Attachment 8 - Vol 4 Drawings.pdf

PDF 15 MB Posted

Attached to
Y1DZ--502-21-222 | EHRM Infrastructure Upgrades | Pineville, LA |
Solicitation number
36C77626R0104
Issued by

About this file

This is a construction document set (Volume 4 Drawings) for the Electronic Health Record Modernization (EHRM) infrastructure upgrades at the Alexandria VA Health Care System in Pineville, Louisiana, dated March 24, 2026, at 100% construction document phase. The drawings cover electrical, telecommunications, and technology infrastructure improvements across multiple buildings (1-9, 13-16, 45-46, 49, 136, 142, 147, 171) and include detailed plans, riser diagrams, bonding details, and equipment specifications.

The electrical scope includes new power panels with generator backup capability, UPS systems, and rack power distribution units for telecommunications rooms. Technology infrastructure requires Cat 6A copper cabling with 8-pin keystone jacks, fiber optic backbone systems with 24-strand armored single-mode cables, wireless access points, physical access control systems (PACS), and multi-sensor surveillance cameras that comply with the National Defense Authorization Act. Telecommunications rooms feature channel racks (24" wide, 30" deep, 84" high), basket cable trays, bonding busbars per ANSI/TIA 607-D standards, and equipment mounted on fire-retardant plywood. The specifications mandate compliance with NEC, NFPA standards, TIA/EIA cabling standards, and VA standards. The contractor must provide comprehensive cabling, conduit, supports, fire-rated sleeve assemblies, grounding and bonding materials, testing, labeling, and as-built documentation. Construction sequencing requires coordination with ongoing facility operations, with electrical outages requiring 14-day advance notification and a cutover plan approved 30 days prior to implementation.

View the file

Other files

File Type Posted
ME_SUBMITTAL_PKA-AK36NL_PUZ-AK36NL_6PSmo.pdf PDF
Amendment 0007.pdf PDF
ME_SUBMITTAL_PKA-AK24NL_PUZ-AH24NL_XbtyE.pdf PDF
RFI Update 10-7-26.pdf PDF
Amendment 0006.pdf PDF
RFI Responses.pdf PDF
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Site Visit Sign In Sheet 8-20-26.pdf PDF
Site Visit Agenda.pdf PDF
Amendment 0003.pdf PDF
Attachment 11 - Site Visit Details.docx DOCX document
Amendment 0002.pdf PDF
Attachment 11 - Site Visit Details.docx DOCX document
Amendment 0001.pdf PDF
Attachment 7 - Key Subcontractor Information.docx DOCX document
Attachment 9 - Division Pricing Template.xlsx XLSX spreadsheet
Attachment 4 - Vol 3 Drawings.pdf PDF
Attachment 3 - Volume 2 Drawings.pdf PDF
Attachment 10 - Wage Determination.pdf PDF
Attachment 6 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 11 - Site Visit Details.docx DOCX document
Attachment 8 - Key Personnel.docx DOCX document
Attachment 5 - Vol 4 Drawings.pdf PDF
Attachment 13 - Wage Determination.pdf PDF
Attachment 6 - Vol 2 Drawings Part 4.pdf PDF
Attachment 5 - Vol 2 Drawings Part 3.pdf PDF
Attachment 10 - Key Subcontractor Information.docx DOCX document
Attachment 11 - Key Personnel.docx DOCX document
Attachment 9 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 2 - Vol 1 Drawings.pdf PDF
Attachment 1 - Specifications.pdf PDF
Attachment 7 - Vol 3 Drawings.pdf PDF
Attachment 3 - Vol 2 Drawings.pdf PDF
Attachment 12 - Division Pricing Template.xlsx XLSX spreadsheet
Attachment 14 - Site Visit Details.docx DOCX document
Attachment 4 - Vol 2 Drawings Part 2.pdf PDF
36C77626R0104.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:3

:1

A

M C

U s e rs \l s ta rn e s \D o c u m e n ts

\M S

-3

E

H R

M ls ta rn e s C

B U

M B

.r v t

G-001.4

COVER VOLUME 4

1 1MEL

ELECTRONIC HEALTH

RECORD MODERNIZATION

(EHRM)

ALEXANDRIA VA HEALTH CARE SYSTEM

2495 SHREVEPORT HWY, 71N

PINEVILLE, LA 71360

MARCH 24, 2026

100% CONSTRUCTION DOCUMENTS

502-21-22220-398

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

ALEXANDRIA VA HEALTH CARE SYSTEM

2495 SHREVEPORT HWY, 71N

PINEVILLE, LA 71360

VA PROJECT #: 502-21-222

WVS

VOLUME 4

VOLUME 4 OF 4

SHEET LIST

SHEET NUMBER SHEET NAME DWG OF DWG

049.ET601 BUILDING 49, FIBER AND BONDING RISER DIAGRAMS 78 88

049.ET602 BUILDING 49, SINGLE LINE DIAGRAM 79 88

136.ET401 BUILDING 136, FIRST FLOOR, TELECOM ROOM 32 PLANS 80 88

136.ET601 BUILDING 136, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 81 88

142.ET401 BUILDING 142, FIRST FLOOR, TELECOM ENCLOSURE ROOM 7B PLANS 82 88

142.ET601 BUILDING 142, FIBER RISER DIAGRAM 83 88

142.ET602 BUILDING 142, SINGLE LINE AND BONDING RISER DIAGRAMS 84 88

147.ET401 BUILDING 147, FIRST FLOOR, TELECOM ENCLOSURE 102 PLANS 85 88

147.ET601 BUILDING 147, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 86 88

171.ET401 BUILDING 171, FIRST FLOOR, TELECOM ENCLOSURE 108 PLANS 87 88

171.ET601 BUILDING 171, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 88 88

SHEET LIST

SHEET NUMBER SHEET NAME DWG OF DWG

GENERAL

G-001.4 COVER VOLUME 4 1 1

ELECTRICAL

000.ET001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 88

000.ET002 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 2 88

000.ET501 TYPICAL TELECOM ROOM DETAILS 3 88

000.ET502 ELECTRICAL DETAILS 4 88

000.ET503 ELECTRICAL DETAILS 5 88

000.ET504 TECHNOLOGY DETAILS 6 88

000.ET505 CHANNEL RACK DETAILS 7 88

000.ET506 SITE TECHNOLOGY DETAILS 8 88

000.ES101 OUTDOOR BUILDING FIBER LOOP DIAGRAM 9 88

001.ET401 BUILDING 1, FIRST FLOOR, TELECOM ROOM 103 PLANS 10 88

001.ET402 BUILDING 1, SECOND FLOOR, TELECOM ROOM 202 PLANS 11 88

001.ET601 BUILDING 1, FIBER RISER DIAGRAM 12 88

001.ET602 BUILDING 1, SINGLE LINE AND BONDING RISER DIAGRAMS 13 88

002.ET401 BUILDING 2, FIRST FLOOR, TELECOM ROOM 133 PLANS 14 88

002.ET402 BUILDING 2, SECOND FLOOR, TELECOM ROOM 256 PLANS 15 88

002.ET403 BUILDING 2, THIRD FLOOR, TELECOM ROOM 359 PLANS 16 88

002.ET404 BUILDING 2, FOURTH FLOOR, TELECOM ROOM 424 PLANS 17 88

002.ET601 BUILDING 2, FIBER RISER DIAGRAM 18 88

002.ET602 BUILDING 2, SINGLE LINE AND BONDING RISER DIAGRAMS 19 88

003.ET401 BUILDING 3, FIRST FLOOR, TELECOM ROOM 105 PLANS 20 88

003.ET402 BUILDING 3, SECOND FLOOR, TELECOM ROOM 205 PLANS 21 88

003.ET403 BUILDING 3, THIRD FLOOR, TELECOM ROOM 305 PLANS 22 88

003.ET601 BUILDING 3, FIBER RISER DIAGRAM 23 88

003.ET602 BUILDING 3, SINGLE LINE AND BONDING RISER DIAGRAM 24 88

004.ET401 BUILDING 4, FIRST FLOOR, TELECOM ROOM 102E PLANS 25 88

004.ET601 BUILDING 4, FIBER RISER DIAGRAM 26 88

004.ET602 BUILDING 4, SINGLE LINE AND BONDING RISER DIAGRAMS 27 88

005.ET401 BUILDING 5, BASEMENT FLOOR, TELECOM ROOM G06A PLANS 28 88

005.ET402 BUILDING 5, FIRST FLOOR, TELECOM ROOM 110A PLANS 29 88

005.ET403 BUILDING 5, SECOND FLOOR, TELECOM ROOM 212C PLANS 30 88

005.ET601 BUILDING 5, FIBER RISER DIAGRAM 31 88

005.ET602 BUILDING 5, SINGLE LINE AND BONDING RISER DIAGRAMS 32 88

006.ET401 BUILDING 6, BASEMENT FLOOR, TELECOM ROOM 008 PLANS 33 88

006.ET402 BUILDING 6, FIRST FLOOR, TELECOM ROOM 101 PLANS 34 88

006.ET403 BUILDING 6, SECOND FLOOR, TELECOM ROOM 201 PLANS 35 88

006.ET404 BUILDING 6, THIRD FLOOR, TELECOM ROOM 310 PLANS 36 88

006.ET601 BUILDING 6, FIBER RISER DIAGRAM 37 88

006.ET602 BUILDING 6, SINGLE LINE AND BONDING RISER DIAGRAMS 38 88

007.ET400A BASEMENT LEVEL, MAIN COMPUTER ROOM 42, POWER AND TECHNOLOGY PLANS 39 88

007.ET400B BASEMENT LEVEL, MAIN COMPUTER ROOM 42, POWER AND DEMO PLAN 40 88

007.ET401 BUILDING 7, BASEMENT FLOOR, TELECOM ROOM 17 PLAN 41 88

007.ET402 BUILDING 7, FIRST FLOOR, TELECOM ROOM 1A-184A PLANS 42 88

007.ET403 BUILDING 7, FIRST FLOOR, TELECOM ROOM 1A-117 PLANS 43 88

007.ET404 BUILDING 7, FIRST FLOOR, TELECOM ROOM D-33 PLANS 44 88

007.ET405 BUILDING 7, SECOND FLOOR, TELECOM ROOM 267A PLANS 45 88

007.ET406 BUILDING 7, SECOND FLOOR, TELECOM ROOM 2M4 PLANS 46 88

007.ET407 BUILDING 7, THIRD FLOOR, TELECOM ROOM 373D PLANS 47 88

007.ET408 BUILDING 7, THIRD FLOOR, TELECOM ROOM 3M4 PLANS 48 88

007.ET409 BUILDING 7, FOURTH FLOOR, TELECOM ROOM 471A PLANS 49 88

007.ET410 BUILDING 7, FOURTH FLOOR, TELECOM ROOM 402 PLANS 50 88

007.ET601 BUILDING 7, TECHNOLOGY RISER DIAGRAM 51 88

007.ET602 BUILDING 7, SINGLE LINE DIAGRAMS 52 88

007.ET603 BUILDING 7, SINGLE LINE DIAGRAMS 53 88

007.ET604 BUILDING 7 BONDING RISER DIAGRAM 54 88

008.ET401 BUILDING 8, FIRST FLOOR, TELECOM ROOM 105C PLANS 55 88

008.ET601 BUILDING 8, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 56 88

009.ET401 BUILDING 9, FIRST FLOOR, TELECOM ROOM 135 PLANS 57 88

009.ET402 BUILDING 9, SECOND FLOOR, TELECOM ROOM 218 PLANS 58 88

009.ET403 BUILDING 9, THIRD FLOOR, TELECOM ROOM 315 PLANS 59 88

009.ET601 BUILDING 9, FIBER RISER DIAGRAM 60 88

009.ET602 BUILDING 9, SINGLE LINE AND BONDING RISER DIAGRAMS 61 88

013.ET401 BUILDING 13, TELECOM ENCLOSURE 6 PLANS 62 88

013.ET601 BUILDING 13, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 63 88

014.ET401 BUILDING 14, FIRST FLOOR, TELECOM ROOM 1A107 PLANS 64 88

014.ET601 BUILDING 14, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 65 88

015.ET401 BUILDING 15, FIRST FLOOR, TELECOM ROOM 7F PLANS 66 88

015.ET601 BUILDING 15, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 67 88

016.ET401 BUILDING 16, FIRST FLOOR, TELECOM ENCLOSURE 110B PLANS 68 88

016.ET601 BUILDING 16, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 69 88

045.ET401 BUILDING 45, FIRST FLOOR, TELECOM ROOM 170 70 88

045.ET402 BUILDING 45, FIRST FLOOR, TELECOM ROOM 173 71 88

045.ET403 BUILDING 45, SECOND FLOOR, TELECOM ROOM 268 72 88

045.ET404 BUILDING 45, SECOND FLOOR, TELECOM ROOM 272 73 88

045.ET601 BUILDING 45, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 74 88

046.ET401 BUILDING 46, THIRD FLOOR, TELECOM ENCLOSURE 302 PLANS 75 88

046.ET601 BUILDING 46, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 76 88

049.ET401 BUILDING 49, TELECOM ROOM 166 PLANS 77 88

W

AL

TE

R DAVID VAN SCOTER

REG. NO. 9953

Docusign Envelope ID: 7FA18971-B6F6-44A9-896C-7B85FF50EEA5

3/23/2026

120V DUPLEX RECEPTACLE

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

SPECIAL NORMAL POWER RECEPTACLE

208V DUPLEX RECEPTACLE18"

18"

120V SIMPLEX RECEPTACLE18"

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

EQUIPMENT CONNECTION

AS

NOTED

E

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

CLNG

J

J

J

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

SPECIAL EMERGENCY POWER RECEPTACLE18"

2' X 2' RECESSED ARCHITECTURAL TROFFER

2' X 4' RECESSED ARCHITECTURAL TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT LENS TROFFER

2' LINEAR - WALL MOUNTED

7'-0"

CENTER

4' LINEAR - WALL MOUNTED

7'-0"

CENTER

WALL SCONCE

6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

VS: VACANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

DR: DUAL RELAY

VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER

OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

4: 4 WAY

48"

CENTER

OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, LOW VOLTAGE, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

OS

OS

LS

4' LINEAR STRIP - SUSPENDED---

L L

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BIPHENYL

PC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

R RELOCATE/RELOCATED

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

2W TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCT CORRELATED COLOR TEMPERATURE

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

D DEMOLITION

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FU FUSE

FUDS FUSED SAFETY DISCONNECT

SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

HW HARD WIRED

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.

B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE APPROXIMATE ONLY (FIELD VERIFY).

C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK IN NEW WALLS AND WALLS WHERE THE SHEET ROCK IS REPLACED.

D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND

SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.

E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF CONDUITS

AND REMOVE WIRING.

F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.

G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR PLUG

CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.

H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR

PLUGGED.

I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL

BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE COR/VA.

J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO MEET THE

REQUIREMENTS AND INTENT OF THE PROJECT.

K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW

AREAS.

L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT. CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF

SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.

M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED.

PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH THIS REQUIREMENT.

N. IF POSSIBLE, ALL NEWLY INSTALLED ELECTRICAL BOXES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. IF NOT POSSIBLE, ALL NEWLY INSTALLED ELECTRICAL BOXES LOCATED IN COMMON STUD SPACES INSTALLED ON OPPOSITE SIDES OF FIRE-RESISTANCE-RATED WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC 300.21 AND IBC 714.4.2.

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA

STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL

ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO

SUIT THE PARTICULAR INSTALLATION.

5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING

CONSTRUCTION.

8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW

TERMINALS.

12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR

FINAL CONNECTIONS.

16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD

PARTY TESTING AGENCY.

17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.

PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE

PROVIDED.

19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".

21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.

A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE

REMOVED FROM THE PREMISES.

B. ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.

C. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH OTHER

TRADES.

D. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES

CONTINUATION THROUGH THE AREA.

E. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.

F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND

NEW CONSTRUCTION.

G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING

TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.

H. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.

I. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR

SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.

J. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:

A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.

B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.

C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.

D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.

E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT

OF FEED WITH AN ENGRAVED BRASS TAG.

F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.

K. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

/2

:3

:5

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts \0

.T

R R o o m D e ta ils

R ls ta rn e s C

B U

M B

.r v t

000.ET001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 88PDN

ELECTRONIC HEALTH

RECORD MODERNIZATION

(EHRM)

ALEXANDRIA VA HEALTH CARE SYSTEM

2495 SHREVEPORT HWY, 71N

PINEVILLE, LA 71360

MARCH 20, 2026

100% CONSTRUCTION DOCUMENTS

502-21-22220-398

VARIOUS

KTK

ELECTRICAL SYMBOL LEGEND

LIGHTING SYMBOL LEGEND ELECTRICAL ABBREVIATIONS LIST

ELECTRICAL SYMBOL NOTES GENERAL ELECTRICAL REMODELING NOTES

ELECTRICAL GENERAL NOTES

GENERAL ELECTRICAL DEMO NOTES

Docusign Envelope ID: 31EDC0F6-5827-45E5-8E99-758108BAC466

3/23/2026 3/23/2026

Date

MARCH 24, 2026

TECHNOLOGY SYMBOL LEGEND

DATA OUTLET - N-4 PR UTP

TELCO OUTLET - N-4 PR UTP

SYMBOL HEIGHT DESCRIPTION

18"

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SEE DRAWINGS FOR MORE INFORMATION.

NOTE: NOT ALL SYMBOLS ARE USED.

ELECTRONIC LOCKING MECHANISM

DOOR CONTACT

REQUEST FOR EXIT SENSOR

CARD READER

(K - KEYPAD)

48"CR

ES

DC

RX

WIRELESS ACCESS POINT - N-4 PR UTP

WALL PHONEW

N

TV OUTLET WALL MOUNTED

48"

CCTV DOME CAMERA FIXED

CCTV DOME CAMERA PAN/TILT/ZOOM

FOUR POST OIT EQUIPMENT RACK

OIT EQUIPMENT CABINET

MATV EQUIPMENT CABINET

CCTV EQUIPMENT CABINET

MATV

CCTV

LADDER CABLE TARY

N

N

FLOOR BOX FOR DATA

AS NOTED

DOOR

DOOR

ABOVE

DOOR

6' TO TOP

FLOOR

PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP

ELECTRONIC PANIC HARDWAREEP

DO DOOR OPERATOR

GROUND BUS

CEILING

DOOR

DOOR

FLOOR

FLOOR

FLOOR

ABOVE

CEILING

18"

4'x8'x3/4" FIRE RATED TTB8"

FLOOR TWO POST OIT EQUIPMENT RACK

SECURE WIRELESS ACCESS POINT - N-4 PR UTP

N

CEILING

S

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

CEILING

CEILING

CABLES AND CONNECTORS COLOR LEGEND

TELEPHONE

DESCRIPTION

ITEM JACK CABLE PATCH CABLES I.D. NOTES

DATA/COMPUTER

WIRELESS

ACCESS POINT

FIBER - MULTI-MODE

FIBER - SINGLE-MODE

CCTV - IP

IVORY

BLUE

GREEN

BLACK

IVORY

WHITE

IVORY

BLUE

GREEN

AQUA

YELLOW

WHITE

IVORY

BLUE

GREEN

AQUA

YELLOW

WHITE

T

C

WAP

FO

FO

CCTV

4 PAIR CABLE

CCTV

4 PAIR CABLE

4 PAIR CABLE

6/12/24/36

6/12

PACS N/A GRAY N/A PACS

MULTI COLOR

CONDUCTORS

ADO AUTOMATIC DOOR OPERATOR

AFF ABOVE FINISH FLOOR

BOD BASIS OF DESIGN

CCTV CLOSED CIRCUIT TELEVISION

COAX COAXIAL CABLE

COMM COMMUNICATION

COR CONTRACTING OFFICER REPRESENTATIVE

DC DOOR CONTACT SWITCH

DN DOWN

DO DOOR OPERATOR

DVC DIGITAL VOICE COMMAND

DVR DIGITAL VIDEO RECORDER

E EXISTING DEVICES

EEB EMERGENCY EXIT BUTTON

EL ELECTRICAL STRIKE

ETR EXISTING TO REMAIN

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FAAP FIRE ALARM ANNUNCIATOR PANEL

FO FIBER OPTIC

FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL

IT INTERCOMMUNICATION ROOM

MATV MASTER ANTENNA TELEVISION

MM MULTI MODE FIBER

NAC NETWORK APPLIANCE CIRCUIT PANEL

N NEW DEVICES

NCA NETWORK CONTROL ANNUNCIATOR

NS NO SCALE

NTS NOT TO SCALE

NVR NETWORK VIDEO RECORDER

TECHNOLOGY ABBREVIATIONS LIST

OC ON CENTER

OIT OFFICE OF INFORMATION TECHNOLOGY

PACS PHYSICAL ACCESS CONTROL SYSTEM

PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM

PB PUSH BUTTON

PBB PRIMARY BONDING BUSBAR

PDU RACK POWER DISTRIBUTION UNITS

POE POWER OVER ETHERNET

PR PAIR

RBB RACK BONDING BUSBAR

R RELOCATE

RL RELOCATED

RX REQUEST TO EXIT

SBB SECONDARY BONDING BUSBAR

SEP SERVICE ENTRANCE PROTECTION

SLC SIGNALING LINE CIRCUIT

SM SINGLE MODE FIBER

TBB TELECOM BONDING CONDUCTOR

TEL TELEPHONE

TGB TELECOM GROUND BUS BAR

TM TELEMONITORING

TMGB TELECOM MAIN GROUND BUS BAR

TP TWISTED PAIR

TR TELECOM ROOM

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

WM WIRE MANAGEMENT

WAP WIRELESS ACCESS POINT

UL UNDERWRITERS LABORATORY

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

TECHNOLOGY GENERAL NOTES

1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT

SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL LISTING

REQUIREMENT AND APPLICABLE BUILDING CODES.

4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION METHOD

MANUAL AND ANSI/TIA/EIA PUBLICATIONS.

5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758-B AND 607-D - GROUNDING AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS IN COMMERCIAL BUILDING.

6. COMPLY WITH THE LATEST ANSI/TIA/EIA 568-B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING STANDARD, AND ANSI/TIA-568-1.E - COMMERCIAL BUILDING TELECOMMUNICATIONS INFRASTRUCTURE.

7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569-E - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS

PATHWAYS AND SPACES.

8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.

9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.

10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.

11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.

12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN ACT".

13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.

15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY TESTING

AGENCY.

16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE MORE

STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.

17. PROVIDE TIA/EIA CAT 6A COPPER OUTLETS AND CONNECTORS.

18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6A KEYSTONE JACK WIRED PER T568B AS DIRECTED BY THE VA

COR.

19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606C EDITION AS WELL AS THE STANDARDS SET FORTH

BY THE VA HOSPITAL OIT.

20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.E.

21. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.

22. MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4".

23. DEVICES PLACED IN INTERCOMMUNICATION ROOM TO BE MOUNTED ON FIRE RETARDANT PLYWOOD.

24. PROVIDE OUTDOOR AND INDOOR CONDUITS, INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS FOR

A COMPLETE SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.

25. PROVIDE CABLE TRAY, LADDER TRAY J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING BOTH FIBER AND COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS, VERTICAL AND HORIZONTAL WIRE MANAGEMENT, GROUNDING BUS BARS, RACK MOUNTED GROUND BUS, GROUND CABLING, BONDING TO THE GROUNDING SYSTEM, GROUND CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, UPD'S, UPS'S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND AS

DESCRIBED IN THE SPECIFICATIONS.

26. PROVIDE J-HOOKS WHERE CABLE TRAY IS NOT SHOWN OR IF THERE IS OBSTRUCTION IN THE PATH OF THE CABLE TRAY, OR USE FLEXIBLE CONDUITS (NOT TO EXCEED 10 FEET), JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, COVER PLATES, LABELING, SUPPORT J-HOOKS AND CONDUITS EVERY 4-5 FEET, AS SHOWN HEREIN

AND AS DESCRIBED IN THE SPECIFICATIONS.

27. PROVIDE 12 PORT WALL MOUNTED COPPER PATCH PANEL I THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT IN EACH NEW TR AND RUN 12-4PR CAT 6A CABLE BETWEEN THESE TR'S TERMINATE AND TEST, LABEL EACH

PORT.

28. PROVIDE 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN EACH NEW TR AND RUN 12 STRAND FIBER CABLE BETWEEN THESE TELECOM ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.

29. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION SYSTEM (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN

AND AS DESCRIBED IN THE SPECIFICATIONS.

30. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMIANTIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.

31. PROVIDE NEW FIRE ALARM SYSTEM DEVIES, FIRE ALARM PANEL, NAC PANEL, POWER SUPPLY, FOR A COMPLETE FIRE AND DETECTION SYSTEM, RED CONDUIT AND JUNCTION BOXES, COVERPLATES, LABELING, CABLING BOTH COPPER AND FIBER, PROGRAMMING, SOFTWARE, LICENSES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, TESTING AND RELATED MATERIALS FOR SPECIFICATIONS.

32. CAMERAS SHALL BE PANORAMIC MULTI0SENSOR AND SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION ACT-

NDAA.

33. CONTRACTOR IS RESPONSIBLE FOR PROVIDING RECORD/AS-BUILT DRAWINGS AS PART OF CLOSEOUT SUBMITTALS SHOWING ALL NEW WORK AREA OUTLET LOCATIONS ON THE MOST UP-TO-DATE FLOOR PLAN.

34. PROVISION OF MULTI-SENSOR SSTV CAMERAS AS WELL AS ASSOCIATED NVR'S, STORAGE, SOFTWARE, AND LICENSES SHALL BE COORDINATED WITH AVIGILON. CONTACT LOCAL AVIGILON REPRESENTATIVE.

35. PROVISION OF CARD READERS AND ASSOCIATED DOOR SECURITY HARDWARE AS WELL AS ASSOCIATED HEAD

END EQUIPMENT SHALL BE COORDINATED WITH OPEN OPTIONS. CONTACT LOCAL OPEN SOURCE

REPRESENTATIVE.

36. PROVIDE 6 CISCO C9K-PWR-CAB-AC-US POWER CORDS FOR CISCO CATALYST 9300 SWITCHES PER TR.

37. WHERE THERE ARE HARD LID CEILINGS, PROVIDE FLEXIBLE CONDUIT FROM THE WORK AREA OUTLET TO THE

CABLE TRAY.

38. COORDINATE DOOR HARDWARE WITH THE EXISTING ELECTRIC KEY SYSTEM EMPLOYED BY THE VA. ALL DOOR

SECURIY HARDWARE SHALL INTEGRATE WITH THE ELECTRIC KEY SYSTEM.

39. TEN (10) SWITCHES WILL BE PROVIDED TO THE SITE TO ACCOMMODATE TRANSITIONING TELECOMMUNICATIONS

ROOMS.

40. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INSTALL COPPER PATCH CABLES IN ALL TELECOMMUNICATIONS ROOMS. ONE COPPER PATCH CABLE IS REQUIRED TO SERVE EVERY WORK AREA OUTLET, WIRELESS ACCESS POINT, AND ALL OTHER CONNECTION POINTS SERVED BY OIT NETWORK SWITCHES.

THE APPROXIMATE AMOUNT OF PATCH CABLES NEEDED IS 10,000 (VARYING LENGTHS OF 2, 4, AND 8 FEET) TO

REACH FROM THE SWITCH TO THE PATCH PANELS.

1. CONTRACTOR TO REFER TO TELECOMM ROOM PHASING NOTES, SHEETS G-002, FOR

ADDITIONAL INFOMATION.

2. CONTRACTOR TO REFER TO CIVIL DRAWINGS, SHEETS C-401-C-404, PARTIAL SITE PLAN -

PROPOSED EHRM LINES FOR EXTERIOR FIBER OPTIC PATHWAYS.

SEQUENCE 1 - DEMOLITION:

A. REMOVE LEGACY UNUSED EQUIPMENT FROM THE CABINETS LISTED BELOW. (CONFIRM WITH OIT THAT EQUIPMENT IS

OFFLINE AND CAN BE DEMOLISHED BEFORE COMMENCING WORK).

B. REMOVE EQUIPMENT FROM THE CABINETS TO ALLOW SPACE FOR NEW MDAS, HDAS, AND ED SERVER/NETWORK

CABINETS.

C. WITH ALL UNUSED SERVER EQUIPMENT REMOVED THE CABINETS SHALL BE DEMOLISHED TO MAKE ROOM FOR NEW MDA-A, HDA-A, AND ED SERVER/NETWORK.

SEQUENCE 1 - NEW WORK:

A. RELOCATE EQUIPMENT FROM RACKS/CABINETS 3. THESE RACKS/CABINETS CAN BE USED AS SWING SPACE FOR

EQUIPMENT DURING INTERIM PHASES.

B. WITH EXISTING DATA CENTER RACKS/CABINETS REMOVED THE NEW MDA-A, HDA-A, AND ED SERVER/NETWORK CABINETS CAN BE INSTALLED ALONG WITH THE FIBER AND COPPER CABLING FROM THE HDAS TO EACH SERVER CABINET.

SEQUENCES 2 & 3 - DEMOLITION:

A. WITH ALL UNUSED SERVER EQUIPMENT REMOVED THE FOLLOWING CABINETS SHALL BE DEMOLISHED TO MAKE ROOM FOR

NEW MDA-B, HDA-B, AND ED SERVER/NETWORK CABINETS.

SEQUENCES 2 & 3 - NEW WORK:

A. WITH EXISTING DATA CENTER RACK/CABINETS 3 AND 4 REMOVED THE NEW MDA-B, HDA-B, AND ED SERVER/NETWORK

CABINETS CAN BE INSTALLED ALONG WITH THE FIBER AND COPPER CABLING FROM THE HDAS TO EACH SERVER CABINET.

1. CONSTRUCTION SEQUENCING IS THE RESPONSIBILITY OF THE CONTRACTOR, IN COORDINATION WITH THE VA, UNLESS OTHERWISE STATED IN THIS DOCUMENT. THE TRADES INVOLVED INCLUDE BUT ARE NOT LIMITED TO, ARCHITECTURE, CIVIL, ELECTRICAL, MECHANICAL AND TELECOMMUNICATIONS. THE CONTRACTOR SHALL SUBMIT PROPOSED SEQUENCING PLANS FOR THE ENTIRE PROJECT AND FOR EACH EFFECTED AREA WITH DETAILED CONSTRUCTION SCHEDULES FOR REVIEW AND APPROVAL TO THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) 30 DAYS PRIOR TO BEGINNING WORK.

2. THE OPERATIONS OF THE FACILITY WILL CONTINUE WHILE CONSTRUCTION OCCURS. THE CONTRACTOR SHALL MAINTAIN A

PROTECTIVE DEMARCATION BETWEEN ACTIVE AND CONSTRUCTION AREAS DURING EACH PHASE.

3. GC WILL CONDUCT A PRE-CONSTRUCTION MEETING WITH THE COR TO IDENTIFY AREAS WHERE AFTER HOURS WORK WILL BE REQUIRED. AREAS INCLUDE, BUT NOT LIMITED TO: OCCUPIED SPACES WHERE CONSTRUCTION WOULD DISRUPT THE WORK ENVIRONMENT OF THE INDIVIDUAL OCCUPYING THE SPACE (OFFICES THAT OPERATE 8AM - 5 PM), FOR AREAS THAT

OPERATE 24/7 AND PUBLIC AREAS.

4. FIELD VERIFY ACTUAL CONDITIONS AND DIMENSIONS. NOTIFY COR OF ANY DEVIATIONS FROM DRAWINGS OR ANY

UNFORESEEN CONDITIONS THAT MAY CONFLICT WITH NEW WORK.

5. THE PROJECT CONDUITS OF SEQUENCING WITHIN THE DATA CENTER. THE CONTRACTOR SHALL REVIEW THE SEQUENCING NOTES PRIOR TO THE COMMENCEMENT OF ANY WORK AND DEVELOP A CONSTRUCTION SEQUENCING PLAN THAT DEMONSTRATES THE UNDERSTANDING OF THE RELATIONSHIPS AND CRITICAL RELATIONSHIPS BETWEEN THE AREAS OF

WORK.

6. THE EXISTING INFRASTRUCTURE SUPPORTING THE IT VOICE AND DATA NETWORK SHALL REMAIN FULLY OPERATIONAL UNTIL THE NEW INFRASTRUCTURE IS COMPLETE AND A COORDINATED CUTOVER SCHEDULE/PLAN HAS BEEN APPROVED BY THE LOCAL VA OFFICE OF INFORMATION TECHNOLOGY (OIT) AND COR. A CUTOVER SCHEDULE/PLAN SHALL BE SUBMITTED AND APPROVED BY THE VA A MINIMUM OF 30 DAYS BEFORE THE SCHEDULED CUTOVER IS TO COMMENCE.

7. ANY ELECTRICAL OUTAGE REQUEST SHALL BE SUBMITTED TO THE COR 14 CALENDAR DAYS IN ADVANCE. THE REQUEST SHALL INCLUDE THE BUILDING, THE ROOM NUMBER, THE PANEL NUMBER AND THE TIME PERIOD OF THE OUTAGE.

8. ANY INTERRUPTION TO THE EXISTING HVAC SERVICE SHALL BE SUBMITTED TO THE COR 14 CALENDAR DAYS IN ADVANCE.

THE REQUEST SHALL INCLUDE THE BUILDING, THE ROOM NUMBER, THE UNIT IDENTIFIER, AND THE TIME PERIOD OF THE

OUTAGE.

9. GC WILL PROVIDE AND INSTALL ICRA APPROVED, FIRE RATED, TEMPORARY CONSTRUCTION BARRIERS PRIOR TO START OF DEMOLITION AND REMAIN IN PLACE THROUGH COMPLETION OF NEW CONSTRUCTION OF EACH PHASE.

10. GC TO VERIFY AND SECURE RAISED ACCESS FLOORING IS STABLE AND PROVIDE REQUIRED HORIZONTAL BRACING AS

NEEDED FOR SUPPORT OF FLOORING TO REMAIN DURING EACH PHASE.

11. TELECOM SEQUENCING NOTES LISTED BELOW ARE FOR REFERENCE ONLY AND DO NOT DESCRIBE ALL DEMOLITION AND

NEW WORK TO BE COMPLETED WITH THIS PROJECT.

GENERAL TECHNOLOGY DEMOLITION AND REMODEL NOTES

A. ALL EXISTING CONDITIONS - INCLUDING EQUIPMENT, CABINETS, CABLE TRAY, DEVICES, AND CONDUIT - ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.

B. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. ALL OTHER MATERIAL SHALL BE REMOVED FROM THE PREMISES (E.G., PATCH PANELS, CABLES, COVER PLATES, PATCH CORDS, AND RELATED MATERIAL).

C. EXISTING CABLE TRAY SHALL REMAIN. REMOVE EXISTING CABLING SERVING WORK AREA OUTLETS (WAO). NO ABANDONED CABLING WILL BE ALLOWED TO REMAIN ABOVE THE CEILING. INSTALL NEW CABLE TRAY NEXT TO

THE EXISTING CABLE TRAY.

D. EXISTING CONDUIT AND SURFACE RACEWAY MAY BE REUSED FOR NEW WAO. COORDINATE LOCATION WITH THE

COR.

E. EXISTING TR: ONCE ALL ACTIVE CONNECTIONS TO AN EXISTING TR HAVE BEEN REPLACED BY CONNECTIONS TERMINATED IN THE NEW TR - AND OIT HAS CONFIRMED THAT THERE ARE NO LONGER ANY ACTIVE CONNECTIONS FROM THE EXISTING TR - COORDINATE REMOVAL OF ALL VA OWNED NETWORK SWITCHES. REMOVE PATCH PANELS AND ALL ASSOCIATED CABLING. BID DEMOLITION AND DISPOSAL OF THE RACKS IN THE TR UNLESS THERE ARE REMAINING NON-NETWORK COMPONENTS WHICH SHALL REMAIN IN PLACE WITH THE UPS AND POWER

SOURCE IN TACT.

F. EXISTING TR IDENTIFIED TO BE RENOVATED: PROTECT NETWORK RACK, EQUIPMENT, AND CABLING FROM DAMAGE, DUST, AND DEBRIS. MAINTAIN EXISTING PHYSICAL SECURITY DURING RENOVATION. NOTIFY THE COR

AND VA POLICE A MINIMUM OF 14 DAYS PRIOR TO ANY PHYSICAL SECURITY OUTAGES.

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

/2

:3

:5

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts \0

.T

R R o o m D e ta ils

R ls ta rn e s C

B U

M B

.r v t

000.ET002

TECHNOLOGY GENERAL NOTES,

SYMBOL LEGEND, AND

ABBREVIATIONS

2 88LAS

ELECTRONIC HEALTH

RECORD MODERNIZATION

(EHRM)

ALEXANDRIA VA HEALTH CARE SYSTEM

2495 SHREVEPORT HWY, 71N

PINEVILLE, LA 71360

MARCH 20, 2026

100% CONSTRUCTION DOCUMENTS

502-21-22220-398

VARIOUS

ADR

CONDITIONAL NOTES

TELECOM SEQUENCING NOTES

GENERAL SEQUENCING NOTES

CHANNEL RACK FRAME WHERE

EQUIPMENT IS MOUNTED.

CABLE WATERFALL

ATTACHED TO THE

TOP OF THE

CHANNEL RACK.

REAR EQUIPMENT

RAIL AT THE TOP OF

THE RACK.

6" VERTICAL WIRE MANAGEMENT. THE REAR

OF THE WIRE MANAGEMENT MOUNTS TO THE

FRONT OF THE CHANNEL RACK. THE CABLE

WATERFALL DIRECTS CABLING INTO THE

VERTICAL WIRE MANAGEMENT FROM THE TOP.

CHANNEL RACK SYMBOL NOTES

Docusign Envelope ID: 31EDC0F6-5827-45E5-8E99-758108BAC466

3/23/2026 3/23/2026

E

CR

DC ES RX

M

E

W

CR

DC ES RX

MD

10 10

PANEL 'A' PANEL 'B'

000.ET5016

SBB

K

A

B

A

B

A

B

B-25,27,29

A-25,27,29

B-7,9,11

A-7,9,11

B-13,15,17

A-13,15,17

B-2

A-2

B-2

A-2B-2

A-2

B-2

A-2

N

A

6FIRE RATED PATHWAYS

A

AA

J

PANEL A

MOTOR RATED

SWITCH

"B" PANEL"A" PANEL

SBB

BASKET TRAY

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R

15 15

1515 16

"B" PANEL

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

/2

:3

:5

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts \0

.T

R R o o m D e ta ils

R ls ta rn e s C

B U

M B

.r v t

000.ET501

TYPICAL TELECOM ROOM DETAILS

3 88PDN

ELECTRONIC HEALTH

RECORD MODERNIZATION

(EHRM)

ALEXANDRIA VA HEALTH CARE SYSTEM

2495 SHREVEPORT HWY, 71N

PINEVILLE, LA 71360

MARCH 20, 2026

100% CONSTRUCTION DOCUMENTS

502-21-22220-398

VARIOUS

KTK

1 ROOMS ARE COOLED WITH DUCTLESS

MINI-SPLITS. DUCTLESS MINI-SPLIT UNITS SHALL

BE POWERED FROM THEIR ASSOCIATED

OUTDOOR CONDENSING UNITS. PROVIDE A

CIRCUIT TO THE CONDENSING UNIT, INCLUDING

RACEWAYS AND CONDUCTORS TO POWER THE

INDOOR UNITS. SEE G SERIES SHEETS FOR MORE

INFORMATION.

2 TELECOMMUNICATIONS CHANNEL RACK, 24

INCHES WIDE, 30 INCHES DEEP, 84 INCHES HIGH,

45RU, WHITE. PROVIDE ORTRONICS (LEGRAND)

MM2073038-W, OR APPROVED EQUIVALENT.

CONTRACTOR SHALL COORDINATE ADDITIONAL

DETAILS INCLUDING, BUT NOT LIMITED TO

GROUNDING AND BONDING DETAILS, DATA

ELEVATIONS AND POWER ELEVATIONS IN THE

DRAWINGS.

3 VERTICAL CABLE MANAGEMENT CAGE WITH

DOOR, 6 INCHES WIDE, 84 INCHES HIGH, 45RU,

WHITE. PROVIDE ORTRONICS (LEGRAND)

MM20VMD706-W, OR APPROVED EQUIVALENT.

4 RACK POWER CONNECTION MOUNTED TO THE

CHANNEL STEEL ABOVE THE RACKS. MINIMUM 12"

AWAY FROM BASKET TRAY FOR EACH RACK.

PROVIDE L21-20R RECEPTACLE. PROVIDE (3) #12

AWG, (1) #10 AWG NEUTRAL, (1) #12 AWG GROUND

IN 3/4" CONDUIT. REFER TO RACK POWER

ELEVATION AND SCHEMATIC DIAGRAMS ON

SHEET 000.ET502 AND 000.ET505

5 SECONDARY BONDING BUSBAR TO BE LOCATED

BEHIND OR TO THE SIDE OF THE RACKS.

TELECOMMUNICATIONS EQUIPMENT SHALL BE

BONDED ACCORDING TO THE GROUNDING AND

BONDING DETAILS. REFER TO DETAILS 3 AND 4

ON SHEET 000.ET503 FOR MORE INFORMATION.

6 FIRE/SMOKE SLEEVE ASSEMBLIES. PROVIDE UL

LISTED ASSEMBLIES, STI EZ-PATH, SERIES 44+

FIRE-RATED PATHWAY, OR APPROVED

EQUIVALENT. INSTALL SLEEVES AT AN ELEVATION

COORDINATED TO BE ABOVE EXISTING CEILING

HEIGHT IN THE ADJACENT CORRIDOR. REFER TO

ET400 SERIES SHEETS FOR QUANTITIES. DO NOT

PLACE FIRE/SMOKE SLEEVE ASSEMBLIES OVER

DOORS TO AVOID COLLISION WITH ACCESS

CONTROL CONDUITS AND BOXES.

7 PROVIDE NEW 24 BASKET TRAY AROUND THE

ROOM AND ABOVE THE CHANNEL RACKS, WITH

WATERFALL DROPOUTS INTO EACH RACK, 90

DEGREE CORNERS AND ALL RELATED FITTINGS,

SEE BASKET TRAY DETAIL ON 000.ET504 FOR

MORE INFO.

B.O.D.: CABLEOFIL CF105/600 SERIES OR

EQUIVALENT.

8 PROVIDE JUNCTION BOX FOR THE PACS DOOR

CONTROLLER.

9 PAINTED FIRE RETARDANT PLYWOOD

BACKBOARD. SEE ARCHITECTURAL.

10 LIGHTING AND APPLIANCE PANELBOARDS.

PROVIDE PANELS MOUNTED ON CHANNEL STEEL

SUPPORTS, UNLESS NOTED OTHERWISE ON THE

ET400 SERIES SHEETS. PANEL 'A' SHALL BE FED

FROM A SOURCE WITH GENERATOR BACKUP, AND

PANEL 'B' SHALL BE FED FROM A NORMAL UTILITY

SOURCE.

11 PROVIDE EMERGENCY CIRCUIT POWER TO THE

TR PACS DOOR CONTROLLER.

12 PROVIDE MULTI SENSOR CAMERA AND CONNECT

TO EXISTING CAMERA SYSTEM. LOCATION

SHOULD BE COORDINATED WITH THE CHANNEL

RACK LAYOUT AND OIT.

13 PROVIDE CABLING FOR VA FURNISHED WIRELESS

ACCESS POINT.

14 PROVIDE RECEPTACLE NEAR DOOR, WITH POWER

EXTENDED FROM AN EXISTING CONVENIENCE

OUTLET CIRCUIT ORIGINATING FROM A PANEL

NOT IN THE TELECOM ROOM.

15 BASKET TRAY IS SHOWN OFFSET FOR GRAPHICAL

PURPOSES ONLY. INSTALL TRAY FLUSH WITH

WALL, EXCEPT ABOVE POWER PANELS AND

MECHANICAL EQUIPMENT WHERE SPACE IS

NEEDED FOR PIPES AND CONDUIT.

16 PROVIDE MOTION SENSOR FOR REQUEST TO EXIT

(RX) DOOR RELEASE.

17 LIGHTING IS TO BE FED VIA NEAREST

EMERGENCY CIRCUIT OUTSIDE OF THE TE/TR.

(TYPICAL ALL)

Scale: No Scale

ELECTRICAL FLOOR PLAN - TYPICAL 3-RACK TR

Scale: No Scale

ELECTRICAL CEILING PLAN - TYPICAL 3-RACK TR

Scale: No Scale

PLAN WEST ELEVATION

Scale: No Scale

PLAN NORTH ELEVATION

Scale: No Scale

PLAN SOUTH ELEVATION

Scale: No Scale

PLAN EAST ELEVATION

PER PHASE CONNECTED LOAD: 3.21 kVA 2.63 kVA 3.09 kVA

SPACE -- 1 41 -- -- 42 1 -- SPACE

SPACE -- 1 39 -- -- 40 1 -- SPACE

SPACE -- 1 37 -- -- 38 1 -- SPACE

SPACE -- 1 35 -- -- 36 1 -- SPACE

SPACE -- 1 33 -- -- 34 1 -- SPACE

SPACE -- 1 31 -- -- 32 1 -- SPACE

29 0 -- 30 1 -- SPACE

27 0 -- 28 1 -- SPACE

SPARE

(SEE PANEL NOTE 1 BELOW)

20 A 3

25 0 -- 26 1 -- SPACE

23 0.83 -- 24 1 -- SPACE

21 0.83 -- 22 1 -- SPACERACK RECEPTACLE (L21-20) 20 A 3

19 0.83 0 20 1 20 A SPARE

17 0.83 0 18 1 20 A SPARE

15 0.83 0 16 1 20 A SPARERACK RECEPTACLE (L21-20) 20 A 3

13 0.83 0 14 1 20 A SPARE

11 0.83 0 12 1 20 A SPARE

9 0.83 0 10RACK RECEPTACLE (L21-20) 20 A 3

7 0.83 0 8

2 30 A SPARE (SEE NOTE 2)

5 0 0.6 6 1 20 A TELECOM ROOM PACS EQUIPMENT

3 0 0.14 4 1 20 A SPARE

SURGE PROTECTION DEVICE

(SEE PANEL NOTE 4 BELOW)

30 A 3

1 0 0.72 2 1 20 A TELECOM ROOM RCPT

LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME

ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction

MOUNTING: SURFACE FED FROM: LOCATION:

PANEL: A

VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC:

10,000 AMPS

SYMMETRICAL

PER PHASE CONNECTED LOAD: 3.21 kVA 2.67 kVA 2.49 kVA

SPACE -- 1 41 -- -- 42 1 -- SPACE

SPACE -- 1 39 -- -- 40 1 -- SPACE

SPACE -- 1 37 -- -- 38 1 -- SPACE

SPACE -- 1 35 -- -- 36 1 -- SPACE

SPACE -- 1 33 -- -- 34 1 -- SPACE

SPACE -- 1 31 -- -- 32 1 -- SPACE

29 0 -- 30 1 -- SPACE

27 0 -- 28 1 -- SPACE

SPARE

(SEE PANEL NOTE 1 BELOW)

20 A 3

25 0 -- 26 1 -- SPACE

This is the start of the file's text. The full file is on GovTribe.