This is a product specification sheet for a Mitsubishi Electric Trane HVAC heat pump system comprised of two integrated units: the PKA-AK36NL wall-mounted indoor unit and the PUZ-AK36NL outdoor unit. The indoor unit delivers 33,400 BTU/h rated cooling capacity and features swing mode air distribution, auto vane control for temperature optimization, horizontal vane control, three-speed fan adjustment, and dual set point programming capability. The outdoor heat pump unit provides 36,000 BTU/h rated capacity and incorporates an inverter-driven compressor, blue fin anti-corrosion coating, and seacoast protection for salt and sulfur resistance. Both units are ENERGY STAR certified with efficiency ratings of SEER2 20.30, EER2 12, and HSPF2 [IV] 9.40.

The system operates on 208/230V, 1-phase, 60Hz electrical service with a recommended 35A fuse/breaker size and uses R454B refrigerant pre-charged at 9 lbs 14 oz with maximum piping length of 165 feet. Cooling performance at 95°F yields maximum capacity of 36,000 BTU/h with 3,110W maximum power input, while heating at 47°F provides 40,000 BTU/h maximum capacity. The outdoor unit weighs 224 lbs and measures 41-11/32" W x 14" D x 52-43/64" H. Extensive accessories are available including condensate removal pumps, control interfaces (thermostats, wireless controllers, BACnet interfaces), drain solutions, linesets of various lengths (10-100 feet), wind baffles for cold-weather operation, and mounting hardware. The specification sheet indicates all dimensions, electrical parameters, noise levels, airflow rates, and refrigerant requirements needed for system design and installation.

View the file

Other files

File Type Posted
Amendment 0007.pdf PDF
RFI Update 10-7-26.pdf PDF
ME_SUBMITTAL_PKA-AK24NL_PUZ-AH24NL_XbtyE.pdf PDF
RFI Responses.pdf PDF
Amendment 0006.pdf PDF
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0003.pdf PDF
Site Visit Agenda.pdf PDF
Site Visit Sign In Sheet 8-20-26.pdf PDF
Attachment 11 - Site Visit Details.docx DOCX document
Attachment 11 - Site Visit Details.docx DOCX document
Amendment 0002.pdf PDF
Amendment 0001.pdf PDF
Attachment 4 - Vol 3 Drawings.pdf PDF
Attachment 7 - Key Subcontractor Information.docx DOCX document
Attachment 8 - Key Personnel.docx DOCX document
Attachment 11 - Site Visit Details.docx DOCX document
Attachment 5 - Vol 4 Drawings.pdf PDF
Attachment 3 - Volume 2 Drawings.pdf PDF
Attachment 9 - Division Pricing Template.xlsx XLSX spreadsheet
Attachment 6 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 10 - Wage Determination.pdf PDF
Attachment 10 - Key Subcontractor Information.docx DOCX document
Attachment 13 - Wage Determination.pdf PDF
Attachment 12 - Division Pricing Template.xlsx XLSX spreadsheet
Attachment 14 - Site Visit Details.docx DOCX document
Attachment 2 - Vol 1 Drawings.pdf PDF
36C77626R0104.pdf PDF
Attachment 5 - Vol 2 Drawings Part 3.pdf PDF
Attachment 9 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 11 - Key Personnel.docx DOCX document
Attachment 1 - Specifications.pdf PDF
Attachment 4 - Vol 2 Drawings Part 2.pdf PDF
Attachment 6 - Vol 2 Drawings Part 4.pdf PDF
Attachment 8 - Vol 4 Drawings.pdf PDF
Attachment 3 - Vol 2 Drawings.pdf PDF
Attachment 7 - Vol 3 Drawings.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

PKA-AK36NL & PUZ-AK36NL

33,400 BTU/H WALL-MOUNTED INDOOR UNIT

36,000 BTU/H HEAT PUMP OUTDOOR UNIT

Job Name:

System Reference: Date:

INDOOR Unit ... PKA-AK36NL

OUTDOOR Unit ... PUZ-AK36NL

INDOOR UNIT FEATURES

Swing Mode: An indoor unit with this capability can move air throughout the room like an oscillating fan.

Auto Vane Control: Auto Vane Control allows the indoor unit vanes to be moved left, right, up, and down to provide even temperatures throughout a space.

Light Commercial: Light commercial applications include small offices, restaurants, and retail.

Horizontal Vane Control: Horizontal Vane Control allows the indoor unit vanes to be moved left right to provide even temperatures throughout a space.

Three Speed Fan: Adjust the fan between three speed settings to optimal comfort.

Dual Set Point: The controller can be used to program two different set points. The unit will automatically adjust between the set points for optimum comfort.

OUTDOOR UNIT FEATURES

Inverter Driven Compressor: Inverter technology uses only the precise amount of energy needed to keep a space comfortable.

Blue Fin Coating: Anti-corrosion coating that protects the outdoor heat exchanger against salt, sulfur, and other airborne contaminants that impact the efficiency and performance of the outdoor units.

Seacoast Protection: Designed to protect against the corrosive effects of environments that are in close proximity to the sea.

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PKA-AK36NL & PUZ-AK36NL

Cooling at 95F1

Maximum Capacity Btu/h 36000

Rated Capacity Btu/h 33400

Minimum Capacity Btu/h 13200

Maximum Power Input W 3110

Rated Power Input W 2770

Moisture Removal Pints/h 12

Sensible Heat Factor 0.61

Power Factor [208V / 230V] % 98 / 98

Heating at 47F2

Maximum Capacity Btu/h 40000

Rated Capacity Btu/h 40000

Minimum Capacity Btu/h 13200

Maximum Power Input W 2859

Rated Power Input W 2859

Power Factor [208V / 230V] % 98 / 98

Heating at 17F3

Maximum Capacity Btu/h 23200

Rated Capacity Btu/h 23200

Maximum Power Input W 2400

Rated Power Input W 2400

Heating at 5F5 Maximum Capacity Btu/h 20000

Maximum Power Input W 2120

Heating at -4F6 Maximum Capacity Btu/h 17600

Efficiency

SEER2 20.30

EER21 12

HSPF2 [IV] 9.40

COP at 47°F2 4.10

COP at 17°F at Maximum Capacity3 2.80

COP at 5°F at Maximum Capacity5 2.70

COP at -4°F at Maximum Capacity6 2.56

ENERGY STAR® Certified Yes

Electrical

Voltage, Phase, Frequency V AC / V AC , ø , Hz 208 / 230 , 1 , 60

Guaranteed Voltage Range V AC 198 - 253

Voltage: Indoor - Outdoor, S1-S2 V AC 208/230

Voltage: Indoor - Outdoor, S2-S3 V DC 12-24

Short-circuit Current Rating [SCCR] kA 5

Recommended Fuse/Breaker Size (Outdoor) A 35

Recommended Wire Size [Indoor - Outdoor] AWG 14

Indoor Unit

Fan Motor Output W 69

Fan Motor Type DC Motor

Airflow Rate at Cooling, Dry CFM 705 , 810 , 920

Airflow Rate at Cooling, Wet CFM 705 , 810 , 920

Airflow Rate at Heating, Dry CFM 705 , 810 , 920

Sound Pressure Level [Cooling] dB (A) 43 , 46 , 49

Sound Pressure Level [Heating] dB (A) 43 , 46 , 49

External Static Pressure in.WG

Dual Barrier Coating on Fan No

External Finish Color 0.7PB 9.2/0.4

Unit Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]

46-1/16 x 11-5/8 x 14-3/8 [ 1170 x 295 x 365 ]

Package Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]

51-3/16 x 14-3/16 x 18-9/16 [ 1300 x 360 x 470 ]

Unit Weight lbs [ kg ] 46 [ 21 ]

Package Weight lbs [ kg ] 51 [ 23 ]

IDU Operating Temp. Range Cooling Intake Air Temp [Maximum / Minimum] deg F , deg F / deg F

, deg F 90 , 73 / 66 , 59

Heating Intake Air Temp [Maximum / Minimum] deg F 82 / 50

Outdoor Unit

MCA A 34

MOCP A 56

Fan Motor Full Load Amperage A

Notes

1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB - test 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB 5Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB *Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): • Wind baffles required to operate below 23°F DB in cooling mode. • Heat pump system with wind baffle: 0°F - 115°F. • Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): • System cuts out in heating mode and automatically restarts at these temperatures.

6Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PKA-AK36NL & PUZ-AK36NL

Outdoor Unit

Fan Motor Output W 74+74

Airflow Rate Cooling CFM 3910

Airflow Rate Heating CFM 3910

Defrost Method Reverse Cycle

Coating on Heat Exchanger (Bluefin, Sea Coast) Yes , Yes

Sound Pressure Level, Cooling1 dB (A) 52

Sound Pressure Level, Heating2 dB (A) 53

Compressor Type Twin Rotary

Compressor Model MRB36FEGMC

Compressor Oil [Type // Charge] // oz RM68EH // 45

External Finish Color Munsell 3Y 7.8/1.1

Base Pan Heater Optional

Unit Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]

41-11/32 x 14 x 52-43/64 [ 1050 x 355 x 1338 ]

Package Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]

42-15/16 x 17-3/4 x 58-5/16 [ 1090 x 450 x 1480 ]

Unit Weight lbs [ kg ] 224 [ 102 ]

Package Weight lbs [ kg ] 251 [ 114 ]

ODU Operating Temp. Range

Cooling Intake Air Temp [Maximum / Minimum*] F 115 / 23

Cooling Thermal Lock-out / Re-start Temperatures** F

Heating Intake Air Temp [Maximum / Minimum] F , F / F , F 70 , 59 / -4 , -4

Heating Thermal Lock-out / Re-start Temperatures** F -13 / -4

Refrigerant

Type R454B

Pre-Charged Refrigerant Amount lbs , oz 9 , 14

Maximum Pre-Charged Piping Length ft [ m ] 100 [ 30 ]

Additional Refrigerant Charge Per Additional Piping Length oz/ft 0.6

Piping

Gas Pipe Size O.D. [Flared] inch [ mm ] 5/8 [ 15.88 ]

Liquid Pipe Size O.D. [Flared] inch [ mm ] 3/8 [ 9.52 ]

Maximum Piping Length ft [ m ] 165 [ 50 ]

Maximum Height Difference ft [ m ] 100 [ 30 ]

Maximum Number of Bends 15

Notes

1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB - test 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB 5Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB *Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): • Wind baffles required to operate below 23°F DB in cooling mode. • Heat pump system with wind baffle: 0°F - 115°F. • Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): • System cuts out in heating mode and automatically restarts at these temperatures.

6Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

INDOOR UNIT ACCESSORIES: PKA-AK36NL

Condensate

Refco Condensate Removal Pump with Wall Mount Enclosure 120-240V up to 120k BTU/h GOBI-II

Blue Diamond (MaxiBlue Advanced) Mini Condensate Pump w/ Reservoir & Sensor (110V) up to 48,000 BTU/H [recommended] X87-711

Blue Diamond MegaBlue Condensate Pump with Reservoir Sensor 115-230V up to 170k BTU/h X87-835

Sauermann Condensate Pump 120-230V up to 60k BTU/h SI30-230

Blue Diamond MaxiBlue Condensate Pump with Reservoir Sensor 115-230V up to 48k BTU/h X88-721

Drain Pan Level Sensor/Control SS610E

Blue Diamond Sensor Extension Cable 15 Ft C13-103

Refco Condensate Pump 100-240V up to 120k BTU/h COMBI

Control Interface

Thermostat Interface for 3rd Party Thermostats PAC-US445CN-1

Airzone Wired Blueface Controller Black AZZBSBLUEZEROCN

Wireless Interface 2 for Comfrot app PAC-USWHS002-WF-2

IT Extender PAC-WHS01IE-E

Airzone Wireless Think Controller White AZZBSTHINKRB

Airzone Wireless Lite Controller Black AZZBSLITERN

Airzone Wired Blueface Controller White AZZBSBLUEZEROCB kumo station® for Comfort app PAC-WHS01HC-E

Airzone Wireless Lite Controller White AZZBSLITERB

Airzone Wireless Think Controller Black AZZBSTHINKRN

Procon BACnet® and Modbus® Interface PAC-UKPRC001-CN-1

Disconnect Switch 30A600VUL fits 2 X 4 utility box - Black TAZ-MS303

(30A/600V/UL) [fits 2” X 4” utility box] - White TAZ-MS303W

Drain Hose Flexible Mini-Split Drain Hose DRX-16

Lineset

3/8 x 5/8 Lineset Twin-Tube Insulation - 15 feet MPLS385812T-15

3/8 x 5/8 Lineset Twin-Tube Insulation - 50 feet MPLS385812T-50

3/8 x 5/8 Lineset Twin-Tube Insulation - 65 feet MPLS385812T-65

3/8 x 5/8 Lineset Twin-Tube Insulation - 30 feet MPLS385812T-30

3/8 x 5/8 Lineset Twin-Tube Insulation - 10 feet MPLS385812T-10

3/8 x 5/8 Lineset Twin-Tube Insulation - 100 feet MPLS385812T-100

Mini-Split Wire 14 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW144-250

14 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW144-50

N/A Unknown

Remote Sensor

Wireless temperature and humidity sensor for Comfort app PAC-USWHS003-TH-1

Wall Mounted Remote Temperature Sensor PAC-SE41TS-E

Flush Mount Remote Temperature Sensor for SEZ SLZ SVZ and all P-Series models PAC-USSEN002-FM-1

Terminal Signal Adapter

3-Pin Wiring Harness PAC-715AD

Backup Heat Relay Kit CN24RELAY-KIT-CM3

5-Pin Wiring Harness PAC-725AD

Wired Remote Controller

Deluxe MA Wired Remote Controller PAR-42MAAUB

Simple MA Remote Controller PAC-YT53CRAU-J

Simple Direct Wired Remote Controller PAC-SDW01RC-1

Touch MA Remote Controller PAR-CT01MAU-SB

Wireless Remote Controller

Wireless RedLINK™ Remote Controller MHK2

Lockdown Bracket for Wireless Handheld Remote Controllers RCMKP1CB

Wireless Remote Contoller PAR-SL101A-E

Wireless MA Handheld Remote Controller (requires PAR-FA32MA-E) PAR-FL32MA-E

Notes

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

OUTDOOR UNIT ACCESSORIES: PUZ-AK36NL

Air Outlet Guide Air Outlet Guide 1 Piece PAC-SH96SG-E (two pieces required)

Centralized Drain Pan Centralized Drain Pan PAC-SH97DP-E

Control/Service Tool

Maintenance Tool Interface PAC-USCMS-MN-1

M- & P-Series Maintenance Tool Cable Set M21EC0397

ControlService Tool PAC-SK52ST

Drain Socket Drain Socket PAC-SG61DS-E

Hail Guards Hail Guard HG-A2

M-NET Converter M-Net Interface for P-Series PAC-SJ95MA-E

Mini-Split Wire

14 Gauge 4 wire MiniSplit Cable50 ft roll S144-50

14 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW144-50

14 Gauge 4 wire MiniSplit Cable250 ft roll S144-250

14 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW144-250

Mounting Pad Condensing Unit Mounting Pad 24 x 42 x 3 ULTRILITE2

Optional Defrost Heater Optional Defrost Heater PAC-SL11BH-E

Snow/Rain Diverter SnowRain Diverter SRD-5

Stand

18 Dual Fan Stand QSMS1802M

24 Dual Fan Stand QSMS2402M

Outdoor Unit Stand 12 High QSMS1202M

Outdoor Unit 3-14 inch Mounting Base Pair - Plastic DSD-400P

Terminal Signal Adapter 5-Pin Wiring Harness PAC-725AD

3-Pin Wiring Harness PAC-715AD

Wind Baffle

Front Wind Baffle WB-PA3 (two pieces required)

Rear Wind Baffle WB-RE6

Side Advanced Wind Baffle WB-SD6

Notes

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

INDOOR UNIT DIMENSIONS: PKA-AK36NL

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

OUTDOOR UNIT DIMENSIONS: PUZ-AK36NL

1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 · mitsubishicomfort.com

METUS_2026-04_PROPIN

SystemReference:
JobName:
Date:

File details come from the government source that posted it. Updated .