Attachment 9 - 544-329 Equipment Cut Sheets Part 3.pdf

PDF 25 MB Posted

Attached to
Y1DZ--VHA MINOR CONSTRUCTION Solicitation CANCELLED Project 544-329 Construct Eye Clinic Center Minor Construction Columbia, SC VAMC
Solicitation number
36C77624R0028
Issued by

About this file

This document appears to be Attachment 9 - 544-329 Equipment Cut Sheets Part 3.pdf, related to the federal contract opportunity for Solicitation Number 36C77624R0028 to construct a new 15,000 GSF optometric facility at the William Jennings Bryan Dorn VA Medical Center in Columbia, SC. The intent of the project is to address the needs of VA patients and employees with a building tailored to the functional and operational requirements of the Optometry and Ophthalmology departments. The project will include new construction, HVAC, utility work, interior finishes, utility coordination, site work, underground storm water detention, asbestos and lead survey and abatement, and communication utility work inside an active hospital. This attachment appears to provide equipment cut sheets, which are technical specifications or details about the equipment to be used in the project.

View the file

Other files

File Type Posted
36C77624R0028 0007 - Signed.pdf PDF
36C77624R0028 0006 - Signed.pdf PDF
36C77624R0028 0005 - Signed.pdf PDF
Technical Questions Tracking Spreadsheet - 9-3-24- 36C77624R0028 - Construct Eye Clinic Columbia SC.docx DOCX document
RoomFinishes.pdf PDF
2024-08-29 544-329 BID DRAWING REVISIONS.pdf PDF
South Carolina Tax Language - 04.04.2024 - FINAL.docx DOCX document
01 00 00 General Requirements_rev 2_8.29.24.pdf PDF
36C77624R0028 0004 - Signed.pdf PDF
09 91 00 Painting_Rev 1 8.30.24.docx DOCX document
544 329 SOW 100_rev2.pdf PDF
00 01 10 Table of Contents_Rev 1 8.30.24.docx DOCX document
Attachment 6 - 544-329 Eye Clinic CD Specs 8.19.24.pdf PDF
SIGN IN SHEET Site Visit 8.15.24.pdf PDF
Amendment 0003 - 36C77624R0028 - Construct Eye Clinic - Columbia SC 8.19.24 - Signed.pdf PDF
Solicitation - 36C77624R0028 - Construct Eye Clinic - Columbia SC 8.19.24.pdf PDF
Attachment 7 - 544-329 Equipment Cut Sheets Part 1.pdf PDF
Attachment 24 - Richland County Wage Rates 6.14.24.pdf PDF
Attachment 28 - Division Cost Breakdown - 5-29-24.xlsx XLSX spreadsheet
Attachment 22 - Site Visit Dorn VAMC Google Map.jpg JPG image
Attachment 20 - 2023-09-29 544-329 BID DRAWINGS_Part7.pdf PDF
Attachment 18 - 2023-09-29 544-329 BID DRAWINGS_Part5.pdf PDF
Attachment 17 - 2023-09-29 544-329 BID DRAWINGS_Part4.pdf PDF
Attachment 3 - 544 329 VAMC Columbia SC Asbestos Inspection columbia part 1.pdf PDF
Attachment 26 - 544 329 SOW 100_rev1.pdf PDF
Attachment 5 - 544 329 VAMC Columbia SC Asbestos Inspection Report All Buildi.pdf PDF
Attachment 6 - 544-329 Eye Clinic CD Specs_120823.pdf PDF
Attachment 10 - 544-329 Equipment Cut Sheets Part 4.pdf PDF
Solicitation - 36C77624R0028 - Construct Eye Clinic - Columbia SC 8-8-24.pdf PDF
Attachment 12 - 544-329 Equipment Cut Sheets Part 6.pdf PDF
Attachment 23 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 11 - 544-329 Equipment Cut Sheets Part 5.pdf PDF
Attachment 27 - 544 329 Brand Name J and A.pdf PDF
Attachment 2 - 544 329 Eye Clinic Equipment List.xlsx XLSX spreadsheet
Attachment 8 - 544-329 Equipment Cut Sheets Part 2.pdf PDF
Attachment 1 - 544 329 Eye Clinic ConstructionAssessmentPackage 100 Percent.pdf PDF
Attachment 21 - Site Visit Dorn VAMC Campus Map_B101 and Contractor Parking.pdf PDF
Attachment 14 - 2023-09-29 544-329 BID DRAWINGS_Part1.pdf PDF
Attachment 25 - VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 6-2024.docx DOCX document
Attachment 16 - 2023-09-29 544-329 BID DRAWINGS_Part3.pdf PDF
Attachment 4 - 544 329 VAMC Columbia SC Asbestos Inspection columbia part 2.pdf PDF
Attachment 15 - 2023-09-29 544-329 BID DRAWINGS_Part2.pdf PDF
Attachment 13 - 544-329 Geotech Report.pdf PDF
Attachment 19 - 2023-09-29 544-329 BID DRAWINGS_Part6.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D is cl ai m er

: T hi s do cu m en ta tio n is n ot in te nd ed a s a su bs tit ut e fo r a nd is n ot to b e us ed fo r d et er m in in g su ita bi lit y or re lia bi lit y of th es e pr od uc ts fo r s pe ci fic u se r a pp lic at io ns

Aug 20, 2018

Product data sheet Characteristics

H364RB

SWITCH FUSIBLE HD 600V 200A 3P NEMA3R

Product availability : Stock - Normally stocked in distribution facility

Price* : 2259.00 USD

Main Product or component type Single Throw Safety Switch Line Rated Current 200 A Product certifications UL listed NEMA degree of protection NEMA 3R galvannealed steel Device composition None Disconnector device type Fusible disconnect Short-circuit current 10 kA H or K

200 kA R, J or L Device mounting Surface Number of poles 3 Electrical connection Lugs Series name Heavy duty System Voltage 600 V AC/DC AWG gauge AWG 6...250 kcmil (copper or aluminium)

Ordering and shipping details Category 00009 - H&HU SW,2&3P,N3R,30-200A Discount Schedule DE1

GTIN 00785901482710

Nbr. of units in pkg. 1 Package weight(Lbs) 44.859999999999999 Returnability Y Country of origin US

Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1313 - Schneider Electric declaration of conformity

Appendix N

Schneider Electric declaration of conformity

REACh Reference not containing SVHC above the threshold Reference not containing SVHC above the threshold

Product environmental profile Available Product end of life instructions Need no specific recycling operations

Contractual warranty Warranty period 18 months

Appendix N http://www.reach.schneider-electric.com/DistantRequestDispatcher.aspx?action=export&pid=364697&lang=en-us http://www.reach.schneider-electric.com/DistantRequestDispatcher.aspx?action=exportPdfReach&pid=364697&lang=en-us

D is cl ai m er

: T hi s do cu m en ta tio n is n ot in te nd ed a s a su bs tit ut e fo r a nd is n ot to b e us ed fo r d et er m in in g su ita bi lit y or re lia bi lit y of th es e pr od uc ts fo r s pe ci fic u se r a pp lic at io ns

Aug 20, 2018

Product data sheet Characteristics

EE75T3H

Transformer Dry Type 75kVA 480D208Y120

Product availability : Stock - Normally stocked in distribution facility

Price* : 9393.00 USD

Main Product or component type Energy Efficient Transformer Box number 20D NEMA degree of protection NEMA 2 Insulation temperature 428 °F (220 °C) Phase 3 phases Primary voltage 480 V delta Rated power in VA 75 kVA Secondary voltage 208Y/120 V Number of tap-offs 6 2.5 % 2+ 4- Temperature rise 150 °C Material Aluminium

Ordering and shipping details Category 16285 - 3 PH EE/TP1 15-75 KVA LVGP XFMR Discount Schedule PE2E

GTIN 00785901786849

Nbr. of units in pkg. 1 Package weight(Lbs) 562.00 Returnability Y Country of origin MX

Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1347 - Schneider Electric declaration of conformity

Schneider Electric declaration of conformity

REACh Reference not containing SVHC above the threshold http://www.reach.schneider-electric.com/DistantRequestDispatcher.aspx?action=export&pid=456791&lang=en-us

Reference not containing SVHC above the threshold

Product environmental profile Available Product end of life instructions Need no specific recycling operations

Contractual warranty Warranty period 18 months http://www.reach.schneider-electric.com/DistantRequestDispatcher.aspx?action=exportPdfReach&pid=456791&lang=en-us

I-Line®

Circuit Breaker Panelboards

Class 2110

CONTENTS

Description Page Product Description Features and Benefits Accessories General and Application Information Dimensions Replacement Parts

Catalog

Appendix N jezekiel Typewritten Text Panel CDP

I-Line® Circuit Breaker Panelboards Product Description

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

PRODUCT DESCRIPTION

Square D®-brand I-Line® circuit breaker power distribution panelboards are for use on AC or DC systems. The panels, labeled cULus (compliance to UL and CSA standards certified by UL) are also Underwriters Laboratories®

(UL®) Listed under File E33139. The following are suitable for use as service entrance equipment:

• All main circuit breaker panelboards.

• All main lugs panelboards with branch-mounted, back-fed main circuit breaker. (For Canadian MLO service entrance, use HCP-SU and HCR-U only).

• All main lugs panelboards with six disconnects or less.

• A solid neutral that is insulated, but may be bonded to the box with a grounding strap.

• Service entrance panelboards meeting the requirements of CSA are available in Canada factory-assembled only.

I-Line circuit breaker panelboards are available as 225–1200 A main lugs only and 100–1200 A main circuit breakers. I-Line panelboards are designed to accept the following circuit breakers: FY, FA, FH, FC, FJ, FK, FI, HD, HG, HJ, HL, QB, QD, QG, QJ, QO, KA, KH, KC, KI, JD, JG, JJ, JL, LA, LH, LC, LI, LE, LX, LXI, MA, MH, MG, MJ, PG, PJ, PK*, PL, RG, RJ, RK*, and RL.

* Canada only.

Standards

I-Line circuit breaker panelboards are designed, manufactured, and tested to comply with the following standards:

Service

I-Line circuit breaker panelboards can be used on the following system voltages:

• 120/240 VAC; 1-phase, 3-wire

• 240 VAC; 1-phase, 2-wire

• 240 VAC; 3-phase, 3-wire

• 240 VAC Ground, B-phase; 3-phase, 3-wire

• 208Y/120 VAC; 3-phase, 4-wire

• 480Y/277 VAC; 3-phase, 4-wire

• 480 VAC; 3-phase, 3-wire

• 600Y/347 VAC; 3-phase, 4-wire

• 600 VAC; 3-phase, 3-wire

• 125/250 VDC; 3-wire

• 250 VDC; 2-wire

Standard Description

UL 50 Standard for enclosures for electrical equipment

UL 67 Standard for panelboards

CSA C22.2, Nos. 29 and 94—1989 Standard for panelboards and enclosed panelboards

NFPA 70 National Electrical Code (NEC)

NEMA PB 1 Standard for panelboards

W–P 115C Type 1 Class 1 Specification for circuit breaker panelboards

2000 IBC US standard for seismic requirements

1995 NBCC Canadian standard for seismic requirements

Type HCR-U—1200 A Main Circuit Beaker

Type HCR-U—1200 A Main Circuit Beaker

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Panelboard Types

Panelboard Type

Maximum Mains Ampacity Maximum Branch Circuit

Breaker Frame Size ❖ Enclosure

Dimensions ■

Main Lugs Main Circuit

Breakers Left Right

Width IN (mm)

Depth IN (mm)

HCN 600 A 400 A FA, QB, HD FA, QB, HD 26 (660) 6.50 (165)

HCM 800 A 800 A JD JD 32 (813)

8.25 (210)/

9.50 (241)

HCP-SU 800 A 800 A ◆ MG, PG None 26 (600) 9.50 (241)

HCP 1200 A 800 A ◆ MG, PG JD 42 (1067) 9.50 (241)

HCR-U 1200 A 1200 A ◆ RG JD 44 (1118) 9.50 (241)

❖ For a complete listing of applicable circuit breaker types, refer to the dimensions section.

■ Refer to the Dimensions section for standard panelboard heights.

◆ Available as a main circuit breaker panelboard when provided with a branch mounted back-fed main circuit breaker.

Type HCP—600 A Main Circuit Breaker

Type HCP-SU 800 A Main Circuit Beaker Type HCM—400 A Main Lugs

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

Type 3R, 5, and 12 Enclosures

Enclosure Types

Types Environments Provides Protection Against

Type 1 Indoor Contact with the enclosed equipment

Type 2 Indoor Falling water and dirt

Type 3R Outdoor Falling rain, sleet; undamaged by ice

Type 4/4X Stainless Indoor/Outdoor Corrosion, hose-directed water, dust

Type 5 Indoor Settling dust, falling dirt, dripping liquids

Type 12 Indoor Circulating dust, falling dirt, dripping liquids

Fronts:

HCN, HCM, HCP, HCP-SU, and HCR-U surface and flush trims available as four-piece construction, standard (door not included). An optional four-piece trim with door is also available.

Type 1 Enclosures

Finished with gray-baked enamel electrodeposited over cleaned phosphatized steel

(ANSI 49).

Directory card holders provided with all fronts.

Boxes:

Galvanized steel in 26, 32, 42, and 44-inch (660, 813, 1067, and 1118 mm) widths.

Removable endwalls without knockouts.

Type 3R, 5, and 12 Enclosures

Gasketed door with vault handle and directory card holder.

Three-point latching.

End and side gutter trim.

No knockouts.

Removable drain screw for Type 3R.

Finished with gray-baked enamel electrodeposited over cleaned phosphatized steel

(ANSI 49).

Type 4X Enclosures (Factory- Assembled Only)

Corrosion-resistant, fiberglass-reinforced polyester.

Watertight and dusttight.

Gasketed door with trunk latches.

Directory card located on inside of door.

Types 1 and 2 Enclosure with Optional Door

Flush Lock used on HCN, HCM, and HCP-SU

Types 1 and 2 Fronts (Catalog No. PK4FL)

Sliding Vault Lock used on HCN, HCP, and HCR-U Types 1 and 2 Fronts (Catalog No. PK5FL)

Vault Handle used on all Type 3R, 5, and 12 Enclosures

(Catalog No. PK4NVL)Type 3R, 5, and 12 Enclosures

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Main Breaker Panelboards

• Accept a maximum 1200 A, 80% or 100% rated main breaker.

• Available factory-assembled or merchandised.*

• Factory-assembled main circuit breaker interiors are available bottom-feed or top-feed.

• Suitable for use as service entrance equipment, US and Canada.

• Accept plug-on I-Line circuit breakers.

• Available with a short circuit current rating (SCCR) up to 200 kA maximum (100 kA @ 600 VAC) when supplied by an I-Limiter® circuit breaker.

• Available with a silver-plated or tin-plated copper bus, or tin-plated aluminum bus.

• Solid neutral is mounted in the mains compartment with the main circuit breaker.

• Merchandised (RTA in Canada) main circuit breaker panelboards are provided bottom-feed as standard.

* Ready-to-Assemble (RTA) in Canada

Main Lugs Only Panelboards

• Available with main lug only interiors rated up to 1200 A.

• Available factory-assembled or merchandised (RTA in Canada).

• Suitable for use as service entrance equipment when provided with a main circuit breaker, US and Canada.

• Accept plug-on I-Line circuit breakers.

• Available with a short circuit current rating (SCCR) up to 200 kA maximum (100 kA @ 600 VAC) when supplied by an I-Limiter circuit breaker.

• Available with a silver-plated or tin-plated copper bus, or tin-plated aluminum bus.

• Solid neutral is mounted in the mains compartment with the main lugs.

• Hinged cover, isolated main lugs compartment.

• Main lug interiors are available as top-feed or bottom-feed.

Solid Neutral

• Mounts in main lug or main circuit breaker compartment.

• Does not take up interior circuit breaker mounting space.

• UL/CSA Listed for use with Al or Cu conductors.

• Copper or aluminum neutral available.

• 200% rated neutral available as a factory-assembled option.

Main Circuit Breaker and Solid Neutral Compartment (Canada service entrance not shown)

Main Lug and Solid Neutral Compartment

Typical Solid Neutral

Main neutral lug

Full capacity bonding strap for use on service entrance applications

Neutral with C/T for Use on HCR-U When Ground-Fault Protection is Required (Catalog No. HCR12SNCT)

Features and Benefits

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

FEATURES AND BENEFITS

Featured below are just a few of the many features and benefits of Square D-brand I-Line circuit breaker panelboards.

Circuit Breakers

I-Line panelboards are available with a complete line of thermal magnetic, Micrologic®, and electronic circuit breakers. The I-Line circuit breakers, with their exclusive plug-on connection design provide superior reliability and performance advantages.

Circuit Breaker Mounting

• 15–1200 A frame circuit breakers require only a screwdriver and are ratcheted firmly onto the bus stack. They are secured in place by a screw.

• The connectors are an integral part of the I-Line circuit breaker— eliminating the assembly of connectors to the bus bar.

• Pre-assembled hardware means reduced installation time.

• The unique line side connection requires no routine maintenance.

I-Line Bus Structure and Circuit Breaker Mounting

Push-to-Trip

Push-to-trip is a standard feature on all I-Line circuit breakers. It is useful for checking circuit breaker operation and for testing auxiliary devices. The circuit breaker is mechanically tripped by pressing the push-to-trip button in the circuit breaker case.

Blow-On Connections

All circuit breaker connections are “blow-on” type. Under high-level short circuit conditions, the magnetic forces developed tend to draw the connector jaws together, gripping the I-Line bus bar more firmly.

Ratchet-Type Mounting

Bus phase insulators interlock with the circuit breaker insulating shroud and provide high dielectric strength between the bus bars.

Circuit breakers on right-hand side of the bus structure are completely independent of position and frame size of those on left-hand side.

Insulating shroud keys into slots in bus support base.

Aligns and supports line end of circuit breaker.

Glass-reinforced polyester insulators provide continuous bus bar support.

Circuit breaker connectors are shrouded and braced in molded protective insulator. Circuit breaker jaws are lubricated and pre-set at the factory and require no adjustment.

Circuit breaker mounting bracket— an integral part of each circuit breaker;

securely supports and aligns load end of circuit breaker.

Steel channels provide additional support for insulator bracing structure.

Blow-On Connections

Features and Benefits

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Short Circuit Current Rating (SCCR)

• SCCR is equal to the lowest interrupting capacity of a branch or main circuit breaker installed in the panelboard.

• I-Line panelboards, with branch circuit breakers installed, are short-circuit tested as complete units.

• All tests are conducted in accordance with UL 67 and CSA C22.2 (Standards for Panelboards).

With I-Limiter main circuit breaker, I-Line main circuit breaker panelboards are UL/CSA Listed for use on systems with up to a 200,000 maximum RMS symmetrical amperes available fault current (100 kA @ 600 VAC).

I-Line Plug-on Unit with Surgelogic® TVSS

• Plug-on design requires less cable and conduit than end gutter-mounted TVSS unit, saving labor time and material costs.

• Bus-connected design enhances performance.

• Meets the requirements of UL and CSA for retrofit applications in existing I-Line panelboards and switchboards.

• Integrated TVSS and circuit breaker disconnects feature compact design, requiring only 13.50 inches (343 mm) of branch mounting space.

• SCCR up to 200 kA rating (100 kA @ 600 VAC) meets a wide variety of customer applications.

ACCESSORIES

A wide variety of accessories are available for field or factory installation of I-Line panelboards.

Equipment Ground Bars

Equipment ground bars mount in the panelboard box to provide convenient termination of equipment grounding conductors. They are available in copper or aluminum.

Box Extensions

Box extensions provide additional end gutter for feeding cables into the end of the cabinet; they are UL/CSA Listed.

Blank Fillers

Blank fillers are required to cover unused mounting space in I-Line panelboards.

Backfed Main Breaker Barriers

Primarily for use in Canada, these barriers provide additional protection for backfed main breakers.

I-Line Plug-On Unit with Surgelogic® TVSS

Equipment Ground Bar (Catalog No. PK32DGTA)

Typical Box Extensions

Blank Fillers (Catalog Nos. HNM4BL and HNM1BL)

General and Application Information

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

GENERAL AND APPLICATION INFORMATION

Circuit Breaker Ratings

Circuit Breaker Frame Type

Maximum Voltage Rating

Number of Poles

Cont.

Ampere Rating

UL/CSA Interrupting Rating—RMS Amperes (Symmetrical)

AC Volts, 50/60 Hz DC Volts

120 240 480 600 125 250

FY ‡ 277 1 15–30 18 K 14 K — — — —

FA 240 V

15–100 10 K

10 K 10 K

5 K

5 K

FA 480 V

15–100 25 K 18 K c 25 K 25 K

18 K 18 K

10 K

10 K 10 K

FA 600 V 600 2, 3 15–100 25 K 25 K 18 K 14 K 10 K 10 K

FH ◆

2, 3

15–30 35–100 15–100

65 K 65 K c 25 K c 65 K

25 K

18 K

10 K 10 K

10 K

FC 480 2, 3 15–100 100 K 100 K 65 K — — —

FG 277 1 15–70 35 K 35 K 35 K 18 K ✵ ❑ — —

FJ 277 1 15–70 65 K 65 K 65 K 25 K ✵ ❑ — —

FK ❑ 347 1 15–30 65 K 65 K 65 K 65 K — —

FI 600 2, 3 20–100 200 K 200 K 200 K 100 K — —

HD 600 2, 3 15–150 25 K 25 K 18 K 14 K 20 K 20 K

HG 600 2, 3 15–150 65 K 65 K 35 K 18 K 20 K 20 K

HJ 600 2, 3 15–150 100 K 100 K 65 K 25 K 20 K 20 K

HL 600 2, 3 15–150 125 K 125 K 100 K 50 K 20 K 20 K

QB 240 2, 3 70–225 10 K 10 K — — — —

QD 240 2, 3 70–225 25 K 25 K — — — —

QG 240 2, 3 70–225 65 K 65 K — — — —

QJ ❖ 240 2, 3 70–225 100 K 100 K — — — —

KA 600 2, 3 70–250 42 K 42 K 25 K 22 K 10 K 10 K

KH ◆ 600 2, 3 70–250 65 K 65 K 35 K 25 K 10 K 10 K

KC 480 2, 3 110–250 100 K 100 K 65 K — — —

KI 600 2, 3 110–250 200 K 200 K 200 K 100 K — —

JD 600 2, 3 150–250 25 K 25 K 18 K 14 K 20 K 20 K

JG 600 2, 3 150–250 65 K 65 K 35 K 18 K 20 K 20 K

JJ 600 2, 3 150–250 100 K 100 K 65 K 25 K 20 K 20 K

JL 600 2, 3 150–250 125 K 125 K 100 K 50 K 20 K 20 K

LA 600 2, 3 125–400 42 K 42 K 30 K 22 K 10 K 10 K

LH ◆ 600 2, 3 125–400 65 K 65 K 35 K 25 K 10 K 10 K

LC 480 2, 3 300–600 100 K 100 K 65 K 35 K — —

LI 480 2, 3 300–600 200 K 200 K 200 K 100 K — —

MA 600 2, 3 300–800 42 K 42 K 30 K 22 K 14 K 14 K

MH ◆ 600 2, 3 300–800 65 K 65 K 65 K 25 K 14 K 14 K

MG 600 2, 3 300–800 65 K 65 K 35 K 18 K — —

MJ 600 2, 3 300–800 100 K 100 K 65 K 25 K — —

PG 600 2, 3 600–1200 65 K 65 K 35 K 18 K — —

PJ 600 2, 3 600–1200 100 K 100 K 65 K 25 K — —

PK ❑ 600 2, 3 600–1200 65 K 65 K 50 K 50 K — —

PL 480 2, 3 600–1200 125 K 125 K 100 K — — —

MIicrologic Trip Circuit Breakers

LX 600 3 100–600 100 K 100 K 65 K 35 K — —

LXI 600 3 100–600 200 K 200 K 200 K 100 K — —

LE 600 3 100–600 100 K 100 K 65 K 35 K — —

PG 600 2, 3 250–1200 65 K 65 K 35 K 18 K — —

PJ 600 2, 3 250–1200 100 K 100 K 65 K 25 K — —

PK ❑ 600 2, 3 250–1200 65 K 65 K 50 K 50 K — —

PL 480 2, 3 250–1200 125 K 125 K 100 K — — —

RG 600 2, 3 1000–1200 65 K 65 K 35 K 18 K — —

RJ 600 2, 3 1000–1200 100 K 100 K 65 K 25 K — —

RK ❑ 600 2, 3 1000–1200 65 65 K 65 K 65 K — —

RL 600 2, 3 1000–1200 125 K 125 K 100 K 50 K — —

‡ 15 and 20 A are Switching Duty rated (SWD).

c 277 VAC rated.

◆ Separate UL rating available for 240 V and 480 V grounded B phase systems. Circuit breakers must be ordered with 5861 suffix.

✵ FG and FJ 600Y/347 VAC @ 15–30 A only.

❑ Canada only.

❖ QJ 3-pole is rated 100 KA@208Y/120 VAC.

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Circuit Breaker Terminal Data

Circuit Breaker Accessories

• Shunt trip

• Undervoltage trip

• Alarm switch

• Auxiliary contacts

• Ground-fault shunt trip

Circuit Breaker Frame Size Ampere Rating Terminal Lug Wire Size

FY 100 A 15–30 #14-#4 Al/Cu

FA 100 A 15–30 #14-#4 Cu or #12-#4 Al

FA 100 A 35–100 #14-1/0 Cu or #12-1/0 Al

FC 100 A 15–30 #14-#10 Cu

FC 100 A 35–100 #14-#3 Cu or #12-#1 Al

FG, FJ, FK ❑ 100 A 15–30 #14-#6 Cu or #12-#6 Al

FJ 100 A 35–70 #14-2/0 Cu or #12-2/0 Al

FH 100 A 15–30 #14-#4 Cu or #12-#4 Al

FH 100 A 35–100 #14-1/0 Cu or #12-1/0 Al

FI 100 A 20–30 #14-#4 Cu or #12-#4 Al

FI 100 A 35–100 #14-1/0 Cu or #12-1/0 Al

HD, HG, HJ, HL 150 A 15–150 #14-3/0 Al/Cu

QB 225 A 70–225 #4-300 kcmil Al/Cu

QD 225 A 70–225 #4-300 kcmil Al/Cu

QG 225 A 70–225 #4-300 kcmil Al/Cu

QJ 225 A 70–225 #4-300 kcmil Al/Cu

KA 250 A 125–250 (1) #6-350 kcmil Al/Cu

KC 250 A 110–175 (1) #6-350 kcmil Al/Cu

KC 250 A 200–250 (1) 1/0-350 kcmil Al/Cu

KH 250 A 125–250 (1) #6-350 kcmil Al/Cu

KI 250 A 110–175 (1) #6-350 kcmil Al/Cu

KI 250 A 200–250 (1) 1/0-350 kcmil Al/Cu

JD, JG, JJ, JL 250 A 150–175 #1/0-4/0 Al/Cu

JD, JG, JJ, JL 250 A 200–250 #3/0-350 kcmil Al/Cu

LA, LH 400 A 250–400 (1) #1-600 kcmil or

(2) #1-250 kcmil Al/Cu

LC 600 A 300–600 (2) 4/0-500 kcmil Al/Cu

LE 600 A 100–250 (2) #1-350 kcmil Al/Cu

LE 600 A 300–600 (2) 4/0-500 kcmil Al/Cu

LI 400 A 300–400 (2) 4/0-500 kcmil Al/Cu

LI 600 A 450–600 (2) 4/0-500 kcmil Al/Cu

LX 600 A 100–250 (2) #1-350 kcmil Al/Cu

LX 600 A 300–600 (2) 4/0-500 kcmil Al/Cu

LXI 600 A 100–250 (2) #1-350 kcmil Al/Cu

LXI 600 A 300–600 (2) 4/0-500 kcmil Al/Cu

MA, MH 800 A 300–800 (3) 3/0-500 kcmil Al/Cu

MG, MJ 800 A 300–800 (3) 3/0-500 kcmil Al/Cu

PG, PJ, PK❑ , PL 1200 A 250–800 (3) 3/0-500 kcmil Al/Cu

PG, PJ, PK❑ , PL 1200 A 1000–1200 (4) 3/0-500 kcmil Al/Cu

RG, RJ, RK❑ , RL 1200 A 1000–1200 (4) 3/0-600 kcmil Al/Cu

NOTE: Lugs are rated for 75 °C wire, except FA (15–30 A) and FI (20–30 A), which are rated for 60/75 °C. Torque values are listed on the circuit breaker faceplate tables.

❑ Canada only.

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

NOTE: All accessories, except for the Ground-fault shunt trip are field-installable for LA, LH, LC, LI, LX, LXI, LE, MA, and MH circuit breakers.

For detailed information on circuit breakers and accessories, refer to the Digest.

Plug-On Lugs Terminal Data

Plug-On QO® Distribution Panel (Catalog No. HQO306)

• Six-pole, 240 VAC maximum

• Use with QO®, QO-H, QO-VH, QH, and Qwik-Gard® plug-on circuit breakers through 30 A. For detailed information, refer to DP Catalog Class 730 and 910.

• Mounts in all I-Line panelboards.

QO Distribution Panel Branch Circuit Breakers

Circuit Breaker Class Circuit Breaker Class

HD, HG, HJ, HL 611 LI 830

FI 820 LE, LX 661

QB, QD, QG, QJ 734 MG, MJ 612

JD, JG, JJ, JL 611 PG, PJ, PK❑ , PL 612

KI 825 RG, RJ, RK❑ , RL 612

LA, LH, LC 660 ❑ Canada only.

Amperage Rating Frame Size Catalog

No.

Terminal Lug Wire Size

100 A 100 A SL100 #14-1/0 Cu or #12-1/0 Al

250 A 250 A SL250 (1) #4-300 kcmil Al/Cu

400 A 400 A SL400

(1) #1-600 kcmil or

(2) #1-250 kcmil Al/Cu

800 A 800 A SL800 (3) 3/0-500 kcmil Al/Cu

1200 A 1200 A S33931 (4) 3/0-500 kcmil Al/Cu

1200 A ‡ 1200 A S33930 (4) 3/0-600 kcmil Al/Cu

‡ For 100% rated applications (“R” frame breakers).

Distribution Channel Type Number of Poles & Amperages

10 k AIR, QO 1-Pole 10–30 A 2-Pole 10–30 A 3-Pole 10–30 A

10 k AIR, QO-GFI 1-Pole 15–30 A ‡ 2-Pole 15–30 A ‡

22 k AIR, QO-VH 1-Pole 15–30 A 2-Pole 15–30 A 3-Pole 15–30 A

22 k AIR, QO-VHGFI 1-Pole 15–30 A ‡

65 k AIR, QH 1-Pole 15–30 A 2-Pole 15–30 A 3-Pole 15–30 A

‡ Maximum of three GFI-suffix circuit breakers can be installed.

Plug-On Lugs

100 A 225 A

1200 A

400 A

800 A

QO with Visi-Trip® Indicator

1-Pole 2-Pole 3-Pole

Qwik-Gard® Circuit Breaker with Ground Fault Circuit Interrupter

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Circuit Breaker Types

FY

1-Pole; 15–30 A

FA, FH

1-, 2-, and 3-Pole; 15–100 A

FI

2- and 3-Pole; 20–100 A

QB, QD, QG, QJ

2- and 3-Pole; 70–225 A

HD, HG, HJ, HL

2- and 3-Pole; 15–150 A

JD, JG, JJ, JL

2- and 3-Pole; 150–250 A

KI

2- and 3-Pole; 110–250 A

LC, LI

2- and 3-Pole; 300–600 A

LE, LX

2- and 3-Pole; 100–600 A

MG, MJ

2- and 3-Pole; 300–800 A

PG, PJ, PK, PL

2- and 3-Pole; 250–1200 A

RG, RJ, RK, RL

2- and 3-Pole; 1000–1200 A

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

Main Lugs and Main Circuit Breaker Ratings and Lug Sizes

Mains Ampere Rating

Main Lugs Main Circuit Breaker

Actual Lug Size Cable Size Per UL/CSA Wire Bending Space

Actual Lug Size Cable Size Per UL/CSA Wire Bending Space

Mechanical Lug Sizes

100 — — (1) #14-1/0 Al/Cu (1) #14-#1 Al/Cu

225 (1) #6-300 kcmil Al/Cu (1) #6-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu

400 (2) #2-600 kcmil Al/Cu (1) #2-600 kcmil Cu or

(2) #2-500 kcmil Al/Cu

(1) #1-600 kcmil Al/Cu

(2) #1-250 kcmil Al/Cu

(1) #1-600 kcmil Cu or

(2) #1-250 kcmil Al/Cu

600 (2) #2-600 kcmil Al/Cu (2) #2-500 kcmil Al/Cu (3) 3/0-500 kcmil Al/Cu (3) 3/0-500 kcmil Al/Cu

800 (4) 3/0-750 kcmil Al/Cu (3) 3/0-500 kcmil Al/Cu (4) 3/0-500 kcmil Al/Cu (3) 3/0-500 kcmil Al/Cu

1200 (4) 3/0-750 kcmil Al/Cu (4) 3/0-500 kcmil Al/Cu (4) 3/0-600 kcmil Al/Cu (4) 3/0-500 kcmil Al/Cu

VCEL Lug Sizes c

100 — — (1) #8-1/0 Al/Cu (1) #8-#1 Al/Cu

225 (1) #4-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu

(1) 2/0-500 kcmil Al/Cu or

(1) 500-750 kcmil Al or

(2) #4-300 kcmil Al/Cu

(1) 2/0-500 kcmil Al/Cu or

(1) 500-750 kcmil Al or

(2) #4-250 kcmil Al/Cu

(1) 500 kcmil Cu or

(1) 500-750 kcmil Al

(1) 500 kcmil Cu or

(1) 500-750 kcmil Al

600 (2) 2/0-500 kcmil Al/Cu (2) 2/0-500 kcmil Al/Cu (2) 2/0-500 kcmil Al/Cu (2) 2/0-500 kcmil Al/Cu

800 (3) 2/0-500 kcmil Al/Cu (3) 2/0-500 kcmil Al/Cu (2) 500 kcmil Cu or

(2) 500-750 kcmil Al

(2) 500 kcmil Cu or

(2) 500-750 kcmil Al

1200 (4) 500 kcmil Cu or

(4) 500-750 kcmil Al

(4) 500 kcmil Cu or

(4) 600 kcmil Al — — c Compression lugs vary depending on interior type used; contact your local Schneider Electric sales office for assistance.

NOTE: All lugs are suitable for 75 °C wire. Torque values are included on the neutral diagram.

Dimensions

02/2005© 1998–2005 Schneider Electric All Rights Reserved

DIMENSIONS

Type HCN—600 A Maximum Main Lugs

Main Lugs Ampere Rating

Catalog Number H A B C D E

Interior Box 4-Piece Trim without Door ‡ 4-Piece Trim with Door ‡ in. mm in. mm in. mm in. mm in. mm in. mm

HCN1452-2N ❖ HC2652B HCN52T( ) HCN52T( )D 52.00 1321 13.50 343 29.50 749 23.85 606 15.56 395 11.50 292 HCN2365-2N HC2665B HCN65T[( ) HCN65T( )D 65.00 1651 22.50 572 38.50 978 30.35 771 17.56 446 13.50 343 HCN3274-2N HC2674B HCN74T( ) HCN74T( )D 74.00 1880 31.50 800 47.50 1207 23.20 589 17.56 446 13.50 343 HCN4183-2N HC2683B HCN83T( ) HCN83T( )D ■ 83.00 2108 40.50 1029 56.50 1435 26.20 666 17.56 446 13.50 343 HCN5092-2N HC2692B HCN92T( ) HCN92T( )D ■ 92.00 2337 49.50 1257 65.50 1664 29.20 742 17.56 446 13.50 343

HCN1452-4 ❖ HC2652B HCN52T( ) HCN52T( )D 52.00 1321 13.50 343 29.50 749 23.85 606 16.03 407 11.50 292 HCN2365-4 HC2665B HCN65T( ) HCN65T( )D 65.00 1651 22.50 572 38.50 978 30.35 771 18.03 458 13.50 343 HCN3274-4 HC2674B HCN74T( ) HCN74T( )D 74.00 1880 31.50 800 47.50 1207 23.20 589 18.03 458 13.50 343 HCN4183-4 HC2683B HCN83T( ) HCN83T( )D ■ 83.00 2108 40.50 1029 56.50 1435 26.20 666 18.03 458 13.50 343 HCN5092-4 HC2692B HCN92T( ) HCN92T( )D ■ 92.00 2337 49.50 1257 65.50 1664 29.20 742 18.03 458 13.50 343

HCN1452-6 HC2652B HCN52T( ) HCN52T( )D 52.00 1321 13.50 343 29.50 749 23.85 606 16.59 421 11.50 292 HCN2365-6 HC2665B HCN65T( ) HCN65T( )D 65.00 1651 22.50 572 38.50 978 30.35 771 18.59 472 13.50 343 HCN3274-6 HC2674B HCN74T( ) HCN74T( )D 74.00 1880 31.50 800 47.50 1207 23.20 589 18.59 472 13.50 343 HCN4183-6 HC2683B HCN83T( ) HCN83T( )D ■ 83.00 2108 40.50 1029 56.50 1435 26.20 666 18.59 472 13.50 343 HCN5092-6 HC2692B HCN92T( ) HCN92T( )D ■ 92.00 2337 49.50 1257 65.50 1664 29.20 742 18.59 472 13.50 343

‡ Replace parentheses with “F” for flush or “S” for surface.

■ Vault lock is supplied in lieu of flush lock.

❖ Add Cu to suffix for copper bus.

Solid Neutral When Required

Typical Box with Interior

H

Typical Box Side View

6.50

16.50

2.13

26.00 6601.50

27/64 Dia.

B

D

A

C

CEnd of Main Lugs

E

20.88

Flush Lock

S ur fa ce

M ou nt in g H

Typical 4-Piece Trim with Optional Door

F lu sh M ou nt in g

H

.0

Typical 4-Piece Trim without Optional Door

Aφ Bφ Cφ

Front Bus

Center Bus

Rear Bus

A B C

Typical Wiring Diagram Branch connection phasing is determined by circuit breaker selection.

S/N

Typical Endwall

Surface Mounting 26.25

Flush Mounting 28.25

Typical Mounting of FA, FC, FH, FK, FY, HD, HG, HJ, HL, QB, QD, QG, QJ, or QO

Circuit Breakers

5.00

5.00

Dual Dimensions: INCHES Millimeters

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

Type HCN—400 A Maximum Main Circuit Breaker

Main Circuit

Breaker Ampere Rating

Catalog Number H A B C D E

Interior Box

4-Piece Trim without Door ‡

4-Piece Trim with Door ‡ in. mm in. mm in. mm in. mm in. mm in. mm

HCN0952-1MN HC2652B HCN52T( ) HCN52T( )D 52.00 1321 9.00 229 29.50 749 23.85 606 14.78 375 11.50 292 HCN1865-1MN HC2665B HCN65T( ) HCN65T( )D 65.00 1651 18.00 457 38.50 978 30.35 771 16.78 426 13.50 343 HCN2774-1MN HC2674B HCN74T( ) HCN74T( )D 74.00 1880 27.00 686 47.50 1207 23.20 589 16.78 426 13.50 343

HCN0952-2MN ❖ HC2652B HCN52T( ) HCN52T( )D 52.00 1321 9.00 229 29.50 749 23.85 606 13.31 338 11.50 292 HCN1865-2MN HC2665B HCN65T( ) HCN65T( )D 65.00 1651 18.00 457 38.50 978 30.35 771 15.31 389 13.50 343 HCN2774-2MN HC2674B HCN74T( ) HCN74T( )D 74.00 1880 27.00 686 47.50 1207 23.20 589 15.31 389 13.50 343 HCN3283-2MN HC2683B HCN83T( ) HCN83T( )D ■ 83.00 2108 31.50 800 56.50 1435 26.20 666 15.31 389 13.50 343 HCN4592-2MN HC2692B HCN92T( ) HCN92T( )D ■ 92.00 2337 45.00 1143 65.50 1664 29.20 742 15.31 389 13.50 343

HCN1465-4M HC2665B HCN65T( ) HCN65T( )D 65.00 1651 13.50 343 38.50 978 30.35 771 16.87 428 13.50 343 HCN2374-4M HC2674B HCN74T( ) HCN74T( )D 74.00 1880 22.50 572 47.50 1207 23.20 589 16.87 428 13.50 343 HCN3283-4M HC2683B HCN83T( ) HCN83T( )D ■ 83.00 2108 31.50 800 56.50 1435 26.20 666 16.87 428 13.50 343 HCN4192-4M HC2692B HCN92T( ) HCN92T( )D ■ 92.00 2337 40.50 1029 65.50 1664 29.20 742 16.87 428 13.50 343

‡ Replace parentheses with “F” for flush or “S” for surface.

■ Vault lock is supplied in lieu of flush lock.

❖ Add Cu to suffix for copper bus.

Solid Neutral When Required

Typical Box with Interior

H

Typical Box Side View

6.50

16.50

2.13

26.00 6601.50

27/64 Dia.

B

C

C End of

Main Circuit Breaker Lugs

E

20.88

Flush Lock

S ur fa ce

M ou nt in

Typical 4-Piece Trim with Optional Door

F lu sh M ou nt in g

H

Typical 4-Piece Trim without Optional Door

Aφ Bφ Cφ

Front Bus

Center Bus

Rear Bus

A B C

Typical Wiring Diagram Branch connection phasing is determined by circuit breaker selection.

S/N

Typical Endwall

Surface Mounting 26.25

Flush Mounting 28.25

Typical Mounting of FA, FC, FH, FK, FY, HD, HG, HJ, HL, QB, QD, QG, QJ, or QO

Circuit Breakers

5.00

5.00

A

D

Service Entrance Bsrrier (Canada only)

Dual Dimensions: INCHES

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Type HCM—800 A Maximum Main Lugs

Main Lugs

Ampere Rating

Catalog Number H A B C D E

Interior Box

4-Piece Trim without Door ‡

4-Piece Trim with Door ‡ in. mm in. mm in. mm in. mm in. mm in. mm

HCM1448-2N ❖ HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 14.43 367 9.30 236 HCM2364-2N HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 17.93 455 12.80 325 HCM3273-2N HC3273B HCM73T( ) HCM73T( )D ◆ 73.00 1854 31.50 800 48.00 1219 22.90 582 17.93 455 12.80 325 HCM5091-2N HC3291B HCM91T( ) HCM91T( )D ◆ 91.00 2311 49.50 1257 66.00 1676 28.90 734 17.93 455 12.80 325

HCM1448-4 ❖ HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 14.90 378 9.30 236 HCM2364-4 HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 18.40 467 12.80 325 HCM3273-4 ❖ HC3273B HCM73T( ) HCM73T( )D ◆ 73.00 1854 31.50 800 48.00 1219 22.90 582 18.40 467 12.80 325 HCM5091-4 HC3291B HCM91T( ) HCM91T( )D ◆ 91.00 2311 49.50 1257 66.00 1676 28.90 734 18.40 467 12.80 325

HCM1448-6 ❖ HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 16.50 419 9.30 236 HCM2364-6 HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 20.00 508 12.80 325 HCM3273-6 ❖ HC3273B HCM73T( ) HCM73T( )D ◆ 73.00 1854 31.50 800 48.00 1219 22.90 582 20.00 508 12.80 325 HCM5091-6 HC3291B HCM91T( ) HCM91T( )D ◆ 91.00 2311 49.50 1257 66.00 1676 28.90 734 20.00 508 12.80 325

HCM1448-8 HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 15.32 389 9.30 236 HCM2364-8 HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 18.82 478 12.80 325 HCM3273-8 HC3273B HCM73T( ) HCM73T( )D ◆ 73.00 1854 31.50 800 48.00 1219 22.90 582 18.82 478 12.80 325 HCM5091-8 HC3291B HCM91T( ) HCM91T( )D ◆ 91.00 2311 49.50 1257 66.00 1676 28.90 734 18.82 478 12.80 325

‡ Replace parentheses with “F” for flush or “S” for surface.

◆ Two flush locks are supplied.

❖ Add Cu to suffix for copper bus.

Aφ Bφ Cφ

Front Bus

Center Bus

Rear Bus

A B C

Typical Wiring Diagram Branch connection phasing is determined by circuit breaker selection.

S/N

Flush Lock

S ur fa ce

M ou nt in

F lu sh M ou nt in g

H

Typical 4-Piece Trim without Optional Door

Flush Mounting 34.25

Surface Mounting 32.25

Typical Mounting of FY, FA, FH, FC, FK, FI, HD, HG, HJ, HL, JD, JG, JJ, JL, KA, KH, QB, QD, QG, QJ, or QO Circuit Breakers

5.00

5.00

Typical Endwall

Solid Neutral When

Required

Typical Box with Interior Typical Box Side View

22.00

2.00

32.00 8131.75

3/8 Dia.

C

C End of

Main Lugs

E

26.38

8.25

D

A B H

Dual Dimensions: INCHES

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

Type HCM—400 A Maximum Main Circuit Breaker

Main Circuit

Breaker Ampere Rating

Catalog Number H A B C D E

Interior Box

4-Piece Trim without Door ‡

4-Piece Trim with Door ‡ in. mm in. mm in. mm in. mm in. mm in. mm

225 HCM1864-2MN HC3264B HCM64T( ) HCM64T( )D 64.00 1626 18.00 457 39.00 991 29.85 758 15.50 394 12.80 325 225 HCM2773-2MN ❖ HC3273B HCM73T( ) HCM73T( )D ◆ 73.00 1854 27.00 686 48.00 1219 22.90 582 15.50 394 12.80 325

400 HCM1464-4M HC3264B HCM64T( ) HCM64T( )D 64.00 1626 13.50 343 39.00 991 29.85 758 16.96 431 12.80 325

400 HCM2373-4M HC3273B HCM73T( ) HCM73T( )D ◆ 73.00 1854 22.50 572 48.00 1219 22.90 582 16.96 431 12.80 325

400 HCM4191-4M ❖ HC3291B HCM91T( ) HCM91T( )D ◆ 91.00 2311 40.50 1029 66.00 1676 28.90 734 16.96 431 12.80 325

‡ Replace parentheses with “F” for flush or “S” for surface.

◆ Two flush locks are supplied.

❖ Add Cu to suffix for copper bus.

Aφ Bφ Cφ

Front Bus

Center Bus

Rear Bus

A B C

Typical Wiring Diagram Branch connection phasing is determined by circuit breaker selection.

S/N

Flush Lock

S ur fa ce

M ou nt in

F lu sh M ou nt in g

H

Typical 4-Piece Trim without Optional Door

Flush Mounting 34.25

Surface Mounting 32.25

Typical Mounting of FY, FA, FH, FC, FK, FI, HD, HG, HJ, HL, JD, JG, JJ, JL, KA, KH, QB, QD, QG, QJ, or QO Circuit Breakers

5.00

5.00

Typical Endwall

Solid Neutral When

Required

Typical Box with Interior Typical Box Side View

22.00

2.00

32.00 8131.75

3/8 Dia.

C

CEnd of Main Circuit

Breaker Lugs

E

26.38

8.25

D

A

B H

Dual Dimensions: INCHES Millimeters

Service Entrance Barrier

(Canada only)

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Type HCM—800 A Maximum Main Circuit Breaker

Main Circuit

Breaker Ampere Rating

Catalog Number H A B C D E

Interior Box 4-Piece

Trim without Door ‡

4-Piece Trim with Door ‡ ◆

in. mm in. mm in. mm in. mm in. mm in. mm

HCM1873-6MP HC3273DB9 HCM73T( ) HCM73T( )D 73.00 1854 18.00 457 48.00 1219 22.90 582 18.68 474 12.80 325 HCM3691-6MP HC3291DB9 HCM91T( ) HCM91T( )D 91.00 2311 36.00 914 66.00 1676 28.90 734 18.68 474 12.80 325

HCM1873-8MP HC3273DB9 HCM73T( ) HCM73T( )D 73.00 1854 18.00 457 48.00 1219 22.90 582 18.68 474 12.80 325 HCM3691-8MP HC3291DB9 HCM91T( ) HCM91T( )D 91.00 2311 36.00 914 66.00 1676 28.90 734 18.68 474 12.80 325

‡ Replace parentheses with “F” for flush or “S” for surface.

◆ Two flush locks are supplied.

Aφ Bφ Cφ

Front Bus

Center Bus

Rear Bus

A B C

Typical Wiring Diagram Branch connection phasing is determined by circuit breaker selection.

S/N

Flush Lock

S ur fa ce

M ou nt in

F lu sh M ou nt in g

H

Typical 4-Piece Trim without Optional Door

Flush Mounting 34.25

Surface Mounting 32.25

Typical Mounting of FY, FA, FH, FC, FK, FI, HD, HG, HJ, HL, JD, JG, JJ, JL, KA, KH, QB, QD, QG, QJ, or QO Circuit Breakers

5.00

5.00

Typical Endwall

Solid Neutral When

Required

Typical Box with Interior Typical Box Side View

22.00

2.00

32.00 8131.75

3/8 Dia.

C

CEnd of Main Circuit

Breaker Lugs

E

26.38

9.50

D

A

B H

Dual Dimensions: INCHES Millimeters

Service Entrance Barrier

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

Type HCP—800 A Maximum Main Lugs

Main Lugs

Ampere Rating

Catalog Number H A B C D

Interior Box 4-Piece Trim without Door ‡ 4-Piece Trim with Door ‡ in. mm in. mm in. mm in. mm in. mm

HCP1450-4 HC4250DB HCW50T( ) HCW50T( )D 50.00 1270 13.50 343 30.00 762 22.85 580 17.50 445 HCP2359-4 HC4259DB HCW59T( ) HCW59T( )D 59.00 1499 22.50 572 39.00 991 27.35 695 17.50 445 HCP3268-4 HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 31.50 800 48.00 1219 31.85 809 17.50 445 HCP5086-4 HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 49.50 1257 66.00 1676 27.23 692 17.50 445

HCP1450-6 HC4250DB HCW50T( ) HCW50T( )D 50.00 1270 13.50 343 30.00 762 22.85 580 17.50 445 HCP2359-6 HC4259DB HCW59T( ) HCW59T( )D 59.00 1499 22.50 572 39.00 991 27.35 695 17.50 445 HCP3268-6 HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 31.50 800 48.00 1219 31.85 809 17.50 445 HCP5086-6 HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 49.50 1257 66.00 1676 27.23 692 17.50 445

HCP1450-8 HC4250DB HCW50T( ) HCW50T( )D 50.00 1270 13.50 343 30.00 762 22.85 580 16.32 415 HCP2359-8 HC4259DB HCW59T( ) HCW59T( )D 59.00 1499 22.50 572 39.00 991 27.35 695 16.32 415 HCP3268-8 HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 31.50 800 48.00 1219 31.85 809 16.32 415 HCP5086-8 HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 49.50 1257 66.00 1676 27.23 692 16.32 415

‡ Replace parentheses with “F” for flush or “S” for surface.

Aφ Bφ Cφ

Front Bus

Center Bus

Rear Bus

A B C

S/N

Solid Neutral

When Required

H

2.13

42.00 10672.00

27/64 Dia.

C

C

End of Main Lugs

34.38

30.00

9.50

D

A

B

10.30

Vault Lock

S ur fa ce

M ou nt in lu sh M ou nt in g

H

Flush Mounting 44.25

Surface Mounting 42.25

8.00

8.00

Typical Wiring Diagram Branch connection phasing is determined by circuit breaker selection.

Typical 4-Piece Trim with Optional Door

Typical 4-Piece Trim without Optional Door

Typical Endwall

Typical Mounting of FY, FA, FH, FC, FK, FI, HD, HG, HJ, HL, JD, JG, JJ, JL, KA, KH, KC, KI, LA, LH, LC, LI, LXI, LE, MG, MJ, PG, PJ, PK, PL, QB, QD, QG, QJ, or QO

Circuit Breakers

Typical Box with Interior Typical Box Side View

Dual Dimensions: INCHES

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Type HCP—1200 A Maximum Main Lugs

Main Lugs

Ampere Rating

Catalog Number H A B C D

Interior Box 4-Piece Trim without Door ‡ 4-Piece Trim with Door ‡ in. mm in. mm in. mm in. mm in. mm

HCP1450-12N HC4250DB HCW50T( ) HCW50T( )D 50.00 1270 13.50 343 30.00 762 22.85 580 16.32 415 HCP2359-12N HC4259DB HCW59T( ) HCW59T( )D 59.00 1499 22.50 572 39.00 991 27.23 692 16.32 415 HCP3268-12N HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 31.50 800 48.00 1219 31.85 809 16.32 415 HCP5086-12N HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 49.50 1257 66.00 1676 27.23 692 16.32 415

‡ Replace parentheses with “F” for flush or “S” for surface.

Aφ Bφ Cφ

Front Bus

Center Bus

Rear Bus

A B C

S/N

Solid Neutral

When Required

H

2.13

42.00 10672.00

27/64 Dia.

C

End of Main Lugs

35.47

30.00

9.50

D

A

B

10.30

Vault Lock

S ur fa ce

M ou nt in sh M ou nt in g

H

Flush Mounting 44.25

Surface Mounting 42.25

10.35

5.41

Typical Wiring Diagram Branch connection phasing is determined by circuit breaker selection.

Typical 4-Piece Trim with Optional Door

Typical 4-Piece Trim without Optional Door

Typical Endwall

Typical Mounting of FY, FA, FH, FC, FK, FI, HD, HG, HJ, HL, JD, JG, JJ, JL, KA, KH, KC, KI, LA, LH, LC, LI, LX, LE, LXI

MG, MJ, PG, PJ, PK, PL,

QB, QD, QG, QJ, or QO

Circuit Breakers

Typical Box with Interior Typical Box Side View

C

Dual Dimensions: INCHES

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

Type HCP—800 A Maximum Main Circuit Breaker

Main Circuit

Breaker Ampere Rating

Catalog Number H A B C D

Interior Box 4-Piece Trim without Door ‡ 4-Piece Trim with Door ‡ in. mm in. mm in. mm in. mm in. mm

HCP1868-6M HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 18.00 457 48.00 1219 31.85 809 18.68 474 HCP3686-6M HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 36.00 914 66.00 1676 27.23 692 18.68 474

HCP1868-8M HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 18.00 457 48.00 1219 31.85 809 18.68 474 HCP3686-8M HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 36.00 914 66.00 1676 27.23 692 18.68 474

‡ Replace parentheses with “F” for flush or “S” for surface.

Aφ Bφ Cφ

Front Bus

Center Bus

Rear Bus

A B C

S/N

Solid Neutral

When Required

H

2.13

42.00 10672.00

27/64 Dia.

C

End of Main Circuit

Breaker Lugs

34.38

30.00 762 9.50

D

A

B

10.30

Vault Lock

S ur fa ce

M ou nt in sh M ou nt in g

H

Flush Mounting 44.25

Surface Mounting 42.25

8.00

8.30

Typical 4-Piece Trim with Optional Door

Typical 4-Piece Trim without Optional Door

Typical Endwall

Typical Mounting of FY, FA, FH, FC, FK, FI, HD, HG, HJ, HL, JD, JG, JJ, JL, KA, KH, KC, KI, LA, LH, LC, LI, LXI, LE, MG, MJ, QB, QD, QG, QJ, or QO

Circuit Breakers

Typical Box with Interior Typical Box Side View

C

Typical Wiring Diagram Branch connection phasing is determined by circuit breaker selection.

Dual Dimensions: INCHES Millimeters

Service Entrance Barrier

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Type HCP-SU—800 A Maximum Main Circuit Breaker

Main Circuit

Breaker Ampere Rating

Catalog Number H A B C

Interior Box 2-Piece Trim without Door ‡ ◆

2-Piece Trim with Door ‡ ◆

in. mm in. mm in. mm in. mm

800 HCP5486-8SU HC2686DB HC2686T( ) HC2686T( )D 86.00 2184 54.00 1372 65.40 1661 27.23 692

‡ Replace parentheses with “F” for flush or “S” for surface.

◆ Flush trims are 4-piece.

Typical 2-Piece Trim with Optional Door

Typical Box with Interior Typical Box Side View

Typical 2-Piece Trim without Optional Door

Typical Mounting of FY, FA, FH, FC, FK, FI, HD, HG, HJ, HL, JD, JG, JJ, JL, KA, KH, KC, KI, LA, LH, LC, LI, LX, LE, LXI

MG, MJ, PG, PJ, PK, PL,

QB, QD, QG, QJ, or QO

Circuit Breakers

Front bus

Center bus

Rear bus

BΦ

CΦ

AΦ

Branch connection phasing is determined by circuit breaker selection.

8.25

.25 (6)

Flush Lock

Directory

2.07

2.07 5326.16

1.86

1.86

2.00

.42

26.16

Surface Mounting

85.75

Surface Mounting

Dual Dimensions: INCHES Millimeters

H

B

C

A

Service Entrance Barrier

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

Type HCR-U—1200 A Main Lugs or Main Circuit Breaker

NOTE: The back-fed RG, RJ, and RL Main Circuit Breaker or Main Lugs Kit takes up 15 in. (381 mm) of mounting space, leaving 93 in. (2362 mm) of branch circuit breaker mounting space. The back-fed PG, PJ, PL Main Circuit Breaker takes up 9 in. (229 mm) of mounting spaces, leaving 99 in. (2515 mm) of branch circuit breaker mounting space.

Main Lugs or Main Circuit Breaker

Ampere Rating

Catalog Number H A B C

Interior Box 4-Piece Trim without Door ‡ 4-Piece Trim with Door ‡ in. mm in. mm in. mm in. mm

1200 HCR5486-12U HC4486DB HCR86T( ) HCR86T( )D 86.00 2184 54.00 1372 65.10 1654 18.00 457

‡ Replace parentheses with “F” for flush or “S” for surface.

Aφ Bφ Cφ

Solid Neutral

When Required

H

30.00

2.13

44.25 11242.00

27/64 Dia.

40.40

9.50

B

10.30

Vault Lock

S ur fa ce

M ou nt in sh M ou nt in g

H

Flush Mounting 46.25

Surface Mounting 44.25

11.04

5.25

Typical 4-Piece Trim with Optional Door

Typical 4-Piece Trim without Optional Door

Typical Endwall

Typical Mounting of FY, FA, FH, FC, FK, FI, HD, HG, HJ, HL, JD, JG, JJ, JL, KA, KH, KC, KI, LA, LH, LC, LI, LX, LE, LXI

MA, MH, MG, MJ, PG, PJ, PK, PL,

QB, QD, QG, QJ, or QO RG, RJ, RK, and RL

Circuit Breakers

Typical Box with Interior Typical Box Side View

C

A

Typical Wiring Diagram Branch connection phasing is determined by circuit breaker selection.

Back-fed PG, PJ, PL, RG RJ, and RL Main Circuit Breaker or Main Lugs Kit S33930 (see Note:)

A B C

Service Entrance Barrier

(Cananda only)

Dual Dimensions: INCHES

Replacement Parts

02/2005© 1998–2005 Schneider Electric All Rights Reserved

REPLACEMENT PARTS

Main Lugs and Main Circuit Breaker Parts and Part Numbers

Type HCN—600 A Maximum Main Lugs and Main Circuit Breakers

HCN Main Lugs Only Code Letter Description Part Number

Not Shown

Interior Deadfront Trim Assembly 27" Breaker Mounting Space 80104-411-50 45" Breaker Mounting Space 80104-411-51 63" Breaker Mounting Space 80104-411-52 81" Breaker Mounting Space 80104-411-53 99" Breaker Mounting Space 80104-411-54 Screw, Interior Trim Mounting (4) 80025-067-01

A End Barrier Assembly 40517-500-01

Screw, Barrier Mounting (4) 80114-171-01

Not Shown Lug Cover Strap 80104-018-02

B C

Mains Compartment Shield Left (fingered) 40517-505-01 Right (plain) 40517-506-01 Push Rivet, Shield Mounting (2 each) 29215-52126

D Lug Compartment Cover Assembly 40517-507-50

Screw, Cover Mounting (4) 80114-171-01

E Screw, Lug Cover (2) 80025-067-01

F Bracket, Lug Cover and Trim Support 40517-499-01 G Screw, Bracket Mounting (2 each) 80114-171-01

H

Main Lug 225 A 40251-162-51 400–600 A 80116-122-50 Mounting Assembly

225 A–Nut 23427-02200 400 and 600 A –Bolt 21401-28483

–Nut 23427-02800 –Washer 23903-33201

J K

Neutral Insulator 40517-101-01 Screw, Insulator Mounting–225 A (2) 21903-20200 Screw, Insulator Mounting–400 and 600 A (2) 80114-171-01

L Insulator, CØ Lug–400 and 600 A Only 221838

HCN Main Circuit Breaker

Code Letter Description Part Number

100–225 A Mains 400 A Mains

Not Shown

Interior Deadfront Trim Assembly 18" Breaker Mounting Space 80104-414-50 — 27" Breaker Mounting Space — 80104-414-51 36" Breaker Mounting Space 80104-410-50 — 45" Breaker Mounting Space — 80104-410-54 54" Breaker Mounting Space 80104-410-51 — 63" Breaker Mounting Space 80104-410-57 80104-410-58 81" Breaker Mounting Space — 80104-410-56 90" Breaker Mounting Space 80104-410-52 — Screw, Interior Trim Mounting (8) — 80025-067-01

A End Barrier Assembly 40517-500-01 40517-500-01

Screw, Barrier Mounting (4) — 80114-171-01

B C

Mains Compartment Shield Left (fingered) 40517-505-01 40517-505-01 Right (plain) 40517-506-01 40517-506-01 Push Rivet, Shield Mounting (2 each) 29215-52126 29215-52126

N O

Bus Stack Shields Left 80104-821-01 80104-821-01 Right 80104-820-01 80104-820-01 Screw, Shield Mounting (2 each) — 80114-171-01

F Bracket, Trim Support 40517-499-01 40517-499-01 G Screw, Bracket Mounting (2 each) — 80114-171-01

J K

Neutral Insulator — 40517-101-01 Screw, Insulator Mounting (2) 21903-20200 80114-171-01

M

Main Breaker

100 A FA 36100 —

225 A JD 36225 —

400 A — LAP 36400 MB

A

B C

D

J H

F

E

L

K

G

O

B C

J

N

F

M K

G

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

Type HCM—800 A Maximum Main Lugs and Main Circuit Breakers

HCM Main Lugs Only

Code Letter

Description Part Number

225–400 A 600–800 A

Not Shown

Interior Deadfront Trim Assembly 80104-987-50 80104-987-51 80104-987-52 80104-987-53 80025-067-01

27" Breaker Mounting Space 80104-988-50 45" Breaker Mounting Space 80104-988-51 63" Breaker Mounting Space 80104-988-52 99" Breaker Mounting Space 80104-988-53 Screw, Interior Deadfront Trim Mounting (5) —

A End Barrier Assembly 40517-007-01 40517-007-01

80114-171-01

Screw, Barrier Mounting (4) — End Barrier Insulator 80104-056-01

Not Shown Lug Cover Strap 80104-018-02 80104-018-02

21594-12061Screw, Cover Strap Mounting 21594-12061

B C

Mains Compartment Shield 2200068 2200069

29215-52126

Left (fingered) 2200068 Right (plain) 2200069 Push Rivet, Shield Mounting (2 each) 29215-52126

D E

Lug Compartment Cover Assembly 40517-002-50 40517-002-50 80114-171-01 80025-067-01

Screw, Cover Mounting (4) — Screw, Lug Cover (2) —

F Bracket, Lug Cover and Trim Support 80104-385-01 80104-385-01 G Screw, Bracket Mounting (2 each) — 80114-171-01

Code Letter

Description 225 A 400–600 A 800 A

H

Main Lugs Assembly

Lug 40251-162-51 80116-122-50 25098-25110

Nut (1 per lug) 23427-02200 23427-02800 23040-28000

Stud (1 per lug) — 23903-33201 21401-28643

Washer, Lug Mounting (1 per lug) — 21401-28483 23903-33201

Washer (1 per lug) — — 23903-34002

J Neutral Insulator 40517-101-01 221869 221869

Screw, Insulator Mounting (2) 21903-20200 21903-20200 80114-171-01

HCM Main Circuit Breaker

Code Letter

Description Part Number

225–400 A Mains 600–800 A

Not Shown

Interior Deadfront Trim Assembly 18" Breaker Mounting Space 80104-989-50 — 27" Breaker Mounting Space 80104-991-50 — 36" Breaker Mounting Space 80104-989-51 80104-738-52 45" Breaker Mounting Space 80104-991-51 — 54" Breaker Mounting Space 80104-989-52 — 72" Breaker Mounting Space — 80104-738-53 81" Breaker Mounting Space 80104-991-52 — 90" Breaker Mounting Space 80104-989-53 — Screw, Interior Deadfront Trim Mounting (8) — 80025-067-01

A End Barrier Assembly

Screw, Barrier Mounting (4) 40517-007-01 40517-007-01 End Barrier Insulator — 80114-171-01

B C

Mains Compartment Shield Left (fingered) 2200074 40517-093-01 Right (plain) 2200075 40517-098-01 Push Rivet, Shield Mounting (2 each) 29215-52126 29215-52126

K L

Bus Stack Shields Left 80104-821-01 80104-821-01 Right 80104-820-01 80104-820-01 Screw, Shield Mounting (2 each) — 80114-171-01

F Bracket, Trim Support 80104-384-01 80104-384-01 G Screw, Bracket Mounting (2 each) — 80114-171-01

N O

Neutral Insulator 40517-101-01 40517-101-01 Screw, Insulator Mounting (2) –225 A 21903-20200 —

–400, 600, 800 A — 80114-171-01

M

Main Breaker

225 A JD 35225 —

400 A LA 36400 —

600 A — MGP 36600

800 A — MGP 36800

B

C D

J

H

F

E

G

F

A

B

C

O

N

F

M

L K

G

B

02/2005© 1998–2005 Schneider Electric All Rights Reserved

Type HCP—1200 A Main Lugs and 800 A Main Breakers

HCP Main Lugs Only

Code Letter

Description Part Number

400 A Mains 600–800 A

Mains 1200 A Mains

Not Shown

Interior Deadfront Trim Assembly 27" Breaker Mounting Space 80121-041-50 80121-052-50 80121-046-50 45" Breaker Mounting Space 80121-041-51 80121-052-51 80121-046-51 63" Breaker Mounting Space 80121-041-52 80121-052-52 80121-046-52 99" Breaker Mounting Space 80121-041-53 80121-052-53 80121-046-53 Screw, Interior Deadfront Trim Mounting (5) 80025-067-01 80025-067-01 80025-067-01

A End Barrier Assembly 80104-387-01 40517-354-01

Screw, Barrier Mounting (4) 80025-067-01 80025-067-01 End Barrier Insulator 80104-056-01 80104-056-01

Not Shown

Lug Cover Strap 80104-018-02 80104-018-02 Screw, Cover Strap Mounting 21594-12061 21594-12061

B C

Mains Compartment Shield Left 2200077 40517-171-01 Right 2200076 40517-355-01 Push Rivet, Shield Mounting (2 each) 29215-52126 29215-52126

D E

Lug Compartment Cover Assembly 80121-128-50 80121-153-50 Screw, Cover Mounting (4) 80025-067-01 80025-067-01 Screw, Lug Cover (2) 80025-067-01 80025-067-01

F G

Bracket, Lug Cover and Trim Support 80104-385-01 80104-385-01 Screw, Bracket Mounting (2 each) 80025-067-01 80025-067-01

H

Main Lugs Assembly 400 and 600 A 80116-122-50 — 800 A 25098-25110 — 1200 A — 25098-25110

Bolt, Lug Mounting 400 and 600 A 21401-28483 — 800 A 21401-28643 — 1200 A — 21401-28661

Nut, Lug Mounting 400 and 600 A 23427-02800 — 800 and 1200 A 23040-28000 23040-28000

Washer, Lug Mounting 400, 600, 800, and 1200 A 23903-33201 23903-33201

J Neutral Insulator 221854 221854

Screw, Insulator Mounting (2) –400, 600, 800 A –1200 A

80114-171-01 —

— 21903-20200

HCP Main Circuit Breaker

Code Letter Description Part

Number

Not Shown

Interior Deadfront Trim Assembly 36" Breaker Mounting Space 80121-16550 72" Breaker Mounting Space 80121-16551 Screw, Interior Deadfront Trim Mounting (8) 80025-067-01

A End Barrier Assembly 80104-387-01

Screw, Barrier Mounting (4) 80114-171-01

B C

Mains Compartment Shield Left (fingered) 40517-108-01 Right (plain) 40517-098-01 Push Rivet, Shield Mounting (2 each) 29215-52126

K L

Bus Stack Shields Left 80104-821-01 Right 80104-820-01 Screw, Shield Mounting (2 each) 80114-171-01

F G

Bracket, Trim Support 80104-384-01 Screw, Bracket Mounting (2 each) 80114-171-01

N Neutral Insulator 40517-109-01

Screw, Insulator Mounting (2) 80114-171-01

M

Main Breaker

600 A MGL 36600

800 A MGL 36800

A

B

C D J

H

F

E

F G

N

B

C

M

F

L K

G

02/2005 © 1998–2005 Schneider Electric All Rights Reserved

Type HCP-SU—800 A Maximum Universal Main Lugs or Main Breaker

Type HCR-U—1200 A Universal Main Lugs or Main Breaker

HCP-SU Universal Main Lugs or Main Breaker Code Letter Description Part Number

Not Shown Interior Deadfront Trim Assembly 80121-091-50

Screw, Interior Deadfront Trim Mounting (4) 80025-067-01

A Mounting Bracket, Interior Trim (4) 80104-262-01

Screw, Bracket Mounting (8) 80025-067-01

B End Barrier Insulator (2) 80121-090-01

Rivet, Black Nylon (4) 24303-65260

C Neutral Insulator 80121-118-02

Screw, Insulator Mounting (2) 80025-067-01

Not Shown…