Attachment 8 - Vol 4 Drawings.pdf
PDF 15 MB Posted
- Solicitation number
- 36C77626R0104
About this file
This is a construction document set (Volume 4 Drawings) for the Electronic Health Record Modernization (EHRM) infrastructure upgrades at the Alexandria VA Health Care System in Pineville, Louisiana, dated March 24, 2026, at 100% construction document phase. The drawings cover electrical, telecommunications, and technology infrastructure improvements across multiple buildings (1-9, 13-16, 45-46, 49, 136, 142, 147, 171) and include detailed plans, riser diagrams, bonding details, and equipment specifications.
The electrical scope includes new power panels with generator backup capability, UPS systems, and rack power distribution units for telecommunications rooms. Technology infrastructure requires Cat 6A copper cabling with 8-pin keystone jacks, fiber optic backbone systems with 24-strand armored single-mode cables, wireless access points, physical access control systems (PACS), and multi-sensor surveillance cameras that comply with the National Defense Authorization Act. Telecommunications rooms feature channel racks (24" wide, 30" deep, 84" high), basket cable trays, bonding busbars per ANSI/TIA 607-D standards, and equipment mounted on fire-retardant plywood. The specifications mandate compliance with NEC, NFPA standards, TIA/EIA cabling standards, and VA standards. The contractor must provide comprehensive cabling, conduit, supports, fire-rated sleeve assemblies, grounding and bonding materials, testing, labeling, and as-built documentation. Construction sequencing requires coordination with ongoing facility operations, with electrical outages requiring 14-day advance notification and a cutover plan approved 30 days prior to implementation.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:3
:1
A
M C
U s e rs \l s ta rn e s \D o c u m e n ts
\M S
-3
E
H R
M ls ta rn e s C
B U
M B
.r v t
G-001.4
COVER VOLUME 4
1 1MEL
ELECTRONIC HEALTH
RECORD MODERNIZATION
(EHRM)
ALEXANDRIA VA HEALTH CARE SYSTEM
2495 SHREVEPORT HWY, 71N
PINEVILLE, LA 71360
MARCH 24, 2026
100% CONSTRUCTION DOCUMENTS
502-21-22220-398
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
ALEXANDRIA VA HEALTH CARE SYSTEM
2495 SHREVEPORT HWY, 71N
PINEVILLE, LA 71360
VA PROJECT #: 502-21-222
WVS
VOLUME 4
VOLUME 4 OF 4
SHEET LIST
SHEET NUMBER SHEET NAME DWG OF DWG
049.ET601 BUILDING 49, FIBER AND BONDING RISER DIAGRAMS 78 88
049.ET602 BUILDING 49, SINGLE LINE DIAGRAM 79 88
136.ET401 BUILDING 136, FIRST FLOOR, TELECOM ROOM 32 PLANS 80 88
136.ET601 BUILDING 136, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 81 88
142.ET401 BUILDING 142, FIRST FLOOR, TELECOM ENCLOSURE ROOM 7B PLANS 82 88
142.ET601 BUILDING 142, FIBER RISER DIAGRAM 83 88
142.ET602 BUILDING 142, SINGLE LINE AND BONDING RISER DIAGRAMS 84 88
147.ET401 BUILDING 147, FIRST FLOOR, TELECOM ENCLOSURE 102 PLANS 85 88
147.ET601 BUILDING 147, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 86 88
171.ET401 BUILDING 171, FIRST FLOOR, TELECOM ENCLOSURE 108 PLANS 87 88
171.ET601 BUILDING 171, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 88 88
SHEET LIST
SHEET NUMBER SHEET NAME DWG OF DWG
GENERAL
G-001.4 COVER VOLUME 4 1 1
ELECTRICAL
000.ET001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 88
000.ET002 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 2 88
000.ET501 TYPICAL TELECOM ROOM DETAILS 3 88
000.ET502 ELECTRICAL DETAILS 4 88
000.ET503 ELECTRICAL DETAILS 5 88
000.ET504 TECHNOLOGY DETAILS 6 88
000.ET505 CHANNEL RACK DETAILS 7 88
000.ET506 SITE TECHNOLOGY DETAILS 8 88
000.ES101 OUTDOOR BUILDING FIBER LOOP DIAGRAM 9 88
001.ET401 BUILDING 1, FIRST FLOOR, TELECOM ROOM 103 PLANS 10 88
001.ET402 BUILDING 1, SECOND FLOOR, TELECOM ROOM 202 PLANS 11 88
001.ET601 BUILDING 1, FIBER RISER DIAGRAM 12 88
001.ET602 BUILDING 1, SINGLE LINE AND BONDING RISER DIAGRAMS 13 88
002.ET401 BUILDING 2, FIRST FLOOR, TELECOM ROOM 133 PLANS 14 88
002.ET402 BUILDING 2, SECOND FLOOR, TELECOM ROOM 256 PLANS 15 88
002.ET403 BUILDING 2, THIRD FLOOR, TELECOM ROOM 359 PLANS 16 88
002.ET404 BUILDING 2, FOURTH FLOOR, TELECOM ROOM 424 PLANS 17 88
002.ET601 BUILDING 2, FIBER RISER DIAGRAM 18 88
002.ET602 BUILDING 2, SINGLE LINE AND BONDING RISER DIAGRAMS 19 88
003.ET401 BUILDING 3, FIRST FLOOR, TELECOM ROOM 105 PLANS 20 88
003.ET402 BUILDING 3, SECOND FLOOR, TELECOM ROOM 205 PLANS 21 88
003.ET403 BUILDING 3, THIRD FLOOR, TELECOM ROOM 305 PLANS 22 88
003.ET601 BUILDING 3, FIBER RISER DIAGRAM 23 88
003.ET602 BUILDING 3, SINGLE LINE AND BONDING RISER DIAGRAM 24 88
004.ET401 BUILDING 4, FIRST FLOOR, TELECOM ROOM 102E PLANS 25 88
004.ET601 BUILDING 4, FIBER RISER DIAGRAM 26 88
004.ET602 BUILDING 4, SINGLE LINE AND BONDING RISER DIAGRAMS 27 88
005.ET401 BUILDING 5, BASEMENT FLOOR, TELECOM ROOM G06A PLANS 28 88
005.ET402 BUILDING 5, FIRST FLOOR, TELECOM ROOM 110A PLANS 29 88
005.ET403 BUILDING 5, SECOND FLOOR, TELECOM ROOM 212C PLANS 30 88
005.ET601 BUILDING 5, FIBER RISER DIAGRAM 31 88
005.ET602 BUILDING 5, SINGLE LINE AND BONDING RISER DIAGRAMS 32 88
006.ET401 BUILDING 6, BASEMENT FLOOR, TELECOM ROOM 008 PLANS 33 88
006.ET402 BUILDING 6, FIRST FLOOR, TELECOM ROOM 101 PLANS 34 88
006.ET403 BUILDING 6, SECOND FLOOR, TELECOM ROOM 201 PLANS 35 88
006.ET404 BUILDING 6, THIRD FLOOR, TELECOM ROOM 310 PLANS 36 88
006.ET601 BUILDING 6, FIBER RISER DIAGRAM 37 88
006.ET602 BUILDING 6, SINGLE LINE AND BONDING RISER DIAGRAMS 38 88
007.ET400A BASEMENT LEVEL, MAIN COMPUTER ROOM 42, POWER AND TECHNOLOGY PLANS 39 88
007.ET400B BASEMENT LEVEL, MAIN COMPUTER ROOM 42, POWER AND DEMO PLAN 40 88
007.ET401 BUILDING 7, BASEMENT FLOOR, TELECOM ROOM 17 PLAN 41 88
007.ET402 BUILDING 7, FIRST FLOOR, TELECOM ROOM 1A-184A PLANS 42 88
007.ET403 BUILDING 7, FIRST FLOOR, TELECOM ROOM 1A-117 PLANS 43 88
007.ET404 BUILDING 7, FIRST FLOOR, TELECOM ROOM D-33 PLANS 44 88
007.ET405 BUILDING 7, SECOND FLOOR, TELECOM ROOM 267A PLANS 45 88
007.ET406 BUILDING 7, SECOND FLOOR, TELECOM ROOM 2M4 PLANS 46 88
007.ET407 BUILDING 7, THIRD FLOOR, TELECOM ROOM 373D PLANS 47 88
007.ET408 BUILDING 7, THIRD FLOOR, TELECOM ROOM 3M4 PLANS 48 88
007.ET409 BUILDING 7, FOURTH FLOOR, TELECOM ROOM 471A PLANS 49 88
007.ET410 BUILDING 7, FOURTH FLOOR, TELECOM ROOM 402 PLANS 50 88
007.ET601 BUILDING 7, TECHNOLOGY RISER DIAGRAM 51 88
007.ET602 BUILDING 7, SINGLE LINE DIAGRAMS 52 88
007.ET603 BUILDING 7, SINGLE LINE DIAGRAMS 53 88
007.ET604 BUILDING 7 BONDING RISER DIAGRAM 54 88
008.ET401 BUILDING 8, FIRST FLOOR, TELECOM ROOM 105C PLANS 55 88
008.ET601 BUILDING 8, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 56 88
009.ET401 BUILDING 9, FIRST FLOOR, TELECOM ROOM 135 PLANS 57 88
009.ET402 BUILDING 9, SECOND FLOOR, TELECOM ROOM 218 PLANS 58 88
009.ET403 BUILDING 9, THIRD FLOOR, TELECOM ROOM 315 PLANS 59 88
009.ET601 BUILDING 9, FIBER RISER DIAGRAM 60 88
009.ET602 BUILDING 9, SINGLE LINE AND BONDING RISER DIAGRAMS 61 88
013.ET401 BUILDING 13, TELECOM ENCLOSURE 6 PLANS 62 88
013.ET601 BUILDING 13, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 63 88
014.ET401 BUILDING 14, FIRST FLOOR, TELECOM ROOM 1A107 PLANS 64 88
014.ET601 BUILDING 14, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 65 88
015.ET401 BUILDING 15, FIRST FLOOR, TELECOM ROOM 7F PLANS 66 88
015.ET601 BUILDING 15, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 67 88
016.ET401 BUILDING 16, FIRST FLOOR, TELECOM ENCLOSURE 110B PLANS 68 88
016.ET601 BUILDING 16, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 69 88
045.ET401 BUILDING 45, FIRST FLOOR, TELECOM ROOM 170 70 88
045.ET402 BUILDING 45, FIRST FLOOR, TELECOM ROOM 173 71 88
045.ET403 BUILDING 45, SECOND FLOOR, TELECOM ROOM 268 72 88
045.ET404 BUILDING 45, SECOND FLOOR, TELECOM ROOM 272 73 88
045.ET601 BUILDING 45, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 74 88
046.ET401 BUILDING 46, THIRD FLOOR, TELECOM ENCLOSURE 302 PLANS 75 88
046.ET601 BUILDING 46, SINGLE LINE, FIBER RISER, AND BONDING RISER DIAGRAMS 76 88
049.ET401 BUILDING 49, TELECOM ROOM 166 PLANS 77 88
W
AL
TE
R DAVID VAN SCOTER
REG. NO. 9953
Docusign Envelope ID: 7FA18971-B6F6-44A9-896C-7B85FF50EEA5
3/23/2026
120V DUPLEX RECEPTACLE
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
SPECIAL NORMAL POWER RECEPTACLE
208V DUPLEX RECEPTACLE18"
18"
120V SIMPLEX RECEPTACLE18"
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
EQUIPMENT CONNECTION
AS
NOTED
E
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
SPECIAL EMERGENCY POWER RECEPTACLE18"
2' X 2' RECESSED ARCHITECTURAL TROFFER
2' X 4' RECESSED ARCHITECTURAL TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT LENS TROFFER
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
VS: VACANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
DR: DUAL RELAY
VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER
OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, LOW VOLTAGE, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
OS
OS
LS
4' LINEAR STRIP - SUSPENDED---
L L
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HW HARD WIRED
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.
B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE APPROXIMATE ONLY (FIELD VERIFY).
C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK IN NEW WALLS AND WALLS WHERE THE SHEET ROCK IS REPLACED.
D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND
SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.
E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF CONDUITS
AND REMOVE WIRING.
F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.
G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR PLUG
CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.
H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR
PLUGGED.
I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL
BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE COR/VA.
J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO MEET THE
REQUIREMENTS AND INTENT OF THE PROJECT.
K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW
AREAS.
L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT. CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF
SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.
M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED.
PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH THIS REQUIREMENT.
N. IF POSSIBLE, ALL NEWLY INSTALLED ELECTRICAL BOXES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. IF NOT POSSIBLE, ALL NEWLY INSTALLED ELECTRICAL BOXES LOCATED IN COMMON STUD SPACES INSTALLED ON OPPOSITE SIDES OF FIRE-RESISTANCE-RATED WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC 300.21 AND IBC 714.4.2.
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO
SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.
PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE
REMOVED FROM THE PREMISES.
B. ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
C. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH OTHER
TRADES.
D. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES
CONTINUATION THROUGH THE AREA.
E. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND
NEW CONSTRUCTION.
G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING
TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.
H. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.
I. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR
SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
J. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT
OF FEED WITH AN ENGRAVED BRASS TAG.
F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.
K. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:3
:5
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts \0
.T
R R o o m D e ta ils
R ls ta rn e s C
B U
M B
.r v t
000.ET001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 88PDN
ELECTRONIC HEALTH
RECORD MODERNIZATION
(EHRM)
ALEXANDRIA VA HEALTH CARE SYSTEM
2495 SHREVEPORT HWY, 71N
PINEVILLE, LA 71360
MARCH 20, 2026
100% CONSTRUCTION DOCUMENTS
502-21-22220-398
VARIOUS
KTK
ELECTRICAL SYMBOL LEGEND
LIGHTING SYMBOL LEGEND ELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES GENERAL ELECTRICAL REMODELING NOTES
ELECTRICAL GENERAL NOTES
GENERAL ELECTRICAL DEMO NOTES
Docusign Envelope ID: 31EDC0F6-5827-45E5-8E99-758108BAC466
3/23/2026 3/23/2026
Date
MARCH 24, 2026
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
TELCO OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
ELECTRONIC LOCKING MECHANISM
DOOR CONTACT
REQUEST FOR EXIT SENSOR
CARD READER
(K - KEYPAD)
48"CR
ES
DC
RX
WIRELESS ACCESS POINT - N-4 PR UTP
WALL PHONEW
N
TV OUTLET WALL MOUNTED
48"
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
FOUR POST OIT EQUIPMENT RACK
OIT EQUIPMENT CABINET
MATV EQUIPMENT CABINET
CCTV EQUIPMENT CABINET
MATV
CCTV
LADDER CABLE TARY
N
N
FLOOR BOX FOR DATA
AS NOTED
DOOR
DOOR
ABOVE
DOOR
6' TO TOP
FLOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
ELECTRONIC PANIC HARDWAREEP
DO DOOR OPERATOR
GROUND BUS
CEILING
DOOR
DOOR
FLOOR
FLOOR
FLOOR
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RATED TTB8"
FLOOR TWO POST OIT EQUIPMENT RACK
SECURE WIRELESS ACCESS POINT - N-4 PR UTP
N
CEILING
S
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
CEILING
CEILING
CABLES AND CONNECTORS COLOR LEGEND
TELEPHONE
DESCRIPTION
ITEM JACK CABLE PATCH CABLES I.D. NOTES
DATA/COMPUTER
WIRELESS
ACCESS POINT
FIBER - MULTI-MODE
FIBER - SINGLE-MODE
CCTV - IP
IVORY
BLUE
GREEN
BLACK
IVORY
WHITE
IVORY
BLUE
GREEN
AQUA
YELLOW
WHITE
IVORY
BLUE
GREEN
AQUA
YELLOW
WHITE
T
C
WAP
FO
FO
CCTV
4 PAIR CABLE
CCTV
4 PAIR CABLE
4 PAIR CABLE
6/12/24/36
6/12
PACS N/A GRAY N/A PACS
MULTI COLOR
CONDUCTORS
ADO AUTOMATIC DOOR OPERATOR
AFF ABOVE FINISH FLOOR
BOD BASIS OF DESIGN
CCTV CLOSED CIRCUIT TELEVISION
COAX COAXIAL CABLE
COMM COMMUNICATION
COR CONTRACTING OFFICER REPRESENTATIVE
DC DOOR CONTACT SWITCH
DN DOWN
DO DOOR OPERATOR
DVC DIGITAL VOICE COMMAND
DVR DIGITAL VIDEO RECORDER
E EXISTING DEVICES
EEB EMERGENCY EXIT BUTTON
EL ELECTRICAL STRIKE
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FO FIBER OPTIC
FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
IT INTERCOMMUNICATION ROOM
MATV MASTER ANTENNA TELEVISION
MM MULTI MODE FIBER
NAC NETWORK APPLIANCE CIRCUIT PANEL
N NEW DEVICES
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
TECHNOLOGY ABBREVIATIONS LIST
OC ON CENTER
OIT OFFICE OF INFORMATION TECHNOLOGY
PACS PHYSICAL ACCESS CONTROL SYSTEM
PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM
PB PUSH BUTTON
PBB PRIMARY BONDING BUSBAR
PDU RACK POWER DISTRIBUTION UNITS
POE POWER OVER ETHERNET
PR PAIR
RBB RACK BONDING BUSBAR
R RELOCATE
RL RELOCATED
RX REQUEST TO EXIT
SBB SECONDARY BONDING BUSBAR
SEP SERVICE ENTRANCE PROTECTION
SLC SIGNALING LINE CIRCUIT
SM SINGLE MODE FIBER
TBB TELECOM BONDING CONDUCTOR
TEL TELEPHONE
TGB TELECOM GROUND BUS BAR
TM TELEMONITORING
TMGB TELECOM MAIN GROUND BUS BAR
TP TWISTED PAIR
TR TELECOM ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
WM WIRE MANAGEMENT
WAP WIRELESS ACCESS POINT
UL UNDERWRITERS LABORATORY
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
TECHNOLOGY GENERAL NOTES
1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT
SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL LISTING
REQUIREMENT AND APPLICABLE BUILDING CODES.
4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION METHOD
MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758-B AND 607-D - GROUNDING AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
6. COMPLY WITH THE LATEST ANSI/TIA/EIA 568-B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING STANDARD, AND ANSI/TIA-568-1.E - COMMERCIAL BUILDING TELECOMMUNICATIONS INFRASTRUCTURE.
7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569-E - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS
PATHWAYS AND SPACES.
8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN ACT".
13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY TESTING
AGENCY.
16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE MORE
STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.
17. PROVIDE TIA/EIA CAT 6A COPPER OUTLETS AND CONNECTORS.
18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6A KEYSTONE JACK WIRED PER T568B AS DIRECTED BY THE VA
COR.
19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606C EDITION AS WELL AS THE STANDARDS SET FORTH
BY THE VA HOSPITAL OIT.
20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.E.
21. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
22. MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4".
23. DEVICES PLACED IN INTERCOMMUNICATION ROOM TO BE MOUNTED ON FIRE RETARDANT PLYWOOD.
24. PROVIDE OUTDOOR AND INDOOR CONDUITS, INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS FOR
A COMPLETE SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.
25. PROVIDE CABLE TRAY, LADDER TRAY J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING BOTH FIBER AND COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS, VERTICAL AND HORIZONTAL WIRE MANAGEMENT, GROUNDING BUS BARS, RACK MOUNTED GROUND BUS, GROUND CABLING, BONDING TO THE GROUNDING SYSTEM, GROUND CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, UPD'S, UPS'S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND AS
DESCRIBED IN THE SPECIFICATIONS.
26. PROVIDE J-HOOKS WHERE CABLE TRAY IS NOT SHOWN OR IF THERE IS OBSTRUCTION IN THE PATH OF THE CABLE TRAY, OR USE FLEXIBLE CONDUITS (NOT TO EXCEED 10 FEET), JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, COVER PLATES, LABELING, SUPPORT J-HOOKS AND CONDUITS EVERY 4-5 FEET, AS SHOWN HEREIN
AND AS DESCRIBED IN THE SPECIFICATIONS.
27. PROVIDE 12 PORT WALL MOUNTED COPPER PATCH PANEL I THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT IN EACH NEW TR AND RUN 12-4PR CAT 6A CABLE BETWEEN THESE TR'S TERMINATE AND TEST, LABEL EACH
PORT.
28. PROVIDE 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN EACH NEW TR AND RUN 12 STRAND FIBER CABLE BETWEEN THESE TELECOM ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.
29. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION SYSTEM (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN
AND AS DESCRIBED IN THE SPECIFICATIONS.
30. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMIANTIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
31. PROVIDE NEW FIRE ALARM SYSTEM DEVIES, FIRE ALARM PANEL, NAC PANEL, POWER SUPPLY, FOR A COMPLETE FIRE AND DETECTION SYSTEM, RED CONDUIT AND JUNCTION BOXES, COVERPLATES, LABELING, CABLING BOTH COPPER AND FIBER, PROGRAMMING, SOFTWARE, LICENSES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, TESTING AND RELATED MATERIALS FOR SPECIFICATIONS.
32. CAMERAS SHALL BE PANORAMIC MULTI0SENSOR AND SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION ACT-
NDAA.
33. CONTRACTOR IS RESPONSIBLE FOR PROVIDING RECORD/AS-BUILT DRAWINGS AS PART OF CLOSEOUT SUBMITTALS SHOWING ALL NEW WORK AREA OUTLET LOCATIONS ON THE MOST UP-TO-DATE FLOOR PLAN.
34. PROVISION OF MULTI-SENSOR SSTV CAMERAS AS WELL AS ASSOCIATED NVR'S, STORAGE, SOFTWARE, AND LICENSES SHALL BE COORDINATED WITH AVIGILON. CONTACT LOCAL AVIGILON REPRESENTATIVE.
35. PROVISION OF CARD READERS AND ASSOCIATED DOOR SECURITY HARDWARE AS WELL AS ASSOCIATED HEAD
END EQUIPMENT SHALL BE COORDINATED WITH OPEN OPTIONS. CONTACT LOCAL OPEN SOURCE
REPRESENTATIVE.
36. PROVIDE 6 CISCO C9K-PWR-CAB-AC-US POWER CORDS FOR CISCO CATALYST 9300 SWITCHES PER TR.
37. WHERE THERE ARE HARD LID CEILINGS, PROVIDE FLEXIBLE CONDUIT FROM THE WORK AREA OUTLET TO THE
CABLE TRAY.
38. COORDINATE DOOR HARDWARE WITH THE EXISTING ELECTRIC KEY SYSTEM EMPLOYED BY THE VA. ALL DOOR
SECURIY HARDWARE SHALL INTEGRATE WITH THE ELECTRIC KEY SYSTEM.
39. TEN (10) SWITCHES WILL BE PROVIDED TO THE SITE TO ACCOMMODATE TRANSITIONING TELECOMMUNICATIONS
ROOMS.
40. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INSTALL COPPER PATCH CABLES IN ALL TELECOMMUNICATIONS ROOMS. ONE COPPER PATCH CABLE IS REQUIRED TO SERVE EVERY WORK AREA OUTLET, WIRELESS ACCESS POINT, AND ALL OTHER CONNECTION POINTS SERVED BY OIT NETWORK SWITCHES.
THE APPROXIMATE AMOUNT OF PATCH CABLES NEEDED IS 10,000 (VARYING LENGTHS OF 2, 4, AND 8 FEET) TO
REACH FROM THE SWITCH TO THE PATCH PANELS.
1. CONTRACTOR TO REFER TO TELECOMM ROOM PHASING NOTES, SHEETS G-002, FOR
ADDITIONAL INFOMATION.
2. CONTRACTOR TO REFER TO CIVIL DRAWINGS, SHEETS C-401-C-404, PARTIAL SITE PLAN -
PROPOSED EHRM LINES FOR EXTERIOR FIBER OPTIC PATHWAYS.
SEQUENCE 1 - DEMOLITION:
A. REMOVE LEGACY UNUSED EQUIPMENT FROM THE CABINETS LISTED BELOW. (CONFIRM WITH OIT THAT EQUIPMENT IS
OFFLINE AND CAN BE DEMOLISHED BEFORE COMMENCING WORK).
B. REMOVE EQUIPMENT FROM THE CABINETS TO ALLOW SPACE FOR NEW MDAS, HDAS, AND ED SERVER/NETWORK
CABINETS.
C. WITH ALL UNUSED SERVER EQUIPMENT REMOVED THE CABINETS SHALL BE DEMOLISHED TO MAKE ROOM FOR NEW MDA-A, HDA-A, AND ED SERVER/NETWORK.
SEQUENCE 1 - NEW WORK:
A. RELOCATE EQUIPMENT FROM RACKS/CABINETS 3. THESE RACKS/CABINETS CAN BE USED AS SWING SPACE FOR
EQUIPMENT DURING INTERIM PHASES.
B. WITH EXISTING DATA CENTER RACKS/CABINETS REMOVED THE NEW MDA-A, HDA-A, AND ED SERVER/NETWORK CABINETS CAN BE INSTALLED ALONG WITH THE FIBER AND COPPER CABLING FROM THE HDAS TO EACH SERVER CABINET.
SEQUENCES 2 & 3 - DEMOLITION:
A. WITH ALL UNUSED SERVER EQUIPMENT REMOVED THE FOLLOWING CABINETS SHALL BE DEMOLISHED TO MAKE ROOM FOR
NEW MDA-B, HDA-B, AND ED SERVER/NETWORK CABINETS.
SEQUENCES 2 & 3 - NEW WORK:
A. WITH EXISTING DATA CENTER RACK/CABINETS 3 AND 4 REMOVED THE NEW MDA-B, HDA-B, AND ED SERVER/NETWORK
CABINETS CAN BE INSTALLED ALONG WITH THE FIBER AND COPPER CABLING FROM THE HDAS TO EACH SERVER CABINET.
1. CONSTRUCTION SEQUENCING IS THE RESPONSIBILITY OF THE CONTRACTOR, IN COORDINATION WITH THE VA, UNLESS OTHERWISE STATED IN THIS DOCUMENT. THE TRADES INVOLVED INCLUDE BUT ARE NOT LIMITED TO, ARCHITECTURE, CIVIL, ELECTRICAL, MECHANICAL AND TELECOMMUNICATIONS. THE CONTRACTOR SHALL SUBMIT PROPOSED SEQUENCING PLANS FOR THE ENTIRE PROJECT AND FOR EACH EFFECTED AREA WITH DETAILED CONSTRUCTION SCHEDULES FOR REVIEW AND APPROVAL TO THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) 30 DAYS PRIOR TO BEGINNING WORK.
2. THE OPERATIONS OF THE FACILITY WILL CONTINUE WHILE CONSTRUCTION OCCURS. THE CONTRACTOR SHALL MAINTAIN A
PROTECTIVE DEMARCATION BETWEEN ACTIVE AND CONSTRUCTION AREAS DURING EACH PHASE.
3. GC WILL CONDUCT A PRE-CONSTRUCTION MEETING WITH THE COR TO IDENTIFY AREAS WHERE AFTER HOURS WORK WILL BE REQUIRED. AREAS INCLUDE, BUT NOT LIMITED TO: OCCUPIED SPACES WHERE CONSTRUCTION WOULD DISRUPT THE WORK ENVIRONMENT OF THE INDIVIDUAL OCCUPYING THE SPACE (OFFICES THAT OPERATE 8AM - 5 PM), FOR AREAS THAT
OPERATE 24/7 AND PUBLIC AREAS.
4. FIELD VERIFY ACTUAL CONDITIONS AND DIMENSIONS. NOTIFY COR OF ANY DEVIATIONS FROM DRAWINGS OR ANY
UNFORESEEN CONDITIONS THAT MAY CONFLICT WITH NEW WORK.
5. THE PROJECT CONDUITS OF SEQUENCING WITHIN THE DATA CENTER. THE CONTRACTOR SHALL REVIEW THE SEQUENCING NOTES PRIOR TO THE COMMENCEMENT OF ANY WORK AND DEVELOP A CONSTRUCTION SEQUENCING PLAN THAT DEMONSTRATES THE UNDERSTANDING OF THE RELATIONSHIPS AND CRITICAL RELATIONSHIPS BETWEEN THE AREAS OF
WORK.
6. THE EXISTING INFRASTRUCTURE SUPPORTING THE IT VOICE AND DATA NETWORK SHALL REMAIN FULLY OPERATIONAL UNTIL THE NEW INFRASTRUCTURE IS COMPLETE AND A COORDINATED CUTOVER SCHEDULE/PLAN HAS BEEN APPROVED BY THE LOCAL VA OFFICE OF INFORMATION TECHNOLOGY (OIT) AND COR. A CUTOVER SCHEDULE/PLAN SHALL BE SUBMITTED AND APPROVED BY THE VA A MINIMUM OF 30 DAYS BEFORE THE SCHEDULED CUTOVER IS TO COMMENCE.
7. ANY ELECTRICAL OUTAGE REQUEST SHALL BE SUBMITTED TO THE COR 14 CALENDAR DAYS IN ADVANCE. THE REQUEST SHALL INCLUDE THE BUILDING, THE ROOM NUMBER, THE PANEL NUMBER AND THE TIME PERIOD OF THE OUTAGE.
8. ANY INTERRUPTION TO THE EXISTING HVAC SERVICE SHALL BE SUBMITTED TO THE COR 14 CALENDAR DAYS IN ADVANCE.
THE REQUEST SHALL INCLUDE THE BUILDING, THE ROOM NUMBER, THE UNIT IDENTIFIER, AND THE TIME PERIOD OF THE
OUTAGE.
9. GC WILL PROVIDE AND INSTALL ICRA APPROVED, FIRE RATED, TEMPORARY CONSTRUCTION BARRIERS PRIOR TO START OF DEMOLITION AND REMAIN IN PLACE THROUGH COMPLETION OF NEW CONSTRUCTION OF EACH PHASE.
10. GC TO VERIFY AND SECURE RAISED ACCESS FLOORING IS STABLE AND PROVIDE REQUIRED HORIZONTAL BRACING AS
NEEDED FOR SUPPORT OF FLOORING TO REMAIN DURING EACH PHASE.
11. TELECOM SEQUENCING NOTES LISTED BELOW ARE FOR REFERENCE ONLY AND DO NOT DESCRIBE ALL DEMOLITION AND
NEW WORK TO BE COMPLETED WITH THIS PROJECT.
GENERAL TECHNOLOGY DEMOLITION AND REMODEL NOTES
A. ALL EXISTING CONDITIONS - INCLUDING EQUIPMENT, CABINETS, CABLE TRAY, DEVICES, AND CONDUIT - ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
B. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. ALL OTHER MATERIAL SHALL BE REMOVED FROM THE PREMISES (E.G., PATCH PANELS, CABLES, COVER PLATES, PATCH CORDS, AND RELATED MATERIAL).
C. EXISTING CABLE TRAY SHALL REMAIN. REMOVE EXISTING CABLING SERVING WORK AREA OUTLETS (WAO). NO ABANDONED CABLING WILL BE ALLOWED TO REMAIN ABOVE THE CEILING. INSTALL NEW CABLE TRAY NEXT TO
THE EXISTING CABLE TRAY.
D. EXISTING CONDUIT AND SURFACE RACEWAY MAY BE REUSED FOR NEW WAO. COORDINATE LOCATION WITH THE
COR.
E. EXISTING TR: ONCE ALL ACTIVE CONNECTIONS TO AN EXISTING TR HAVE BEEN REPLACED BY CONNECTIONS TERMINATED IN THE NEW TR - AND OIT HAS CONFIRMED THAT THERE ARE NO LONGER ANY ACTIVE CONNECTIONS FROM THE EXISTING TR - COORDINATE REMOVAL OF ALL VA OWNED NETWORK SWITCHES. REMOVE PATCH PANELS AND ALL ASSOCIATED CABLING. BID DEMOLITION AND DISPOSAL OF THE RACKS IN THE TR UNLESS THERE ARE REMAINING NON-NETWORK COMPONENTS WHICH SHALL REMAIN IN PLACE WITH THE UPS AND POWER
SOURCE IN TACT.
F. EXISTING TR IDENTIFIED TO BE RENOVATED: PROTECT NETWORK RACK, EQUIPMENT, AND CABLING FROM DAMAGE, DUST, AND DEBRIS. MAINTAIN EXISTING PHYSICAL SECURITY DURING RENOVATION. NOTIFY THE COR
AND VA POLICE A MINIMUM OF 14 DAYS PRIOR TO ANY PHYSICAL SECURITY OUTAGES.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:3
:5
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts \0
.T
R R o o m D e ta ils
R ls ta rn e s C
B U
M B
.r v t
000.ET002
TECHNOLOGY GENERAL NOTES,
SYMBOL LEGEND, AND
ABBREVIATIONS
2 88LAS
ELECTRONIC HEALTH
RECORD MODERNIZATION
(EHRM)
ALEXANDRIA VA HEALTH CARE SYSTEM
2495 SHREVEPORT HWY, 71N
PINEVILLE, LA 71360
MARCH 20, 2026
100% CONSTRUCTION DOCUMENTS
502-21-22220-398
VARIOUS
ADR
CONDITIONAL NOTES
TELECOM SEQUENCING NOTES
GENERAL SEQUENCING NOTES
CHANNEL RACK FRAME WHERE
EQUIPMENT IS MOUNTED.
CABLE WATERFALL
ATTACHED TO THE
TOP OF THE
CHANNEL RACK.
REAR EQUIPMENT
RAIL AT THE TOP OF
THE RACK.
6" VERTICAL WIRE MANAGEMENT. THE REAR
OF THE WIRE MANAGEMENT MOUNTS TO THE
FRONT OF THE CHANNEL RACK. THE CABLE
WATERFALL DIRECTS CABLING INTO THE
VERTICAL WIRE MANAGEMENT FROM THE TOP.
CHANNEL RACK SYMBOL NOTES
Docusign Envelope ID: 31EDC0F6-5827-45E5-8E99-758108BAC466
3/23/2026 3/23/2026
E
CR
DC ES RX
M
E
W
CR
DC ES RX
MD
10 10
PANEL 'A' PANEL 'B'
000.ET5016
SBB
K
A
B
A
B
A
B
B-25,27,29
A-25,27,29
B-7,9,11
A-7,9,11
B-13,15,17
A-13,15,17
B-2
A-2
B-2
A-2B-2
A-2
B-2
A-2
N
A
6FIRE RATED PATHWAYS
A
AA
J
PANEL A
MOTOR RATED
SWITCH
"B" PANEL"A" PANEL
SBB
BASKET TRAY
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
15 15
1515 16
"B" PANEL
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:3
:5
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts \0
.T
R R o o m D e ta ils
R ls ta rn e s C
B U
M B
.r v t
000.ET501
TYPICAL TELECOM ROOM DETAILS
3 88PDN
ELECTRONIC HEALTH
RECORD MODERNIZATION
(EHRM)
ALEXANDRIA VA HEALTH CARE SYSTEM
2495 SHREVEPORT HWY, 71N
PINEVILLE, LA 71360
MARCH 20, 2026
100% CONSTRUCTION DOCUMENTS
502-21-22220-398
VARIOUS
KTK
1 ROOMS ARE COOLED WITH DUCTLESS
MINI-SPLITS. DUCTLESS MINI-SPLIT UNITS SHALL
BE POWERED FROM THEIR ASSOCIATED
OUTDOOR CONDENSING UNITS. PROVIDE A
CIRCUIT TO THE CONDENSING UNIT, INCLUDING
RACEWAYS AND CONDUCTORS TO POWER THE
INDOOR UNITS. SEE G SERIES SHEETS FOR MORE
INFORMATION.
2 TELECOMMUNICATIONS CHANNEL RACK, 24
INCHES WIDE, 30 INCHES DEEP, 84 INCHES HIGH,
45RU, WHITE. PROVIDE ORTRONICS (LEGRAND)
MM2073038-W, OR APPROVED EQUIVALENT.
CONTRACTOR SHALL COORDINATE ADDITIONAL
DETAILS INCLUDING, BUT NOT LIMITED TO
GROUNDING AND BONDING DETAILS, DATA
ELEVATIONS AND POWER ELEVATIONS IN THE
DRAWINGS.
3 VERTICAL CABLE MANAGEMENT CAGE WITH
DOOR, 6 INCHES WIDE, 84 INCHES HIGH, 45RU,
WHITE. PROVIDE ORTRONICS (LEGRAND)
MM20VMD706-W, OR APPROVED EQUIVALENT.
4 RACK POWER CONNECTION MOUNTED TO THE
CHANNEL STEEL ABOVE THE RACKS. MINIMUM 12"
AWAY FROM BASKET TRAY FOR EACH RACK.
PROVIDE L21-20R RECEPTACLE. PROVIDE (3) #12
AWG, (1) #10 AWG NEUTRAL, (1) #12 AWG GROUND
IN 3/4" CONDUIT. REFER TO RACK POWER
ELEVATION AND SCHEMATIC DIAGRAMS ON
SHEET 000.ET502 AND 000.ET505
5 SECONDARY BONDING BUSBAR TO BE LOCATED
BEHIND OR TO THE SIDE OF THE RACKS.
TELECOMMUNICATIONS EQUIPMENT SHALL BE
BONDED ACCORDING TO THE GROUNDING AND
BONDING DETAILS. REFER TO DETAILS 3 AND 4
ON SHEET 000.ET503 FOR MORE INFORMATION.
6 FIRE/SMOKE SLEEVE ASSEMBLIES. PROVIDE UL
LISTED ASSEMBLIES, STI EZ-PATH, SERIES 44+
FIRE-RATED PATHWAY, OR APPROVED
EQUIVALENT. INSTALL SLEEVES AT AN ELEVATION
COORDINATED TO BE ABOVE EXISTING CEILING
HEIGHT IN THE ADJACENT CORRIDOR. REFER TO
ET400 SERIES SHEETS FOR QUANTITIES. DO NOT
PLACE FIRE/SMOKE SLEEVE ASSEMBLIES OVER
DOORS TO AVOID COLLISION WITH ACCESS
CONTROL CONDUITS AND BOXES.
7 PROVIDE NEW 24 BASKET TRAY AROUND THE
ROOM AND ABOVE THE CHANNEL RACKS, WITH
WATERFALL DROPOUTS INTO EACH RACK, 90
DEGREE CORNERS AND ALL RELATED FITTINGS,
SEE BASKET TRAY DETAIL ON 000.ET504 FOR
MORE INFO.
B.O.D.: CABLEOFIL CF105/600 SERIES OR
EQUIVALENT.
8 PROVIDE JUNCTION BOX FOR THE PACS DOOR
CONTROLLER.
9 PAINTED FIRE RETARDANT PLYWOOD
BACKBOARD. SEE ARCHITECTURAL.
10 LIGHTING AND APPLIANCE PANELBOARDS.
PROVIDE PANELS MOUNTED ON CHANNEL STEEL
SUPPORTS, UNLESS NOTED OTHERWISE ON THE
ET400 SERIES SHEETS. PANEL 'A' SHALL BE FED
FROM A SOURCE WITH GENERATOR BACKUP, AND
PANEL 'B' SHALL BE FED FROM A NORMAL UTILITY
SOURCE.
11 PROVIDE EMERGENCY CIRCUIT POWER TO THE
TR PACS DOOR CONTROLLER.
12 PROVIDE MULTI SENSOR CAMERA AND CONNECT
TO EXISTING CAMERA SYSTEM. LOCATION
SHOULD BE COORDINATED WITH THE CHANNEL
RACK LAYOUT AND OIT.
13 PROVIDE CABLING FOR VA FURNISHED WIRELESS
ACCESS POINT.
14 PROVIDE RECEPTACLE NEAR DOOR, WITH POWER
EXTENDED FROM AN EXISTING CONVENIENCE
OUTLET CIRCUIT ORIGINATING FROM A PANEL
NOT IN THE TELECOM ROOM.
15 BASKET TRAY IS SHOWN OFFSET FOR GRAPHICAL
PURPOSES ONLY. INSTALL TRAY FLUSH WITH
WALL, EXCEPT ABOVE POWER PANELS AND
MECHANICAL EQUIPMENT WHERE SPACE IS
NEEDED FOR PIPES AND CONDUIT.
16 PROVIDE MOTION SENSOR FOR REQUEST TO EXIT
(RX) DOOR RELEASE.
17 LIGHTING IS TO BE FED VIA NEAREST
EMERGENCY CIRCUIT OUTSIDE OF THE TE/TR.
(TYPICAL ALL)
Scale: No Scale
ELECTRICAL FLOOR PLAN - TYPICAL 3-RACK TR
Scale: No Scale
ELECTRICAL CEILING PLAN - TYPICAL 3-RACK TR
Scale: No Scale
PLAN WEST ELEVATION
Scale: No Scale
PLAN NORTH ELEVATION
Scale: No Scale
PLAN SOUTH ELEVATION
Scale: No Scale
PLAN EAST ELEVATION
PER PHASE CONNECTED LOAD: 3.21 kVA 2.63 kVA 3.09 kVA
SPACE -- 1 41 -- -- 42 1 -- SPACE
SPACE -- 1 39 -- -- 40 1 -- SPACE
SPACE -- 1 37 -- -- 38 1 -- SPACE
SPACE -- 1 35 -- -- 36 1 -- SPACE
SPACE -- 1 33 -- -- 34 1 -- SPACE
SPACE -- 1 31 -- -- 32 1 -- SPACE
29 0 -- 30 1 -- SPACE
27 0 -- 28 1 -- SPACE
SPARE
(SEE PANEL NOTE 1 BELOW)
20 A 3
25 0 -- 26 1 -- SPACE
23 0.83 -- 24 1 -- SPACE
21 0.83 -- 22 1 -- SPACERACK RECEPTACLE (L21-20) 20 A 3
19 0.83 0 20 1 20 A SPARE
17 0.83 0 18 1 20 A SPARE
15 0.83 0 16 1 20 A SPARERACK RECEPTACLE (L21-20) 20 A 3
13 0.83 0 14 1 20 A SPARE
11 0.83 0 12 1 20 A SPARE
9 0.83 0 10RACK RECEPTACLE (L21-20) 20 A 3
7 0.83 0 8
2 30 A SPARE (SEE NOTE 2)
5 0 0.6 6 1 20 A TELECOM ROOM PACS EQUIPMENT
3 0 0.14 4 1 20 A SPARE
SURGE PROTECTION DEVICE
(SEE PANEL NOTE 4 BELOW)
30 A 3
1 0 0.72 2 1 20 A TELECOM ROOM RCPT
LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME
ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction
MOUNTING: SURFACE FED FROM: LOCATION:
PANEL: A
VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC:
10,000 AMPS
SYMMETRICAL
PER PHASE CONNECTED LOAD: 3.21 kVA 2.67 kVA 2.49 kVA
SPACE -- 1 41 -- -- 42 1 -- SPACE
SPACE -- 1 39 -- -- 40 1 -- SPACE
SPACE -- 1 37 -- -- 38 1 -- SPACE
SPACE -- 1 35 -- -- 36 1 -- SPACE
SPACE -- 1 33 -- -- 34 1 -- SPACE
SPACE -- 1 31 -- -- 32 1 -- SPACE
29 0 -- 30 1 -- SPACE
27 0 -- 28 1 -- SPACE
SPARE
(SEE PANEL NOTE 1 BELOW)
20 A 3
25 0 -- 26 1 -- SPACE