORDINATE EXACT LOCATION WITH
ELECTRICAL CONTRACTOR.
FIRE ALARM SYSTEM SEQUENCE OF OPERATIONSC2
SCALE: NOT TO SCALEFA501
MANUAL PULL STATION
O P E R A
TIO
N
A C
TIV
A
TE W
A
TER
F
LO
W A
LA
R M
B
ELL
A
LA
R M
C O
N D
IT
IO
N A
T F A C P
TR
O
U
BLE
C O
N D
IT
IO
N A
T F A C P
TR
A N S M
IT
A
LA
R M
S
IG
N A L
TO
F
IR
E D
EP
A R
TM
EN
T
OTHER TROUBLE CONDITION
FIRE ALARM INPUT
AREA SMOKE DETECTOR ACTIVATION
TR
A N S M
IT
T
R O
U B
LE
S
IG
N A L
TO
F
IR
E D
EP
A R
TM
EN
T
FACP CIRCUIT FAULT (OPEN, GROUND, SHORT)
A C
TIV
A
TE N
O
TIF
IC
A
TIO
N A
PPLI
A N C
ES
TR
A N S M
IT
S
U P
ER
V
IS
O R Y S
IG
N A L
TO
F
IR
E D
E
PA
R
TM
EN
T
SU
PE
R
VIS
O R Y C
O N D
IT
IO
N A
T F A C P
AUTOMATIC SPRINKLER SYSTEM WATERFLOW SWITCH
AUTOMATIC SPRINKLER SYSTEM TAMPER SWITCH
A C
TIV
A
TE
E G R
ES
S L
IG
H
TIN
G
3-FT MIN
4-IN MIN
5-FT MAX
4-
IN
M
IN
-I
N M
A X
-I
N M
A X
FIRE ALARM
PULL DOWN
FIREFIRE
TYPICAL DEIVCE MOUNTING HEIGHTSA2
SYNCHRONIZE MORE
THAN TWO APPLIANCES
IN ANY FIELD OF VIEW.
NOTE: MEASUREMENTS
SHOWN ARE TO THE
CLOSEST POINT ON THE
DETECTOR.
A/C SUPPLY
DIFFUSER
CEILING
SIDE WALL
44-INCH
80-INCH MIN
96-INCH MAX
FINISHED
FLOOR
MANUAL
PULL
STATION
AUDIO/VISUAL
& VISUAL-ONLY
DEVICES
CEILING MOUNTED
SMOKE DETECTOR
FINISHED
WALL
HEAT DETECTOR
ACCEPTED HERE
HEAT DETECTOR
PROHIBITED HERE
HEAT DETECTOR
ACCEPTED HERE
SIDE WALL
FINISHED
WALL
SMOKE DETECTOR
ACCEPTED HERE
SCALE: NOT TO SCALEFA501
FACP
P
SS
ANNKF
MMMM
FIRE ALARM SYSTEM RISER DIAGRAMC4
SCALE: NOT TO SCALEFA501
EOLR
120-VAC
EOLR
135 110
EOLR CM
EGRESS
LIGHTING
ACTIVATION
Lic. No. 044409
AARON P FREIDC
O M M O
N W
EAL
THOF
V
IR
G
IN
IA
P R O F
E
SSIONAL EN
G
IN
E E R
12/17/2021
ENGINEERS + SURVEYORS
1 2 3 4 5
3 4 5
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
P -4
F
O
P E
R A
TI
O
N A
L S
U P
P O
R T
FA
C
IL
IT
Y (O
S F)
D C
C O
R E
B E
A U
F O
R T
, S C
N O
R F
O
LK
, V A
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
M C
A S
B E
A U
F O
R T
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1362850
DRAWFORM REVISION: 07 AUG 2018
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
D
C
B
A
1 2
CJW / SVR
Approved by J. Scott Roberts, Asset Management Branch Head
& Supervisory Facility Planner, PWD Beaufort, SC via email
EJA
DSN
DSN
12/17/2021
B
IM
- P -4
F
-3
O pe ra tio na l S up po rt F ac ili ty /B
LD
G
P
5_ O
S F
-F P
.r vt
/1
6/
1:
:0
A M
As indicated
F
IR
E A
LA
R
M D
E T
A
IL
S
FA501
APF AHE AJW
12854118
97 129
| FIRE ALARM |
| FA001 - FIRE ALARM GENERAL NOTES AND LEGEND |
| FA101 - FIRE ALARM FLOOR PLAN - FIRST FLOOR |
| FA501 - FIRE ALARM DETAILS |
2022-01-27T07:46:38-0500
2022-01-27T07:49:00-0500
2022-01-27T07:49:00-0500
| 2022-02-16T19:31:52-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-02-16T19:32:21-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-02-16T19:32:21-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-02-16T19:32:31-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-02-16T19:32:47-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-02-16T19:32:47-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
File details come from the government source that posted it. Updated .