Attachment F - USCG Base Miami Beach Asbestos Report.pdf

PDF 1 MB Posted

Attached to
Design/Build Rebuild Paint and Sandblast Facility at U. S. Coast Guard Base Miami Beach, Miami, FL.
Solicitation number
70Z04720RBASMIA00
Issued by

About this file

This pre-renovation asbestos survey report identifies asbestos-containing materials found in select areas of two buildings at the U.S. Coast Guard Base Miami Beach prior to renovation. Laboratory analysis detected chrysotile asbestos in the silver roof coating, various metal seam caulks, and an exhaust door frame caulk at levels ranging from 2-10% in the Sandblast and Paint Shop building. The report recommends these non-friable materials be abated by a licensed asbestos contractor if disturbed during renovations.

The related federal contract opportunity is to rebuild the damaged Paint and Sandblast facility for approximately $7.37 million, including demolition of the existing building, site work, and construction of a new 7,370 square foot facility. An option to provide four multi-axis mast lifts, two for each paint and sandblast booth, is also included. The opportunity was posted to the Department of Homeland Security Coast Guard.

View the file

Other files

File Type Posted
Amendment No. 0004.pdf PDF
10877504 Miami P_SB CAD Files.zip ZIP file
Appendix F - Individual Space Criteria Sheets.pdf PDF
AMENDMENT 0003.pdf PDF
Amendment 0002.pdf PDF
70Z04720RBASMIA00 AMENDMENT 0001.pdf PDF
1 10877504_Miami PSB Facility RFP Drawings.pdf PDF
Attachment A - Geotechnical Reference Documents.pdf PDF
Attachment J - Florida State Clearinghouse Correspondence.pdf PDF
General Wage Determination_FL20200215_Building.pdf PDF
Attachment I - Environmental Planning and Historic Preservation Decision Support System Project Approval.pdf PDF
Site Visit MAP.ppt PPT presentation
10877504_G100.pdf PDF
10877504_C103.pdf PDF
Attachment L - Spill Prevention Control and Countermeasures Plan.pdf PDF
10877504_O110.pdf PDF
Appendix A - ComputerGenDrwgs.pdf PDF
Appendix H - Construction Forms.pdf PDF
Attachment K - Air Emission Operating Permit.pdf PDF
Visitors Access List 70Z04720RBASMIA00.pdf PDF
Attachment H - DHS NEPA Record of Environmental Consideration for CatEx Actions.pdf PDF
Appendix J - Outfitting Items.pdf PDF
SPECIFICATIONS.pdf PDF
Attachment D - Boat Cradle.pdf PDF
10877504_A101.pdf PDF
Appendix B - Electronic Deliverables.pdf PDF
Appendix D - Design Narrative.pdf PDF
10877504_C104.pdf PDF
Appendix C - FDCC Adept File Naming.pdf PDF
Appendix E - Industry Standards for Const Docs.pdf PDF
10877504_C102.pdf PDF
Solicitation 70Z04720RBASMIA00 Final.pdf PDF
Attachment B - Homeporting FRC Miami Beach As-Builts.pdf PDF
Attachment M - Marine Facilities Annual Operating Permit.pdf PDF
Attachment G - USCG Base Miami Beach Lead Based Paint Report.pdf PDF
Attachment E - ICAM Data.pdf PDF
Appendix G - Operation and Maintenance.pdf PDF
Attachment C - Vessel Data 45RBM-601-001.pdf PDF
10877504_C101.pdf PDF
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PRE-RENOVATION

REPORT OF BUILDING MATERIAL SURVEY, SAMPLING AND

EVALUATION OF ASBESTOS-CONTAINING MATERIALS

FOR

ARMORY (BUILDING 6) AND SANDBLAST & PAINT SHOP (BUILDING 9)

U.S. COAST GUARD BASE MIAMI BEACH

100 MAC ARTHUR CAUSEWAY

MIAMI BEACH, FLORIDA 33139

AIRQUEST PROJECT NUMBER: 16-01-10592

PREPARED FOR:

MR. ALBERTO PUIG, PM

U.S. COAST GUARD

CIVIL ENGINEERING UNIT

15608 SOUTHWEST 117TH AVENUE

MIAMI, FLORIDA 33177

PREPARED BY:

AIRQUEST ENVIRONMENTAL, INC.

6851 SOUTHWEST 45TH STREET

FORT LAUDERDALE, FLORIDA 33314

MAY 10, 2016

ii

CERTIFICATION PAGE

PRE-RENOVATION

REPORT OF BUILDING MATERIAL SURVEY, SAMPLING AND

EVALUATION OF ASBESTOS-CONTAINING MATERIALS

FOR

ARMORY (BUILDING 6) AND SANDBLAST & PAINT SHOP (BUILDING 9)

U.S. COAST GUARD BASE MIAMI BEACH

100 MAC ARTHUR CAUSEWAY

MIAMI BEACH, FLORIDA 33139

AIRQUEST PROJECT NUMBER: 16-01-10592

PREPARED FOR:

MR. ALBERTO PUIG, PM

U.S. COAST GUARD

CIVIL ENGINEERING UNIT

15608 SOUTHWEST 117TH AVENUE

MIAMI, FLORIDA 33177

PREPARED BY:

AIRQUEST ENVIRONMENTAL, INC.

6851 SOUTHWEST 45TH STREET

FORT LAUDERDALE, FLORIDA 33314

MAY 10, 2016

Carol Gagnon Traci-Anne Boyle, CIH, CSP Project Manager Florida Asbestos Consultant #AX-60 iii

EXECUTIVE SUMMARY

AirQuest Environmental, Inc. (“AirQuest”) performed a survey for asbestos-containing materials (ACM) on the Armory (Building 6) and Sandblast & Paint Shop (Building 9) at the U.S. Coast Guard Base Miami Beach, located at 100 Mac Arthur Causeway in Miami Beach, Florida 33139 (“the site”). The survey was performed on April 4, 2016 by AirQuest Project Manager, Ms.

Carol Gagnon, an EPA-trained Asbestos Hazard Emergency Response Act (AHERA) certified asbestos inspector.

The purpose of the survey was to locate and identify ACM within select areas of the exterior and roof of the Sandblast & Paint Shop (Building 9) and the roof of the Armory (Building 6) prior to renovation activities.

The results of our observation and laboratory analysis identified the following ACM:

Homogeneous Area Number 1 – Sandblast & Paint Shop (Building 9) Sample No.: 10592-20 & 10592-21 Material: Roof Silver Coating Location: Roof – Small Building Section Results: 2-5% Chrysotile Asbestos Quantity: Approximately 540 Square Feet on Small Building

Section Roof Approximately 4,500 Square Feet Presumed on Large Building Section Roof

The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida licensed asbestos abatement contractor, with prior notification to the appropriate County and the State of Florida agencies.

Homogeneous Area Number 2 – Sandblast & Paint Shop (Building 9) Sample No.: 10592-22 & 10592-23 Material: Roof Metal Seam Caulk Location: @ Roof Seam – Small Building Section Results: 6-8% Chrysotile Asbestos Quantity: Approximately 115 Linear Feet (Five [5] Square Feet) on Small Building Section Roof Approximately 1,125 Linear Feet (Forty-Five [45] Square Feet) Presumed on Large Building Section Roof

The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida iv

Homogeneous Area Number 3 – Sandblast & Paint Shop (Building 9) Sample No.: 10592-24 & 10592-25 Material: Wall Metal Seam Caulk Location: @ Wall Seams– Small Building Section Results: 5-7% Chrysotile Asbestos Quantity: Approximately 490 Linear Feet (Forty-One [41] Square

Feet) The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

Homogeneous Area Number 5 – Sandblast & Paint Shop (Building 9) Sample No.: 10592-28 & 10592-29 Material: Exhaust System Door Frame Caulk Location: @ Exhaust System Door Frame– Small Building

Section Results: 5-7% Chrysotile Asbestos Quantity: Approximately One (1) Square Foot The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

Homogeneous Area Number 7 – Sandblast & Paint Shop (Building 9) Sample No.: 10592-33 & 10592-34 Material: North Wall Base Seam Caulk Location: @ North Wall Base Seams– Small and Large Building

Sections Results: 8-10% Chrysotile Asbestos Quantity: Approximately Three (3) Square Feet v

The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

Homogeneous Area Number 8 – Sandblast & Paint Shop (Building 9) Sample No.: 10592-35 & 10592-36 Material: Wall Metal Seam Caulk Location: @ Wall Metal Seams- Large Building Section Results: 3-6% Chrysotile Asbestos Quantity: Approximately 3,480 Linear Feet (290 Square Feet) The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

Due to the deteriorated condition of the upper roof of the Sandblast & Paint Shop (Building 9), roof samples were collected from the lower roof. The upper roof was observed from an adjacent building and it was determined that the two (2) roofs had like materials and were, therefore, homogenous.

At the request of the Client, the survey was limited to building materials that will be impacted by upcoming renovations to the exterior and roof of the Sandblast & Paint Shop (Building 9) and the roof of the Armory (Building 6). The remaining exterior areas and interiors of the buildings were not included in the scope of the survey. If any materials are encountered during renovation activities that were not sampled in this report, the materials should not be disturbed until they have been sampled and identified as non-ACM through laboratory analysis.

vi

TABLE OF CONTENTS

PAGE

CERTIFICATION PAGE II

EXECUTIVE SUMMARY III

1 INTRODUCTION 1

2 FACILITY DESCRIPTION 2

3 SURVEY METHODS AND LABORATORY ANALYSIS 3

4 SUSPECT ASBESTOS-CONTAINING MATERIALS (ACM) 4

5 ASBESTOS CONTAINING MATERIAL (ACM) 7

6 CONCLUSIONS 9

7 LIMITATIONS 12

TABLES

Table 1 – Laboratory Analysis and Summary

APPENDICES

Appendix I – Certification Appendix II - Laboratory Report & Chain of Custody Record Appendix III – Photographs

1 INTRODUCTION

AirQuest Environmental, Inc. (“AirQuest”) performed a survey for asbestos-containing materials (ACM) on the Armory (Building 6) and Sandblast & Paint Shop (Building 9) at the U.S. Coast Guard Base Miami Beach, located at 100 Mac Arthur Causeway in Miami Beach, Florida 33139 (“the site”). The survey was performed on April 4, 2016 by AirQuest Project Manager, Ms.

Carol Gagnon, an EPA-trained Asbestos Hazard Emergency Response Act (AHERA) certified asbestos inspector (see Appendix I).

The purpose of the survey was to locate and identify ACM within select areas of the exterior and roof of the Sandblast & Paint Shop (Building 9) and the roof of the Armory (Building 6) prior to renovation activities.

The scope of services for this project consisted of the following five steps:

Building Walk-Through and Observations, Bulk Sampling of Suspect Asbestos-Containing Building Materials (ACBM), Polarized Light Microscopy (PLM) Analysis of Bulk Samples, Hazard Assessment and Evaluation, and Final Report Preparation.

2 FACILITY DESCRIPTION

The subject areas included the Armory (Building 6) and Paint & Sandblast Shop (Building 9) at the United State Coast Guard Base Miami Beach, located at 100 Mac Arthur Causeway in Miami Beach, Florida 33129. The scope of the inspection was limited to select areas of the exterior and roof of the Sandblast & Paint Shop building and the roof of the Armory building.

Armory (Building 6): The roof deck was constructed of concrete with concrete parapet walls and metal flashing. Sections were finished with insulated roofing membrane. Scuppers and vent units were present. Various types of mastic and caulk were observed.

Sandblast & Paint Shop (Building 9): The building consisted of two (2) attached sections and was constructed of metal sheeting skin on a metal frame with metal roof decks and a concrete slab foundation. A blue flange, metal deck platform and metal ladder were attached to the exterior of the larger section of the building.

The roof decks consisted of an upper/large section and a lower/smaller section. The upper/larger section of had a silver coating finish. Metal vent units, pipe penetrations and a wall seam repair were present. Various types of caulk were observed. The lower/smaller section had a silver coating finish. An HVAC unit and exhaust vent were present. Various types of caulk were observed.

Due to the deteriorated condition of the upper roof of the Sandblast & Paint Shop (Building 9), roof samples were collected from the lower roof. The upper roof was observed from an adjacent building and it was determined that the two (2) roofs had like materials and were, therefore, homogenous.

3 SURVEY METHODS AND LABORATORY ANALYSIS

The sampling protocol used in this asbestos survey are those detailed in Title 40, Code of Federal Regulations (CFR), Part 763.86 for the sampling of friable surfacing materials, thermal systems insulation and miscellaneous materials (i.e. ceiling tiles). The Environmental Protection Agency (EPA) regulations require that sample locations be randomly selected. Suspect ACBM were identified and samples of each different type of material were obtained.

The bulk sampling procedure utilized for the collection of samples suspected of being ACBM required the establishment of homogeneous sampling areas. A homogeneous sampling area is defined as an area of friable or non-friable material of similar type that appeared to be applied or constructed during the same general period of time. This is the most acceptable and cost-effective method for the sampling of suspect ACBM.

Samples of suspect materials were collected from predetermined homogeneous sampling areas and the location of each sample was recorded. Samples were labeled and transported to the laboratory for analysis, using polarized light microscopy (PLM) coupled with dispersion staining. The samples were analyzed in accordance with Title 61 Code of Federal Regulation.

Polarized light microscopy is a method of analysis that utilizes the unique optical crystallographic properties of the various crystalline forms in the samples. These properties, such as refractive indices, birefringence, sign of elongation and extinction angle, are unique to crystalline asbestos forms and therefore can be used to identify the type of asbestos mineral as chrysotile, amosite, crocidolite, anthophyllite, tremolite, or actinolite. Each type of asbestos displays unique characteristics when subjected to these tests. Percentages of the identified types of asbestos are determined by visual estimation. Any material containing over one percent (1%) by weight is considered by the U.S. Environmental Protection Agency (EPA) to be an asbestos containing material and if disturbed must be handled according to specific local, state and federal regulations.

4 SUSPECT ASBESTOS-CONTAINING MATERIALS (ACM)

Eleven (11) homogeneous areas (HA) of suspect material were identified and a total of forty-wo

(42) samples were collected. The laboratory split the samples into layers, resulting in the analysis of forty-four (44) samples. Sample descriptions and laboratory results are summarized in Table 1. A copy of the laboratory report and chain of custody record is included in Appendix II. Sample locations and homogeneous areas identified to be asbestos containing are described in Section 5.0.

Table 1 – Laboratory Analysis and Summary Samples Collected on April 4, 2016

Sample Number

HA Location Description of Suspect Material Asbestos Content %

Armory (Building 6) Roof 10592-01 1 & 2 Roof Area Roof Core Black Mastic/Concrete

Decking

ND

10592-02 2 Roof Area Roof Core Black Mastic ND 10592-03 1 Roof Area Roof Core Concrete Decking ND 10592-04 3 Parapet Wall Concrete Parapet Wall ND 10592-05 3 Parapet Wall Concrete Parapet Wall ND 10592-06 4 Roof Flashing Roof Edge Flashing Yellow

Mastic

ND

10592-07 7 Roof Flashing Roof Edge Flashing Yellow Mastic

ND

10592-08 5 Roof Flashing Roof Edge Flashing Grey Caulk ND 10592-09 5 Roof Flashing Roof Edge Flashing Grey Caulk ND 10592-10 6 Southeast Scupper Edge White Caulk @ Scupper Edge ND 10592-11 6 East Scupper Edge White Caulk @ Scupper Edge ND 10592-12 7 Roof Flashing to Vent Flashing to Vent Grey Mastic ND 10592-13 7 Roof Flashing to Vent Flashing to Vent Grey Mastic ND 10592-14 8 Rooftop HVAC Unit Grey HVAC Duct Mastic ND 10592-15 8 Rooftop HVAC Unit Grey HVAC Duct Mastic ND

10592-16 9 Rooftop HVAC Unit White HVAC Duct Mastic ND

10592-17 9 Rooftop HVAC Unit White HVAC Duct Mastic ND

10592-18 10 Rooftop HVAC Unit Black HVAC Duct Mastic ND

10592-19 10 Rooftop HVAC Unit Black HVAC Duct Mastic ND

Sandblast & Paint Shop (Building 9) Small Building Section 10592-20 1 Roof Roof Silver Coating 2% Chrysotile 10592-21 1 Roof Roof Silver Coating 5% Chrysotile 10592-22 2 Roof Roof Metal Seam Caulk 6% Chrysotile 10592-23 2 Roof Roof Metal Seam Caulk 8% Chrysotile 10592-24 3 @ Metal Wall Seam Wall Metal Seam Caulk 5% Chrysotile 10592-25 3 @ Metal Wall Seam Wall Metal Seam Caulk 7% Chrysotile

10592-26 4 Paint Locker Door Frame

Paint Locker Room Door Frame Caulk ND

10592-27 4 Paint Locker Door Frame

Paint Locker Room Door Frame Caulk ND

10592-28 5 Exhaust System Door Frame

Exhaust System Door Frame Caulk 5% Chrysotile

Sample Number

HA Location Description of Suspect Material Asbestos Content %

10592-29 5 Exhaust System Door Frame

Exhaust System Door Frame Caulk 7% Chrysotile

10592-30 6 Interior Interior Spray-Applied Fireproofing ND

10592-31 6 Interior Interior Spray-Applied Fireproofing ND

10592-32 6 Interior Interior Spray-Applied Fireproofing ND

10592-33 7 North Wall Base Seam Wall Base Seam Caulk 8% Chrysotile Sandblast & Paint Shop (Building 9) Large Building Section

10592-34 7 East Wall Base Seam Wall Base Seam Caulk 10% Chrysotile 10592-35 8 @ Wall Metal Seams Wall Metal Seam Caulk 6% Chrysotile 10592-36 8 @ Wall Metal Seams Wall Metal Seam Caulk 3% Chrysotile 10592-37 9 @ Wall Seam Repair White Wall Seam Repair Caulk ND 10592-38 9 @ Wall Seam Repair White Wall Seam Repair Caulk ND 10592-39 10 Shop Door Frame Shop Door Frame Caulk ND 10592-40 10 Shop Door Frame Shop Door Frame Caulk ND 10592-41 11 Pipe Penetration Grey Pipe Penetration Caulk ND 10592-42 11 Pipe Penetration Grey Pipe Penetration Caulk ND

HA = Homogenous Area ND = None Detected

5 ASBESTOS CONTAINING MATERIAL (ACM)

This section describes the ACM observed during the inspection. The quantities of material described herein are approximate and are not to be relied upon by asbestos abatement contractors for bidding purposes.

The results of our observation and laboratory analysis identified the following ACM:

Homogeneous Area Number 1 – Sandblast & Paint Shop (Building 9) Sample No.: 10592-20 & 10592-21 Material: Roof Silver Coating Location: Roof – Small Building Section Results: 2-5% Chrysotile Asbestos Quantity: Approximately 540 Square Feet on Small Building

Section Roof Approximately 4,500 Square Feet Presumed on Large Building Section Roof

Material: Roof Metal Seam Caulk Location: @ Roof Seam – Small Building Section Results: 6-8% Chrysotile Asbestos Quantity: Approximately 115 Linear Feet (Five [5] Square Feet) on Small Building Section Roof Approximately 1,125 Linear Feet (Forty-Five [45] Square Feet) Presumed on Large Building Section Roof

Sample No.: 10592-24 & 10592-25 Material: Wall Metal Seam Caulk Location: @ Wall Seams– Small Building Section Results: 5-7% Chrysotile Asbestos Quantity: Approximately 490 Linear Feet (Forty-One [41] Square

Feet)

Material: Exhaust System Door Frame Caulk Location: @ Exhaust System Door Frame– Small Building

Section Results: 5-7% Chrysotile Asbestos Quantity: Approximately One (1) Square Foot

Material: North Wall Base Seam Caulk Location: @ North Wall Base Seams– Small and Large Building

Sections Results: 8-10% Chrysotile Asbestos Quantity: Approximately Three (3) Square Feet

Sample No.: 10592-35 & 10592-36 Material: Wall Metal Seam Caulk Location: @ Wall Metal Seams- Large Building Section Results: 3-6% Chrysotile Asbestos Quantity: Approximately 3,480 Linear Feet (290 Square Feet)

Photographs of the ACM is included in Appendix III.

6 CONCLUSIONS

The results of our observation and laboratory analysis identified the following ACM:

Homogeneous Area Number 1 – Sandblast & Paint Shop (Building 9) Sample No.: 10592-20 & 10592-21 Material: Roof Silver Coating Location: Roof – Small Building Section Results: 2-5% Chrysotile Asbestos Quantity: Approximately 540 Square Feet on Small Building

Section Roof Approximately 4,500 Square Feet Presumed on Large Building Section Roof

The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

Material: Roof Metal Seam Caulk Location: @ Roof Seam – Small Building Section Results: 6-8% Chrysotile Asbestos Quantity: Approximately 115 Linear Feet (Five [5] Square Feet) on Small Building Section Roof Approximately 1,125 Linear Feet (Forty-Five [45] Square Feet) Presumed on Large Building Section Roof

The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

Sample No.: 10592-24 & 10592-25 Material: Wall Metal Seam Caulk Location: @ Wall Seams– Small Building Section Results: 5-7% Chrysotile Asbestos Quantity: Approximately 490 Linear Feet (Forty-One [41] Square

Feet) The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

Material: Exhaust System Door Frame Caulk Location: @ Exhaust System Door Frame– Small Building

Section Results: 5-7% Chrysotile Asbestos Quantity: Approximately One (1) Square Foot The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

Material: North Wall Base Seam Caulk Location: @ North Wall Base Seams– Small and Large Building

Sections Results: 8-10% Chrysotile Asbestos Quantity: Approximately Three (3) Square Feet The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

Sample No.: 10592-35 & 10592-36 Material: Wall Metal Seam Caulk Location: @ Wall Metal Seams- Large Building Section Results: 3-6% Chrysotile Asbestos Quantity: Approximately 3,480 Linear Feet (290 Square Feet) The non-friable material was in good condition. There is no regulatory guideline that requires removal of this material unless it will be disturbed during renovation or remodeling activities.

If the material is to be impacted or removed, the removal must be conducted by a Florida

7 LIMITATIONS

Due to the deteriorated condition of the upper roof of the Sandblast & Paint Shop (Building 9), roof samples were collected from the lower roof. The upper roof was observed from an adjacent building and it was determined that the two (2) roofs had like materials and were, therefore, homogenous.

At the request of the Client, the survey was limited to building materials that will be impacted by upcoming renovations to the exterior and roof of the Sandblast & Paint Shop (Building 9) and the roof of the Armory (Building 6). The remaining exterior areas and interiors of the buildings were not included in the scope of the survey. If any materials are encountered during renovation activities that were not sampled in this report, the materials should not be disturbed until they have been sampled and identified as non-ACM through laboratory analysis.

Appendix I Certifications

Appendix II Laboratory Report and

Chain of Custody Record

EMSL Analytical, Inc.

2700 West Cypress Creek Rd, Suite B-111 Fort Laude

Tel/Fax: (954) 786-9331 / (954) 941-4145 http://www.EMSL.com / pompanobeachlab@emsl.com

561601647EMSL Order:

Customer ID: AQE63

Customer PO:

Project ID:

Attention: Phone:Paul LeBlanc (954) 214-2640

Fax:AirQuest Environmental, Inc. (954) 792-2221

Received Date:6851 Southwest 45th Street 04/06/2016 10:15 AM

Analysis Date:Fort Lauderdale, FL 33314 04/06/2016

Collected Date: 04/04/2016

Project: US Coast Guard - 10592

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light

Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

10592-01-Roofing

561601647-0001

None DetectedNon-fibrous (Other)90%Cellulose

Glass

5%

5%

Brown/Black

Fibrous

Homogeneous

Roof Core

10592-01-Concrete

561601647-0001A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof Core

10592-02-Roofing

561601647-0002

None DetectedNon-fibrous (Other)90%Cellulose

Glass

5%

5%

Brown/Black

Fibrous

Homogeneous

Roof Core

10592-02-Concrete

561601647-0002A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof Core

10592-03

561601647-0003

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

Roof Core

10592-04

561601647-0004

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

Concrete

10592-05

561601647-0005

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

Concrete

10592-06

561601647-0006

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Mastic

10592-07

561601647-0007

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Mastic

10592-08

561601647-0008

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

Caulking

10592-09

561601647-0009

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

Caulking

10592-10

561601647-0010

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

Caulk

10592-11

561601647-0011

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

Caulk

10592-12

561601647-0012

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Mastic

10592-13

561601647-0013

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Mastic

10592-14

561601647-0014

None DetectedNon-fibrous (Other)100%Gray/Black

Non-Fibrous

Homogeneous

Mastic

Initial Report From: 04/07/2016 09:16:38

Page 1 of 2PLM - 1.69 Printed: 4/7/2016 9:16 AM

Tel/Fax: (954) 786-9331 / (954) 941-4145 http://www.EMSL.com / pompanobeachlab@emsl.com

561601647EMSL Order:

Customer ID: AQE63

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light

Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

10592-15

561601647-0015

None DetectedNon-fibrous (Other)100%Gray/Black

Non-Fibrous

Homogeneous

Mastic

10592-16

561601647-0016

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Mastic

10592-17

561601647-0017

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Mastic

10592-18

561601647-0018

None DetectedNon-fibrous (Other)70%Cellulose30%Brown/Black

Non-Fibrous

Homogeneous

Mastic

10592-19

561601647-0019

None DetectedNon-fibrous (Other)70%Cellulose30%Brown/Black

Non-Fibrous

Homogeneous

Mastic

Analyst(s)

Anne Paul (11)

Hannah Mills (10)

Amrita Paul, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government . Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%

Samples analyzed by EMSL Analytical, Inc. Fort Lauderdale, FL

Initial Report From: 04/07/2016 09:16:38

Page 2 of 2PLM - 1.69 Printed: 4/7/2016 9:16 AM

O r d e r I D

P a g e f d e r I D

P a g e

Tel/Fax: (954) 786-9331 / (954) 941-4145 http://www.EMSL.com / pompanobeachlab@emsl.com

561601646EMSL Order:

Customer ID: AQE63

Customer PO:

Project ID:

Attention: Phone:Paul LeBlanc (954) 214-2640

Fax:AirQuest Environmental, Inc. (954) 792-2221

Received Date:6851 Southwest 45th Street 04/06/2016 10:15 AM

Analysis Date:Fort Lauderdale, FL 33314 04/06/2016

Collected Date: 04/04/2016

Project: US Coast Guard - 10592

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light

Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

10592-20

561601646-0001

2% ChrysotileNon-fibrous (Other)98%Gray/Silver

Non-Fibrous

Homogeneous

Roof Coating

10592-21

561601646-0002

5% ChrysotileNon-fibrous (Other)95%Black/Silver

Fibrous

Homogeneous

Roof Coating

10592-22

561601646-0003

6% ChrysotileNon-fibrous (Other)94%Gray

Non-Fibrous

Homogeneous

Caulk

10592-23

561601646-0004

8% ChrysotileNon-fibrous (Other)92%Gray/Silver

Non-Fibrous

Homogeneous

Caulk

10592-24

561601646-0005

5% ChrysotileNon-fibrous (Other)95%Gray/Black

Non-Fibrous

Homogeneous

Caulk

10592-25

561601646-0006

7% ChrysotileNon-fibrous (Other)93%Gray

Non-Fibrous

Homogeneous

Caulk

10592-26

561601646-0007

None DetectedNon-fibrous (Other)90%Wollastonite10%Tan/White

Non-Fibrous

Homogeneous

Caulk

10592-27

561601646-0008

None DetectedNon-fibrous (Other)90%Wollastonite10%Tan/White

Non-Fibrous

Homogeneous

Caulk

10592-28

561601646-0009

5% ChrysotileNon-fibrous (Other)95%Gray/Black

Non-Fibrous

Homogeneous

Caulk

10592-29

561601646-0010

7% ChrysotileNon-fibrous (Other)93%Gray/White

Non-Fibrous

Homogeneous

Caulk

10592-30

561601646-0011

None DetectedNon-fibrous (Other)20%Cellulose80%Brown

Fibrous

Homogeneous

Spray Applied

10592-31

561601646-0012

None DetectedNon-fibrous (Other)20%Cellulose80%Brown

Fibrous

Homogeneous

Spray Applied

10592-32

561601646-0013

None DetectedNon-fibrous (Other)20%Cellulose80%Brown/Tan/White

Fibrous

Homogeneous

Spray Applied

10592-33

561601646-0014

8% ChrysotileNon-fibrous (Other)92%Brown

Fibrous

Homogeneous

Caulk

10592-34

561601646-0015

10% ChrysotileNon-fibrous (Other)90%White/Black

Fibrous

Homogeneous

Caulk

10592-35

561601646-0016

6% ChrysotileNon-fibrous (Other)94%Gray

Non-Fibrous

Homogeneous

Caulk

Initial Report From: 04/07/2016 08:29:03

Page 1 of 2PLM - 1.69 Printed: 4/7/2016 8:29 AM

Tel/Fax: (954) 786-9331 / (954) 941-4145 http://www.EMSL.com / pompanobeachlab@emsl.com

561601646EMSL Order:

Customer ID: AQE63

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light

Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

10592-36

561601646-0017

3% ChrysotileNon-fibrous (Other)97%Gray

Non-Fibrous

Homogeneous

Caulk

10592-37

561601646-0018

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Caulk

10592-38

561601646-0019

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Caulk

10592-39

561601646-0020

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Caulk

10592-40

561601646-0021

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Caulk

10592-41

561601646-0022

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Pipe Penetration

10592-42

561601646-0023

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Pipe Penetration

Analyst(s)

Anne Paul (11)

Hannah Mills (12)

Amrita Paul, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government . Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%

Samples analyzed by EMSL Analytical, Inc. Fort Lauderdale, FL

Initial Report From: 04/07/2016 08:29:03

Page 2 of 2PLM - 1.69 Printed: 4/7/2016 8:29 AM d e r I D

P a g e d e r I D

P a g e

Appendix III Photographs

Sandblast & Paint Shop (Building 9) USCG Base Miami Beach 100 Mac Arthur Causeway Miami Beach, Florida 33139 Photographs of Asbestos-Containing Material

Exterior

HA 1- Silver Coating on Roof

(Building 9 small building section)

Asbestos Containing Material

HA 2- Metal Seam Caulk on Roof

HA 3- Caulk on Metal Wall Seam

HA 5- Exhaust System Door Frame Caulk

HA 7- Caulk at North Wall Base Seam

(Building 9 small and large building sections)

Sandblast & Paint Shop (Building 9) USCG Base Miami Beach 100 Mac Arthur Causeway Miami Beach, Florida 33139 Photographs of Asbestos-Containing Material

HA 8- Caulk at Metal Wall Seam

(Building 9 large building section)