Y1DZ--VHA MINOR CONSTRUCTION Solicitation CANCELLED Project 544-329 Construct Eye Clinic Center Minor Construction Columbia, SC VAMC
Solicitation number
36C77624R0028
Issued by

About this file

This document appears to be Attachment 20 - 2023-09-29 544-329 BID DRAWINGS_Part7.pdf, which is related to the federal contract opportunity for Solicitation Number 36C77624R0028 to construct a new 15,000 gross square foot optometric facility at the William Jennings Bryan Dorn VA Medical Center in Columbia, SC. The project will include new construction, HVAC, utility work, interior finishes, utility coordination, site work, underground storm water detention, asbestos and lead survey and abatement, and communication utility work. The Department of Veterans Affairs Technology Acquisition Center Austin is the federal agency issuing this solicitation. No additional details on pricing, award dates, set asides or incumbents are provided in this attachment, as it appears to be a set of drawings related to the construction project.

View the file

Other files

File Type Posted
36C77624R0028 0007 - Signed.pdf PDF
36C77624R0028 0006 - Signed.pdf PDF
36C77624R0028 0005 - Signed.pdf PDF
Technical Questions Tracking Spreadsheet - 9-3-24- 36C77624R0028 - Construct Eye Clinic Columbia SC.docx DOCX document
RoomFinishes.pdf PDF
2024-08-29 544-329 BID DRAWING REVISIONS.pdf PDF
South Carolina Tax Language - 04.04.2024 - FINAL.docx DOCX document
01 00 00 General Requirements_rev 2_8.29.24.pdf PDF
36C77624R0028 0004 - Signed.pdf PDF
09 91 00 Painting_Rev 1 8.30.24.docx DOCX document
544 329 SOW 100_rev2.pdf PDF
00 01 10 Table of Contents_Rev 1 8.30.24.docx DOCX document
Attachment 6 - 544-329 Eye Clinic CD Specs 8.19.24.pdf PDF
SIGN IN SHEET Site Visit 8.15.24.pdf PDF
Amendment 0003 - 36C77624R0028 - Construct Eye Clinic - Columbia SC 8.19.24 - Signed.pdf PDF
Solicitation - 36C77624R0028 - Construct Eye Clinic - Columbia SC 8.19.24.pdf PDF
Attachment 7 - 544-329 Equipment Cut Sheets Part 1.pdf PDF
Attachment 24 - Richland County Wage Rates 6.14.24.pdf PDF
Attachment 9 - 544-329 Equipment Cut Sheets Part 3.pdf PDF
Attachment 28 - Division Cost Breakdown - 5-29-24.xlsx XLSX spreadsheet
Attachment 22 - Site Visit Dorn VAMC Google Map.jpg JPG image
Attachment 18 - 2023-09-29 544-329 BID DRAWINGS_Part5.pdf PDF
Attachment 17 - 2023-09-29 544-329 BID DRAWINGS_Part4.pdf PDF
Attachment 3 - 544 329 VAMC Columbia SC Asbestos Inspection columbia part 1.pdf PDF
Attachment 26 - 544 329 SOW 100_rev1.pdf PDF
Attachment 5 - 544 329 VAMC Columbia SC Asbestos Inspection Report All Buildi.pdf PDF
Attachment 6 - 544-329 Eye Clinic CD Specs_120823.pdf PDF
Attachment 10 - 544-329 Equipment Cut Sheets Part 4.pdf PDF
Solicitation - 36C77624R0028 - Construct Eye Clinic - Columbia SC 8-8-24.pdf PDF
Attachment 12 - 544-329 Equipment Cut Sheets Part 6.pdf PDF
Attachment 23 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 11 - 544-329 Equipment Cut Sheets Part 5.pdf PDF
Attachment 27 - 544 329 Brand Name J and A.pdf PDF
Attachment 2 - 544 329 Eye Clinic Equipment List.xlsx XLSX spreadsheet
Attachment 8 - 544-329 Equipment Cut Sheets Part 2.pdf PDF
Attachment 1 - 544 329 Eye Clinic ConstructionAssessmentPackage 100 Percent.pdf PDF
Attachment 21 - Site Visit Dorn VAMC Campus Map_B101 and Contractor Parking.pdf PDF
Attachment 14 - 2023-09-29 544-329 BID DRAWINGS_Part1.pdf PDF
Attachment 25 - VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 6-2024.docx DOCX document
Attachment 16 - 2023-09-29 544-329 BID DRAWINGS_Part3.pdf PDF
Attachment 4 - 544 329 VAMC Columbia SC Asbestos Inspection columbia part 2.pdf PDF
Attachment 15 - 2023-09-29 544-329 BID DRAWINGS_Part2.pdf PDF
Attachment 13 - 544-329 Geotech Report.pdf PDF
Attachment 19 - 2023-09-29 544-329 BID DRAWINGS_Part6.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

J

COMBINATION DUPLEX

RECEPTACLE/USB CHARGER

USB CHARGING PORT

HOSPITAL GRADE 20 AMP

125 VOLT AC DUPLEX

RECEPTACLE

EQUAL TO TD HUBBELL

USB8300 SERIES

USB

FEATURES

PATTERN: 180 DEGREES

COVERAGE: UP TO 900 SF

TIME DELAY: ADJUSTABLE 1 TO 30 MINUTES

OPTIONS

CONTROL: MANUAL OFF, DUAL TECHNOLOGY LIGHTING CONTROL

GENERAL DESCRIPTION

HOUSING: MEDIUM IMPACT INJECTION MOLDED ABS

MOUNTING: WALL MOUNT AT 48" AFF TO CENTER OF DEVICE.

ELECTRICAL: 120 OR 277 VOLT

FINISH: MATCH FACILITY'S STANDARDS

NOM. DIMENSIONS: 119 mm X 75 mm (4 11/16" X 2 15/16")

WALL MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR WITH DIMMER SWITCH

CEILING HANGER

WIRE, TYP.

RECESSED

CAN

LUMINAIRE

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX)

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING RECOMMENDED MOUNTING HARDWARE

DOWNLIGHT MOUNTING - LAY-IN CEILING

ACOUSTICAL

CEILING TILE

(TYP)

RECESSED CAN

LUMINAIRE

ARCHITECTURAL

CEILING GRID

LUMINAIRE SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

LUMINAIRE

BAR HANGERS

ARCHITECTURAL

CEILING GRID

WIRE TIE OR SCREW

BAR HANGER TO

ARCHITECTURAL

CEILING GRID TYP.

CEILING HANGER WIRE

ARCHITECTURAL

CEILING GRID

ARCHITECTURAL

CEILING GRID

ACOUSTICAL

CEILING TILE

(TYP)

HANGER WIRE AND

MOUNTING CHANNEL

ATTACHED TO STRUCTURE

REFER TO SPECIFICATION

SECTION 26 51 00

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

JUNCTION BOX

LOCKING

SQUARE

WASHER & NUT

6.35mm (1/4") SCREW

ARCHITECTURAL

CEILING

WIRE TIE THROUGH

MOUNTING CHANNEL &

CROSS BEAM, TYP.

FIXTURE WHIP FROM

JUNCTION BOX (1829mm

(6') LONG MAX)

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

EXIT SIGN MOUNTING - LAY-IN CEILING

GRID

ACOUSTICAL CEILING TILE (TYP)

ARCHITECTURAL

CEILING

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND

USING THE RECOMMENDED MOUNTING HARDWARE.

LUMINAIRE MOUNTING - LAY-IN CEILING

LUMINAIRE

SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

3 TWIST MINIMUM

(TYP)

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX.)

LUMINAIRE. REFER

TO SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE. REFER TO

SPECIFICATION SECTION 26 51 00

CEILING CROSS

BEAM

LUMINAIRE. REFER TO SCHEDULE

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND

USING THE RECOMMENDED MOUNTING HARDWARE.

DOWNLIGHT MOUNTING - GYP. BOARD CEILING

CEILING HANGER

WIRE, TYP.

RECESSED CAN

LUMINAIRE

REFER TO

SCHEDULE.

CEILING MAIN BEAM

GYPSUM

BOARD (TYP)

WIRE TIE OR SCREW

BAR HANGER TO

CROSS BEAM TYP.

LUMINAIRE

BAR HANGERS

LUMINAIRE SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

CEILING CROSS

BEAM

RECESSED CAN

LUMINAIRE

CEILING BEAM

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX)

GRID

A

A

Section A-A

1. RATED WALL OR FLOOR ASSEMBLY - PROVIDE FIRE STOPPING ASSEMBLY FOR

PARTITION TYPE & RATING ENCOUNTERED.

2. THROUGH PENETRATION - PROVIDE FIRE STOPPING ASSEMBLY FOR SIZE &

MATERIAL OF THROUGH PENETRATION UTILIZED.

3. FIRE STOPPING MATERIAL - PROVIDE FIRE STOPPING MATERIAL FOR WALL

ASSEMBLY & THROUGH PENETRATION MATERIAL ENCOUNTERED. FILL VOIDS OR

CAVITY ACCORDING TO THE REQUIREMENTS OF THE FIRE STOPPING SYSTEM

UTILIZED.

ALL RATED WALLS, PARTITIONS OR FLOORS SHALL BE PROVIDED WITH A UL LISTED

FIRE STOP SYSTEM. THE SYSTEM UTILIZED SHALL MATCH THE SEPARATION

PENETRATED AND THE THROUGH PENETRATION MATERIAL.

DETAILS FOR THE INSTALLATION OF SYSTEM TYPE UTILIZED SHALL BE AVAILABLE AT

THE PROJECT SITE FOR THE DURATION OF CONSTRUCTION AND SHALL BE PROVIDED

TO THE AUTHORITY HAVING JURISDICTION AND TO THE BUILDING OWNER AT THE

PROJECT COMPLETION.

PROVIDE WALL OR FLOOR LABELS INDICATING THE SYSTEM MANUFACTURER AND UL

LISTED ASSEMBLY NUMBER AT EACH LOCATION WHERE THE FIRE STOPPING SYSTEM

IS INSTALLED.

THROUGH PENETRATION FIRESTOP SYS.

(PROVIDE UL LISTED SYSTEM)

LUMINAIRE

SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

3 TWIST MINIMUM

(TYP)

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX.)

CEILING MAIN

BEAM

GYPSUM BOARD

(TYP)

LUMINAIRE. REFER

TO SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE. REFER TO

SPECIFICATION SECTION 26 51 00

CEILING CROSS

BEAM

GYPSUM BOARD

CEILING CROSS

BEAM

LUMINAIRE. REFER TO SCHEDULE

DRYWALL

BORDER

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND

USING THE RECOMMENDED MOUNTING HARDWARE.

LUMINAIRE MOUNTING - GYP. BOARD CEILING

DEVICE MOUNTING DETAIL

TOP PLATE

STUDS

JUNCTION BOX ABOVE

CEILING MOUNTED ON

BRACKET, TOP PLATE,

OR BY THREADED

ROD FROM STRUCTURE.

HOMERUN

IN EMT.

EMT

CADDY STRAP.

MOUNT TO

STUDS ON BOTH

SIDES.

SWITCH OR

RECEPTACLE.

FEATURES

PATTERN: 360 DEGREES

COVERAGE: 46-186 SQ M (500-2000SF)

TIME DELAY: ADJUSTABLE 30 SECONDS TO 30 MINUTES

OPTIONS

PROVIDE DUAL RELAY IN SPACES WITH MULTIPLE SWITCHING.

CONTROL: MANUAL OFF, DUAL TECHNOLOGY LIGHTING CONTROL

GENERAL DESCRIPTION

HOUSING: IMPACT RESISTANT INJECTION MOLDED ABS

MOUNTING: CEILING BETWEEN 2440-3050 mm (8'-10') H

ELECTRICAL: 24 VOLT DC (FROM POWER PACK), 120 OR 277

VOLT AC

INPUT

FINISH: MATCH FACILITY'S STANDARDS

NOM. DIMENSIONS: 121 mm X 102 mm (4 3/4" DIA X 4"D)

CEILING MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR

2-POLE CEILING MOUNTED OCCUPANCY SENSOR

FOR CONTROL OF DUAL LEVEL SWITCHING

N

LOAD

HN

LOAD

H

LIGHT

SWITCH

LIGHTING CIRCUIT LIGHTING CIRCUIT

EXIT

12", UNLESS CEILING IS HIGHER

THAN 12'-0", THEN 24" ABOVE DOOR.

CEILING

FLOOR

WALL MOUNTED

TELEPHONE

2" TO

TOP OF

COUNTER OR

BACKSPLASH

18"

RECEPTACLE

LIGHT SWITCH

OR DIMMER

ALIGN WHERE

POSSIBLE

TELEPHONE OR

VOICE DATA OUTLET

TV OUTLET

OR CLOCK

OUTLET

FIRE ALARM DEVICES

" A

BO

VE

F

LO

O R

T O

B O

TT

O

M O

F D

EV

IC

E O

N C

O

LU

M N

S

MOUNTING HEIGHTS OF DEVICES

FOR WALL MOUNTED UNITS:

BOTTOM

OF DEVICE

N O

T

TO

E

XC

EE

D

6"

T O

B O

TT

O

M

GENERAL DETAIL NOTES:

A. PARTICULAR ATTENTION SHALL BE GIVEN TO THE ALIGNMENT OF DEVICES.

WHEREVER DEVICES, ON THIS SHEET OR OTHER SHEETS, ARE SHOWN AT

GIVEN LOCATION WITH DIFFERENT MOUNTING HEIGHTS THEY SHALL BE

ALIGNED VERTICALLY. IF THEY ARE SHOWN AT THE SAME MOUNTING HEIGHT

THEY SHALL BE ALIGNED HORIZONTALLY. REFER TO THE ARCHITECTURAL

PLANS, ELEVATIONS AND DETAILS. COORDINATE WITH ARCHITECT PRIOR TO

ROUGH-IN.

B. ALL DIMENSIONS ARE TO THE CENTER LINE OF DEVICE UNLESS INDICATED

OTHERWISE.

C. MOUNTING HEIGHTS SHOWN HERE ARE TYPICAL. PRIOR TO ROUGH-IN,

COORDINATE WITH ARCHITECTURAL PLANS, ELEVATIONS, AND DETAILS. IF A

CONFLICT OCCURS, REQUEST CLARIFICATION FROM ARCHITECT/ENGINEER

PRIOR TO ROUGH-IN.

6"

7FCL-37FCL-1

SMOKE, & FIRE/SMOKE DAMPER

WIRING DETAIL

NOTES:

1. ALL WIRING SHALL BE INSTALLED IN RACEWAY.

2. MULTIPLE DAMPERS CAN BE SERVED BY EACH JUNCTION BOX UP TO A MAXIMUM OF

10 AMPS PER CIRCUIT.

WIRING FROM JUNCTION

BOX TO DISCONNECT

SWITCH AND FROM

DISCONNECT SWITCH

TO DAMPER ACTUATOR

BY EC.

WIRING FROM

ELECTRICAL

PANEL TO

JUNCTION BOX

PROVIDED BY EC.

FIRE, SMOKE, OR

FIRE/SMOKE DAMPER BY

MC.

FIRE ALARM SYSTEM

CONNECTION,

REQUIRED FOR

SMOKE AND

FIRE/SMOKE

DAMPERS. PROVIDED

BY FIRE ALARM

CONTRACTOR.

TO OTHER

DAMPERS

(SEE NOTE 2)

DISCONNECT SWITCH (LEVITON

#1221, OR APPROVED EQUAL)

WITH LOCKABLE COVER; AND

INDICATOR LIGHT (DAYTON/ZORO

RED, OR APPROVED EQUAL)

MOUNTED IN STAINLESS STEEL

PLATE ON UTILITY BOX THAT IS

MOUNTED WITHIN 18 INCHES OF

DAMPER ACCESS DOOR. PROVIDE

CIRCUIT LABEL ON PLATE.

ELECTRICAL PANEL LOCATED IN

ELECTRICAL ROOM, PROVIDED BY EC.

PILOT LIGHT BY EC.

ON WHEN SWITCH IS

ON. MOUNT NEXT TO

SWITCH.

DEVICE LABELING DETAIL

PROVIDE ALL WIRING DEVICES WITH A SELF-

ADHESIVE METALLIC LABEL WITH BLACK

LETTERING INDICATING PANEL AND CIRCUIT

NUMBER SERVING THE DEVICE. THE LABEL

SHALL MATCH THE CURRENT FACILITY'S

STANDARDS FOR NORMAL AND EMERGENCY

BRANCH CIRCUITS. 1/4 " MINIMUM LETTERING

HEIGHT.

GENERAL DETAIL NOTES:

A. COORDINATE LABELING WITH OWNER PRIOR TO INSTALLATION.

NTS 5

NTS 6

NTS 11

NTS 10

NTS 9

NTS 8NTS 12

NTS 13

NTS 18

NTS 17

NTS 16 NTS 1

NTS 14

NTS 15

NTS

T

N

DEVICE LEGEND:

LIGHT SWITCH

RECEPTACLE

VOICE/DATA OUTLET

NURSE CALL DEVICES

THERMOSTAT

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

LOCKING SQUARE

WASHER & LOCKNUT

9.52mm (3/8") MIN GALVANIZED

THREADED ROD, TYP.

UV-INHIBITED POLYCARBONATE

OR HIGH-DENSITY

POLYPROPYLENE PLASTIC

BLOCK, LENGTH AS REQUIRED

CAST METAL "WHILE-IN-USE"

WP COVER(S) &

RECEPTACLE(S).

CAST IRON, NEMA 3R

JUNCTION BOX WITH

THREADED HUBS.

RIGID STEEL CONDUIT

FOR WIRING

SECTION "A-A"

ELEVATION

RIGID STEEL CONDUIT

FOR SUPPORT PER

N.E.C. ART. 314

ROOF PENETRATION AND

CONDUIT SUPPORT PER

DETAIL 5

RECEPTACLE ROOF MOUNTING DETAIL

A

A m m

(1 8"

) M

AX

m m

(1 2"

) M

AX

ROOF CONDUIT SUPPORT DETAIL

PER NEC

4NTS

7NTS

FEATURES

PATTERN: 170 DEGREES

COVERAGE: 28-93 SQ M (300-1000 SF)

TIME DELAY: ADJUSTABLE 15 SECONDS

TO 30 MINUTES

OPTIONS

CONTROL: MANUAL OFF, DUAL TECHNOLOGY LIGHTING CONTROL

GENERAL DESCRIPTION

HOUSING: MEDIUM IMPACT INJECTION MOLDED ABS

MOUNTING: WALL MOUNT AT 48" AFF TO CENTER OF DEVICE.

ELECTRICAL: 120 OR 277 VOLT

FINISH: MATCH FACILITY'S STANDARDS

NOM. DIMENSIONS: 114 mm X 24 mm (4 1/2" H X 15/16" D X 4 5/8" W)

WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY

SENSOR 2NTS

COMBINATION TV RECEPTACLE OUTLET

COVER PLATE AS SHOWN.

TWO GANG BACK BOX WITH

SNAP IN PLASTIC CLOSURE.

CONNECTOR. PROVIDE TEMPORARY

OPENING FOR SYSTEM

BARRIER

DUPLEX RECEPTACLE

ACCESSIBLE CEILING.

STUBBED TO ABOVE

WITH PULL STRING

1" EMPTY CONDUITSYMBOL:

TV

3NTS

INTEGRAL

GALVANIZED LIPPED

STEEL MOUNTING

CHANNEL

LOCKING

SQUARE

WASHER &

LOCKNUT

1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF PENETRATION

FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHING SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT. PROVIDE STEEL EXPANSION

ANCHORS FOR CONCRETE ROOF DECK; BOLTED CONNECTIONS FOR STRUCTURAL

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR.

CONDUIT CLAMP.

SIZE AS REQUIRED

BATT INSULATION

ROOF MEMBRANE

STAINLESS CLAMP, TYP.

3/8" MIN.

GALVANIZED

THREADED ROD

ROOF STRUCTURE ANCHOR, SEE

NOTE 3

CONDUIT,

TYP.

CONDUIT ROOF PENETRATION DETAIL

PREFABRICATED FORMED

1.52mm (0.06") THICK

ALUMINUM FLASHING ROUND

COLLAR WITH MIN. 76mm (3")

WIDE FLANGE. ATTACH TO

ROOF PER MANUFACTURER'S

INSTRUCTIONS

CONDUIT

CLAMP.

SIZE AS

REQUIRED

SEALANT AT

PENETRATION TO

MEMBRANE JUNCTURE

CONTRACTOR

PREFABRICATED RUBBER

BOOT CAP WITH

GRADUATED STEPS &

WEATHER-PROOF

PRESSURE SEAL TO

COLLAR

STEEL MEMBERS.

BY ROOFING

NTS 20

BOND TO BUILDING STEEL OR

TO WATER PIPE WITHIN FIVE FEET

FROM POINT OF ENTRANCE.

XO TERMINATOR

BOND TO TRANSFORMER

ENCLOSURE.

GENERAL NOTES:

PROVIDE TRANSFORMER LUGS, BONDING STRAP, BONDING

BUSHINGS AND JUMPER AT CONDUIT TERMINATION.

SECONDARY FEEDER

(3∅, NEUTRAL AND GND.)

TO MAIN CIRCUIT BREAKER

PANEL BOARD

PRIMARY FEEDER

(3∅ AND GND.)

FROM FEEDER CIRCUIT

BREAKER

GROUNDING CONDUCTOR

TRANSFORMER

DRY TRANSFORMER DETAIL

NTS 19

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

D :\L oc al

R ev it M od el s\

\3

2\

.0 1-

C E

C en tra l M od el

.rv t

8/

/2

:5 7:

A

M

E002

ELECTRICAL - DETAILS

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212

(704) 531-3000 Michael Eaves

HDR, INC

440 South Church Street, Suite 1000 Charlotte, NC 28202

(704) 338-6844 Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

08/18/2022 JCE JLRevisions: Date:

A

C

A C

A A

A

B

A

C

C

C

A A

CADWELD MOLD DETAIL

6 SCALE: NOT TO SCALE11

EXPOSED DOWNLEAD DETAIL

SCALE: NOT TO SCALE

12 SCALE: NOT TO SCALE

PVC CABLE GUARD SCALE: NOT TO SCALE

THRU-ROOF PENETRATION

SCALE: NOT TO SCALE

CADWELD MOLD - TA

MISCELLANEOUS

SCALE: NOT TO SCALE10

SCALE: NOT TO SCALE

THRU-ROOF CONNECTION

AIR TERMINAL

SCALE: NOT TO SCALE

TYPICAL DOWNLEAD DETAIL

SCALE: NOT TO SCALE5

TYPICAL DOWNLEAD DETAIL

SCALE: NOT TO SCALE1

CLASS I COPPER

LIGHTNING CONDUCTOR

AIR TERMINAL

SCALE: NOT TO SCALE

AIR TERMINAL

2 SCALE: NOT TO SCALE

AIR TERMINAL

SCALE: NOT TO SCALE3

AIR TERMINAL

SCALE: NOT TO SCALE

NOTE: ALL DETAILS MAY NOT APPLY TO THIS PROJECT.

3M VHB TAPE

SELF CONTAINED

STAINLESS STEEL NUT

AND LOCK WASHER

3M VHB TAPE

3M VHB TAPE

SELF CONTAINED

STAINLESS STEEL NUT

AND LOCK WASHER

SELF CONTAINED

STAINLESS STEEL NUT

AND LOCK WASHER

All fasteners shall have appropriate loop supports. No support penetrations shall be made in any sheet metal flashing or roof top equipment. Sheet metal screws shall not be used. Appropriate adhesive supports and construction mastic may be used on Membrane roof surfaces only.

Adhesive supports and construction mastic shall not be used on any sheet metal surfaces.

The contractor shall furnish 10 Year Adhesion Warranty on the fastener system.

1/2" X 12"

COPPER SAFETY TIPPED

AIR TERMINAL

COPPER

CABLE CLIP FASTENING SYSTEM

CLASS I

ALUMINUM MAIN CONDUCTOR

COPPER UNIVERSAL LIGHTNING ROD MOUNT

ASSEMBLY, SECURE WITH ADHESIVE

1/2" X 12"

COPPER SAFETY TIPPED

AIR TERMINAL

COPPER

ADHESIVE CABLE FASTENER

CLASS I

COPPER MAIN CONDUCTOR

COPPER 8"

SURFACE BONDING PLATE

UNIVERSAL LIGHTNING

ROD MOUNT ASSEMBLY

1/2" GALVANIZED STEEL TRIPOD

BASE

1/2" X 48"

COPPER SAFETY TIPPED AIR TERMINAL

COPPER ONE HOLE CABLE

STRAP

COPPER PIPE CLAMP

U-BOLT GROUND

ROD CLAMP

COPPER

CLASS I CONDUCTOR

COPPER U

BOLT CLAMP BASE

1/2" X 12"

COPPER SAFETY TIPPED

AIR TERMINAL

2 SCREW STANDING

SEAM SUPPORT

COPPER

CABLE CLIP

1/2" x 18"

COPPER CONCEALED BASE

CLASS I COPPER MAIN

CONDUCTOR

1/2" X 12" UNIVERSAL AIR

TERMINAL

SWIVEL ADAPTER, 1/2" TO 1/2"

UNIVERSAL PARALLEL CABLE SPLICER ASSEMBLY

USE TO SPLICE MAIN

SIZE CONDUCTOR TO

MAIN SIZE CONDUCTOR

BRONZE PARALLEL CLAMP

BRONZE CABLE TO FLAT

METAL CLAMP

CLASS I COPPER MAIN

CONDUCTOR

1" PVC CONDUIT

BRONZE

FLANGE BONDING

PLATE

1" PVC CONDUIT

CLASS I

COPPER MAIN CONDUCTOR

CLASS I

COPPER MAIN CONDUCTOR

BI-METAL

THRU-ROOF CONNECTOR

CLASS I

ALUMINUM MAIN CONDUCTOR

BRONZE

CROSS-RUN CABLE

CONNECTOR

BRONZE

FLANGE BONDING PLATE

BI-METAL

CONNECTOR

HEAVY

DUTY BONDING LUG

COPPER PIPE CLAMP

BONDING LUG

CABLE TO

FLAT METAL CLAMP

STRAP

TYPE PIPE CLAMP

COPPER

FLAT BONDING PLATE

COPPER

BONDING PLATE

CADWELD MOLD

CABLE TO CABLE CONNECTION

CLASS I

COPPER MAIN CONDUCTOR

CLASS I MAIN

CONDUCTOR COPPER

CLASS I MAIN

CONDUCTOR COPPER

FLANGE

BONDING PLATE

THRU-ROOF

ASSEMBLYCLASS I

COPPER MAIN CONDUCTOR

CLASS I

ALUMINUM MAIN CONDUCTOR

BI-METAL

CONNECTOR

PVC

CABLE GUARD

CLASS I

COPPER MAIN CONDUCTOR

PIPE GROUNDING

CLAMP

CLASS I COPPER

MAIN SIZE CONDUCTOR

BI-METAL

CONNECTOR

CLASS I

COPPER MAIN CONDUCTOR

CLASS I

COPPER MAIN CONDUCTOR

CADWELD MOLD

CABLE TO CABLE CONNECTION

CLASS I

COPPER MAIN CONDUCTOR

CADWELD MOLD

3/4" X 10 COPPER CLAD

GROUND ROD

AIR TERMINAL

MECHANICAL CONNECTION

MISC. BONDING

THRU-ROOF CONNECTOR

CLASS I ALUMINUM MAIN CONDUCTOR

CLASS I COPPER MAIN CONDUCTOR

COPPER CLAD GROUND ROD

WITH ULTRAWELD CONNECTION

TR

LEGEND

M

IN

M

IN

B E

LO

W

F

IN

IS

H

G R A D E

INSTALLATION NOTES

1. LIGHTNING PROTECTION SYSTEM DEPICTED IN THESE PLANS ARE

FOR BIDDING PURPOSES. CONTRACTOR TO PROVIDE SHOP

DRAWINGS DEPICTING A UL LISTED LIGHTING PROTECTION SYSTEM.

THEY SHALL BE COMPLETED AND STAMPED BY AN LPI CERTIFIED

MASTER DESIGNER - INSTALLER OF LIGHTNING PROTECTION

SYSTEMS.

2. LOCATE AIR TERMINALS AS REQUIRED. TAKE CARE TO ENSURE

THAT ALL POINTS ARE WITHIN 2'-0" (609mm) OF OUTSIDE BUILDING

EDGE, OUTSIDE CORNERS, RIDGE ENDS, AND THAT MAX SPACING

DOES NOT EXCEED 20'-0" (6,096mm), AND THAT MIN PROJECTION ABOVE OBJECT PROTECTED IS 10" (254mm); POINTS PROJECTING 24" (609mm) MAY BE SPACED @ 25'-0" (7,520mm) MAX.

3. MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN

CONDUCTOR. ENSURE THAT ALL BENDS HAVE AT LEAST AN 8"

(203mm) RADIUS AND DO NOT EXCEED 90 DEGREES.

4. ATTACH ALL EXPOSED ROOF, DOWN LEAD AND BONDING CABLES AT

3'-0" (914mm) ON CENTER MAX. VERIFY COMPATIBILITY OF ADHESIVE

ON MEMBRANE ROOF APPLICATION PRIOR TO INSTALLATION.

5. GROUND ELECTRODES SHALL BE INSTALLED AS REQUIRED, BUT IN

NO INSTANCE SHALL THEY BE LESS THAN 1'-0" (304mm) BELOW GRADE AND 2'-0" (609mm) FROM FOUNDATION WALL. DRIVEN RODS SHALL PENETRATE THE EARTH AT LEAST 10'-0" (3,048mm).

6. BOND TO WATER SERVICE AND OTHER PIPING SYSTEMS AS

REQUIRED.

7. MAIN SIZE LIGHTNING CONDUCTOR SHALL BE BONDED TO MAIN

GROUND BUS FIELD. VERIFY LOCATION. PROVIDE 1" CONDUIT FOR

ACCESS. INTERCONNECT LIGHTNING PROTECTION GROUND TO

TELEPHONE AND OTHER BUILDING GROUND SYSTEMS LOCATION

FIELD. DETERMINE OR AS REQUIRED BY CODE.

8. SYSTEM SHALL BE INSTALLED AS REQUIRED TO ENSURE PROPER

CODE COMPLIANCE AND SYSTEM CERTIFICATION. ANY MAJOR

VARIANCE SHALL BE RESUBMITTED FOR APPROVAL.

9. ALL MATERIALS SHALL BE UNDERWRITER'S LABORATORIES

APPROVED WITH "A" LABELS ON CONDUCTORS @ 10'-0" INTERVALS

AND "B" LABELS ON ALL AIR TERMINALS.

10. FINAL SYSTEM INSPECTION AND QUALITY CONTROL

A. THE CONTRACTOR SHALL FURNISH AN LPI-IP CERTIFICATE OR A

UL CERTIFICATE UPON COMPLETION OF THE INSTALLATION.

B. LPI CERTIFICATION REQUIRES A SIGNATURE BY A

REPRESENTATIVE OF THE OWNER AT MULTIPLE STAGES OF

INSTALLATION & BY THEIR THIRD PARTY FIELD STAFF. UL

CERTIFICATION REQUIRES INSPECTION BY THEIR THIRD-PARTY

FIELD STAFF AFTER COMPLETION OF THE INSTALLATION.

C. AS-BUILT DRAWINGS SHALL BE COMPLETED AND STAMPED BY

AN LPI CERTIFIED MASTER DESIGNER - INSTALLER OF LIGHTNING

PROTECTION SYSTEMS.

D. FINAL INSPECTION REPORT - A FINAL INSPECTION AND

INSPECTION REPORT SHALL BE COMPLETED BASED ON

ANSI/TIA/EIA 607, NEC, NFPA 780, AND UL96A INDUSTRY

STANDARDS AS APPLICABLE. THE SCOPE OF THE INSPECTION

AND REPORT SHALL INCLUDE;

a. TEST AND EVALUATION THE GROUNDING SYSTEM. RECORD

FINAL SYSTEMS TO GROUND RESISTANCE LEVEL.

b. EVALUATION AND TESTING OF THE INTERNAL BONDING AND

GROUNDING SYSTEMS.

c. EVALUATION AND TESTING OF EQUIPMENT GROUNDING.

d. EVALUATION OF AC SURGE SUPPRESSION INSTALLATION.

e. EVALUATION OF TELCO SURGE SUPPRESSION INSTALLATION.

f. COPY OF THE LPI-IP LIGHTNING PROTECTION CERTIFICATION.

g. FINAL AS-BUILT REVIEW AND SUBMISSION.

E. REPORT SHALL INCLUDE DETAILED REPORTING AND TEST

RESULTS WITH CORRESPONDING PHOTOS OF EACH EVALUATION

CATEGORY.

TYPICAL BODIES OF CONDUCTANCE AS NOTED BELOW. USE FULL SIZE

CONDUCTOR AND APPROPRIATE FITTING SHOWN FOR CONNECTION.

(PLUMBING STACK) REQUIRES BONDING WITH MAIN SIZE CABLE ONLY IF

WITHIN 6'-0" (1,828mm) OF LIGHTING PROTECTION SYSTEM.

TYPICAL BODIES OF INDUCTANCE AS NOTED BELOW. USE SECONDARY

SIZE (SMALLER) CONDUCTOR AND APPROPRIATE FITTING SHOWN FOR

CONNECTION.

A

B

C

GENERAL BONDING NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

D :\L oc al

R ev it M od el s\

\3

2\

.0 1-

C E

C en tra l M od el

.rv t

8/

/2

:5 7:

A

M

E003

ELECTRICAL - LIGHTNING DETAILS

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212

(704) 531-3000 Michael Eaves

HDR, INC

440 South Church Street, Suite 1000 Charlotte, NC 28202

(704) 338-6844 Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

08/18/2022 JCE JLRevisions: Date:

CONTRACTOR SHALL PROVIDE CONCRETE PAD/PIT, PLUS

ALL LABOR, MATERIALS AND PAY ALL POWER COMPANY

CONNECTION FEES TO PROVIDE A COMPLETE AND

OPERATING SYSTEM FOR THE OWNER.

THIS DESIGN ASSUMES A 500KVA POWER COMPANY

TRANSFORMER WITH 15,689 FAULT CURRENT.

CONTRACTOR SHALL VERIFY THE EXACT TRANSFORMER

AND FAULT CURRENT WITH THE POWER COMPANY BEFORE

WORK BEGINS OR EQUIPMENT IS ORDERED. CONTRACTOR

SHALL PROVIDE A PLAQUE STATING FAULT CURRENT

CALCULATION AND DATE PERFORMED AT THE SERVICE

DISCONNECT. IF POWER COMPANY SUPPLIED

TRANSFORMER IS LARGER THAN SHOWN THEN

CONTRACTOR SHALL CONTACT THIS ENGINEER PRIOR TO

ORDERING PANELS.

CONNECT ALL AVAILABLE GROUNDING MEANS PER NEC

250.50.

SEE SITE PLAN FOR LOCATION OF THE TRANSFORMER.

PROVIDE 4" HOUSEKEEPING PADS AT ALL EQUIPMENT AND

TRANSFORMERS.

CONTRACTOR SHALL COORDINATE ALL SERVICE

REQUIREMENTS WITH UTILITY COMPANY PRIOR TO ROUGH-

IN AND NEW WORK.

GENERAL NOTES

A.

B.

C.

D.

E.

F.

PAD MOUNTED

UTILITY

TRANSFORMER

480/277v

METER

GROUND LEVEL

150 KVA

XFMR

PANEL 'LDP1'

SECTION 2 SECTION 1

NEW PRIMARY SERVICE

BY DOMINION ENERGY

120/208V

PANEL 'LDP2'

SECTION 2 SECTION 1

120/208V

4 SETS OF (4 #350KCMIL, 3"C.) SECONDARY

200Δ

1/0G

1"C.

TVSS

60Y

225A MLO225A MCB

225Y

ELECTRICAL ROOM 1A024ELECTRICAL ROOM 1A108

NEW WORK KEYED NOTES

NEW UTILITY TRANSFORMER TO BE PROVIDED BY DOMINION ENERGY .

COORDINATE WITH UTILITY FOR EXACT SIZE AND REQUIREMENTS.

PROVIDE CONCRETE BASE TO COMPLY WITH POWER COMPANY

REQUIREMENTS. SEE GENERAL NOTES 'A'.

PROVIDE CONDUIT TO COMPLY WITH POWER COMPANY

REQUIREMENTS. SEE SITE PLAN SHEET ES-001 FOR ADDITIONAL

INFORMATION.

PROVIDE 4" CONCRETE PAD. COORDINATE WITH STRUCTURAL

CONTRACTOR.

PROVIDE PANEL WITH DIGITAL METERING INCLUDING: AMPS,

VOLTS(PHASE-PHASE AND PHASE-NEUTRAL), KW, KVA.

PROVIDE PANEL WITH 100% RATED MAIN BREAKER.

MLDP

120/208V

500A MCB

225Y

PANEL 'LDP4'

120/208V

225A MCB

225Y

PANEL 'LDP3'

120/208V

225A MLO

225Y

ISC: 5,322

ISC: 19,316

ISC: 20,747

PANEL 'COMM1'PANEL 'COMM2'

120/208V120/208V

100A MCB100A MCB

COMM 1A016COMM 1A102

100Y

100Y

2 SETS OF

(4#250KCMIL,

1/0 G, 2 1/2" C)

PANEL 'MDP'

1200A

MCB

480/277V

2/0 G

PANEL 'H1'

225A

MLO

480/277V

225Y

#3/0G,1-1/4"C.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

C U s e rs \j e d w a rd s .C

H A

R E

N G

\D o c u m e n ts \R e v it

\3

.0

-C

E C e n tr a l M o d e l.

rv t

/1

/2

:3

:2

P

M

E004

ELECTRICAL - RISER DIAGRAM AND

LUMINAIRE SCHEDULECharlotte Engineers, LLP

5838 Monroe Road

Charlotte, NC 28212

(704) 531-3000

Michael Eaves

HDR, INC

440 South Church Street, Suite 1000

Charlotte, NC 28202

(704) 338-6844

Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

08/18/2022 JCE JL

LUMINAIRE SCHEDULE

TYPE DESCRIPTION

LUMEN

OUTPUT

A221 2'x2' LED BACKLIT FLAT PANEL, WHITE, 0-10V DIMMABLE. MULTI-VOLT (120-277V).

2000 4000K LED/30W

2'x4' LED BACKLIT FLAT PANEL, WHITE, 0-10V DIMMABLE. MULTI-VOLT (120-277V).

3000 4000K

D611

6" DIAMETER LED DOWNLIGHT, WHITE INTERIOR DOME REFLECTOR,

GALVANIZED STEEL FRAME. 0-10V DIMMABLE. MULT VOLT (120-277V).

1000 4000K LED/18W

E6

EXIT SIGN, WALL OR CEILING MOUNTED AS SHOWN ON DRAWINGS, EDGELIT,

MIRROR BACKGROUND, RED LETTERS. NUMBER OF FACES AND

DIRECTIONAL CHEVRONS AS SHOWN ON DRAWINGS. MULT VOLT (120-277).

- LED/5W

LUMINAIRE SCHEDULE NOTES:

2. ALL LED FIXTURES SHALL BE UL LISTED AND HAVE A CRI OF AT LEAST 85.

3. ALL LUMINAIRE SUBMITTALS SHALL INCLUDE LED AND DRIVER CUT/DATA SHEETS.

LAMP/

WATTAGE

COLOR

TEMP.

1. COORDINATE WITH ARCHITECTURAL DRAWINGS (REFLECTED CEILING PLANS AND ELEVATIONS)

FOR EXACT LOCATIONS OF FIXTURES, CEILING TYPES AND MOUNTING HEIGHTS.

3000 4000K

LED/30W

ILE

6" DIAMETER LED DOWNLIGHT WITH 90 MINUTE BATTERY BACKUP, WHITE

INTERIOR DOME REFLECTOR, GALVANIZED STEEL FRAME. 0-10V DIMMABLE.

MULT VOLT (120-277V).

1000 4000K LED/18WD611E

A421E 2'x4' LED BACKLIT FLAT PANEL, WHITE, 0-10V DIMMABLE. MULTI-VOLT

(120-277V). PROVIDE WITH 90 MINUTE BATTERY BACKUP.

A221E 2'x2' LED BACKLIT FLAT PANEL, WHITE, 0-10V DIMMABLE. MULTI-VOLT

(120-277V). PROVIDE WITH 90 MINUTE BATTERY BACKUP.

2000 4000K LED/30W

A421 LED/40W

LED STRIP FIXTURE WITH 90 MINUTE BATTERY BACKUP, STEEL HOUSING,

WHITE BAKED ENAMEL FINISH. COORDINATE WITH THE ARCHITECTURAL

CASEWORK DETAILS AS REQUIRED. MULT VOLT (120-277V).

3000 4000K LED/40W

INDIRECT LED "IN USE" LIGHT. SURFACE MOUNTED, WALL OR CEILING;

SINGLE FACE. MULT VOLT (120-277V). POLYCARBONATE HOUSING. LEGEND

COLOR: RED.

WL - - LED/1.5W

P1

BELL SHAPED HANGING PENDANT, 5" DIAMETER, BRONZE FINISH. GLASS

SHADE WITH MATTE FINISH. PROVIDE WITH LED BULB, E26 MEDIUM BASE.

DIMMABLE. 120V.

LED/75W

EQUIVALENT

4000K

WALL MOUNTED EXTERIOR FIXTURE. ALUMINIUM HOUSING. BLACK, ZINC-

INFUSED POWDER COAT FINISH. IMPACT RESISTANT, TEMPERED GLASS

LENS. UL WET LOCATION LABEL. MOUNT APPROXIMATELY 12' AFF. MULT

VOLT (120-277V).

WP 7027 5000K LED/72W

D611WPE

WPE

6" DIAMETER LED DOWNLIGHT WITH 90 MINUTE BATTERY BACKUP, WHITE

INTERIOR DOME REFLECTOR, GALVANIZED STEEL FRAME. DIMMABLE.

LISTED AND LABELED FOR DAMP LOCATION. MULT VOLT (120-277V).

1000 4000K LED/18W

WALL MOUNTED EXTERIOR FIXTURE. ALUMINIUM HOUSING. BLACK, ZINC-

INFUSED POWDER COAT FINISH. IMPACT RESISTANT, TEMPERED GLASS

LENS. UL WET LOCATION LABEL. MOUNT APPROXIMATELY 12' AFF. MULT

VOLT (120-277V). PROVIDE WITH 90 MINUTE EMERGENCY BATTERY BACKUP.

LED/72W

V1

2' DECORATIVE LED STRIP FOR ABOVE MIRROR LED, EXTRUDED ALUMINUM

HOUSING, FROSTED ACRYLIC

LENS AND MACHINED ALUMINUM END CAPS. SURFACE MOUNTED. 120V.

2200 4000K LED/18W

7027 5000K

UC

36" UNDER SHELF CABINET LINEAR LIGHTING FIXTURE, DIE FORMED 20

GAUGE STEEL. APPROXIMATE 1" HOUSING. SOLID FRONT, WHITE PAINT

AFTER FABRICATION, CLEAR PRISMATIC LENS, ROCKER SWITCH. 120V.

LED/15W3000K1344

D611WP

6" DIAMETER LED DOWNLIGHT WHITE INTERIOR DOME REFLECTOR,

GALVANIZED STEEL FRAME. 0-10V DIMMABLE. LISTED FOR DAMP LOCATION.

MULT VOLT (120-277V).

1000 4000K LED/18W

SCALE: NONE

ELECTRICAL - POWER RISER DIAGRAM

Revisions: Date:

LDP2LDP1

MDP2MLDPMDP1

H1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

D :\L oc al

R ev it M od el s\

\3

2\

.0 1-

C E

C en tra l M od el

.rv t

8/

/2

:5 7:

A

M

E005

ELECTRICAL - PANEL SCHEDULES

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212

(704) 531-3000 Michael Eaves

HDR, INC

440 South Church Street, Suite 1000 Charlotte, NC 28202

(704) 338-6844 Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

08/18/2022 JCE JL

Notes:

Total Est. Demand: 139 A Total Conn.: 136 A

Total Est. Demand: 115639 VA Lighting 11498 VA 125.00% 14372 VA Total Conn. Load: 112787 VA

HVAC 101391 VA 100.00% 101391 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

148 A 140 A 123 A Total Load: 40.5 kVA 38.1 kVA 34.2 kVA

PHASE A PHASE B PHASE C

53 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 54

51 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 52

49 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 50

47 DISC - VAV 1-1-15V 12 12 2 3/4 1 15 1.0 0.0 20 1 SPARE 48

45 DISC - VAV 1-2-18V 12 12 2 3/4 1 15 3.0 3/4 2 10 10 46

43 DISC - VAV 1-2-15V 12 12 2 3/4 1 15 3.0 1.5 20 1 3/4 2 12 12 LTG - EXTERIOR 44 41 DISC - VAV 1-2-10V 12 12 2 3/4 1 15 3.1 1.5 15 1 3/4 2 12 12 DISC - VAV 1-2-16V 42

39 SPARE 1 20 0.0 4.0 20 1 3/4 2 12 12 DISC - VAV 1-2-17V 40

37 DISC - VAV 1-2-2V 12 12 2 3/4 1 20 5.0 1.0 15 1 3/4 2 12 12 DISC - VAV 1-2-14V 38 35 DISC - VAV 1-2-8V 12 12 2 3/4 1 15 3.1 4.0 20 1 3/4 2 12 12 DISC - VAV 1-2-13V 36

33 DISC - VAV 1-2-5V 12 12 2 3/4 1 15 3.8 2.3 34

31 DISC - VAV 1-2-7V 12 12 2 3/4 1 20 3.5 2.3

15 2 3/4 2 12 12 DISC - VAV 1-2-12V

29 DISC - VAV 1-2-9V 12 12 2 3/4 1 15 1.5 2.5 15 1 3/4 2 12 12 DISC - VAV 1-2-6V 30

27 2.3 1.5 15 1 3/4 2 12 12 DISC - VAV 1-1-12V 28

DISC - VAV 1-2-1V 12 12 2 3/4 2 15

2.3 2.5 15 1 3/4 2 12 12 DISC - VAV 1-2-11V 26

23 DISC - VAV 1-1-14V 12 12 2 3/4 1 15 3.0 3.0 15 1 3/4 2 12 12 DISC - VAV 1-1-3V 24

21 2.0 2.2 20 1 3/4 2 12 12 LTG - EAST SIDE 22

DISC - VAV 1-1-11V 12 12 2 3/4 2 15

2.0 2.0 15 1 3/4 2 12 12 DISC - VAV 1-2-4V 20

17 DISC - VAV 1-1-13V 12 12 2 3/4 1 15 1.5 1.2 15 1 3/4 2 12 12 DISC - VAV 1-2-3V 18 15 DISC - VAV 1-1-8V 12 12 2 3/4 1 20 4.4 4.0 20 1 3/4 2 12 12 DISC - VAV 1-1-7V 16 13 DISC - VAV 1-1-10V 12 12 2 3/4 1 15 1.2 3.0 15 1 3/4 2 12 12 DISC - VAV 1-1-4V 14

11 4.0 2.5 15 1 3/4 2 12 12 DISC - VAV 1-1-5V 12

DISC - VAV 1-1-2V 12 12 2 3/4 2 25

4.0 3.0 15 1 3/4 2 12 12 DISC - VAV 1-1-6V 10

7 DISC - VAV 1-1-1V 12 12 2 3/4 1 20 4.0 3.5 20 1 3/4 2 12 12 DISC - VAV 1-1-9V 8 5 LTG - CORR. NORTH 12 12 2 3/4 1 20 0.9 1.3 20 1 3/4 2 12 12 LTG - SOUTHWEST SIDE 6 3 LTG - CORR. SOUTH 12 12 2 3/4 1 20 0.6 1.2 20 1 3/4 2 12 12 LTG - SOUTHEAST SIDE 4

1 LTG - EXTERIOR 12 12 2 3/4 1 20 1.2 2.7 20 1 3/4 2 12 12 LTG - WEST SIDE 2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1 Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: MDP2 Phases: 3 Mains Type: MLO Location: ELEC 1A024 Volts: 480/277 Wye A.I.C. Rating: 42,000

Branch Panel: H1

1. PROVIDE GFCI CIRCUIT BREAKER.

2. SEE SHEET ES001 FOR WIRE AND CONDUIT SIZING.

Notes:

MISCELLANEOUS 4900 VA 100.00% 4900 VA

Receptacle 36000 VA 63.89% 23000 VA Total Est. Demand: 90 A Power 3600 VA 100.00% 3600 VA Total Conn.: 126 A Lighting 240 VA 125.00% 300 VA Total Est. Demand: 32400 VA Heating 200 VA 100.00% 200 VA Total Conn. Load: 45340 VA Equipment 400 VA 100.00% 400 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

133 A 142 A 109 A Total Load: 15.6 kVA 16.6 kVA 13.1 kVA

PHASE A PHASE B PHASE C

83 SPARE 1 20 0.0 0.0 20 1 SPARE 84

81 SPARE 1 20 0.0 0.0 20 1 SPARE 82

79 SPARE 1 20 0.0 0.0 20 1 SPARE 80

77 SPARE 1 20 0.0 0.0 20 1 SPARE 78

75 SPARE 1 20 0.0 0.0 20 1 SPARE 76

73 REC - DOMESTIC HOT BOX 2 1 20 0.1 0.0 20 1 SPARE 74

71 REC-SHARED OFF 1A087 12 12 2 3/4 1 20 1.0 0.1 20 1 2 REC - FIRE HOT BOX HEATER 72 69 REC-PRINTER SHRD OFF... 12 12 2 3/4 1 20 0.8 1.0 20 1 3/4 2 12 12 REC-SHARED OFF 1A078 70 67 REC-SHARED OFF 1A082 12 12 2 3/4 1 20 1.0 0.8 20 1 3/4 2 12 12 REC-EX 13 1A066 68

65 REC-OCT 2 1A083 12 12 2 3/4 1 20 0.8 0.8 20 1 3/4 2 12 12 REC-OCT 1 1A085 66

63 HEAT TRACE PIPING ROOF 8 10 2 1 1 40 3.6 0.6 20 1 3/4 2 12 12 REC-OCT 2 1A083 64 61 REC-OCT 1 1A085 12 12 2 3/4 1 20 0.6 1.4 20 1 3/4 2 12 12 REC-SHARED OFF 1A078 62 59 AFAMP-MECH 1A092 12 12 2 3/4 1 20 0.4 1.4 20 1 3/4 2 12 12 REC-SHARED OFF 1A082 60 57 NITROGEN GEN-VALVE 1A089 12 12 2 3/4 1 20 0.3 0.8 20 1 3/4 2 12 12 REC-TLT,HAC 1A112,1A104 58 55 REC-EX 13 1A066 12 12 2 3/4 1 20 0.6 2.3 30 1 3/4 2 10 10 HEAT TRACE-MECH 1A092 56

53 RCP-1 12 12 2 3/4 1 20 0.2 0.8 20 1 3/4 2 12 12 REC-VF 2 1A079 54

51 LTG-RCPT DESK PENDANTS 12 12 2 3/4 1 20 0.2 0.5 20 1 3/4 2 12 12 FAA-VEST 1A001 52 49 FUTURE IONIZATION SYSTEM 12 12 2 3/4 1 20 0.2 0.6 20 1 3/4 2 12 FACP-MECH 1A092 50

47 REC-CORR 1A080 12 12 2 3/4 1 20 1.2 0.8 20 1 3/4 2 12 12 REC-CH-1 48

45 REC-WATER COOLER 12 12 2 3/4 1 20 0.7 0.8 20 1 3/4 2 12 12 REC-TLT,SOILED, CLEAN... 46 43 REC-VF 1 1A081 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-VEST/CORR/ELEC... 44

41 SPARE 1 20 0.0 0.0 20 1 SPARE 42

39 SPARE 1 20 0.0 0.0 20 1 SPARE 40

37 SPARE 1 20 0.0 0.0 20 1 SPARE 38

35 SPARE 1 20 0.0 0.0 20 1 SPARE 36

33 SPARE 1 20 0.0 0.0 20 1 SPARE 34

31 SPARE 1 20 0.0 0.0 20 1 SPARE 32

29 SPARE 1 20 0.0 0.0 20 1 SPARE 30

27 REC-EX 12 1A068 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 12 1A068 28

25 REC-EX 11 1A072 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 11 1A072 26

23 REC-EX 10 1A074 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 10 1A074 24

21 REC-EX 9 1A076 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 9 1A076 22

19 REC-EX 8 1A077 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-EX 8 1A077 20

17 REC-EX 7 1A084 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 7 1A084 18

15 REC-EX 6 1A086 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 6 1A086 16

13 REC-EX 5 1A088 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 5 1A088 14

11 REC-EX 4 1A097 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-EX 4 1A097 12

9 REC EX 3 1A095 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 3 1A095 10

7 REC-EX 2 1A093 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 2 1A093 8

5 REC-EX 1 1A094 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 1 1A094 6

3 REC-WAITING 1A101 12 12 2 3/4 1 20 1.0 0.6 20 1 3/4 2 12 12 REC-EYEGLASS FIT D&D... 4 1 REC-MECH 1A092 12 12 2 3/4 1 20 0.4 0.6 20 1 3/4 2 12 12 REC-EYEGLASS FIT D&D... 2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1 Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: MLDP Phases: 3 Mains Type: MCB Location: ELEC 1A108 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: LDP2

1. PROVIDE GFCI CIRCUIT BREAKER.

Notes:

Total Est. Demand: 83 A Receptacle (Equipment) 1400 VA 100.00% 1400 VA Total Conn.: 126 A MISCELLANEOUS 3000 VA 100.00% 3000 VA Total Est. Demand: 29895 VA Receptacle 40740 VA 62.27% 25370 VA Total Conn. Load: 45240 VA Lighting 100 VA 125.00% 125 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

135 A 139 A 110 A Total Load: 15.8 kVA 16.3 kVA 13.2 kVA

PHASE A PHASE B PHASE C

83 SPARE 1 20 0.0 0.0 20 1 SPARE 84

81 SPARE 1 20 0.0 0.0 20 1 SPARE 82

79 SPARE 1 20 0.0 0.0 20 1 SPARE 80

77 SPARE 1 20 0.0 0.0 20 1 SPARE 78

75 SPARE 1 20 0.0 1.2 20 1 3/4 2 12 12 REC - EXTERIOR 76

73 REC-LOCKER 1A056A 12 12 2 3/4 1 20 0.6 1.0 20 1 3/4 2 12 12 REC-COFFEE-LOCKER 1A056A 74

71 REC-VF 1 1A047 12 12 2 3/4 1 20 0.4 1.0 20 1 3/4 2 12 12 REC-VF 1 1A047 72

69 REC-WAITING 1A011 12 12 2 3/4 1 20 0.8 0.2 20 1 3/4 2 12 12 REC-EQPT ALC 1A031 70 67 REC-NURSE WKRM 1A026 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-NURSE WKRM 1A026 68 65 REC-SHARED OFF 1A062 12 12 2 3/4 1 20 0.8 0.8 20 1 3/4 2 12 12 REC-SHARED OFF 1A062 66 63 REC-SHARED OFF 1A058 12 12 2 3/4 1 20 0.8 0.8 20 1 3/4 2 12 12 REC-SHARED OFF 1A058 64 61 REC-SHARED OFF 1A054 12 12 2 3/4 1 20 1.0 0.6 20 1 3/4 2 12 12 REC-SHARED OFF 1A054 62 59 REC-OPTH CHIEF 1A052 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-OPTH CHIEF 1A052 60 57 REC-CONFERENCE 1A059 12 12 2 3/4 1 20 1.2 0.8 20 1 3/4 2 12 12 REC-RECEPTION 1A006 58 55 REC-LOW VIS 1A064 12 12 2 3/4 1 20 1.0 0.6 20 1 3/4 2 12 12 REC-CONFERENCE 1A059 56

53 REC-TLT... 12 12 2 3/4 1 20 0.8 1.0 20 1 3/4 2 12 12 REC-LOW VIS 1A064 54

51 REC - WATER COOLER 1 12 12 2 3/4 1 20 1.4 1.2 20 1 3/4 2 12 12 REC-VEST/CORR... 52 49 REC-YAG LSR 1A049 12 12 2 3/4 1 20 0.8 0.8 20 1 3/4 2 12 12 REC-YAG LSR 1A049 50

47 REC-PHOTO 1A045 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-PHOTO 1A045 48

45 REC-LOUNGE 1A056 12 12 2 3/4 1 20 0.4 2.0 20 1 3/4 2 12 12 REC-COOR/HAC 1A040,1A041 46 43 REC-MICRO-LOCKER 1A056A 12 12 2 3/4 1 20 1.0 1.0 20 1 3/4 2 12 12 REC-REF-LOCKER 1A056A 44

41 SPARE 1 20 0.0 0.0 20 1 SPARE 42

39 SPARE 1 20 0.0 0.0 20 1 SPARE 40

37 SPARE 1 20 0.0 0.0 20 1 SPARE 38

35 SPARE 1 20 0.0 0.0 20 1 SPARE 36

33 SPARE 1 20 0.0 0.0 20 1 SPARE 34

31 SPARE 1 20 0.0 0.0 20 1 SPARE 32

29 SPARE 1 20 0.0 0.0 20 1 SPARE 30

27 EXT. LIGHTING CONTROLS 12 12 2 3/4 1 20 0.1 0.0 20 1 SPARE 28

25 REC-OCT 1 1A029 12 12 2 3/4 1 20 0.4 1.0 20 1 3/4 2 12 12 REC-OCT 2 1A027 26

23 REC-EX 10 1A048 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-EX 10 1A048 24

21 REC-EX 9 1A046 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-EX 9 1A046 22

19 REC-EX 8 1A044 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-EX 8 1A044 20

17 REC-EX 7 1A042 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-EX 7 1A042 18

15 REC-EX 6 1A043 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-EX 6 1A043 16

13 REC-EX 5 1A023 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 5 1A023 14

11 REC-EX 4 1A025 12 12 2 3/4 1 20 0.6 0.8 20 1 3/4 2 12 12 REC-EX 4 1A025 12

9 REC-EX 3 1A028 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-EX 3 1A028 10

7 REC-PRE OP EX2 1A032 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-PRE OP EX2 1A032 8 5 REC-PRE OP EX1 1A034 12 12 2 3/4 1 20 0.8 0.6 20 1 3/4 2 12 12 REC-PRE OP EX1 1A034 6 3 REC-PROCEDURE 1A022 12 12 2 3/4 1 20 0.6 0.6 20 1 3/4 2 12 12 REC-PROCEDURE 1A022 4

1 REC-ELEC 1A024 12 12 2 3/4 1 20 0.2 0.2 20 1 3/4 2 12 12 REC-ELEC 1A024 2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1 Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: MLDP Phases: 3 Mains Type: MLO Location: ELEC 1A024 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: LDP1

1. PROVIDE WITH EQUIPMENT GROUND BUS.

2. SEE RISER DIAGRAM FOR WIRE AND CONDUIT SIZING.

Notes:

Receptacle (Equipment) 15000 VA 100.00% 15000 VA

MISCELLANEOUS 13000 VA 100.00% 13000 VA

Receptacle 88740 VA 55.63% 49370 VA Power 10100 VA 100.00% 10100 VA Total Est. Demand: 306 A Lighting 340 VA 125.00% 425 VA Total Conn.: 354 A Heating 200 VA 100.00% 200 VA Total Est. Demand: 254626 VA HVAC 148131 VA 100.00% 148131 VA Total Conn. Load: 293911 VA Equipment 18400 VA 100.00% 18400 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

366 A 368 A 335 A Total Load: 100.2 kVA 100.8 kVA 92.9 kVA

PHASE A PHASE B PHASE C

29 SPACE ONLY -- -- 0.0 0.2 30

27 SPACE ONLY -- -- 0.0 0.2 28

25 SPACE ONLY -- -- 0.0 0.2

60 3 1 3 4 10 TVSS

23 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 24

21 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 22

19 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 20

17 25.7 0.0 -- -- SPACE ONLY 18

15 25.7 0.0 -- -- SPACE ONLY 16

RTU-1 ELECTRIC HEAT 6 1 3 2 3 125

25.7 0.0 -- -- SPACE ONLY 14

11 12.0 0.0 -- -- SPACE ONLY 12

9 12.0 0.0 -- -- SPACE ONLY 10

RTU-1 FANS 8 4 3 1 3 70

12.0 0.0 -- -- SPACE ONLY 8

5 46.5 8.6 6 3 54.3 8.6 4

XFMR MLDP 2 3 200

53.7 8.6

40 3 2 PPS-1

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 600 A

Supply From: Phases: 3 Mains Type: MLO Location: ELEC 1A024 Volts: 480/277 Wye A.I.C. Rating: 42,000

Branch Panel: MDP1

1. PROVIDE WITH EQUIPMENT GROUND BUS.

2. SEE RISER DIAGRAM FOR WIRE SIZING.

Notes:

Receptacle (Equipment) 15000 VA 100.00% 15000 VA

MISCELLANEOUS 12500 VA 100.00% 12500 VA

Receptacle 88740 VA 55.63% 49370 VA Power 10100 VA 100.00% 10100 VA Total Est. Demand: 320 A Lighting 340 VA 125.00% 425 VA Total Conn.: 429 A Heating 200 VA 100.00% 200 VA Total Est. Demand: 115185 VA HVAC 9190 VA 100.00% 9190 VA Total Conn. Load: 154470 VA Equipment 18400 VA 100.00% 18400 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

457 A 462 A 387 A Total Load: 53.7 kVA 54.3 kVA 46.5 kVA

PHASE A PHASE B PHASE C

29 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 30

27 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 28

25 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 26

23 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 24

21 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 22

19 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 20

17 3.6 2.7 18 15 3.5 4.3 16

COMM1 2 3 100

3.9 4.7

100 3 2 COMM2

11 4.3 9.6 12 9 5.1 8.6 10

LDP3 2 3 225

6.1 7.7

225 3 2 LDP4

5 13.2 13.1 6 3 16.3 16.6 4

LDP1 2 3 225

15.8 15.6

225 3 2 LDP2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1 Mounting: Surface Wires: 4 Mains Rating: 500 A

Supply From: XFMR MLDP Phases: 3 Mains Type: MCB Location: ELEC 1A024 Volts: 120/208 Wye A.I.C. Rating: 25,000

Branch Panel: MLDP

1. PROVIDE WITH EQUIPMENT GROUND BUS.

2. SEE RISER DIAGRAM FOR WIRE AND CONDUIT SIZING.

Notes:

Total Est. Demand: 394 A Total Conn.: 391 A

MISCELLANEOUS 500 VA 100.00% 500 VA Total Est. Demand: 327599 VA Lighting 11498 VA 125.00% 14372 VA Total Conn. Load: 324751 VA

HVAC 312862 VA 100.00% 312862 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

403 A 395 A 379 A Total Load: 111.2 kVA 108.7 kVA 104.9 kVA

PHASE A PHASE B PHASE C

29 SPACE ONLY -- -- 0.0 0.2 30

27 SPACE ONLY -- -- 0.0 0.2 28

25 SPACE ONLY -- -- 0.0 0.2

60 3 1 3 4 10 TVSS

23 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 24

21 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 22

19 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 20

17 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 18

15 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 16

13 SPACE ONLY -- -- 0.0 0.0 -- -- SPACE ONLY 14

11 25.7 32.8 12 9 25.7 32.8 10

RTU-2 ELECTRIC HEAT 6 1 3 2 3 125

25.7 32.8

175 3 2 3 2/0 6 CH-1

5 34.2 12.0 6 3 38.1 12.0 4

PANEL 'H1' 2 3 225

40.5 12.0

70 3 1 3 4 8 RTU-2 FANS

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: Type 1 Mounting: Surface Wires: 4 Mains Rating: 600 A

Supply From: Phases: 3 Mains Type: MLO Location: ELEC 1A024 Volts: 480/277 Wye A.I.C. Rating: 42,000

Branch Panel: MDP2

LDP3

COMM2COMM1

LDP4--

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

D :\L oc al

R ev it M od el s\

\3

2\

.0 1-

C E

C en tra l M od el

.rv t

8/

/2

:5 7:

A

M

E006

ELECTRICAL - PANEL SCHEDULES

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212

(704) 531-3000 Michael Eaves

HDR, INC

440 South Church Street, Suite 1000 Charlotte, NC 28202

(704) 338-6844 Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

08/18/2022 JCE JL

Notes:

Total Est. Demand: 32 A Total Conn.: 32 A

Total Est. Demand: 11600 VA Receptacle (Equipment) 8000 VA 100.00% 8000 VA Total Conn. Load: 11600 VA Receptacle 3600 VA 100.00% 3600 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

41 A 38 A 22 A Total Load: 4.7 kVA 4.3 kVA 2.7 kVA

PHASE A PHASE B PHASE C

29 SPARE 1 20 0.0 0.0 20 1 SPARE 30

27 SPARE 1 20 0.0 0.0 20 1 SPARE 28

25 SPARE 1 20 0.0 0.0 20 1 SPARE 26

23 SPARE 1 20 0.0 0.0 20 1 SPARE 24

21 SPARE 1 20 0.0 0.0 20 1 SPARE 22

19 SPARE 1 20 0.0 0.0 20 1 SPARE 20

17 SPARE 1 20 0.0 0.0 20 1 SPARE 18

15 SPARE 1 20 0.0 0.0 20 1 SPARE 16

13 SPARE 1 20 0.0 0.0 20 1 SPARE 14

11 SPARE 1 20 0.0 0.0 20 1 SPARE 12

9 REC-COMM 1A102 12 12 2 3/4 1 20 0.8 0.8 20 1 3/4 2 12 12 REC-COMM 1A102 10

7 REC-COMM 1A102 12 12 2 3/4 1 20 1.2 0.8 20 1 3/4 2 12 12 REC-COMM 1A102 8

5 1.3 1.3 6 3 1.3 1.3 4

REC - RACK A 10 10 4 3/4 3 30

1.3 1.3

30 3 3/4 4 10 10 REC - RACK B

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1 Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: MLDP Phases: 3 Mains Type: MCB Location: COMM 1A102 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: COMM2

Notes:

Total Est. Demand: 30 A Receptacle (Equipment) 5600 VA 100.00% 5600 VA Total Conn.: 30 A MISCELLANEOUS 1200 VA 100.00% 1200 VA Total Est. Demand: 10900 VA Receptacle 3600 VA 100.00% 3600 VA Total Conn. Load: 10900 VA Power 500 VA 100.00% 500 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

32 A 29 A 30 A Total Load: 3.9 kVA 3.5 kVA 3.6 kVA

PHASE A PHASE B PHASE C

29 SPARE 1 20 0.0 0.0 20 1 SPARE 30

27 SPARE 1 20 0.0 0.0 20 1 SPARE 28

25 SPARE 1 20 0.0 0.0 20 1 SPARE 26

23 SPARE 1 20 0.0 0.0 20 1 SPARE 24

21 SPARE 1 20 0.0 0.0 20 1 SPARE 22

19 SPARE 1 20 0.0 0.0 20 1 SPARE 20

17 SPARE 1 20 0.0 0.0 20 1 SPARE 18

15 SPARE 1 20 0.0 0.0 20 1 SPARE 16

13 SPARE 1 20 0.0 0.0 20 1 SPARE 14

11 NURSE CALL HEADEND 12 12 2 3/4 1 20 1.2 0.5 20 1 3/4 2 12 12 PUBLIC ADDRESS AMPLIFIER 12

9 REC - COMM 1A016 12 12 2 3/4 1 20 0.8 0.8 20 1 3/4 2 12 12 REC - COMM 1A016 10

7 REC - COMM 1A016 12 12 2 3/4 1 20 0.8 1.2 20 1 3/4 2 12 12 REC - COMM 1A016 8

5 0.9 0.9 6 3 0.9 0.9 4

REC - RACK A 10 10 4 3/4 3 20

0.9 0.9

20 3 3/4 4 10 10 REC - RACK B

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1 Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: MLDP Phases: 3 Mains Type: MCB Location: COMM 1A016 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: COMM1

Notes:

Total Est. Demand: 72 A MISCELLANEOUS 1200 VA 100.00% 1200 VA Total Conn.: 72 A Power 2200 VA 100.00% 2200 VA Total Est. Demand: 25895 VA HVAC 4495 VA 100.00% 4495 VA Total Conn. Load: 25895 VA Equipment 18000 VA 100.00% 18000 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

64 A 73 A 81 A Total Load: 7.7 kVA 8.6 kVA 9.6 kVA

PHASE A PHASE B PHASE C

41 SPARE 1 20 0.0 0.0 20 1 SPARE 42

39 SPARE 1 20 0.0 0.0 20 1 SPARE 40

37 SPARE 1 20 0.0 0.0 20 1 SPARE 38

35 SPARE 1 20 0.0 0.0 20 1 SPARE 36

33 SPARE 1 20 0.0 0.0 20 1 SPARE 34

31 SPARE 1 20 0.0 0.0 20 1 SPARE 32

29 SPARE 1 20 0.0 0.0 20 1 SPARE 30

27 SPARE 1 20 0.0 0.0 20 1 SPARE 28

25 SPARE 1 20 0.0 0.0 20 1 SPARE 26

23 SPARE 1 20 0.0 0.0 20 1 SPARE 24

21 SPARE 1 20 0.0 0.0 20 1 SPARE 22

19 SPARE 1 20 0.0 0.0 20 1 SPARE 20

17 SPARE 1 20 0.0 0.0 20 1 SPARE 18

15 JCT - RTU-1 CONTROLS 12 12 2 3/4 1 20 0.2 0.5 20 1 3/4 2 12 12 JB-PASS THRU - CLEAN 1A069 16

13 DOOR CONTROLS 12 12 2 3/4 1 20 0.2 4.5 14

11 4.5 4.5

60 2 1 2 4 10 EWH-2-MECH 1A092

EWH-1-MECH 1A092 10 4 2 1 2 60

4.5 1.5 10

7 DOOR CONTROLS 12 12 2 3/4 1 20 0.8 1.5

30 2 3/4 2 10 10 CU-1

5 SECURITY BLUE LIGHT 12 12 2 3/4 1 20 0.4 0.2 20 1 3/4 2 12 12 JCT - RTU-2 CONTROLS 6

3 DOOR CONTROLS 12 12 2 3/4 1 20 0.4 1.5 20 1 3/4 2 12 12 EH-1 4

1 DOOR CONTROLS 12 12 2 3/4 1 20 0.2 0.5 20 1 3/4 2 12 12 JCT - BAS PANEL 2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1 Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: MLDP Phases: 3 Mains Type: MCB Location: ELEC 1A108 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: LDP4

1. DEDUCT ALTERNATE #11: REMOVE ELECTRIC VEHICLE CHARGING STATIONS

Notes:

Total Est. Demand: 43 A MISCELLANEOUS 2200 VA 100.00% 2200 VA Total Conn.: 43 A Receptacle 4800 VA 100.00% 4800 VA Total Est. Demand: 15495 VA Power 3800 VA 100.00% 3800 VA Total Conn. Load: 15495 VA

HVAC 4695 VA 100.00% 4695 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

52 A 44 A 36 A Total Load: 6.1 kVA 5.1 kVA 4.3 kVA

PHASE A PHASE B PHASE C

41 SPARE 1 20 0.0 0.0 20 1 SPARE 42

39 SPARE 1 20 0.0 0.0 20 1 SPARE 40

37 SPARE 1 20 0.0 0.0 20 1 SPARE 38

35 SPARE 1 20 0.0 0.0 20 1 SPARE 36

33 SPARE 1 20 0.0 0.0 20 1 SPARE 34

31 SPARE 1 20 0.0 0.0 20 1 SPARE 32

29 SPARE 1 20 0.0 0.0 20 1 SPARE 30

27 SPARE 1 20 0.0 0.0 20 1 SPARE 28

25 SPARE 1 20 0.0 0.0 20 1 SPARE 26

23 SPARE 1 20 0.0 1.5 24

21 EV-CHARGING STATION 1 12 12 2 3/4 1 20 1.0 1.5

30 2 3/4 2 10 10 CU-2

19 EV-CHARGING STATION 1 12 12 2 3/4 1 20 1.0 1.5 20 1 3/4 2 12 12 EH-2 20

17 REC - ROOFTOP 12 12 2 3/4 1 20 0.4 0.2 20 1 3/4 2 12 12 DOOR CONTROLS 18

15 JB - VAV CONTROLS 12 12 2 3/4 1 20 0.2 0.2 20 1 3/4 2 12 12 WRNG LGT CNTLR - RM 1A049 16

13 DOOR CONTROLS 12 12 2 3/4 1 20 0.6 0.2 20 1 3/4 2 12 12 DOOR CONTROLS 14

11 DOOR CONTROLS 12 12 2 3/4 1 20 0.2 1.0 20 1 3/4 2 12 12 VEST 1A001 DOOR MOTOR 12 9 PROJECTION SCRN - CONF... 12 12 2 3/4 1 20 0.2 0.2 20 1 3/4 2 12 12 DOOR CONTROLS 10 7 REC-MED PREP 1A067 12 12 2 3/4 1 20 0.4 0.4 20 1 3/4 2 12 12 REC-MED PREP 1A067 8

5 REC-BROS 1A002 12 12 2 3/4 1 20 0.8 0.2 20 1 3/4 2 12 12 REC-MED PREP 1A067 6

3 REC-BROS 1A002 12 12 2 3/4 1 20 0.8 1.0 20 1 3/4 2 12 12 REC-VIST 1A004 4

1 REC-RECEPTION 1A006 12 12 2 3/4 1 20 0.8 1.2 20 1 3/4 2 12 12 REC-COPY 1A006A 2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1 Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: MLDP Phases: 3 Mains Type: MLO Location: ELEC 1A024 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: LDP3

NEUTRAL BUS

GROUND BUS

PROVIDE BONDING JUMPER FOR

SERVICE EQUIPMENT (TYPICAL)

TRANSFORMER

(TYPICAL)

PANEL

(TYPICAL)

LIGHTING

PANEL

(TYPICAL)

DOUBLE

PANEL

(TYPICAL)

GROUNDING BUS

NEUTRAL BUS

TO TYPICAL

BRANCH

CIRCUIT

TO TYPICAL

BRANCH

CIRCUIT

TO TYPICAL

BRANCH

CIRCUIT

#3/0 MIN.

'MDP1' MAIN PANELBOARD

#3/0 MIN.

GROUND ROD

ACCESS

(TEST WELL)

#3/0 UNLESS

NOTED OTHERWISE

3/4" DIA. x 10'-0" COPPER GROUND ROD, QUANTITY OF RODS AS REQUIRED TO

MEET SPECIFICATIONS (25 OHMS OR

LESS)

AIR TERMINAL "LIGHTING

ROD" ROOF (TYPICAL)

DOWN LEAD CONDUCTOR TYP.

LIGHTING PROTECTION

GROUND ROD (TYPICAL)

'-0

10'-0"

10'-0"

METAL WATER PIPE CONNECT

TO STREET SIDE OF METER

#3/0 MIN.

MAIN ELECTRICAL

ROOM WALL

MOUNTED COPPER

EQUIPMENT GROUND

BUS BAR MGB

#3/0 MIN.

#6 MIN.

(FIRST FLOOR)

TELECOMMUNICATIONS ROOM (TR)

1A012 WALL MOUNTED TMGB. SEE

DETAIL.

TO FIRE

ALARM

SYSTEM

GROUNDING

TO

TELEPHONE

SYSTEM

GROUNDING

TO A/V

SYSTEM

GROUNDING

#6 COPPER BONDING

CONDUCTOR (TYPICAL)

TYPICAL

EQUIPMENT

BONDED TO

GROUND BAR

EQUIPMENT

RACKS

CABLE TRAY

BASKET (TYP)

PANELS SERVING

TELECOMM ROOMS

BUILDING

STEEL

ALL TELECOMM

SLEEVES AND

RACEWAYS

3/4" x 10' GROUND ROD

REFER TO RISER

DIAGRAM FOR SIZE OF

GROUND CONDUCTOR

6" DIA. PVC CDT.

CRUSHED STONE FILL

WELDED GROUND

CONNECTION

6" PVC CDT.

COUPLING.

6" DIA. THREADED PVC PLUG FINISHED GRADE

TOP OF GROUND

ROD SHALL BE 6"

MIN. BELOW

FINISHED GRADE

GROUND CONDUCTOR TEST WELL DETAIL

NOT TO SCALE

#6 COPPER BONDING

CONDUCTOR (TYPICAL)

TYPICAL

EQUIPMENT

BONDED TO

GROUND BAR

EQUIPMENT

RACKS

CABLE TRAY

BASKET (TYP)

PANELS SERVING

TELECOMM ROOMS

BUILDING

STEEL

ALL TELECOMM

SLEEVES AND

RACEWAYS

TO FIRE

ALARM

SYSTEM

GROUNDING

TO

TELEPHONE

SYSTEM

GROUNDING

TO A/V

SYSTEM

GROUNDING

#6 MIN.

(FIRST FLOOR)

TELECOMMUNICATIONS ROOM (TR)

WALL MOUNTED TGB. SEE DETAIL.

NEUTRAL BUS

GROUND BUS

'MDP2' MAIN PANELBOARD

LIGHTING

PANEL

(TYPICAL)

DOUBLE

PANEL

(TYPICAL)

TO TYPICAL

BRANCH

CIRCUIT

TO TYPICAL

BRANCH

CIRCUIT

FROM UTILITY COMPANY

PAD MOUNTED

TRANSFORMER

TELECOMMUNICATIONS MAIN GROUNDING BUSBAR, TMGB 7

TELECOMMUNICATIONS GROUNDING BUSBAR, TGB 9NTS

#3/0 MIN.

#3/0 MIN.

SERVICE DISCONNECT 1 SERVICE DISCONNECT 2

MAIN GROUNDING ELECTRODE

G

N

TO MDP1

G

N

TO MDP2

PROVIDE BONDING JUMPER FOR

SERVICE EQUIPMENT (TYPICAL)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

C U s e rs \j e d w a rd s .C

H A

R E

N G

\D o c u m e n ts \R e v it

\3

.0

-C

E C e n tr a l M o d e l.

rv t

/1

/2

:3

:2

P

M

E007

ELECTRICAL - GROUNDING RISER

DIAGRAM AND DETAILSCharlotte Engineers, LLP

5838 Monroe Road

Charlotte, NC 28212

(704) 531-3000

Michael Eaves

HDR, INC

440 South Church Street, Suite 1000

Charlotte, NC 28202

(704) 338-6844

Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

08/18/2022 Checker Author

NOT TO SCALE

ELECTRICAL - GROUNDING RISER DIAGRAM

S S S

OS

OS OS

DLDL DL

TC

LC

S S

S S

S S

S

S

SSSSS

S S S S S

S

SS

S S

S

SSS

S S S

THE DRAWINGS SHALL NOT BE SCALED FOR

CONSTRUCTION PURPOSES. THE SCALE, WHEN

INDICATED, IS INTENDED FOR GENERAL REFERENCE ONLY.

COORDINATE INTERIOR AND EXTERIOR LIGHT LOCATIONS

WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.

EXIT SIGNS EMERGENCY LIGHT BATTERIES TO BE

CONNECTED TO POWER CIRCUIT AHEAD OF ANY CONTROL

SWITCHES.

GENERAL NOTES

A.

B.

C.

ROUTE CIRCUIT THROUGH TIMECLOCK AND PHOTOCELL.

PHOTOCELL "ON". TIMECLOCK "OFF".

SEE DETAIL 4/EP100 FOR ADDITIONAL INFORMATION.

DEDUCT ALTERNATE #4: REMOVE EYE BROW CANOPY.

REMOVE CANOPY MOUNTED LIGHTING. PROVIDE AND

INSTALL WALL MOUNTED WPE FIXTURE ABOVE DOOR FOR

EMERGENCY EGRESS ILLUMINATION.

LUMINAIRE SHALL BE UNSWITCHED.

NEW WORK KEYED NOTES

1 HOUR FIRE BARRIER in accordance with NFPA 101 Section 8.3 Fire Barrier

WALL RATING LEGEND

SMOKE BARRIER in accordance with NFPA 101 Section 8.5 Smoke Barrier

E

A

D

D.6

B

7 8 10 11 12654321 6.3 6.6

CONFERENCE

1A059

OPHTH CHIEF

1A052

YAG LSR

1A049

PRE-OP EX 2

1A032

PRE-OP EX 1

1A034

EX 4

1A025

PHOTO

1A045

EX 7

1A042

EX 5

1A088

EX 6

1A086

EX 7

1A084

EX 8

1A077

EX 3

1A095

EX 4

1A097

TLT

1A112

TLT

1A106

RME DROP-OFF

1A073

LOW VIS

1A064

RECE…