This is a product specification sheet for a Mitsubishi Electric Trane HVAC mini-split heat pump system comprising the PKA-AK24NL indoor wall-mounted unit and PUZ-AH24NL outdoor heat pump unit. The system is designed for light commercial applications such as small offices, restaurants, and retail spaces.

The indoor unit delivers 24,000 BTU/h cooling capacity with a rated capacity of 24,000 BTU/h and minimum capacity of 10,100 BTU/h. Key features include swing mode air distribution, auto vane control for directional airflow adjustment, horizontal vane control, three-speed fan operation, and dual set point capability. The outdoor unit is a 23,600 BTU/h heat pump with an inverter-driven compressor, blue fin anti-corrosion coating, and seacoast protection. Electrical specifications indicate 208V/230V single-phase, 60Hz operation with a 25A recommended breaker and 14 AWG wire sizing. Efficiency ratings include SEER2 of 21.1, EER2 of 12, and HSPF2 of 9.20, with ENERGY STAR certification. Heating performance is rated at 28,000 BTU/h at 47°F and 15,300 BTU/h at 17°F. The system uses R454B refrigerant with a pre-charge of 7 lbs 11 oz, supports piping runs up to 165 feet, and operates across temperature ranges from -4°F to 115°F (with wind baffle for extended heating capability). Comprehensive accessory listings are provided for condensate management, control interfaces (wireless and wired), mounting hardware, drain components, linesets, and wind baffles for both indoor and outdoor units. Detailed dimensional drawings are included for installation planning.

View the file

Other files

File Type Posted
Amendment 0007.pdf PDF
ME_SUBMITTAL_PKA-AK36NL_PUZ-AK36NL_6PSmo.pdf PDF
RFI Update 10-7-26.pdf PDF
RFI Responses.pdf PDF
Amendment 0006.pdf PDF
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0003.pdf PDF
Site Visit Agenda.pdf PDF
Site Visit Sign In Sheet 8-20-26.pdf PDF
Attachment 11 - Site Visit Details.docx DOCX document
Attachment 11 - Site Visit Details.docx DOCX document
Amendment 0002.pdf PDF
Amendment 0001.pdf PDF
Attachment 4 - Vol 3 Drawings.pdf PDF
Attachment 7 - Key Subcontractor Information.docx DOCX document
Attachment 8 - Key Personnel.docx DOCX document
Attachment 11 - Site Visit Details.docx DOCX document
Attachment 5 - Vol 4 Drawings.pdf PDF
Attachment 3 - Volume 2 Drawings.pdf PDF
Attachment 9 - Division Pricing Template.xlsx XLSX spreadsheet
Attachment 6 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 10 - Wage Determination.pdf PDF
Attachment 10 - Key Subcontractor Information.docx DOCX document
Attachment 13 - Wage Determination.pdf PDF
Attachment 12 - Division Pricing Template.xlsx XLSX spreadsheet
Attachment 14 - Site Visit Details.docx DOCX document
Attachment 2 - Vol 1 Drawings.pdf PDF
36C77626R0104.pdf PDF
Attachment 5 - Vol 2 Drawings Part 3.pdf PDF
Attachment 9 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 11 - Key Personnel.docx DOCX document
Attachment 1 - Specifications.pdf PDF
Attachment 4 - Vol 2 Drawings Part 2.pdf PDF
Attachment 6 - Vol 2 Drawings Part 4.pdf PDF
Attachment 8 - Vol 4 Drawings.pdf PDF
Attachment 3 - Vol 2 Drawings.pdf PDF
Attachment 7 - Vol 3 Drawings.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

PKA-AK24NL & PUZ-AH24NL

24,000 BTU/H WALL-MOUNTED INDOOR UNIT

23,600 BTU/H HEAT PUMP OUTDOOR UNIT

Job Name:

System Reference: Date:

INDOOR Unit ... PKA-AK24NL

OUTDOOR Unit ... PUZ-AH24NL

INDOOR UNIT FEATURES

Swing Mode: An indoor unit with this capability can move air throughout the room like an oscillating fan.

Auto Vane Control: Auto Vane Control allows the indoor unit vanes to be moved left, right, up, and down to provide even temperatures throughout a space.

Light Commercial: Light commercial applications include small offices, restaurants, and retail.

Horizontal Vane Control: Horizontal Vane Control allows the indoor unit vanes to be moved left right to provide even temperatures throughout a space.

Three Speed Fan: Adjust the fan between three speed settings to optimal comfort.

Dual Set Point: The controller can be used to program two different set points. The unit will automatically adjust between the set points for optimum comfort.

OUTDOOR UNIT FEATURES

Inverter Driven Compressor: Inverter technology uses only the precise amount of energy needed to keep a space comfortable.

Blue Fin Coating: Anti-corrosion coating that protects the outdoor heat exchanger against salt, sulfur, and other airborne contaminants that impact the efficiency and performance of the outdoor units.

Seacoast Protection: Designed to protect against the corrosive effects of environments that are in close proximity to the sea.

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PKA-AK24NL & PUZ-AH24NL

Cooling at 95F1

Maximum Capacity Btu/h 24500

Rated Capacity Btu/h 24000

Minimum Capacity Btu/h 10100

Maximum Power Input W 2050

Rated Power Input W 1990

Moisture Removal Pints/h 6.20

Sensible Heat Factor 0.72

Power Factor [208V / 230V] % 97 / 97

Heating at 47F2

Maximum Capacity Btu/h 31000

Rated Capacity Btu/h 28000

Minimum Capacity Btu/h 8300

Maximum Power Input W 2770

Rated Power Input W 2414

Power Factor [208V / 230V] % 98 / 98

Heating at 17F3

Maximum Capacity Btu/h 15300

Rated Capacity Btu/h 15300

Maximum Power Input W 1600

Rated Power Input W 1600

Heating at 5F5 Maximum Capacity Btu/h 11600

Maximum Power Input W 1620

Heating at -4F6 Maximum Capacity Btu/h 10400

Efficiency

SEER2 21.1

EER21 12

HSPF2 [IV] 9.20

COP at 47°F2 3.40

COP at 17°F at Maximum Capacity3 2.80

COP at 5°F at Maximum Capacity5 2

COP at -4°F at Maximum Capacity6 1.96

ENERGY STAR® Certified Yes

Electrical

Voltage, Phase, Frequency V AC / V AC , ø , Hz 208 / 230 , 1 , 60

Guaranteed Voltage Range V AC 198 - 253

Voltage: Indoor - Outdoor, S1-S2 V AC 208/230

Voltage: Indoor - Outdoor, S2-S3 V DC 12-24

Short-circuit Current Rating [SCCR] kA 5

Recommended Fuse/Breaker Size (Outdoor) A 25

Recommended Wire Size [Indoor - Outdoor] AWG 14

Indoor Unit

Fan Motor Output W 69

Fan Motor Type DC Motor

Airflow Rate at Cooling, Dry CFM 635 , 705 , 775

Airflow Rate at Cooling, Wet CFM 635 , 705 , 775

Airflow Rate at Heating, Dry CFM 635 , 705 , 775

Sound Pressure Level [Cooling] dB (A) 39 , 42 , 45

Sound Pressure Level [Heating] dB (A) 39 , 42 , 45

External Static Pressure in.WG

Dual Barrier Coating on Fan No

External Finish Color 0.7PB 9.2/0.4

Unit Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]

46-1/16 x 11-5/8 x 14-3/8 [ 1170 x 295 x 365 ]

Package Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]

51-3/16 x 14-3/16 x 18-9/16 [ 1300 x 360 x 470 ]

Unit Weight lbs [ kg ] 46 [ 21 ]

Package Weight lbs [ kg ] 51 [ 23 ]

IDU Operating Temp. Range Cooling Intake Air Temp [Maximum / Minimum] deg F , deg F / deg F

, deg F 90 , 73 / 66 , 59

Heating Intake Air Temp [Maximum / Minimum] deg F 82 / 50

Outdoor Unit

MCA A 22

MOCP A 37

Fan Motor Full Load Amperage A

Notes

1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB - test 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB 5Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB *Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): • Wind baffles required to operate below 23°F DB in cooling mode. • Heat pump system with wind baffle: 0°F - 115°F. • Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): • System cuts out in heating mode and automatically restarts at these temperatures.

6Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PKA-AK24NL & PUZ-AH24NL

Outdoor Unit

Fan Motor Output W 7

Airflow Rate Cooling CFM 1940

Airflow Rate Heating CFM 1940

Defrost Method Reverse Cycle

Coating on Heat Exchanger (Bluefin, Sea Coast) Yes , Yes

Sound Pressure Level, Cooling1 dB (A) 49

Sound Pressure Level, Heating2 dB (A) 52

Compressor Type Twin Rotary

Compressor Model SRB172FQHMC-L1

Compressor Oil [Type // Charge] // oz RM68EH // 23

External Finish Color Munsell 3Y 7.8/1.1

Base Pan Heater Optional

Unit Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]

37-13/32 x 14 x 37-1/8 [ 950 x 355 x 943 ]

Package Dimensions (W x D x H) inch x inch x inch [ mm x mm x mm ]

41-15/16 x 17-3/4 x 42-1/2 [ 1065 x 450 x 1079 ]

Unit Weight lbs [ kg ] 155 [ 70 ]

Package Weight lbs [ kg ] 179 [ 81 ]

ODU Operating Temp. Range

Cooling Intake Air Temp [Maximum / Minimum*] F 115 / 23

Cooling Thermal Lock-out / Re-start Temperatures** F

Heating Intake Air Temp [Maximum / Minimum] F , F / F , F 70 , 59 / -4 , -4

Heating Thermal Lock-out / Re-start Temperatures** F -13 / -4

Refrigerant

Type R454B

Pre-Charged Refrigerant Amount lbs , oz 7 , 11

Maximum Pre-Charged Piping Length ft [ m ] 165 [ 50 ]

Additional Refrigerant Charge Per Additional Piping Length oz/ft 0

Piping

Gas Pipe Size O.D. [Flared] inch [ mm ] 5/8 [ 15.88 ]

Liquid Pipe Size O.D. [Flared] inch [ mm ] 3/8 [ 9.52 ]

Maximum Piping Length ft [ m ] 165 [ 50 ]

Maximum Height Difference ft [ m ] 100 [ 30 ]

Maximum Number of Bends 15

Notes

1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB - test 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB 5Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB *Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): • Wind baffles required to operate below 23°F DB in cooling mode. • Heat pump system with wind baffle: 0°F - 115°F. • Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): • System cuts out in heating mode and automatically restarts at these temperatures.

6Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

INDOOR UNIT ACCESSORIES: PKA-AK24NL

Condensate

Blue Diamond (MaxiBlue Advanced) Mini Condensate Pump w/ Reservoir & Sensor (110V) up to 48,000 BTU/H [recommended] X87-711

Blue Diamond Sensor Extension Cable 15 Ft C13-103

Sauermann Condensate Pump 120-230V up to 60k BTU/h SI30-230

Refco Condensate Pump 100-240V up to 120k BTU/h COMBI

Refco Condensate Removal Pump with Wall Mount Enclosure 120-240V up to 120k BTU/h GOBI-II

Blue Diamond MaxiBlue Condensate Pump with Reservoir Sensor 115-230V up to 48k BTU/h X88-721

Blue Diamond MegaBlue Condensate Pump with Reservoir Sensor 115-230V up to 170k BTU/h X87-835

Drain Pan Level Sensor/Control SS610E

Control Interface

Procon BACnet® and Modbus® Interface PAC-UKPRC001-CN-1

Airzone Wireless Lite Controller White AZZBSLITERB

Airzone Wireless Think Controller White AZZBSTHINKRB

Airzone Wireless Lite Controller Black AZZBSLITERN

IT Extender PAC-WHS01IE-E

Wireless Interface 2 for Comfrot app PAC-USWHS002-WF-2

Airzone Wired Blueface Controller Black AZZBSBLUEZEROCN kumo station® for Comfort app PAC-WHS01HC-E

Airzone Wireless Think Controller Black AZZBSTHINKRN

Thermostat Interface for 3rd Party Thermostats PAC-US445CN-1

Airzone Wired Blueface Controller White AZZBSBLUEZEROCB

Disconnect Switch 30A600VUL fits 2 X 4 utility box - Black TAZ-MS303

(30A/600V/UL) [fits 2” X 4” utility box] - White TAZ-MS303W

Drain Hose Flexible Mini-Split Drain Hose DRX-16

Lineset

3/8 x 5/8 Lineset Twin-Tube Insulation - 65 feet MPLS385812T-65

3/8 x 5/8 Lineset Twin-Tube Insulation - 10 feet MPLS385812T-10

3/8 x 5/8 Lineset Twin-Tube Insulation - 100 feet MPLS385812T-100

3/8 x 5/8 Lineset Twin-Tube Insulation - 30 feet MPLS385812T-30

3/8 x 5/8 Lineset Twin-Tube Insulation - 15 feet MPLS385812T-15

3/8 x 5/8 Lineset Twin-Tube Insulation - 50 feet MPLS385812T-50

Mini-Split Wire 14 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW144-250

14 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW144-50

N/A Unknown

Remote Sensor

Wireless temperature and humidity sensor for Comfort app PAC-USWHS003-TH-1

Wall Mounted Remote Temperature Sensor PAC-SE41TS-E

Flush Mount Remote Temperature Sensor for SEZ SLZ SVZ and all P-Series models PAC-USSEN002-FM-1

Terminal Signal Adapter

Backup Heat Relay Kit CN24RELAY-KIT-CM3

5-Pin Wiring Harness PAC-725AD

3-Pin Wiring Harness PAC-715AD

Wired Remote Controller

Deluxe MA Wired Remote Controller PAR-42MAAUB

Touch MA Remote Controller PAR-CT01MAU-SB

Simple Direct Wired Remote Controller PAC-SDW01RC-1

Simple MA Remote Controller PAC-YT53CRAU-J

Wireless Remote Controller

Wireless RedLINK™ Remote Controller MHK2

Wireless MA Handheld Remote Controller (requires PAR-FA32MA-E) PAR-FL32MA-E

Wireless Remote Contoller PAR-SL101A-E

Lockdown Bracket for Wireless Handheld Remote Controllers RCMKP1CB

Notes

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

OUTDOOR UNIT ACCESSORIES: PUZ-AH24NL

Air Outlet Guide Air Outlet Guide 1 Piece PAC-SG59SG-E

Centralized Drain Pan Centralized Drain Pan PAC-SG64DP-E

Control/Service Tool ControlService Tool PAC-SK52ST

M- & P-Series Maintenance Tool Cable Set M21EC0397

Drain Socket Drain Socket PAC-SG61DS-E

Hail Guards Hail Guard HG-A6

M-NET Converter M-Net Interface for P-Series PAC-SJ95MA-E

Mini-Split Wire

14 Gauge 4 wire MiniSplit Cable250 ft roll S144-250

14 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW144-50

14 Gauge 4 wire MiniSplit Cable50 ft roll S144-50

14 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW144-250

Mounting Pad Condensing Unit Mounting Pad 24 x 42 x 3 ULTRILITE2

Optional Defrost Heater Optional Defrost Heater PAC-SK62BH-E

Snow/Rain Diverter SnowRain Diverter SRD-4

Stand

24 Single Fan Stand QSMS2401M

Outdoor Unit 3-14 inch Mounting Base Pair - Plastic DSD-400P

Outdoor Unit Stand 12 High QSMS1201M

Condenser Wall Bracket QSWB2000M-1

Condenser Wall Bracket - Stainless Steel Finish QSWBSS

18 Single Fan Stand QSMS1801M

Terminal Signal Adapter 5-Pin Wiring Harness PAC-725AD

3-Pin Wiring Harness PAC-715AD

Wind Baffle

Front Wind Baffle WB-PA5

Rear Wind Baffle WB-RE5

Side Advanced Wind Baffle WB-SD5

Notes

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

INDOOR UNIT DIMENSIONS: PKA-AK24NL

Specifications are subject to change without notice. © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

OUTDOOR UNIT DIMENSIONS: PUZ-AH24NL

1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 · mitsubishicomfort.com

METUS_2026-04_PROPIN

SystemReference:
JobName:
Date:

File details come from the government source that posted it. Updated .