Attachment 19 - 2023-09-29 544-329 BID DRAWINGS_Part6.pdf

PDF 20 MB Posted

Attached to
Y1DZ--VHA MINOR CONSTRUCTION Solicitation CANCELLED Project 544-329 Construct Eye Clinic Center Minor Construction Columbia, SC VAMC
Solicitation number
36C77624R0028
Issued by

About this file

This document appears to be Attachment 19 - 2023-09-29 544-329 BID DRAWINGS_Part6.pdf, which contains bid drawings related to a federal contract opportunity from the Department of Veterans Affairs Technology Acquisition Center Austin.

The federal contract opportunity is for a project to construct a new, 15,000 gross square foot optometric facility at the William Jennings Bryan Dorn VA Medical Center in Columbia, SC. The project will include new construction, HVAC, utility work, interior finishes, utility coordination, site work, underground storm water detention, asbestos and lead survey and abatement, and communication utility work inside an active hospital. The solicitation number is 36C77624R0028, and the opportunity type is a Solicitation.

View the file

Other files

File Type Posted
36C77624R0028 0007 - Signed.pdf PDF
36C77624R0028 0006 - Signed.pdf PDF
36C77624R0028 0005 - Signed.pdf PDF
Technical Questions Tracking Spreadsheet - 9-3-24- 36C77624R0028 - Construct Eye Clinic Columbia SC.docx DOCX document
RoomFinishes.pdf PDF
2024-08-29 544-329 BID DRAWING REVISIONS.pdf PDF
South Carolina Tax Language - 04.04.2024 - FINAL.docx DOCX document
01 00 00 General Requirements_rev 2_8.29.24.pdf PDF
36C77624R0028 0004 - Signed.pdf PDF
09 91 00 Painting_Rev 1 8.30.24.docx DOCX document
544 329 SOW 100_rev2.pdf PDF
00 01 10 Table of Contents_Rev 1 8.30.24.docx DOCX document
Attachment 6 - 544-329 Eye Clinic CD Specs 8.19.24.pdf PDF
SIGN IN SHEET Site Visit 8.15.24.pdf PDF
Amendment 0003 - 36C77624R0028 - Construct Eye Clinic - Columbia SC 8.19.24 - Signed.pdf PDF
Solicitation - 36C77624R0028 - Construct Eye Clinic - Columbia SC 8.19.24.pdf PDF
Attachment 7 - 544-329 Equipment Cut Sheets Part 1.pdf PDF
Attachment 24 - Richland County Wage Rates 6.14.24.pdf PDF
Attachment 9 - 544-329 Equipment Cut Sheets Part 3.pdf PDF
Attachment 28 - Division Cost Breakdown - 5-29-24.xlsx XLSX spreadsheet
Attachment 22 - Site Visit Dorn VAMC Google Map.jpg JPG image
Attachment 20 - 2023-09-29 544-329 BID DRAWINGS_Part7.pdf PDF
Attachment 18 - 2023-09-29 544-329 BID DRAWINGS_Part5.pdf PDF
Attachment 17 - 2023-09-29 544-329 BID DRAWINGS_Part4.pdf PDF
Attachment 3 - 544 329 VAMC Columbia SC Asbestos Inspection columbia part 1.pdf PDF
Attachment 26 - 544 329 SOW 100_rev1.pdf PDF
Attachment 5 - 544 329 VAMC Columbia SC Asbestos Inspection Report All Buildi.pdf PDF
Attachment 6 - 544-329 Eye Clinic CD Specs_120823.pdf PDF
Attachment 10 - 544-329 Equipment Cut Sheets Part 4.pdf PDF
Solicitation - 36C77624R0028 - Construct Eye Clinic - Columbia SC 8-8-24.pdf PDF
Attachment 12 - 544-329 Equipment Cut Sheets Part 6.pdf PDF
Attachment 23 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 11 - 544-329 Equipment Cut Sheets Part 5.pdf PDF
Attachment 27 - 544 329 Brand Name J and A.pdf PDF
Attachment 2 - 544 329 Eye Clinic Equipment List.xlsx XLSX spreadsheet
Attachment 8 - 544-329 Equipment Cut Sheets Part 2.pdf PDF
Attachment 1 - 544 329 Eye Clinic ConstructionAssessmentPackage 100 Percent.pdf PDF
Attachment 21 - Site Visit Dorn VAMC Campus Map_B101 and Contractor Parking.pdf PDF
Attachment 14 - 2023-09-29 544-329 BID DRAWINGS_Part1.pdf PDF
Attachment 25 - VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 6-2024.docx DOCX document
Attachment 16 - 2023-09-29 544-329 BID DRAWINGS_Part3.pdf PDF
Attachment 4 - 544 329 VAMC Columbia SC Asbestos Inspection columbia part 2.pdf PDF
Attachment 15 - 2023-09-29 544-329 BID DRAWINGS_Part2.pdf PDF
Attachment 13 - 544-329 Geotech Report.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROOFTOP UNIT ROOF CURB (DOWN FLOW

DISCHARGE)

ROOFTOP UNIT

FLASHING &

COUNTER

FLASHING BY MC.

DUCT OPENING

DISCONNECT

BY EC.

COORDINATE

LOCATION

FLEXIBLE CONDUIT

BY EC.

ROOFING BY

OTHERS

NOTES:

1. ROOF CURB SHALL BE A MINIMUM HEIGHT OF 14".

2. GENERAL CONTRACTOR SHALL COORDINATE LOCATIONS OF ROOF

PENETRATIONS WITH STRUCTURE.

3. MECHANICAL CONTRACTOR SHALL PROVIDE TREATED LUMBER,

CUSTOM TRIMMED TO LEVEL THE ROOF CURB. MECHANICAL

CONTRACTOR SHALL COORDINATE WORK WITH GENERAL

CONTRACTOR.

4. SEAL ALL ROOF PENETRATIONS LOCATED BELOW THE RTU, WITHIN

THE ROOF CURB, WITH SOUND DEADENING TAPE.

MISC. STEEL

SUPPORT BY GC.

ROOF OPENINGS

SUPPLY AND

RETURN DUCT

W/FLEX

CONNECTOR

ROOFTOP UNIT

DUCT MOUNTED

SMOKE DETECTOR,

SIX EQUIVALENT

DUCT DIAMETERS

FROM ELBOW

CEILING

RETURN

DUCT

SUPPLY DUCT

ROOF TOP UNIT

FLEXIBLE

DUCT

CONNECTION

TYP.

ROOF

ROOF CURB

PROVIDED BY

RTU

MANUFACTURER.

NTS

NOTES:

1. PIPE CONDENSATE DRAIN AS SHOWN ON MH100A AND MH100B.

SUPPORT DRAIN ON TREATED WOOD BLOCKS EVERY FOUR FEET.

NTS

PIPING THRU CURBED ROOF OPENING

INSULATED INSIDE

OF COVER WITH

3/4" ARMAFLEX

SUBMIT COMPLETE

SHOP DRAWINGS

ON CURB ASSEMBLY

INSULATED PIPING

WITH ALUMINUM

JACKET

FURNISH AND INSTALL A PORTALS PLUS PIPE PORTAL

AS MANUFACTURED BY PORTALS PLUS FOR PIPE

PENETRATION THRU ROOF. SYSTEM SHALL INCLUDE A

8"H PREFAB CURB WITH CURB COVER WITH

PRE-PUNCHED MOUNTING HOLES AND MOLDED

SEALING RINGS ON A COLLARED OPENING.

COMPRESSION MOLDED CAP SHALL BE EPDM WITH

STAINLESS STEEL CLAMPS.

INSULATION

ROOF STRUCTURE

ROOF CURB

PROVIDED BY RTU

MANUFACTURER.

20 19 17 16 15 14 13 12 11 9 8

2 1

5 4 3 6

R.A.S.A.

20 19 18 17 16 14 13 11 10 75 4 3 6

PIPING

CABINET

M

M

M

M

E.A.

M

R.A.

O.A.

FAN

EXHAUST

FAN

SUPPLY

PLAN VIEW

NTS

RTU SCHEMATICS

NTS

SIDE VIEW

F RATING = 2 AND 3 HR.

T RATING = 0-HR.

SYSTEM NO. C-AJ-1421

TOP VIEW SECTION A-A

1. FLOOR OR WALL ASSEMBLY -- MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. FLOOR MAY ALSO BE CONSTRUCTED OF ANY MIN 6 IN. THICK UL CLASSIFIED HOLLOW-CORE

PRECAST CONCRETE UNITS*.

SEE CONCRETE BLOCKS (CAZT) CATEGORIES IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.

2. METALLIC SLEEVE - (OPTIONAL) NOM. 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL SLEEVE CAST OR

GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES.

3. THROUGH-PENETRANT - ONE METALLIC PIPE OR CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY

WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, TUBE OR CONDUIT AND PERIPHERY OF OPENING SHALL BE 0 IN. (0MM) (POINT CONTACT) TO MAX 5-3/8 IN. (137 MM). PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR CONDUITS MAY BE USED:

A. STEEL PIPE - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. COPPER PIPE - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

D. COPPER TUBING - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

E. CONDUIT - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) STEEL CONDUIT.

F. CONDUIT - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT).

4. FIRESTOP SYSTEM -- THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:

A. PACKING MATERIAL -- MIN 4 IN. (102 MM) THICKNESS OF MIN 4 PCF (64 KG/M3) MINERAL WOOL BATT INSULATION FIRMLY

PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM BOTTOM OR TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.

B. FILL, VOID OR CAVITY MATERIAL* -- MIN 1/2 IN. (13 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTTOM OR TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL . A MIN 1/2 IN. (13 MM) DIAM BEAD OF CAULK

SHALL BE APPLIED AT THE POINT CONTACT LOCATION BETWEEN PIPE AND SLEEVE/CONCRETE.

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS ONE SEALANT

*BEARING THE UL CLASSIFICATION MARK

A

1 4a 4b

22A

UL FLOOR OR WALL ASSEMBLY PENETRATION

NTS

7 1

RTU-1/2 = 477 3/4"

104 1/2"

EXHAUST

DUCT

RTU AND CHILLED WATER PUMPING

PACKAGE ENCLOSURE CURB MOUNTING NTS 3

ROOF DECK

CURB GASKETING

ROOFTOP UNIT

PREFABRICATED

ROOF CURB BY RTU

MANUFACTURER

14" MIN

POS# MODULE

1 AIR MIXING SECTION

2 CUSTOM LENGTH SECTION

3 ACCESS SECTION

4 FILTER SECTION

5 AIR MIXING SECTION

6 EXHAUST FAN SECTION

7 AIR TO AIR HEAT EXCHANGER SECTION

8 AIR MIXING SECTION

9 AIR MIXING SECTION

10 ACCESS SECTION

11 ELECTRIC HEATING COIL SECTION

12 ACCESS SECTION

13 COOLING COIL SECTION

14 ACCESS SECTION

15 SUPPLY FAN SECTION

16 ACCESS SECTION

17 SILENCER

18 ACCESS SECTION

19 FILTER SECTION

20 CONTROLS SECTION

M

M

NOTES:

1. ROOFTOP UNIT DIMENSIONS MAY VERY PER

MANUFACTURER. CONTRACTOR IS RESPONSIBLE

TO MAKE ALL REQUIRED CHANGES AND

COORDINATE UNIT SUPPORT WITH STRUCTURAL

BELOW. VERIFY WITH ENGINEER IN SUBMITTAL

PROCESS PRIOR TO ANY CHANGES.

NTS

RTU PIPING CABINET 4

CHILLED WATER

PIPING ON ROOF

WITH SUPPORT. SEE

DETAIL 12/M002.

RTU PIPING CABINET (TYP. FOR TWO)

HINGED

ACCESS DOOR

PREMANUFACTURED

RTU ROOF CURB

M

OA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

C R

E V

IT

F

IL

E

S \R e v it

\3

.0

-C

E C e n tr a l M o d e l.

rv t

/9

/2

:1

:4

P

M

M002A

MECHANICAL - DETAILS

Charlotte Engineers, LLP

5838 Monroe Road

Charlotte, NC 28212

(704) 531-3000

Michael Eaves

HDR, INC

440 South Church Street, Suite 1000

Charlotte, NC 28202

(704) 338-6844

Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

08/18/2022 GAT CACRevisions: Date:

YES

YES

NO

YES

YES

8570 (4285)

VARIABLE VOLUME

CUSTOM

1ST FLOOR

ROOF

RTU-1

YES

YES

YES

1660/8570

FRONT TOP

YES

MERV 16A

12" CARTRIDGE

(2) 20"x20" AND (4)20"X24"

MERV 8

2" PLEATED

18.89

PLENUM

II

DIRECT

3.5

22.25

56.21

1.067

8.24

PER MANUFACTURER

16.81

CHILLED WATER

394.88

282.79

0.166

ELECTRIC

14.58

92.10

MERV 8

28.89

0.494

II

BACK TOP

YES

DIRECT

PLENUM

16.5

2.0

RTU-2

ROOF

1ST FLOOR

CUSTOM

VARIABLE VOLUME

1660/8570

MERV 8

28.89

0.494

394.88

282.79

79/65

49/48

56.21

1.067

8.24

PER MANUFACTURER

16.81

CHILLED WATER

YES

YES

MERV 16A

12" CARTRIDGE

18.89

YES

YES

NO

YES

YES

YES

8570 (4285)

2.0

16.5

DIRECT

PLENUM

II

BACK TOP

YES

FRONT TOP

YES

PLENUM

II

DIRECT

3.5

22.25

2" CARTRIDGE 2" CARTRIDGE

8570 8570

2 @ 10/460/3Ø/60

20/460/3Ø/60

FAN SIZED FOR

ECONOMIZER

YES YES

UNIT WEIGHT: (LBS)

GENERAL NOTES:

1. INSTALL REFRIGERANT PIPING IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION

RECOMMENDATIONS. INSULATE WITH 1" THICK FLEXIBLE ELASTOMETRIC TYPE OF INSULATION.

PROVIDE PIPING APPURTENANCES AS REQUIRED.

2. UNIT SHALL BE PROVIDED WITH THE FOLLOWING FACTORY INSTALLED ACCESSORIES: (MODEL

NUMBER WILL REFLECT SOME OF THESE ACCESSORIES BUT NOT NECESSARILY ALL)

· AUTO RESTART

· DEHUMIDIFICATION MODE

· CLEANABLE FILTERS

· WALL MOUNTED THERMOSTAT.

· PROVIDE UNIT WITH LOW AMBIENT COOLING.

3.

4.

TYPE REFRIGERANT SHALL BE R-410A

5.

REFER TO SPECIFICATIONS FOR SEQUENCE OF OPERATION FOR SPLIT SYSTEMS.

6.

INDOOR UNIT SHALL BE POWERED FROM OUTDOOR UNIT.

7.

PROVIDE EVAPORATOR UNITS WITH INTEGRAL CONDENSATE PUMP.

INSTALL EVAPORATIVE UNITS HIGH ON WALL AND EXTEND AND TERMINATE EACH OF CONDENSATE DRAINS PER THE DRAWINGS.

HSPF (BTU/H/W)

TOTAL INPUT (W)

TOTAL HEATING CAPACITY (MBH)

COOLING EDb/EWb (°F)

GROSS COOLING CAP (MBH)

TOTAL CFM

UNIT TAG:

SEER

LOCATION

SYSTEM DESCRIPTION

ELECTRICAL CONNECTION (MCA/MOCP)

ELECTRICAL CHARACTERISTICS

CU-2 AC-2

CONDENSING UNIT EVAPORATOR UNIT

DUCTLESS SPLIT SYSTEM

163 46

ROOF

SPLIT SYSTEM

COOLING ONLY

SPLIT SYSTEM

COOLING ONLY

COMM 1A016

CU-1 AC-1

CONDENSING UNIT EVAPORATOR UNIT

DUCTLESS SPLIT SYSTEM

163 46

ROOF

1,940 705

17.0 17.0

80/6795/75

N/A

2,270 2,270

N/A N/A

N/A

208V/1

18/30 SEE NOTE 6

SPLIT SYSTEM

COOLING ONLY

208V/1

SPLIT SYSTEM

COOLING ONLY

COMM 1A102

1,940 705

17.0 17.0

80/6795/75

N/A

2,270 2,270

N/A N/A

N/A

208V/1

18/30 SEE NOTE 6

208V/1∅ ∅

0.166

ELECTRIC

14.58

92.10

MERV8

2" PLEATED

(2) 20"x20" AND (4)20"X24"

79/65

49/48

C O

O L

IN

G C

O

IL

A C

C E

S S

S

U P

P L Y

F A

N F

IN

A

L F

IL

T

E R

E L E

C T

R

IC

H E

A T

P R

E F

IL

T

E R

E X

H A

U S

T F

A N

ROOF TOP AIR HANDLING UNIT SCHEDULE

ROOF TOP AIR HANDLING UNITS RTU-1 & RTU-2 ACOUSTICS IN DECIBELS PER OCTAVE BAND

SPLIT SYSTEM AIR HANDLING UNITS (DUCTLESS)

REFER TO AIR TO AIR PLATE FRAME HEAT EXHANGER SCHEDULE THIS SHEET

REMARKS:

SERVES

WATER PRESSURE DROP (FT WG)

AIR PRESSURE (IN WG)

GPM

WHEEL DIAMETER

FILTER PRESSURE DROP (IN WG)

FILTER AREA (SQUARE FEET)

FILTER MINIMUM EFFICIENCY

FILTER TYPE

REMARKS:

TYPE UNIT

LOCATION

SYSTEM NO.

VFD

REMARKS:

TYPE FAN

REMARKS:

REMARKS:

VSD

REMARKS:

TYPE FAN

SOUND ATTENUATOR

SQ. FT. FACE AREA MIN.

FACE VELOCITY MAX. (fpm)

PREFILTER MIN. EFF.

PREFILTER TYPE

PREFILTER AREA - SQ FT.

FINAL FILTER MIN. EFF.

FINAL FILTER TYPE

FINAL FILTER SIZE & NO.

ACCESS SECTION WITH ACCESS DOOR

SUPPORT BASE

VIBRATION ISOLATORS ON ALL FANS

MOTOR OPER. SMOKE DAMPERS

DISCHARGE AIR PLENUM W/ ACCESS DOOR

RETURN AIR PLENUM W/ ACCESS DOOR

MIXING SECTION WITH ACCESS DOOR

SENSIBLE LOAD (MBH)

EAT Db/Wb (°F)

LAT Db/Wb (°F)

FINS PER FOOT MAX.

SQ. FT. FACE AREA MIN.

FACE VELOCITY MAX.

EWT °F

KW TOTAL LOAD

LAT Db °F

EAT Db °F

TYPE

TOTAL CFM

ROWS MIN.

TYPE COIL

WHEEL DIAMETER MIN. (in.)

RPM APPROX.

TYPE DRIVE

HP MIN/VOLT/PH/HZ

CLASS FAN

ARRANGEMENT

RPM APPROX.

HP MIN/VOLT/PH/HZ

TYPE DRIVE

EXTERNAL STATIC PRESSURE

TOTAL CFM (CFM PER FAN)

TOTAL LOAD (MBH)

ARRANGEMENT

CLASS FAN

TOTAL CFM

TOTAL CFM (CFM PER FAN)

EXTERNAL STATIC PRESSURE (IN WG)

SYSTEM TYPE

AIR PRESSURE (IN WG)

ECONOMIZER

OUTSIDE AIR CFM (MINIMUM/ECONOMIZER)

LWT °F

REMARKS:

SOUND PATH

SUPPLY FAN

BOTTOM

RETURN AIR PATH

63 HZ 125 250 500 1K 2K 4K 8K

74 DB 80 DB 73 DB 55 DB 48 DB 51 DB 56 DB 55 DB

78 DB 75 DB 88 DB 74 DB 71 DB 72 DB 67 DB 60 DB

AIR TO AIR PLATE FRAME HEAT EXCHANGER SCHEDULE

AIR

HANDLING

UNIT

LOCATION

VENTILATION/

EXHAUST AIR

FLOWS CFM

OUTSIDE AIR DELIVERED /SUPPLY AIR EXHAUST AIR OUT

SUMMER

TEMP (Db)

SUMMER

Wb

WINTER

TEMP

(Db)

WINTER

Wb

CFM

PRESSURE

DROP IN.

WG

SUMMER

TEMP

(Db)

SUMMER

TEMP

(Wb)

WINTER

TEMP

(Db)

WINTER

TEMP

(Wb)

CFM

STATIC

PRESSURE

SUMMER

TEMP

(Db)

SUMMER

TEMP

(Wb)

WINTER

TEMP

(Db)

WINTER

TEMP

(Wb)

RTU-1 ROOF 1660

99 74 15 12

1660 0.710 82.9 69.4 55.4 37.9 1420 0.864 93.8 69.1 29.9 29.6

RTU-2 ROOF 1660 1660 0.710 82.9 69.4 55.4 37.9 1420 0.864 93.8 69.1 29.6 29.6

20/460/3Ø/60

2 @ 10/460/3Ø/60

FAN SIZED FOR

ECONOMIZER

SCR STAGING SCR STAGING

460V/3⌀/60HZ 460V/3⌀/60HZ

MOCP MCA MOCP MCA

70.00 A

125.00 A

50.15 A

115.90 A

70.00 A

125.00 A

50.15 A

115.90 A

E L E

C T

R

IC

A

L VOLTAGE/PHASE/HZ

CONNECTION #1

CONNECTION #2

PROVIDE ONE

ADDITONAL TO OWNER.

PROVIDE ONE

ADDITONAL TO OWNER.

PROVIDE ADDITIONAL SET OF

FILTERS TO OWNER.

NONE NONE

NONE NONE

NONE NONE

3.63 3.63TOTAL STATIC PRESSURE

8.47 8.47TOTAL STATIC PRESSURE (IN WG)

PROVIDE ADDITIONAL SET OF

FILTERS TO OWNER.

SUMMER SENSIBLE EFF.

ENERGY

RECOVERED

78.2% 29.0 MBH

DRY DESIGN

78.2%

78.2% 78.2%

WINTER SENSIBLE EFF.

ENERGY

RECOVERED

78.6% 72.4 MBH

DRY DESIGN

82.8%

78.6% 82.8%29.0 MBH 72.4 MBH

ROOF CURB: YES YES

LEAVING

RH

50.95%

50.95%

LEAVING

RH

9.33%

9.33%

LEAVING

RH

28.24%

28.24%

LEAVING

RH

96.59%

96.59%

AIR COOLED CHILLER ACOUSTICAL PERFORMANCE SCHEDULE

SOUND PATH 63 HZ 125 250 500 1K 2K 4K 8K

67 DB 66 DB 62 DB 63 DB 59 DB 57 DB 53 DB 48 DB

SOUND PRESSURE LEVELS AT 30 FEET.

NOTES:

1. SOUND PRESSURE LEVELS DERIVED FROM AHRI 370 SOUND POWER USING HEMISPHERE METHOD.

COOLING COIL PIPING ENCLOSURE YES YES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

C R

E V

IT

F

IL

E

S \R e v it

\3

.0

-C

E C e n tr a l M o d e l.

rv t

/9

/2

:1

:5

P

M

M003

MECHANICAL - SCHEDULES

Charlotte Engineers, LLP

5838 Monroe Road

Charlotte, NC 28212

(704) 531-3000

Michael Eaves

HDR, INC

440 South Church Street, Suite 1000

Charlotte, NC 28202

(704) 338-6844

Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

08/18/2022 GAT CAC

GENERAL NOTES

1. COIL AND BOX SIZE MAY BE INCREASED TO MEET REQUIRED CONDITIONS; BUT SHALL NOT BE DECREASED FROM SIZE SHOWN.

2. BOXES SHALL BE SET FOR MAXUMUM CFM SHOWN ON PLANS.

3. DUCT CONNECTIONS TO BOXES SHALL BE SAME SIZE AS BOX INLET UNLESS SHOWN OTHERWISE.

4. VARIABLE VOLUME BOXES SHALL OPERATE DOWN TO 50% OF MAXIMUM FLOW.

5. CONTROLS SHALL BE DDC PROVIDED BY CONTROLS CONTRACTOR AND INSTALLED BY BOX MANUFACTURER.

6. MAXIMUM NC LEVEL OF 30 ON ALL BOXES. PROVIDE SOUND ATTUNUATOR AS REQUIRED.

7. PROVIDE DIFFERENTIAL AIRFLOW SWITCH.

ELECTRIC TERMINAL UNIT SCHEDULE

Terminal No. Airflow Min. CFM Reheat CFM Unit Size E.A.T. (°F) Heating L.A.T.

(°F) EC Capacity

(kW) Steps Volts MOP MCA

1-1-1V 620 CFM 310 CFM 310 CFM 10 55 95.61 4.0 SCR 277/1 20 18.05

1-1-2V 1400 CFM 700 CFM 700 CFM 12 55 90.97 8.0 SCR 480/1 25 20.83

1-1-3V 460 CFM 230 CFM 230 CFM 8 55 96.05 3.0 SCR 277/1 15 13.54

1-1-4V 530 CFM 265 CFM 265 CFM 8 55 90.63 3.0 SCR 277/1 15 13.54

1-1-5V 400 CFM 200 CFM 200 CFM 8 55 94.34 2.5 SCR 277/1 15 11.28

1-1-6V 470 CFM 235 CFM 235 CFM 8 55 96.05 3.0 SCR 277/1 15 13.54

1-1-7V 840 CFM 420 CFM 310 CFM 10 55 93.47 5.5 SCR 277/1 15 14.32

1-1-8V 560 CFM 280 CFM 280 CFM 10 55 93.65 3.5 SCR 277/1 20 15.79

1-1-9V 600 CFM 300 CFM 300 CFM 8 55 91.72 3.5 SCR 277/1 20 15.79

1-1-10V 220 CFM 110 CFM 110 CFM 6 55 90.00 1.0 SCR 277/1 15 4.51

1-1-11V 670 CFM 335 CFM 335 CFM 10 55 92.58 4.0 SCR 480/1 15 10.42

1-1-12V 250 CFM 125 CFM 125 CFM 6 55 92.77 1.5 SCR 277/1 15 6.77

1-1-13V 130 CFM 70 CFM 70 CFM 6 55 91.32 1.5 SCR 277/1 15 6.77

1-1-14V 360 CFM 180 CFM 180 CFM 8 55 90.00 2.0 SCR 277/1 15 13.54

1-1-15V 190 CFM 175 CFM 175 CFM 6 55 98.10 2.5 SCR 277/1 15 11.3

1-2-1V 800 CFM 400 CFM 400 CFM 10 55 90.41 4.5 SCR 480/1 15 11.72

1-2-2V 630 CFM 315 CFM 315 CFM 10 55 94.97 4.0 SCR 277/1 20 18.05

1-2-3V 190 CFM 95 CFM 95 CFM 6 55 90.00 1.0 SCR 277/1 15 4.51

1-2-4V 360 CFM 180 CFM 180 CFM 8 55 90.00 2.0 SCR 277/1 15 9.03

1-2-5V 420 CFM 210 CFM 210 CFM 8 55 99.50 3.0 SCR 277/1 15 13.54

1-2-6V 420 CFM 210 CFM 210 CFM 8 55 92.47 2.5 SCR 277/1 15 11.28

1-2-7V 570 CFM 285 CFM 285 CFM 8 55 93.65 3.5 SCR 277/1 20 15.79

1-2-8V 380 CFM 190 CFM 190 CFM 8 55 94.34 2.5 SCR 277/1 15 11.28

1-2-9V 250 CFM 125 CFM 130 CFM 6 55 91.32 1.5 SCR 277/1 15 6.77

1-2-10V 380 CFM 190 CFM 190 CFM 8 55 94.34 2.5 SCR 277/1 15 11.28

1-2-11V 400 CFM 200 CFM 200 CFM 8 55 94.34 2.5 SCR 277/1 15 11.28

1-2-12V 680 CFM 340 CFM 340 CFM 10 55 92.58 4.0 SCR 480/1 15 11.72

1-2-13V 630 CFM 315 CFM 315 CFM 10 55 94.97 4.0 SCR 277/1 20 18.05

1-2-14V 210 CFM 105 CFM 105 CFM 6 55 90.00 1.0 SCR 277/1 15 4.51

1-2-15V 500 CFM 250 CFM 250 CFM 8 55 92.77 3.0 SCR 277/1 15 13.54

1-2-16V 160 CFM 80 CFM 80 CFM 6 55 90.00 1.5 SCR 277/1 15 6.77

1-2-17V 325 CFM 300 CFM 300 CFM 8 55 98.70 4.0 SCR 277/1 20 18.1

1-2-18V 420 CFM 210 CFM 210 CFM 8 55 92.47 2.5 SCR 277/1 15 13.54

Revisions: Date:

CFM

A

CFM

B

CFM

C

CFM

D

CFM

E

CFM

F

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

LOUVERED SUPPLY DIFFUSER

SIDEWALL EXHAUST REGISTER

PERFORATED EXHAUST REGISTERS

PERFORATED RETURN REGISTERS

SIDEWALL RETURN REGISTER

SIDEWALL SUPPLY REGISTER

AIR COOLED WATER CHILLER SCHEDULE

UNIT NO.

TOTAL

COOLING

CAPACITY

(TONS)

ENTERING

WATER

TEMPERATURE

(°F)

LEAVING

WATER

TEMPERATURE

(°F)

WATER

FLOWRATE

(GPM)

MAX. WATER

PRESS. DROP

(EVAPORATOR)

(FT. WG)

OUTSIDE AIR

TEMP (°F)

ELECTRICAL DATA COMPRESSOR

IPLV.IP

MCA

VOLTAGE

(V/PH/HZ)

TYPE QUANTITY

CH-1 70 56 42 113 8.42 95 147.8 460/3/60 SCROLL 4 14.71

SYMBOL TYPICAL MODULE SIZE - 24"x24"

136-210 CFM 9"x9" FACE 8" NECK

0-135 CFM 6"x6" FACE 6"∅ NECK

211-325 CFM 12"x12" FACE 10" NECK

326-475 CFM 12"x12" FACE 12" NECK

476-650 CFM 15"x15" FACE 14" NECK

CFM

CFM

CFM

CFM

CFM

CFM

CFM

650-840 CFM 18"x18" FACE 16" NECK

841-1125 CFM 18"X18" FACE & NECK

NOTES:

1. ALL AIR TERMINALS SHALL BE ALUMINUM CONSTRUCTION.

ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

2. DIFFUSERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE

MOUNTED FRAMES.

3. PROVIDE SR MODEL ROUND NECK ADAPTER.

CFM RANGE, FACE SIZE, & NECK SIZE

CFM

0-120 CFM 6"X6" FACE 6" NECK

CFM

121-240 CFM 9"X9" FACE 8" NECK

12"x12" REGISTER

12"x12" REGISTER

SYMBOL SIZE

111-250 CFM 10"x6"

0-110 CFM 8"x4"

251-480 CFM 14"x8"

481-650 CFM 18"x10"

651-835 CFM 18"x12"

836-1400 CFM 24"x18"

ALL AIR TERMINALS SHALL BE ALUMINUM CONSTRUCTION.

SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

SYMBOL REGISTER SIZE 24"x24"

136-210 CFM 8" ROUND NECK

0-135 CFM 6" ROUND NECK

211-325 CFM 10" ROUND NECK

326-475 CFM 12" ROUND NECK

651-840 CFM 16" ROUND NECK

841-2000 CFM 22"x22" NECK

476-650 CFM 14" ROUND NECK

CFM

A

CFM

B

CFM

C

CFM

D

CFM

E

CFM

F

CFM

G

NOTES:

1. ALL AIR TERMINALS SHALL BE ALUMINUM CONSTRUCTION.

ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

2. REGISTERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE

MOUNTED FRAMES.

SYMBOL REGISTER SIZE 24"x24"

136-210 CFM 8" ROUND NECK

0-135 CFM 6" ROUND NECK

211-325 CFM 10" ROUND NECK

326-475 CFM 12" ROUND NECK

651-840 CFM 16" ROUND NECK

841-2000 CFM 22"x22" NECK

476-650 CFM 14" ROUND NECK

CFM

CFM

CFM

CFM

CFM

CFM

CFM

NOTES:

1. ALL AIR TERMINALS SHALL BE ALUMINUN CONSTRUCTION.

ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

2. GRILLES LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE

MOUNTED FRAMES.

12"x12" REGISTER

CFM

H

0-135 CFM 6"∅ NECK

CFM

CFM

CFM

0-120 CFM 6" NECK

12"x12" REGISTER

0-130 CFM 6" NECK

16"x16" REGISTER

131-240 CFM 8" NECK

16"x16" REGISTER

SYMBOL SIZE

111-250 CFM 10"x8"

0-110 CFM 8"x4"

251-480 CFM 14"x10"

481-650 CFM 18"x12"

651-835 CFM 20"x14"

836-1400 CFM 24"x18"

ALL AIR TERMINALS SHALL BE ALUMINUM CONSTRUCTION.

SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

226-450 CFM 12"x10"

0-225 CFM 10"x6"

451-700 CFM 18"x12"

701-900 CFM 24"x12"

901-1180 CFM 30"x12"

1181-1350 CFM 36"x12"

SYMBOL CFM RANGE & MODULE SIZE

ALL AIR TERMINALS SHALL BE ALUMINUM CONSTRUCTION.

SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

DOUBLE DEFLECTION

TYPE

ELECTRIC UNIT HEATER SCHEDULE

MARK

MODEL

NUMBER

CAPACITY

BTU

CAPACITY

WATTS

VOLTAGE AMPS DIMENSIONS

EH-1 400C61 5,120 1,500 120 1.6 - 12.5 18"x12"x3.5"

EH-2 400C61 5,120 1,500 120 1.6 - 12.5 18"x12"x3.5"

1. INTEGRAL THERMOSTAT SHALL BE LOCATED IN JUNCTION BOX WITH ADJUSTMENT KNOB

FOR TAMPER PROOF OPERATION.

2. DISCONNECT SWITCH SHALL BE MOUNTED IN JUNCTION BOX.

3. DISCONNECT SWITCH PROVIDED BY MECHANICAL CONTRACTOR.

4. UNIT SHALL BE RECESSED WALL MOUNTED.

NOTES

CHILLED WATER PACKAGED PUMPING SYSTEMS SCHEDULE

TAG

PUMP

TAG

MIN

SUCT

MIN

DISCH SERVICE GPM FT.

PPS-1

CHWP-1 2.0 1.5 CHW 113.0 78.0 5.0 1750 460/3/60 PREMIUM

NOTES:

1. EACH PUMP SIZED FOR 100% OF SYSTEM DEMAND.

2. MAXIMUM PACKAGE DIMENSIONS SHALL NOT EXCEED 102"W x 120"L x 131"H.

3. SYSTEM CONNECTIONS SHALL BE 4".

4. TOTAL PACKAGE PRESSURE DROP SHALL NOT EXCEED 10.5 FEET (Cv = 47.9).

5. REFER TO PACKAGED PUMPING SYSTEM SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

6. FURNISH HYDRONIC INDICATOR ON PACKAGE WITH EACH PUMP.

7. PROVIDE ENCLOSURE. REFER TO 2/M003A.

8. INSULATION FOR BUFFER TANK SHALL BE 2" THICK MINIMUM, FLEXIBLE ELASTOMERIC CELLULAR. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. INSULATE

CHILLED WATER PIPING AND EQUIPMENT INSIDE CHILLED WATER PIPING SYSTEM ENCLOSURE WITH FLEXIBLE ELASTOMERIC CELLULAR INSULATION BASED ON

INSULATION SPECIFICATIONS REQUIREMENT.

9. SOFT START VFD.

10. EXHAUST WALL MOUNTED FAN 500 CFM; 0.5" SP, 1/4HP, 120V/60HZ WITH EXTERIOR SWITCH. PROVIDE ELECTRICAL TRANSFORMER IF REQUIRED.

11. ELECTRIC HEATER 4.0KW, 120 OR 240V. PROVIDE ELECTRICAL TRANSFORMER IF REQUIRED. HEATER CONTROLLED BY WALL MOUNTED THERMOSTAT.

12. WALL MOUNTED LOUVER 18”X18” WITH GRAVITY DAMPER.

13. PUMPS SHALL BE INSTALLED WITH NEOPRENE PADS FLOOR MOUNTED. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

14. PROVIDE 3/4" CONDENSATE DRAIN AT THE PUMPS. EXTEND PIPE ON ROOF TO THE GUTTERS.

15. CHILLED WATER PUMPING SYSTEM TO BE PROVIDE AS A SINGLE PACKAGE AND INDIVIDUAL COMPONENTS ARE NOT TO BE FIELD INSTALLED.

16. SINGLE POINT POWER PANEL TO BE HARD WIRED BY EC.

17. SEE DETAIL BELOW FOR ADDITIONAL EQUIPMENT INFORMATION.

18. PROVIDE AND INSTALL ROOF CURB SUPPORT FOR ENCLOSURE.

19. PROVIDE PIPE TRANSITIONS FOR ALL 2" AND 3" CONNECTIONS.

CHWP-2

ODP VFD 2" / 85 3"x2" 500

GALLON

8 GALLON

HP RPM V/PH/HZ EFF TYPE

MOTOR

CONTROL

TRIPLE DUTY

VALVE / MIN Cv

SUCTION

DIFFUSER

BUFFER

TANK

EXPANSION

TANK

MOTORS

MAJOR HYDRONIC COMPONENT MODEL NUMBERSPUMPS

2.0 1.5 CHW 113.0 78.0 1750 460/3/60 PREMIUM ODP VFD5.0

NOTES:

1. STARTER / DISCONNECT.

2. R410A REFRIGERANT.

3. PROVIDE WITH FACTORY INSTALLED CONTROLS.

4. UNIT MANUFACTURER SHALL INSTALL ACOUSTICAL INSULATION ON ALL COMPRESSORS. INSTALL AT LEAST 1" CLOSED CELL WRAP.

5. CONDENSER FANS SHALL BE CORROSION RESISTANT GLASS FIBER REINFORCED COMPOSITE BLADES MODLED INTO LOW NOISE PERFORMANCE.

6. UNIT SHALL HAVE LOW AMBIENT HEAD PRESSURE CONTROL.

7. CHILLER SHALL BE ABLE TO MODULATE IT'S CAPACITY FROM 100% DOWN TO 25% MINIMUM OR LOWER WITHOUT SACRIFICING EFFICIENCY OF PERFORMANCE.

8. UNIT SHALL BE MANUFACTURED WITH SECURITY GRILLES/HAIL GUARDS.

MOCP

175.0

DOUBLE DEFLECTION

DOUBLE DEFLECTION

DOUBLE DEFLECTION

DOUBLE DEFLECTION

DOUBLE DEFLECTION

NPLV

14.37

3"x2"2" / 85

CHILLED WATER PUMPING SYSTEM (PPS-1) 1CHILLED WATER PUMPING SYSTEM (PPS-1) ENCLOSURE 2

NTS NTS

PARTS LIST

ITEM QTY DESCRIPTION

5HP 1800 RPM END SUCTION

PUMP

3" X 2" FLANGED SUCTION

DIFFUSER

2" FLANGED TRIPLE DUTY

VALVE

500 GALLON, 3" FLANGE

CONN. CHILLED WATER

BUFFER TANK

8 GALLON VERTICAL

EXPANSION.

16 460V/3⌀ SINGLE POINT

POWER PANEL WILL THE

FOLLOWING ELECTRICAL

CHARACTERISTICS:

FLA: 31

MCA:33

MOCP: 40

MAKE-UP AIR WALL LOUVER

WITH HOOD.

4 KW UNIT HEATER.19

500 CFM 0.5HP WALL

MOUNTED EXHAUST FAN

NOTES:

1. ALL ENCLOSURE DIMENSIONS

ARE SUBJECT TO CHANGED BASED

ON MANUFACTURER.

2. SEE CHWP SCHEDULE FOR MORE

DETAILS.

NEMA COMBINATION

STARTER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

C R

E V

IT

F

IL

E

S \R e v it

\3

.0

-C

E C e n tr a l M o d e l.

rv t

/9

/2

:1

:5

P

M

M003A

MECHANICAL - SCHEDULES

Charlotte Engineers, LLP

5838 Monroe Road

Charlotte, NC 28212

(704) 531-3000

Michael Eaves

HDR, INC

440 South Church Street, Suite 1000

Charlotte, NC 28202

(704) 338-6844

Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

08/18/2022 GAT CAC

NOTES:

1. PROVIDE FIBERGLASS ENCLOSURE. BASIS OF

DESIGN "VPC FIBERGLASS MODEL VPC-B8X10. PRE

ENGINEERED INSULATED FRP WITH DIMENSIONS OF

120"L X 96"W X 104"H.

2. ENCLOSURE SHALL WITHSTAND 125 MPH WIND AND

30 PSF OF SNOW.

3. ENCLOSURE SHALL HAVE 36"X80" DOOR WITH

STAINLESS STEEL HINGES WITH 3-POINT LATCH.

MECHANICAL - CHILLED WATER PIPING SCHEMATIC

NTS

M004

CHILLER

CH-1

TI PI

TI PI FS

EXTEND TO

THE GUTTER

1"

4" CHWS

4" CHWR

TI PI

PI

CHWP-1 (VFD)

SUCTION DIFFUSER

W/ STRAINER

TI PI

PI

CHWP-2 (VFD)

SUCTION DIFFUSER

W/ STRAINER

4" CHWR

CHECK

VALVE

CHECK

VALVE

4" CHWR

BUFFER

TANK

EXPANSION

TANK

PRESSURE

REDUCING

VALVE

UNION

(TYPICAL)

CHECK

VALVE

(TYPICAL)

STRAINER

(TYPICAL)

BALL

VALVE

(TYPICAL)

4" CHWR

RTU-1 RTU-2

.5

C

H W

R

.5

C

H W

S

.5

C

H W

R

.5

C

H W

S

2.5"CHWS

2.5"CHWR

3 WAY CONTROL

VALVE (TYPICAL)

4" CHWR

GENERAL NOTES:

1. CHILLED WATER PUMPING PACKAGE SHALL BE PROVIDED BY MANUFACTURER AS COMPLETE

STAND ALONE PACKAGE TOTALLY ASSEMBLED AT THE FACTORY AND READY FOR INSTALLATION

BY CONTRACTOR .

A. COMPLETE ASSEMBLY SHALL BE MOUNTED ON A COMMON BASE AND AS A MINIMUM

INCLUDE, DUAL SET OF PUMPS WITH VFDs, EXPANSION TANK, BUFFER TAHNK, ALL

REQUIRED ELECTRICAL, HYDRONIC SPECIALTIES, COMPONENTS AND CONTROLS FOR

STAND ALONE OPERATIONS.

B. REFER TO SPECIFICATIONS FOR COMPLETE DESCRIPTION OF REQUIREMENTS.

2. CONTRACTOR SHALL PROVIDE AND INSTALL PIPING, SUPPORTS AND HYDRONIC SPECIALTIES NOT

PROVIDED WITH PUMPING PACKAGE INCLUDING ISOLATION VALVES, VIBRATION ISOLATORS,

BYPASS VALVES, ETC. INSTALLATION SHALL BE IN COMPLIANCE WITH DESIGN DOCUMENTS AND

MANUFACTURER AND INSTALLATION MANUALS.

3. ALL EXPOSED CHILLED WATER PIPING OUTSIDE OF THE BUILDING SHALL HAVE ELECTRICAL HEAT

TRACE FURNISHED WITH ALL NECESSARY CONTROLS AS REQUIRED BY MANUFACTURER.

CHILLED WATER

PUMPING PACKAGE

SCALE:

WATER BACKFLOW PREVENTER

(BY OTHERS)

1"

FLOW

METER

LEGEND

FS

T1

P1

M

WATER FLOW SWITCH

THERMOMETER IN PIPING WELL

PRESSURE GAUGE IN PIPING WELL

BALL VALVE

GATE VALVE

WATER FLOW BALANCING VALVE

MOTORIZED ISOLATION VALVE (2 WAY)

4" CHWS

CHEMICAL

SHOT FEEDER

4" VALVE WITH

BLIND FLANGE

2" VALVE FOR

QUICK FILL

4" CHWS

CONTROL VALVE (3 WAY)

UNION

CHECK VALVE

STRAINER

4" VALVE W/

BLIND FLANGE

MAKEUP WATER

PIPING SHOWN ON

MH200 AND PLUMBING

PLANS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

C R

E V

IT

F

IL

E

S \R e v it

\3

.0

-C

E C e n tr a l M o d e l.

rv t

/9

/2

:1

:5

P

M

M004

MECHANICAL - WATER FLOW

DIAGRAMSCharlotte Engineers, LLP

5838 Monroe Road

Charlotte, NC 28212

(704) 531-3000

Michael Eaves

HDR, INC

440 South Church Street, Suite 1000

Charlotte, NC 28202

(704) 338-6844

Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

CONDENSING UNIT

REFRIGERANT

COOLING COIL

D

X

RETURN AIR

FILTER

SUPPLY FAN SPLIT SYSTEM AIR HANDLING UNIT CONTROL (TYPICAL)

SPACE TEMPERATURE CONTROL: THE SPACE TEMPERATURE CONTROLLED LOCALLY. A DDC TEMPERATURE

SENSOR SHALL BE PROVIDED. THIS TEMPERATURE SENSOR SHALL REPORT THE SPACE TEMPERATURE TO THE ECC.

ALARMS: ALARM IF SPACE TEMPERATURE REPORTED BY THE DDC TEMPERATURE SENSOR REPORTS A TEMPERATURE

ABOVE 80 DEGREES FAHRENHEIT.

PROVIDE DDC TEMP SENSOR LOCATED IN COMM ROOM

TT

T-1

BI-1

HIGH TEMPERATURE

AI-1

SPACE TEMPERATURE

DUCTLESS SPLIT SYSTEM DIAGRAM

N.T.S.

CHILLER AND PUMPS CONTROL:

A. CHILLED WATER SYSTEM WILL CONSIST OF ONE AIR-COOLED, CHILLER

AND DUAL PUMP PACKAGED PUMPING SYSTEM.

6. NORMAL OPERATION' MODES:

A. NORMAL DAMPER D-6 POSITIONING, WITH MINIMUM OUTSIDE AIR. WHEN THE AIR SYSTEM IS OPERATING WITH THE 'OUTSIDE AIR

ECONOMIZER' MODE DISABLED, THE SYSTEM SHALL OPERATE WITH THE REQUIRED MINIMUM VENTILATION (OUTSIDE) AIR, AND

THE SYSTEM DAMPERS SHALL BE POSITIONED AS FOLLOWS:

(1) THE OUTSIDE AIR DAMPER D-6 BE OPENED TO ITS MINIMUM OUTSIDE AIR POSITION. THE POSITION SHALL BE DETERMINED

BY THE TEST AND BALANCE CONTRACTOR.

(2) D-4 RETURN AIR DAMPER AS WELL AS SUPPLY AIR DAMPER D-7 SHALL BE IN THEIR FULL-OPEN POSITIONS.

(3) THE EXHAUST AIR DAMPERS D-1 AND D-5 SHALL BE OPEN TO OPERATE IN NORMAL VENTILATION POSITIONS (NOT ECONOMIZER).

B. OUTSIDE AIR ECONOMIZER' COOLING MODE OPERATIONS:

(1) TEMPERATURE AND HUMIDITY SENSORS SHALL BE INSTALLED IN THE OUTSIDE AIR STREAM AND IN THE RETURN AIR DUCT OF

THIS RTU. THE DDC SYSTEM SHALL USE THESE SENSORS TO CALCULATE THE ENTHALPIES OF THE RESPECTIVE

AIRSTREAMS.

(2) COMPARATIVE ENTHALPY SHALL BE USED TO AS THE BASIS FOR SWITCHING THE SYSTEM TO OPERATE IN THE 'OUTSIDE AIR

ECONOMIZER' MODE.' WHEN THE CALCULATED ENTHALPY IN THE OUTSIDE AIR IS LESS THAN THE CALCULATED ENTHALPY IN THE

RETURN AIR STREAM, THE `OUTSIDE AIR ECONOMIZER' MODE SHALL BE ENABLED.

(3) DURING THE 'OUTSIDE AIR ECONOMIZER' MODE THE OUTSIDE AIR AND BOTH EXHAUST AIR DAMPERS D-1 AND D-5 SHALL BE

MODULATED AND CONTROLLED BY THE RTU DISCHARGE AIR TEMPERATURE SENSOR THROUGH

THE DDC SYSTEM. RETURN AIR DAMPERS D-2 AND D-4 SHALL MODULATE OPEN .

(4) THE ECONOMIZER DAMPERS SHALL HAVE THE FOLLOWING OPERATION POSITIONING: OUTSIDE AIR DAMPER D-6

SHALL BE NORMALLY-CLOSED AND EXHAUST DAMPERS D-1 AND D-5 OPEN.

(5) DURING THE 'OUTSIDE AIR ECONOMIZER' MODE A SENSOR IN THE MIXED AIR PLENUM SHALL ACT, THROUGH THE DDC SYSTEM, AS A MODULATING LOW LIMIT (SET AT 50 DEGREES, F.) TO KEEP THE MIXED AIR TEMPERATURE FROM FALLING TOO LOW.

(6) THE 'OUTSIDE AIR ECONOMIZER' MODE SHALL CONTINUE UNTIL THE UNIT IS SHUTDOWN BY THE DDC SYSTEM, OR UNTIL THE

ENTHALPY IN THE OUTSIDE AIR IS HIGHER THAN THE ENTHALPY IN THE RETURN AIR STREAM. WHEN THE 'OUTSIDE AIR

ECONOMIZER' MODE IS DISABLED, THE OUTSIDE AIR DAMPER D-6 AND EXHAUST DAMPERS D-1 AND D-5 SHALL BE

RETURNED TO THEIR NORMAL VENTILATION POSITIONS.

C. SUPPLY AIR TEMPERATURE CONTROLS:

(1) THE RTU DISCHARGE AIR TEMPERATURE CONTROLLER SHALL CONTROL THE OPERATIONS OF THE

RTU DAMPERS (WHEN THE OUTSIDE AIR ECONOMIZER' MODE IS ENABLED, AS PREVIOUSLY DESCRIBED), THE CHILLED WATER

COOLING COIL AND THE ELECTRIC HEAT. UPON A RISE IN DISCHARGE AIR TEMPERATURE ABOVE THE SETPOINT 55°F, THE DDC SYSTEM

SHALL ACT TO MODULATE RTU DAMPERS AS DESCRIBED ABOVE TO PROVIDE

COOLER AIR TO REDUCE THE DISCHARGE AIR TEMPERATURE. UPON A FALL IN DISCHARGE AIR TEMPERATURE BELOW THE

SETPOINT, THE SYSTEM'S DDC SHALL ACT TO MODULATE THE DAMPERS TO INCREASE THE DISCHARGE AIR TEMPERATURE.

THE HEATING AIR COIL CONTROLLER SHALL BE MODULATD FROM DISCHARGE AIR T-RA SENSOR THROUGH RTU DDC CONTROLS.

DISCHARGE SENSOR SHALL ACT AS A MODULATING LOW LIMIT SWITCH SUCH THAT THE HEAT COILS DISCHARGE AIR SHALL BE MAINTAINED AT 50°F MINIMUM DURING HEATING OPERATIONS. SET POINT SHALL BE ADJUSTABLE

(2) WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 50 DEGREES, F., THE HEATING SHUTOFF.

(3) COOLING COIL OPERATION SHALL BE CONTROLLED WITH A 3-WAY CONTROL VALVE. 42 DEGREES F COOLED

CHILLED WATER SHALL BE PROVIDED BY A REMOTE AIR-COOLED CHILLER, USING DUAL PUMP PUMPING

PACKAGE SYSTEM.

(4) WHEN THE DISCHARGE AIR TEMPERATURE SENSOR, THRU THE DDC, IS CALLING FOR COOLING, AND THE `OUTSIDE AIR

ECONOMIZER' MODE IS DISABLED, THE DDC SYSTEM SHALL SEND A SIGNAL TO START THE PRIMARY CHILLED WATER PUMP AND

THE CHILLER. THE DDC WILL ALSO MODULATE THE 3-WAY CONTROL VALVE TO SEND CHILLED WATER FLOW

THROUGH THE COOLING COIL.

(5) WHEN THE DISCHARGE AIR TEMPERATURE FALLS, THE DDC SYSTEM SHALL ACT TO MODULATE THE 3-WAY CONTROL VALVE TO

REDUCE THE FLOW OF CHILLED WATER THROUGH THE COOLING COIL.

(6) WHEN THE OUTSIDE AIR TEMPERATURE IS BELOW 40 DEGREES, F., ADJUSTABLE, THE CHILLER AND PUMPS SHALL BE DISABLED.

THE POSITION SHALL BE DETERMINED BY THE TEST AND BALANCE CONTRACTOR.

(4) D-2 DAMPER SHALL BE IN CLOSED POSITION.

THE DYNAMIC DUCT STATIC PRESSURE CONTROL SETPOINT SHALL BE CONTINUOUSLY MONITORED AND THE SETPOINT SHALL

BE ADJUSTED TO KEEP AT LEAST ONE AIR TERMINAL UNIT VAV BOX DAMPER AT 95 PERCENT OPEN, MINIMUM.

THE AIRFLOW THROUGH THE SUPPLY AIR FANS SHALL BE CONTINUOUSLY READ AND SENT TO THE DDC SYSTEM AND

OPERATOR'S WORKSTATION. AIRFLOW THROUGH THE EXHAUST AIR FANS SHALL BE CONTINUOUSLY READ AND

SENT TO THE DDC SYSTEM AND THE OPERATOR'S WORKSTATION.

PROVIDE A SYSTEM SWITCH, AT THE BAS, TO ALLOW FOR MANUAL OVERRIDE SHUTDOWN OF THE UN-OCCUPIED PERIOD

OPERATIONS.

DUCTWORK SMOKE DETECTOR

TEMPERATURE SENSOR - SUPPLY AIR

TEMPERATURE SENSOR - OUTSIDE AIR

TEMPERATURE SENSOR - MIXED AIR

TEMPERATURE SENSOR - HEATING COIL

TEMPERATURE SENSOR - LOW LIMIT (AVERAGING)

RELATIVE HUMIDITY SENSOR - SUPPLY AIR

RELATIVE HUMIDITY SENSOR - OUTSIDE AIR

RELATIVE HUMIDITY SENSOR - MIXED AIR

RELATIVE HUMIDITY SENSOR - RETURN AIR

TEMPERATURE SENSOR - RETURN AIR

DAMPER AND #

VARIABLE FREQUENCY DRIVE - SUPPLY FAN

PRESSURE DIFFERENTIAL - FINAL FILTER

PRESSURE DIFFERENTIAL - PRE-FILTER

STATIC PRESSURE

HIGH STATIC LIMIT

ANALOG INPUTAI

ANALOG OUTPUTAO

BINARY INPUTBI

BINARY OUTPUT

HVAC CONTROLS LEGEND

TEMPERATURE SENSOR - COOLING COIL

VARIABLE FREQUENCY DRIVE - EXHAUST FAN

SWITCH - ON/OFF

HEAT EXCHANGER BY-PASS DAMPER

AIR FLOW MONITORING STATION

RELATIVE HUMIDITY EXHAUST SENSOR

SMOKE DETECTOR - EXHAUST AIR

VARIABLE FREQUENCY DRIVE - CHILLED WATER PUMP

EMERGENCY STOP SWITCH

TEMPERATURE SENSOR

ENGINEERING CONTROL CENTER

SEQUENCE OF OPERATION

EXHAUST AIR

OUTSIDE AIR SUPPLY

DDC CONTROLLER PANEL

TO FIRE

ALARM

SYSTEM

ESS

RETURN AIR

EXHAUST AIREXHAUST AIR

SD

TO FIRE ALARM

SYSTEM

THE CONTROL OF PRESSURE INDEPENDENT VAV BOXES WITH ELECTRIC REHEAT AT

THE VAV TERMINAL SHALL BE AS FOLLOWS:

THE CONTROLLER SHALL MODULATE THE SUPPLY AIR DAMPER AND ELECTRIC REHEAT

IN SEQUENCE AS REQUIRED TO MAINTAIN SPACE TEMPERATURE SETPOINT.

THE SUPPLY AIR DAMPER SHALL BE SET TO MINIMUM WHEN THE ROOM

TEMPERATURE IS BELOW THE COOLING SETPOINT 75°F. THE REHEAT SHALL NOT

TURN ON UNTIL THE ROOM TEMPERATURE HAS DROPPED BELOW THE HEATING

SETPOINT 70°F. THE ROOM TEMPERATURE SETPOINT MAY BE ADJUSTED BY THE

OCCUPANT, WITHIN PRESELECTED LIMITS, BY CHANGING A SETPOINT ADJUSTMENT

ON THE ROOM THERMOSTAT, OR A SETPOINT MAY BE SELECTED BY THE DDC

SYSTEM OPERATOR THAT WILL OVERRIDE AND LIMIT ANY CHANGES MADE AT THE

ROOM STATUS.

THE ROOM TEMPERATURE SENSOR IS LOCATED IN THE SPACE. THE SENSOR

FEATURES WARMER/COOLER SETPOINT ADJUSTMENT DDC

THERMOMETER. A DIAGNOSTIC JACK WILL ALLOW FOR A PORTABLE TERMINAL

INTERFACE. THE PORTABLE TERMINAL INTERFACE IS A HAND-HELD DEVICE WHICH

GIVES THE OPERATOR THE CAPABILITY TO EDIT VAV TERMINAL BOX PARAMETERS.

WHEN COMMANDED TO CHANGE OVER TO THE UNOCCUPIED MODE, THE CONTROLLER

SHALL RAISE THE COOLING SETPOINT 60°F AND LOWER THE HEATING SETPOINT TO OPERATOR

DETERMINED VALUES. DURING UNOCCUPIED MODE, THE CONTROLLER SHALL BE RESET TO

THE OCCUPIED MODE FOR AN OPERATOR DETERMINED TIME PERIOD BY DEPRESSING THE

LOCAL OVERRIDE SWITCH PROVIDED FOR EACH ROOM OR WHEN THE OPERATOR HAS

COMMANDED IT. AT THE END OF THE TIME PERIOD, THE CONTROLLER SHALL

AUTOMATICALLY SWITCH BACK TO UNOCCUPIED MODE.

THE CONTROLLER SHALL MONITOR EACH OF THE FOLLOWING PARAMETERS OF THE TERMINAL BOX:

(1) CHILLED WATER CHILLER SERVING AIR HANDLING UNITS SHALL BE STARTED BY SIGNAL SENT

FROM THE BUILDING AUTOMATION SYSTEM OR MANUALLY BY OPERATOR UPON PROOF OF

CHILLED WATER FLOW. BUILDING AUTOMATION SYSTEM (BAS) SHALL BE ABLE TO MONITOR

CHILLER OPERATION FUNCTIONS INCLUDING SETTING POINTS AND ALL ALARM SIGNALS.

CHILLER SHALL BE PROVIDED WITH DIRECT DIGITAL CONTROLLER WHICH SHALL ALLOW CHILLER

CAPACITY MODULATION DURING COLD WEATHER. CHILLER CONTROLLER SHALL STAGE THE

OPERATIONS OF COMPRESSORS AND CONTROL CONDENSER DAMPERS AS NEEDED TO STARTUP AND

MAINTAIN STABLE OPERATIONS. CHILLER FLOW SHALL BE CONFIRMED THROUGH THE FLOW SWITCH

AT THE CHILLER.

(2) CHILLER CONTROLS SHALL MAINTAIN THE CONTROL OF THE LEAVING WATER AT 42 DEGREES, F., ADJUSTABLE AT THE OPERATOR'S WORKSTATION.

(3) A MINIMUM RUN-TIMER OF 10 MINUTES (ADJUSTABLE) SHALL BE INITIATED EACH TIME THAT THE

CHILLER IS SIGNALED TO START.

(4) CHILLER CONTROLS SHALL PROVIDE DATA OUTPUT THAT SHALL BE SENT THROUGH THE DDC SYSTEM

TO THE OPERATOR'S WORKSTATION. DATA AVAILABLE SHALL INCLUDE, AS A MINIMUM; THE

COMPRESSORS RUNNING, REFRIGERANT SUCTION AND DISCHARGE PRESSURES, THE CONDENSER

FANS RUNNING, OIL TEMPERATURE AND PRESSURE, OUTSIDE AIR TEMPERATURE, SUPPLY WATER

TEMPERATURE, AND RETURN WATER TEMPERATURE.

(5) ALARM ON CHILLER FAILURE SHALL BE MANUALLY RESET.

(6) THE BAS SHALL MONITOR KW AND CALCULATE LOAD OF THE CHILLER USING EVAPORATOR WATER

FLOW AND TEMPERATURE DIFFERENTIAL.

(7) THE BAS AND CHILLER CONTROLLER SHALL CONTROL AND MONITOR PUMPS OPERATION. UPON CALL

FOR COOLING AND CHILLER START, THE CHILLER CONTROLLER SHALL START AND OPERATE 'LEAD'

PUMP.

(CHECK VALVES IN THE PIPING SYSTEM AT THE PUMPS SHALL PREVENT SHORT-CYCLING THROUGH THE INACTIVE PUMP.)

OPERATING PUMP SHALL BE SHUTDOWN BY THE CHILLER CONTROLS AFTER THE CHILLER'S

REFRIGERANT PUMP-DOWN CYCLE HAS BEEN COMPLETED. PROVIDE SOFTWARE TO ROTATE THE

'LEAD' AND 'LAG' PUMPS.

T

CONTROLLER

TO BUILDING

AUTOMATION

SYSTEM

VARIABLE

DRIVE

SPEED

VARIABLE

DRIVE

SPEED

VARIABLE

DRIVE

SPEED

AIR HANDLING EQUIPMENT

VARIABLE AIR VOLUME AIR HANDLING UNIT - SEQUENCE OF OPERATION

1. THE RTU WILL START ON COMMAND FROM THE BAS, WHEN THE HOA SWITCH IS IN THE "AUTO" MODE. THE RTU

MAY ALSO BE STARTED LOCALLY WHEN THE HOA SWITCH IS PLACED IN THE "HAND MODE", UNTIL THAT TIME

WHEN TIMER WILL RETURN OPERATION TO HOA.

2. WHEN THE AIR HANDLER IS COMMANDED TO START THE OUTDOOR AIR DAMPER D-6 SHALL BE OPENED 100% AND

PROVE "OPEN" BASED ON INPUT FROM THE DAMPER END SWITCH, PRIOR TO STARTING THE SUPPLY AND

EXHAUST FANS. IF THE OUTDOOR AIR D-6 DOES NOT PROVE OPEN THE FAN SHALL REMAIN OFF AND AN

ALARM SHALL BE ROUTED TO THE OPERATOR'S WORKSTATION.

3. WITH THE OUTDOOR D-6 VERIFIED OPEN THE VFD SHALL START AND MODULATE THE SUPPLY. EXHAUST FANS

SHALL RAMP UNP IN SEQUENCE TO CFM ESTABLISHED BY TAB.

CURRENT TRANSFORMER (CT) SWITCHES SHALL SIGNAL THE CONTROLLER TO VERIFY OPERATION OF THE

SUPPLY AND EXHAUST FANS. IF SUPPLY FAN OPERATION IS NOT VERIFIED WITHIN 30 SECONDS (CUSTOMER

ADJUSTABLE) THEN THE UNIT SHALL BE SHUT DOWN AND AN ALARM BE ROUTED TO THE OPERATORS

WORKSTATION. IF THE EXHAUST FAN OPERATION IS NOT VERIFIED THE UNIT SHALL CONTINUE TO OPERATE AND

AN ALARM SHALL BE ROUTED TO THE OPERATORS WORKSTATION.

4. THE RTU SHALL STOP WHEN COMMANDED BY THE BAS, OR WHEN THE HOA SWITCH IS PLACED IN "HAND". THE

UNIT SHALL SHUT DOWN BY FIRST COMMANDING OFF THE FAN VFDS, WHEN THE FANS ARE PROVEN OFF (BY THE

CT INPUT) THE OUTDOOR AIR DAMPER SHALL THEN BE CLOSED. WHILE IN THE OFF MODE HEAT EXCHANGER

WILL BE OFF.

5. THE RTU WILL STOP (FANS OFF, OUTDOOR DAMPER D-6 CLOSED, HEAT EXCHANGER OFF) AND AN ALARM BE ROUTED TO

THE OPERATORS WORKSTATION WHEN ANY OF THE FOLLOWING CONDITIONS OCCUR:

A. IF EMERGENCY STOP SWITCH IS IN "PUSHED" POSITION, THEN THE SWITCH MUST BE MANUALLY "PULLED" IN

ORDER TO RESTART RTU.

B. IF HIGH DISCHARGE PRESSURE SWITCH LOCATED IN THE UNIT AND AFTER THE SUPPLY FAN IS TRIGGERED DUE

TO HIGH PRESSURE, THE RTU SHALL SHUT DOWN AND WILL NOT RESTART AUTOMATICALLY. (HIGH STATIC

PRESSURE SWITCH SHALL BE SET ACCORDING TO TEST & BALANCE'S INSTRUCTION.)

C. IF THE VAPOR TENSION LOW LIMIT THERMOSTAT ("FREEZESTAT") SENSES A TEMPERATURE BELOW 35

DEGREES (SHALL REQUIRE A MANUAL RESET). DURING THIS TIME DDS SHOULD SEND A SIGNAL TO OPEN UP 3-WAY CHILLED

WATER VALVE TO THE COOLING COIL AND START UP ONE OF THE CHILLED WATER PUMPS FOR CIRCULATION.

D. SMOKE MODE - IF ANY OF THE DUCT MOUNTED SMOKE DETECTORS (FURNISHED BY DIVISION 28) AND

INSTALLED IN THE SUPPLY, EXHAUST AND OUTSIDE AIR STREAMS DETECT SMOKE OR A SPACE DETECTOR

DETECTS SMOKE. UNIT SHALL RESTART WHEN THE ALARM CLEARS.

(8) PUMPS SHALL BE ALTERNATED TO EQUALIZE EQUIPMENT RUNTIME. SELECTION OF THE LEAD AND SECOND

PUMP IS EVALUATED ON A WEEKLY BASIS. THE PUMP WITH THE LEAST RUNTIME IS THE LEAD. THE

REMAINING PUMP IS LAG. IN THE EVENT THAT THE LEAD PUMP FAILS (AS DETECTED BY A CURRENT

TRANSDUCER) THE LAG PUMP SHALL START AND AN ALARM SHALL BE ROUTED TO THE OPERATORS

8. AIR FILTERS

1. A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR STATIC PRESSURE ON THE ENTERING

AND LEAVING SIDE OF AIR FILTER BANKS. THE SET -POINT VALUE SHALL BE CONNECTED TO

TO UNIT DDC CONTROLLER AND ENABLE AN ALARM AT THE COMPUTER CONSOLE WHEN FILTERS

NEEDS TO BE REPLACED ACCORDING TO MANUFACTURERS RECOMMENDATIONS.

A. WHEN AVERAGE SPACE TEMPERATURE FALLS BELOW UNOCCUPIED HEATING SETPOINT OF 60 DEG. F (ADJ.) THE SUPPLY FAN WILL START, EXHAUST FAN WILL BE OFF. THE OUTSIDE AIR DAMPER D-6 REMAIN CLOSED AND HEATING COIL CONTROL VALVE WILL MODULATE

B. WHEN AVERAGE SPACE TEMPERATURE RISES ABOVE UNOCCUPIED COOLING SETPOINT OF 85 DEG. F (ADJ.) THE SUPPLY FAN WILL START THE OUTSIDE AIR DAMPER D-6 WILL REMAIN CLOSED. EXHAUST FAN WILL BE OFF AND HEATING COIL VALVE WILL BE CLOSED.

9. UNOCCUPIED MODE

TO HOLD A SET POINT (ADJ.) ALL R.A. DAMPERS SHALL BE OPEN. HEAT EXCHANGER SHALL BE DE-ENERGIZED.

COOLING COIL CONTROL VALVE WILL MODULATE TO HOLD A SET POINT OF 85 DEG. F (ADJ.). ALL R.A. DAMPERS SHALL BE OPEN. ENERGY

WHEEL SHALL BE DE-ENERGIZED.

RTU-1, RTU-2 UNITS CONTROL SCHEMATIC

EXHAUST FANS

SUPPLY

DAMPER

EXHAUST

DAMPER

RETURN AIR

DAMPER

LOCATE 2/3 DOWNSTREAM

OF SUPPLY DUCT

1. CONTROL CONTRACTOR SHALL PROVIDE AND INSTALL DDC CONTROLLER FOR EACH ROOFTOPO UNIT.

2. DURING AIR BALANCING PROCEDURE CONTRACTOR SHALL ACHIEVE HEAT EXCHANGER TO HAVE SUPPLY SIDE UNDER POSITIVE

EXHAUST SIDE UNDER NEGATIVE PRESSURES.

NOTES:

BY-PASS DAMPER

RETURN

DAMPER

WALL-MOUNTED

TEMPERATURE SENSOR

W/

SETPOINT ADJUSTMENT

ELECTRIC

REHEAT COIL

SUPPLY AIR

TO SPACE

120/1PH

TO RTU CONTROLLER

AIRFLOW

MEASURING

DEVICE

VOLUME

REGULATOR

H

C

SUPPLY AIR

FROM RTU

ANALOG

INPUT SIGNAL

B. THE EXHAUST FAN AIRFLOW SHALL MEASURED WITH THE AIRFLOW MONITORS IN THE UNIT

THE EXHAUST FAN AIR FLOW SHALL BE ESTABLISHED AT FINAL TEST AND

BALANCE TO KEEP THE BUILDING AT SLIGHTLY POSITIVE PRESSURE.

C. THE EXHAUST FAN(S) SHALL RUN CONTINUOUSLY WHEN OUTSIDE AIR DAMPER D-6 IS OPEN

AND SUPPLY FAN IS RUNNING.

TYPICAL TERMINAL UNIT CONTROL DIAGRAM

AIR TO AIR PLATE

AND FRAME HEAT

EXCHANGER

DP DP

FILTER

H-ETS

COOLING

COIL

T-LL

FILTER

SD

HSTS

L

AFMS

H

D-5

NO

SUPPLY FAN

PRE- ELECTRIC

HEAT

ELECTRIC

CONTROLLER

LL-1

CHWSCHWR

NC

V-2

TS

FINAL

L

AFMS

H

L H

P-FF

L H

P-PF

HS

NC

D-7

TS HS

SPL

AFMS

H

AFMS

D-6

NC

NO

D-2

TS

TS-MIX

COMPUTER ACCESS120V/1PH POWER SUPPLY

DB1

DB-2

BY-PASS

D-4

NO

D-1

NO

BO

VFD-SF

VFD-CHWP

SD-EA

H-E

AFMS

DB-1

ON-OFF

VFD-EF

SD

T-CC

HSL

SP

P-PF

P-FF

D-1

T-RA

H-RA

H-MIX

H-OA

H-SA

T-LL

T-HC

T-MIX

T-OA

T-SA

H-RA

H-OA H-SA

TS HS

HS-MIX

H-MIX

SP

HSLTS

TS-CC

TS

TS-HC

T-OA

T-RA

T-SA

ESS

T-1

ECC

DAMPER

L

AFMS

H

(1)

C. VARIABLE AIR VOLUME TERMINAL UNITS (VAV BOXES)

(a)

(b)

(c)

(3)

(2)

7. SUPPLY AIR AND EXHAUST AIR FANS SPEED CONTROL: SUPPLY & EXHAUST FAN MOTORS VARIABLE FREQUENCY DRIVES SHALL

CONTROL EACH FAN AIR FLOW RATE.

A. STATIC PRESSURE SENSOR SHALL BE LOCATED 2/3 OF THE WAY DOWN THE LONGEST MEDIUM PRESSURE DUCT RUN AND IN AN

EASILY-ACCESSIBLE LOCATION. THIS SENSOR SHALL SEND A SIGNAL TO THE DDC SYSTEM FOR CONTROL OF THE SUPPLY AIR FANS

SPEED. UPON A FALL IN THE DUCT STATIC PRESSURE, BELOW THE DYNAMIC SETPOINT (SEE BELOW), THE SPEED OF THE SUPPLY

AIR FANS SHALL BE INCREASED. UPON A RISE IN THE DUCT STATIC PRESSURE, ABOVE THE DYNAMIC SETPOINT, THE SPEED OF

THE SUPPLY AIR FANS SHALL BE REDUCED.

THE CENTRAL GRAPHICS CONSOLE AND ANY OTHER OPERATOR'S CONSOLE SHALL BE

CAPABLE OF DISPLAY AND CONTROL OF EACH OF THESE PARAMETERS. THE PORTABLE

DISPLAY TERMINAL CONNECTED TO THE CONTROLLER SHALL ALSO BE ABLE TO MONITOR

AND CONTROL THESE PARAMETERS.

PROVIDE A GRAPHIC FOR EACH ROOM SHOWING FLOOR PLAN, ROOM TEMPERATURE AND

ROOM SETPOINT. THESE SHALL BE ARRANGED SO THAT THE OPERATOR SHALL "CLICK ON

THE ROOM" AND A WINDOW SHALL APPEAR ALLOWING ANY OF THE PARAMETERS

AVAILABLE ON THE CONTROLLER TO BE SELECTED AND MODIFIED BY THE POINTING OF A

THESE ROOM GRAPHICS SHALL BE GROUPED TOGETHER IN FLOOR QUADRANTS.

THE ROOM'S COLOR SHALL INDICATE GREEN IF THE ROOM TEMPERATURE IS WITHIN ALARM

RANGE AND IT SHALL INDICATE RED IF THE ROOM TEMPERATURE IS ABOVE OR BELOW

ALARM RANGE. THE QUADRANT GRAPHIC SHALL CONTAIN A SMALL LAYOUT OF THE TOTAL

FLOOR AND SHALL SHOW THE PRESENTLY DISPLAYED GRAPHIC'S REACTION TO THE REST

OF THE FLOOR. ALSO LOCATED ON THE QUADRANT GRAPHIC SHALL BE "QUICK LINKS" TO

THE QUADRANTS OF THIS AND OTHER FLOORS.

(4)

(5)

BAS PANEL

BUILDING

CONTROLLER

ASC ASC ASC

ASC ASC ASC

RTU-1 CONTROLLER

RTU-2 CONTROLLER (BC)BACNET IP NEW FIBER TO

ECC IN BUILDING 100

120V AC BY

DIV. 26

BACNET MS/TP

CONTROLS SYSTEM ARCHITECTURE

BACNET IP TO BAS PANEL

APPLICATION SPECIFIC

CONTROLLERIR

120V AC

BY DIV. 26

120V BY DIV 26

NOTE:

1. CONTROL POWER SHOWN IS BASIS OF DESIGN. ADDITIONAL POWER FOR CONTROL PANELS

ADDED BY THE TEMPERATURE CONTROLS CONTRACTOR ARE TO BE PROVIDED AND

INSTALLED BY DIV. 26.

AUTOMATIC CALIBRATION IS ACCOMPLISHED THROUGH THE CONTROLLER AUTO ZERO

FEATURE. THIS FEATURE CALIBRATES THE AIRFLOW SENSOR. THE AUTO ZERO FEATURE

CAN BE COMMANDED FROM THE BMS OR CAN BE SCHEDULED. THIS FEATURE OVERRIDES

THE DAMPER ACTUATOR CLOSED WHILE PERFORMING AUTO ZERO. WHEN THE DAMPER IS

FULLY CLOSED, THE PRESENT VALUE OF DELTA P SENSOR IS READ INTO THE AI OFFSET

TABLE.

(6)

277/480

EXHAUST AIR

DAMPER

OUTSIDE AIR

DAMPER

BUILDING WARM UP AND COOL DOWN SHALL START AT PREDETERMINED TIME BY OWNER SCHEDULE

AND FOLLOW NORMAL START-UP/SHUTDOWN OPERATIONS AS DESCRIBED IN SEQUENCE OF OPERATIONS.

10.

(9) CHILLED WATER PACKAGE SYSTEM ELECTRIC HEATER SHALL BE CONTROLLED BY MANUFACTURER PROVIDED THERMOSTAT

AND SET AT 80°F (ADJUSTABLE).

(10) EXHAUST FAN SHALL BE CONTROLLED BY EXTERIOR WALL MOUNTED "ON-OFF" SWITCH.

(a) SUPPLY AIR TEMPERATURE

(b) SUPPLY AIR VOLUME

(c) SUPPLY DAMPER CONTROL

(d) SUPPLY DAMPER CONTROL

(e) REHEAT VALVE CONTOL

(f) ROOM TEMPERATURE

(g) ROOM TEMPERATURE COOLING SETPOINT

(h) ROOM TEMPERATURE HEATING SETPOINT

(i) UNOCCUPIED TEMPERATURE DEADBAND

(j) SUPPLY AIR VOLUME MAXIMUM FLOW

(k) SUPPLY AIR VOLUME MINIMUM FLOW

(l) LOCAL OCCUPIED OVERRIDE SWITCH

(a) DURING ECONOMIZER MODE, THE CONTROLLER SHALL DISABLE MECHANICAL COOLING AND UTILIZE RTU DAMPERS TO

MAINTAIN DISCHARGE AIR TEMPERAURE.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

C R

E V

IT

F

IL

E

S \R e v it

\3

.0

-C

E C e n tr a l M o d e l.

rv t

/9

/2

:1

:5

P

M

M005

MECHANICAL - SEQUENCE OF

OPERATIONSCharlotte Engineers, LLP

5838 Monroe Road

Charlotte, NC 28212

(704) 531-3000

Michael Eaves

HDR, INC

440 South Church Street, Suite 1000

Charlotte, NC 28202

(704) 338-6844

Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

FD

F D

FD FD

D D

D D

S S

S S

S S

S

S

SSSSS

S S S S S

S

SS

S S

S

SSS

S S S

E

A

D

D.6

B

7 8 10 11 12654321 6.3 6.6

CONFERENCE

1A059

OPHTH CHIEF

1A052

YAG LSR

1A049

PRE-OP EX 2

1A032

PRE-OP EX 1

1A034

EX 4

1A025

PHOTO

1A045

EX 7

1A042EX 5

1A088

EX 6

1A086

EX 7

1A084

EX 8

1A077

EX 3

1A095

EX 4

1A097

TLT

1A112

TLT

1A106

RME DROP-OFF

1A073

LOW VIS

1A064

RECEPTION

1A006

HAC

1A104

MECH

1A092

VF 1

1A081

EYEGLASS FIT D&D

1A103

WAITING

1A101

VEST

1A001

WAITING

1A011

OCT 2

1A027

VF 1

1A047

NURSE WKRM

1A026

EX 3

1A028

COMM

1A016

EQPT ALC

1A031

EX 9

1A076

EX 10

1A074

EX 11

1A072

LOUNGE

1A056

EX 10

1A048

EX 9

1A046

EX 8

1A044

CORR

1A090

CORR

1A080

LOBBY

1A000

CORR

1A040

CORR

1A020

CORR

1A070

LOCKER

1A056A

SHARED OFF

1A087

SHARED OFF

1A078

SHARED OFF

1A054

EX 12

1A068

BROS

1A002

VIST

1A004

SHARED OFF

1A058

ELEC

1A108

TLT

1A012

TLT

1A057

TLT

1A014

EX 6

1A043

HAC

1A041

VEST

1A021

ELEC

1A024

CORR

1A030

COMM

1A102

HLD STOR

1A069

TLT

1A075

REPROCESS

1A071

WHCH ALC

1A101A

MED PREP

1A067

EX 5

1A023

TLT

1A055

VALVE

1A089

WHCH ALC

1A011A

EX 1

1A094

VEST

1A091

EX 2

1A093

OCT 1

1A085

OCT 2

1A083

VF 2

1A079

PROCEDURE

1A022

CORR

1A100

CORR

1A010

SHARED OFF

1A062

SHARED OFF

1A082

EX 13

1A066

OCT 1

1A029

COPY

1A006A

RTU-1 ON

ROOF

RTU-2 ON ROOF

KEY PLAN: (DO NOT SCALE)

AREA OF WORK

PLAN

NORTH

GRAPHIC SCALE

( in Feet )

1 inch = 8 ft.

8 84 16 32

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

C R

E V

IT

F

IL

E

S \R e v it

\3

.0

-C

E C e n tr a l M o d e l.

rv t

/2

/2

:4

:0

A

M

MH100

MECHANICAL - FIRST FLOOR PLAN -

DUCTWORK - OVERALLCharlotte Engineers, LLP

5838 Monroe Road

Charlotte, NC 28212

(704) 531-3000

Michael Eaves

HDR, INC

440 South Church Street, Suite 1000

Charlotte, NC 28202

(704) 338-6844

Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

09/29/2023 GAT CAC

1/8" = 1'-0"

MECHANICAL - FIRST FLOOR PLAN - DUCTWORK - OVERALL

FOR REFERENCE ONLY. REFER TO MH100A AND MH100B

FOR DUCTWORK SIZES, AND AIR FLOWS.

T

T

T

T

T

T

T TT

T

T T T

T

T

T

T

T

T

T

T

T

T

T

T

T T

T

T

T

TT

T

T

T

T

S S

S S

S S

S

S

SSSSS

S S S S S

S

SS

S S

S

SSS

S S S

E

A

D

D.6

B

7 8 10 11 12654321 6.3 6.6

CONFERENCE

1A059

388 SF

OPHTH CHIEF

1A052

132 SF

YAG LSR

1A049

188 SF

PRE-OP EX 2

1A032

132 SF

PRE-OP EX 1

1A034

130 SF

EX 4

1A025

131 SF

PHOTO

1A045

131 SF

EX 7

1A042

131 SF

EX 5

1A088

131 SF

EX 6

1A086

132 SF

EX 7

1A084

132 SF

EX 8

1A077

131 SF

EX 3

1A095

131 SF

EX 4

1A097

127 SF

TLT

1A112

67 SF

TLT

1A106

71 SF

LOW VIS

1A064

296 SF

RECEPTION

1A006

141 SF

HAC

1A104

67 SF

MECH

1A092

138 SF

VF 1

1A081

85 SF

EYEGLASS FIT D&D

1A103

418 SF

WAITING

1A101

373 SF VEST

1A001

76 SF

WAITING

1A011

237 SF

OCT 2

1A027

65 SF

VF 1

1A047

131 SF

NURSE WKRM

1A026

115 SF

EX 3

1A028

132 SF

COMM

1A016

90 SF

EQPT ALC

1A031

48 SF

EX 9

1A076

132 SF

EX 10

1A074

132 SF

EX 11

1A072

132 SF

LOUNGE

1A056

158 SF

EX 10

1A048

132 SF

EX 9

1A046

132 SF

EX 8

1A044

132 SF

CORR

1A090

245 SF

CORR

1A080

171 SF

LOBBY

1A000

517 SF

CORR

1A040

650 SF

CORR

1A020

452 SF

CORR

1A070

1104 SF

LOCKER

1A056A

36 SF

SHARED OFF

1A087

111 SF

SHARED OFF

1A078

176 SF

SHARED OFF

1A054

132 SF

EX 12

1A068

132 SF

BROS

1A002

152 SF

VIST

1A004

115 SF

SHARED OFF

1A058

112 SF

ELEC

1A108

22 SF

TLT

1A012

63 SF

TLT

1A057

75 SF

TLT

1A014

53 SF

EX 6

1A043

132 SF

HAC

1A041

46 SF

VEST

1A021

62 SF

ELEC

1A024

110 SF

CORR

1A030

172 SF

COMM

1A102

100 SF

HLD STOR

1A069

61 SF

TLT

1A075

72 SF

REPROCESS

1A071

69 SF

WHCH ALC

1A101A

21 SF

MED PREP

1A067

69 SF

EX 5

1A023

132 SF

TLT

1A055

87 SF

VALVE

1A089

44 SF

WHCH ALC

1A011A

21 SF

EX 1

1A094

132 SF

VEST

1A091

62 SF

EX 2

1A093

132 SF

OCT 1

1A085

74 SF

OCT 2

1A083

73 SF

VF 2

1A079

87 SF

PROCEDURE

1A022

152 SF

CORR

1A100

465 SF

CORR

1A010

251 SF

SHARED OFF

1A062

113 SF

SHARED OFF

1A082

173 SF

EX 13

1A066

132 SF

OCT 1

1A029

65 SF

COPY

1A006A

78 SF

R R

1-1-13V

130 CFM

1-1-1V

620 CFM

1-1-4V

530 CFM

1-1-5V

400 CFM

1-1-6V

470 CFM

1-1-10V

220 CFM

1-1-7V

840 CFM

1-1-8V

560 CFM

1-1-9V

600 CFM

1-2-11V

400 CFM

1-2-10V

380 CFM

1-2-9V

250 CFM

1-2-8V

380 CFM

1-2-15V

500 CFM

1-2-17V

325 CFM

1-2-4V

360 CFM

1-2-3V

190 CFM

1-2-16V

160 CFM

1-2-2V

630 CFM

1-2-6V

420 CFM

AC-2

1-2-1V

800 CFM

1-2-12V

680 CFM

1-2-13V

630 CFM

1-2-18V

420 CFM

1-1-12V

250 CFM

1-1-11V

670 CFM

1-1-2V

1400 CFM

AC-1

E S

S

TO RTU-1

EH-1 EH-2

TO RTU-2

E S

S

B A

S

RTU-1 ON ROOF RTU-2 ON ROOF

1-1-14V

360 CFM

1-2-7V

570 CFM

1-2-14V

210 CFM

R

RME DROP-OFF

1A073

51 SF

HAC

1A073H

19 SF

1-1-15V

190 CFM

1-1-3V

460 CFM

1-2-5V

420 CFM

1 1/2"D

3/4"D

/4

"D

1 1/2"D

/4

"D

KEY PLAN: (DO NOT SCALE)

AREA OF WORK

PLAN

NORTH

GRAPHIC SCALE

( in Feet )

1 inch = 8 ft.

8 84 16 32

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultants:

C R

E V

IT

F

IL

E

S \R e v it

\3

.0

-C

E C e n tr a l M o d e l.

rv t

/2

/2

:4

:0

A

M

MH100.1

MECHANICAL - FIRST FLOOR PLAN -

VAV ZONE PLAN - OVERALLCharlotte Engineers, LLP

5838 Monroe Road

Charlotte, NC 28212

(704) 531-3000

Michael Eaves

HDR, INC

440 South Church Street, Suite 1000

Charlotte, NC 28202

(704) 338-6844

Nicholas Nash

EYE CLINIC CENTER

WJBD VAMC - COLUMBIA, SC 29209

544-329

09/29/2023 GAT CAC

1/8" = 1'-0"

MECHANICAL - FIRST FLOOR PLAN - VAV ZONE PLAN - OVERALL

FOR REFERENCE ONLY. REFER TO MH100A AND MH100B

FOR DUCTWORK SIZES AND AIRFLOWS.

S S S

FD

F D

D D

S S

S S

S S

S

S

SSSSS

S S S

INSTALL 10 FT LONG LINEAR BAR GRILLE, 0° DEFLECTION, TO SUPPLY 1,100 CFM. PROVIDE GRILLE WITH 14"x12"(H) SHEET METAL PLENUM WITH 1/2" LINER. MC TO FABRICATE

PLENUM. PROVIDE PLENUM WITH (3) THREE 10" DIAMETER DUCT INLETS AND CONNECT

INLET DUCTS TO MAIN SUPPLY DUCT. INSTALL BALANCING DAMPER AT EACH INLET TO THE

PLENUM. COORDINATE EXACT BAR GRILLE LOCATION AND ELEVATION WITH PROJECT

ARCHITECT.

28"x28" S.A. DUCT UP TO RTU-1 LOCATED ON ROOF. INSTALL DUCT FITTINGS TO CONNECT

S.A. DUCT TO UNIT S.A. OPENING AT THE BOTTOM.

44"x22" R.A. DUCT UP TO RTU-1 LOCATED ON ROOF. INSTALL DUCT FITTINGS TO CONNECT

R.A. DUCT TO UNIT R.A. OPENING AT THE BOTTOM.

44"x22" E.A. DUCT UP TO RTU-1 LOCATED ON ROOF. INSTALL DUCT FITTINGS TO CONNECT

E.A. DUCT TO…