ME_SUBMITTAL_PKA-AK24NL_PUZ-AH24NL_XbtyE.pdf
PDF 4 MB Posted
- Solicitation number
- 36C77626R0104
About this file
This is a product specification sheet for a Mitsubishi Electric Trane HVAC mini-split heat pump system comprising the PKA-AK24NL indoor wall-mounted unit and PUZ-AH24NL outdoor heat pump unit. The system is designed for light commercial applications such as small offices, restaurants, and retail spaces.
The indoor unit delivers 24,000 BTU/h cooling capacity with a rated capacity of 24,000 BTU/h and minimum capacity of 10,100 BTU/h. Key features include swing mode air distribution, auto vane control for directional airflow adjustment, horizontal vane control, three-speed fan operation, and dual set point capability. The outdoor unit is a 23,600 BTU/h heat pump with an inverter-driven compressor, blue fin anti-corrosion coating, and seacoast protection. Electrical specifications indicate 208V/230V single-phase, 60Hz operation with a 25A recommended breaker and 14 AWG wire sizing. Efficiency ratings include SEER2 of 21.1, EER2 of 12, and HSPF2 of 9.20, with ENERGY STAR certification. Heating performance is rated at 28,000 BTU/h at 47°F and 15,300 BTU/h at 17°F. The system uses R454B refrigerant with a pre-charge of 7 lbs 11 oz, supports piping runs up to 165 feet, and operates across temperature ranges from -4°F to 115°F (with wind baffle for extended heating capability). Comprehensive accessory listings are provided for condensate management, control interfaces (wireless and wired), mounting hardware, drain components, linesets, and wind baffles for both indoor and outdoor units. Detailed dimensional drawings are included for installation planning.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
PKA-AK24NL & PUZ-AH24NL
24,000 BTU/H WALL-MOUNTED INDOOR UNIT
23,600 BTU/H HEAT PUMP OUTDOOR UNIT
Job Name:
System Reference: Date:
INDOOR Unit ... PKA-AK24NL
OUTDOOR Unit ... PUZ-AH24NL
INDOOR UNIT FEATURES
Swing Mode: An indoor unit with this capability can move air throughout the room like an oscillating fan.
Auto Vane Control: Auto Vane Control allows the indoor unit vanes to be moved left, right, up, and down to provide even temperatures throughout a space.
Light Commercial: Light commercial applications include small offices, restaurants, and retail.
Horizontal Vane Control: Horizontal Vane Control allows the indoor unit vanes to be moved left right to provide even temperatures throughout a space.
Three Speed Fan: Adjust the fan between three speed settings to optimal comfort.
Dual Set Point: The controller can be used to program two different set points. The unit will automatically adjust between the set points for optimum comfort.
OUTDOOR UNIT FEATURES
Inverter Driven Compressor: Inverter technology uses only the precise amount of energy needed to keep a space comfortable.
Blue Fin Coating: Anti-corrosion coating that protects the outdoor heat exchanger against salt, sulfur, and other airborne contaminants that impact the efficiency and performance of the outdoor units.
Seacoast Protection: Designed to protect against the corrosive effects of environments that are in close proximity to the sea.
Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
SPECIFICATIONS: PKA-AK24NL & PUZ-AH24NL
Cooling at 95F1
Maximum Capacity Btu/h 24500
Rated Capacity Btu/h 24000
Minimum Capacity Btu/h 10100
Maximum Power Input W 2050
Rated Power Input W 1990
Moisture Removal Pints/h 6.20
Sensible Heat Factor 0.72
Power Factor [208V / 230V] % 97 / 97
Heating at 47F2
Maximum Capacity Btu/h 31000
Rated Capacity Btu/h 28000
Minimum Capacity Btu/h 8300
Maximum Power Input W 2770
Rated Power Input W 2414
Power Factor [208V / 230V] % 98 / 98
Heating at 17F3
Maximum Capacity Btu/h 15300
Rated Capacity Btu/h 15300
Maximum Power Input W 1600
Rated Power Input W 1600
Heating at 5F5 Maximum Capacity Btu/h 11600
Maximum Power Input W 1620
Heating at -4F6 Maximum Capacity Btu/h 10400
Efficiency
SEER2 21.1
EER21 12
HSPF2 [IV] 9.20
COP at 47°F2 3.40
COP at 17°F at Maximum Capacity3 2.80
COP at 5°F at Maximum Capacity5 2
COP at -4°F at Maximum Capacity6 1.96
ENERGY STAR® Certified Yes
Electrical
Voltage, Phase, Frequency V AC / V AC , ø , Hz 208 / 230 , 1 , 60
Guaranteed Voltage Range V AC 198 - 253
Voltage: Indoor - Outdoor, S1-S2 V AC 208/230
Voltage: Indoor - Outdoor, S2-S3 V DC 12-24
Short-circuit Current Rating [SCCR] kA 5
Recommended Fuse/Breaker Size (Outdoor) A 25
Recommended Wire Size [Indoor - Outdoor] AWG 14
Indoor Unit
Fan Motor Output W 69
Fan Motor Type DC Motor
Airflow Rate at Cooling, Dry CFM 635 , 705 , 775
Airflow Rate at Cooling, Wet CFM 635 , 705 , 775
Airflow Rate at Heating, Dry CFM 635 , 705 , 775
Sound Pressure Level [Cooling] dB (A) 39 , 42 , 45
Sound Pressure Level [Heating] dB (A) 39 , 42 , 45
External Static Pressure in.WG
Dual Barrier Coating on Fan No
External Finish Color 0.7PB 9.2/0.4
Unit Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]
46-1/16 x 11-5/8 x 14-3/8 [ 1170 x 295 x 365 ]
Package Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]
51-3/16 x 14-3/16 x 18-9/16 [ 1300 x 360 x 470 ]
Unit Weight lbs [ kg ] 46 [ 21 ]
Package Weight lbs [ kg ] 51 [ 23 ]
IDU Operating Temp. Range Cooling Intake Air Temp [Maximum / Minimum] deg F , deg F / deg F
, deg F 90 , 73 / 66 , 59
Heating Intake Air Temp [Maximum / Minimum] deg F 82 / 50
Outdoor Unit
MCA A 22
MOCP A 37
Fan Motor Full Load Amperage A
Notes
1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB - test 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB 5Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB *Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): • Wind baffles required to operate below 23°F DB in cooling mode. • Heat pump system with wind baffle: 0°F - 115°F. • Refer to wind baffle documentation for further information.
**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): • System cuts out in heating mode and automatically restarts at these temperatures.
6Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB
Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
SPECIFICATIONS: PKA-AK24NL & PUZ-AH24NL
Outdoor Unit
Fan Motor Output W 7
Airflow Rate Cooling CFM 1940
Airflow Rate Heating CFM 1940
Defrost Method Reverse Cycle
Coating on Heat Exchanger (Bluefin, Sea Coast) Yes , Yes
Sound Pressure Level, Cooling1 dB (A) 49
Sound Pressure Level, Heating2 dB (A) 52
Compressor Type Twin Rotary
Compressor Model SRB172FQHMC-L1
Compressor Oil [Type // Charge] // oz RM68EH // 23
External Finish Color Munsell 3Y 7.8/1.1
Base Pan Heater Optional
Unit Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]
37-13/32 x 14 x 37-1/8 [ 950 x 355 x 943 ]
Package Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]
41-15/16 x 17-3/4 x 42-1/2 [ 1065 x 450 x 1079 ]
Unit Weight lbs [ kg ] 155 [ 70 ]
Package Weight lbs [ kg ] 179 [ 81 ]
ODU Operating Temp. Range
Cooling Intake Air Temp [Maximum / Minimum*] F 115 / 23
Cooling Thermal Lock-out / Re-start Temperatures** F
Heating Intake Air Temp [Maximum / Minimum] F , F / F , F 70 , 59 / -4 , -4
Heating Thermal Lock-out / Re-start Temperatures** F -13 / -4
Refrigerant
Type R454B
Pre-Charged Refrigerant Amount lbs , oz 7 , 11
Maximum Pre-Charged Piping Length ft [ m ] 165 [ 50 ]
Additional Refrigerant Charge Per Additional Piping Length oz/ft 0
Piping
Gas Pipe Size O.D. [Flared] inch [ mm ] 5/8 [ 15.88 ]
Liquid Pipe Size O.D. [Flared] inch [ mm ] 3/8 [ 9.52 ]
Maximum Piping Length ft [ m ] 165 [ 50 ]
Maximum Height Difference ft [ m ] 100 [ 30 ]
Maximum Number of Bends 15
Notes
1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB - test 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB 5Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB *Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): • Wind baffles required to operate below 23°F DB in cooling mode. • Heat pump system with wind baffle: 0°F - 115°F. • Refer to wind baffle documentation for further information.
**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): • System cuts out in heating mode and automatically restarts at these temperatures.
6Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB
Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
INDOOR UNIT ACCESSORIES: PKA-AK24NL
Condensate
Blue Diamond (MaxiBlue Advanced) Mini Condensate Pump w/ Reservoir & Sensor (110V) up to 48,000 BTU/H [recommended] X87-711
Blue Diamond Sensor Extension Cable 15 Ft C13-103
Sauermann Condensate Pump 120-230V up to 60k BTU/h SI30-230
Refco Condensate Pump 100-240V up to 120k BTU/h COMBI
Refco Condensate Removal Pump with Wall Mount Enclosure 120-240V up to 120k BTU/h GOBI-II
Blue Diamond MaxiBlue Condensate Pump with Reservoir Sensor 115-230V up to 48k BTU/h X88-721
Blue Diamond MegaBlue Condensate Pump with Reservoir Sensor 115-230V up to 170k BTU/h X87-835
Drain Pan Level Sensor/Control SS610E
Control Interface
Procon BACnet® and Modbus® Interface PAC-UKPRC001-CN-1
Airzone Wireless Lite Controller White AZZBSLITERB
Airzone Wireless Think Controller White AZZBSTHINKRB
Airzone Wireless Lite Controller Black AZZBSLITERN
IT Extender PAC-WHS01IE-E
Wireless Interface 2 for Comfrot app PAC-USWHS002-WF-2
Airzone Wired Blueface Controller Black AZZBSBLUEZEROCN kumo station® for Comfort app PAC-WHS01HC-E
Airzone Wireless Think Controller Black AZZBSTHINKRN
Thermostat Interface for 3rd Party Thermostats PAC-US445CN-1
Airzone Wired Blueface Controller White AZZBSBLUEZEROCB
Disconnect Switch 30A600VUL fits 2 X 4 utility box - Black TAZ-MS303
(30A/600V/UL) [fits 2” X 4” utility box] - White TAZ-MS303W
Drain Hose Flexible Mini-Split Drain Hose DRX-16
Lineset
3/8 x 5/8 Lineset Twin-Tube Insulation - 65 feet MPLS385812T-65
3/8 x 5/8 Lineset Twin-Tube Insulation - 10 feet MPLS385812T-10
3/8 x 5/8 Lineset Twin-Tube Insulation - 100 feet MPLS385812T-100
3/8 x 5/8 Lineset Twin-Tube Insulation - 30 feet MPLS385812T-30
3/8 x 5/8 Lineset Twin-Tube Insulation - 15 feet MPLS385812T-15
3/8 x 5/8 Lineset Twin-Tube Insulation - 50 feet MPLS385812T-50
Mini-Split Wire 14 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW144-250
14 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW144-50
N/A Unknown
Remote Sensor
Wireless temperature and humidity sensor for Comfort app PAC-USWHS003-TH-1
Wall Mounted Remote Temperature Sensor PAC-SE41TS-E
Flush Mount Remote Temperature Sensor for SEZ SLZ SVZ and all P-Series models PAC-USSEN002-FM-1
Terminal Signal Adapter
Backup Heat Relay Kit CN24RELAY-KIT-CM3
5-Pin Wiring Harness PAC-725AD
3-Pin Wiring Harness PAC-715AD
Wired Remote Controller
Deluxe MA Wired Remote Controller PAR-42MAAUB
Touch MA Remote Controller PAR-CT01MAU-SB
Simple Direct Wired Remote Controller PAC-SDW01RC-1
Simple MA Remote Controller PAC-YT53CRAU-J
Wireless Remote Controller
Wireless RedLINK™ Remote Controller MHK2
Wireless MA Handheld Remote Controller (requires PAR-FA32MA-E) PAR-FL32MA-E
Wireless Remote Contoller PAR-SL101A-E
Lockdown Bracket for Wireless Handheld Remote Controllers RCMKP1CB
Notes
Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT ACCESSORIES: PUZ-AH24NL
Air Outlet Guide Air Outlet Guide 1 Piece PAC-SG59SG-E
Centralized Drain Pan Centralized Drain Pan PAC-SG64DP-E
Control/Service Tool ControlService Tool PAC-SK52ST
M- & P-Series Maintenance Tool Cable Set M21EC0397
Drain Socket Drain Socket PAC-SG61DS-E
Hail Guards Hail Guard HG-A6
M-NET Converter M-Net Interface for P-Series PAC-SJ95MA-E
Mini-Split Wire
14 Gauge 4 wire MiniSplit Cable250 ft roll S144-250
14 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW144-50
14 Gauge 4 wire MiniSplit Cable50 ft roll S144-50
14 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW144-250
Mounting Pad Condensing Unit Mounting Pad 24 x 42 x 3 ULTRILITE2
Optional Defrost Heater Optional Defrost Heater PAC-SK62BH-E
Snow/Rain Diverter SnowRain Diverter SRD-4
Stand
24 Single Fan Stand QSMS2401M
Outdoor Unit 3-14 inch Mounting Base Pair - Plastic DSD-400P
Outdoor Unit Stand 12 High QSMS1201M
Condenser Wall Bracket QSWB2000M-1
Condenser Wall Bracket - Stainless Steel Finish QSWBSS
18 Single Fan Stand QSMS1801M
Terminal Signal Adapter 5-Pin Wiring Harness PAC-725AD
3-Pin Wiring Harness PAC-715AD
Wind Baffle
Front Wind Baffle WB-PA5
Rear Wind Baffle WB-RE5
Side Advanced Wind Baffle WB-SD5
Notes
Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
INDOOR UNIT DIMENSIONS: PKA-AK24NL
Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT DIMENSIONS: PUZ-AH24NL
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 · mitsubishicomfort.com
METUS_2026-04_PROPIN
| SystemReference: |
| JobName: |
| Date: |
File details come from the government source that posted it. Updated .